2 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan
3 We focused on the characteristics of the fire behavior of car fire. Car fire is not so powerful and unlikely to spread. We installed minimum fire safety items such as compartmentation with openings and smoke exhaust system utilizing ramp and smoke shaft. Evacuation safety was verified except the occupants in the dead-end of parking space. Dense smoke and soot affected firefighting activity. Executive Summary
4 1. Fire Spread 2. Smoke Control 3. Evacuation 4. Fire-Fighting Strategy of Fire Safety
5 1. Fire Spread 2. Smoke Control 3. Evacuation 4. Fire-fighting
6 Fire Does Not Spread Beyond Lanes
7 number of data average = Probability of Non-Exceedance =95% Fire Growth Rate [kw/s 2 ] fire growth rate α [kw/s 2 ] Design design value = value =0.112 lognormal (0.0362, ) number of data Ref: MZM. Tohir, M. Spearpoint, Distribution analysis of the fire severity characteristics of single passenger road vehicles using heat release rate data, Fire Science Reviews, Vol. 2, No. 5, Maximum HRR [kw] average=4260 design value =8900 Design value lognormal (4260, 2449) =8,900 Lognormal (4260, 2449) maximum heat release rate Q max [kw] Statistically Process: a, Q max
8 Three Kinds of HRR Curves HRR 6Qmax Fail to control by sprinkler in a stacked zone 2Qmax Fire spread to adjacent cars 3Qmax Fail to control by sprinkler in a non-stacked zone Qmax Q=αt 2 Qsp Fire spread to adjacent cars Succeed to control by sprinkler time Design Fire
9 1. Fire Spread 2. Smoke Control 3. Evacuation 4. Fire-Fighting
10 Prevent Horizontal Smoke Spread by Natural Smoke Ventilation smoke shaft Active smoke compartment Induction of fresh air GF ramp ramp B1F B2F Smoke Control
11 Fresh Air Zone B Zone A Fresh Air z Dividing the car park into 3 smoke zones Smoke is exhausted through smoke shaft or a ramp Zone C Smoke Exhaust Vestibule Pressurization Fresh air is supplied through other ramps Installing vestibule pressurization system Strategy of Fire Safety
12 Scenario-s1 Scenario-f1 Zone C Scenario-s3 Scenario-f3 Scenario-s2 Scenario-f2 Settings of Each Scenario Scenario Sprinkler Fire Growth rate α Qmax [MW] HRR [kw/m 2 ] Scenario-s1 Success Scenario-f1 Fail Scenario-s2 Success Scenario-f2 Fail Scenario-s3 Success Scenario-f3 Fail Fire Scenarios
13 Temperature Distribution at Z=1.8m Time 120s 300s 420s Scenario-f1 Sprinkler failed case Scenario-s1 Sprinkler succeeded case [ C] Simulation Results
14 1. Fire Spread 2. Smoke Control 3. Evacuation 4. Fire-Fighting
15 Huge space - Requires long time for evacuation - Exposes occupants to smoke before noticing emergency Limited illumination - Reduces evacuation speed - Impairs sight of direction Closed space - Rises smoke temperature - Causes F.O. Characteristics of This Car Park
16 Evacuation Strategy - Compartment - Emergency light and Exit sign - Smoke shaft - Temporary refuge area ZoneB ZoneA stair Temporary refuge area Smoke Shaft Exit Exit sign Compatment Emergency light ZoneC ELV Horizontal evacuation Evacuation Planning
17 Hs [m] 1.8 [m] Hs [m] < 1.8 [m] Toxic More than 1.8m Exit Less than 1.8m Loss of Visibility Exit SAFE Yes UNSAFE No [Toxic] Cs [1/m] 0.5 [1/m] CO 2 [%] 0.5 [%] Ts [deg C] 44.8 [deg C] [Visibility] V [m] L (20m) [m] Ts [deg C] 140 [deg C] 30 [min] t escape [min] Tenability Criteria
18 Occupants are supposed to start evacuation when smoke descends in an adjacent grid Grid size: 24mx24m Smoke Level [m] Time[sec] An adjacent grid! Smoke Level [m] Time[sec] An adjacent grid! Evacuation Start Time
19 Sprinkler: Failure ASET: 197 [sec] RSET: 310 [sec] Hs : 1.3 [m] CO 2 : 0.6 [%] Cs : 1.9 [1/m] V : 4.2 [m] Ts : 45.1 [deg C] OK! ASET: 90 [sec] RSET: 116 [sec] Hs : 1.6 [m] CO 2 : 0.17 [%] Cs : 0.28 [1/m] V : 25.0 [m] Ts : 27.8 [deg C] ASET: 166 [sec] RSET: 274 [sec] Hs : 1.1 [m] CO 2 : 0.45 [%] Cs : 1.55 [1/m] V : 6.2 [m] Ts : 39.0 [deg C] Exit(3) NG Scenario-f1 Scenario-f2 Scenario-f3 Exit(3) NG Sprinkler: Success ASET: 207 [sec] RSET: 375 [sec] Hs : 1.4 [m] CO 2 : 0.21 [%] Cs : 0.53 [1/m] V : 16.1 [m] Ts : 26.1 [deg C] OK! ASET: 91 [sec] RSET: 116 [sec] Hs : 1.6 [m] CO 2 : 0.16 [%] Cs : 0.29 [1/m] V : 25.0 [m] Ts : 27.6 [deg C] OK! Exit(3) NG Scenario-s1 Scenario-s2 Scenario-s3 ASET: 175 [sec] RSET: 326 [sec] Hs : 1.3 [m] CO 2 : 0.21 [%] Cs : 0.48[1/m] V : 20.0 [m] Ts : 26.7 [deg C] Verification Result of Evacuation Safety
20 Fire Control Sprinklers can improve evacuation conditions such as smoke layer and visibility. Evacuation Starting Time Prompt activation of emergency alarm/voice system and facility management are necessary. Remediation of Dead Ends Means of egress should be arranged to the dead end to prepare an evacuation route getting away from fire origin. Verification Result of Evacuation Safety
21 1. Fire Spread 2. Smoke Control 3. Evacuation 4. Fire-Fighting
22 Entrance-B1 Stairwell-B1 Stairwe11-A1 Entrance-A1 The firefighters would arrive at the fire site 11 minutes after the fire has occurred. Entrance-B2 Entrance-C1 Stairwell-B2 Stairwell-C1 Ground floor of the Car Park Stairwell-A2 Entrance-C2 Entrance-A2 Three out of six fire crews approach the entrances located on the ground floor of the building. Stairwell-C2 Access of Fire-Fighters
23 Stairwe-B1 Zone B Stairwe-A1 Zone A The firefighters would reach the vestibules on the floor of fire origin 20 minutes after the fire has occurred. Stairwe-B2 Stairwe-C1 Zone C Stairwe-C2 Stairwe-A2 The maximum value of extinction coefficient of smoke in the compartment of fire origin would become 2.0 L/m at that time. Rescue
24 Fire Engine Fire stand pipe Hose Wat er Tank Firefighters should spray water in a rough direction toward the fire origin through the opened door from the vestibules. Car Park Spr i nkl er Head Room of Fire Origin Wat er Tank z Al ar m Firefighters Val ve Spr i nkl er Pump Stairwell Water will be continuously sent to the sprinkler system from a fire engine. Firefighters will spray water to the fire origin until extinguishment. Suppression
25 Installed the least fire safety items Compartment : Fire resistant walls and active smoke barriers Smoke exhaust : Ramps and smoke shaft Smoke density and visibility are critical For evacuation Only evacuation from dead end is not secured, even with sprinkler. For fire-fighting Sprinklers and interconnection of fire engine to sprinklers are necessary. Conclusion
26 Questions? Thank You for Your Attention
27 Appendix
28 Sprinkler Activation Qsp : HRR of SP system activated HRR Qsp=861kW 1.0MW time Near the thermal point temperature Tg [deg] Activation time of SP α=0.122 RTI=32 Nominal Activation Temperature of SP Head = 72 [deg.] 84sec(HRR=861kW) Time[sec] HRR of SP Activated Case
29 Whole Model For the Simulation of Fire Fighting (0-20minutes) Partial Model For the Simulation of Evacuation (0-10minutes) *Only Zone C *The cell size of Z direction is more detailed Simulation Models
30 Car Park Rescue Crew Entrance Firefighters will use entrances on the ground floor as staging areas to allocate firefighting equipment and extend water hose. B1 B2 Room of Fire Origin Vestibule Firefighters Stairwell These groups of firefighters will search evacuees who failed to escape, in order to rescue or lead them to the outdoor. Rescue
Case Study by Team Japan. Underground Car Park
11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study by Team Japan Underground Car Park Ai Sekizawa,Tokyo University of Science Ayako Tanno, Akeno Facility Resilience Inc.
More informationCase Study 1 Underground Car Park
Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building
More informationHow to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs
How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada
More informationCase Study 1 Underground car park
Case Study 1 Underground car park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, INBEPO Wroclaw, Poland 1. Introduction
More informationFIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016
FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural
More informationTunnel Fire Dynamics and Evacuation Simulations
Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation
More informationFirefighting operations on multi-tiered vehicle stacking buildings F5-13 GD
DESIGNER S GUIDE Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position
More informationThird Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG
1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for
More informationCHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION
- 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT
More informationSMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN
, Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen
More informationCOSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN
COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING
More informationFire Engineering in High Rise 15 November 2013
Fire Engineering in High Rise 15 November 2013 Neal Butterworth Arup UK www.arup.com Neal.Butterworth@arup.com Contents How do we protect against fire? How do we know this works? Why evacuate? What assumptions
More informationA New Zealand Case Study Building Design 11 th International Conference on Performance
A New Zealand Case Study Building Design 11 th International Conference on Performance Prof Charles Fleischmann University of Canterbury Dept. Civil and Nat Res Eng. Christchurch, New Zealand Carol Caldwell
More informationOVERVIEW. Increasing Awareness of Occupant Evacuation in Tall Buildings. Traditional Focus has been on Evacuation From Fire
OVERVIEW Increasing Awareness of Occupant Evacuation in Tall Buildings Traditional Focus has been on Evacuation From Fire Current Practice - Facilitate Broad Variety of Evacuation Scenarios Design to Facilitate
More informationVirtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel
Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,
More informationFire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett
Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University
More informationThe Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD
The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD BFS 2011:27 with amendments up to BFS 2013:12 The
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction
More informationSCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY
SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies
More informationBy: Russell Bainbridge March 18th, 2016 FPE 596
By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse
More informationSprinklers Modeling for Tunnel Road Fire Fighting
Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and
More informationWill Clay Spring 2014
Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 75 Fox Street Building OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report:
More informationStatue of Liberty: A Risk Analysis
Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress
More informationBOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015
Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22
More informationSAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.
SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.
More informationThe Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE
The Mont Blanc tunnel project Eric CESMAT, Sylvain DESANGHERE 24/09/2009 International water mist conference 2009 Fires in tunnel Car fire > 4 to 8 MW Van fire > 15 MW HGV fire > 30 MW Big HGV fire > 100
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More informationObjective based approach
Objective based approach Failure probabilities Introduction: fire safety objectives Example 1: personal safety Example 2: fire compartment 15-11-2017 1 Introduction RUUD VAN HERPEN Eindhoven University
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More informationUCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES
Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments
More informationSmoke Management in High-Rise Structures
Smoke Management in High-Rise Structures Most modern building codes define a high-rise structure as a building greater than 75 feet in height from the lowest level of fire department vehicle access to
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationCulminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering
Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo,
More informationREVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS
REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav
More informationF.R.A.M.E. EVENT NETWORKS used in "FRAME".
EVENT NETWORKS used in "FRAME". In 2004, Dipl. Ing. Trond Maag wrote his doctorates' thesis "Risikobasierte Beurteilung der Personensicherheit von Wohnbauten im Brandfall unter Verwendung von Bayes'schen
More informationElement C3.5 Means of Escape
.5 Means of Escape RRFSO Article 14 Legal Factors Responsible person must ensure routes to emergency exits and exits themselves are kept clear at all times Exits must directly lead to place of safety Safe
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationFinal Report - Volume III - Technical Manual for Planning of Fire Prevention System
4 EVACUATION The Study on Development of A Building Safety System Focusing on Fire Prevention in the Kingdom of Thailand Outbreak Initial Fire Fire Spread Evacuation Fire Fighting Collapse Exposure Fire
More informationFire Safety Design when Normal Limits Don t Apply
Fire Safety Design when Normal Limits Don t Apply INTRODUCTION Fredrik Nystedt, BSc. FSE Øresund Safety Advisers AB P.O. Box 82, SE-201 20 Malmö, SWEDEN fredrik@oresundsafety.se Swedish building regulations
More informationEMERGENCY EVACUATION PLAN
UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY EVACUATION PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying
More informationand Sprinkler System in Resalat Tunnel of Tehran
CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home
More informationHot Issues in Fire Engineering July 2014
Hot Issues in Fire Engineering July 2014 Crowded Railway Stations and Train Compartments to Watch Y.W. Ng and W.K. Chow, JP FHKEng Research Centre for Fire Engineering, Department of Building Services
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter ((shall)) apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationTable EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c
Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in
More informationNFPA-APSEI Fire & Security 2010
NFPA-APSEI Fire & Security 2010 Smoke control in industrial buildings Paul Compton, Colt International Ltd A brief introduction Private British Company founded in 1931 Owned by O Hea family and the Colt
More information12/14/2013. Fire alarm and emergency power SPRINKLER HEAD
Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector
More informationSimple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings
Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research
More informationCFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS
CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology PO Box 310 North
More informationSPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,
More informationDate: Place: Technical University of Denmark. Knowledge FOr Resilient society
Date: 27-06-2017 Place: Technical University of Denmark Knowledge FOr Resilient society 11B25 Smoke and temperature ACTION 11B04 11B12 fire development 11B01 Evacuation human behaviour building response
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationNew developments in Nordic countries in fire safety engineering guidance
New developments in Nordic countries in fire safety engineering guidance Vidar Stenstad Senior Engineer National Office of Building Technology and Administration, Norway Madrid, del 23 al 25 de febrero
More informationCase Study 2 (Production and Storage Buildings) - Spain
Case Study 2 (Production and Storage Buildings) - Spain OBJECTIVE Developed by the SFPE Spanish Chapter Editor: Jimmy Jönsson, JVVA Fire & Risk The objective of this case study is to show how a project
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 69 PRESIDENT SEPTEMBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: 69
More informationMechanical Smoke Extract Shaft Systems
Mechanical Smoke Extract Shaft Systems Presented by Mechanical Smoke Extract Shaft Systems Why Choose Crossflow? Crossflow is a family run company with over 45 years technical expertise. We are a solutions
More informationEmergency Planning and Preparedness
Emergency Planning and Preparedness Writing an Emergency Evacuation Plan A thorough emergency plan will include the following components: The procedure for reporting emergencies The procedure for relocating
More informationDate and Time of Incident. March 10, 1975
Building Name Address Sennari Hostel 1-8-20 Oginochaya, Nishinari-ku, Osaka City, OSAKA Use (as per FSA Annexed Table 1) Hostel (5) a Date and Time of Incident March 10, 1975 Breakout at 06:16 (approx)
More informationANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS
ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.
More informationINITIAL FIRE ASSESSMENT REPORT (FAR)
INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction
More informationBuilding Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design
June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor
More informationCFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES
UDC 614.84 : 628.854 : 52-17 DOI: 10.7562/SE2011.1.01.03 Original article www.safety.ni.ac.rs DARKO ZIGAR 1 DESIMIR JOVANOVIĆ 2 MARTINA ZDRAVKOVIĆ 3 1-4 University of Niš, Faculty of Occupational Safety
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationSteven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION
Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Mid-Rise Workshop, Coast Plaza Inn, Calgary, Feb. 4 th, 2016 Outline Overview of risks Regulations Changes to 2015 NFC for mid-rise
More informationApplying the New Zealand Performance Based Design Fire Framework to Buildings Designed in Accordance with NFPA5000
Applying the New Zealand Performance Based Design Fire Framework to Buildings Designed in Accordance with NFPA5000 Submitted by Chin Hung (Marco) Yip Supervised by Assoc. Professor Charles Fleischmann,
More informationLife Safety - Means of Egress/Exits NFPA 101
Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all
More information22 BISHOPSGATE Lift Evacuation Strategy
June 28, 2018 22 BISHOPSGATE Lift Evacuation Strategy Romain Hourqueig, Head of UK Fire Engineering Neil Allardice, Senior Fire Engineer AGENDA The project Fire Safety Strategy Why lift evacuation? The
More informationINITIAL FIRE SAFETY ASSESSMENT - EXPANSION
INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Plot 47-52 & 68-73, KEPZ North Patenga Chittagong Chittagong 06 Mar 2017 The Alliance for Bangladesh Worker Safety Page 1/23 06 Mar 2017 Introduction
More information2012 B.C. Building Code Compliance Review (Division B Part 3)
Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting
More informationFIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA
93 FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA INTRODUCTION 94 Legal requirements for the protection of firefighters Requirements of Building Act Fire Prevention Act Technical Guidelines OIB
More informationConstruction Innovation Center Building 186
Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview
More informationPracticalities and Limitations of Coupling FDS with Evacuation Software
ABSTRACT Practicalities and Limitations of Coupling FDS with Evacuation Software Daniel Rådemar, WSP, Sweden Daniel Blixt, WSP, Sweden Brecht Debrouwere, WSP, Sweden Björn Grybäck Melin, WSP, Sweden Andrew
More informationThe Situation. Modeling Storage Occupancies Under Sloped Ceilings. Concerns (Elevation View) The Concerns 4/29/ NFPA Conference & Expo
2014 NFPA Conference & Expo Modeling Storage Occupancies Under Sloped Ceilings Presented by: Kenneth E. Isman NFSA Victoria B. Valentine NFSA Andre Marshal CSS NFPA 13 defines a sloped ceiling as one where
More informationPREMISES FIRE SAFETY HANDBOOK
UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 188 TOTTENHAM COURT ROAD University College London 188 TOTTENHAM COURT ROAD, LONDON,
More informationFINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS
- 203 - FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS Hofer R., IBS Institute for Technical Fire Protection and Safety Research, Linz / Austria
More informationECONOMIC JUSTIFICATION FOR SPRINKLER SYSTEMS
ECONOMIC JUSTIFICATION FOR SPRINKLER SYSTEMS 08.03.2016 Vladimir Mozer University of Zilina INTRODUCTION The usual question: Why would I consider sprinkler protection when it is not required by codes?
More informationSPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,
More informationEmergency Evacuation Plan. Tiffany Tower Plot W2 Jumeirah Lakes Towers
Emergency Evacuation Plan Tiffany Tower Plot W2 Jumeirah Lakes Towers September 2017 TABLE OF CONTENTS 1.0 I N T R O D U C T I O N... 1 2.0 B U I L D I N G I N F O R M A T I O N... 1 3.0 F I R E S Y S
More informationCase Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)
Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) So What Are You We Going to Show You? A lot of tables, simplified methods
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationFranz Evegren. Robust brandriskbedömning ur ett IMO-perspektiv
Franz Evegren Robust brandriskbedömning ur ett IMO-perspektiv SP a wide technical range SP Calibration and Verification SP Certification SP Electronics SP Chemistry, Materials and Surfaces SP Energy Technology
More informationIs There A Need to ENCLOSE ELEVATOR LOBBIES IN TALL BUILDINGS?
Is There A Need to ENCLOSE ELEVATOR LOBBIES IN TALL BUILDINGS? by Richard W. Bukowski, P.E., FSFPE Several proposals have been submitted in recent years to model building code organizations to require
More informationISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people
TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations
More informationStudy of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan
Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke
More informationTHE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY
THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY 8619 Westwood Center Drive Suite 300 Vienna, Virginia 22182, USA Tel: +1 703 790 3434 Fax: +1 703 790 5655 Email: safety@liscr.com Web: www.liscr.com
More informationCalifornia Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19
PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection
More informationC/VM2 Verification Method: Framework for Fire Safety Design For New Zealand Building Code Clauses C1-C6 Protection from Fire
C/VM2 Verification Method: Framework for Fire Safety Design For New Zealand Building Code Clauses C1-C6 Protection from Fire Using this Verification Method The Ministry of Business, Innovation and Employment
More informationGuidance for writing a Personal Emergency Evacuation Plan (PEEP)
Guidance for writing a Personal Emergency Evacuation Plan (PEEP) If assistance with escape is required, the extent of such assistance should be identified in the PEEP i.e. the number of assistants and
More informationEVACUATION PROCEDURES IN EDUCATION PREMISES
EVACUATION PROCEDURES IN EDUCATION PREMISES MARCH 2009 ISSUE 01 1.0 INTRODUCTION 1.1 Every establishment will have its own individual evacuation procedure which should cover the following basic facts:
More informationPACDA Application Forms. 5/15/2018 Aman Fire Protection Consultants 1
PACDA Application Forms 5/15/2018 Aman Fire Protection Consultants 1 PACDA Submission Forms Preliminary Approval Form Final Approval Form Hazards Material Approval Form 5/15/2018 Aman Fire Protection Consultants
More informationFire and smoke management in a uni-directional road tunnel for a congested traffic condition
Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation
More informationDesign of Fire safety in Multi Occupancy Residential Accommodation
Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability
More informationUnit 2 Fire Safety (Zone 2)
IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 2) Examiner Report March 2017 Introduction 21% of the candidates that sat the examination attained a pass. Candidates did not
More informationFire Hazard Analysis of Technical Area 53 Building 1
Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the
More informationHuman Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE
Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses
More informationQuantitative risk assessment for a fire suppression system in the New Tyne Crossing. Dr Fathi Tarada
Quantitative risk assessment for a fire suppression system in the New Tyne Crossing Dr Fathi Tarada Contents The brief Feasibility study Risk assessment Cost-benefit analysis Primary assumptions Risk parameters
More informationNUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,
More information