GRUNDFOS INSTRUCTIONS. Dedicated Controls. Service instructions

Size: px
Start display at page:

Download "GRUNDFOS INSTRUCTIONS. Dedicated Controls. Service instructions"

Transcription

1 GRUNDFOS INSTRUCTIONS Dedicated Controls Service instructions

2 Contents 1. Symbols used in this document Identification Dedicated Controls CU IO 351B Separate components Control cabinet Environmental conditions and connection Examples of control variants CU 361 control panel Menu overview Overview of inputs and outputs of control unit/modules Functions of terminals CU 361 terminals IO 351B terminals IO 111 terminals Configuration Necessary equipment Configuration of Dedicated Controls Documentation supplied with Dedicated Controls PC Tool Connection of PC to Dedicated Controls Fieldbus communication module SCADA system Data communication Fitting the CIM module General settings, CU Display language Fault finding Power supply External control, data collection, SCADA systems Pumps Fault finding tools CU 361 display System Specific pump GSM/GPRS Float switch status Mixer Electrical overview Alarms and warnings Alarm indicators Alarm settings How to trace an alarm Menu Status Menu Alarm Password protection R Fault finding by means of fault codes Alarm list (system) Alarm list (pump) Alarm list (mixer) Alarm list (combi alarms) Alarm list (IO 111 belongs to a pump) / 60

3 Symbols used in this document Warning If these safety instructions are not observed, it may result in personal injury! Caution Note If these safety instructions are not observed, it may result in malfunction or damage to the equipment! Notes or instructions that make the job easier and ensure safe operation. 2. Identification This section shows the nameplates, the type keys and the codes that can appear in a variant code. Note As codes can be combined, a code position may contain more than one code (letter). 2.1 Dedicated Controls Nameplate Type: 1 Model: 2 Serial No: 3 Mains supply: 4 Power consumption: 5 W Fuse: 6 A TAMB: 7 º C VCONTACT MAX. : 8 9 A V ICONTACT MAX. : No. of Fixed speed pumps: 10 Imax Vmax Relay output: Order No.: Options: IP 18 Weight: 19 kg Made in 21 TM Fig. 1 Nameplate, Dedicated Controls Pos. Description Pos. Description 1 Type designation 10 Number of fixed-speed pumps 2 Model 11 I max., relay output 3 Serial number 12 V max., relay output 4 Mains supply 13 Order number 5 Power consumption Options 6 Fuse 18 Enclosure class 7 T amb. 19 Weight in kg 8 V contact max. 20 CE-mark 9 I contact max. 21 Country of origin 3 / 60

4 2.1.2 Type key Example DCD DOL -IGM Number of pumps DC: 1 pump DCD: 2 pumps Type number Supply voltage, frequency 230: 230 V, 50 Hz 400: 400 V, 50 Hz Number of phases 1 = single-phase 3 = three-phase Maximum current per pump [A] 5: 1-5 A (230 V and 3 x 415 V DOL) 12: 5-12 A (230 V DOL) 23: A (3 x 415 V DOL) 20: 20 A (3 x 415 V SD/SS) 30: 30 A (3 x 415 V SD/SS) 59: 59 A (3 x 415 V SD/SS) 85: 85 A (3 x 415 V SD/SS) Run/starting capacitor [µf] (only 12 A operating current) [ ] = without capacitor 30 = run capacitor 30/150 = 30 µf run capacitor and 150 µf starting capacitor Starting method DOL (Direct On Line): Direct-on-line starting SD: Star-delta starting SS: Soft starter Setup S: Standard I: IO 111 (both pumps) G: GSM module and battery backup M: Mixer/flush valve IG: IO 111, GSM module and battery backup IM: IO 111 and mixer/flush valve GM: GSM module, battery backup and mixer/flush valve IGM: IO 111, GSM module, battery backup and mixer/flush valve 4 / 60

5 2.2 CU Nameplate The CU 361 can be identified by means of the nameplate on the back. See fig Type CU 361 Serial No Product No VO1 P.c UN Vac 50/60Hz - Max. 22W Made in Thailand! 30 XP OPEN TYPE PROCESS CONTROL EQUIPMENT TM Fig. 2 CU 361 nameplate Pos. Description 1 Type designation 2 Product number and version number 3 Serial number 4 Production code (year, week) 5 Rated voltage, frequency and power Type key Code Description CU CU Control unit 36 Controller series 1 Model number The CU 361 has a label for backup battery. See fig. 3. Battery powered TM Fig. 3 Label for backup battery Warning Remove the battery before starting work on the CU 361. TM V dc 0V 12V Fig. 4 Protective earth terminal 5 / 60

6 2.3 IO 351B Nameplate 1 2 Type Product No. IO 351B VO1 Serial No. P.c UN Made in Denmark Vac 50/60Hz - max. 9W! 30 XP OPEN TYPE PROCESS CONTROL EQUIPMENT 5 TM Fig. 5 Nameplate, IO 351B Pos. Description 1 Type designation 2 Product number and version number Permissible supply voltage, frequency and 3 maximum power consumption 4 Production code (year, week) 5 Serial number Type key Code Description IO B IO Input/output module 35 Controller series 1 Model number B For pumps with fixed-speed and pumps controlled by external frequency converters or as input/output module 6 / 60

7 2.4 Separate components Component Description Functions CU 361 IO 351B GrA 6588 The CU 361 is the 'brains' of the Dedicated Controls system and is mounted in the front of the control cabinet. The CU 361 can control and monitor one or two Grundfos wastewater pumps. The pumps can drain a pit using built-in draining algorithms. The algorithms are based on a water level measured by float switches or an analog level sensor. CU 361 inputs and outputs: GENIbus communication (RS-485) 3 analog inputs for connection to sensors with current (0-20 ma/ 4-20 ma) or voltage (0-10 V) 3 digital inputs 2 digital relay outputs, 240 VAC, 2 A Connection to battery backup (UPS) (optional) Ethernet connection (VNC) Connection to fieldbus CIM modules (CIM = Communication Interface Module): CIM 200 (Modbus via RS-485) CIM 250 (Modbus and SMS via GSM/GPRS) CIM 270 (GRM) (GRM = Grundfos Remote Management). Product number IO 111 TM TM The IO 351B is a general I/O module. The IO 351B communicates with the CU 361 via GENIbus. Via the IO 351B inputs and outputs, the CU 361 controls the pumps according to the built-in algorithms. The IO 111 is a protection module for a Grundfos wastewater pump. The IO 111 has inputs for digital and analog pump sensors and can stop the pump if a sensor indicates a pump fault. The IO 111 is connected to the CU 361 and allows the monitoring of several sensors. IO 351B inputs and outputs: GENIbus communication (RS-485) 2 analog inputs for connection to sensors with current (0-20 ma/ 4-20 ma) or voltage (0-10 V) 9 digital inputs 7 digital outputs, 240 VAC, 2 A 4 PTC inputs. IO 111 inputs and outputs: 1 digital input for moisture in motor 1 digital input for water-in-oil detection 1 digital input for high motor temperature 1 analog input for insulation resistance 1 analog input for stator temperature 1 digital output for alarm relay 1 digital output for warning 1 digital output for moisture-inmotor alarm 1 digital output for stator temperature alarm 1 digital output for insulation resistance alarm / 60

8 Component Description Functions Product number CIM 200 GrA 6120 The CIM 200 is a Grundfos communication interface module used for the fieldbus protocol Modbus RTU. The CIM 200 is to be fitted in the CU 361 control unit. The CIM 200 is used to communicate with a Modbus RTU network. The CIM 200 module has terminals for the Modbus connection. DIP switches are used to set parity and line termination. Two hexadecimal rotary switches are used to set the Modbus address. Two LEDs are used to indicate the actual status of the CIM 200. One LED is used for internal communication, and the other is used to indicate Modbus communication status CIM 250 TM The CIM 250 is a Grundfos communication interface module used for GSM/GPRS communication. The CIM 250 is to be fitted in the CU 361 control unit. The CIM 250 is used to communicate via a GSM network. The CIM 250 module has a SIM-card slot and an SMA connection to the GSM antenna. The CIM 250 also has an internal backup battery. Two LEDs are used to indicate the actual status of the CIM 250. One LED is used for internal communication, and the other is used to indicate GSM/GPRS communication status CIM 270 TM The CIM 270 is a Grundfos communication interface module used in Grundfos Remote Management. The CIM 270 is to be fitted in the CU 361 control unit. The CIM 270 establishes communication between the CU 361 control unit and the Grundfos Remote Management system, thereby allowing the CU 361 to be monitored and controlled remotely. The CIM 270 uses GSM/ GPRS communication. The CIM 270 module has a SIM-card slot and an SMA connection to the GSM antenna. The CIM 270 also has an internal backup battery. Two LEDs are used to indicate the actual status of the CIM 270. One LED is used for internal communication, and the other is used to indicate GSM/GPRS communication status / 60

9 2.5 Control cabinet Cabinet Description Functions Control cabinet GrA 6270 The control cabinet is delivered with all necessary components, including battery backup. Different types of control cabinets are available, depending on functions and network. The control cabinet is designed for installation in a control cabinet for outdoor use. Note: The main switch and backup fuses have to be installed externally. Digital input Energy measurement* Volume measurement* Motor protection, pump 1 Motor protection, pump 2 Relay resetting External fault Common phase error Alarm relay resetting Contactor feedback, pump 1 Contactor feedback, pump 2 Contactor feedback, mixer Auto/On/Off, pump 1 On/Off, pump 1 Auto/On/Off, pump 2 On/Off, pump 2 Float switch 1 Float switch 2 Float switch 3 Float switch 4 Float switch 5 Too high motor temperature** Moisture in motor** PTC, pump 1 Klixon, pump 1 PTC, pump 2 Klixon, pump 2. Analog input Pressure sensor* Ultrasonic sensor* Flow rate* Motor current, pump 1* Motor current, pump 2* Water in oil, pump 1* or ** Water in oil, pump 2* or ** User-defined sensor 1* User-defined sensor 2* User-defined sensor 3* Insulation resistance** Stator temperature** Digital output Pump 1, start Pump 2, start Mixer, start User-defined relay High-level alarm Urgent alarms All alarms All alarms and warnings User-defined alarms Alarm relay** Warning** Moisture-in-motor alarm** Stator temperature alarm** Insulation resistance alarm** Communication SMS and Modbus GSM/GPRS*** Modbus-wired**** * External sensor required ** Only via the IO 111 *** Via the CIM 250 GSM module **** Via the CIM 200 Modbus module 9 / 60

10 2.6 Environmental conditions and connection Ambient temperature 20 C to +50 C Relative air humidity Maximum 95 % Mains supply, overload protection, fuses See Grundfos wiring diagrams (technical data) supplied with Dedicated Controls. 10 / 60

11 2.7 Examples of control variants One pump with two float switches One or two pumps with three float switches One or two pumps with four float switches TM TM TM One or two pumps with five float switches One or two pumps with analog sensor One or two pumps with analog sensor and mixer TM TM TM One or two pumps with analog sensor and safety float switches One or two pumps with analog sensor, safety float switches and mixer TM TM / 60

12 2.8 CU 361 control panel Pos. Description 1 LCD display 2 Changes to next column in menu structure 1 CU Changes to help text 4 Goes up in lists 5 Goes down in lists 6 Increases the value of a selected parameter 7 Decreases the value of a selected parameter 8 Goes one display back Goes back to the Status menu Fig. 6 CU 361 TM Saves a value 11 Green indicator light (operation) 12 Red indicator light (alarm) 13 Changes the contrast of the display 2.9 Menu overview 1. Status 1.1 System 1.2 Specific pump 1.3 GSM/GPRS 1.4 Float switch status 1.5 Mixer 1.6 Electrical overview Analog inputs Digital inputs Digital outputs 2. Operation 2.1 Overview 2.2 Auto/On/Off pump control 2.3 Start and stop levels 2.4 Resetting alarm relays 3. Alarm 3.1 Current alarms 3.2 Alarm log 12 / 60

13 4. Settings 4.1 Basic functions Primary settings Pit configuration and flow calculation Pump delays Float switch functions Drain function, one pump and two float switches Drain function, one pump and three float switches Drain function, one pump and four float switches Drain function, two pumps and three float switches Drain function, two pumps and four float switches Drain function, two pumps and five float switches Analog sensor with safety float switches Out of operation 4.2 Advanced functions Anti-seizing Daily emptying Foam draining Mixer configuration Adjustment of counters Resetting alarm log Duty/standby 4.3 Communication settings Selecting communication module Ethernet GENIbus number SMS numbers SMS schedule SMS heartbeat message SMS authentication SIM card settings SCADA settings Interlock settings GPRS settings 4.4 I/O settings Analog inputs Digital inputs Digital outputs Counter inputs Alarm relays 4.5 Alarm settings System alarms Pump alarms Mixer alarms Combi alarms 4.6 General settings, CU Run configuration wizard again Display language Units Date and time Password Ethernet GENIbus number Software status 13 / 60

14 3. Overview of inputs and outputs of control unit/modules Unit/ module Digital input Analog input Relay output Communication Extra CU NO/NC GENIbus master (RS-485) Ethernet (VNC) SMS and Modbus GSM/GPRS (via CIM 250) Modbus-wired (via CIM 200) IO 351B PTC 7 NO GENIbus slave (RS-485) IO (dedicated) 2 (dedicated) 5 (dedicated) GENIbus slave (RS-485) Battery backup 12 V input 3.1 Functions of terminals CU 361 0V 12V TM Fig. 7 Back of CU 361 Pos. Description 1 Nameplate 2 Terminals for digital output relays 3 Terminals for analog inputs 4 Service connection 5 Ethernet (RJ45) 6 Voltage indicator 7 Terminals for digital inputs 8 Terminals for backup battery 9 Terminals for CIM module (optional) 10 Cable clamps for GENIbus connections 11 Internal GENIbus connection 12 Terminal for power supply 13 Label for backup battery 14 / 60

15 3.1.2 IO 351B 5 3C 4B 4A 2 3B 3A 1 TM Fig. 8 Terminal groups The module can be divided into these groups: Group 1 Connection of power supply Group 2 Digital outputs 1-3 Digital inputs Group 3A, 3B, 3C Analog inputs and outputs GENIbus Group 4A, 4B Inputs for PTC sensor or thermal switch Group 5 Digital outputs Indicator lights on the IO 351B Red Green TM Fig. 9 Indicator lights on the IO 351B The IO 351B has a green and a red indicator light. Indicator lights Green Red Description Off. The power supply is interrupted. Flashes slowly (1 Hz). The module is ready for operation, but there is no communication yet. Permanently on. The power supply is on, and the module is starting up. Flashes quickly (5 Hz). The module is ready for operation, and the IO 351B and CU 361 communicate. Flashing The IO 351B and R100 communicate. 15 / 60

16 GENIbus addresses for IO modules IO module GENIbus address GENIbus number (DIP switch) (R100) IO 351B 41 IO 111, pump 1 40 IO 111, pump IO T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 PE 16 D1 D2 D3 D4 D5 D6 D7 D8 A Y B Reset ON DIP P1 P2 P3 P4 P5 10 Fig. 10 IO 111 module I1 I2 I3 9 TM Pos. Description 1 Terminal for alarm relay. 2 Terminal for analog and digital inputs and outputs. 3 Terminal for power supply (24 VAC/24 VDC). Potentiometer for setting the warning limit of stator 4 insulation resistance. 5 Terminal for RS-485 for GENIbus or Modbus. 6 Red indicator light. Alarm in case of too high motor temperature. Indicator lights for stator insulation resistance. Green light = OK. 7 Yellow light = warning. Red light = alarm. 8 Indicator lights for measurement of water in oil. 9 Terminal for measurement of stator insulation resistance. 10 Terminal for connection of pump sensors. 11 DIP switch for configuration. 12 Green indicator light. On when the pump is running. 13 Red indicator light. Alarm in case of moisture in the motor. 14 Button for alarm resetting. 15 Yellow indicator light. Warning in case of pump fault. 16 Terminal for digital outputs. 16 / 60

17 3.2 CU 361 terminals Pos. Terminal Designation Data Diagram 1 2 L N PE A1 Y1 B1 Connection to phase conductor Connection to neutral conductor Connection to protective earth RS-485 A RS-485 GND RS-485 B Functional earth 1 x VAC ± 10 %, 50/60 Hz GENIbus (Fix the screen with a cable clamp.) CU 361 L N CU 361 A1 Y1 B1 L N PE IO 351B A Y B 3 Connection to external fieldbus, see installation and operating instructions for the CIM module V +12 VDC 10 DI1 11 GND 12 DI2 13 GND 14 DI3 Connection to battery Backup battery Digital input All terminals (except mains terminals) must only be connected to voltages not exceeding 16 V rms and 22.6 V peak or 35 VDC. 14 Ethernet RJ45 6 External computing devices connected to the Ethernet connection must comply with the standards IEC and UL GENIbus Service connection V V 51 AI1 Supply to sensor. Short-circuit-protected 30 ma. Supply to sensor. Short-circuit-protected 30 ma. Input for analog signal, 0-20/4-20 ma or 0-10 V V Supply to sensor. Short-circuit-protected 30 ma. 54 AI2 Input for analog signal, 57 AI3 0-20/4-20 ma or 0-10 V 58 GND* All terminals (except mains terminals) must only be connected to voltages not exceeding 16 V rms and 22.6 V peak or 35 VDC. 70 Relay 1 C 71 Relay 1 NO 72 Relay 1 NC 73 Relay 2 C 74 Relay 2 NO Relay 2 NC 75 * GND is isolated from other earth connections. 17 / 60

18 3.3 IO 351B terminals Group Terminal Designation Data Diagram 1 L L N N Connection to phase conductor Connection to neutral conductor 1 x VAC ± 10 %, 50/60 Hz IO 351B L N L N Connection to protective earth PE 2 76 DO1, 2, 3 C 76 DO1, 2, 3 C 77 DO1 NO 79 DO2 NO 81 DO3 NO Relay contact, NO Maximum load: 240 VAC, 2 A Minimum load: 5 VDC, 10 ma IO 351B A 3A 3C 10 DI1 12 DI2 Digital input 14 DI3 15 GND All terminals (except mains supply terminals) must only be connected to voltages of maximum 16 V rms and 22.6 V peak or 35 VDC. Fit jumpers instead of the external stops for which the controller is designed V Supply to sensor. Max. 50 ma. 55 GND 57 AI1 Input for analog signal, 60 AI2 0/4-20 ma or 0-10 V All terminals (except mains supply terminals) must only be connected to voltages of maximum 16 V rms and 22.6 V peak or 35 VDC. A A Y Y B B RS-485 A RS-485 A RS-485 GND* RS-485 GND* RS-485 B RS-485 B GENIbus (internal) (Fix the screen with a cable clamp.) IO 351B IO 351B A Y B IO 351B CU 361 A1 Y1 B1 Functional earth 30 PTC 1 32 PTC 2 Input for PTC sensor or thermal switch 34 PTC 3 4A 35 GND, PTC Fit jumpers if no PTC sensor or thermal switch is connected. All terminals (except mains supply terminals) must only be connected to voltages of maximum 16 V rms and 22.6 V peak or 35 VDC. * GND is isolated from other earth connections. IO 351B / 60

19 Group Terminal Designation Data Diagram 3B 4B 5 16 DI4 Digital input 17 GND 18 AO4 Analog output, 0-10 V 20 DI5 Digital input 21 GND 22 AO5 Analog output, 0-10 V 24 DI6 Digital input 25 GND 26 AO6 Analog output 42 DI7 44 DI8 Digital input 46 DI9 47 GND Fit jumpers instead of the external stops for which the controller is designed. 36 PTC 4 38 PTC 5 Input for PTC sensor or thermal switch 40 PTC 6 41 GND, PTC Fit jumpers if no PTC sensor or thermal switch is connected. All terminals (except mains supply terminals) must only be connected to voltages of maximum 16 V rms and 22.6 V peak or 35 VDC. 82 DO4 NO 83 DO4 C 83 DO4 C 84 DO5 NO 85 DO5 C 85 DO5 C 86 DO6 NO 87 DO6 C 87 DO6 C 88 DO7 NO 89 DO7 C Relay contact IO 351B IO 351B IO 351B / 60

20 3.4 IO 111 terminals T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 PE 16 D1 D2 D3 D4 D5 D6 D7 D8 A Y B Reset ON DIP P1 P2 P3 P4 P5 10 Fig. 11 IO 111 module I1 I2 I3 9 TM Pos. Terminal Description Data Function Diagram T1 T2 G1 A1 G2 A2 Terminal for alarm relay Terminal for alarm relay GND for analog output 1 Terminal for analog output 1 GND for analog output 2 Terminal for analog output 2 Max. 250 VAC Max. 250 VAC 1) 0 V 2) 0 V 1) 15 VDC 2) 24 VDC, max. 100 ma 1) 0 V 2) 0 V 1) 15 VDC 2) 24 VDC, rated 1 ma All alarms trip the alarm relay. The alarm relay is closed during normal operation. In case of alarm or if the IO 111 is not connected to the power supply, the relay opens and breaks the connection between T1 and T2. Analog output 1 has two functions set via DIP switch 7. See section Analog outputs. 1) 4-20 ma for content of water in oil. Load resistance: Max. 250 Ω. 2) Pulse output for content of water in oil and stator insulation resistance. Analog output 2 has two indications set via DIP switch 6. See section Analog outputs. 1) 4-20 ma for stator winding temperature. Load resistance: Max. 250 Ω. There is no 4-20 ma signal in PTC installations. 2) Pt1000 emulator for stator winding temperature. K1 K2 GND connection Terminal for conductor for contactor status 0 V Digital input Feedback from motor contactor whether the pump is running or not. The input must be short-circuited when the pump is running. The signal is used by the IO 111 for filtering of measuring signals and for analysis during fault indication. R1 R2 GND connection Terminal for resetting 0 V Digital input For resetting of alarms, see installation and operating instructions for the IO 111. The input must be short-circuited when alarms are reset. PE Earth Earth GND for power supply + Plus for power supply 0 VDC 24 VAC ± 10 % 24 VAC ± 10 % 24 VDC ± 10 % A RS-485 A Bus input Y RS-485 GND 0 V B RS-485 B Bus input I1 Earth Earth I2 Not connected I3 Terminal for measurement of stator insulation resistance CAT II 600 V Power supply to the IO 111. RS-485 communication connection (9600 baud). The insulation resistance between stator windings and earth is measured. The measurement is only correct when the motor is stopped. Measurement voltage: 10 VDC. 1) 2) 1) 2) A1 G1 A2 G2 A Y B L1 L2 L3 I3 I1 A1 G1 T2 T1 A2 G2 K2 K1 R2 R1 + R R 20 / 60

21 Pos. Terminal Description Data Function Diagram P1 P2 P3 P4 P5 D1 D2 D3 D4 D5 D6 D7 Terminal for sensors in the pump Terminal for power supply to sensors in the pump Terminal for sensors in the pump Terminal for power supply to sensors in the pump Terminal for sensors in the pump Terminal for alarm in case of too high stator temperature GND for alarm in case of too high stator temperature Terminal for alarm in case of moisture in the motor GND for alarm in case of moisture in the motor Terminal for alarm in case of insulation fault GND for alarm in case of insulation fault Terminal for warning Sensor input 15 V Sensor input 15 V Sensor input Digital output 24 VDC min. 10 kω 0 V Digital output 24 VDC min. 10 kω 0 V Digital output 24 VDC min. 10 kω 0 V D8 GND for warning 0 V Digital output 24 VDC min. 10 kω Thermal switch or PTC sensor according to DIN and P1 to P5 are used for the connection of sensors in the pump. All sensors in contact with phase voltage must be doubleinsulated according to EN Alarm in case of too high temperature in the stator windings. The output is closed during normal operation. If an alarm occurs, the connection is broken between D1 and D2. Alarm in case of moisture in the motor part of the pump. The output is closed during normal operation. If an alarm occurs, the connection is broken between D3 and D4. Alarm in case of too low insulation value between stator windings and earth. The output is closed during normal operation. If an alarm occurs, the connection is broken between D5 and D6. Warning. The output is closed during normal operation. If a warning occurs, the connection is broken between D7 and D8. The following warnings can occur: communication warning configuration warning too much water in oil stator insulation resistance below warning limit. See also section 8. Indication in the installation and operating instructions for the IO 111 and section Indicator lights on the IO 351B. P1..P5 D1 D2 D3 D4 D5 D6 D7 D8 21 / 60

22 4. Configuration 4.1 Necessary equipment The following equipment is needed: R100, SW version 14, Nov. 01, 2005 or later PC Tools PC Tool Link adapter. 4.2 Configuration of Dedicated Controls The configuration consists of three steps: Setting the GENIbus number in the IO 351B module, if installed. See section Setting the GENIbus number in IO 351B modules, if installed. Configuration of the CU 361 control unit. Use the configuration wizard or the PC Tool WW Controls supplied on CD-ROM. See section 6. PC Tool. Configuration of the IO 111 module, if installed. Use the PC Tool Water Utility, DIP switches in section or see the installation and operating instructions for the IO Setting the GENIbus number in IO 351B modules, if installed This module must have a GENIbus number according to the following table: Module number GENIbus number A01 (IO 351B) 41 To assign a GENIbus number to the IO 351B module, proceed as follows: 1. Switch on the power supply to the Dedicated Controls. 2. Switch on the R100 and point it at the IR window of the first IO 351B to establish connection. Note If there are more than one IO 351B module, move close to the IR window to make sure that the R100 only communicates with one module at a time. Fig. 12 IR window of the IO 351B 3. Go to the first display "Number, IO 351" in the INSTALLATION menu with the R100. See fig. 13. Set the number of the module according to the above table. TM TM Fig. 13 Menu INSTALLATION, "Number, IO 351" 4. Send the number to the module by pressing [OK] on the R Configuration of the IO 111, if installed See section IO 111 settings. 22 / 60

23 4.2.3 IO 111 settings Potentiometer The warning limit for stator insulation resistance is set by means of a potentiometer (pos. 4). See fig. 10. The limit can be set between 10 and 1 MΩ. Note The alarm limit is 1 MΩ. 1 MΩ 10 MΩ TM Fig. 14 Potentiometer DIP switches The IO 111 must be configured for the pump connected by means of the DIP switches (pos. 11). See fig. 10. ON DIP TM Fig. 15 DIP switch A configuration alarm will be given if the configuration does not correspond to the pump connected. if the configuration fault is of safety-related importance. See section 8. Indication, point 6, in the installation and operating instructions for the IO 111. A configuration warning will be given if the configuration fault is of function-related importance. See section 8. Indication, point 15, in the installation and operating instructions for the IO 111 and section Indicator lights on the IO 351B. Switch 9 is not used. Pump variant The IO 111 must be set to the actual pump. In the pump type designation, there is an A or D. Example 1, internal wiring: SE A Ex 4 5 1D Example 2, external wiring: SE S.496.Ex.S.5.13.C.Q.S These letters (A and D in the examples) can be found on the pump nameplate and refer to the setting of DIP switches 1 and 2. Note The SM 111 cannot be used together with Dedicated Controls. The signals from the SM 111 will not be monitored. Pump variant ON DIP Description Variant A Variant D ON 1 2 ON 1 2 Installation without SM 111. Sensors are connected directly to the IO 111. Installation without SM 111. All sensors are hardwired out of the pump. The IO 111 can be used for indication of water in oil and as PTC relay. 23 / 60

24 Address for bus communication The IO 111 can communicate with control systems via a bus connection. In connection with bus communication, the IO 111 is slave. As a control system must be able to identify the slave units with which it communicates, the IO 111 modules must have unique addresses. Addresses between 40 and 46 are set by means of the switches 3, 4 and 5. See table. If the DIP switches are set to bus configuration, the address of the IO 111 module is set from the control system via bus. The address can be selected between 32 and 231. As standard, the address is set to 231. Address ON DIP Description 40 Pump Pump Pump Pump Pump Pump Pump Bus configuration The address of the IO 111 is set from the control system via the bus connection. Default address: / 60

25 Analog outputs The analog outputs of the IO 111 can be set to various types of output signal. Analog output Analog output 2: G2 and A2 (pos. 2) Analog output 2: G2 and A2 (pos. 2) Analog output 1: G1 and A1 (pos. 2) Analog output 1: G1 and A1 (pos. 2) ON DIP Description Motor temperature 4-20 ma, C 0 ma = no sensor Motor temperature Pt1000 emulator Ω, C Water in oil 4-20 ma, 0-20 % 0 ma = water-in-oil sensor not fitted 3.5 ma = alarm, air in oil chamber 22 ma = warning, water content far outside the measuring range Water in oil Pulse output: 0-20 % Maximum connection: 24 V, 100 ma Status of output transistor Off On Pulse A Pulse B Time Pulse A, water in oil: s = 0-20 % 10 s = water content far outside the measuring range Pulse B, insulation resistance: 0.5 s = 0 MΩ 10.5 s = 20 MΩ Bus protocol By setting the bus protocol, the type of bus connection is chosen. GENIbus is a Grundfos standard protocol for Grundfos products. The Modbus protocol is used for communication between the IO 111 and a control unit from another supplier. Bus protocol ON DIP Description GENIbus Modbus 8 8 Grundfos standard protocol for communication between Grundfos products See WebCAPS, Literature, Accessories, Accessories, electrical and Operating the IO 111 via Modbus, document number / 60

26 ATEX/IECEx protection ATEX/IECEx protection can be activated/deactivated by means of DIP switch 10. ATEX/IECEx protection ON DIP Description Deactivated Activated Activation of ATEX/IECEx protection enables additional alarms: Main bearing temperature to high. Default alarm temperature: 140 C (installation with SM 111). Support bearing temperature to high. Default alarm temperature: 140 C (installation with SM 111). Missing signal from bearing sensor (installation with SM 111). Missing signal from water-in-oil sensor Communication alarm (installation with SM 111) CU 361 and IO 351 installation and operating instructions See WinCAPS or WebCAPS > Service > Dedicated Controls > CU 361 or IO 351 > Installation and operating instructions. 26 / 60

27 5. Documentation supplied with Dedicated Controls The following documentation is supplied with the Dedicated Controls control cabinet. Instructions Safety instructions for Dedicated Controls (printed multilingual version) Installation and operating instructions for Dedicated Controls (monolingual version on CD-ROM) Supplement to installation and operating instructions for Dedicated Controls (printed version) Installation and operating instructions for the CU 361 (multilingual version) Installation and operating instructions for the IO 351 (multilingual version). Other documentation on control cabinet Electrical wiring diagrams List of supplied components (parts list) and description of cable colours and dimensions as well as sizes of backup fuses Control cabinet layout. 6. PC Tool For information about PC Tool, open the help function in the software. 6.1 Connection of PC to Dedicated Controls For the physical connection between the PC and Dedicated Controls, a Grundfos PC Tool Link is used. This converts the RS-485 used by Dedicated Controls to USB used by the PC. The PC Tool Link also provides a galvanic separation between Dedicated Controls and the PC. 70 DO1, C 71 DO1, NO 72 DO1, NC 73 DO2, C 74 DO2, NO 75 DO2, NC USB cable PC Tool Link TTL cable V 51 AI V 54 AI 2 57 AI 3 58 GND DI 1 GND DI 2 GND DI 3 RS485, A RS485, GND RS485, B RS485, A RS485, GND RS485, B BYA A1 Y1 B1 Line Neutral PE L N Service plug Fig. 16 Connection of PC to Dedicated Controls using the PC Tool Link 27 / 60

28 7. Fieldbus communication module 7.1 SCADA system See the installation and operating instructions for Dedicated Controls to set up communication to SCADA systems. See also section 7.2 Data communication or menu 4.3 in the CU 361. Grundfos does not supply SCADA systems. If it seems as if the SCADA system is faulty, we recommend you to contact the supplier. Note The SCADA system integrator can order a functional profile from Grundfos Communication The communication takes place via a Modbus module or a GSM/GPRS module. See section 7.2 Data communication. 7.2 Data communication The CU 361 must have a CIM module (CIM = Communication Interface Module) fitted to be able to transfer data to the SCADA system or to a mobile phone. Various CIM modules are available, depending on the type of network. The CIM module can be fitted directly in the CU 361. See section 7.3 Fitting the CIM module. For configuration of the CIM module, see the installation and operating instructions and the functional profile on the CD-ROM supplied with the module. The user must select the type of communication module fitted before a network connection can be established. The following CIM modules can be fitted in the CU 361: CIM 200 (Modbus via RS-485) CIM 250 (Modbus and SMS via GSM/GPRS) CIM 270 (GRM) (GRM = Grundfos Remote Management). Display_4.3 Fig. 17 Example, selection of CIM module and communication 28 / 60

29 7.2.1 Modbus network CIM 200 (Modbus via RS-485) The CIM 200 module transfers data to/from the CU 361 and the local Modbus network. See fig. 18. SCADA Modbus network CU 361 (CIM 200 built-in) TM Fig. 18 Example, CIM 200 CIM 250 (Modbus and SMS via GSM/GPRS) The CIM 250 transfers data to/from the CU 361 and a GSM/GPRS network. See fig. 19. The CIM 250 can send/receive SMS messages to/from one or more mobile phones. The CIM 250 can also send data to a remote SCADA system. Note A series of system parameters must be set before SMS messaging can be used. SCADA GSM antenna Mobile phone CU 361 (CIM 250 built-in) TM Fig. 19 Example, CIM / 60

30 7.2.2 CIM 270 (GRM) The CIM 270 module is used to link with Grundfos Remote Management. GRM server GRM WebAccess GSM antenna Mobile phone CU 361 (CIM 270 built-in) TM Fig. 20 Example, CIM Ethernet Ethernet is the most widely used standard for local networks (LAN). The standardisation of this technology has created some of the easiest and cheapest ways of creating communication between electrical units, for instance between computers or between computers and control units. The web server of the CU 361 makes it possible to connect a computer to the CU 361 via an Ethernet connection (Ethernet crossover cable). The user interface can thus be exported from the CU 361 to a computer so that the CU 361 and consequently the Dedicated Controls system can be remotely monitored and controlled. See figs 21 and 22. Note Grundfos recommends that the system administrator is contacted to arrange security protection for the CU 361 connection. In order to use the web server, the user must know the IP address of the CU 361. All network units must have a unique IP address to communicate with each other. The IP address of the CU 361 from factory is Alternatively to the factory-set IP address, it is possible to use a dynamic assignment of IP address. This is possible by activating a DHCP (Dynamic Host Configuration Protocol) either directly in the CU 361 or via the web server. Ethernet crossover cable CU 361 TM Fig. 21 Example, Ethernet connection 30 / 60

31 PC with access to the CU 361 via the internet Ethernet cable for internet connection CU 361 TM Fig. 22 Example, internet connection Dynamic assignment of an IP address for the CU 361 requires a DHCP server in the network. The DHCP server assigns a number of IP addresses to the electrical units and makes sure that two units do not receive the same IP address. A standard internet browser is used for connection to the web server of the CU 361. If the user wants to use the factory-set IP address, no changes are required in the menu display. Open the internet browser, and enter the IP address of the CU 361. Now open the browser, and enter the CU 361 "Host name" (Default: CU361) instead of the IP address. The internet browser will try to connect to the CU 361. The host name can be read in the display, but can only be changed using a PC tool or via a web browser. Note DHCP requires a host name. This is the first menu display seen when the CU 361 connects. TM Fig. 23 Connecting to the CU 361 Factory setting Username: admin Password: admin When username and password have been entered, a Java Runtime Environment application starts up in the CU 361, provided that it has been installed on the computer in question. If this is not the case, but the computer is connected to the internet, then use the link on the screen to download and install the Java Runtime Environment application. 31 / 60

32 Fig. 24 Display with link to JavaScript application The Java Runtime Environment application transfers the CU 361 user interface (including display and panel functions) onto the computer screen. The CU 361 can now be controlled from the PC. Fig. 25 Network setting Change of network setting When the connection to the web server of the CU 361 has been established, it is possible to change the network setting. TM TM TM Fig. 26 Change of network setting 1. Click the icon "Network admin". 2. Enter the changes. 3. Click [Submit] to enable the changes. 32 / 60

33 Change of password TM Fig. 27 Change of password 1. Click the icon "Change password". 2. Enter the new password. 3. Click [Submit] to enable the new password GENIbus By installing an external GENIbus module (CIM 050), it is possible to connect a CU 361 to an external network. The connection can be established via a gateway. For more information, contact Grundfos. 33 / 60

34 7.3 Fitting the CIM module The CIM module must be fitted by authorised personnel. Warning Switch off the power supply to the CU 361 before fitting the CIM module. Warning Electrostatic discharge (ESD) must be avoided when fitting the CIM module, for instance by wearing an antistatic wrist strap as shown in fig. 30. Fit the CIM module as follows: 1. Remove the screw in the back cover of the CU 361. See fig. 28. Fig. 28 Removing the screw holding the back cover 2. Remove the cover. Place the cover on a plane surface, and push out the marked knockout using a screwdriver or a similar tool. See fig. 29. TM TM Fig. 29 Opening the back cover and removing the knockout 34 / 60

35 3. Fit the CIM module. See fig. 30. TM Fig. 30 Fitting the CIM module 4. Place the labels supplied with the CIM module on the back cover. See fig. 31. CIM 250 GSM Type: CIM 250 Kit Funct. module - Geni/RS485Op Prod. No P. C Version V01 Serial No TM Fig. 31 Placing the new labels on the back cover 5. Refit the back cover to the CU 361, and secure it with the mounting screw. See fig. 32. TM Fig. 32 Refitting the back cover 35 / 60

36 8. General settings, CU Display language In this menu, the CU 361 display language is selected. In connection with service, it is easy to change over to the service language, using the function "Change language to the service language (English)". Path: Settings>General settings, CU 361> Description Other functions related to CU 361 Display language. Display_ Fault finding 9.1 Power supply See the system wiring diagram and system documentation. 9.2 External control, data collection, SCADA systems See the system wiring diagram and system documentation. 9.3 Pumps See the documentation for the connected pump(s). For example via WinCAPS, WebCAPS or service instructions for the connected Grundfos pump(s). 36 / 60

37 10. Fault finding tools 10.1 CU 361 display Status The first status display is shown below. This display appears when the Dedicated Controls is switched on, and it appears when the buttons of the control panel have not been touched for 15 minutes. The status display is the main opening display of the CU 361. Note If the buttons on the control panel have not been activated for 15 minutes, the CU 361 automatically reverts to this display. An alarm is shown as an alarm bell next to the unit that caused the alarm. When the system registers an alarm or warning, the following will happen: An alarm bell is shown on the right of the upper status line. The red indicator light on the control panel lights up. "Current alarms" appear as the first line below the pit graphics. The alarm relay operates. The indication is maintained as long as the system has an active alarm. An alarm is active until it has been reset, either automatically or manually via "Current alarms" in the status display. An alarm cannot be reset until the fault causing the alarm has been corrected. Example: An overtemperature alarm cannot be reset until the pump has cooled. Note The display shown below should be considered as an example. Path: Status> Description Options: Current alarms See current alarms. The line is only active if there is one or more active alarms. System See operating parameters for the system. Pump 1 See operating parameters for pump 1. Pump 2 See operating parameters for pump 2. The hand symbol indicates that the pump is manually controlled, i.e. the pump can only be started and stopped manually. Float switches See current positions and status of the float switches. Mixer See mixer status. Electrical overview See actual values for analog and digital inputs as well as digital outputs. Note: Float switches and mixer will only appear if they are installed in the system Display_1 37 / 60

38 Key to display Pos. Description 1 Lowest start level: If the water level rises above this level, the first pump will start. 2 Lowest stop level: If the water level falls below this level, both pumps will stop. 3 The display shows that pump 1 is started. The bottom is a dotted/broken line. 4 The actual flow is measured by a flowmeter or with the help of level measurements and pit data. See installation and operating instructions for Dedicated Controls. Alarm bell: The alarm bell is visible as long as there are active alarms. The red indicator light on the control panel 5 has the same function. 6 The broken line moves up to symbolise flow. The line appears when one or both pumps are running. 7 Shows the water level as falling or rising. 8 This value and the wavy line show the current water level in the pit. 9 Mixer: The propeller rotates if the mixer is operating. 10 The display shows that pump 2 is stopped. The bottom is a thick, unbroken line. 11 Pressure sensor symbol: The sensor is shown at the bottom of the pit and represents a standard pressure sensor. 38 / 60

39 10.2 System This display shows the actual operating parameters of the system. Note The display shown below should be considered as an example. Path: Status>System> Description The display shows an operating overview of the system. Operating hours Parallel-operation time Overflow time Overflow volume Number of overflows Total volume Energy Specific energy GSM/GPRS. Display_1.1 Description of operating parameters Operating parameter Operating hours Parallel-operation time Overflow time Overflow volume Number of overflows Total volume Energy Specific energy GSM/GPRS Function Total number of system operating hours. The accumulated time in which more than one pump has been in operation. Overflow duration. The estimated overflow volume, based on the latest flow calculation. The number of registered overflows. The accumulated volume of liquid removed. Note: Requires a flowmeter (analog or pulse measurement), or the volume is calculated using an analog sensor if the pit dimensions are known. For more pit configuration details, see installation and operating instructions for Dedicated Controls. Total amount of energy in kwh. Shows the specific energy, indicating the efficiency of the pump to convert the electrical energy (measured in kwh) to pumped volumes (measured in m 3 ). The specific energy is indicated in kwh/m 3. To be able to make a satisfactory average measurement, the measuring interval is one hour. Note: Requires an energy meter (pulse input or analog input). GSM/GPRS modem status: Ready Invalid PIN code Invalid PUK code Invalid service centre Insert SIM card SIM card defective Invalid SIM card SIM busy. 39 / 60

40 10.3 Specific pump This display shows the actual operating parameters of pump 1. Many parameters will show a value only if the relevant sensors and modules are fitted. Note Note If two pumps are installed in the pit, a display for pump 2 will appear. The display shown below should be considered as an example. Path: Status>Pump 1> Display_1.2 Description The display shows an operating overview of pump 1. Status Controlled by Operation Operating hours Latest runtime Time since service Time for service Number of starts Number of starts/hour Average flow Latest flow Number of flow measurements Average current Latest current Start level Stop level. Description of operating parameters Operating parameters Status Controlled by Operation Operating hours Latest runtime Time since service Time for service Number of starts Number of starts/hour Average flow Latest flow Number of flow measurements Average current Latest current Start level Stop level Function Shows if a pump is started or stopped. CU 361 (system), manually by switch (Auto/On/Off) or via SCADA. Shows how the system is being controlled, automatically or manually. Number of hours the pump has been in operation (can be changed if another pump is installed). The pump's latest operating period. The time elapsed since the pump was last serviced (can be reset by Grundfos Service). Time until the next service is due. Number of pump starts since the pump was installed/connected (can be changed if another pump is installed). Number of pump starts in the last hour. Requires an analog level sensor or flow sensor. See installation and operating instructions for Dedicated Controls. The calculated/measured flow of the last pump that was running. Requires an analog level sensor. See installation and operating instructions for Dedicated Controls. The actual average current consumption. 0 A when the pump stops. The current value when the pump stopped. The value updates when the pump is running. Requires a current sensor/ammeter. Requires an analog level sensor (not shown with alternating operation). Requires an analog level sensor. 40 / 60

41 10.4 GSM/GPRS This display shows the status of the GSM modem. Note This display is only shown if a modem has been configured in the system. The display can be used to check the antenna conditions and for fault finding. SIM card status Shows the SIM card status message sent to the system. Signal strength A graph shows the actual signal strength. If the signal strength is unknown, " " is displayed. If there is no signal, "No signal" is displayed. GPRS state Shows the GPRS network state. Statistics Displays the number of sent and received SMS messages and the amount (kb) of sent and received GPRS data. GPRS network The current network IP address. Note The display shown below should be considered as an example. Path: Status>System>GSM/GPRS> Description The display shows the status of the GSM modem. GSM/GPRS SIM card status Signal strength GPRS state. Display_1.1.1 Statistics SMS messages sent SMS messages received GPRS data sent GPRS data received Outgoing calls Incoming calls. GPRS network IP address. 41 / 60

42 10.5 Float switch status This display shows the current positions and functions of the float switches. The display can be used for function testing and fault finding. "Off" means that the float switch is hanging downwards. "On" means that the float switch is kept up by the water. Note The display shown below should be considered as an example. Path: Status>Float switch status> Description The display shows the current positions and functions of the float switches. Float switch 4: High level. Float switch 3: Pump 2 starts. Float switch 2: Pump 1 starts, and both pumps stop. Float switch 1: Dry running. Display_ / 60

43 10.6 Mixer This display shows the status of the mixer and the mixer counters. The display can be used for fault finding and service. Note Note This display will only appear if a mixer is installed. The display shown below should be considered as an example. Path: Status>Mixer> Description The display shows the status of the mixer and the mixer counters. Status Operating hours Time since service Time for service Number of starts Number of starts/hour. Display_ / 60

44 10.7 Electrical overview This display shows an overview of the various inputs and outputs. Note The display shown below should be considered as an example. Path: Status>Electrical overview> Description The display shows an overview of the various inputs and outputs. Electrical overview Select submenu: Analog inputs Digital inputs Digital outputs. Display_ / 60

45 Analog inputs This display shows the status of the individual analog inputs. Note The display shown below should be considered as an example. Path: Status>Electrical overview>analog inputs> Description Analog input AI1 (CU 361) [51]: The AI1 analog input on the CU 361 (designated terminal 51) is set up as a current input. The measured value of 14.9 ma corresponds to a level and a pressure of 3.40 m. Display_ / 60

46 Digital inputs This display shows the status of the individual digital inputs. Note The display shown below should be considered as an example. Path: Status>Electrical overview>digital inputs> Description Digital input DI2 (IO ) [12]: The DI2 digital input on the IO 351 (designated terminal 12) is linked to the function "Contactor feedback, pump 1", and the contact is closed. Display_ / 60

47 Digital outputs This display shows the status of the individual digital outputs. Note The display shown below should be considered as an example. Path: Status>Electrical overview>digital outputs> Description Digital output DO1 (CU 361) [71]: The DO1 digital output on the CU 361 (designated terminal 71) is linked to the function "High-level alarm", and the alarm is active. Display_ Alarms and warnings 11.1 Alarm indicators Dedicated Controls systems feature the following alarm indicators: Red indicator light on the CU 361. The indicator light will be on when an alarm or a warning is active or until the alarm or warning has been reset. The display of the CU 361. The alarm relay in the CU 361. Alarms and warnings are divided into System alarms Pump alarms Mixer alarms Combi alarms. 47 / 60

48 11.2 Alarm settings Alarms can only be indicated if the desired alarms have been enabled. See section "Alarm settings" in the installation and operating instructions for Dedicated Controls. All fault sources are either of the analog or digital fault type Analog fault configuration Analog faults are activated if the currently measured value is outside a set limit. An analog fault can be registered as a warning or as an alarm. Alarm delay An alarm delay is typically used when a measuring signal is unstable. The signal from surface water waves may generate a high water level for a short period. An alarm delay allows time for the unstable signal to pass, e.g. for the water level to steady. User-defined alarm relay A warning or alarm can be coupled to a relay output. Alarm resetting Select the alarm resetting as manual or automatic. All warnings will be reset automatically. Action, warning and alarm (High level) Set SMS messaging schedules for the service manager in the following periods: Work, Off, Sleep. Schedule periods serve practical purposes, e.g. to avoid sending SMS messages about minor faults to the service manager in the middle of the night. The service manager will receive the SMS messages when he/she has returned to work. Warning or alarm callback to the SCADA system is also selected in this display. Note The display shown below should be considered as an example. Path: Settings>Alarm settings>system alarms>high level> Description Make the required settings. Alarm delay Warning Enabled Limit User-defined alarm relay. Alarm Enabled Limit User-defined alarm relay. Manual resetting Automatic resetting. Display_ Action, warning and alarm Enable SMS, work Enable SMS, off Enable SMS, sleep SCADA callback. 48 / 60

49 Digital fault configuration Digital faults are activated in case of a faulty system condition. A digital fault can be registered as a warning or as an alarm. Alarm delay An alarm delay is typically used when a measuring signal is unstable. The signal from surface water waves may generate a high water level for at short period. An alarm delay allows time for the unstable signal to pass, e.g. for the water level to steady. User-defined alarm relay A warning or alarm can be coupled to a relay output. Alarm resetting Select the alarm resetting as manual or automatic. All warnings will be reset automatically. Action, warning and alarm (Battery backup (UPS)) Set SMS messaging schedules for the service manager in the following periods: Work, Off, Sleep. Schedule periods serve practical purposes, e.g. to avoid sending SMS messages about minor faults to the service manager in the middle of the night. The service manager will receive the SMS messages when he/she has returned to work. Warning or alarm callback to the SCADA system is also selected in this display. Note The display shown below should be considered as an example. Path: Settings>Alarm settings>system alarms>battery backup (UPS)> Description Make the required settings. Alarm delay Disabled Warning Alarm. Alarm User-defined alarm relay Manual resetting Automatic resetting. Display_ Action, warning and alarm Enable SMS, work Enable SMS, off Enable SMS, sleep SCADA callback. 49 / 60

50 12. How to trace an alarm 12.1 Menu Status See installation and operating instructions for Dedicated Controls, section 13. Status. 1. If an alarm occurs, "Current alarms" will be displayed as the first line in the Status menu. 2. Select "Current alarms", and press [ok] on the CU Menu Alarm The display shows the last 24 alarms with date and time of occurrence Current alarms This display shows all active system alarms. An alarm can only be reset when it is no longer active. An alarm can be reset when a date/time is given to the right of "Disappeared at". Press [ok] to reset the marked alarm. See section Alarm log. Symbol Description Alarm Warning This menu shows the following: Warnings caused by faults that still exist. Warnings caused by faults that have disappeared, but the warning requires manual resetting. Alarms caused by faults that still exist. Alarms caused by faults that have disappeared, but the alarm requires manual resetting. All warnings and alarms with automatic resetting are automatically removed from the menu when the fault has been corrected. Alarms requiring manual resetting are reset in this display by pressing [ok]. For every warning or alarm, the following is shown: Whether it is a warning or an alarm. Where the fault occurred: System, Pump 1, Pump 2, etc. What the cause of the fault is, and the alarm code in brackets, e.g. High level (191). When the fault occurred: Date and time. When the fault disappeared: Date and time. If the fault still exists, date and time are shown as The latest warning/alarm is shown at the top of the display. Note The display shown below should be considered as an example. Path: Alarm>Alarm status>current alarms> Description The display shows two active alarms. Display_ / 60

51 Alarm log The alarm log can store up to 24 warnings and alarms. For every warning or alarm, the following is shown: Whether it is a warning or an alarm. Where the fault occurred: System, Pump 1, Pump 2, etc. In the case of an input-related fault, the input will appear. What the cause of the fault is, and the alarm code in brackets, e.g. warning: Conflicting levels (204), etc. When the fault occurred: Date and time. When the fault disappeared: Date and time. If the fault still exists, date and time are shown as The latest warning/alarm is shown at the top of the display. Note The display shown below should be considered as an example. Path: Alarm>Alarm status>alarm log> Description The display shows one warning and three alarms, two of which are still active. To reset alarms, see section Current alarms. Note: An alarm cannot be reset until the fault has been corrected. Display_ Password protection A password can be set in order to prevent unintentional change of settings. There are two different passwords: password for menu Settings password for menu Operation Service password If a customer-set password is not available for the Grundfos service engineer, the Dedicated Controls system can be unlocked by using the Grundfos service code "6814". Please protect this code, and prevent access by unauthorised persons. 51 / 60

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions GRUNDFOS INSTRUCTIONS LCD 08 Installation and operating instructions Installation and operating instructions Original installation and operating instructions CONTENTS Page. Symbols used in this document.

More information

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE isocket Smart Relay is a complex Smart House system which is installed in the fuse cabinet (electric cabinet) in the house. We therefore assume that

More information

CU 300. Installation and operating instructions GRUNDFOS INSTRUCTIONS

CU 300. Installation and operating instructions GRUNDFOS INSTRUCTIONS GRUNDFOS STRUCTIONS CU 300 Installation and operating instructions No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm Other languages www.grundfos.com/cu300-manual

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

THX-DL Data Logger USER & INSTALLATION MANUAL V

THX-DL Data Logger USER & INSTALLATION MANUAL V THX-DL Data Logger USER & INSTALLATION MANUAL V1.2012 www.thermomax-refrigeration.com Contents PRESENTATION Summary of Features 2 INSTALLATION Safety Precautions 4 THX Unit 4 Sensors 4 Alarm Relay 4 Power

More information

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction... 4 2. Product Features... 4 3. Package

More information

WebAlert WA500 Series Process Monitor Instruction Manual

WebAlert WA500 Series Process Monitor Instruction Manual W A L C H E M IWAKI America Inc. WebAlert WA500 Process Monitor WebAlert WA500 Series Process Monitor Instruction Manual Five Boynton Road Hopping Brook Park Holliston, MA 01746 USA TEL: 508-429-1110 FAX:

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5

More information

600 Range Dialer Installation Manual. Version 1.0

600 Range Dialer Installation Manual. Version 1.0 600 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract

More information

User manual. KNXgal. version

User manual. KNXgal. version User manual version 1.3 gal Management alarm control panels Galaxy from bus powered from bus Communication indication on and with Galaxy control panel DIN rail mount (1 modul) Adjustable address on with

More information

SC-F3G User Manual 1.0

SC-F3G User Manual 1.0 SC-F3G User Manual 1.0 Table of Contents 1. Introduction... 3 2. Functions... 3 3. Features... 3 4. Package Contents... 3 5. Device Configuration... 4 6. Status LED signals... 5 7. Before You Start...

More information

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014 Solar Charge controller with Ethernet Release : 19 June 2014 Hardware Version : Version 1 Firmware version 1 PC Application Software : Version 1.0.0.0 Hardware Description : The Solar Smart regulator was

More information

Monitoring Solutions

Monitoring Solutions GSM Systems Monitor: Temperature, Humidity, Power, Water, Smoke, Carbon Monoxide and More September 2016 Table of Contents GSM Systems... 3 Argon 100 GSM... 3 Ares 12 & 14 GSM... 4 Poseidon2 4002... 5

More information

T M. User Manual. MarinaGuard. Ground Fault Monitoring Panel For Marina Shore Power

T M. User Manual. MarinaGuard. Ground Fault Monitoring Panel For Marina Shore Power T M User Manual MarinaGuard Ground Fault Monitoring Panel For Marina Shore Power NAE1095810 / 03.2013 T M Bender Inc. USA: 700 Fox Chase Coatesville, PA 19320 Toll-Free: 800-356-4266 Phone: 610-383-9200

More information

REMOTE MONITORING AND ALARM SYSTEM

REMOTE MONITORING AND ALARM SYSTEM FUNCTIONALITY A. The water and wastewater facilities remote monitoring, reporting and alarm notification system shall be comprised of a hosted, Web-based user-interface which communicates to remotely monitored

More information

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems) ISOSCAN EDS460/490 EDS461/491 Insulation fault locators with control and display function for EDS systems (insulation fault location systems) EDS460-490_D00085_01_D_XXEN/01.2017 ISOSCAN EDS460/490 EDS461/491

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with,,,, 0 and signal inputs Storage of the last state of inputs and sequence in the case

More information

Ethernet General Purpose

Ethernet General Purpose Ethernet General Purpose Technical Manual Revision 1.03 8 November 2013 Pakton Technologies IO PAE224 Ethernet GPIO Manual.docx Page 1 of 22 Revision 1.03 Last updated 8/11/2013 Table of Contents INTRODUCTION...3

More information

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual Revision 1.03 8 November 2013 JVA Technologies Ethernet General Purpose IO Technical Manual www.jva-fence.com.au Table of Contents INTRODUCTION...3 Scope and Purpose...3 Glossary...3 SPECIFICATIONS...4

More information

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations. 1 P age Ezeio v9-120317 Eze Cloud Based Monitoring Systems. Created by Intech Instruments Ltd December 2014 Important Supplementary Manual to the main Ezeio manual. Ezeio Controller and the 2400-A16 input

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

Alarm module for leak detection with webserver

Alarm module for leak detection with webserver This instruction document consists of 2 parts : one part about the assembly of the components and one part about configuration and starting-up of the system. The assembly is done by the qualified installer

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

Lift Station Level Controller

Lift Station Level Controller Lift Station Level Controller Installation and Operation Manual 1 California Motor Controls, Inc. Benicia, CA Table of Contents 1. Features Product Overview... 4-6 Access Security... 7 Optional Features...

More information

Insulation fault evaluator EDS460-DG

Insulation fault evaluator EDS460-DG Insulation fault evaluator for localising insulation faults in DC IT systems with a number of branch circuits where high system leakage capacitances are involved Preliminary data sheet TDB108021en/09.2008

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

7 USE THE COMMANDS INTERNET VOICE MESSAGES RECORD VOICE MESSAGE DURATION OF VOICE MESSAGES 64

7 USE THE COMMANDS INTERNET VOICE MESSAGES RECORD VOICE MESSAGE DURATION OF VOICE MESSAGES 64 MANUAL FOR PROFORT GSM DEVICES 1 MANUAL FOR PROFORT GSM DEVICES 2 1.1 SPECIFICATIONS 2 1.2 FUNCTIONS 4 1.3 DESCRIPTION 6 1.4 SYSTEM ILLUSTRATION 7 2 MOUNTING 8 2.1 PREPARE THE UNIT 8 2.2 ELECTRIC MOUNTING

More information

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark Description ECL Comfort 310 controller series ECL 310 The ECL Comfort 310 is an electronic weather

More information

RACK MONITORING SYSTEM - RAMOS Ultra

RACK MONITORING SYSTEM - RAMOS Ultra CONTEG DATA SHEET version: 9-05-0 COMPLEMENTARY SYSTEMS RACK MONITORING SYSTEM marketing@dafnia.com www.dafnia.com ABU DHABI UAE +97 55575 DUBAI JAFZA +97 4 5995 +97 4 8840 MUSCAT DOHA OMAN +968 4 75005

More information

IRIS Touch 400 & 600 Range Installation Manual. Honeywell Galaxy Range. Version 2.0

IRIS Touch 400 & 600 Range Installation Manual. Honeywell Galaxy Range. Version 2.0 IRIS Touch 400 & 600 Range Installation Manual Honeywell Galaxy Range Version 2.0 Table of Contents 1 System Overview... 4 2 IRIS Touch 440 & 640 PCB Layout... 5 3 Connection & Configuration for Honeywell

More information

PowerLogic ION Setup Meter Configuration Software Configuration Guide

PowerLogic ION Setup Meter Configuration Software Configuration Guide PowerLogic ION Setup Meter Configuration Software Configuration Guide 70002-0293-03 12/2010 Conventions Used in this Manual This section describes the symbols and terminology used in this guide. Symbols

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

INSTALLATION INSTRUCTIONS and BASIC SYSTEM CONFIGURATION

INSTALLATION INSTRUCTIONS and BASIC SYSTEM CONFIGURATION INSTALLATION INSTRUCTIONS and BASIC SYSTEM CONFIGURATION 200091-A 2/23 Contents 1. Warnings & Notes... 3 2. Installation of system to electrical cabinet or modular box... 3 3. Powering the system... 7

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

Diagnostics and Monitoring System WEB Tool 2. User Manual

Diagnostics and Monitoring System WEB Tool 2. User Manual Diagnostics and Monitoring System 2 (Translation of the original documentation) User Manual S/N: Valid from: 01.05.2012 Rev.: 2.0 2 Rev. 1.... 1 1.1 General information... 1 1.1.1 Equipment... 1 1.1.2

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with 8, 16, 24, 32, 40 and 48 signal inputs Status retention of inputs and sequence in case

More information

EviKontroll Silo. Monitor Your Grain Anytime, Anywhere

EviKontroll Silo. Monitor Your Grain Anytime, Anywhere C Grain temperature monitoring system Monitoring the temperature inside grain silos is the most important measure to assure the storage quality. EviKontroll Silo fully automatic temperature monitoring

More information

Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING. Manual

Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING. Manual Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING Manual Introduction The AK-SM 350 is a combined data collection and monitoring unit for use in refrigeration

More information

HTC-915-CONT. Heat-Trace Control system

HTC-915-CONT. Heat-Trace Control system Heat-Trace Control system Product overview The Raychem HTC-915 system is a compact, full-featured microprocessor-based single-point heat-trace controller. The HTC-915-CONT provides control and monitoring

More information

Fratech Multipath-IP

Fratech Multipath-IP Rev 2.0 (May 2013) Installer Manual 1 Current Part Numbers: Fratech Multipath-IP E-Link STU PCB & Accessory Kit only In Metal Enclosure with Power Supply 998325-PK 998325-XS Installer Manual This document

More information

CU 300 GRUNDFOS INSTRUCTIONS. Installation and operating instructions

CU 300 GRUNDFOS INSTRUCTIONS. Installation and operating instructions GRUNDFOS STRUCTIONS CU 300 Installation and operating instructions No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm Declaration of Conformity We Grundfos

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

MANUAL FOR PROFORT GSM/LAN DEVICES Ver MANUAL FOR PROFORT GSM/LAN DEVICES 3

MANUAL FOR PROFORT GSM/LAN DEVICES Ver MANUAL FOR PROFORT GSM/LAN DEVICES 3 MANUAL FOR PROFORT GSM/LAN DEVICES 1 MANUAL FOR PROFORT GSM/LAN DEVICES 3 1.1 SPECIFICATIONS 3 1.2 FUNCTIONS 5 1.3 DESCRIPTION 8 1.4 SYSTEM ILLUSTRATION 10 2 MOUNTING 11 2.1 PREPARE THE UNIT 11 2.2 ELECTRIC

More information

Smart Combiners Installation Guide. For Obvius A89DC-08 sensor modules

Smart Combiners Installation Guide. For Obvius A89DC-08 sensor modules For Obvius A89DC-08 sensor modules Introduction Large roof and ground arrays connect the panels into stings that are merged together in combiner boxes. Each string will typically consist of 10-15 panels

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint

More information

S F IT 6" / 8"HES. Quick Installation Guide. franklinwater.eu

S F IT 6 / 8HES. Quick Installation Guide. franklinwater.eu GB D S F IT 6" / 8"HES Quick Installation Guide franklinwater.eu Summary Page English 5-19 Deutsch 25-39 Svenska 44-60 French 63-81 Italian 84-101 GB 6" / 8"HES Quick Installation Guide franklinwater.eu

More information

Dew point set DS 400

Dew point set DS 400 set DS 400 Dew point set DS 400 for stationary dew point monitoring of refrigeration or adsorption dryers. The touch screen graphic display enables an intuitive operation and shows the progress of the

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-1343 5/06b INSTALLATION INSTRUCTIONS Original Issue Date: 8/03 Model: Automatic Transfer Switches Equipped with Series 1000 Programmable Controller Market: ATS Subject: Remote Annunciator Kits GM28938-KP1,

More information

Security designed for your lifestyle

Security designed for your lifestyle Security designed for your lifestyle The Paradox Insight : The Big Picture A single CAT5 or higher cable can be used to wire a single HD77 camera. Camera Detector Module HD 720p camera Quad PIR with auto

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

Operating Guide. ECL Comfort 210 / 296 / 310, application A247 / A Table of Contents

Operating Guide. ECL Comfort 210 / 296 / 310, application A247 / A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 6 2.1 Before you start.....................................................

More information

RACK MONITORING SYSTEM RAMOS Ultra

RACK MONITORING SYSTEM RAMOS Ultra version: 7-05-03 CONTEG DATASHEET COMPLEMENTARY SYSTEMS RACK MONITORING SYSTEM CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 79/4 40 00 Prague 4 Tel.: +40 6 9 8 Fax: +40 6 9 9 Production

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

SUPREMATouch. Modular Fire & Gas Detection System

SUPREMATouch. Modular Fire & Gas Detection System SUPREMATouch Modular Fire & Gas Detection System Fire & Gas Detection Solutions MSA permanent gas detection systems are used throughout the world to protect plant and personnel from hazardous gases in

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

IP & SMS Alarm Communicator

IP & SMS Alarm Communicator Models: WGSMSC You deserve to feel safe, secure & protected IP & SMS Alarm Communicator Quick Start Guide Thank you for purchasing a Watchguard IP & SMS Alarm Communicator This Quick Start Guide covers

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Phone: 040 807-0 Fax: 040 807-259 Alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC display

More information

Healthy. Atmosphere. for Pigs and Poultry. for a

Healthy. Atmosphere. for Pigs and Poultry. for a Healthy Atmosphere for Pigs and Poultry for a m e t s y s Your Climate ll requirements Alarm Energy Our new 3G product range for a healthy climate in stables for pigs and poultry! The 3G product range

More information

T4000 Security Communicator

T4000 Security Communicator Inner Range T4000 Security Communicator 1 T4000 Security Communicator by Inner Range P/N: 998530 / 998530NZ 998530LT (Lite Version) Installation & Operation Manual. Rev: 1.5 Inner Range Pty. Ltd. www.innerrange.com

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Bender Incorporated 700 Fox Chase, Coatesville PA 1930 Tel.: (800) 356-466 Fax: (610) 383-7100 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control function

More information

DELOMATIC 400, DM-400 HYDRO

DELOMATIC 400, DM-400 HYDRO Delomatic 400 HYDRO controller OPERATOR S MANUAL DELOMATIC 400, DM-400 HYDRO Functional description User interface Log books Alarm handling Document no.: 4189340880A SW version 1.0 or later Table of contents

More information

IndigoVision Alarm Panel. User Guide

IndigoVision Alarm Panel. User Guide IndigoVision Alarm Panel User Guide THIS MANUAL WAS CREATED ON 2/21/2017. DOCUMENT ID: IU-AP-MAN002-4 Legal considerations LAWS THAT CAN VARY FROM COUNTRY TO COUNTRY MAY PROHIBIT CAMERA SURVEILLANCE. PLEASE

More information

SACE PR021/K SIGNALLING UNIT

SACE PR021/K SIGNALLING UNIT SACE PR021/K SIGNALLING UNIT 1SDH000559R0002 L3016 1/52 EN CONTENTS 1. GENERAL INFORMATION...4 1.1. FOREWORD...4 1.2. APPLICABLE SCENARIOS...5 2. TECHNICAL SPECIFICATIONS...6 2.1. ELECTRICAL CHARACTERISTICS...6

More information

Remote alarm indicator and test combination MK2430

Remote alarm indicator and test combination MK2430 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Tel.: 040 807-0 Fax: 040 807-259 Remote alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC

More information

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction...4 2. Product Features...4 3. Package

More information

M1000 Alarm Annunciator

M1000 Alarm Annunciator Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D ASCO 5350 The ASCO 5350 ATS Remote Annunciator is listed under the Underwriter s Laboratories Standard UL-1008 for Automatic Transfer Switch accessories. This stand-alone device provides individual status

More information

ModBus DE-1 INSTALLATION AND USER MANUAL

ModBus DE-1 INSTALLATION AND USER MANUAL ModBus DE-1 INSTALLATION AND USER MANUAL INTESIS Software, SL Distributed by DURAN ELECTRONICA S.L Tomás Bretón 50 28045 MADRID, España duran@duranelectronica.com www.duranelectronica.com 2 2010 DURAN

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option Description of options Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M 4189340401D SW 1.4X.X Description of option Functional description DEIF A/S Parameter list DEIF A/S,

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Instruction Manual Model Backup Switch, 1 for 8

Instruction Manual Model Backup Switch, 1 for 8 Instruction Manual Model 2582-282 Backup Switch, 1 for 8 December 2011, Rev. 0 MODEL 2582 SWITCH CROSS TECHNOLOGIES INC. SWITCH ALARM PSA PSB ALARM OFFLINE ONLINE UNIT STATUS 1 2 3 4 5 6 7 8 BU PROT MODE

More information

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction... 3 2. Product Features... 3 3. Package Contents... 4 4. Board Configuration... 4 5. Before You Start... 5 6. Installing

More information

Corrigo E. Second generation which contains all applications and languages

Corrigo E. Second generation which contains all applications and languages revision 05 2009 Corrigo E Second generation which contains all applications and languages The controllers in the Corrigo E series are intended for applications within heating, boiler and ventilation control

More information

Operating manual. Condor Modular pump control CPSM

Operating manual. Condor Modular pump control CPSM Condor Status: 27.01.2011 Version: 900 160 - V1.2 GLP: HW 1.30 SW: V2.21 This documentation refers exclusively to the control unit and contains basic information that must be adhered to during installation,

More information

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 505 Grünberg Tel.: 060 807-0 Fax: 060 807-59 A-ISOMETER IRDH575 Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with

More information

PTE0705 Electric Fence Monitor

PTE0705 Electric Fence Monitor PTE0705 Electric Fence Monitor The JVA logo is a registered trademark of JVA Technologies. JVA Technologies. TABLE OF CONTENTS DESCRIPTION... 2 QUICK START GUIDE... 3 FEATURES... 4 EXPLANATION OF TERMS...

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS XXXXXXX-0 EN 1904 READ AND SAVE THESE INSTRUCTIONS BASIC-PLC CONTROLLER MANUAL For all Condair desiccant dryer with equipped with Basic- PLC valid from version: PLC-35/PLC-45 18.04.03 Dehumidification

More information

Memcom Emergency Telephone

Memcom Emergency Telephone Memcom Emergency Telephone Installation Guide Ref No. 450 900 (GB) Version 2 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based programming

More information

RS485 MODBUS Module 8AI

RS485 MODBUS Module 8AI Version 1.4 15/04/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL Installation and operation manual Table of contents Page 1. Supplied accessories and intended use... 1 2. General layout and setup of a system... 2 3. Installation...

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

Products no longer available

Products no longer available Technical data sheet MONICO-.. Turnkey automation station MONICO-.. Forms an efficient fire protection system together with the motorisation sets BF(G)24MP Completely wired controller in matching control

More information

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System MOBILE CALL GSM Alarm System GSM Alarm System System disarmed 11/26/2013 User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. CONTENTS

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

TE809-Ats Instructions Manual

TE809-Ats Instructions Manual TE809-Ats Instructions Manual Project: v2.0 PREFACE Thanking you for preference, TECNOELETTRA SRL hopes that the use of this equipment could be a reason of satisfaction. This manual is designed to put

More information

IRIS Touch Firmware Enhancements and Additions from Version to Version

IRIS Touch Firmware Enhancements and Additions from Version to Version Overview IRIS Touch Firmware Enhancements and Additions from Version 1.14.3 to Version 1.19.1 This document details enhancements to the feature set of the IRIS Touch from firmware Version 1.14.3 to Version

More information

Сontrol panel Contact GSM-9N

Сontrol panel Contact GSM-9N Сontrol panel Contact GSM-9N Data sheet Device identification number 2 1. General Information The Contact GSM-9N control panel (hereinafter referred to as the device) is designed for setting up security

More information

Labkotec Ice Detector

Labkotec Ice Detector Labkotec Ice Detector LID 3300IP Level and flow know-how since 1964 Benefits of using Ice Detector Stops wind turbine to prevent icethrow Safety first of all! Safety device Authorities / construction licence

More information

NU2 Smart Power Supply (SPS) Manual

NU2 Smart Power Supply (SPS) Manual GENERAL The Smart Power Supply (SPS) is an innovative Quad Output, field programmable power supply. Each of the four outputs can provide four Amps for a total of sixteen Amps in either 12VDC or 24VDC.

More information

SUPREMATouch. Modular Fire & Gas Detection System

SUPREMATouch. Modular Fire & Gas Detection System SUPREMATouch Modular Fire & Gas Detection System Tel: +44 (0)8 9388 Email: info@ Fire & Gas Detection Solutions MSA permanent gas detection systems are used throughout the world to protect plant and personnel

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

CAREL heatersteam Electric Element Steam Humidifiers

CAREL heatersteam Electric Element Steam Humidifiers Suggested Engineering Specifications Section 23 84 13 CAREL heatersteam Electric Element Steam Humidifiers 1. GENERAL SCOPE 1. Furnish and install as indicated on the drawings and plans, in-duct [space]

More information