1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time.

Size: px
Start display at page:

Download "1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time."

Transcription

1 Sprinkler 1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. 2. Does the annual sprinkler head inspection have to be done by a licensed technician vs. facility staff? The sprinkler head inspection can be completed by facility staff. The key will be the identification and documentation that each sprinkler head has been inspected. 3. What is the frequency of the sprinkler internal inspection? NFPA requirements have been strengthened over the years for the inspection, testing and maintenance of sprinkler systems. NFPA adopted a code requiring that an internal inspection of piping be conducted every 5 years, or when conditions indicate the need for an internal inspection. This type of inspection may identify microbiologically influenced corrosion (MIC), rust, or slime that may obstruct the piping and compromise the system. If the facility has not done an inspection previously, then the first one is due by July 5, 2021, otherwise it is due 5 years since the last one completed. 4. What are the sprinkler testing annual inspection intervals? Sprinkler head professional inspection criteria is below. The facility is required to test 1% or 4 heads whichever is greater at the following intervals: a. Dry heads 10 years b. Quick response 20 years c. Standard response 50 years. Non-Hospital Grade Receptacle Testing 1. For electrical receptacles, does the inspection only apply to resident rooms or does it cover all plugs in the building? No, it only applies to receptacles within 6 of the patient s bed in the patient s room. 2. Is there a form for the electrical testing? Yes, there is a receptacle testing form attached to this Q&A. 3. Do the receptacles have to be labeled? No, but it is the recommended way to individually identify each for the inspection and testing documentation. 4. Where do we find the tool to measure receptacle retention? Electrical or internet suppliers such as granger.com or amazon.com.

2 Hazardous Spaces How do you determine if the load of a room exceeds capacity and needs a closer to avoid a K-29 (K 321)? This is a very subjective standard, but any room that appears to have a load that exceeds the facility design would be considered hazardous storage if the room is generally 50 sq. ft. or larger. The code reference is LSC 18/ , which for new facilities requires a 1-hr separation and for existing facilities requires separation that resists the passage of smoke. In both new and existing facilities there needs to be self-closing or automatic closing doors to hazardous areas including: a. Combustible Storage > 50 sq. ft b. Laundries > 100 sq. ft c. Boiler Room d. Repair, Maintenance & Paint Shops e. Trash Collection Rooms > 64 gallons f. Soiled Linen Rooms > 64 gallons Fire and Smoke Door Inspection 1. Does this training make us qualified to do our own door inspection? Yes, in most cases. The ability to be qualified is a combination of experience and training. This training along with being an experienced Facility/Maintenance Manager is adequate to perform the door inspection. NFPA 80 allows for individuals on the facility staff to perform this function if they are performed by individuals with knowledge and understanding.. 2. What about scrapes from wheel chairs? Can we cover it up with protective barrier (plastic or metal)? Damage on doors will be subjective. Scrapes should not be considered non-compliance as long as they are superficial. Yes, plates may be installed on smoke doors and for fire doors; check with manufacturer or door retailer on permitted in-field modifications. 3. Regarding fire and smoke door seals: is there a specification that must be met or can we get the seals at Ace Hardware for instance? Check with door retailers on appropriate gasketing/seals for smoke and fire doors. 4. What if there is a label indicating UL certification but not fire rated with hour rating? If this is discovered the door would not be considered fire rated labeled door. Each fire rated labeled door will indicate the amount of time the door is rated.

3 5. Do resident room doors that are not fire rated need to be inspected, and do we have to inspect restroom door a joining resident rooms? No, these are not a required door to be inspected and tested. The fire/smoke door inspection requirement Life Safety Code, NFPA 101 Section requires all fire and smoke doors to be inspected and tested, including: a. Fire rated labeled doors b. Doors in exit enclosures - typically stairwells and exit passageways c. Doors in smoke barriers d. Doors in other fire resistance rated walls such as hazardous areas and fire pump enclosures 6. The gap between the door and the floor is as follows: a. Fire rated and labeled doors ¾ b. Non-fire rated doors is 1 7. What is the door inspection regulation for an assistant living facility? The Ohio Fire Code does not require this inspection for Residential Care Facilities. 8. Can you use astragal on the door? Yes, in existing facilities with older door assemblies in with the two doors rely on each other to function there must be a coordinator and astragal which manages the two doors with one appropriately closing first. 9. Would it be permissible to have wood doors with a mail pocket screwed to the door? Yes, no, maybe It really depends on the door s use and whether it is fire rated and labeled or not. If it is a simple door which is not fire rated labeled then it may be permissible so long as it does not affect the door s function or the ability for the door to resist the passage of smoke. If the door is fire rated/labeled then this would likely not be permissible. 10. What if door hardware does not have a label on it? I am unsure how the state intends to determine the UL rating. Often obtaining the as built plans will provide you with the documentation regarding the fire door hardware. 11. Is a piano hinge acceptable? The requirement for fire rated doors is ball-bearing hinges that are UL rated. Need to check with the door retailer to see if there are appropriate piano hinge for the door installation. 12. I was informed by door repair company that if only one door of double doors is damaged that both door would have to be replaced. That may or may not be accurate but first consider the door s function when determining whether it can be repaired. Also clarify the nature of the damage and research if it can be repaired before concluding that both have to be replaced. 13. Is there any grandfathering of the door requirements? No, the requirements are applied for all doors in new and existing healthcare facilities.

4 Other 1. Will there be a webinar on CO2 detectors for a nursing facility? It is anticipated that CO2 protection will be required later this year as part of revisions to NH licensure. Education will be provided at that time. 2. During the weekly generator inspection does the generator have to be run? No, the weekly requirement is for a visual inspection of all of the parts of the generator, fuel level, oil level and battery. An example of a weekly inspection is attached. 3. Is there an example of a NFPA 99 Risk Assessment? Yes, the one developed by OHCA is attached. 4. How do you document an emergency light test when your lights are hard wired into the generator system? There is no requirement for emergency lighting devices to be tested monthly. Only those that have a battery in them are required to be tested 30 seconds monthly/90 minutes annually. There is a requirement that there be a battery powered emergency lighting at the generator/ transfer switch if indoors which would be tested in this fashion. Emergency lighting that is on the generator should be inspected monthly during the exercising of the generator to ensure lighting units are working. 5. What are the requirements for two locking/ delayed egress doors in the exit pathway? This is permitted in the Life Safety Code but may not be permitted by Ohio Fire Code. Some State Fire Marshals may still enforce the single device standard. The NFPA requirements for lock on doors in the path of egress is not permitted unless complies with: Clinical needs locks where individuals pose a security risk provided staff can unlock doors (dementia and psychiatric units) Delay egress locks permitted if the facility is fully sprinklered or smoke detected Provisions must exist for rapid removal Remote control locks Keys carried by ALL staff Other reliable means Smoke detection throughout secured area OR remote unlocking at CONSTANTLY supervised location Smoke and/or sprinkler activation will release the locks Locks release with loss of power 18/ and 18/ The requirements for delayed egress locks: 1. Releases with/in 15 seconds or 30 seconds per AHJ 2. <15 lb. for < 3 seconds to initiate 3. Unlocks with the loss of power 4. Unlocks with the initiation of fire alarm and/or smoke detector 5. Emergency lighting at door 6. Instructional sign at the door 7. Required signage: 8. PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS

5 6. Are gated patios or courtyards required to have alarms/ releasing devices on them? 7. Yes, if the patio or courtyard is an established fire egress pathway. 8. What are the requirement for the Fire Safety Evaluation Survey? The FSES was developed by the National Bureau of Standards at the request of the Department of Health and Human Services (DHHS) as an alternative method of determining compliance with the LSC. Facilities that pass the FSES may be certified for participation in the Medicare/Medicaid program even though they have repeat deficiencies reflected on the CMS The FSES is required when a facility has a serious building construction deficiency(s) that would make it difficult or impossible to correct reasonably and prevents the facility from technically meeting NFPA requirements such as hallway width, number of stories, wrong building type, inadequate number of exits etc. The FSES is no longer completed by state surveyors and the facility must hire a trained expert to complete. The 2013 FSES will be used in place of the 2001 FSES which was previously approved for use (Survey and Certification policy memorandum, S&C-03-21, dated May 8, 2003) with the 2000 LSC. The 2013 FSES has been updated by the NFPA and is calibrated to the requirements found in the recently adopted 2012 LSC. This will allow for a more accurate determination of LSC equivalencies.

6 Life Safety Documentation Is there a list of required inspection or documents for facilities to maintain? Yes, the following is a list of the commonly requested inspection and documentation by Ohio LSC Surveyors. The documentation should be kept in an orderly fashion such as in a 3-ring binder, and separated by each item topic. The binders should be maintained in an area where they are easily retrievable by key staff when the survey begins. Each binder should reflect required documentation for the current year or compliance cycle. When documentation is greater than annually then maintain the most recent testing or maintenance documentation available. Remove all older documentation and maintain separately. Only include documents that actually demonstrate a test or an inspection. Do not include copies of invoices, purchase orders, or any other document that is not relevant for testing and inspection. When required testing and maintenance is performed and there are recommendations for repairs and follow up work attach copies of work orders, contractor test reports, or work tickets that demonstrate the device was repaired/replaced, and re-tested. Have a copy of this document stapled to the test report so you don t have to spend time looking for it. Complete all documentation in pen (no pencil) or have it typed. Make sure the documents are legible You may need to requests originals where carbonless copies are not readable. Again, each item should be a topic tab for the facility s Life Safety Notebook. 1. Facility Layout Up to date facility floor plan of all levels of the building which shows the rooms and spaces the facility is currently utilizing (not necessarily as was originally constructed). The layout should identify features of fire protection including exits, pull stations, smoke and fire barriers. 2. NFPA 99 Risk Assessment Include the facility s completed risk assessment. 3. Emergency battery operated lighting Document the testing of all emergency battery operated lighting fixtures for 30 second each month and 90 minutes once a year. 4. Fire Alarm System Include the documentation, normally from licensed contractor, of the quarterly, semi-annual and annual testing of the fire alarm and corresponding components including smoke detectors, heat detectors, magnetic hold open devices, alarms, strobes, etc. 5. Smoke and fire dampers Include the documentation of the required smoke and fire damper testing and maintenance minimally done every 4 years. 6. Automatic Sprinkler System quarterly and annual inspections documentation. 7. Automatic Sprinkler System recording of the air pressure gauge reading MONTHLY for wet system. Note the gauge(s) should be tested or replaced every five years. The gauge itself should have install date identified on it. 8. Automatic Sprinkler System recording of the air pressure gauge reading WEEKLY for dry system. Note the gauge(s) should be tested or replaced every five years. The gauge itself should have install date identified on it.

7 9. Automatic Sprinkler System Annual sprinkler head inspection including piping and fittings completed by contractor of facility staff. Must be documented. Also ensure that the facility has a minimum of 6 spare sprinkler heads for each type utilized by the facility and the installation tool provided. 10. Automatic Sprinkler System Internal inspection conducted every 5 years. 11. Automatic Sprinkler System Back flow testing conducted annually. 12. Automatic Sprinkler System Where the system is utilizing anti-freeze the facility shall have system tested annually by qualified individual. Following the annual test, a tag must be attached to the riser indicating the date of the last test, the type and concentration of antifreeze solution, the date the antifreeze was replaced (if applicable). 13. Smoke detector Annual functional testing (normally included with annual fire alarm testing). 14. Smoke detector Sensitivity testing which is required by NFPA 72 requires smoke detectors to be sensitivity tested upon installation, first year afterwards and then every two years subsequently and all test results must be documented. 15. Smoke and Fire Door testing Doors required to be inspected and tested potentially including: Labeled fire rated doors Doors in exit enclosures -typically stairwells and exit passageways Doors in smoke barriers Doors in other fire resistance rated walls such as hazardous area and fire pump enclosure 16. Exits Signs Monthly inspection of all emergency and exit signs and lighting systems to ensure they are appropriately functioning. Annual testing of all emergency and exit lighting systems 17. Fire Drills There should be a minimum of 12 fire drill annually. Maintain documentation concerning fire drills that shows at least the following: Differing times for drills conducted on each shift. Drills should be conducted at various times throughout the shift to avoid patterns. Fire drills that occur within one hour may be considered as having occurred at the same time. One drill per shift per quarter. Varying conditions of drill. A drill conducted at mealtime is an example of a varying condition. Differing days of the week including weekends. Involvement of all departments. Documented observations of staff response.

8 Record of equipment functioning such as the release of doors and alarms sounding. Between the hours of 9:00 PM to 6:00 AM a silent alarm may be used instead of the audible alarm. 18. Fire Alarm Testing Document the time the alarm monitoring company received the alarm (within 90 seconds of alarm). When conducting a silent alarm, ensure that the alarm is tested the following morning noting the time the alarm signal was received. 19. Fire Pump Testing Fire pumps shall be tested under minimum, rated, and peak flows of the fire pump by controlling the quantity of water discharged through approved test devices annually. A monthly test of electric motor-driven fire pump assemblies shall be conducted without flowing water. This test shall be conducted by starting the pump automatically. The pump shall run a minimum of 10 minutes. A weekly test of a diesel engine-driven fire pump assemblies shall be conducted without flowing water. This test shall be conducted by starting the pump automatically, and the pump shall run a minimum of 30 minutes. 20. Policies Include as appropriate Fire- Evacuation Fire watch Facility disaster plan Smoking Use of space heaters Limiting Access to alcohol-based hand Rub 21. Generators Weekly visual inspection minimum, should include a check of the following: Fuel (check main and day tank fuel supply levels; day tank float switch; piping, hoses and connectors; operating fuel pressure; and for any obstructions to tank vents and overflow piping) Oil Cooling system Exhaust system Battery system (check specific gravity, electrolyte level and battery charger) Electrical Prime Mover/Generator and components 22. Generators Monthly exercise for a minimum of 30 minutes not including the warm up or cool down time at under operating temperature conditions and at not less than 30 percent of the generator s nameplate kw rating (diesel generators). For diesel generators that do not operate at 30% of nameplate rating a facility may use a Load Bank test (generator is exercised annually for 90 minutes [30 50% and 60 75%])

9 23. Generator Type 1 and 2 generators shall be exercised 4 hours every 36 months 24. Generator Diesel generators shall have the fuel tested annually and documented according to ASTM standards. 25. Kitchen Range hood system Inspect and maintain the hood suppression system in accordance with NFPA 96 semi-annually. 26. Kitchen Range Hood system inspect monthly including: Ensure system is in its proper place; Manual actuators are not obstructed; Tamper seals and indicators are intact; Maintenance tag is in place; No obvious physical damage that might prevent operation; Ensure pressure gauge is in operable range; Nozzle blow-off caps are intact and undamaged; The protected equipment has not been replaced, modified or relocated 27. Non-Hospital Grade Receptacles Testing non-hospital-grade receptacles at patient bed locations at intervals not exceeding 12 months and documentation should include: The physical integrity of each receptacle shall be confirmed by visual inspection The continuity of the grounding circuit in each electrical receptacle shall be verified Correct polarity of the hot and neutral connections in each receptacle shall be confirmed The retention force of the grounding blade of each receptacle shall not be less than 4oz. 28. Elevator Fire Fighter Service Requirements found in ASME/ANSI A17.3 Safety Code for Existing Elevators and Escalators requires testing monthly with a written record documented. The facility shall also have elevator inspected and maintenance performed not less than annually. 29. Electrical Equipment Servicing and Maintenance- Facility should develop maintenance program including testing intervals for testing patient care related electrical equipment based on manufacture guidelines and normally not less than annually. Testing will normally include: Physical integrity and Resistance. 30. Certificate State Boiler Certification 31. Certificate State Elevator Certification 32. Elevator annual maintenance and servicing

10 33. Elevator monthly recall testing documentation. 34. Medical gas End User Certificate 35. Other If required by jurisdiction fire hydrants on facility property may need to have required testing and maintenance. 36. Other - HVAC Filter inspection and replacement 37. Other Portable fire extinguishers devices are to be inspected monthly by facility staff and the attached card initialed and dated. Annually these devices shall have maintenance performed by licensed contractor 38. Other Providers with natural gas generators who do not have a backup fuel source must be able to demonstrate that the reliability of natural gas fuel will not be interrupted to maintain compliance. This can be proven with a letter from natural gas vendor that contains: A statement the fuel source is reasonable reliably Description supporting the reasonable reliability assertion A statement of the low likelihood of an interruption Description supporting the low interruption assertion Signature from technical personnel 39. Other Documentation of in-service of staff on facility Fire/ Disaster policy and procedure annual 40. Other Documentation of in-service of all staff you use and/or handle medical gases annual 41. Other ODH Self Inspection form completed monthly

11 Final Thoughts Is the presentation available? Yes, the door inspection PowerPoints are attached. Yes, you can print the presentation. List of additional documents attached: Receptacle Testing Form Weekly Generator Inspection Form NFPA 99 Risk Assessment For additional question, please contact: Kenn Daily

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA Adoption of 2012 Life Safety Code Health Care Facilities Code Kenneth Daily, LNHA kenn@qissurvey.com CMS Announcement May 2016 Life Safety Code Health Care Code Effective July 5 th Numerous changes many

More information

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance 2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance Will begin at 1 pm Housekeeping Announcements Problems during the call? Press *0

More information

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers, NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101

More information

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments

More information

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet

Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet This document is used for frequently cited Life Safety Code violations. This is not an all-inclusive list and is intended for reference only.

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey. Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the

More information

LIFE SAFETY CODE MAINTENANCE MANUAL

LIFE SAFETY CODE MAINTENANCE MANUAL LIFE SAFETY CODE MAINTENANCE MANUAL 1 P a g e Table of Contents Introduction 3 Alcohol Based Hand Rub (ABHR) Dispensers 4 Corridor Walls 4 Corridor Width 5 Doors 5 Electrical 6 Elevators & Dumbwaiters

More information

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012) 1. K62 Automatic Sprinkler Systems - Automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested periodically. 18.7.6, 19.7.6, 4.6.12, NFPA 13,

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities Fire & Life Safety Code Compliance Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities LTC, Skilled Nursing Facilities COMMON LIFE SAFETY DEFICIENCIES

More information

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &

More information

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT

More information

4/9/2014. Life Safety Code. Nursing Facility Life Safety Code Today and Tomorrow. Kenneth Daily, LNHA.

4/9/2014. Life Safety Code. Nursing Facility Life Safety Code Today and Tomorrow. Kenneth Daily, LNHA. Nursing Facility Life Safety Code Today and Tomorrow Kenneth Daily, LNHA kenn@qissurvey.com April 2014 Life Safety Code Life Safety Code 101 (2000 Ed.) Promulgated by the National Fire Protection Association

More information

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care

More information

Iowa State Fire Marshal

Iowa State Fire Marshal Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards

More information

GENERAL AREAS OF INSPECTION

GENERAL AREAS OF INSPECTION This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that

More information

Are there any policies regarding outlets that contain USB ports?

Are there any policies regarding outlets that contain USB ports? Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types

More information

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in

More information

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services Life Safety Code Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services danilo.concepcion@stjoe.org 714-771-8944 The findings and conclusions in this presentation are

More information

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Center for Clinical Standards and Quality /Survey & Certification Group

Center for Clinical Standards and Quality /Survey & Certification Group DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality /Survey

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99

More information

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1 Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained

More information

Life Safety Code Potpourri

Life Safety Code Potpourri Life Safety Code Potpourri JAMES P. LOVELAND P.E. MINNESOTA DEPARTMENT OF HEALTH Engineering Services Section FEDERAL MONITORING SURVEYS 2007 2008 2009 No. of FMSs 20 20 20 No. of Deficiencies 332 252

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Issued June 28, 207 Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Nursing Care Center (NCC) Accreditation Program Standard

More information

Agency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014

Agency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014 Agency for Health Care Administration Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014 CMS S&C Letter Interpretation CMS- S&C: 13-58-LSC Dated: 08/30/2013 Several Categorical LSC

More information

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA 31548 912-510-4302 February 9, 2011 Greetings Camden County Businesses, As always, our department is working vigilantly

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary

More information

Compliance w/ the 2012 Life Safety Code

Compliance w/ the 2012 Life Safety Code Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February

More information

FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION

FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION To be kept in school administration office Crown Copyright, Province of Nova Scotia 2004 Prepared by Nova Scotia Department of Education No part of this document

More information

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT BEQ KNIT LTD. ZIRABO, ASHULIA, SAVAR, DHAKA Other Factories: Beq Sweaters Ltd., Tammam Design Ltd. April 22, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K0100 - General Requirements - Other Title General Requirements - Other General Requirements - Other List in the REMARKS

More information

School Fire Safety Checklist

School Fire Safety Checklist Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

Emergency Planning for Institutional Facilities

Emergency Planning for Institutional Facilities Emergency Planning for Institutional Facilities Pacific ADA Emergency Preparedness Webinars Presented by: Kimberly Paarlberg, ICC Based on the 2015 edition of the International Building Code (IBC) and

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

Fort Bragg Fire and Emergency Services Division Fire Safety Survey For use of this form, see FB Reg 420-1, the proponent agency for this form is DES.

Fort Bragg Fire and Emergency Services Division Fire Safety Survey For use of this form, see FB Reg 420-1, the proponent agency for this form is DES. Fort Bragg Fire and Emergency Services Division Fire Safety Survey For use of this form, see FB Reg 420-1, the proponent agency for this form is DES. Date of Survey: Building Number: UNIT / Organization:

More information

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work. 3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;

More information

Fire Sprinkler Plan Submittal Form

Fire Sprinkler Plan Submittal Form Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10

More information

FHCA 2014 Annual Conference & Trade Show

FHCA 2014 Annual Conference & Trade Show FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion

More information

THE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission

THE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission 2013 THE HEALTHCARE ENVIRONMENT UPDATE Anne M. Guglielmo, Engineer Engineering Department The Joint Commission Standard/NPSG 2012 Non Compliance 2013 Non Compliance (1 st Six Months) RC.01.01.01 61% 55%

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

FIRE PREVENTION STANDARDS

FIRE PREVENTION STANDARDS DATE: 04/11/02 APPROVED: NUMBER: FP0-010 REVISED: FIRE PREVENTION STANDARDS TITLE: Large Family Day Cares (9-14 kids) PURPOSE: The purpose of this standard is to acquaint the applicant with the applicable

More information

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICE Form Approved OMB Exempt FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION

10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION Enjoy Your TJC Survey Bill H. McCully CHFM SASHE Senior Consultant MSL Healthcare Partners PREPARATION 1 Top Eight Most Cited Standards (George Mills) EC News May 2015 Top Citations EC.02.06.01 56% EC.02.05.01

More information

Candy Easterling K-063. Adequate and Reliable Water Supply for the Sprinkler System. CITY WATER or WATER TANK for Sprinkler System

Candy Easterling K-063. Adequate and Reliable Water Supply for the Sprinkler System. CITY WATER or WATER TANK for Sprinkler System Candy Easterling K-063 Adequate and Reliable Water Supply for the Sprinkler System CITY WATER or WATER TANK for Sprinkler System Life Safety Code Presentation 1 Fire Extinguishers K-064 2000 NFPA 101,

More information

Written Fire Safety Plans

Written Fire Safety Plans Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was

More information

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2 FIRE SAFETY PLAN BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089 DATE: 15-August-10 FPO #2 INDEX Introduction 2 Locations of Fire Safety Plans 3 Forward 4 Audit of Building Data 5-6 Fire Fighting

More information

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 HCFMO Harris County Fire Marshal M.S. Montgomery Fire Marshal FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 EFFECTIVE JANUARY 1, 2007 These guidelines

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

Common Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive.

Common Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive. Common Fire Code Violation Checklist Listed are some of the most commonly found fire code violations and should not be considered as all inclusive. Exterior Features All fire access roads signed per TFD

More information

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Form Approved OMB No. 0938-0242 1. (A) PROVER NUMBER 1. (B) MEDICA I.D. NO. 1. HOSPITAL

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MULTIFABS LTD KASHIMPUR, NAYAPARA Other Factories: ne April 9, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was surveyed for fire safety on

More information

Narrative Reports As Regulated by 780 CMR, Section 903.0

Narrative Reports As Regulated by 780 CMR, Section 903.0 EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for

More information

Programmatic Policy and Procedure

Programmatic Policy and Procedure Page 1 of 6 Programmatic Policy and Procedure Section Sub-section Psychiatric Health Facility (PHF) Crisis and Emergency Response Effective: Version: Policy Emergency Subsistence Management Last Revised:

More information

5/19/2011. Fire Safety Survey. Hi, we re from the Health Department and would like to speak with the Administrator and Maintenance Director

5/19/2011. Fire Safety Survey. Hi, we re from the Health Department and would like to speak with the Administrator and Maintenance Director APRIL 2011 The Survey Process and Your Surveyors Presented by State of Connecticut Department of Public Health Facilities Licensing & Investigations Building & Fire Safety Unit 410 Capitol Avenue Hartford,

More information

ASCs & LSC. Alice Epstein, DFASHRM, FNAHQ

ASCs & LSC. Alice Epstein, DFASHRM, FNAHQ , DFASHRM, FNAHQ Disclaimer The purpose of this presentation is to provide information, rather than advice or opinion. It is accurate to the best of the speaker's knowledge as of the date of the presentation.

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets

More information

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal M.S. Montgomery Fire Marshal September 1, 2010 This document describes rules changes affecting the operation and fire safety in foster homes licensed and regulated by the Texas Department of Family and

More information