1 INSTALLATION INSTRUCTIONS Modbus Supplemental Manual for LC6000 Controller The LC6000 is capable of being remotely monitored through the integrated Ethernet port. Through this port the controller will respond to Modbus commands allowing access to setpoints, alarms, temperature measurements and humidity measurements for each zone. The controller has the following connection settings: Protocol: Modbus TCP/IP Address: 1 Timeout: 3000 ms IP Address: Subnet: The IP settings are defaulted to the values listed above; however, in general for remote monitoring of these values the IP settings will have to be adjusted to match the shelter network settings. To change the IP settings of the LC6000: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter USER password Press UP or DOWN keys to scroll to Settings; press ENTER key. 4. Press UP or DOWN keys to scroll to Network Config; press ENTER key. 5. Press ENTER key to scroll down the screen (see Figure 1). Press the UP or DOWN keys to change the value of each parameter to match the setting required for the network the LC will be added to. 6. ce settings have been entered, change Update Config? from No to Yes to save the settings. Figure 1 The units of the values retrieved during communication are determined by the controller unit of measure setting. This is configured onsite and cannot be changed remotely. For more information about how to use each of these values, please refer to the latest version of the LC6000 Service Instructions manual. Bard Manufacturing Company, Inc. Bryan, Ohio Manual: A Supersedes: Date: Page 1 of 7
2 Modbus Register List MULTI-TEC Number Name R/W Register Type Register Variable Format Range Comments 1 System Disable R/W Coil 0 UnitMng.Bms Enable/Disable 0-1 Used to turn off system remotely 2 Generator Alarm R DiscreteInput 0 Al_LC_Generator.Trigger / = 0/1 0-1 Displays status of Generator Run Alarm 3 Unit of Measure R/W Holding Register 0 BMS_UOM No Conversion, 1 to 7 Sets Units of BMS variables SI,US Customary, Imperial Units, Canadian, Carel LON Card, SI Pressure (bar) = 1,2,3,4,5,6,7 4 Smoke Input Status R DiscreteInput 1 Smoke / = 0/1 0-1 Displays status of smoke input 5 Generator Input Status R DiscreteInput 2 Generator_Status / = 0/1 0-1 Displays status of generator input 6 Hydrogen Input Status R DiscreteInput 3 HydrogenStatus / = 0/1 0-1 Displays status of hydrogen input 7 Zone 1 Smoke Alarm R DiscreteInput 100 Al_LC_SmokeZ1.Trigger / = 0/1 0-1 Displays status of smoke alarm 8 Zone 1 Hydrogen Alarm R DiscreteInput 101 Al_LC_HydrogenZ1.Trigger / = 0/1 0-1 Displays status of hydrogen alarm 9 Zone 1 Indoor Temperature R DiscreteInput 102 Al_LC_IndoorTempZ1.Active / = 0/1 0-1 Indicates a sensor failure 10 Zone 1 Remote Temperature R DiscreteInput 103 Al_LC_RemoteTempZ1.Active / = 0/1 0-1 Indicates a sensor failure 11 Zone 1 Indoor Humidity Sensor R DiscreteInput 104 Al_LC_IndoorHumZ1.Active / = 0/1 0-1 Indicates a sensor failure Failure 12 Zone 1 Low Temperature Alarm R DiscreteInput 105 Al_LC_LowTempZ1.Active / = 0/1 0-1 Indicates a low temperature in zone 1 13 Zone 1 High Temperature Warning R DiscreteInput 106 Al_LC_HighTempZ1.Active / = 0/1 0-1 Indicates a high temperature warning in zone 1 14 Zone 1 High Temperature Alarm R DiscreteInput 107 Al_LC_HighTemp2Z1.Active / = 0/1 0-1 Indicates a high temperature alarm in zone 1 15 Zone 1 Low Humidity Alarm R DiscreteInput 108 Al_LC_LowHumZ1.Trigger / = 0/1 0-1 Indicates a low humidity alarm in zone 1 16 Zone 1 High Humidity Alarm R DiscreteInput 109 Al_LC_HighHumZ1.Trigger / = 0/1 0-1 Indicates a high humidity alarm in zone 1 17 Zone 2 Smoke Alarm R DiscreteInput 200 Al_LC_SmokeZ2.Trigger / = 0/1 0-1 Displays status of smoke alarm 18 Zone 2 Hydrogen Alarm R DiscreteInput 201 Al_LC_HydrogenZ2.Trigger / = 0/1 0-1 Displays status of hydrogen alarm 19 Zone 2 Indoor Temperature R DiscreteInput 202 Al_LC_IndoorTempZ2.Active / = 0/1 0-1 Indicates a sensor failure 20 Zone 2 Indoor Humidity Sensor R DiscreteInput 204 Al_LC_IndoorHumZ2.Active / = 0/1 0-1 Indicates a sensor failure Failure 21 Zone 2 Low Temperature Alarm R DiscreteInput 205 Al_LC_LowTempZ2.Active / = 0/1 0-1 Indicates a low temperature in Zone 2 22 Zone 2 High Temperature Warning R DiscreteInput 206 Al_LC_HighTempZ2.Active / = 0/1 0-1 Indicates a high temperature warning in Zone 2 Page 2 of 7
3 23 Zone 2 High Temperature Alarm R DiscreteInput 207 Al_LC_HighTemp2Z2.Active / = 0/1 0-1 Indicates a high temperature alarm in Zone 2 24 Zone 2 Low Humidity Alarm R DiscreteInput 208 Al_LC_LowHumZ2.Trigger / = 0/1 0-1 Indicates a low humidity alarm in Zone 2 25 Zone 2 High Humidity Alarm R DiscreteInput 209 Al_LC_HighHumZ2.Trigger / = 0/1 0-1 Indicates a high humidity alarm in Zone 2 26 Zone 3 Smoke Alarm R DiscreteInput 300 Al_LC_SmokeZ3.Trigger / = 0/1 0-1 Displays status of smoke alarm 27 Zone 3 Hydrogen Alarm R DiscreteInput 301 Al_LC_HydrogenZ3.Trigger / = 0/1 0-1 Displays status of hydrogen alarm 28 Zone 3 Indoor Temperature R DiscreteInput 302 Al_LC_IndoorTempZ3.Active / = 0/1 0-1 Indicates a sensor failure 29 Zone 3 Indoor Humidity Sensor R DiscreteInput 304 Al_LC_IndoorHumZ3.Active / = 0/1 0-1 Indicates a sensor failure Failure 30 Zone 3 Low Temperature Alarm R DiscreteInput 305 Al_LC_LowTempZ3.Active / = 0/1 0-1 Indicates a low temperature in Zone 3 31 Zone 3 High Temperature Warning R DiscreteInput 306 Al_LC_HighTempZ3.Active / = 0/1 0-1 Indicates a high temperature warning in Zone 3 32 Zone 3 High Temperature Alarm R DiscreteInput 307 Al_LC_HighTemp2Z3.Active / = 0/1 0-1 Indicates a high temperature alarm in Zone 3 33 Zone 3 Low Humidity Alarm R DiscreteInput 308 Al_LC_LowHumZ3.Trigger / = 0/1 0-1 Indicates a low humidity alarm in Zone 3 34 Zone 3 High Humidity Alarm R DiscreteInput 309 Al_LC_HighHumZ3.Trigger / = 0/1 0-1 Indicates a high humidity alarm in Zone 3 35 Zone 1 Cooling Temperature 36 Zone 1 Heating Temperature R/W HoldingRegister 100 UnitClSpZ1 #### = ###.# 90 F Max R/W HoldingRegister 101 UnitHtSpZ1 #### = ###.# 32 F Min Cooling temperature setpoint Heating temperature setpoint 37 Zone 1 Humidity R/W HoldingRegister 102 HumSpZ1 #### = ###.# 0-45% Humidification Dehumidification 38 Zone 1 Dehumidification 39 Zone 1 Low Temperature Alarm 40 Zone 1 High Temperature Warning 41 Zone 1 High Temperature Alarm R/W HoldingRegister 103 DehumSpZ1 #### = ###.# % R/W HoldingRegister 104 LowTempSpZ1 #### = ###.# F R/W HoldingRegister 105 HighTempSpZ1 #### = ###.# 70- R/W HoldingRegister 106 HighTempSp2Z1 #### = ###.# 70- Low Temperature setpoint High Temperature Warning High Temperature Alarm 42 Zone 1 Low Humidity R/W HoldingRegister 107 LowHumSetZ1 #### = ###.# 0-100% Low Humidity Alarm 43 Zone 1 High Humidity R/W HoldingRegister 108 HighHumSetZ1 #### = ###.# 0-100% High Humidity Alarm 44 Zone 1 Continuous Blower Setting R/W HoldingRegister 109 ContBlowerZ1 None, Lead, All 45 Zone 1 Staging Type Setting R/W HoldingRegister 110 RotationTypeZone1 LIFO, FIFO, Demand 0-2 Determines continuous blower settings 0-2 Determines staging setting Page 3 of 7
4 46 Zone 1 Dehumidification Method 47 Zone 1 Passive Dehumidification 48 Zone 1 Active Dehumidification 49 Zone 1 Freecooling Staging Delay 50 Zone 1 Freecooling Staging Delay 51 Zone 1 Cooling Staging Delay 52 Zone 1 Cooling Staging Delay 53 Zone 1 Heating Staging Delay 54 Zone 1 Heating Staging Delay 55 Zone 2 Cooling Temperature 56 Zone 2 Heating Temperature R/W HoldingRegister 111 DehumModeZ1 None, Electric Reheat, Mechanical Reheat, Cycle Reheat = 0,1,2,3 R/W HoldingRegister 112 DehumPassiveSpZ1 #### = ###.# 46- R/W HoldingRegister 113 DehumActiveSpZ1 #### = ###.# Determines method for R/W HoldingRegister 114 Delay_FCZ1 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 115 Delay_FCZ1 #### = ###.# 0-999s Staging delay off R/W HoldingRegister 116 Delay_CLZ1 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 117 Delay_CLZ1 #### = ###.# 0-999s Staging delay off R/W HoldingRegister 118 Delay_HTZ1 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 119 Delay_HTZ1 #### = ###.# 0-999s Staging delay off R/W HoldingRegister 200 UnitClSpZ2 #### = ###.# 90 F Max R/W HoldingRegister 201 UnitHtSpZ2 #### = ###.# 32 F Min Humidity level required to start passive Humidity level required to start active Cooling temperature setpoint Heating temperature setpoint 57 Zone 2 Humidity R/W HoldingRegister 202 HumSpZ2 #### = ###.# 0-45% Humidification Dehumidification 58 Zone 2 Dehumidification 59 Zone 2 Low Temperature Alarm 60 Zone 2 High Temperature Warning 61 Zone 2 High Temperature Alarm R/W HoldingRegister 203 DehumSpZ2 #### = ###.# % R/W HoldingRegister 204 LowTempSpZ2 #### = ###.# F R/W HoldingRegister 205 HighTempSpZ2 #### = ###.# 70- R/W HoldingRegister 206 HighTempSp2Z2 #### = ###.# 70- Low Temperature setpoint High Temperature Warning High Temperature Alarm 62 Zone 2 Low Humidity R/W HoldingRegister 207 LowHumSetZ2 #### = ###.# 0-100% Low Humidity Alarm 63 Zone 2 High Humidity R/W HoldingRegister 208 HighHumSetZ2 #### = ###.# 0-100% High Humidity Alarm 64 Zone 2 Continuous Blower Setting R/W HoldingRegister 209 ContBlowerZ2 None, Lead, All 65 Zone 2 Staging Type Setting R/W HoldingRegister 210 RotationTypeZone2 LIFO, FIFO, Demand 0-2 Determines continuous blower settings 0-2 Determines staging setting Page 4 of 7
5 66 Zone 2 Dehumidification Method 67 Zone 2 Passive Dehumidification 68 Zone 2 Active Dehumidification 69 Zone 2 Freecooling Staging Delay 70 Zone 2 Freecooling Staging Delay 71 Zone 2 Cooling Staging Delay 72 Zone 2 Cooling Staging Delay 73 Zone 2 Heating Staging Delay 74 Zone 2 Heating Staging Delay 75 Zone 3 Cooling Temperature 76 Zone 3 Heating Temperature R/W HoldingRegister 211 DehumModeZ2 None, Electric Reheat, Mechanical Reheat, Cycle Reheat = 0,1,2,3 R/W HoldingRegister 212 DehumPassiveSpZ2 #### = ###.# 46- R/W HoldingRegister 213 DehumActiveSpZ2 #### = ###.# Determines method for R/W HoldingRegister 214 Delay_FCZ2 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 215 Delay_FCZ2 #### = ###.# 0-999s Staging delay off R/W HoldingRegister 216 Delay_CLZ2 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 217 Delay_CLZ2 #### = ###.# 0-999s Staging delay off R/W HoldingRegister 218 Delay_HTZ2 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 219 Delay_HTZ2 #### = ###.# 0-999s Staging delay off R/W HoldingRegister 300 UnitClSpZ3 #### = ###.# 90 F Max R/W HoldingRegister 301 UnitHtSpZ3 #### = ###.# 32 F Min Humidity level required to start passive Humidity level required to start active Cooling temperature setpoint Heating temperature setpoint 77 Zone 3 Humidity R/W HoldingRegister 302 HumSpZ3 #### = ###.# 0-45% Humidification Dehumidification 78 Zone 3 Dehumidification 79 Zone 3 Low Temperature Alarm 80 Zone 3 High Temperature Warning 81 Zone 3 High Temperature Alarm R/W HoldingRegister 303 DehumSpZ3 #### = ###.# % R/W HoldingRegister 304 LowTempSpZ3 #### = ###.# F R/W HoldingRegister 305 HighTempSpZ3 #### = ###.# 70- R/W HoldingRegister 306 HighTempSp2Z3 #### = ###.# 70- Low Temperature setpoint High Temperature Warning High Temperature Alarm 82 Zone 3 Low Humidity R/W HoldingRegister 307 LowHumSetZ3 #### = ###.# 0-100% Low Humidity Alarm 83 Zone 3 High Humidity R/W HoldingRegister 308 HighHumSetZ3 #### = ###.# 0-100% High Humidity Alarm 84 Zone 3 Continuous Blower Setting R/W HoldingRegister 309 ContBlowerZ3 None, Lead, All 0-2 Determines continuous blower settings Page 5 of 7
6 85 Zone 3 Staging Type Setting R/W HoldingRegister 310 RotationTypeZone3 LIFO, FIFO, 0-2 Determines staging setting Demand 86 Zone 3 Dehumidification Method 87 Zone 3 Passive Dehumidification 88 Zone 3 Active Dehumidification 89 Zone 3 Freecooling Staging Delay 90 Zone 3 Freecooling Staging Delay 91 Zone 3 Cooling Staging Delay 92 Zone 3 Cooling Staging Delay 93 Zone 3 Heating Staging Delay 94 Zone 3 Heating Staging Delay R/W HoldingRegister 311 DehumModeZ3 None, Electric Reheat, Mechanical Reheat, Cycle Reheat = 0,1,2,3 R/W HoldingRegister 312 DehumPassiveSpZ2 #### = ###.# 46- R/W HoldingRegister 313 DehumActiveSpZ3 #### = ###.# Determines method for R/W HoldingRegister 314 Delay_FCZ3 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 315 Delay_FCZ3 #### = ###.# 0-999s Staging delay off R/W HoldingRegister 316 Delay_CLZ3 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 317 Delay_CLZ3 #### = ###.# 0-999s Staging delay off R/W HoldingRegister 318 Delay_HTZ3 #### = ###.# 0-999s Staging delay on R/W HoldingRegister 319 Delay_HTZ3 #### = ###.# 0-999s Staging delay off Humidity level required to start passive Humidity level required to start active 95 Number of Units R InputRegister 0 NumUnits #-## 0-14 Number of units configured 96 Humidification Setup R InputRegister 1 HumSetup Zone1, Zone1 & 0-3 Configured zones for humidification 2, Zone 1,2 & 3 97 Humidification Type R InputRegister 2 HumType Relay, Comm 0-1 Humidification Control Type = 0,1 98 Configured UoM R InputRegister 3 STD_UOM_ZONE_UI No Conversion, SI,US Customary, Imperial Units, Canadian, Carel LON Card, SI Pressure (bar) = 1,2,3,4,5,6,7 99 Zone 1 Indoor Humidity 100 Zone 1 Indoor Temperature 1 to 7 Unit of measure configured for local display R InputRegister 100 IndoorHumZ1 #### = ###.# 0-100% Indoor Humidity R InputRegister 101 IndoorZ1 #### = ###.# -40- Indoor Temperature Page 6 of 7
7 Indoor Temperature 101 Zone 1 Remote Temperature 102 Zone 2 Indoor Humidity 103 Zone 2 Indoor Temperature 104 Zone 3 Indoor Humidity 105 Zone 3 Indoor Temperature R InputRegister 102 RemoteZ1 #### = ###.# -40- R InputRegister 200 IndoorHumZ2 #### = ###.# 0-100% Indoor Humidity R InputRegister 201 RemoteZ2 #### = ###.# -40- Indoor Temperature R InputRegister 300 IndoorHumZ3 #### = ###.# 0-100% Indoor Humidity R InputRegister 301 RemoteZ3 #### = ###.# -40- Indoor Temperature Page 7 of 7
LV CONTROLLER
SERVICE INSTRUCTIONS WITH REPLACEMENT PARTS LIST LV1000-200 CONTROLLER NOTE: LV1000 controller is required for operation when FUSION-TEC HR**BP wall-mount units are used. Bard Manufacturing Company, Inc.
More informationMC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option
MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option The MC4000 has 2 stages of cooling control available for each connected air conditioner. It is
More informationLC6000 Controller used with MULTI-TEC Wall Mount Units Specification Sheet & Application Guide
LC6000 Controller used with MULTI-TEC Wall Mount Units Specification Sheet & Application Guide FEATURES OF THE LC6000 CONTROLLER Control up to 14 units with a single LC6000 controller. Complete control
More informationDAP III Zone Master User s Guide
DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP
More informationModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.
ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page
More informationReference Guide for Microprocessor Controller
Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before
More informationSetup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software
La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A36D & TPSD Chargers with S2A-341S and S2A-383S communication cards. Option 21P,
More informationTAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products
Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate
More informationINSTALLATION AND OPERATING MANUAL
INSTALLATION AND OPERATING MANUAL Spectron Gas Control Systems GmbH Fritz-Klatte-Str. 8 65933 Frankfurt Germany Tel.: +49 69 38016-0 Fax: +49 69 38016-200 info@spectron.de www.spectron.de is a unit that
More informationINSTALLATION, OPERATION & QUICK START GUIDE
INSTALLATION, OPERATION & QUICK START GUIDE Controller CS9B-THOA CS9B-THOCA Models: CS9BE-THOA CS9BE-THOCA Bard Manufacturing Company, Inc. Bryan, Ohio 4506 www.bardhvac.com Manual: 00-684 Supersedes:
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS CONTROLLER INSTALLATION, OPERATION & QUICK START GUIDE Bard CompleteStat TM CS9B-THO CS9B-THOC Models: CS9BE-THO CS9BE-THOC Bard Manufacturing Company, Inc. Bryan, Ohio 43506
More informationC-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY
A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G
More informationReference Guide for Microprocessor Controller
Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting
More informationCONTROLS MANUAL For all Innovent and Valent air handling products
CONTROLS MANUAL For all Innovent and Valent air handling products TABLE OF CONTENTS TABLE OF CONTENTS IMPORTANT INFORMATION Safety information...................................................................................
More informationLennox Climatic 50 and BMS Modbus, Trend or BACnet.
Lennox Climatic 50 and BMS Modbus, Trend or BACnet. Specification of the Bus: Type: RS485 Speed: (Adjustable on Climatic 50 via display ; Setting 3933) 1200 2400 4800 9600 19200 Parity: Fixed no parity
More informationREAD AND SAVE THESE INSTRUCTIONS
XXXXXXX-0 EN 1904 READ AND SAVE THESE INSTRUCTIONS BASIC-PLC CONTROLLER MANUAL For all Condair desiccant dryer with equipped with Basic- PLC valid from version: PLC-35/PLC-45 18.04.03 Dehumidification
More informationPowerLogic ION Setup Meter Configuration Software Configuration Guide
PowerLogic ION Setup Meter Configuration Software Configuration Guide 70002-0293-03 12/2010 Conventions Used in this Manual This section describes the symbols and terminology used in this guide. Symbols
More informationA36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS
SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS with 500 and 550 option. A36D/TPSD Modbus TCP SCADA INTERFACE OPTION 21Q INSTRUCTIONS This manual is valid for A36D/TPSD Chargers equipped
More informationSERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER
SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER Models: HR36APA HR36APB HR58APA HR58APB Part of the Bard Free Cooling Unit System NOTE: LV1000 Controller is required for operation when multiple
More informationStandard Chiller Modular HP 1/4 Generic/Bitzer screw compressor and CAREL valve
Application program for pco¹ pco² pco 3 Standard Chiller Modular HP 1/4 Generic/Bitzer screw compressor and CAREL valve 1.1 09 / 11 / 2006 version of manual Program code: FLSTDmMSBE We wish to save you
More informationStandard Instructions For MC-2000/3000/4000 Controllers
Standard Instructions For MC-2000/3000/4000 Controllers Manual Update: 09/12/11 Version: 3.10 1 1 QUICK REFERENCE GUIDE 1.1 NAVIGATING THE DISPLAY Interacting with the AboveAir Technologies unit is accomplished
More informationPre-Cool and Free- Cool Fan Control
5/26/2014 Pre-Cool and Free- Cool Fan Control ArcticCool Chillers ArcticCool Chillers Limited Authored by: Casey Smith ArcticCool Chillers Limited Pre-Cool and Free-Cool Fan Control Sequence of Operations
More information5. Slowly turn thermostat toward cooler position. Both fan and compressor should shut offwhen thermostat set point equals room temperature. Room temperature must be above 65 F for unit to shut off. Unit
More informationSERVICE INSTRUCTIONS
SERVICE INSTRUCTIONS MULTI-TEC WALL-MOUNT AIR CONDITIONER Part of the Bard Free Cooling Unit System W18AAPA W24AAPA W24AAPB W24AAPC W30AAPA W30AAPB W30AAPC W36AAEA W36AAEB W36AAEC W36AAMA W36AAMB W36AAMC
More informationReference Guide for Microprocessor Controller
Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting
More informationCultivator & Hybrid Cultivator
Cultivator & Hybrid Cultivator Precision Temperature & Humidity Packaged Unit INTRODUCTION The Cultivator Series package unit is the industry s MOST ENERGY EFFICIENT and HIGHEST capacity dehumidifier on
More informationAIRSYS-P-SC-CHILLROW-E1503V01.1 CHILLROW. Row Cooling Precision Air Conditioner. Cooling Capacity: 26.2kW~68.6kW
AIRSYS-P-SC-CHILLROW-E1503V01.1 CHILLROW Row Cooling Precision Air Conditioner Cooling Capacity: 26.2kW~68.6kW CHILLROW is installed closely with the server cabinets and refrigerating independently. The
More informationModular Standard HP Chiller 1/4 screw compressor with Carel driver
Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?
More informationProduct Description...3 Communication Interface...4 Client Interface...4. Accessible Registers...4 Data Format...4
FAAST Fire Alarm Aspiration Sensing Technology Modbus USER GUIDE Table of Contents Product Description...3 Communication Interface...4 Client Interface...4 Accessible Registers...4 Data Format...4 Device
More informationIndex. 1. General description of the application Types of units controlled Types of regulation Condensation...
LCS pco ADVANCED MICROPROCESSOR USER MANUAL GB Index 1. General description of the application... 4 1.1. Types of units controlled...4 1.2. Types of regulation...4 1.3. Condensation...4 1.4. Safety devices
More informationFlexible & Innovative. Cooling Solutions
Flexible & Innovative Cooling Solutions Flexible & Innovative Compu-Aire Inc. offers a variety of high performance precision cooling systems that can adapt to your application needs. With today s rapidly
More informationModbus Point Map. for the. Data Aire DAP-II
Modbus Point Map for the Data Aire DAP-II Revision 1 November 11, 2003 Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Table of Contents 1 Introduction... 3 1.1 Scope... 3 1.2 References...
More informationSERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER
SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER Models: HR58APA HR58APB Part of the Bard Free Cooling Unit System NOTE: LV1000 Controller is required for operation when multiple HR58AP* units
More informationLift Station Level Controller
Lift Station Level Controller Installation and Operation Manual 1 California Motor Controls, Inc. Benicia, CA Table of Contents 1. Features Product Overview... 4-6 Access Security... 7 Optional Features...
More informationFan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication
Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication Description The TFHB24F3XYZ1 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications.
More informationThe system shall be described in the following specification as manufactured by Schneider Electric
Guide Specifications Uniflair LE High Capacity Chilled Water Units THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTER FORMAT. THIS SECTION MUST
More informationPoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP
PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP-20180529 UPDATED: MAY 2018 INTRODUCTION PoolPak dehumidifiers equipped with the CommandPak Control System
More informationNGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X
NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS Firmware versions up to V2.0.X INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGCUIT2Protocol-IM-H57880 06/15 1/32 Contents Section I Introduction
More informationFeature Summary. I. System
I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in
More informationSERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER
SERVICE INSTRUCTIONS FUSION-TEC WALL-MOUNT AIR CONDITIONER Models: HR36APA HR36APB HR58APA HR58APB Part of the Bard Free Cooling Unit System NOTE: LV1000 Controller is required for operation when multiple
More informationNGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1
NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...
More informationComPak Series with CommandPak Control System CPCS BACnet MS/TP BAS Interface User s Guide DOCUMENT #: SVW06-CPBACNETMSTP
ComPak Series with CommandPak Control System CPCS BACnet MS/TP BAS Interface User s Guide DOCUMENT #: SVW06-CPBACNETMSTP-20180529 UPDATED: MAY 2018 INTRODUCTION ComPak dehumidifiers equipped with the CommandPak
More informationHOMEOWNER S MANUAL. Harmony III Zone Control System. IMPORTANT: Read this instruction manual completely! Retain for future reference.
2008 Lennox Industries Inc. Dallas, Texas, USA HOMEOWNER S MANUAL Harmony III Zone Control System CONTROLS 505,024M 07/08 Supersedes 05/06 IMPORTANT: Read this instruction manual completely! Retain for
More informationA36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS
SCADA INTERFACE INSTRUCTIONS - OPTION 21S - FOR A36D/TPSD SYSTEMS with option 500 and 550. A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE OPTION 21S INSTRUCTIONS This manual is valid for A36D/TPSD Chargers
More informationTEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers
TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date
More informationEXD-HP1/2 Stand-alone Superheat/Economizer Controller
Technical Bulletin EXD-HP1/2 are stand-alone universal superheat and or economizer controllers for heat pumps, heating units, air conditioning and precision cooling such as telecom and shelter applications.
More informationINSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST
INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST DC3002 and DC3003 SOLID STATE LEAD/LAG CONTROLLER with DC FAN CONTROL Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just
More informationINSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST
INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST MC400 SERIES SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 4506 www.bardhvac.com Manual : 100-614I Supersedes:
More informationREMOTE CONTROL FOR CHILLER MYCHILLER
REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN
More informationManual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:
Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description
More informationData Aire DAP TM III. Metasys Control Points
Data Aire DAP TM III Metasys Control Points Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-703 September 2009 Rev. 5.0 Document 600-000-703 Page 1 of 7 Table
More informationHIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER
This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS CMH-28 Compressor Cutout Thermostat Kit For Use with W18HA, W24HA, W30HA and W36HA Wall-Mount Heat Pumps The CMH-28 is a field-installable compressor cutout outdoor thermostat
More informationA-Tech-20 Advanced Microprocessor Controller
A-Tech-20 Controller Operation Manual (04/02/01) 1 C Y B E R A i R Product Division A-Tech-20 Advanced Microprocessor Controller Operations Manual Project: SATS Model: SATS SN: SATS JN: Unit Tags: REVISION
More informationInstallation, Configuration and User Manual
Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.
More information*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide
Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch
More informationSYSTEM 2500 PROGRAMMABLE CONTROLLER -USER MANUAL-
SYSTEM 2500 PROGRAMMABLE CONTROLLER -USER MANUAL- 8167 Byron Road Whittier, CA 90606 Phone: (562) 945-8971 Fax: (562) 696-0724 SUBJECT TO CHANGE WITHOUT INCURRING OBLIGATION Rev.01 03-27-17 Page 1 of 71
More informationLiebert CW 1.0 GENERAL
1.1 SUMMARY Liebert CW Guide Specifications Chilled Water Environmental Control System 1.0 GENERAL These specifications describe requirements for a Thermal Management system. The system shall be designed
More informationElectro-Sentry. Users Manual
Electro-Sentry Users Manual 2. To view an individual point, e.g. Speed just touch that point and it will display a graph showing the 45 min. of activity. Viewing a Leg: 1. Touch the desired leg, e.g. East
More informationPROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM
PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk sales@protec.co.uk
More informationTEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs
TEC2620 Series Non-Programmable Fan Coil Network Thermostat ler and Remote I/O Relay Packs TEC2620H-0, TEC2620C-0, TEC2620H-0+PIR, TEC2620C-0+PIR, TEC2621H-0, TEC2621C-0, TEC2621H-0+PIR, TEC2621C-0+PIR
More informationControl manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions
KNCT2-808 KN Series Gas-fired direct vent Cast iron boilers Models KN-6, -10, -20 only (HeatNet control firmware edition 45 ) Control manual Control adjustment and Operation instructions Also read and
More informationSEQUENCE OF OPERATIONS
SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,
More informationContents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47
WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document
More informationQ-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17
Q-SMART MODBUS KIT Modbus Protocol & Parameters Cod.001085120EN rev.a ed.08/2018 Q-SMART Software Version AE17 Index 1 Modbus Protocol on Q-SMART... 4 1.1 Broadcasting... 4 1.2 Data Protection... 4 1.3
More informationSYSTEM 2500 S PROGRAMMABLE CONTROLLER -USER MANUAL-
SYSTEM 2500 S PROGRAMMABLE CONTROLLER -USER MANUAL- 8167 Byron Road Whittier, CA 90606 Phone: (562) 945-8971 Fax: (562) 696-0724 Rev.01 03-27-17 Page 1 of 67 Compu-Aire SUBJECT TO CHANGE WITHOUT INCURRING
More informationSiemens RDY2000BN. Start Up Guide
Siemens RDY2000BN Start Up Guide Answers for infrastructure and cities. What this slide set is about This is a start up guide for the RDY2000BN BACnet Commercial Thermostat. This procedure show how to
More informationThe system shall be described in the following specification as manufactured by Schneider Electric
Guide Specifications Uniflair LE Air-Cooled Direct Expansion (DX) Cooling Systems THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTER FORMAT. THIS
More informationPLC / HMI Modbus (Slave) Addressing
Made in the USA PLC / HMI Modbus (Slave) Addressing Legacy - HMI touch screen with built in Legacy - Pentra PLC with Expandable I/O Legacy Chiller Systems, Inc. General Information IMPORTANT READ BEFORE
More informationER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller
PB_ER65-DRW_ 202 ER65-DRW Controller Heating Applications Product Bulletin The controller is a digital device for domestic or residential heating units. It covers water and air heating applications. All-in-one
More informationA77 SNMPv1 SCADA INTERFACE INSTRUCTIONS
A77 SNMPv1 SCADA INTERFACE OPTION 21X INSTRUCTIONS This manual is only valid for A77 Chargers equipped with the following: S2A-368S card with software version P368S0111 080116 MIB file P389S-21X4-00 S2A-389S
More informationN M AirControl AHU. Control manual
N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4
More informationUniversal Monitoring System. Model IMEC8A. User Manual Version 1.10 Software version 2.3.1
Unit 7/8, Heathrow Causeway Estate, Ariel Way, Hounslow Middlesex, TW4 6JW +44 (0) 208 6302270 www.cpcuk.co.uk Universal Monitoring System Model IMEC8A User Manual Version 1.10 Software version 2.3.1-1
More informationRF SCOUT PLUS INSTRUCTION MANUAL. Dielectric, LLC 22 Tower Rd. Raymond, ME Phone: January 2015, Rev B 1
RF SCOUT PLUS INSTRUCTION MANUAL Dielectric, LLC 22 Tower Rd. Raymond, ME 04071 Phone: 800.341.9678 www.dielectric.com 21 January 2015, Rev B 1 WARNING Powering RF sensors above +30dBm (1W) will cause
More informationFor Raychem ACS-30 Controls Systems
ACS-30 Protocol Interface Mapping For Raychem ACS-30 Controls Systems Firmware Version 5.05 THERMAL BUILDING SOLUTIONS EN-RaychemACS30-AR-H58324 03/16 Table of Content Section 1. Introduction... 3 1.1
More informationAD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System
AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin AD-1272 Code No. LIT-12012477 Issued December 2017 Refer to the QuickLIT website for the most up-to-date version of
More informationManual for the integration in BMS/GTC
Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2
More informationT60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Product Bulletin T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4, T601DFH-4+PIR, T602DFH-4+PIR,
More informationMARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER
MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective May 2017 ***Interactive PDF*** CONTENTS GENERAL PURPOSE 3 MARVEL PREMIUM - CONTROLLABLE SYSTEM COMPONENT
More informationINSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST
INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST MC4000 SERIES SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned.
More informationFlameGard 5 UV/IR HART
FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized
More informationAlarm module for leak detection with webserver
This instruction document consists of 2 parts : one part about the assembly of the components and one part about configuration and starting-up of the system. The assembly is done by the qualified installer
More informationI/O ZONE 560/583 USERS GUIDE
I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6
More informationDiagnostics and Monitoring System WEB Tool 2. User Manual
Diagnostics and Monitoring System 2 (Translation of the original documentation) User Manual S/N: Valid from: 01.05.2012 Rev.: 2.0 2 Rev. 1.... 1 1.1 General information... 1 1.1.1 Equipment... 1 1.1.2
More informationCONTENTS SAFETY SYMBOLS... 1 GENERAL WARNINGS... 1 MAIN FEATURES... 2 MAIN FUNCTIONS... 2 USER UNIT... 3
CONTENTS SAFETY SYMBOLS... 1 GENERAL WARNINGS... 1 MAIN FEATURES... 2 MAIN FUNCTIONS... 2 USER UNIT... 3 KEYBOARD...3 ACTIVE KEY COMBINATIONS...4 TURNING THE UNIT ON/OFF...4 CHANGING TEMPERATURE AND FAN
More informationLONWORKS Solution for Orion PT-LON-Link
Point Map February 5, 2008 Systems Integration LONWORKS Solution for Orion PT-LON-Link Table 1. Orion PT-Link-LON APOGEE Points, Application Number: 9158, Program ID: 90:00:95:47:1E:02:04:B3. 1 LAI AppSoftVer
More informationTouchscreen Comfort Control
12-5058-04 Touchscreen Comfort Control Model ACONT624AS42DA User Guide Nexia Home Intelligence Customer Service: (877) 288-7707 For HVAC related issues, contact your servicing dealer ÎÎ NOTE: A 24 Volt
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS MC3000 SERIES SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-452 Supersedes:
More informationINSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST
INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST DC3002 & DC3003 SOLID STATE LEAD/LAG CONTROLLER WITH DC FAN CONTROL Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual No.: 2100-484F
More informationStandard Air Handling Units
Application software for pco² - pco XS Standard Air Handling Units Program code: FLSTDMAHUA We wish to save you time and money! We can assure you that the thorough reading of this manual will guarantee
More informationSequence of operation
Sequence of operation IPS 4000 secondary variable speed control File No: 90.96 Date: february 21, 2013 Supersedes: new Date: new sequence of operation ips 4000 2 list of abbreviations: adj: Field Adjustable
More informationIntelligent Chiller Manager (icm)
Inverter Installation, Operation and Maintenance Manual Installation and Operation Manual D-EIOCH00305-17EN Intelligent Chiller Manager (icm) Original Instructions Revision History Version Date icm version
More informationKey benefits. Why Condair CP3?
Condair Cp3 Humidification The Electrode Steam Humidifier. Powerful and User-Friendly Why? Tailored technology. You can program your specifications exactly to the last kilogram with the CP3 Card. This
More informationCurrent-Input-Module (CIM) MOTOR PROTECTION UNIT QUICK REFERENCE ESC. December 19, 2006 Revision 0 MAIN MENU. ²Messages Ñ. Metering Ñ.
R 34 33 3 31 30 9 8 7 6 5 4 3 1 0 19 C D R S C D R C D R S C D R S INP 8 H INP 7 INP 6 H INP 5 PG PWR STARTCO ENGINEERING LTD. COMM MPS-RTD INPUT MODULE CTU/ MPU + INP 1 4V S INP INP 3 S INP 4 COMM 0 D
More informationicomfort Residential Communicating Control System icomfort Touch Communicating Thermostat
C O N T R O L S icomfort Residential Communicating Control System icomfort Touch Communicating Thermostat P R O D U C T S P E C I F I C AT I O N S Bulletin No. 210538 March 2012 Supersedes October 2011
More informationMicroTech Rooftop/RMC
Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version
More informationTable of Contents. WSHP Open v3
WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1
More information8-101kW. AlphaCool close control range ADDITIONAL CAPACITIES. NOW AVAILABLE Plus EC fan option kW. Typical applications
AlphaCool close control range 8-101kW - 101kW > Typical applications > Data Centres > Telecommunications and ISP facilities > Computer rooms > Clean rooms > Switching stations > Laboratories www.airedale.com
More informationInstallation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function) GOLD RX
Installation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function) GOLD RX 04-120 1. General The TBLZ-2-66 accessory is a control system incorporated into a
More informationPROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS
PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min
More information