SECTION FIRE PUMP AND CONTROLS
|
|
- Della Houston
- 5 years ago
- Views:
Transcription
1 SECTION FIRE PUMP AND CONTROLS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Fire pump, jockey pump, and controls including necessary accessories as shown in Construction Documents, specified in this section, and as required by NFPA 20. B. Related Sections: Fire Protection Automatic Sprinkler System Standpipe and Hose System REFERENCES A. American Society for Testing and Materials (ASTM). B. American National Standards Institute (ANSI). C. Factory Mutual (FM). D. National Electrical Code (NEC). E. National Electrical Manufacturers Association (NEMA). F. National Fire Protection Association (NFPA). G. Underwriters Laboratories (UL) SUBMITTALS A. Submit properly identified manufacturer's literature before starting work. B. Shop Drawings: 1. Fire pump and accessories. 2. Control panels and devices. 3. Jockey Pump and accessories. Project No. SPECIFICATION GUIDELINES
2 1.04 QUALITY ASSURANCE A. Fire protection equipment and devices shall be UL listed or FM approved for service intended. B. Install according to NFPA 20, NEC requirements, and local code regulations. PART 2 PRODUCTS 2.01 EQUIPMENT A. Fire Pump: 1. UL listed and FM approved automatic centrifugal pump complete with motor, controller and accessories, capable of delivering not less than 150 percent of rated capacity at not less than 65 percent of rated pressure, with characteristics as shown in Construction Documents. 2. Manufacturers: a. Aurora. b. Patterson. c. Peerless. 3. Pump: Centrifugal, horizontal split case, single stage casing with renewable bronze, case wearing rings and impeller wearing rings, steel shaft with renewable bronze or stainless steel sleeves, grease lubricated ball bearings, deep type stuffing boxes with bronze glands and external water seal, and lubrication fittings. Minimum suction pressure 20 psig. 4. Provide required UL accessories including: a. Discharge manifold. b. Automatic air release valve. c. Suction and discharge pressure gages. d. Suction and discharge tapered reducers. e. Circulation relief valve. 5. Motor: Project No. SPECIFICATION GUIDELINES
3 a. Motors shall be listed for fire pump service. b. Horizontal open drip-proof grease lubricated, ball bearing squirrel cage, and induction type with nonoverloading characteristics at any point of the curve. c. Pump and motor shall be mounted on a cast iron drip rim base plate. Motor mounting bracket on machined pump shall be completely aligned. 6. Transfer Switch Fire Pump Controller: a. Design and build according to the latest edition of NFPA 20. b. The fire pump controller and built-in automatic transfer switch shall have a withstand current rating of at least 100,000 RMS symmetrical amps on the normal power supply. c. The power transfer switch and fire pump controller shall be factory assembled, wired, and tested. d. Controller and transfer switch shall be in a NEMA Type 12 enclosure with floor mounting legs. The power transfer switch shall include a disconnect/isolating switch capable of interrupting the motor locked rotor current. e. Controller shall be of the primary resistor or reactor reduced voltage type with a combined automatic/manual start and manual/timed automatic stop. 1) Use reactor type when facility has a generator set. f. Controller shall have the following required accessories: 1) Pressure switch for automatic starting. 2) "Power-on" pilot light indicating breaker closed and power available. 3) Pressure recorder, not AC power dependent, with 7-day charts. 4) Power monitor for phase failure and phase reversal. 5) START and STOP push buttons for manual operation. 6) Timing relay for reduced voltage starting. Project No. SPECIFICATION GUIDELINES
4 7) Relays with normally open (N.O.) and normally closed (N.C.) dry contacts for pump running, power failure, and phase reversal. 8) Failed to start relay with N.O. and N.C. dry contacts. 9) Automatic stop timer set at 10 minutes, with provision to change to manual shutdown only. g. Transfer switch operation and accessories shall be according to NFPA 20. h. Provide extra N.O. dry contact for pilot light indicating pump running at central control station. i. Wiring of controller, transfer switch, and alarms shall be under Division 16. j. Transfer switch pump controllers shall be as manufactured by Firetrol, Joslyn-Clark, and Master Control. B. Jockey Pump: Peerless Pump Co. or accepted equivalent, Burks Series CS, close coupled, turbine pump with bronze impeller, and mechanical seal. Characteristics as shown in Construction Documents. C. Jockey Pump Controller: Main disconnect, fuse block with power fuses across the line starter, H-O-A selector switch, minimum run period timer, pressure switch in NEMA 12 cabinet, and UL listed. D. Test header according to NFPA 20. PART 3 EXECUTION 3.01 INSTALLATION A. Provide pump concrete foundations of size not less than the weight of the pumps or as shown in Construction Documents. B. Check pump and motor on foundation for misalignment FIELD QUALITY CONTROL A. Factory test each pump for performance data and compliance with specifications. Project No. SPECIFICATION GUIDELINES
5 1. Hydrostatically test pump for not less than 5 minutes. 2. Test Pressure: 150 percent of pump working pressure but not less than 250 psi. 3. Pump casings shall be tight with joints leakproof. B. Furnish NFPA 20 pump acceptance test data. Test data form shall be as shown in NFPA 20, figure A (f). Tests shall be conducted according to the requirements of NFPA 20. END OF SECTION Project No. SPECIFICATION GUIDELINES
University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL
SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,
More informationPHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps
Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and
More informationWayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No
SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationPhiloWilke Partnership Addendum No. 2 A/E Project No April 2016
SECTION 23 21 23 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section.
More informationSECTION ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2
More informationA. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.
SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes
SECTION 210200 Formatted 1.00 PART 1 & GENERAL 1.01 Description of Work A. Provide pumps for fire suppression. 1.02 Section Includes A. Single Stage, Double Suction, 8100 Series Horizontal Splitcase Fire
More informationDESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES
SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.
More informationP.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton
P.C. Simonton & Associates, Inc. Consulting Engineers 309 North Main Street 1050 Parkside Commons Post Office Box 649 Suite 101 Hinesville, Georgia 31310 Greensboro, Georgia 30642 Addendum No. One Date:
More informationSECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY
SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where
More informationSECTION PLUMBING EQUIPMENT Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections.
SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15410 - Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections. 1.02 SUBMITTALS A. Submit properly identified
More information.2 Section Waste Management and Disposal..5 Section Motors, Drives and Guards for Mechanical Systems.
Issued 2006/08/01 Section 15131 Pumps Hydronic Systems Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal.3 Section 01780
More informationSECTION Fire Pumps
SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.
More informationSECTION STEAM CONDENSATE PUMPS
SECTION 23 22 23 - STEAM CONDENSATE PUMPS PART I - GENERAL 1.1 SECTION INCLUDES A. Steam Condensate Return Units, Gravity Return Type 1. Receiver 2. Pumps 3. Control Panel 4. Accessories Note to PSC: Although
More informationSECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED
More informationC. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers
More informationSECTION HEATING BOILER FEEDWATER EQUIPMENT
SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING
SECTION 221123 - DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1.
More informationBuildingName The Description of the Project P DOCUMENTS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
More informationMARLOW PUMPS RECIRCULATION
End suction centrifugal pump line available in both close coupled and frame mounted configurations allow users to meet exactly most flow conditions on commercial pool and waterpark applications. Features
More informationSECTION DOMESTIC WATER PUMPS
SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,
More information1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.
Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1
More informationSECTION ELECTRIC-DRIVEN, FIRE PUMPS
SECTION 21 30 13 ELECTRIC-DRIVEN, FIRE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between // --- // if not applicable to the project. Also delete any other item or paragraph including
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards
Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product
More informationC. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.
SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS
PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate
More informationSECTION STEAM CONDENSATE PUMPS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationSECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS
SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,
More informationSECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section
PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide
More informationLABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS
SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",
More informationSECTION PLUMBING EQUIPMENT
PART 1 GENERAL 1.01 SECTION INCLUDES A. Water heaters. B. Packaged water heating systems. C. Domestic water heat exchangers. D. Water storage tanks. E. Water softeners. F. Reverse osmosis equipment. G.
More informationHorizontal Split Case Pumps Type U
Horizontal Split Case Pumps Type U 7.1 7.2 Stage U Type Pumps Features: Axially Split Case Design Range from 20M 3 /Hr to 600M 3 /Hr Two Stage Pump Single Suction Twin Volute Casing Design Closed type
More informationN N O V A T I O N E F F I C I E N C Y Q U A L I T Y VTP. Vertical Turbine Pump
N N O V A T I O N E F F I C I E N C Y Q U A L I T Y VTP Vertical Turbine Pump For more than 60 years the name Ruhrpumpen TM has been synonymous worldwide with innovation and reliability for pumping technology
More informationMODEL 652A MODEL 654A MODEL 652A MODEL 653A MODEL 651A AURORA. 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS
MODEL 652A MODEL 654A MODEL 652A MODEL 651A MODEL 653A AURORA 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS WWW.AURORAPUMP.COM 2 AURORA 650 Series Single Stage Solids Handling Pumps Capacities to 2000
More informationSECTION CHILLERS
SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings
More informationA. This section includes design and performance information for fire protection and suppression systems.
SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials
More informationSECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.
SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.
More information3020/3120 Series DEMING PUMPS. Frame-mounted and close-coupled Enclosded and semi-enclosed impeller Capacities to 4,000 GPM Heads to 780 feet
3020/3120 Series Frame-mounted and close-coupled Enclosded and semi-enclosed impeller Capacities to 4,000 GPM Heads to 780 feet A Crane Co. Company DEMING PUMPS Introducting Deming 3020/3120 Series End-Suction
More informationPUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...
PUMPS FOR INDUSTRY CONTENTS: The Vertical Pump Specialists Introduction & User List Product Overview Vertical Process Pumps... Series 600 Vertical Sewage Pumps... Series 700 Vertical Sump Pumps... Series
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL
SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationC. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.
SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this
More informationDomestic Pump Series VCMD TM Combination Vacuum & Boiler Feed Unit
Custom engineered units to maintain optimum boiler levels and system vacuum requirements Four styles to choose from to minimize floor space requirements Multi-jet vacuum pumps for quiet, dependable and
More informationWET AUTOMATIC FIRE SPRINKLER SYSTEMS
SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,
More informationSECTION ROTARY-SCREW WATER CHILLERS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.
More informationDesign and Construction Standards SECTION PLUMBING EQUIPMENT
SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES
More informationHORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).
SECTION 15555 HORIZONTAL FIRE TUBE BOILERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15510 - Piping (HVAC). 2. 15540 - Pumping Equipment (HVAC). 1.02 SUBMITTALS A. Submit properly identified
More informationDean Pump High Temperature Chemical Process Inline Pumps
Bulletin C-1.2.21. Dean Pump High Temperature Chemical Process Inline Pumps Series DL Dean Pump Series DL High Temperature Chemical Process Inline Pumps Capacities to 600 GPM (182 m 3 /hr) Heads to 0 feet
More informationMODEL 664A MODEL 662A MODEL 663A MODEL 661A AURORA. 660 Series SINGLE STAGE SOLIDS HANDLING VORTEX PUMPS
MODEL 662A MODEL 664A MODEL 661A MODEL 663A AURORA 660 Series SINGLE STAGE SOLIDS HANDLING VORTEX PUMPS WWW.AURORAPUMP.COM 2 AURORA 660 Series Single Stage Solids Handling Vortex Pumps Capacities to 2600
More informationRuhrpumpen Fire Systems
FIRE SYSTEMS RP FIRE SYSTEMS Ruhrpumpen Fire Systems Fire pumps play a vital role as the first response to a fire situation, saving countless lives and property from destruction. They are usually found
More informationSECTION PLUMBING EQUIPMENT
PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT
More informationC. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.
Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED
More informationSoft Start Series MP700 Solid State, Reduced Voltage
Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s
More informationLN series STERLING PUMPS. Horizontal Split Case Pumps. Double Volute. Single Stage.
LN series Horizontal Split Case Pumps Double Volute. Single Stage www.sterlingpumps.com.au LN series Sizes: 6 to 42 Capacity to 12,500 m³/h Heads to 190 metres A rugged, single stage, double volute horizontal
More informationPUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...
PUMPS FOR INDUSTRY CONTENTS: The Vertical Pump Specialists Introduction & User List Product Overview Vertical Process Pumps... Series 600 Vertical Sewage Pumps... Series 700 Vertical Sump Pumps... Series
More informationD. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof
More informationSTR-Series Indirect-Fired Air Turnover Units
STR-Series Indirect-Fired Air Turnover Units Equipment Specifi cations 1.800.589.3691 www.weather-rite.com GAS/OIL HEATING ONLY INDIRECT-FIRED AIR TURNOVER UNIT GUIDE SPECIFICATIONS PART 1 GENERAL [Gas][Oil][Gas/Oil
More informationN N O V A T I O N E F F I C I E N C Y Q U A L I T Y CPO. Open Impeller ASME (ANSI) B73.1 Pump for continuous use in Chemical Process Services
N N O V A T I O N E F F I C I E N C Y Q U A L I T Y CPO Open Impeller ASME (ANSI) B73.1 Pump for continuous use in Chemical Process Services Horizontal Split Case For more than 6 years the name Ruhrpumpen
More informationSECTION : FIRE PROTECTION SYSTEMS
SECTION 21 00 10: FIRE PROTECTION SYSTEMS 1. GENERAL A. This section applies to the design and performance information for fire protection and suppression systems. B. All fire protection materials and
More informationAcross-the-Line SERIES MP300 Combined Manual and Automatic
Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps
More informationVariable Frequency Drive SERIES MP800 VFD
Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for
More informationReferences are in agreement with UMRL dated April 2018 **************************************************************************
USACE / NAVFAC / AFCEC / NASA UFGS-23 21 23 (August 2017) ---------------------------- Preparing Activity: USACE Superseding UFGS-43 21 13 (January 2008) UFGS-43 21 39 (April 2008)) UNIFIED FACILITIES
More informationSECTION PUMPS. 6. Section Steam and Condensate Piping and Specialties.
SECTION 15540 PUMPS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Base Mounted Pumps. 2. Horizontal Split Case Pumps. 3. In line Pumps. 4. Steam Condensate Return Pumps. B. Related Sections: 1. Section
More informationDS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP
DS series Industrial End Suction Pumps ISO/DP 5199 www.sterlingpumps.com.au DS series Capacities from: Heads from: 340 to 5,680 m3/h (1,500 to 25,000 USPGM) 21 to 106 metres (70 to 350 feet) Power range
More informationB. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationA. Codes and Standards that are Standard at the University:
PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The
More informationA. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:
SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationA. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.
15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional
More informationSECTION FM-200 FIRE SUPPRESSION SYSTEM
SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to
More informationFull-line Product Overview
Full-line Product Overview End Suction Centrifugal Pumps This general purpose pump can be configured in frame-mounted and close-coupled, semi-open and enclosed impeller configurations. They are available
More informationSERIES 1600 Quality Design Features Assure Long, Trouble-Free Service
Vortex End Suction SERIES 1600 Quality Design Features Assure Long, Trouble-Free Service WIDE RANGE OF APPLICATIONS: Food Processing Solids Waste Water Treatment Pollution Control Slurries Industrial Process
More informationVent-Rite. Cast Iron And Steel Receivers. Simplex, Duplex, Triplex And Quadruplex Units. Pump Capacities To 150 GPM. Discharge Pressure To 75 PSI
Vent-Rite BULLETIN VCRV AUGUST 0 GUARDIAN Plus Cast Iron And Steel Receivers Simplex, Duplex, Triplex And Quadruplex Units Pump Capacities To 0 GPM Discharge Pressure To 7 PSI 87 Dewey Avenue Benton Harbor,
More informationA. Section includes wet-pipe sprinkler system, system design, installation, and certification.
SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes wet-pipe sprinkler system, system design, installation, and certification. 1.2 REFERENCES A. General: Comply
More informationSECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM
PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary
More informationSECTION WASTEWATER PUMPING STATION DESCRIPTION
SECTION 33 3200 WASTEWATER PUMPING STATION DESCRIPTION The contractor shall furnish and install one submersible sewage lift station with concrete wet well and valve vault, pumps, 4 piping and valves, and
More informationFire Pump Specification
GPS Amsterdam Phase 2 Expansion Project No: 1703 Fire Pump Specification Rev. Description Date Issued by 00 First Issue 10-09-2017 1703-F02-403-001 GPS Amsterdam Phase 2 Expansion Table of Contents 1 F02-403-001
More informationKITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM
PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.
More informationEssex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL
Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 SECTION 232116 - HYDRONIC PIPING SPECIALTIES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationB. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.
DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS
More informationTECHNICAL. Series 18. Pump Packages
TECHNICAL S Y S T E M S Series 18 Pump Packages Series 18 Pump Packages Standard Features Close-coupled, end-suction, centrifugal pumps Mounted and wired pump starters Hand-Off-Auto switch for each pump
More informationDIVISION 21 FIRE SUPPRESSION FIRE SUPPRESSION GENERAL PROVISIONS .1 PREPARATION OF CONTRACT DOCUMENTS
2006 Edition, Published January 1, 2006; Division Revision Date: June 30, 2016 21 00 00. FIRE SUPPRESSION 21 00 03. GENERAL PROVISIONS.1 PREPARATION OF CONTRACT DOCUMENTS.1.1 PLUMBING CONTRACT: Include
More informationSECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE
SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED
More information1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:
SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.
More informationSECTION WATER BASED FIRE SUPPRESSION SYSTEMS
PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University-San Marcos for automatic fire sprinkler and standpipe systems.
More informationDualPak Series FILE NO: DATE: Feb. 15, 1999 SUPERSEDES: DATE: Sept. 28, DualPak 6900 Series Booster System
DualPak Series 6900 FILE NO: 62.11 DATE: Feb. 15, 1999 SUPERSEDES: 62.11 DATE: Sept. 28, 1995 DualPak 6900 Series Booster System D U A L P A K 6 9 0 0 Armstrong proudly presents the Series 6900 DualPak
More informationSECTION PACKAGED HEAT TRANSFER SYSTEM
PACKAGED HEAT TRANSFER SYSTEM Page 1 of 6 SECTION PACKAGED HEAT TRANSFER SYSTEM 1 GENERAL 1.1 SUMMARY A. Packaged steam-to-water heat transfer system 1.2 REFERENCES A. ASHRAE American Society of Heating,
More informationSECTION HEATING BOILERS
SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,
More informationSECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.
SECTION 15855 AIR HANDLING UNITS WITH COILS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Central Station Air Handling Units. B. Related Sections: 1.02 REFERENCES 1. Section 15010 - Basic Mechanical
More informationSioux E-Series. All-Electric Compact Industrial Steam Cleaners & Pressure Washers. Sioux E-Series All-Electric Steam Cleaners and Pressure Washers
Sioux E-Series All-Electric Steam Cleaners and Pressure Washers Sioux E-Series All-Electric Compact Industrial Steam Cleaners & Pressure Washers Model E3.5HS3000 3 Consider Benefits... these Sioux s E-Series
More informationChilled Water DOAS Fan Powered Terminal Units
Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner
More informationSPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS
SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification
More informationPumps SELECTION OF A PUMP
Pumps SELECTION OF A PUMP A water system needs to move the water produced from the source to its customers. In almost all cases in Minnesota, the source is at a lower elevation than the user so the water
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating
More informationDTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5
Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3
More informationCentrifugal Pumps acc. to DIN EN ISO 2858 with Shaft Sealing Type NCL
Centrifugal Pumps acc. to DIN EN ISO 2858 with Shaft Sealing Type NCL General The DICKOW centrifugal pump, type NCL, is designed for handling liquids in the chemical and petrochemical industry, in refineries,
More informationGH Series End Suction Centrifugal Pumps For Flows to 2,500 GPM
GH Series End Suction Centrifugal Pumps For Flows to 2,500 GPM The GH Series The GH is Carver s horizontal, end suction pump series for handling water, oils, and chemicals in marine, process, and general
More informationEnd-Suction Centrifugal Pump
GH End-Suction Centrifugal Pump GH Horizontal end-suction pump for handling water, oils and chemicals in marine, process and general industrial applications. Hydraulic performance extends to 2,500 GPM
More informationEnd-Suction Centrifugal Pump
GH End-Suction Centrifugal Pump GH Horizontal end-suction pump for handling water, oils and chemicals in marine, process and general industrial applications. Hydraulic performance extends to 2,500 GPM
More informationFTA200-A REMOTE ALARM PANEL
FTA200-A REMOTE ALARM PANEL (FOR USE WITH ELECTRIC FIRE PUMP CONTROLLERS) STANDARD SUBMITTAL PACKAGE SBP200A FTA200-A Remote Alarm Panels for Electric Fire Pump Controllers Product Description Type A -
More informationSECTION STEAM AND STEAM CONDENSATE SPECIALTIES
SECTION 23 22 18 STEAM AND STEAM CONDENSATE SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Steam Traps. B. Flash Tanks. C. Condensate Return Units. D. Pressure Reducing Valves. E. Safety Valves.
More information