Fire Safety Guidelines and Requirements CenturyLink Field and Event Center June 2015

Size: px
Start display at page:

Download "Fire Safety Guidelines and Requirements CenturyLink Field and Event Center June 2015"

Transcription

1 Fire Safety Guidelines and Requirements CenturyLink Field and Event Center June 2015 The Seattle Fire Department is required to review and enforce all issues relating to public safety in assembly occupancies in the City of Seattle. The authority for fire safety requirements resides in the Seattle Fire Code and the Seattle Building Code. Our goal is to attempt to maintain a philosophy of flexibility when dealing with event planners, with the knowledge that public safety issues are the Seattle Fire Department s primary concern. The purpose of this document is to: Provide guidelines for the operation of the Stadium and the Event Center Help planners of public assembly events with the permit process, including; Permit application Floor plan approval Issuance of needed permits. Before a public assembly event can take place in the City of Seattle, the three permit process items must be completed. Communication between the event planners, the Stadium/Exhibition Center and the Seattle Fire Department is crucial to the issuance of a permit and a successful and safe public event. Most public assembly occupancies are designed and built with minimal emergency exiting to maximize meeting and exhibit space. Therefore, the Seattle Fire Marshal s Office cannot allow for compromise on the size or amount of viable exits and aisles. When exits and aisles deviate from the standard SEC floor plans or there is a proposal to partially block or visually obscure mandated exits a written proposal must be submitted to the Fire Marshal or their representative. These proposals will be handled on a case by case basis and are subject to review prior to issuance or denial of a public assembly permit. Roles and Responsibilities: SEC Coordinator (Seattle Fire Department) is responsible for ensuring the event complies with the Seattle Fire Code or an acceptable alternative. Client Representative is responsible to the Client, the Fire Marshal, and the SEC. Contractor Representative is responsible to the Client, the Fire Marshal and the SEC. Fire Marshal is responsible to the public for all safety issues. Permitting Process: The Permit Application for Public Assembly, Permit Application Fee and floor plans need to be sent together as a package to: Seattle Fire Department Page 1 of 5

2 Attention: Permit Desk (2 nd Floor) rd Avenue South Seattle, WA The Fire Marshal or his/her representative reviews the floor plans. After review, floor plans will either be stamped approved or the required changes will be indicated. The SEC Coordinator or the Fire Marshal will communicate with the client or contractor on required plan revision(s). After floor plans have received final approval, the public assembly permit will be issued. The Fire Marshal will conduct a final walk-through of the show floor prior. This may occur prior to Doors, but also randomly during show hours. See page 5 for permit titles and fees. Points to consider during the permit process: 1. Booth and/or concert ticket sales cannot begin until the floor plans have been reviewed and approved by both the Fire Marshal and the SEC. 2. Floor plans must be submitted to the Fire Marshal at least 45 days before the first move-in day. (Suggest submitting floor plans as early as possible for review and approval.) There will be a late fee of 50% of the permit value added to the cost of the permit if the entire paperwork packet (plans, application, application fee) is NOT received by the Permit Section of the Fire Marshal s Office at least 30 days prior to the event date. 3. The Fire Marshal requires a floor plan drawing to scale along with the permit application. Drawings should indicate aisles, aisle widths, booths and exits for all occupied floor space. This shall include registration areas, espresso carts, giveaways, radio remotes, popular booths and/or personalities. Floor plan drawings must be 8.5 x 11. Larger sizes may be additionally provided to clarify detail. Remember to include displays outside the building. EXHIBITION HALL GUIDELINES SHOW FLOOR 1. A clear perimeter exit aisle of 12 feet must be maintained in all exhibit halls. 2. The West Hall, East Hall and Concourse hall have a minimum of five (5) straight East/West aisles. Perimeter aisles do not count in this East/West minimum. The minimum aisle width shall be 10 feet. Smaller East/West aisles may be allowed in some instances, but are considered an exception not the rule. 3. Both the main hall and garage/swing space must have a minimum of one (1) straight and continuous North/South cross aisle. The minimum aisle width shall be 15 feet. Page 2 of 5

3 4. The exit corridor leading from the mezzanine to the football stadium shall be a minimum of 12 feet. A minimum clear area of 15 feet shall be maintained in front of the entry/exit doors. 5. The storage of crates, cardboard boxes and fiber cases is not permitted in the facility except in designated and approved bone yards. 6. All fire hose cabinets, fire extinguishers, strobes and pull stations must be visible and kept clear and readily accessible during move-in, show days and move-out. 7. Any tent or covered structure over 100 square feet indoors requires a smoke detector and one fire extinguisher with a minimum UL classification of 2A 10BC. Any tent or covered structure over 1000 square feet indoors requires an automatic fire suppression system (i.e. automatic fire sprinklers) and will need to be wired into the CenturyLink Field Event Center s smoke alarm system. EXHIBIT HALL LOBBY AREA 1. Major attractions should not be located at the entrance to the exhibit space. i.e. espresso cards, giveaways, radio remotes, and popular booths or personalities. 2. All registration counters, kiosks and entry units must be indicated to scale on the submitted floor plans. 3. All meeting rooms are subject to maximum occupant load as dictated by the Seattle Fire Code. Meeting rooms with an occupant load greater than 50 persons require a minimum of two (2) exits from the room. SHOW FLOOR MISCELLANEOUS 1. All curtains, draperies, hangings and other decorative materials suspended from walls or ceilings must meet NFPA 701 or California State Fire Marshal standards for flame retardancy. The use of oilcloth, tarpaper, sisal paper, nylon, Orlon and certain other synthetic materials cannot be made flame resistant and their use is strictly prohibited. (An approved certificate verifying the flame retardancy of those materials required to meet the flame retardant criteria shall be readily available.) 2. Special effects permits are required for indoor and outdoor fireworks. Each of these effects will be subject to review and will be handled on a case by case basis. Permits are not required to use smoke machines or lasers. Note: Smoke machine usage must be communicated to the Fire Marshal s Office. Page 3 of 5

4 3. LPG (Propane) may be used in extremely limited quantities under permit. Contact the Fire Combustible storage is not allowed on the event floor. Combustible storage is specifically prohibited in dead spaces behind booth drape or in unsold areas. Cardboard must be removed from the event floor including empty cardboard boxes intended for repacking. Booth storage of literature, brochures and product is limited to full boxes that can be easily stored under tables in the booth and may not exceed one days supply. 5. Helium and Nitrogen tanks are not allowed on the event floor without prior approval of the Fire Marshal. Tanks must be properly labeled for contents and firmly secured in the upright position with valves protected against damage. 6. Indicate the location and size of Official Contractor Service Centers on exhibition floor plans. 7. Event planners requesting permission to mask off an area, block access to an exit or block exit visibility may in some cases be allowed to do so by adding illuminated exit signs and a double baffle in the drape. Prior approval from the Fire Marshal is required. It should not be assumed that this variance would always be allowed. These proposals will be evaluated on a case by case basis. Additional signs may be required for Fire Extinguisher or Fire Hose cabinets. DISPLAY VEHICLES and EQUIPMENT Display vehicles must be indicated on submitted floor plans and are subject to the following conditions: 1. The fuel load as determined by a working fuel gauge shall not exceed five gallons or ¼ tank, whichever is less. Vehicles with non-functioning fuel gauges will not be allowed in public assembly areas unless approved by the Fire Marshal. 2. Positive and negative battery cables must be disconnected and the ends covered with a non-conductive material such as electrical tape or rubber boots to prevent sparking. Disconnect switches may be use in lieu of with prior approval. 3. Fuel tank fill openings must be equipped with a suitable cap to prevent the escape of vapors. Additionally the cap must be either locking or taped shut to prevent tampering. 4. Fuel systems must not leak. 5. A set of keys to the vehicle must remain on the show site and available at all times together with complete information. This information must include the names and phone numbers of the vehicle owner and responsible party. Page 4 of 5

5 6. You must possess a valid fuel pass before entering building. This pass must be displayed in a visible location on the equipment or in the vehicle until the show opens. COOKING and OPEN FLAMES 1. Candles require an open flame permit. A single candle may be burned without a permit. 2. The use of Sterno does not require a permit. 3. Butane table top units do NOT require a permit, however fuel is limited to containers no larger than 10 ounces. One per unit with one spare. 4. Deep fat fryers are limited to a capacity one gallon. Capacities of more than one gallon must have a permit. A metal cover that fits snuggly over the fryer must be readily available. Have a U.L. rated K extinguisher must be visible, available and away from the hazard. 5. All cooking appliances must meet these requirements: Carry a nationally recognized listing. i.e. UL, FM, etc. Separated from the public by a minimum of four feet or have a protective shield ¼ inch thick, 18 inches high and border the front three sides. 6. A portable fire extinguisher with a minimum UL rating of 2A 40BC must be visible, available and away from the hazard in the cooking booth. The extinguisher must have been tested or purchased within one year as evidenced by a service tag or sales receipt. 7. All cooking is subject to the following (Cooking and other similar activities may require an additional permit): a. State and Local Health Codes. (RCW and URL s) b. City of Seattle Fire and Building Codes. c. Some cooking requires additional extinguishers. Consult with the Fire Marshal or his or her representative for requirements. d. This is a public facility and is subject to Washington State No Smoking Laws. Page 5 of 5

6 EXTENSION CORDS, PLUGS and LIGHTING 1. All extension cords must be a minimum of 14 gauge, 3 wire and grounded. Use ties or cable clamps when running cord Lightweight extension cords or zip cords are strictly not allowed 2. Power strips are approved for additional outlet plugs. Cube tabs are strictly not allowed Power strips can not be daisy chained 3. Cords, plugs and strips must have UL labeling 4. Lighting must be UL labeled and used consistent with their design. Page 6 of 5

Washington State Convention Center Fire Safety Guidelines

Washington State Convention Center Fire Safety Guidelines Washington State Convention Center Fire Safety Guidelines ROLE OF THE SEATTLE FIRE DEPARMENT A Seattle Fire Department (SFD) Public Assembly Permit is required for exhibits, registration areas, any proposed

More information

FIRE DEPARTMENT CONDITIONS BELLEVUE FESTIVAL OF THE ARTS Fire Retardant or Flame Retardant Treatment

FIRE DEPARTMENT CONDITIONS BELLEVUE FESTIVAL OF THE ARTS Fire Retardant or Flame Retardant Treatment FIRE DEPARTMENT CONDITIONS BELLEVUE FESTIVAL OF THE ARTS 2016 The Bellevue Fire Department would like to welcome you to this year s Bellevue Arts Museum Arts Fair. In order to ensure a safe and enjoyable

More information

Township of Upper Providence Office of the Fire Marshal

Township of Upper Providence Office of the Fire Marshal Township of Upper Providence Office of the Fire Marshal Convention Center Fire Safety Regulations 1286 Black Rock Road P.O. Box 406 Oaks, Pa 19456 9 610N933N9179 JULY 2010 REVISION www.uprovnmontco.org

More information

Dear Exhibitor, To assist in th. and safety issues that you may encounter with your booth.

Dear Exhibitor, To assist in th. and safety issues that you may encounter with your booth. Dear Exhibitor, The Phoenix Convention Center and the Phoenix Fire Department have partnered to assist you in both a safe and successful experience in our facility. To facilitate this, the Phoenix Convention

More information

FIREDEPARTMENT REGULATIONS AND GUIDELINES

FIREDEPARTMENT REGULATIONS AND GUIDELINES FIREDEPARTMENT REGULATIONS AND GUIDELINES FIRE DEPARTMENT REGULATIONS Safety, for our guests and vendors, is our number one priority at the Spokane Convention Center. Please familiarize yourself with the

More information

FIRE & SAFETY REGULATIONS (Updated )

FIRE & SAFETY REGULATIONS (Updated ) FIRE & SAFETY REGULATIONS (Updated 09.01.14) The following are the Los Angeles City Fire Department's minimum requirements for shows and exhibits in the LACC. No variance or alternate method of compliance

More information

ATTACHMENT B FIRE CODE REQUIREMENTS FOR EXHIBITS AND SPECIAL EVENTS

ATTACHMENT B FIRE CODE REQUIREMENTS FOR EXHIBITS AND SPECIAL EVENTS ATTACHMENT B FIRE CODE REQUIREMENTS FOR EXHIBITS AND SPECIAL EVENTS DALLAS FIRE-RESCUE DEPARTMENT Inspection and Life Safety Education Division Special Events Section 1551 Baylor Street, Suite 400, Dallas,

More information

PALM SPRINGS FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS, CONVENTIONS AND SPECIAL EVENT GATHERINGS BASED ON THE 2010 CALIFORNIA FIRE CODE

PALM SPRINGS FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS, CONVENTIONS AND SPECIAL EVENT GATHERINGS BASED ON THE 2010 CALIFORNIA FIRE CODE PALM SPRINGS FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS, CONVENTIONS AND SPECIAL EVENT GATHERINGS BASED ON THE 2010 CALIFORNIA FIRE CODE FIRE DEPARTMENT REGULATIONS For Additional Information

More information

All orders are governed by the GES Payment Policy and GES Terms & Conditions of Contract as specified in this Exhibitor Services Manual.

All orders are governed by the GES Payment Policy and GES Terms & Conditions of Contract as specified in this Exhibitor Services Manual. Fire Regulations G-8 All orders are governed by the GES Payment Policy and GES Terms & Conditions of Contract as specified in this Exhibitor Services Manual. Automechanika Chicago McCormick Place April

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD July 2017 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD SPECIAL EVENT PUBLIC ASSEMBLY PURPOSE This standard is applicable to any public event, exhibit space, booth, festival or any other similar

More information

Exhibits and Trade Shows Permit Application

Exhibits and Trade Shows Permit Application Applicant Information: Exhibits and Trade Shows Permit Application Organization: Name: First Last Application Date: Position or Title: Address: Street Address / / City State Zip Phone: Primary Number Other

More information

City of Leduc Fire Services Indoor Special Event Requirements

City of Leduc Fire Services Indoor Special Event Requirements City of Leduc Fire Services Indoor Special Event Requirements 0 Table of Contents Contents Definitions... 2 Indoor Special Event... 3 Special Event Approval... 3 Event Information Sheet Requirements...

More information

Calgary Fire Department Indoor Special Event Requirements. August calgary.ca /fire call

Calgary Fire Department Indoor Special Event Requirements. August calgary.ca /fire call Calgary Fire Department Indoor Special Event Requirements August 2011 calgary.ca /fire call 3-1-1 1 CALGARY FIRE DEPARTMENT INDOOR SPECIAL EVENTS REQUIREMENTS The purpose of this document is to provide

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD

FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD Revised 1/1/17 The Fire Department has a vested interest to ensure the fire and life safety of all events and activities within the city. The

More information

EXCELSIOR FIRE DISTRICT

EXCELSIOR FIRE DISTRICT EXCELSIOR FIRE DISTRICT Minnesota State Fire Code and the Excelsior Fire District Inspection Fire Safety & Code Requirements TENTS OVER 200 SQUARE FEET The following codes set fourth by the Minnesota State

More information

Minimum Information Required to Process your Special Occasion Application. Parking area Access to site

Minimum Information Required to Process your Special Occasion Application. Parking area Access to site FIRE CODE PERMIT SPECIAL OCCASION APPLICATION YAKIMA COUNTY FIRE MARSHAL S OFFICE International Fire Code 128 N. 2nd Street, 4th floor, Yakima, WA 98901 - (509) 574-2300 FORM: BFS45A 6/5/18 Minimum Information

More information

SALT LAKE OFF-ROAD EXPO 2018 Sponsor Information Friday-Saturday April 27 th & 28 th 2018 South Towne Expo Center Hall 5 Off-Roaders Unite!

SALT LAKE OFF-ROAD EXPO 2018 Sponsor Information Friday-Saturday April 27 th & 28 th 2018 South Towne Expo Center Hall 5 Off-Roaders Unite! SALT LAKE OFF-ROAD EXPO 2018 Sponsor Information Friday-Saturday April 27 th & 28 th 2018 South Towne Expo Center Hall 5 Off-Roaders Unite! Mission Statement: Markets Targeted: Salt Lake Off-Road Expo

More information

Fire and Life Safety Requirements San Mateo City Special Events

Fire and Life Safety Requirements San Mateo City Special Events San Mateo City Special Events Fire and Life Safety Requirements cket VERSION 1.0 12/2015 Fire and Life Safety Requirements San Mateo City Special Events The San Mateo Fire Department has a vested interest

More information

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS Last Updated: April 28, 2008 FIRE REGULATIONS The purpose of fire regulations is to maintain an acceptable level of fire safety within CGS facilities.

More information

REQUIREMENTS FOR TENTS, CANOPIES & MEMBRANE STRUCTURES

REQUIREMENTS FOR TENTS, CANOPIES & MEMBRANE STRUCTURES Pierce County Department of Emergency Management LOWELL PORTER Director Fire Prevention Bureau WARNER WEBB 2401 South 35 th Street Room 2 Fire Marshal Tacoma, Washington 98409-7494 (253) 798-7179 FAX (253)

More information

REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES

REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES DATE: January 6, 2014 INFORMATION BULLETIN: F-14-002 APPROVED BY: W. Schellhous 2013 California Fire Code (CFC) and Riverside Municipal

More information

STANDARD DETAILS & SPECIFICATIONS Spec No _SI _ Rev. Date 10/20/11

STANDARD DETAILS & SPECIFICATIONS Spec No _SI _ Rev. Date 10/20/11 EST. 1947 STANDARD DETAILS & SPECIFICATIONS Spec No _SI- - - 4_ Rev. Date 10/20/11 SUBJECT: HAUNTED HOUSES/GHOST WALKS Eff. Date 08/23/90 Approved By Page 1 of 6 SCOPE These regulations shall apply to

More information

CITY OF OKLAHOMA CITY SPECIAL EVENT REQUIREMENTS Revised January, 2011

CITY OF OKLAHOMA CITY SPECIAL EVENT REQUIREMENTS Revised January, 2011 CITY OF OKLAHOMA CITY SPECIAL EVENT REQUIREMENTS Revised January, 2011 No exhibit, concert, fair, festival or trade show shall occur in any structure in the City of Oklahoma City, without first having

More information

FIRE MARSHAL REGULATIONS

FIRE MARSHAL REGULATIONS Cooking Information A Cooking/Open Flame Agreement form must be obtained prior to any on-site cooking, and/or food warming activities on the premises. Cooking/Open Flame Agreement forms can be obtained

More information

TENTS AND TEMPORARY MEMBRANE STRUCTURES PERMIT PROCEDURE

TENTS AND TEMPORARY MEMBRANE STRUCTURES PERMIT PROCEDURE SCOPE Revised 1/1/17 These provisions shall apply to any tent or temporary membrane structure having an area in excess of 400 square feet. The following information shall be submitted with each permit

More information

All temporary special events held within the City of Orlando must be approved and inspected by the Orlando Fire Department prior to holding the event.

All temporary special events held within the City of Orlando must be approved and inspected by the Orlando Fire Department prior to holding the event. December 15, 2005 Dear Event Planner: All temporary special events held within the City of Orlando must be approved and inspected by the Orlando Fire Department prior to holding the event. Applications

More information

PLACES OF ASSEMBLY CHAPTER 17

PLACES OF ASSEMBLY CHAPTER 17 CHAPTER 17 PLACES OF ASSEMBLY SECTION 1701 GENERAL 1701.1 Scope. Places of assembly, including trade shows and exhibitions, outdoor assembly events, outdoors mazes, special amusement buildings and special

More information

Orange County Fire Rescue Department Office of the Fire Marshal 7079 University Blvd. Winter Park, FL Phone: Fax:

Orange County Fire Rescue Department Office of the Fire Marshal 7079 University Blvd. Winter Park, FL Phone: Fax: Office of the Fire Marshal 7079 University Blvd. Winter Park, FL 32792 Phone: 407-836-0004 - Fax: 407-836-8310 Trade Show & Conventions Permit Application Process With the recent upgrade to our Mobile

More information

4. Distances to property line, buildings, other tents, parked vehicles and engines;

4. Distances to property line, buildings, other tents, parked vehicles and engines; Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) Tent Requirements SafetyNet #: 554 Tent permit applications SHALL include all of the following before plans will be approved.

More information

FIRE SAFETY GUIDELINES

FIRE SAFETY GUIDELINES FIRE SAFETY GUIDELINES Assembly Events PRINCE WILLIAM COUNTY FIRE MARSHAL S OFFICE 5 County Complex Ct Prince William, Virginia 22192 TELEPHONE: 703-792-6360 The following fire safety guidelines have been

More information

FOOD PREPARATION WITHIN EXHIBITS

FOOD PREPARATION WITHIN EXHIBITS FOOD PREPARATION WITHIN EXHIBITS Whenever food is prepared within an exhibit, an Application for Food Preparation within Exhibits form should be completed and forwarded to your Convention Services Manager

More information

FACILITY REGULATIONS

FACILITY REGULATIONS FACILITY REGULATIONS (Excerpt from Service Ordering Guide) Animals and Pets Domestic animals: If you plan to use a domestic animal (i.e., cat or dog) in your exhibit, be sure to contact your Show Manager

More information

30 DAY TEMPORARY TENT APPLICATION ON EXISTING COMMERCIAL PROPERTY

30 DAY TEMPORARY TENT APPLICATION ON EXISTING COMMERCIAL PROPERTY AP # Permit # Cost Revised 12/31/17 Page 1 of 2 Check # Receipt # 30 DAY TEMPORARY TENT APPLICATION ON EXISTING COMMERCIAL PROPERTY 6 TH EDITION (2017) OF THE FLORIDA BUILDING CODE IS IN EFFECT THE FLORIDA

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

SAFETY GUIDELINES INDIANA STATE FAIRGROUNDS & EVENT CENTER. Fairgrounds Security:

SAFETY GUIDELINES INDIANA STATE FAIRGROUNDS & EVENT CENTER. Fairgrounds Security: SAFETY GUIDELINES INDIANA STATE FAIRGROUNDS & EVENT CENTER Fire code, life safety, permits and variance information Updated January 2016 Fairgrounds Security: 317-927-7520 All information subject to change

More information

FIRE DEPARTMENT PERMIT GUIDELINES

FIRE DEPARTMENT PERMIT GUIDELINES FIRE DEPARTMENT PERMIT GUIDELINES SPECIAL EVENT PUBLIC ASSEMBLY (EACH EVENT) The Special Event Assembly Permit is applicable to any public event, exhibit space, booth, festival or any other similar event

More information

Outdoor Festival and Special Event Guidelines

Outdoor Festival and Special Event Guidelines Outdoor Festival and Special Event Guidelines Updated January 2016 Arvada Fire Protection District Community Risk Reduction Division If you have any questions or comments regarding the information contained

More information

comprised the facility Cables Candles be placed

comprised the facility Cables Candles be placed Overall Fire Safety Regulations Floor plans, exhibits, and decorative materials must meet thee requirements of the Code of Massachusetts Regulations 780 CMR EIGHT EDITION (Building Code). The 8th edition

More information

Tents and Temporary Membrane Structures Packet

Tents and Temporary Membrane Structures Packet Tents and Temporary Membrane Structures Packet Tents and Temporary Membrane Structures Permit Procedure VERSION 1.0 12/2015 SCOPE: These provisions shall apply to any tent or temporary membrane structure

More information

Note: The event coordinator is responsible for compliance of all regulations.

Note: The event coordinator is responsible for compliance of all regulations. Food Booth and Vendor Regulations SafetyNet #: 555 A signed copy of the Food Booth and Vendor Regulations Agreement Form [1] shall be posted in the structure and signed by the vendor. By signing this form

More information

Note: The event coordinator is responsible for compliance of all regulations.

Note: The event coordinator is responsible for compliance of all regulations. Food Booth and Vendor Regulations FIRENETS March 2000 Revised March 2016 Introduction Vendors invited to participate in events sponsored by various organizations on the UC Davis campus are expected to

More information

Township of Upper Providence Office of the Fire Marshal

Township of Upper Providence Office of the Fire Marshal Township of Upper Providence Office of the Fire Marshal Special Event Guide for Show Exhibitors 1 2010 REVISION THIS PAGE INTENTIONALLY LEFT BLANK 2 2010 REVISION TOWNSHIP OF UPPER PROVIDENCE 1286 BLACK

More information

VENUE (LACC) GUIDELINES

VENUE (LACC) GUIDELINES VENUE (LACC) GUIDELINES FIRE & SAFETY REGULATIONS (Updated 09.01.14) The following are the Los Angeles City Fire Department's minimum requirements for shows and exhibits in the LACC. No variance or alternate

More information

SafetyNet FIRE MARSHAL S OFFICE. Food Booth and Vendor Regulations

SafetyNet FIRE MARSHAL S OFFICE. Food Booth and Vendor Regulations UC Davis Health Fire Marshal s Office 4800 2nd Ave, #1200 Sacramento, CA 95817 (916) 734-3036 hs-fireprevention@ucdavis.edu FIRE MARSHAL S OFFICE Food Booth and Vendor Regulations Introduction Vendors

More information

McCormick Place Fire Safety Regulations

McCormick Place Fire Safety Regulations CANDLES AND OTHER OPEN FLAME DISPLAYS Any open flame devices used for illumination or decoration, such as candles, gelled alcohol fuel fire bowls, firepots or fireplaces must comply with the following:

More information

FACILITY REGULATIONS

FACILITY REGULATIONS FACILITY REGULATIONS Animals and Pets Domestic animals: If you plan to use a domestic animal (i.e., cat or dog) in your exhibit, be sure to contact your Show Manager for approval. An insurance disclaimer

More information

FIRE PROTECTION INTRODUCTION

FIRE PROTECTION INTRODUCTION SECTION IV. Fire/Life Safety Chapter 1. Fire Protection Revision Date 11/19/02 Review Date 01/2007 FIRE PROTECTION INTRODUCTION PURPOSE It is the policy of Duke University to take all possible steps to

More information

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us

More information

Tents and Temporary Membrane Structures Permit Procedure

Tents and Temporary Membrane Structures Permit Procedure FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1040 E. Hillsdale Blvd. Foster City, CA 94404 (650) 522-7940 FAX: (650) 522-7941 Tents and Temporary Membrane Structures

More information

Policies - Building Rules and Regulations

Policies - Building Rules and Regulations Policies - Building Rules and Regulations The following regulations will be enforced during KEC events. It is your responsibility to inform your exhibitors, attendees and service contractors of these regulations.

More information

FIRE PREVENTION EXHIBIT GUIDELINES

FIRE PREVENTION EXHIBIT GUIDELINES FIRE PREVENTION EXHIBIT GUIDELINES Exhibit booth construction shall meet all building requirements. All means of entrance and exit must be clear and free from obstruction at all times. No storage of any

More information

UC Irvine Environmental Health & Safety TITLE: Special Events Program

UC Irvine Environmental Health & Safety TITLE: Special Events Program SECTION: UC Irvine Environmental Health & Safety TITLE: Special Events Program INITIATOR: Steven Eros REVISION DATE September 14, 2011 1. Program Description 2. Scope 3. Definitions 4. Responsibilities

More information

Temporary Haunted Houses

Temporary Haunted Houses Moreno Valley Fire Prevention Bureau Temporary Haunted Houses Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 5, 2017 Temporary Haunted Houses PURPOSE This guide is intended to provide

More information

NATURAL/LP GAS, COOKING, OPEN FLAME, HEAT PRODUCING DEVICE AGREEMENT FORM

NATURAL/LP GAS, COOKING, OPEN FLAME, HEAT PRODUCING DEVICE AGREEMENT FORM EVENT: IAAPA Attractions Expo 2018 BOOTH #: NATURAL/LP GAS, COOKING, OPEN FLAME, HEAT PRODUCING DEVICE AGREEMENT FORM EXHIBITING COMPANY: ORDER CONTACT NAME: I AM: THE EXHIBITOR PHONE: FAX: AN EAC/I&D:

More information

Clackamas Fire District #1 Self Inspection Program. Oregon Fire Code (OFC)

Clackamas Fire District #1 Self Inspection Program. Oregon Fire Code (OFC) Clackamas Fire District #1 Self Inspection Program Oregon Fire Code (OFC) Access Access No parking in the fire access lanes at any time. Even if they are not painted red. An unobstructed width of not less

More information

REQUIREMENTS FOR EVENTS AND TEMPORARY STANDS AT FAIRS AND SHOWS

REQUIREMENTS FOR EVENTS AND TEMPORARY STANDS AT FAIRS AND SHOWS Central Pierce Fire & Rescue Fire Prevention Division 902 7 th Street NW Puyallup, WA 98371 253.538.6402 office 253.538.6486 fax FIRE AND LIFE SAFETY REQUIREMENTS REQUIREMENTS FOR EVENTS AND TEMPORARY

More information

DEPARTMENT OF FIRE AND EMERGENCY SERVICES

DEPARTMENT OF FIRE AND EMERGENCY SERVICES MASHANTUCKET PEQUOT TRIBAL NATION DEPARTMENT OF FIRE AND EMERGENCY SERVICES A Guide to SAFE EXHIBITS, EXPOSITIONS, EVENTS and DECORATIONS PREVENTION IS OUR INTENTION 0 Table of Contents Introduction:.

More information

South Elgin & Countryside Fire Protection District

South Elgin & Countryside Fire Protection District MARY VAN WINKLE President RONALD R. BOHLMAN Secretary JEFFREY A. SPEYERS Treasurer South Elgin & Countryside Fire Protection District 150 WEST STATE STREET SOUTH ELGIN, ILLINOIS 60177 Business Phone (847)

More information

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION 5609 is amended, to read as follows, with the entire section being an addition to the Fire Code: SECTION 5609. FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

More information

MULTI-LEVEL & COVERED BOOTH CONDITIONS

MULTI-LEVEL & COVERED BOOTH CONDITIONS MULTI-LEVEL & COVERED BOOTH CONDITIONS Covered Booth Definition To place something over or upon an exhibit or portion of an exhibit (e.g., roof, ceiling, tenting, lattice, fabric, plastic) to cover the

More information

EVERGREEN RECREATIONAL VEHICLE SHOW SEPTEMBER 29, 30, OCTOBER 1, Exhibitor Information Balance of contract due before move-in

EVERGREEN RECREATIONAL VEHICLE SHOW SEPTEMBER 29, 30, OCTOBER 1, Exhibitor Information Balance of contract due before move-in EVERGREEN RECREATIONAL VEHICLE SHOW SEPTEMBER 29, 30, OCTOBER 1, 2017 PRODUCED BY WESTLAKE PROMOTION INC. Exhibitor Information Balance of contract due before move-in September 29, 10-6pm September 30,

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.6.13 Effective Date: Revision Date: TITLE: SCOPE: EXHIBITS

More information

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE Summary Guadalupe County requirements for the Permit Issuance and safe operation of a Temporary Special Amusement Occupancy. PURPOSE To

More information

General Festival Conditions & Temporary Use of Tents Conditions of Approval

General Festival Conditions & Temporary Use of Tents Conditions of Approval COSUMNES FIRE DEPARTMENT 10573 East Stockton Blvd. Elk Grove, CA 95624 (916) 405-7100 Fax (916) 685-6622 www.yourcsd.com General Festival Conditions & Temporary Use of Tents Conditions of Approval Scope:

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU TENANT IMPROVEMENT GROUP A FIRE PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU TENANT IMPROVEMENT GROUP A FIRE PLAN REVIEW CHECKLIST INFORMATION CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU TENANT IMPROVEMENT GROUP A FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: PROJECT ADDRESS:

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

MUST BE APPROVED IN ADVANCE

MUST BE APPROVED IN ADVANCE Fire Safety Reply Event: Complete and return by: A copy of the Fire Regulations for exhibitors is provided in this manual. Please review the regulations to ensure that your exhibit meets the Ontario Building

More information

Fire Regulations for Exhibitors

Fire Regulations for Exhibitors The purpose of these requirements is to maintain an acceptable level of fire safety within the Metro Toronto Convention Centre. The fire protection systems built into the Convention Centre have been designed

More information

EXHIBITION HALL BOOTH GUIDELINES

EXHIBITION HALL BOOTH GUIDELINES EXHIBITION HALL BOOTH GUIDELINES Questions? Contact: Skip Haile Senior Operations Manager E: Shaile@reedexpo.com P: 203-840-5912 LIGHTS + SOUNDS Speakers and lights should be positioned so as to direct

More information

Fire and Life Safety Review Form

Fire and Life Safety Review Form Exits/Egress Fire and Life Safety Review Form 1. Doors shall swing in the direction of egress travel where serving and occupancy load of 50 or more. IFC 1010.1.2.1 2. Egress shall be readily openable from

More information

Fire Evacuation Plan Davidge Hall. UMB POLICE or

Fire Evacuation Plan Davidge Hall. UMB POLICE or UMB POLICE - 711 or 410-706-3333 If you discover fire, smoke, or excessive heat inside your building, immediately: 1. Activate fire alarm by pulling manual fire alarm pull station (located near exits)

More information

SALEM RECREATIONAL VEHICLE SHOW OCTOBER 12, 13, 14, 15, Exhibitor Information Balance of all contracts due before move-in

SALEM RECREATIONAL VEHICLE SHOW OCTOBER 12, 13, 14, 15, Exhibitor Information Balance of all contracts due before move-in SALEM RECREATIONAL VEHICLE SHOW OCTOBER 12, 13, 14, 15, 2017 PRODUCED BY WESTLAKE PROMOTION INC. Exhibitor Information Balance of all contracts due before move-in October 12, 10-7pm October 13, 10-7pm

More information

City of Cleveland. Division of Fire Fire Prevention Bureau 1645 Superior Avenue Cleveland, Ohio Standard Operating Procedure 18

City of Cleveland. Division of Fire Fire Prevention Bureau 1645 Superior Avenue Cleveland, Ohio Standard Operating Procedure 18 City of Cleveland Division of Fire Fire Prevention Bureau 1645 Superior Avenue Cleveland, Ohio 44114 216.664.6664 Standard Operating Procedure 18 Cleveland Fire Prevention Fire Safety Regulations for Displays

More information

OCFEC Fire Marshal Summary Report

OCFEC Fire Marshal Summary Report OCFEC Fire Marshal Summary Report Fire Marshal report (Correction Notices received on 6/1/2018) OC FAIR & EVENT CENTER Maintenance Restrooms 1. CCR Title 19 Section 3.28 Plans and Specifications : Submit

More information

Narrative Reports As Regulated by 780 CMR, Section 903.0

Narrative Reports As Regulated by 780 CMR, Section 903.0 EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for

More information

Canby Fire District 221 S. Pine Street Canby, OR97013 Bus Fax Fire Marshal, Todd Gary

Canby Fire District 221 S. Pine Street Canby, OR97013 Bus Fax Fire Marshal, Todd Gary Canby Fire District 221 S. Pine Street Canby, OR97013 Bus. 503-266-5851 Fax 503-266-1320 Fire Marshal, Todd Gary 971-563-7359 Fire and Life Safety Requirements: The following requirements apply to all

More information

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225. Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.1) House Name Date Address Inspector(s) No. of Residents

More information

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1. EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-003 EFFECTIVE 06-03-2009 PURPOSE To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified

More information

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES OFFICE OF THE FIRE MARSHAL Worcester County GOVERNMENT CENTER - ONE WEST MARKET STREET - ROOM 1003 SNOW HILL, MARYLAND 21863-1194 TEL: 410-632-5666 FAX: 410-632-5664 GUIDELINES FOR INSPECTING GROUND BASED

More information

Fire/Life Safety Policy

Fire/Life Safety Policy Fire/Life Safety Policy On Campus Student Housing A. Purpose The University supports and maintains a strong commitment to the safety and health of each student living in On Campus Student Housing. The

More information

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: From: Subject: Whom It May Concern Carl Ray Austerman, Fire Marshal Contractor s Guide Welcome to the Glendale Fire Department s Contractors Guide. This

More information

2017 Annual Fire Safety Report

2017 Annual Fire Safety Report 2017 Annual Fire Safety Report King University Security Department Parks Hall 1350 King College Road Bristol, Tennessee 37620 Telephone 423-652-4333 Fax 423-652-6338 Page 1 of 5 Fire Safety The King University

More information

Level I Chapter 1 Worksheet

Level I Chapter 1 Worksheet Chapter 1 Worksheet 1. When the present code requires certain safety to life requirements for existing buildings, those requirements shall. a. be void b. apply c. be approved d. be grand-fathered 2. The

More information

Fire Evacuation Plan Bressler Research Building. UMB POLICE or

Fire Evacuation Plan Bressler Research Building. UMB POLICE or UMB POLICE - 711 or 410-706-3333 If you discover fire, smoke, or excessive heat inside your building, immediately: 1. Activate fire alarm by pulling manual fire alarm pull station (located near exits)

More information

SEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS

SEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS CITY OF SEMINOLE BUILDING DEPARTEMENT/FIRE DEPARTMENT 9199 113 th Street N. SEMINOLE, FL 33772 Phone: (727) 392-1966 - FAX (727) 319-6583 NO SMOKING UNDER THE TENT(S) Tents may be erected in any zoning

More information

Fire Evacuation Plan Health Sciences & Human Services Library. UMB POLICE or

Fire Evacuation Plan Health Sciences & Human Services Library. UMB POLICE or UMB POLICE - 711 or 410-706-3333 If you discover fire, smoke, or excessive heat inside your building, immediately: 1. Activate fire alarm by pulling manual fire alarm pull station (located near exits)

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-002 EFFECTIVE 05-27-2009 PURPOSE: To define the requirements for a License. To facilitate the quick application and review of new or changed

More information

School Fire Safety Checklist

School Fire Safety Checklist Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights

More information

Safety Manual Section 7 Fire/Life Safety

Safety Manual Section 7 Fire/Life Safety 7. FIRE/LIFE SAFETY The following sections provide fire/life safety guidelines and procedures. This section covers the following topics: Topic Page 7.1 General... 7-2 A. The Effects of a Fire... 7-2 B.

More information

West Chester Fire Dept. Fire Code Maintenance Handbook. Fire Prevention Saves Lives and Property

West Chester Fire Dept. Fire Code Maintenance Handbook. Fire Prevention Saves Lives and Property Fire Code Maintenance Handbook Fire Prevention Saves Lives and Property 8/10/2006 Our Mission The West Chester Fire Department Loss Prevention Bureau is committed to the safety of its firefighters, and

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

3. Aerosols It is permissible to exhibit one pressurized container, not exceeding one-pint capacity of each product classified as flammable liquid.

3. Aerosols It is permissible to exhibit one pressurized container, not exceeding one-pint capacity of each product classified as flammable liquid. FIRE REGULATIONS SAFETY REGULATIONS The Calgary Fire Prevention Bureau and the Alberta Occupational Health and Safety Board in conjunction with Calgary Stampede Park require the adherence to safety requirements

More information

FACT SHEET Program: Event Fire Safety

FACT SHEET Program: Event Fire Safety FIRE AND LIFE SAFETY GUIDELINES FOR EVENTS INTRODUCTION The purpose of this fact sheet is to provide information for a safe environment for events and insure compliance with fire safety standards and regulatory

More information

COMPLIANCE WITH THIS PUBLICATION IS MANDATORY

COMPLIANCE WITH THIS PUBLICATION IS MANDATORY BY ORDER OF THE SUPERINTENDENT HQ UNITED STATES AIR FORCE ACADEMY INSTRUCTION 32-2001 9 APRIL 2014 Civil Engineering FIRE PREVENTION PRACTICES AND FIRE PROTECTION ENGINEERING STANDARDS COMPLIANCE WITH

More information

Educational Occupancies

Educational Occupancies ducational Occupancies ducational () Occupancies are defined as: the use of a building or structure, or portion thereof, by more than six or more persons at any one time for educational purposes through

More information

Convention Center Rules & Regulations

Convention Center Rules & Regulations Mandalay Bay Convention Center Level 1 Bayside E&F Las Vegas, NV Convention Center Rules & Regulations AMERICAN DISABILITIES ACT (ADA) The Mandalay Bay Convention Center was designed and constructed to

More information

UNIVERSITY OF RICHMOND HOUSING FIRE SAFETY POLICY

UNIVERSITY OF RICHMOND HOUSING FIRE SAFETY POLICY UNIVERSITY OF RICHMOND HOUSING FIRE SAFETY POLICY SFTY 2 May, 2002 Revised March, 2003 Revised August, 2004 Revised July, 2005 Revised March, 2006 Revised June, 2007 Revised April, 2008 Revised May, 2009

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Fire Prevention Plan. California State University, Chico

Fire Prevention Plan. California State University, Chico California State University, Chico Department of Environmental Health and Safety May 2016 TABLE OF CONTENTS Section Page 1.0 Purpose... 1-1 2.0 Introduction... 2-1 3.0 Responsibilities... 3-1 4.0 Fire

More information