SECTION GYPSUM PLASTER

Size: px
Start display at page:

Download "SECTION GYPSUM PLASTER"

Transcription

1 SECTION PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work under this Section shall include all materials and installation for support of gypsum plaster used as a finish for partitions and ceilings B. Related Work Specified Elsewhere: 1.02 REFERENCES 1. Division 5, Section METAL STUD SYSTEM 2. Division 5, Section COLD-FORMED METAL FRAMING A. American Society for Testing and Materials (ASTM) 1.03 SUBMITTALS 1. A641, Specifications for Zinc-Coated (Galvanized) Carbon steel wire 2. C28, Specification for Gypsum Plaster 3. C35, Specification for Inorganic Aggregates for use in Gypsum Plaster 4. C841, Specification for Installation of Interior Lathing and Furring 5. C842, Specification for Application of Interior Gypsum Plaster 6. C847, Specification for Metal Lath 7. C954, Specification for Steel drill screws for the application of Gypsum or metal plaster bases to steel studs from.33 in. to.112 in. in thickness. 8. C1002, Specification for steel drill screws for the application of gypsum board or metal plaster bases. A. General: See Section SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. B. Product Data for each product specified QUALITY ASSURANCE A. Samples: 1. Lath and plaster an actual wall surface for each finish specified to show color, texture, and workmanship. Provide mock-up of at least 10 sq ft. Obtain approval from University s representative of mock-up locations. 2. Simulate finish lighting conditions for the review and approval by University s representative

2 3. Do not begin plastering until mock-up is approved by University s representative. Provide additional mock-ups if necessary to obtain approval. Do not alter mockup until plaster is completed DELIVERY, STORAGE, AND HANDLING A. Deliver cementitious materials to Project site in original packages, containers, or bundles, labeled with manufacturer's name, product brand name, and lot number. B. Store materials inside, under cover, and dry, protected from weather, direct sunlight, surface contamination, aging, corrosion, and damage from construction traffic and other causes PROJECT CONDITIONS A. Environmental Requirements, General: Comply with requirements of referenced plaster application standards and recommendations of plaster manufacturer for environmental conditions before, during, and after plaster application. B. Warm-Weather Requirements: Protect plaster against uneven and excessive evaporation and from strong flows of dry air, both natural and artificial. Apply and cure plaster as required by climatic and job conditions to prevent dry out during cure period. Provide suitable coverings, moist curing, barriers to deflect sunlight and wind, or combinations of these, as required. PART II - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: 1. Metal Framing and Supports shall be by California Expanded Metal Products Co., Consolidated Systems, Inc., Western Metal Lath Co. or equal. 2. Expanded-Metal Lath shall be by California Expanded Metal Products Co., United States Gypsum Co., Western Metal Lath Co., or equal 3. Wire-Fabric Lath shall be by Davis Wire Corporation, Keystone Steel & Wire Co., K-Lath Building Products, or equal 4. Metal Accessories shall be by California Expanded Metal Products Co., Stockton Products, Western Metal Lath Co., or equal 5. Plastic Accessories shall be by Alabama Metal Industries Corp. (AMICO), Plastic Components, Inc., Vinyl Corp., or equal 6. Gypsum Plaster: Gold Bond Building Products, National Gypsum Co, or equal. a. Base plaster: Gold Bond Two-way Hardwall Gypsum plaster b. Finish plaster: Gold Bond Super-White Gauging Plaster

3 2.02 VERTICAL METAL FURRING 2.03 LATH A. General: Provide vertical furring complying with the following requirements: 1. Protective Coating: ASTM A 653, G40 hot-dip galvanized coating. B. Channel Furring and Braces: Cold-rolled steel, minimum thick base (uncoated) metal. 1. Main runners: 2 x 7 / 16 wide flanges ¾ deep-by- 7 / 16 wide flanges, 590 lb/1000 feet. 2. Cross runners: ¾, 300 lb/1000 feet C. Hat Channels: Hat-shaped screwable furring channels, ⅞ deep, formed from zinccoated (galvanized) steel sheet, minimum thick, Grade 33. D. Z-Furring Members: Manufacturer's standard screw-type Z-shaped furring members formed from minimum thick, zinc-coated (galvanized) steel sheet designed for mechanical attachment of insulation boards or blankets to monolithic concrete and masonry walls. E. Furring Brackets: Serrated-arm type, minimum thick base (uncoated) metal, adjustable from ¼ to 2-¼ wall clearance for channel furring. A. Expanded-Metal Lath: Comply with ASTM C 847 for material, type, configuration, and other characteristics indicated below. 1. Material: Fabricate expanded-metal lath from sheet metal conforming to the following: a. Galvanized Steel: Structural-quality, zinc-coated (galvanized) steel sheet complying with ASTM A 653, G60 minimum coating designation, unless otherwise indicated. 2. Diamond-Mesh Lath: Comply with the following requirements: a. Configuration: Flat. 1) Weight: 2.5 lb/sq. yd. 2) Weight: 3.4 lb/sq. yd. B. Paper Backing: Where paper-backed lath is indicated, provide the following material factory bonded to back of lath. Comply with FS UU-B-790, Type-I, grade and style as indicated below: Vapor-Permeable Paper: Grade D, Style 2. A. Base plaster: Gypsum neat plaster complying with ASTM C28 (Gold Bond Two-Way Hardwall Gypsum Plaster)

4 B. Finish Plaster: Gypsum gauging plaster complying with ASTM C28 (Gold Bond Superwhite Gauging Plaster Quick Set and Gold Bond Super-white Gauging Plaster Slow Set. C. Sand: ASTM C35 D. Water: Potable E. Vapor Barrier: 10 mil polyethylene sheet, lapped minimum 6 at all joints 2.05 ACCESSORIES A. General: Comply with material provisions of ASTM C 1063 and the requirements indicated below; coordinate depth of accessories with thicknesses and number of plaster coats required. 1. Aluminum Components: Alloy, temper, and finish recommended by manufacturer with not less than the strength and durability properties of aluminum extrusions complying with ASTM B 221 for alloy and temper 6063-T5. 2. Galvanized Steel Components: Fabricated from zinc-coated (galvanized) steel sheet complying with ASTM A 653, G40 minimum coating designation. 3. Zinc-Alloy Components: ASTM B 69, 99% pure zinc. 4. Plastic Components: ASTM D 4216, high-impact polyvinyl chloride (PVC) for building products. B. Metal Corner Reinforcement: Expanded, large-mesh, diamond-metal lath fabricated from zinc-alloy or welded-wire mesh fabricated from diameter, zinc-coated (galvanized) wire and specially formed to reinforce external corners of portland cement plaster on exterior exposures while allowing full plaster encasement. C. Cornerbeads: Small nose cornerbeads fabricated from the following metal, with expanded flanges of large-mesh diamond-metal lath allowing full plaster encasement. 1. Galvanized Steel: Minimum thick. 2. Aluminum: Minimum thick. D. Control Joints: Prefabricated, of material and type indicated below: 1. Galvanized Steel: Minimum thick. 2. Aluminum: Minimum thick. a. Provide removable protective tape on plaster face of control joints. E. Lath Attachment Devices: Material and type required by ASTM C 1063 for installations indicated PLASTER MIXES AND COMPOSITIONS A. Proportions and Procedures: In accordance with ASTM C842 and manufacturer s recommendations

5 PART III - EXECUTION 3.01 INSTALLATION OF LATH AND FURRING, GENERAL A. Standards: Comply with ML/SFA 920, "Guide Specifications for Metal Lathing and Furring," and with requirements of ASTM C B. Install supplementary framing, blocking, and bracing at terminations in work and for support of fixtures, equipment services, heavy trim, grab bars, handrails, furnishings, and similar work to comply with details indicated or, if not otherwise indicated, to comply with applicable written instructions of lath and furring manufacturer. C. Isolation: Where lathing and metal support system abuts building structure horizontally and where partition or wall abuts overhead structure, sufficiently isolate from structural movement to prevent transfer of loading from building structure. Install slip- or cushion-type joints to absorb deflections but maintain lateral support. 1. Frame both sides of control joints independently and do not bridge joints with furring and lathing or accessories. D. Install additional framing, furring, runners, lath, and beads, as required to form openings and frames for other work as indicated. Coordinate support system for proper support of framed work that is not indicated to be supported independently of metal furring and lathing system. 1. Extend and attach partition support systems to structure above suspended ceilings, unless 3.02 INSTALLATION OF VERTICAL METAL FURRING A. Install vertical metal furring components of sizes and spacings indicated, but not in smaller sizes or greater spacings than those required by referenced ML/SFA standard. B. Metal Furring to Receive Metal Lath: Comply with requirements of ML/SFA 920, "Guide Specifications for Metal Lathing and Furring," applicable to each installation condition indicated LATHING A. Install metal lath for the following applications where plaster base coats are required. Provide appropriate type, configuration, and weight of metal lath selected from materials indicated that comply with referenced ML/SFA specifications and ASTM lathing installation standards. 1. Exterior sheathed wall surfaces using 3.4-lb/sq. yd. minimum weight, self-furring, diamond-mesh lath PREPARATIONS FOR PLASTERING A. Clean plaster bases and substrates for direct application of plaster, removing loose material and substances that may impair the Work. B. Surface Conditioning: Immediately before plastering, dampen concrete and concrete unit masonry surfaces that are indicated for direct plaster application, except where a bonding

6 agent has been applied. Determine and apply amount of moisture and degree of saturation that will result in optimum suction for plastering INSTALLATION OF PLASTERING ACCESSORIES A. General: Comply with referenced lathing and furring installation standards for provision and location of plaster accessories of type indicated. Miter or cope accessories at corners; install with tight joints and in alignment. Attach accessories securely to plaster bases to hold accessories in place and in alignment during plastering. Install accessories of type indicated at following locations: 1. External Corners: Install corner reinforcement at external corners. 2. Terminations of Plaster: Install casing beads, unless otherwise indicated. 3. Control Joints: Install at locations indicated or, if not indicated, at locations complying with the following criteria and approved by University s Representative: 3.06 PLASTER APPLICATION a. Where an expansion or contraction joint occurs in surface of construction directly behind plaster membrane. b. Distance between Control Joints: Not to exceed 18 in either direction or a length-to-width ratio of 2-½ to 1. c. Wall Areas: Not more than 144 sq. ft. d. Horizontal Surfaces: Not more than 100 sq. ft. in area. e. Where plaster panel sizes or dimensions change, extend joints full width or height of plaster membrane. A. Plaster Application Standard: Apply plaster materials, composition, and mixes to comply with ASTM C 842 B. Do not use materials that are frozen, caked, lumpy, dirty, or contaminated by foreign materials. C. Do not use excessive water in mixing and applying plaster materials. D. Flat Surface Tolerances: Do not deviate more than plus or minus ⅛ in 10 from a true plane in finished plaster surfaces, as measured by a 10 straightedge placed at any location on surface. E. Grout hollow-metal frames, bases, and similar work occurring in plastered areas, with base-coat plaster material, and before lathing where necessary. Except where full grouting is indicated or required for fire-resistance rating, grout at least 6 at each jamb anchor. F. Sequence plaster application with installation and protection of other work so that neither will be damaged by installation of other

7 G. Corners: Make internal corners and angles square; finish external corners flush with cornerbeads on interior work, square and true with plaster faces on exterior work. H. Number of Coats: Apply plaster of composition indicated, to comply with the following requirements: 1. Three Coats: Over the following plaster base: a. Metal lath. b. Finish Coats: Apply finish coats to comply with the following requirements: 2. Float Finish: Apply finish coat to a minimum thickness of ⅛ to completely cover base coat, uniformly floated to a true even plane with fine-textured finish matching University's Representatives sample. 3. Prepared Finish: Apply stucco finish coats, according to manufacturer's written instructions. I. Moist-cure plaster base and finish coats to comply with ASTM C 841, including written instructions for time between coats and curing in "Annex A2 Design Considerations." 3.07 CUTTING AND PATCHING A. Cut, patch, replace, repair, and point up plaster as necessary to accommodate other work. Repair cracks and indented surfaces. Point-up finish plaster surfaces around items that are built into or penetrate plaster surfaces. Repair or replace work to eliminate blisters, buckles, check cracking, dry outs, efflorescence, excessive pinholes, and similar defects. Repair or replace work as necessary to comply with required visual effects CLEANING AND PROTECTING A. Remove temporary covering and other provisions made to minimize spattering of plaster on other work. Promptly remove plaster from doorframes, windows, and other surfaces not to be plastered. Repair surfaces stained, marred or otherwise damaged during plastering work. When plastering work is completed, remove unused materials, containers, equipment, and plaster debris. B. Provide final protection and maintain conditions, in a manner acceptable to manufacturer and Installer that ensure plaster work is without damage or deterioration at the time of Substantial Completion. END OF SECTION

SPECIAL SPECIFICATION 2242 LATH, STUCCO AND PLASTER

SPECIAL SPECIFICATION 2242 LATH, STUCCO AND PLASTER 2004 Specifications CSJ: 0921-02-314 SPECIAL SPECIFICATION 2242 LATH, STUCCO AND PLASTER 1.1 DESCRIPTION A. Section Includes 1. This Item shall govern for the installation of lath, stucco and plaster particularly

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES SECTION 105200 - FIRE-PROTECTION SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

1. Vinyl wall covering. 2. Woven glass-fiber wall covering. 3. Textile wall covering. 4. Wallpaper. 5. Heavy-duty, synthetic, textile wall covering.

1. Vinyl wall covering. 2. Woven glass-fiber wall covering. 3. Textile wall covering. 4. Wallpaper. 5. Heavy-duty, synthetic, textile wall covering. SECTION 09950 - WALL COVERINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Section Plaster Accessories

Section Plaster Accessories Section 09209 Plaster Accessories PART 1 - GENERAL 1.1 SUMMARY A. Related work specified elsewhere includes: 1. Rough carpentry. 2. Finish carpentry and millwork. 3. Metal support systems. 4. Furring and

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-09 23 00 (August 2016) --------------------------- Preparing Activity: NAVFAC Superseding UFGS-09 23 00 (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

1. Portable fire extinguishers. 2. Fire-protection cabinets for portable fire extinguishers.

1. Portable fire extinguishers. 2. Fire-protection cabinets for portable fire extinguishers. SECTION 10 44 13 - FIRE-PROTECTION SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018 SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION FIRE EXTINGUISHER CABINETS

SECTION FIRE EXTINGUISHER CABINETS SECTION 104413 FIRE EXTINGUISHER CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017 SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 104413 FIRE EXTINGUISHER CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

EXAMPLE SPECIFICATION ONLY

EXAMPLE SPECIFICATION ONLY SECTION 097200 WALL COVERINGS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Prime Agreement, including General and Supplementary Conditions, when referenced by the Prime

More information

Product Guide Specification

Product Guide Specification Simonton Windows December 2012 3948 Townsfair Way, Suite 200 Columbus, Ohio 43219 Toll Free 800-746-6686 Website www.simonton.com E-Mail archdetails@simonton.com Product Guide Specification Specifier Notes:

More information

REFRIGERANT PIPING SYSTEM

REFRIGERANT PIPING SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The requirements of this section apply to the refrigerant piping system connecting refrigeration and HVAC equipment specified in other sections of these specifications.

More information

Product Guide Specification

Product Guide Specification December 2012 3948 Townsfair Way, Suite 200 Columbus, Ohio 43219 Toll Free 800-746-6686 Website www.simonton.com E-Mail archdetails@simonton.com Product Guide Specification Specifier Notes: This product

More information

SECTION DOMESTIC WATER HEATERS

SECTION DOMESTIC WATER HEATERS SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017 SECTION 104413 - FIRE PROTECTION CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

c. Oko-Tex (European environmental health standard)

c. Oko-Tex (European environmental health standard) SECTION 09720 Wall Covering Texturglas WALL FINISH SYSTEM GENERAL 1.1 SUMMARY A. Section Includes: Texturglas Wall Finish System. B. Related Sections: Section(s) related to this section include: 1. Gypsum

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

SECTION OVERHEAD COILING FIRE DOORS

SECTION OVERHEAD COILING FIRE DOORS SECTION 08331 OVERHEAD COILING FIRE DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on round Windows logo in top left corner,

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup. SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009. SECTION 235100 - BREECHINGS, CHIMNEYS, AND STACKS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fabricated breechings. B. Manufactured chimneys for gas fired equipment. C. Manufactured double wall chimneys for

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 3300 - ELECTRIC, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

MD Series MEDIUM DUTY SERVICE DOORS. superior product + recognized value

MD Series MEDIUM DUTY SERVICE DOORS. superior product + recognized value MD Series MEDIUM DUTY SERVICE DOORS superior product + recognized value The Roll Up Doors Direct MD Series medium duty service door is a true crossover commercial system that successfully bridges the gap

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening. DIVISION 8 OPENINGS SECTION 08 33 23 PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead coiling counter fire doors. 1.2 RELATED SECTIONS A. Section 05500 - Metal Fabrications: Support framing and framed opening.

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

SECTION AIR OUTLETS AND INLETS

SECTION AIR OUTLETS AND INLETS SECTION 23 37 00 AIR OUTLETS AND INLETS PART 1 - GENERAL 1.1 SUMMARY A. Section includes diffusers, light troffer diffusers, registers/grilles, door grilles, louvers, louvered penthouses, roof hoods, goosenecks.

More information

oem OEM 1" Between the Glass Metal Blind Series P2100 Included:

oem OEM 1 Between the Glass Metal Blind Series P2100 Included: OEM 1" Between the Glass Metal Blind Series P2100 Included: Specifications ^Overview Diagram oem S H D E S INC 700 First Avenue, Ford City, PA 16226 Phone. 724-763-3600 Fax: 724-763-3601 www.oemshades.com

More information

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating. SECTION 15890 DUCTWORK PART 1 - GENERAL 1.1 SECTION INCLUDES A. Metal ductwork. B. Duct cleaning. 1.2 RELATED SECTIONS A. Section 09900 - Painting: Weld priming, weather resistant, paint or coating. B.

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED

More information

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY Welcome to the SAFTIFIRST TM Guide Specification System prepared as an aid to specifiers in preparing written construction documents. For specification assistance with specific product applications, please

More information

A. Provide products and workmanship in accordance to: (Where applicable)

A. Provide products and workmanship in accordance to: (Where applicable) SECTION 10 00 00 SPECIALTIES PART 1 GENERAL 1.1 SUMMARY A. Section includes: 1. Fire Extinguishers, Cabinets, and brackets. 2. Wire Shelving. 3. Coat Racks. B. Related Sections: Documents relating to the

More information

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for detention furniture.

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for detention furniture. SECTION 125500-WALL BED SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SPECIAL SPECIFICATION 3687 Impermeable Liner

SPECIAL SPECIFICATION 3687 Impermeable Liner 1993 Specifications CSJ s 0569-01-043 & 0945-04-025 SPECIAL SPECIFICATION 3687 Impermeable Liner 1. Description. This Item shall govern for the furnishing and installation of the impermeable liner (geomembrane)

More information

SECTION 02230BP AGGREGATE BASE

SECTION 02230BP AGGREGATE BASE SECTION 02230BP AGGREGATE BASE This page is intentionally left blank. Fluor-B&W Portsmouth, LLC (FBP) SITE PREPARATION INFRASTRUCTURE PHASE 1 SPECIFICATION COVER SHEET Client: U.S. Department of Energy

More information

SECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text. SECTION 14 42 13 XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp. Volume 1 Bidding Requirements, Contract Forms, Conditions of the Contract, Division 1, Architectural and Site Specifications 000107 Certification Page 000110 Table of Contents DIV00 PROCUREMENT AND CONTRACTING

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

ARCHITECTURAL PAVING STONE PRODUCT CATALOG

ARCHITECTURAL PAVING STONE PRODUCT CATALOG ARCHITECTURAL PAVING STONE PRODUCT CATALOG ARCHITECTURAL PAVING STONES - 360, H STREET, WASHINGTON, D.C. ARCHITECTURAL PAVING STONE Nitterhouse s high strength Architectural Pavers combine durability with

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS SECTION 22 36 01 ELECTRIC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION (15820) - AIR DUCT ACCESSORIES

SECTION (15820) - AIR DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Section includes: SECTION 23 33 00 (15820) - AIR DUCT ACCESSORIES 1. Manual-Volume Dampers 2. Fire Dampers 3. Turning Vanes 4. Duct-Mounted Access Doors 5. Flexible Connectors

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Impermeable Liner

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Impermeable Liner 1993 Specifications CSJ 0128-01-085 SPECIAL SPECIFICATION ITEM 5327 Impermeable Liner 1. Description. This Item shall govern for the furnishing and installation of the impermeable liner (geomembrane) shown

More information

SECTION (09950) - WALL COVERINGS

SECTION (09950) - WALL COVERINGS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 09 72 00 (09950) - WALL COVERINGS 1. Vinyl Wall Covering a. Furnished by Owner, installed by Contract 2. Prime Coat on Walls 3. Adhesives and Cleaning

More information

Standard Specification for Hardened Steel Washers [Metric] 1

Standard Specification for Hardened Steel Washers [Metric] 1 Designation: F 436M 93 (Reapproved 2000) METRIC Standard Specification for Hardened Steel Washers [Metric] 1 This standard is issued under the fixed designation F 436M; the number immediately following

More information

SECTION Overhead Coiling Doors

SECTION Overhead Coiling Doors SECTION 08 33 00 Overhead Coiling Doors To display hidden notes to specifier, select tools/ options/ view/ hidden text. GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

INSULATED COLD STORAGE ROOMS (FOAMED IN-PLACE INSULATED PANELS)

INSULATED COLD STORAGE ROOMS (FOAMED IN-PLACE INSULATED PANELS) SECTION 11400 INSULATED COLD STORAGE ROOMS (FOAMED IN-PLACE INSULATED PANELS) PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Pre-fabricated, free standing walk-in cooler/freezer rooms, metal clad, designed

More information

Standard Specification for Hardened Steel Washers [Metric] 1

Standard Specification for Hardened Steel Washers [Metric] 1 Designation: F 436M 03 METRIC Standard Specification for Hardened Steel Washers [Metric] 1 This standard is issued under the fixed designation F 436M; the number immediately following the designation indicates

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

E. Luminaire: Complete lighting fixture, including ballast housing if provided.

E. Luminaire: Complete lighting fixture, including ballast housing if provided. SECTION 16511 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 16 Specification

More information

ALUMINUM. ELEVATED. CEDAR RENDITIONS DESIGN SERIES INSTALLATION INSTRUCTIONS

ALUMINUM. ELEVATED. CEDAR RENDITIONS DESIGN SERIES INSTALLATION INSTRUCTIONS ALUMINUM. ELEVATED. CEDAR RENDITIONS DESIGN SERIES INSTALLATION INSTRUCTIONS CEDAR RENDITIONS BY ROYAL 2 INSTALLATION INSTRUCTIONS TABLE OF CONTENTS Important Notes...5 Wall Preparation...7 Installation

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 22 63 13 GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016 SECTION 23 21 23 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section.

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

SECTION OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS

SECTION OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS SECTION 08331 OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION DUCTWORK

SECTION DUCTWORK PART 1 GENERAL 1.1 REFERENCES SECTION 23 31 00 DUCTWORK A. ASHRAE - Handbook, Duct Design B. ASHRAE - Handbook, Duct Construction C. ASTM A90/A90M - Standard Test Method for Weight (Mass) of Coating on

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

FOR PROJECTS INITIATED AFTER FEBRUARY 1, 2010 REVISION 1 ITEM 709 TRIANGULAR FILTER FABRIC FENCE

FOR PROJECTS INITIATED AFTER FEBRUARY 1, 2010 REVISION 1 ITEM 709 TRIANGULAR FILTER FABRIC FENCE AFTER FEBRUARY 1, 2010 ITEM 709 TRIANGULAR FILTER FABRIC FENCE 709.1 Description. This work shall consist of furnishing, installing, and removing temporary erosion protection and sediment control triangular

More information

DARTMOUTH COLLEGE DESIGN March 15, 2003 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN March 15, 2003 & CONSTRUCTION GUIDELINES SECTION 15830 HEATING & COOLING TERMINAL UNITS PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. All fan coil units shall be sized to meet design load while operating at medium speed. In extreme noise sensitive

More information

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperLite TM I-XL minute SuperLite TM I-XL IGU minute PART 1 GENERAL

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperLite TM I-XL minute SuperLite TM I-XL IGU minute PART 1 GENERAL Welcome to the SAFTIFIRST TM Guide Specification System prepared as an aid to specifiers in preparing written construction documents. For specification assistance with specific product applications, please

More information

Installation Manual May 9/14 No revision

Installation Manual May 9/14 No revision 815 NE 172 nd Avenue Vancouver, WA 98684 877-694-0141 Installation Manual May 9/14 No revision Installation steps include job planning, layout, excavating and preparing the soil subgrade, applying geotextiles

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY STANDARD SPECIFICATION. Section SODDING

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY STANDARD SPECIFICATION. Section SODDING Section 02922 PART 1 GENERAL 1.01 SUMMARY This Section includes the following: A. Restoration of existing lawn areas disturbed by construction shall be by installation of new sod. B. Planting of sod within

More information

815 NE 172 nd Avenue Vancouver, WA Installation Manual

815 NE 172 nd Avenue Vancouver, WA Installation Manual 815 NE 172 nd Avenue Vancouver, WA 98684 800-377-3877 www.xeripave.com info@xeripave.com Installation Manual Installation steps include job planning, layout, excavating and preparing the soil sub grade,

More information

A. Provisions of the General and Supplementary Conditions and Division 01 apply to this section. 1. Steel Shelving, counters, and storage cabinets

A. Provisions of the General and Supplementary Conditions and Division 01 apply to this section. 1. Steel Shelving, counters, and storage cabinets DIVISION 10 - SPECIALTIES SECTION 10671 METAL STORAGE SHELVING PART 1 GENERAL 1.1 SUMMARY A. Provisions of the General and Supplementary Conditions and Division 01 apply to this section. B. Section Includes

More information

WALLCOVERINGS WALLCOVERINGS

WALLCOVERINGS WALLCOVERINGS 09950 - WALLCOVERINGS 09950-1 PART ONE: GENERAL 1.1 Description WALLCOVERINGS 1.1.1 Work of this Section, as shown or specified, shall be provided by the Interior Contractor and shall be in accordance

More information

Tectum Direct-Attach Ceiling and Wall Panels Assembly and Installation Instructions for 1-Inch Thick Direct-Attach Wall and Ceiling Panels

Tectum Direct-Attach Ceiling and Wall Panels Assembly and Installation Instructions for 1-Inch Thick Direct-Attach Wall and Ceiling Panels Tectum Direct-Attach Ceiling and Wall Panels Assembly and Installation Instructions for 1-Inch Thick Direct-Attach Wall and Ceiling Panels TECTUM DIRECT-ATTACH WALL AND CEILING PANELS STANDARD ITEMS: Item

More information

DIVISION 10 SPECIALTIES

DIVISION 10 SPECIALTIES DIVISION 10 SPECIALTIES 11/11 SECTION 10 21 13.16 PLASTIC LAMINATE TOILET COMPARTMENTS PART 1 - GENERAL 1.01 SECTION INCLUDES Plastic laminate toilet compartments, urinal screens, head rail braced. 1.02

More information

Tile Tech Warnings. Paving America one step at a time! MANUFACTURER OF DETECTABLE WARNING PAVERS AND TILES

Tile Tech Warnings. Paving America one step at a time! MANUFACTURER OF DETECTABLE WARNING PAVERS AND TILES Tile Tech Warnings Paving America one step at a time! MANUFACTURER OF DETECTABLE WARNING PAVERS AND TILES 2 T a b l e o f C o n t e n t s Applications Roof Decks Plaza Decks Pool Decks... 3 Warning Pavers

More information

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY Welcome to the SAFTIFIRST TM Guide Specification System prepared as an aid to specifiers in preparing written construction documents. For specification assistance with specific product applications, please

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

A. Section Masonry Assemblies: Anchor placement in masonry.

A. Section Masonry Assemblies: Anchor placement in masonry. SECTION 14420 WHEEL CHAIR LIFT PART 1 - GENERAL 1.1 RELATED DOCUMENTS PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform wheelchair lifts. 1.2 RELATED SECTIONS A. Section 04800 - Masonry Assemblies:

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

INTERNAL FRAMING PROFILES

INTERNAL FRAMING PROFILES INTERNAL FRAMING PROFILES Ceiling Furring Sections Dry-Wall Partitioning Sections Angle Beads And Accessories About the Hadley Group Hadley Industries is one of Europe s leading manufacturers of cold rollformed

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

Design Options Analysis on a Heat Wrap used on PVC Pipe Connections in Cold Weather Conditions

Design Options Analysis on a Heat Wrap used on PVC Pipe Connections in Cold Weather Conditions Design Options Analysis on a Heat Wrap used on PVC Pipe Connections in Cold Weather Conditions Bruce W. Smith, CPC and Clint W. Carroll, MS Auburn University Auburn, Alabama Cold weather conditions produce

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

INSULATED COLD STORAGE ROOMS (FOAMED IN-PLACE INSULATED PANELS)

INSULATED COLD STORAGE ROOMS (FOAMED IN-PLACE INSULATED PANELS) SECTION 11400 INSULATED COLD STORAGE ROOMS (FOAMED IN-PLACE INSULATED PANELS) PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Pre-fabricated, free standing walk-in cooler/freezer rooms, metal clad, designed

More information

a. Section includes planting soils specified by composition of the mixes.

a. Section includes planting soils specified by composition of the mixes. SECTION 32 9113 SOIL PREPARATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work

More information

Knauf Direct Bonding and Metal Furring

Knauf Direct Bonding and Metal Furring Knauf Direct Bonding and Metal Furring Knauf Direct Bonding and Metal Furring Linings are the simplest and quickest of drylining systems to install. They are suitable for most brick, block and concrete

More information

Pedimat Installation Instructions

Pedimat Installation Instructions Pedimat Installation Instructions Table of Contents Level Base.. Page 3-5 Tapered Angle Frame.. Page 6-7 Pipestem Frame. Page 8-9 Surface Mounted Aluminum Frame.....Page 10-11 Surface Mounted Tapered Frame......Page

More information

REFRIGERANT PIPING

REFRIGERANT PIPING SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A U TO S M O K E. Model AUTO SMOKE FIRE SHUT Flat Slats Fire Shut Rolling Doors

A U TO S M O K E. Model AUTO SMOKE FIRE SHUT Flat Slats Fire Shut Rolling Doors Model AUTO SMOKE Flat Slats Fire Shut Rolling Doors NOTE: For specifications, architects must choose from a variety of options. The standard choice will be shown first in plain text followed by the options

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SECTION INCLUDES A. Water heaters. B. Packaged water heating systems. C. Domestic water heat exchangers. D. Water storage tanks. E. Water softeners. F. Reverse osmosis equipment. G.

More information

ARBOR SERIES DIVISION FLEXIBLE WOOD VENEER WALLCOVERING

ARBOR SERIES DIVISION FLEXIBLE WOOD VENEER WALLCOVERING PART 1 - GENERAL 1.01 SUMMARY A. Provide wood wallcovering, complete. B. Related Sections 1. Section 165000 - Lighting: Permanent during installation. 2. Section 092500 - Gypsum Board: Wall Substrates.

More information

Innovative Services Give Dayton Contractor A Big Edge

Innovative Services Give Dayton Contractor A Big Edge Case Study Innovative Services Give Dayton Contractor A Big Edge Longtime active AWCI member firm James C. Oren and Associates believes that offering more than traditional surface finishes has paid off

More information