SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

Size: px
Start display at page:

Download "SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM"

Transcription

1 SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM Kratzmeir S. FOGTEC Fire Protection, Research & Development, Germany Keywords: Fire Protection, Fire suppression, water mist 1. INTRODUCTION Fire safety measures were increased during the last years. But recent serious fires in tunnels again showed that there are still similar problems with evacuation of people and access for fire fighters as well as serious damages on tunnel structures. Mainly this is affected by extremely high temperatures and smoke spread due to rapid fire development. Automatic fire suppression systems were considered for years to improve the situation in tunnels, especially shortly after fire detection. First tunnels with innovative suppression systems based on water mist technology are under installation. For these tunnels, applicability was proven in special fire tests. To create sufficient basics for a performance based layout of such systems more research work is carried out now. 2. CURRENT KNOWLEDGE ABOUT FIRE SUPPRESSION SYSTEMS IN TUNNELS Based on a report of PIARC active fire protection measures by means of sprinkler or water mist systems, most tunnel safety designers declined to propose such systems. However, due to lack of knowledge by real scale fire test, the arguments given in this report must be taken seriously into account in past. Anyway, in Australia and Japan, automatic fire suppression systems are to be installed in longer tunnels or tunnels with a high traffic density as a general rule. But the aim and therefore the Figure 1: UPTUN Fire Test Scenarios performance of these systems are mostly different to the aforementioned systems, as they are installed for protection of the tunnel structure against collapse. If a fire occurs, these systems will be activated after completion of the evacuation process, often after Minutes. Recently it is under consideration if this strategy should also be changed to an activation of the system as early as possible. Beside some other experiments with suppression systems in tunnels or similar applications, the European research project UPTUN includes also scientific development of innovative and effective fire mitigation systems for use in tunnels. The main focus was given to a full scale fire test program to assess effectiveness of such systems independently. Fire scenarios for this test program were developed by Sintef (Norway) based amongst others on the results of the Runehamar fire tests. Two different scenarios were used: Partly covered pool fire with a maximum HRR of MW Partly covered wooden crib fire with a potential HRR of approx. 50 MW

2 These scenarios were designed not to simulate any specific fire load, e.g. trucks, cars, but repeatable fires with specific HRR. Obviously, 20 MW or even 50 MW, are not HRR of a full developed fire in a tunnel, but as the aim of such system is fire suppression on early stage, this figure is sufficient and should be taken into account in design process, e.g. for interface with the detection system. According to the internal UPTUN test report, test result of this test program can be summarized as follows: Generally, water mist systems are able to suppress Figure 2: UPTUN Fire Test fires in tunnels up to a certain limit efficiently even with ventilation. HRR can be stabilized or even reduced. Temperatures nearby the fire as well as in a distance of 20 m are reduced significantly. Evacuation conditions as well as conditions for fire fighters are improved during activation of the system. Due to reduction of the smoke production during activation of the system, visibility was improved particularly on the upstream side of the fire The layout of the system (nozzle position, flow rates, droplet size distribution) has a high effect on efficiency of the system. Scaling is only limited. The UPTUN fire tests have shown that especially designed and tested water mist systems can be a very effective fire safety tool for tunnels. Furthermore it turned out, that scaling, even with advanced simulation tools, is very limited. Real scale fire tests are necessary. Maximum effectiveness of such systems can be achieved by adequate interaction with other parts of the tunnel safety system, e.g. detection or ventilation. Although a lot of new knowledge was gathered during the UPTUN project, there are still some important questions to be answered; some even came during the test program and its assessment. Some general questions are as follows: Up to now, any suppression system was only tested with longitudinal ventilation. Are there any differences with other types such as semi transversal or transversal? It already turned out that interaction with other safety systems is of special importance. What influences do these safety systems have against each other? How to assess results of fire tests. Are strict acceptance criteria more useful or should results assessed case by case? 3. ASSESSMENT OF EFFECTIVENESS OF ACTIVE FIRE SUPPRESSION SYSTEMS 3.1. SOLIT Project The research project SOLIT (Safety of Life in Tunnels) further info at - addressed itself to the task to pick up current knowledge about suppression systems for tunnels to enhance these systems and test methods so they can be installed in tunnels efficiently and safe. SOLIT, funded by the German government, has two focal points: The technical aspects are mainly dealing with reliability and life cycle issues of such systems and are not described in this paper. The other main task is focusing on development of methods how such suppression systems for tunnels can be tested and assessed regarding their effectiveness for a wider range of

3 applications than today. Furthermore, above mentioned questions should be analyzed more in detail. Experience has shown that full scale fire tests are still necessary. The SOLIT project is guided by a scientific advisory board containing organizations and institutions that are well experienced in the field of tunnel fire safety e.g. STUVA, Sintef, TNO, BaST or German ministry of transport and infrastructure and TÜV SOLIT Full Scale Fire Test Program Scenarios for real scale fire testing are always a compromise between reality and feasibility. Indeed, real trucks or cars as fire load would be more realistic but due to extreme differences in size and material composition any comparable and repeatable results would be achieved. Therefore, Figure 3: SOLIT Class A Fire Scenario similar to other fire test procedures, scenarios for tunnel fire testing should also consist of common agreed standard fire loads, e.g. EUR wood pallets, so repeatable results can be ensured. Based on a study of real tunnel fires and scenarios used in full scale fire tests, following scenarios will be used for to assess effectiveness of the tested system. The scenarios as well as the measurement concept were gathered together with the scientific advisory board of the SOLIT project, which consists of national and international well accepted experts in tunnel fire safety. Class A Scenario: Wood and plastics The mock up should simulate a common used loaded truck similar to the Runehamar tests presented by Ingason (2003). The load consists of wooden EUR pallets and plastic pallets with the ratio of 80:20. The whole load is covered with a tarpaulin. Total weight: approx. 8 to. Total energy content: GJ Wood/plastic ratio: 80:20 To assess the control of fire spread between vehicles, target objects also consisting of wooden pallets will be used sideward and on downstream side of the mock up. Class B Scenario: Partly covered diesel pools According to the UPTUN fire tests for suppression systems, the scenario is slightly modified. By means of this scenario, specific HRR can be produced as well as fires of burnable liquids. Max estimated HRR: Total energy content: approx. 30 MW MJ The cover ensures that the pool surface can not be hidden directly by any suppression system as this would be the situation with real vehicles in a tunnel. By using a similar scenario than within the UPTUN test program, available data can be compared.

4 The measurement concept is not based on any fixed acceptance criteria. Moreover data should be collected in a way that assessment of efficiency can be done during design of performance based safety measures. Following data will be measured in general: - Temperatures in different positions - Radiant heat - Gas concentrations (CO, CO 2, O 2 ) Of course, toxicity of smoke is an important issue. Standard fire loads are not able to simulate different material compositions of real material. Therefore extended smoke measurement, e.g. HCl, HCN, NO x, is not indicated. - Humidity - Longitudinal air velocity - Visibility In past, no satisfactory results were achieved for visibility measurements during tunnel fires with suppression systems as measurements did not reflect subjective impressions. Therefore new methods of visibility measurements will be studied during these tests. The test program will be carried out between March and June More information about the test program and results will be available at Assessment of Test Results Regarding performance of suppression systems for tunnels until know it was only spoken about effective in general. Assessment of effectiveness of such systems can be conducted in two different ways: performance based analysis or prescriptive based. Particularly in the field of fire protection, prescriptive based layouts of safety systems are often used. If a system fulfils specific requirements, e.g. water flow rate or spacing in case of sprinklers, the system is assumed to be effective. In case the layout of systems is based on real fire tests, e.g. for passive fire protection material but also for water mist systems, there are specific acceptance criteria which must be passed during the testing procedure. Acceptance criteria in a prescriptive way are fixed values based on measurements for defined aims of the system. For simple standard applications prescriptive guidelines are usually well accepted and can be seen as very safe. But especially for complex systems, such as tunnel safety systems, it is extremely complicated to adapt these guidelines and values on specific projects. Performance based layout of safety systems is usually based on an extended risk analysis. Thereupon individual safety measures and systems can be arranged for this specific application. Normally this method is used, when prescriptive guidelines are not available or applicable. Although even for performance based layout accepted guidelines and values should be used as far as possible. Performance based layout of safety systems gives much more flexibility to consultants to adopt systems especially for each project. But of course a much better knowledge and understanding of the whole safety system is necessary. In case of fire suppression systems for tunnels it can be assumed, that even after full scale fire testing no general acceptability for the system can be given. Moreover, for every tunnel project it should be verified individually, how such systems can be applied in combination with other safety measures. For such analysis profound knowledge and performance data, generated during real scale fire testing, is strictly necessary.

5 The methodology to assess effectiveness of suppression systems for tunnels developed within the SOLIT project should not specify approval criteria which must be passed during fire testing but should give suitable fire scenarios and measurement concepts to determine sufficient data for a performance based layout. 4. CONCLUSIONS Based on new knowledge of scientific full scale fire testing open questions, e.g. given by PIARC can be answered basically. Water mist fire suppression systems as a part of the tunnel safety system are able to improve the atmosphere in tunnels during a fire significantly. As knowledge regarding scaling and analysis of test results as well as interaction with other parts of the tunnel safety system was limited in past the research project SOLIT is focusing on these questions. An extended full scale fire test program is carried out to develop a general accepted methodology to assess effectiveness of fire suppression systems in tunnels. REFERENCES Opstad, K, Brandt A, Test Report of UPTUN WP 2.4. for Real Scale Fire Test with Water Mist Fire Suppression Systems. Ingason, H, Lönnermark A, Large Scale Fire Tests in the Runehamar Tunnel. International Symposium on Catastrophic Tunnel Fires, pp. 93

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS - 259 - COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS Kratzmeir S. 1, Rothe R. 1 Peters B. 2, 1 IFAB Institute for applied fire safety research, Rostock 2 Fogtec Fire Protection, Cologne

More information

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION Stefan Kratzmeir*, IFAB Institute for applied fire safety research, Rostock, Germany Max Lakkonen, FOGTEC Fire Protection, Cologne, Germany

More information

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS - 195 - IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS Rajko Rothe; IFAB, Berlin, Germany Max Lakkonen and Dirk Sprakel, FOGTEC Fire Protection, Cologne, Germany ABSTRACT This paper discusses the

More information

Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany

Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany Making rail systems more efficient by using on-board Fire Protection Systems Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany Key Presentation Take-Aways Holistic approach to

More information

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS - 203 - FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS Hofer R., IBS Institute for Technical Fire Protection and Safety Research, Linz / Austria

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities

Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities Roger A. Dirksmeier, FOGTEC Fire Protection, Germany Fire Protection Conference Tel Aviv, 4 th of April 2016

More information

The first tunnel fire. Benefits of fire

The first tunnel fire. Benefits of fire Benefits of fire suppression Quantifying the effects of suppression on energy release. This article by Fathi Tarada, managing director of fire safety, risk management, ventilation and CFD consultant Mosen

More information

Optimisation of ventilation systems costs by using fixed fire fighting systems (FFFS) in tunnels

Optimisation of ventilation systems costs by using fixed fire fighting systems (FFFS) in tunnels Optimisation of ventilation systems costs by using fixed fire fighting systems (FFFS) in tunnels Rajko Rothe IFAB Institute for applied fire safety research, Berlin, Germany Max Lakkonen, Tobias Hoffmann

More information

COMPENSATORY EFFECTS OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS. Stefan Kratzmeir Managing Director.

COMPENSATORY EFFECTS OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS. Stefan Kratzmeir Managing Director. COMPENSATORY EFFECTS OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS Stefan Kratzmeir Managing Director www.ifab-fire.com FFFS in Tunnels State of the Art FFFS in Tunnels are an accepted measure to increase

More information

Sprinklers Modeling for Tunnel Road Fire Fighting

Sprinklers Modeling for Tunnel Road Fire Fighting Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and

More information

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen Linear Heat Series Under Test: Extensive fire tests prove Distributed Temperature Sensing (DTS) enables fast and reliable control of fire protection systems in road and rail tunnels Gerd Koffmane, Henrik

More information

FIRESEAT

FIRESEAT PROTECTION OF TUNNELS WITH WATER MIST SYSTEMS Stefan Kratzmeir IFAB ABSTRACT Water Mist Systems are more and more used for the protection of tunnels. The development started with the European research

More information

TUNPROTEC. Active Tunnel Fire Protection

TUNPROTEC. Active Tunnel Fire Protection VID FIre KIll TUNPROTEC Active Tunnel Fire Protection 9 An Active Tunnel Fire General The tunnel structures are very valuable. Infrastructure tunnels, such as train tunnels and road tunnels represent very

More information

Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist

Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Water Mist for Transformer Fire Protection

More information

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee Fire Protection and Safety in Tunnels Conference Opening Remarks Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee Agenda Background to the conference Key themes Recent tunnel fires Major infrastructure

More information

designed for rail 5000 Series

designed for rail 5000 Series designed for rail 5000 Series 5000 Series The only complete SIL system 20 years of experience in the field. More than 15.000 systems supplied worldwide. A team devoted to rolling stock projects with specialized

More information

Fixed Fire Fighting Systems for Road and Rail Tunnels

Fixed Fire Fighting Systems for Road and Rail Tunnels 40 Brandschutz Fire Safety Tunnel 1/2012 1 Activation of FFFS in the commissioning test of M30 tunnels in Madrid, Spain [8] Fixed Fire Fighting Systems for Road and Rail Tunnels Today, fixed fire fighting

More information

Hot Issues in Fire Engineering 12 March 2013

Hot Issues in Fire Engineering 12 March 2013 Hot Issues in Fire Engineering 12 March 2013 An Update on Design Fires of Vehicular Tunnels W.K. Chow Fellow, Hong Kong Academy of Engineering Sciences Research Centre for Fire Engineering, Department

More information

Impact of quick incident detection on safety in terms of ventilation response

Impact of quick incident detection on safety in terms of ventilation response Impact of quick incident detection on safety in terms of ventilation response P. J. Sturm 1) ; C. Forster 2) ; B. Kohl 2) ; M. Bacher 1) 1) Institute for Internal Combustion Engines and Thermodynamics

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS

TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS - 12 - TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS H. Ingason and Y.Z. Li, SP Technical Research Institute of Sweden ABSTRACT The increasing use of fixed fire-fighting system (FFFS) in tunnels

More information

VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY

VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY Ricky Carvel, Guillermo Rein & José L. Torero BRE Centre for Fire Safety Engineering,

More information

THE IMPACT OF FIXED FIRE FIGHTING SYSTEMS ON TUNNEL SAFETY THE BURNLEY INCIDENT IN A CURRENT THEORETICAL PERSPECTIVE

THE IMPACT OF FIXED FIRE FIGHTING SYSTEMS ON TUNNEL SAFETY THE BURNLEY INCIDENT IN A CURRENT THEORETICAL PERSPECTIVE THE IMPACT OF FIXED FIRE FIGHTING SYSTEMS ON TUNNEL SAFETY THE BURNLEY INCIDENT IN A CURRENT THEORETICAL PERSPECTIVE ABSTRACT Arnold Dix Scientist and Lawyer Associate Professor, University of Western

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System Igor Maevski, PhD, PE Jacobs Engineering, ASHRAE Member Raymond C. Klein, PE Jacobs Engineering, ASHRAE Member ABSTRACT Recently there

More information

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Background of this Presentation In recent years the

More information

Large scale fire tests with fixed fire fighting system in Runehamar tunnel

Large scale fire tests with fixed fire fighting system in Runehamar tunnel Large scale fire tests with fixed fire fighting system in Runehamar tunnel Haukur Ingason Glenn Appel Ying Zhen Li SP Technical Research Institute of Sweden Fire Technology SP Report 214:32 Large scale

More information

Project description and planning of large-scale tests in Runehamar tunnel

Project description and planning of large-scale tests in Runehamar tunnel Project description and planning of large-scale tests in Runehamar tunnel August 2003 Prepared by: Haukur Ingason, SP Swedish National esting and Research Institute Anders Lönnermark, SP able of content

More information

Tunnel Fire Dynamics

Tunnel Fire Dynamics Tunnel Fire Dynamics Haukur Ingason Ying Zhen Li Anders Lönnermark Tunnel Fire Dynamics 1 3 Haukur Ingason Fire Research SP Technical Research Institute of Sweden Borås Sweden Anders Lönnermark Fire Research

More information

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES UDC 614.84 : 628.854 : 52-17 DOI: 10.7562/SE2011.1.01.03 Original article www.safety.ni.ac.rs DARKO ZIGAR 1 DESIMIR JOVANOVIĆ 2 MARTINA ZDRAVKOVIĆ 3 1-4 University of Niš, Faculty of Occupational Safety

More information

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED - 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company

More information

Road tunnel safety rules in Italy: the tunnel country

Road tunnel safety rules in Italy: the tunnel country Safety and Security Engineering II 317 Road tunnel safety rules in Italy: the tunnel country M. Guarascio, M. Lombardi, G. Rossi & G. Sciarra Safety Engineering Sapienza, Rome University, Italy Abstract

More information

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018 RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018 Table of content 1. Safety standards for road and railway tunnels 2. Upgrading the Alrberg Tunnel

More information

The European project UpTun improving the level of fire safety in existing tunnels

The European project UpTun improving the level of fire safety in existing tunnels Safety and Security Engineering 519 The European project UpTun improving the level of fire safety in existing tunnels H. Hejny Dr. Horst Hejny Consulting, UpTun Exploitation Manager Abstract The European

More information

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE The Mont Blanc tunnel project Eric CESMAT, Sylvain DESANGHERE 24/09/2009 International water mist conference 2009 Fires in tunnel Car fire > 4 to 8 MW Van fire > 15 MW HGV fire > 30 MW Big HGV fire > 100

More information

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY World-class services help reduce incidents, protect the environment, and keep people and plants safe White Paper PAGE 1 Introduction

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

and Sprinkler System in Resalat Tunnel of Tehran

and Sprinkler System in Resalat Tunnel of Tehran CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home

More information

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE The Protection of Machinery Spaces by means of the Local Application of Water Mist Dr. Tim R. Nichols CPhys FIFireE 2017 Johnson Controls. All rights reserved. Tyco Fire Products LP is a subsidiary of

More information

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY World-class services help reduce incidents, protect the environment, and keep people and plants safe White Paper PAGE 1 Introduction

More information

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology

More information

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology PO Box 310 North

More information

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel Safety and Security Engineering VI 73 Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel M. Lombardi & G. Rossi Dipartimento di Ingegneria Chimica

More information

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 240 244 A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China LIU Xiao-lu *, WANG Wen-qing Shenyang

More information

FOGTEC Rail Systems. Rolling Stock Applications. Fire Protection Solutions from one source. Experts in Fire Protection

FOGTEC Rail Systems. Rolling Stock Applications. Fire Protection Solutions from one source. Experts in Fire Protection Fire Protection Solutions from one source FOGTEC Rail Systems Rolling Stock Applications Warszawa, 25.06.2014 1 Warszawa, 25.06.2014 From concept design to validation and verification: case study of a

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney

More information

THE EFFECT OF A WATER MIST SYSTEM ON LARGE-SCALE TUNNEL FIRES

THE EFFECT OF A WATER MIST SYSTEM ON LARGE-SCALE TUNNEL FIRES - 211 - THE EFFECT OF A WATER MIST SYSTEM ON LARGE-SCALE TUNNEL FIRES Ir. Victor Meeussen, Ir. Tony Lemaire, Efectis, The Netherlands DI Georg Reichsthaler, Helmut Kern, Aquasys, Austria Ir. M.P. Oude

More information

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS Modeling water-mist based suppression of 34 GJ car-deck fires using FDS S. Li, R. Acharya, M. Colket, V. Sankaran, G. Poncia United Technologies Research Center L. Torpo Marioff Corporation March 1 st,

More information

FOGTEC Rail Systems. Rolling Stock Applications. Fire Protection Solutions from one source. Experts in Fire Protection

FOGTEC Rail Systems. Rolling Stock Applications. Fire Protection Solutions from one source. Experts in Fire Protection Fire Protection Solutions from one source FOGTEC Rail Systems Rolling Stock Applications Modern Trends of Fire Protection in Rolling Stock 2014 designed for rail Warsaw, 25 1 Smart Concepts using innovative

More information

EHAMAR EHAM HAM RUNEHA UNE. Summary of Large Scale Fire Tests in the. gram gra r. ram ra. n with the UPTUN Research Progra gr. el in.

EHAMAR EHAM HAM RUNEHA UNE. Summary of Large Scale Fire Tests in the. gram gra r. ram ra. n with the UPTUN Research Progra gr. el in. Edited by: 100 Jan Brekelmans BSc (TNO Building and Construction on n Rese Research, earch, Cen Centre for Fire Research) 200 René é van den Bosch BSc (Promat, Tunnel Fire re e Protection) P te o 400 Tunnel

More information

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363) EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT 20-07 TASK 363) Louis Ruzzi PennDOT District 11 Igor Maevski, PhD, PE - Jacobs Agenda AASHTO T20 Technical Committee Roadway Tunnels

More information

Growing Strawberries - Under Cover Practices Last Updated Wednesday, 31 August :47 INTRODUCTION:

Growing Strawberries - Under Cover Practices Last Updated Wednesday, 31 August :47 INTRODUCTION: INTRODUCTION: Strawberries are a tricky crop, mainly because of its historical genetic development which dictates its requirements for successful plant development and high production. SB developed from

More information

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS Dr. Arnd Rogner Metaphysics SA 1 Contents Actual detection technologies (in Europe) Field experience in tunnel fire detection System integration 2 Road

More information

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition International Journal of Ventilation ISSN 1473-3315 Volume 8 No 4 Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition Y. Liu 1, J. Munro 1 and B. Dandie 2 1 Parsons

More information

Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches

Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches 2014-09-19 SP Method 4912 Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches 2014-09-19 page 2 (17) Copyright This test method

More information

Fire Extinguishing Concepts for Recycling Plants. 1 Fire Extinguishing Concepts for Recycling Plants

Fire Extinguishing Concepts for Recycling Plants. 1 Fire Extinguishing Concepts for Recycling Plants Fire extinguishing concepts for recycling plants 341 Fire Extinguishing Concepts for Recycling Plants Günter Knopf Ingenieurbüro für Anlagentechnischen Brandschutz Heidesee (Engineering firm for plant-specific

More information

Research on Mobile Water Spray Device Reducing the Temperature of Metro Fire

Research on Mobile Water Spray Device Reducing the Temperature of Metro Fire Applied Mechanics and Materials Online: 2012-05-14 ISSN: 1662-7482, Vols. 166-169, pp 2731-2734 doi:10.4028/www.scientific.net/amm.166-169.2731 2012 Trans Tech Publications, Switzerland Research on Mobile

More information

High-pressure water mist systems and fire testing. Max Lakkonen IFAB Institute for Applied Fire Safety Research

High-pressure water mist systems and fire testing. Max Lakkonen IFAB Institute for Applied Fire Safety Research High-pressure water mist systems and fire testing Max Lakkonen IFAB Institute for Applied Fire Safety Research Content of presentation IFAB Company Application fields Services High-pressure water mist

More information

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 330 335 Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater

More information

Computational simulation of road tunnel fire protection by sprinklers

Computational simulation of road tunnel fire protection by sprinklers European Journal of Environmental and Safety Sciences 2014 2(2): 48-52 ISSN 1339-472X European Science and Research Institute (Original Research Paper) Computational simulation of road tunnel fire protection

More information

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection Julio Toko, Martin Fromme, Bernd Horbach and Wieland Hill LIOS Technology GmbH, Cologne, Germany

More information

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation

More information

Specialists in Tunnel Fire Protection

Specialists in Tunnel Fire Protection Specialists in Tunnel Fire Protection 00-M-0003-A Underground transport facilities are sensitive links in the economic chain that carry thousands of people and tons of goods every day and they are increasingly

More information

WATER MIST CONVENTION AND EXHIBITION

WATER MIST CONVENTION AND EXHIBITION INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology

More information

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Hai Jiang, Vaidya Sankaran, Med Colket, May Corn United Technologies Research Center Kati Laakkonen Marioff Corporation 14th International

More information

2 nd European Forum of Road Tunnel Safety Officers

2 nd European Forum of Road Tunnel Safety Officers 2 nd European Forum of Road Tunnel Safety Officers Brussels, 18 January 2012 How to define a continuous process to improve safety? Bernt Freiholtz How to define a continuous process to improve safety?

More information

Smoke control in car parks

Smoke control in car parks Smoke control in car parks The actual situation in CEN TC 191 SC1 WG9 Imagine the result Jean-Claude DE SMEDT MIFireE,MSFPE,MNFPA Senior Fire Safety Engineering Consultant @ ARCADIS Belgium Convener of

More information

Fire Protection for Printing Machines with High Pressure Water Mist

Fire Protection for Printing Machines with High Pressure Water Mist Fire Protection for Printing Machines with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Case Study PRINOVIS Printing Company - PRINOVIS is Europe s

More information

Sprinkler systems. A presentation for fire brigade staff

Sprinkler systems. A presentation for fire brigade staff Sprinkler systems A presentation for fire brigade staff Sprinkler systems Content Sprinkler system benefits Operation by fire brigade FAQ System description Basic system design Sprinkler systems In this

More information

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) Fire Protection Leaflet Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) 0 General Regulations and recommendations missing from this leaflet do not entitle

More information

SOLIT Safety of Life in Tunnels

SOLIT Safety of Life in Tunnels SOLIT Safety of Life in Tunnels Engineering Guidance for a Comprehensive Evaluation of Tunnels with Fixed Fire Fighting Systems using the example of water based Fixed Fire Fighting Systems Scientific Final

More information

High challenge warehouse case study Summary

High challenge warehouse case study Summary High challenge warehouse case study Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation Objectives Review the results of the high challenge warehouse workshop Recognize

More information

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE Satoru Ito 1, Keisuke Tsukada 1, Nobuyoshi Tsuzuki 2, Takao Ishizuka 3 and Hiroshige Kikura 3 1 Department of nuclear Engineering, Graduate

More information

Mobile ventilation units in tunnels

Mobile ventilation units in tunnels Mobile ventilation units in tunnels Xavier Deckers Mathieu Verpaele FIRE ENGINEERED SOLUTIONS GHENT BVBA (FESG) Oudenaardsesteenweg 32 G B - 9000 Gent T: +32 9 280 03 69 E: info@fesg.be W: www.fesg.be

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke

More information

Comparison and Review of Safety Design Guidelines for Road Tunnels

Comparison and Review of Safety Design Guidelines for Road Tunnels Comparison and Review of Safety Design Guidelines for Road Tunnels Hak Kuen Kim, Anders Lönnermark and Haukur Ingason SP Technical Research Institute of Sweden Foto: Håkan Frantzich Fire Technology SP

More information

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations

More information

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-02-07 THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS March, 2007 Society of Fire Protection Engineers - 1 - Position

More information

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION Generals Caccialanza & C. developed in the last years some technologically very innovative products, aimed to provide a very

More information

Economic Impact of Building Regulations

Economic Impact of Building Regulations Economic Impact of Building Regulations Resources from NFPA and the Fire Protection Research Foundation May 9, 2017 Amanda Kimball, P.E.: Research Director Agenda Background NFPA s statistical activities

More information

Detection of Fires in Heavy Duty (HD) Vehicles

Detection of Fires in Heavy Duty (HD) Vehicles Detection of Fires in Heavy Duty (HD) Vehicles Abstract Detection of fires in the engine compartments, toilet compartments, baggage bays and sleeping cabins of Heavy Duty (HD) vehicles is arduous. The

More information

TEHRAN LONG TERM URBAN RAIL PLAN

TEHRAN LONG TERM URBAN RAIL PLAN TEHRAN LONG TERM URBAN RAIL PLAN Introduction and Methodology Introduction Greater Tehran is currently one of the most populated mega cities in the world with an estimated population of 14 million inhabitants

More information

FIXED FIRE FIGHTING SYSTEMS IN ROAD TUNNELS: CURRENT PRACTICES AND RECOMMENDATIONS

FIXED FIRE FIGHTING SYSTEMS IN ROAD TUNNELS: CURRENT PRACTICES AND RECOMMENDATIONS www.piarc.org 2016R03EN FIXED FIRE FIGHTING SYSTEMS IN ROAD TUNNELS: CURRENT PRACTICES AND RECOMMENDATIONS Technical Committee C.3.3 Road Tunnel Operations of the World Road Association STATEMENTS The

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

Development and Full-Scale Tests of a Water Mist System inside High Speed Trains

Development and Full-Scale Tests of a Water Mist System inside High Speed Trains Development and Full-Scale Tests of a Water Mist System inside High Speed Trains Prof. J. A. Capote ; Dr. D. Alvear; Dr. M. Lázaro and Dr. O. Abreu GIDAI - UNIVERSITY OF CANTABRIA www.gidai.unican.es Objetives

More information

September 11, 2012 Ministry of Economy, Trade and Industry

September 11, 2012 Ministry of Economy, Trade and Industry Data 2 Final Report by Heat Pump Water Heater Evaluation Standards Subcommittee, Energy Efficiency Standards Subcommittee of the Advisory Committee for Natural Resources and Energy September 11, 2012 Ministry

More information

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,

More information

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Peter Stahl Wagner Schweiz AG, Wallisellen, Switzerland Abstract Fire detection system and firefighting solutions are getting a

More information

FIRE CONTAINMENT AND CONTROL SYSTEMS

FIRE CONTAINMENT AND CONTROL SYSTEMS FIRE CONTAINMENT AND CONTROL SYSTEMS III INTERNATIONAL CONFERENCE MODERN TRENDS OF FIRE PROTECTION IN ROLLING STOCK WARSAW 2016-05-18 AUTHORS: SERGE MÉTRAL (SNCF) CONVENOR OF CEN TC256 WG1 GUILLAUME CRAVEUR

More information

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Hong-Zeng (Bert) Yu FM Global 16 th International Water Mist Conference September 21-22, 2016 Vienna,

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment AKIHIKO HOKUGO Building Research Institute Ministry of Construction Tatehara I, Tsukuba-City 305, Japan DAVID YUNG and

More information

CFD Analysis of Fire Characteristics on Subway Junction Station

CFD Analysis of Fire Characteristics on Subway Junction Station ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.

More information

Fire Dynamics During the Channel Tunnel Fires

Fire Dynamics During the Channel Tunnel Fires Fire Dynamics During the Channel Tunnel Fires Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh ABSTRACT Three major fire incidents have occurred in the Channel Tunnel since it

More information

NOVENCO CAR PARK THRUST VENTILATION SYSTEM DESCRIPTION. Pure competence in air.

NOVENCO CAR PARK THRUST VENTILATION SYSTEM DESCRIPTION. Pure competence in air. NOVENCO CAR PARK THRUST VENTILATION SYSTEM DESCRIPTION Pure competence in air. PREFACE GROWING NEED Cars have become a natural part of everyday life. Despite widespread public transport systems, most people

More information

REVIEW ON WATER MIST FIRE SUPPRESSION SYSTEM

REVIEW ON WATER MIST FIRE SUPPRESSION SYSTEM , Volume 5, Number 4, p.170-175, 2003 REVIEW ON WATER MIST FIRE SUPPRESSION SYSTEM N. Zhu Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD DESIGNER S GUIDE Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position

More information