Cosmetology Lab Redesign
|
|
- Jewel Newman
- 5 years ago
- Views:
Transcription
1 Cosmetology Lab Redesign Shane A. Semple /5/2005
2 Design Concept: The Cosmetology Lab is a space that will be used for teaching students the trades of cutting hair, applying make-up, and doing manicures. The space will also be open to the public for people who want to get an inexpensive hair cut or makeover. First and foremost, this space is a learning laboratory. As such, the main goal of the lighting should be functionality, and to provide the best lighting system to aid the student s learning. However; the space is also a retail environment, which leads to the necessity of an attractive lighting system that keeps costumers pleased with their experience. This space also provided an opportunity to add daylight to the school. Daylight can save the school money in energy usage costs and is obviously very important for any LEED rated building. In the original design, there is one 6 X5 window at a height of 7 above finished floor in the northeast wall. The long side of the space, which faces southeast, had no windows. Addition of daylight will aid in the overall concept of having an efficient and natural feeling lighting system. This design concept led to this final design: Recessed Linear Fluorescent fixtures used for general lighting. Linear Fluorescent fixtures recessed vertically into the haircut stations to provide facial lighting for the patrons. Only overhead lighting was present in the original design which would likely cause socket shadows on the faces of people getting makeovers and hair cuts. The addition of frontal lighting will fill in those shadows and make faces more attractive. Addition of a clerestory the length of the southeast side of the space. Skylight additions were considered, but due to the cluttered ceiling plenum, they would not be possible in this space. An overhang will be constructed on the exterior of the building to block direct sunlight for the majority of the time the space is in use, and vertical blinds will be provided to block any unwanted direct sunlight. The vertical blinds will utilize a pearl linen sun screen fabric, with 5% openness. The blinds and fabric will be provided by Lutron. Design Criteria and Goals: The following design criteria are taken from the IESNA handbook, as well as the ideas of the designer. Facial Modeling Extremely important that customers looking in mirrors are not poorly illuminated. Color Appearance and Contrast CRI at least 80. Use of makeup and hair dye leads to necessity of excellent color rendering. Shane A. Semple /5/2005
3 Daylight Integration Provide a dimming system that works with the level of daylight. Horizontal and Vertical Illumination: 50 fc and 30 fc respectively. ASHRAE 90.1 Allowance: 2.1 W/sq. ft Goal Power Density: 1.5 W/sq. ft. Lighting Equipment: (Please refer to appendix for product cut sheets) Luminaires Lamps Fixture Type Number Manufacturer Catalog # CRI CCT Initial Lumens Lumen Maintenance G 4' T5 HO 1 Sylvania FP54830HOECO H 4-Pin CF 1 Sylvania FP28830ECO Ballasts Fixture Type Lamps Manufacturer Catalog # Input Watts G Fluorescent Dimming H Fluorescent Dimming Ballast Factor Power Factor 1 Advance VZT / / Lutron ECO-T ?/69 0.1/1 >0.95 Light Loss Factors Fixture BF Maintenance Cleaning RSDD LDD LLD Total LLF Category Interval G 1 V Clean-12 Mo H 1 V Clean-12 Mo Shane A. Semple /5/2005
4 Lighting Plan: Shane A. Semple /5/2005
5 New Wall Elevation: New Wall Section: Shane A. Semple /5/2005
6 The angle of 46 degrees was chosen for the overhang based on the angle of the sun in Newark, Ohio on March 21 at noon. Panelboard Data: All fixtures will be connected to circuit LPC-12, which is currently used only for luminaires in this space. Hatched fixtures will be wired with emergency ballasts in case of outages. In addition to the luminaires, the vertical blinds will require power. They will be fed by the 208/120 V circuit RPC2-35, which is currently a spare. The total load will be under 2 amps Circuit AWG Breaker Load Size (KW) LPC-12 # Circuit AWG Breaker Load Size (KW) RPC2-35 # Power Density: Floor Area = 3015 ft 2 Fixture G = 30 Ballasts x 63 W/Ballast Fixture H = 25 Ballasts x 69 W/Ballast Total = 3615 W = 1890 W = 1725 W Power Density = 3615 W/3015 ft 2 = 1.2 W/ ft 2 << 1.5 W/ft 2 This is roughly 40% below the ASHRAE allowance of 2.1 W/ft 2 Shane A. Semple /5/2005
7 Calculations: All grids except the desk grid are placed at 4 AFF, to show illumination on top of the heads of people getting their hair cut. This will essentially be the working plane for a lab of this type. Shane A. Semple /5/2005
Surface Materials. Surface Material Reflectance. Acoustic Ceiling 80% Tile. Painted Gypsum 75% Wall Board. Vinyl Composition 32% Tile
Genetics Laboratory Space Description The Genetics Laboratory is located on the second floor of the laboratory building. The main functions of this space are as a learning and research area. There is a
More informationOverview. The Reading Room
Overview The library for is the largest space in the George E. Bello Center. This space not only houses all the school s books and reference material, but there are computer terminals set up for students
More informationDuke Tower Main Entrance Lobby Overview
Duke Tower Main Entrance Lobby Overview This is the main entrance to the building that is located in the prominent tower portion of the building. The floor of this lobby has the Duke University School
More informationAdvanced Lighting For Office
Advanced Lighting For Office Open-Plan Office Applications High-Density 1 This High-Density 1 lighting application module presents alternative energy effective lighting design options for open-plan offices.
More informationLobby Lighting Redesign
Lobby Lighting Redesign Description of Space The lobby is located on the first floor of the building. Upon entering the building through the curved façade that features large expanses of glass, one would
More informationTechnical Report One
Technical Report One Yale Sculpture Building Lighting Conditions and Design Criteria Report: Technical Report 1 10.05.06 Prepared for: Dr. Richard Mistrick CC: Ted Dannerth Date: October 6, 2006 Executive
More informationCafé DUSON- Overview
Café DUSON- Overview Café DUSON is a study lounge with seating and tables to seat approximately 65 people in an area of about 1850 SF. The café is a double high space with full height windows on the North
More informationExterior Façade Lighting Design
Exterior Façade Lighting Design Duques Hall is located on George Washington campus in downtown Washington DC. It is located amidst some other university buildings, however, the façade is very visible from
More informationLobby Lighting Design
Lobby Lighting Design The main lobby in Duques is hall is located on the first and second floor of the building. It is the main pathway in and out of the building for the more important spaces, such as
More information1.0 Introduction to Lighting Depth. 1.1 Hotel Tower Facace and Porte Cochere
1.0 Introduction to Lighting Depth Dover Downs is primarily used for entertainment for the wealthy. When people go somewhere to spend money expectations are higher than usual. The lighting design for Dover
More informationThe Bahen Centre for Information Technology. Meeting Room Lighting Redesign. Introduction. University of Toronto ~ Toronto, Ontario, Canada
Meeting Room Lighting Redesign Meeting Room #4287 Introduction The Meeting Room (room #4287) is located on the fourth floor within the grand spiral staircase in the atrium. The room is shaped like half
More information2.0 Lighting Depth Introduction
2.0 Lighting Depth Introduction The lighting for four different spaces, the business news open office, first floor cafeteria seating, east lobby, and east façade, were analyzed and redesigned. The existing
More informationUniversity of California Santa Barbara. Student Resource Building
Student Resource Building Technical Assignment 1 October 16 th, 2006 1 Executive Summary The following report seeks to address the conditions of the proposed lighting system at the Student Resource Building
More informationTechnical Assignment I
WHEELOCK COLLEGE CAMPUS CENTER AND STUDENT RESIDENCE 200 THE RIVERWAY, BOSTON, MA 02215 Technical Assignment I Lighting Existing Conditions and Design Criteria E X E C U T I V E S U M M A R Y The lighting
More informationLighting Existing Conditions and Design Criteria Report
page 1 of 19 Lighting Existing Conditions and Design Criteria Report The lighting in the includes very general lighting used in buildings with an office type setting. The fixture schedule for the Hall
More informationThe Children s storytelling area
Purpose of Space The Children s storytelling area This area has a circular seating pattern, in different levels going up. Its intended use is for librarians, parents, or young adults to read to children.
More informationTechnical Report #1 Existing Lighting Conditions and Design Criteria
Technical Report #1 Existing Lighting Conditions and Design Criteria Lighting/Electrical Faculty Consultant: Table of Contents Executive Summary 1 Classroom A 2 Firing Range Area 8 Lobby and Corridors
More informationExecutive Summary. CNBC Global Headquarters Christine Cajilig
Executive Summary This report contains information about the existing lighting conditions for the CNBC Global Headquarters in Englewood Cliffs, New Jersey, including hardware, controls, power density,
More informationJennifer Mers. Rio Hondo Library and Learning Resource Center. Executive Summary. General Building. Lighting/Electrical Option
Executive Summary This assignment goes into depth into the existing lighting conditions of the Rio Hondo Library and Learning. The lobby, Reference Stacks and Microfilm Area, the Stack Area on the second
More informationLord Stirling Community School
Lord Stirling Community School Schematic Design Proposal AE Senior Thesis Nehal M. Youssef About the Building A new face for an old town The building of the Lord Stirling Community School was the beginning
More informationLIGHTING NORTH FAÇADE AND PLAZA
LIGHTING NORTH FAÇADE AND PLAZA The main entry to UCI Natural Science Unit II is marked by a four-story glass curtain wall, an outdoor stair feature and a 5875 square foot landscaped plaza. Trees are located
More informationL ig h t in g Dept h 8
Ligh t in g Dept h 8 Lighting Depth The Woolly Mammoth Theatre Company is a very unique group. They have a mission to provide new and edgy productions to the community. Therefore, when designing their
More informationLighting Existing Conditions and Design Criteria Report
The building was constructed a few years ago to act as both a Headquarters and to be a display of what the product they manufacture can accomplish when put to work. The architecture of the building was
More informationLighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY
Lighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY The Lighting Existing Conditions and Design Criteria Report will examine the existing lighting conditions in the (in general and
More informationEric Anderson. Technical Report 1. Existing Lighting Conditions
Eric Anderson Technical Report 1 Existing Lighting Conditions Executive Summary: The contents of Technical Report One include the evaluation of the lighting design and basic features of The Web Shop: The
More informationSouth Nassau Communities Hospital North Addition
1 South Nassau Communities Hospital North Addition Carl Speroff Lighting Electrical Faculty Advisor: Dr. Kevin Houser 4 October 2010 AGI files located on Y Drive folder CAS Thesis 2 Executive Summary The
More informationGathering Space. Function and Orientation. Space Characteristics Gregory Wolfe 2004 Senior Thesis Lighting / Electrical
Gathering Space Function and Orientation The gathering space and reception area on the first floor is the first space you encounter upon entering the Westwood Community Church. As such, its purpose is
More informationREVISIONS Summary of Change. 6/1/12 All Replaced entire document with new revision
Revision Date Section REVISIONS Summary of Change 6/1/12 All Replaced entire document with new revision REV 6/12 1 of 5 UNIVERSITY CONTACT: EXTERIOR LIGHTING Electrical Services, Maintenance & Operations
More informationMarie Ostrowski Lighting/Electrical Dr. Mistrick Science Building Phase 1 Buffalo State College Buffalo, NY Monday, October 5, 2009 Technical Report
2009 Marie Ostrowski Lighting/Electrical Dr. Mistrick Science Building Phase 1 Buffalo State College Buffalo, NY Monday, October 5, 2009 Technical Report 1 Executive Summary The Science Building addition
More informationLindsey Beane. Executive Summary
Executive Summary The purpose of this technical assignment is to compile lighting information and make an analysis about the existing spaces. This report will include a list of the equipment used, required
More informationTABLE OF CONTENTS 3 5.PART 1: EXISTING SPACE AND LIGHTING CONDITIONS 6 8.PART 2: LIGHTING DESIGN CRITERIA
TABLE OF CONTENTS 2. EXECUTIVE SUMMARY CLASSROOM 3 07 3 5.PART 1: EXISTING SPACE AND LIGHTING CONDITIONS 6 8.PART 2: LIGHTING DESIGN CRITERIA 9 12..PART 3: LIGHTING DESIGN CRITIQUE 13 CLASSROOM FLOOR PLAN
More informationSteve Neimeister 8 October 2003 AE 481W AstroPower Headquarters Newark, Delaware Lighting/Electrical Option Consultant: M. Moeck
EXECUTIVE SUMMARY The will examine the existing lighting conditions in the (in general and specifically in the five spaces that will be redesigned) and compare it with respect to the IESNA lighting design
More information1.1.0 Exterior Facade
1.1.0 Exterior Facade 1.1.1 Introduction As a primary marketing tool for potential residents unfamiliar with the Rochester area, the façade lighting calls for aesthetic appeal that meets the requirements
More informationMultipurpose Room. Existing Conditions General Overview. Mark W. Miller Sibley memorial Hospital Grand Oaks Washington, DC
Multipurpose Room ` N Figure 1: 1 st Floor Plan Multipurpose Room Location Existing Conditions General Overview The Multipurpose Room, as the name implies, serves as a multifunctional space for the Assisted
More informationLighting Existing Conditions and Design Criteria Report
Lighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY This report will describe the existing lighting system of the specific spaces of my redesign the auditorium, the atrium, the outdoor
More informationThe AstroPower Headquarters Newark, Delaware
The AstroPower Headquarters Newark, Delaware Steven A. Neimeister The Pennsylvania State University Architectural Engineering Senior Thesis Presentation 13 April 2004 Presentation Outline Lighting Design
More informationAdvances in Non-Residential Lighting Technologies
Advances in Non-Residential Lighting Technologies CABEC conference San Diego, CA October 21, 2011 Steven Mesh, LC, IESNA Lighting Education & Design 140 Gardenside Drive, #304 San Francisco, CA 94131 415-516-8126
More informationLighting Depth Study. Exterior Departure/Canopy Area
Lighting Depth Study Exterior Departure/Canopy Area Overview The Exterior of the Indianapolis International Airport is consisted of 2 levels of traffic circulation. The lower level is the Arrival pick
More informationLighting Existing Conditions and Design Criteria Report Brian Regan Ltg./Elect. Virginia Historical Society 10/8/03
Lighting Existing Conditions and Design Criteria Report Brian Regan Ltg./Elect. Virginia Historical Society 10/8/03 Executive Summary The existing lighting conditions and design criteria report describes
More informationMezzanine Youth Area:
Mezzanine Youth Area: Overview of Space: This is located as a shorter level on the Northeast corner of the building, between the ground and second levels two levels have been placed. The design is to allow
More informationRelated Sections: TBD. Effective Date: January 1, 2016
Description: The purpose of the section is to highlight the current applicable UMCP Design Standards for the design, selection and, installation of lighting fixtures within buildings. Related Sections:
More informationTechnical Assignment 1 Existing Lighting Conditions and Design Criteria
Technical Assignment 1 Existing Lighting Conditions and Design Criteria Jason Greer Lighting/Electrical Option AGI Files: P:\AE 481\Technical Assignment 1\AGI Files October 5, 2007 Table of Contents Table
More informationB. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.
PART 1 GENERAL 1.01 Lighting design: A. Reference UAF Facilities Services Guidelines for Average Illumination Levels. B. It is recognized that these standards are updated irregularly and lighting technology
More informationLIGHTING EXISTING CONDITIONS SUMMARY EXECUTIVE SUMMARY Sara Lappano Ltg./Elec. Corron Cultural Center Middletown, VA
LIGHTING EXISTING CONDITIONS SUMMARY EXECUTIVE SUMMARY Sara Lappano Ltg./Elec. Corron Cultural Center Middletown, VA 11.4.2002 Contained in this report is a summary of the lighting existing conditions
More informationLighting Depth: Courtyard Franklin Care Center, Franklin Lakes, NJ
Lighting Depth: Courtyard Courtyard Overview: The perimeter buildings of the Franklin Care Center wrap around the central two story building creating two courtyard areas. The courtyard is entered through
More informationMain Lobby Area (North Vestibule thru South Vestibule):
Main Lobby Area (North Vestibule thru South Vestibule): Overview of Space: This is the entrance level from both the North, city street entrance, and the South, campus entrance. The space is 190 x 30 x
More informationAbbey Beresik. Executive Summary. Ronald Reagan Presidential Library Simi Valley, California
Executive Summary This report is an analysis of the existing lighting conditions for the Mulitpurpose Room, Reagan Country Café, Exhibition Hall and Presidential Learning Center of The Ronald Reagan Presidential
More informationOregon Non-Residential Building Energy Code
Oregon Non-Residential Building Energy Code Interior Connected Lighting Power Requirements The requirements for interior lighting power are one of the most important sections of the Oregon Energy Code.
More informationSpertus Institute of Jewish Studies
2 Kanis Glaewktgarn Spertus Institute of Jewish Studies Lighting/Electrical Option 610 S Michigan Ave Chicago, IL Lighting Consultant: Dr. Kevin Houser September 29, 2008 Executive Summary This report
More informationUBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical
More informationLumination LED Luminaires
GE Lighting Lumination LED Luminaires Recessed LED Luminaire AB Series Dimensional Distinction GE Lumination AB Series LED Recessed Luminaires invigorate drop ceilings with a gently curved lens and stylishly
More informationWo o l l y Mammo t h Th eat r e
Wo o l l y Mammo t h Th eat r e Was h in gt o n DC Kate Feato Lighting/Electrical Option Spring 2007 Lighting Advisor: Dr. Mistrick Electrical Advisor: Professor Dannerth 2 Table of Contents Executive
More informationLED retrofits! 4 T8 Specification Guide. Retrofit your existing Fluorescent Lights in Seconds No Electrician Needed! Pure Bright
T8 PBT8-DL5004EFX-U AC 100V-277V Day Light 5000K Pure Bright LED retrofits! Retrofit your existing Fluorescent Lights in Seconds No Electrician Needed! With the highest safety rating available, UL Listed,
More informationPacific Gas and Electric Company Energy Efficiency Rebates for Your Business. Lighting Rebate Catalog Saving energy for a brighter future
Pacific Gas and Electric Company Energy Efficiency Rebates for Your Business Lighting Rebate Catalog Saving energy for a brighter future Customers may be eligible to participate in Pacific Gas and Electric
More informationType: Project : Luminaire characteristics: Source: Lumen maintenance: Optics: Material: Mounting: Electrical: Finish: Weight:
Page: 1 of 11 Collection of compact exterior luminaires for architectural lighting. Rugged stainless steel construction, with tempered glass lens, these luminaires are designed to perform in extreme conditions.
More informationEcoSystem H-Series 347 V~ Ballast Overview
Fluorescent Dimming s EcoSystemR H-Series 347 V ~ Architectural Dimming EcoSystem H-Series 347 V~ Overview 369-352e 1 06.04.12 EcoSystem H-Series digitally addressable ballasts provide a low-cost, flexible
More informationUniversity Park, PA. The Pennsylvania State University Architectural Engineering Lighting and Electrical Faculty Advisor: Dr.
University Park, PA The Pennsylvania State University Architectural Engineering Lighting and Electrical Faculty Advisor: Dr. Martin Moeck A Building Overview The main spaces include: Convenience Store
More informationAlbeo LED Luminaire. Heavy Industrial Low Bay Lighting. (ALR1 - Series)
Albeo LED Luminaire Heavy Industrial Low Bay Lighting (ALR1 - Series) Product Features The Albeo ALR1-series LED luminaire is an energy-efficient, low maintenance alternative to traditional fluorescent
More informationGregory A. Wolfe Lighting / Electrical
Executive Summary: This report was created to study the existing lighting system present in the Westwood Community Church. Specifically, the purpose of this report is to analyze luminaire choice, power
More information2013 Nonresidential Appendices Appendix NA8-1. Appendix NA8 Luminaire Power... 1 NA8.1 Luminaire Power... 1
2013 Nonresidential Appendices Appendix NA8-1 Nonresidential Appendix NA8... 1 NA8.1 Luminaire Power... 1 NA8.1 Luminaire Power The following tables contain a limited list of lamp and ballast combinations.
More informationLighting Proposal Memo. Lighting Proposal. Angela Nudy Lighting/Electrical Dr. Mistrick Lighting Proposal Memo 1
Lighting Proposal Angela Nudy Lighting/Electrical Dr. Mistrick 12.16.2006 Lighting Proposal Memo 1 Executive Summary I have chosen to redesign the lighting for four interior spaces and one exterior space
More informationMillenium Os. Luminaire LED. For Stairwells and Public Spaces. Designed and manufactured in the USA. High Abuse Motion-Activated Lighting Product
Millenium Os For Stairwells and Public Spaces High Abuse Motion-Activated Lighting Product HA Designed and manufactured in the USA Occupancy Sensors Just Make Sense As industry standards continually change
More informationGeneral Building Overview
Executive Summary The following Lighting Existing Conditions and Design Criteria Report examines and summarizes the existing lighting systems considered for redesign in Broadway Plaza. These spaces include
More information13-15, 2001 USING LIGHTING SIMULATION TO ASSESS THE PERFORMANCE OF AND INDIRECT OFFICE LIGHTING SYSTEMS IN DYNAMIC WORKPLACES
Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001 USING LIGHTING SIMULATION TO ASSESS THE PERFORMANCE OF AND INDIRECT OFFICE LIGHTING SYSTEMS IN DYNAMIC WORKPLACES R. Ries,
More informationLumination LED Luminaires
GE Lighting Lumination LED Luminaires Recessed LED Troffer BT Series Refreshing Retrofit New Lumination BT Series Recessed LED Troffers from GE Lighting provide all the advantages of LED lighting at a
More informationWoolly Mammoth Theatre. Washington DC
Woolly Mammoth Theatre Washington DC Kate Feato Technical Report #1 Lighting Advisor: Dr. Mistrick Electrical Advisor: Professor Dannerth 04 October 2006 Executive Report The purpose of this technical
More informationEvolution EXWW RECESSED LINEAR WALL WASH LUMINAIRE
Evolution EXWW Project Name Date Type RECESSED LINEAR WALL WASH LUMINAIRE 3-13/16 (96.8mm) 5-1/8 (130.2mm) Extruded aluminum trim with formed cold rolled 20 gauge steel back box housing Highly reflective,
More informationLighting Design Criteria: Codes and Standards
EXTERIOR LIGHTING Lighting Design Criteria: Codes and Standards IESNA Lighting Handbook 10 th Edition RP-33-14 Lighting for Exterior Environments ASHRAE/IES Standard 90.1-2010 IBC 2012 2 Site Lighting
More information2018 Instant Lighting Rebates Product Catalog
MIDSTREAM LIGHTING PRODUCTS Product Code 463993 Interior 4 LED T8 Lamp Product Description Rebate/Unit Page # $5.00/Lamp 8 464791 Commercial LED Candelabra: 1 to
More informationTechnical Report 1 Part 2
Technical Report 1 Part 2 John Conley Lighting + Electrical Option Thesis Advisor Shawn Good Oakland University Engineering Center Rochester, MI 09.19.2014 Lighting calculation 3dsMax files can be found
More informationFranklin Square Hospital Center
Franklin Square Hospital Center Baltimore, MD Thesis Proposal Cassandra Watson + Electrical Electrical Advisor Professor Dannerth Advisor Dr. Mistrick 16 December 2009 Table of Contents Executive Summary...
More informationLighting depth. Mark W. Miller Sibley memorial Hospital Grand Oaks Washington, DC. Introduction
Introduction Grand Oaks is an Assisted Living Facility in the Washington, D.C. area that gives its residents the support they need while maintaining a home like environment. So, when I set out to develop
More informationBuidling 661 Annual Daylight Performance Modeling Studies
Buidling 661 Annual Daylight Performance Modeling Studies A Report for GPIC Task 2.2 Compiled by Richard G. Mistrick, Ph.D., P.E., FIES Associate Professor of Architectural Engineering The Pennsylvania
More informationCorbin Building. Technical Assignment 1. Matthew Trethaway Lighting/ Electrical AE 481W September 22, 2011 Advisor: Dr. Houser
Corbin Building Technical Assignment 1 Matthew Trethaway Lighting/ Electrical AE 481W September 22, 2011 Advisor: Dr. Houser September 22, 2011 Technical Assignment 1 1 Executive Summary The spaces studied
More informationWINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016
SECTION 26 2030 - LIGHTING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Special Conditions and Division 1 Specification Sections,
More informationSECTION INTERIOR AND EXTERIOR LIGHTING FIXTURES
SECTION 26 50 00 INTERIOR AND EXTERIOR LIGHTING FIXTURES PART 1: GENERAL 1.1 WORK INCLUDED: A. Interior lighting fixtures and accessories B. Exterior lighting fixtures and accessories C. Emergency battery
More informationULTRA RT6 and RT6 Gimbal LED Recessed Downlight Kit
www.sylvania.com/rt6 ULTRA RT6 and RT6 Gimbal LED Recessed Downlight Kit Key Features & Benefits Lumen package: 625 lumens @ 11 watts 700 lumens @ 11 watts 900 lumens @ 14 watts Replacement for up to 100W
More informationA. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.
DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire
More informationLED RETROFIT CONVERSION KITS
Our LED RetroFit Conversion Kits come with a complete Gear Tray Assembly to convert older 4-foot and 8-foot T8 or T12 strip-type fixtures into energy efficient LED luminaires. High quality components and
More informationThesis Proposal. Brian Regan The Virginia Historical Society Building West Wing Addition RICHMOND, VIRGINIA
Thesis Proposal Brian Regan The Virginia Historical Society Building West Wing Addition RICHMOND, VIRGINIA New Addition s Functions Auditorium Entrances located on ground and basement floors Museum Art
More informationDaylighting Control Design and Application Guide
Daylighting Control Design and Application Guide DAYAPPS_1206 Design Guide Introduction Introduction Daylighting controls transform a day lit area into an energy-saving opportunity. The U.S. Environmental
More information2018 Midstream Lighting Product Catalog
MIDSTREAM LIGHTING PRODUCTS Product Code Product Description Rebate/Unit Page # 463993 Interior 4 LED T8 Lamp $5.00/Lamp Commercial LED Candelabra 2 Watts 462649 4 $7.00/Lamp Commercial LED Candelabra
More informationNRG SYSTEMS, HINESBURG, VT
Daylighting Case Studies NRG SYSTEMS, HINESBURG, VT Project Highlights Daylight windows separated from view windows Advanced daylightredirecting blinds Low partitions, with desks oriented at right angles
More informationThe New York University Concourse Project. New York City. Existing Conditions and Design Criteria
The New York University Concourse Project New York City Existing Conditions and Design Criteria Kevin Hsia Lighting/Electrical Option Advisor: Dr. Richard Mistrick September 29, 2008 executive summary
More informationSchematic Design Ideas for the Westlake Recreation Center. Presented by: Summer Padgett At Lutron Electronics On December 9, 2003
Schematic Design Ideas for the Westlake Recreation Center Presented by: Summer Padgett At Lutron Electronics On December 9, 2003 The Westlake Recreation This facility serves as a park and recreation center
More informationDepth Work Part 1: Lighting Design
During the upcoming spring semester I will be investigating and redesigning some of the systems in Redifer Commons. This thesis study will be composed of three sections, which will all end up intertwining.
More informationMANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)
MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130) MANDATORY LIGHTING CONTROLS 1. Area Controls: Manual controls that control lighting in each area separately 2. Multi-level
More informationCode Compliance Commercial Application Guide
Code Compliance Commercial Application Guide ASHRAE 90.1-2010 IECC 2012 Title 24-2013 Summary of code requirements for lighting control In the following pages, we ve provided examples of how Lutron solutions
More informationCOMMERCIAL LIGHTING DESIGN GUIDE
COMMERCIAL LIGHTING DESIGN GUIDE WHAT SETS US APART INNOVATION We combine the latest energy efficient technology and design styles to create an extensive range of attractive and sustainable luminaires.
More informationStocking Solutions. Downlights LED Panels Floods & Wall Packs
Stocking Solutions Downlights LED Panels Floods & Wall Packs Because Experience Makes the Difference Since 1976, LSI Industries has been introducing smart, innovative lighting solutions to help its customers
More informationHighbay Linear LED Series Flat Profile Design
Applications Warehouse Manufacturing Facility Gymnasium Features Cafeteria Auditorium Rigid body construction (white finish) Tool-less driver access from below the fixture for easy maintenance and serviceability
More informationLUMINAIRE ID SIZE CENTER OPTICS SIDE OPTICS LIGHT SOURCE CRI LUMEN PACKAGES COLOR TEMP. VOLTAGE. LED - high performance LED 80-80CRI 90-90CRI
PROJECT: APPROVED BY: SIGNATURE: Grid - shown with a Nova flat lens Grid - shown with a Nova Slope lens TYPE QTY DESCRIPTION Nova is an efficient architectural LED troffer with a distinctive luminous shielding
More informationUNIVERSITY OF PENNSYLVANIA NEURAL AND BEHAVIORAL SCIENCES BUILDING 415 University Ave, Philadelphia, PA 19104
UNIVERSITY OF PENNSYLVANIA NEURAL AND BEHAVIORAL SCIENCES BUILDING 415 University Ave, Philadelphia, PA 19104 Reinhardt Swart Lighting + Electrical Advisor Shawn Good Technical Report Part I 9.16.13 Lighting
More informationAdvanced Lighting Solutions
Advanced Lighting Solutions Ben Koyle, LC, LEED Green Assoc. April 20, 2017 Learning Objective Gain a better understanding of the energy savings potential of LED luminaires and networked lighting control
More information1.2.0 Apartment Lobby
1.2.0 Apartment Lobby 1.2.1 Introduction The apartment lobby serves as a primary circulation area as well as a gathering place for residents and visitors alike. A revolving door from the exterior opens
More informationLighting Depth Part 1: Exterior Space
Lighting Depth Part 1: Exterior Space Metaphor and Ideas: The first space of my lighting redesign is the front façade of the Recreation Center shown below. Metaphorically, I want the front porch to act
More informationShepherd University Wellness Center AE 481 Thesis Lighting Technical Report 1
A E 481 THESIS TECHNICAL REPORT ONE Shepherd University Wellness Center AE 481 Thesis Lighting Technical Report 1 Shepherdstown, West Virginia Lighting/ Electrical Option Dr. Houser October 14, 2010 Contents
More informationRTC Recessed LED center basket
RTC Recessed LED center basket 1' x 4' 2' x 2' 2' x 4' RTC Recessed LED center basket The RTC lensed troffer series provides performance, reliability and flexibility with a housing optimized for shallow
More informationLighting Retrofit Rebate
Lighting Retrofit Rebate 2017 Rebate Application Elk River Municipal Utilities, PO Box 430, Elk River, MN 55330 Ph: 763-441-2020 Business Information Company name Billing address Installation address (if
More informationElectrical Systems. Electrical Plans. Electrical Plans. Essential to ensure. National Electrical Code (NES) Consider electrical needs.
Electrical Systems Electrical Plans Essential to ensure Proper wiring National Electrical Code (NES) Electrical Plans Consider electrical needs Office equipment Lighting E t t i t t Entertainment systems
More information