38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

Size: px
Start display at page:

Download "38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS"

Transcription

1 Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions , 7 Introduction Refrigerant Line Sizing Evacuation, Dehydration & Charging Expansion System Service Guides Piping Connection & Compressor Location 7 Electrical Connections and Wiring.... 6, 8, 10 Operation and Start-up Recommended Service Clearances SAFETY CONSIDERATION Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service air conditioning equipment. Observe precautions in the literature, tags and labels attached to the unit and other safety codes. Wear safety glasses and gloves. Use quenching cloth and have fire extinguisher available for all brazing operations. RECEIVING 38GHP condensing units are shipped individually and protected with wood skid and plastic shrink wrap. Do not roll, throw or drop the unit. This may damage unit when you do so. Always store the unit in upright position. PROTECTION Protect unit from damage caused by job site debris. Do not allow dust, debris and water get into the unit. These will damage unit s component and unit performance will be affected. INSPECTION Check the shipment against shipping list and remove unit protective covering. If the unit has been damaged, file claim with transportation company and immediately notify Concepcion- Carrier. ELECTRIC SHOCK HAZARD Before installing or servicing system always switch off main power supply. There may be more than one disconnect switch. Electric shock can cause personal injury. 1

2 Table 1-2 COMPRESSOR SERIES MODEL 38ASB ASB ASB ASB1818 DIMENSIONS HEIGHT, mm 722 WIDTH + VALVE, mm DEPTH, mm 337 NOMINAL AIRFLOW, m 3 /min CONDENSER COIL: Copper Tube/Aluminum Fin NO. OF ROWS FINS PER INCH AREA, m FAN MOTOR 0.25 KW; 1.7 FLA, 1 ea. COMPRESSOR NO TYPE Rotary PROTECTIVE DEVICE Current and Thermal Overload ELECTRICAL CHARACTERISTICS V / 1 ph / 60 Hz FULL LOAD COMP AMPS AT COMP V TOTAL LOCKED COMP ROTOR AMPS COMP AT 230 V POWER COMP INPUT COMP AT 230 V TOTAL NET WEIGHT, KG Table 2-3 COMPRESSOR SERIES MODEL 38GHP GHP GHP GHP GHP DIMENSIONS: HEIGHT, mm 1,835 WIDTH, mm 905 DEPTH + VALVE, mm NOMINAL AIRFLOW, m 3 /min CONDENSER COIL: NO. OF ROWS FINS PER INCH AREA, m FAN MOTOR KW, 2.7 FLA, 1 ea kw, 3.8FLA, 1 ea. COMPRESSOR NO TYPE Rotary ELECTRICAL CHARACTERISTICS Volts/1 phase/60 Hertz FULL LOAD COMP AMPS AT COMP V COMP TOTAL LOCKED COMP ROTOR AMPS COMP AT 230 V COMP POWER COMP INPUT COMP AT 230 V COMP TOTAL NET WEIGHT, KG

3 SYSTEM (2&4 COMPRESSOR SERIES) DIMENSIONS: MODEL 38GHP GHP GHP HEIGHT, mm 1835 WIDTH, mm 905 DEPTH + VALVE, mm NOMINAL AIRFLOW, m 3 /min CONDENSER COIL: NO. OF ROWS FINS PER INCH AREA, m FAN MOTOR 0.395kW; 2.7 FLA; 1 ea kW; 3.8 FLA; 1 ea COMPRESSOR NO. 2 4 TYPE Rotary Scroll Rotary ELECTRICAL CHARACTERISTICS Volts/1 phase/60 Hertz Volts/1 phase/60 Hertz FULL LOAD COMP AMPS AT COMP V COMP COMP TOTAL LOCKED COMP ROTOR AMPS COMP AT 230 V COMP COMP POWER COMP INPUT COMP AT 230 V COMP COMP TOTAL NET WEIGHT, KG INTRODUCTION The 38GHP models are designed for use with 2, 3 or 4 indoor fan coil units depending on the number of compressors. Each compressor has its own independent control & power wirings but all the compressors share a common fan drive system. Each compressor also has its own refrigerant lines and each piping circuit has a holding charge of 0.5 kg. Install these condensing units either thru-the-wall, outdoors on a slab or on the roof. When installing units, allow sufficient space for airflow clearance, wiring, refrigerant piping and servicing units. The air-side clearance must be at least 600 mm or more. REFRIGERANT LINE SIZING Follow the recommendation given under UNIT DATA for the selection of tube OD. Wrong sizing would either result in excessive pressure drop or unsatisfactory oil return. The cooling coils should be connected as close as possible. Both liquid and suction line lengths should be less than 15 meters. Condensing units should not be more than 5 meters above or below the evaporator coils. Run refrigerant tubes as directly as possible, avoiding unnecessary turns and pipe bends. Condensing unit may be connected to evaporator sections using fieldsupplied tubing of refrigerant grade, correct size and condition. Suspend refrigerant tubes so they do not transmit vibration to structure. Leave some slack in refrigerant tubes between structure and unit to absorb vibration. Longer interconnecting pipe run will result considerable cooling capacity drop. See Table 4 for approximate percentage of system cooling capacity reduction Table 4 REDUCTION IN CAPACITY VS. INCREASE IN PIPE LENGTH Actual Compressor Capacity PIPING LENGTH (ONE WAY) 5m 10m 15m 09 k 0 % 1.5 % 3.0 % 12 k 0 % 1.7 % 3.2 % 18 k 0 % 1.6 % 3.4 % 24 k 0 % 1.5 % 3.6 % 36 k 0 % 1.5 % 3.7 % 3

4 FIELD PIPING WORKS Do not bury any section of line set underground. If any section is buried, refrigerant may migrate to cooler buried section during extended periods of unit shutdown. This causes refrigerant slugging and possible compressor damage at start-up. If either refrigerant tubing or indoor coil is exposed to atmospheric conditions for longer than 5 minutes, it must be evacuated to 1000 microns to eliminate contamination and moisture in the system. PIPING CONNECTION Run refrigerant tubes as directly as possible and avoid turns and bends. Use refrigerant grade tubing and correct size Allen wrench. Align tubing flare with service valve connection and tighten the nut with the correct torque. Refer to Table 5 for vertical and horizontal piping length. AIR PURGE Air does not function as refrigerant because it can not be condensed in the condenser. Air and moisture remaining in the system have undesirable effects. Therefore, they must be purged out completely. AIR PURGING PROCEDURE Remove the blind caps of the liquid valve. Loosen the valve stem of the liquid valve by 90 0 for 5 seconds with a hexagonal key wrench. Then close the valve stem quickly. Push the valve core of the suction valve. Stop pushing as soon as the hissing stop. Open the liquid valve for about 3 seconds, then close quickly to check for gas leak. After checking for gas leaks, open the liquid and suction valves all the way. Re-install the blind caps. FIG. 1 MAXIMUM ALLOWABLE PIPING LENGTH AND ELEVATION DIFFERENCE Actual Compressor Capacity MAX. DISTANCE L - m (ft) CDU above FCU MAX. LIFT H m (ft) CDU below FCU 09 k 15 (50) 7.5 (25) 5 (16) 12 k 15 (50) 7.5 (25) 5 (16) 18 k 15 (50) 10 (33) 7.5 (25) 24 k 15 (50) 10 (33) 7.5 (25) 36 k 18 (60) 10 (33) 7.5 (25) Table 5 MAX PIPE DISTANCE L & H FIG. 2 PIPING LENGHT 4

5 SIGHT GLASS AND FILTER DRIER Sight glass and filter drier are field supplied and installed applicable for model 38GHP036,048, 060, other models are factory installed. Warranty will be voided if these models were not fitted with external filter drier in the field installation. TUBING CONNECTIONS AND LEAK TEST Both suction and liquid are equipped with flare type connections. Assemble flare joint by aligning tubing with machine surface of fitting. Start run onto threads by turning backwards first then forwards. All lines should be assembled with type L or quarter hard drawn refrigeration grade copper tubing and not with copper water pipe. Use only the following brazing alloys: Copper to Copper % Silver Alloy (no flux) Copper to Steel or Brass % Silver Alloy (no flux) Remove cap and Schrader core from service port to protect seals from heat damage. Wrap service valve with wet rag before applying heat. Flow dry nitrogen into a service port and through the tubing while brazing to prevent pipe oxidation. Pressurize line set and coil through service fittings with dry nitrogen to 150 psig maximum (or refer to Carrier Standard Service Techniques Manual, chapter 1, section 1-6) If a leak is found, recover pressure and repair all leaks. WARNING: DO NOT USE OXYGEN TO PURGE LINES OR PRESSURE SYSTEM FOR LEAK TEST. OXYGEN REACTS VIOLENTLY WITH OIL, WHICH CAN CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH. PIPING INSULATION Insulate both suction and liquid lines as per Figure 8 shown below. EVACUATION AND DEHYDRATION Evacuation is the most important part of the entire service procedure. The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air and moisture from the system. Air in the system causes high condensing temperature and pressure, resulting in increased power consumption and reduced system efficiency. Moisture chemically reacts with the refrigerant and oil thus forming corrosive acids which attacks motor windings and parts, causing early breakdown. After the system has been leak checked and proven leak free, connect now the vacuum pump and evacuate system to 29 Hg vacuum. It is advisable to connect both vacuum pump hose to the high-side and low-side of the system. FINAL LEAK TEST After the unit has been properly evacuated and charged, use a halogen leak detector to check system for leaks. In the absence of this, water-soap solution is acceptable. All piping within the condensing unit, evaporator, and interconnecting tubing should be checked for leaks. If a leak is detected, the refrigerant should be recovered before repairing the leak. REFRIGERANT CHARGING The 38GHP units are all Factory charged with R22 for holding charge purposes only. Refrigerant charge adjustment is required on all systems following super heat charging method explained in details in the preceding discussions below. IMPORTANT For accurate system performance, charge by superheat method as shown in Table 7 and 8. To check and adjust, follow this procedures: 1. Operate unit for a minimum of 30 minutes before checking charge. 2. Measure suction pressure by attaching a gauge to suction valve service port. 3. Measure suction line temperature by attaching a service thermometer to unit suction line near suction valve. Insulate thermometer for accurate readings. 4. Measure outdoor coil air inlet dry-bulb temperature with a second thermometer. 5. Measure indoor coil air inlet wet-bulb temperature with a sling psychrometer. 6. Refer to Table 7. Find air inlet dry-bulb temperature entering outdoor coil and wet-bulb temperature entering indoor coil. At this intersection note down the superheat. 7. Refer to Table 8. Find superheat temperature and suction pressure, note suction line temperature. 8. If unit has higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached. 9. If unit has lower suction temperature than charted temperature, bleed refrigerant until charted temperature is reached. 10. If air temperature entering outdoor coil or pressure at suction line changes, change to new suction line temperature indicated on chart. 11. This procedure is valid independent of indoor air quantity. 5

6 FIG. 3 PIPE INSULATION ASSEMBLY FIG. 4 ACCURATOR ASSEMBLY EXPANSION SYSTEM The 38GHP units are factory equipped with a system for refrigerant gas expansion called piston while model 38ASB series uses capillary tube type. As shown below, this system has a small piece with a fixed, calibrated, easily removable hole inside a nipple to be easily connected to liquid line by a 3/8 size flare nut. The piston application properties include a more accurate refrigerant gas flow into the evaporator compared, for instance, with the capillary system. On some application wherein long pipe length can not be avoided, piston size can be changed to adjust operating conditions of the applications. Consult Carrier Service Department for proper selection of piston size other than specified. ACTUAL COMPR. CAPACITY 09K 12K 24K 36K PISTON SIZE R22 CHARGING METHOD Table 6 PISTON SIZE TABLE Sh Sh Sh Sh Sh Sh= Charge unit according to Carrier super heat Charging method. COMPLETE ELECTRICAL CONNECTIONS Each refrigerant circuit has its own control and power wiring except the fan motor is common to all the refrigerant circuits. The compressor motor is protected by an overload relay. The compressor is further protected by a high pressure switch. For a 2, 3 and 4 compressor system, fan motor starts together with one or more compressors. For all circuits, any interruption to the load will initiate a 3 minute delay and prevent the compressor from being re-energized until the normal delay period has elapsed. The wiring circuits are wired such that the fan motor is de-energized whenever all the compressor happen to cycle off. Since many of the components in each of the 38GHP models are identical, careful wiring is important. POWER - Unit is factory wired for voltage shown on name plate. Provide adequate fused disconnect switch within sight of unit, readily accessible, but out of reach of children. Provision for locking switch open (off) is advisable to prevent power from being turned on while unit is being serviced. Route power wires through opening in the unit side panel knock-out holes and connect into control box. Unit must be grounded. WIRING PROCEDURE This unit is factory wired for voltage shown on the unit nameplate. Remove service cover of the outdoor unit and connect wires firmly to the terminal block individually as shown in wiring diagrams. Secure service cover back once wiring connection is tested and completed. PISTON REPLACEMENT MUST BE ONLY DONE BY QUALIFIED TRAINED SERVICE TECHINCIANS. IF PISTON ARE NOT PROPERLY POSITIONED, THIS WILL RESULT SYSTEM MALFUNCTION. SEE FIG. 4 FOR CORRECT POSITION AND DIRECTION. All switches, fuses and field wiring must carry unit running ampere and must comply with local code requirements. Unit factory wiring diagram is shown on the inside of the service cover. Note: Operation of unit on improper line voltage constitutes abuse and could affect Carrier Warranty. Do not install unit in system where voltage may fluctuate above or below permissible limits of +/- 10% of the rated voltage. 6

7 SERVICE GUIDES CAUTION: Disconnect electric power from main switch before performing any maintenance or service units. GENERAL NOTES When performing any routine service operations or doing specific repairs to the components, motors, fans and other components, all drain passages should be thoroughly cleaned. Inside painted surfaces should be cleaned with mineral spirits to remove grease. Check indoor and outdoor units to see that all controls are functioning correctly and the operation of the units is normal. Be sure that the tubing does not vibrate against the side of the indoor or outdoor unit. Ensure that the indoor unit is leveled in order that condensate drains correctly from it. When disconnecting power or control wiring, it is recommended that identification tags be attached to the wires to facilitate rapid and correct re-assembly. Before disconnecting any capacitor it is necessary that the capacitor be discharged by shorting its terminals with an insulated screwdriver. CLEANING The single most important item affecting your air conditioning effectiveness is its cleanliness. The following items require regular attention (Caution: disconnect electric power from main switch before performing any maintenance item.) Paint any parts that show evidence of rust with a good rust resistant paint. The rubber mounting grommets for the compressor in the outdoor unit should be replaced if they deteriorate. Check all the wiring for deterioration and electrical contacts for tightness and correction. PIPING CONNECTION AND COMPRESSOR LOCATION 38GHP units are multi-split units. Correct coupling of suction and liquid lines to every fan coil is essential. The same is true for the wiring. The following diagrams should be used for field coupling. (All views are from the back of the unit.) Check fans to see they are centered in the fan housings, correctly positioned and tight on shafts. After replacing fans, check clearance of wheel to housing prior to operation. Shield coils with cardboard prior to removing interior components. FIG. 6 PIPING CONNECTION 7

8 3 COMPRESSOR SERIES: COMPRESSOR CAPACITY, Btu/hr 38GHP GHP GHP GHP GHP K 9K 9K 12K 12K 12K 24K FIG 7 COMPRESSOR & VALVE LOCATION 3 COMPRESSOR SERIES COMPRESSOR SERIES: COMPRESSOR CAPACITY, Btu/hr 38GHP COMPRESSOR 4 9K 9K 12K 2 COMPRESSOR SERIES-HIGH TONNAGE: COMPRESSOR CAPACITY, Btu/hr 38GHP GHP K 24K 36K 36K FIG. 8 COMPRESSOR & VALVE LOCATION 4 COMPRESSOR SERIES 1 2 ELECTRICAL CONNECTIONS POWER WIRING WARNING TO AVOID POSSIBLE INJURY OR DEATH DUE TO ELECTRICAL SHOCK, OPEN THE POWER SUPPLY DISCONNECT SWITCH (SWITCH-OFF) AND SECURE IT IN AN OPEN POSITION DURING INSTALLATION. USE LOCK-OUT AND TAG-OUT SECURITY LOCKS! Unit is factory wired for voltage shown on nameplate. Provide adequate fused disconnect switch within sight of unit, readily accessible but out of reach of children. FIG. 9 COMPRESSOR & VALVE LOCATION 4 COMPRESSOR SERIES Provision for locking switch open (off) is advisable to prevent power from being turned on while unit is installed or serviced. Disconnect switch, fuses and field wiring must comply with local codes. Size the wire as per electrical specification shown in CCAC Service Installer Blue Book. Use terminal marked L and N for 230V-1Ph-60Hz power supply. See respective wiring diagram shown on the preceding pages. CAUTION THE CONTROL VOLTAGE FROM THE FAN COIL UNIT MUST BE OF 230V. DO NOT CONNECT THE POWER SUPPLY TO THE SIGNAL 8

9 OPERATION AND START-UP PRELIMINARY CHECKS Before operating the unit be sure the following are in order. 1. All wiring connections are correct and tight. 2. All barriers, covers and panels are in place. 3. Electrical power supply conform to unit s requirement. 4. All joints are leak tested and leak free. 5. All valves are opened. TO START THE UNIT 1. Field disconnect switch is closed. 2. Set room temperature below ambient setting. 3. Compressor will start once time delay has elapsed (normally 3 minutes as factory setting). 4. Operate unit or at least 30 minutes, then check system refrigerant charge using superheat method. Table 7 Superheat Charging Table (English) (Superheat Entering Suction Service Valve) INDOOR COIL ENTERING AIR ( F) WET-BULB OUTDOOR TEMP( F) Symbol dash (-) means: Do not attempt to charge system under these conditions or refrigerant slugging may occur. Superheat Charging Table (Metric) (Superheat Entering Suction Service Valve) INDOOR COIL ENTERING AIR ( C) WET-BULB OUTDOOR TEMP( C) Symbol dash (-) means: Do not attempt to charge system under these conditions or refrigerant slugging may occur. Table 8 Required Suction Tube Temperature (English) (Entering Suction Service Valve) SUPERHEAT SUCTION PRESSURE AT SERVICE PORT (psig) TEMP ( F) Required Suction Tube Temperature (Metric) (Entering Suction Service Valve) 9 SUPERHEAT SUCTION PRESSURE AT SERVICE PORT (KPaG) TEMP ( K)

10 10

11 AIR BLOW FRONT REAR AIR IN FIG. 10 RECOMMENDED SERVICE CLEARANCES Concepcion Carrier Air conditioning Company Philippines Concepcion Carrier Air Conditioning Company Km. 20 East Service Road, South Superhighway, Alabang, Muntinlupa City Tel. No. (63) Fax No. (63) Website: Manufacturer reserve the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations Form 38GHP-1IOM Replaces: NEW 11

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT Concepcion Carrier Air conditioning Company Philippines INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT CONTENTS Safety Considerations 1 Complete

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

Installation Instructions

Installation Instructions 8GXM / 0GXM Multi---Split High---Wall Duct Free Split System 8GXM --- Size 18k, k, and 0k 0GXM --- Size 9k, 1k, and 18k Installation Instructions NOTE: Read the entire instruction manual before starting

More information

Installation Instructions

Installation Instructions 25HHA4 Performance Series Heat Pump with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-25HHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

Installation Instructions

Installation Instructions Performance Series Heat Pumps with PURONr Refrigerant 1 --- 1/2 to 5 Nominal Tons Installation Instructions Fig. 1 --- A07532 NOTE: Read the entire instruction manual before starting the installation.

More information

Installation Instructions

Installation Instructions 38MPRA Outdoor Unit Single Zone Ductless System Sizes 09 to 12 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes

More information

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS DLCSRA INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only.

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

CAUTION. Check Equipment and Job Site. Clearance Requirements. Unpack Unit

CAUTION. Check Equipment and Job Site. Clearance Requirements. Unpack Unit INSTALLATION IMPORTANT: Effective January 1, 2015, all split system and packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy.!

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER! 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS INSTALLATION GUIDE R-410A ATTENTION, INSTALLER! After installing the system, show the user how to turn off electricity to the unit. Point out control and switch

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

Installation Instructions

Installation Instructions 38MGQ Multi-Zone Ductless System Sizes 18, 27, 36 and 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES 11-AC11D2-5 INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: Condensing Units 2A7A5024-048, 2A7A4018-060, 2A7A2018-060 & 2A7A1018-060 IMPORTANT

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS R 410A Ducted Horizontal Air Conditioner Product Family: HC4A3 Fig. 1 - HC4A3 NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE

More information

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... DLCMRA INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 GENERAL... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATION AND OPERATING INSTRUCTIONS HIGH-EFFICIENCY CONDENSING UNITS RAWD- 6 1 2 & 7 1 2 TON RAWE - 6 1 2 & 7 1 2 TON! RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!! WARNING

More information

Installation Instructions

Installation Instructions 38MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 30, 36 and 48 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 GENERAL... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS...

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION INSTALLATION INSTRUCTION CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS Supersedes: 550.44-N1Y (1194) 550.44-N1Y (495) MODELS H*DE018 THRU H*DE060 035-11029 WARNINGS are given to alert the installer

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS R 410A Ducted Horizontal Heat Pump Product Family: HC4H3 Figure 1 - HC4H3 NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY

More information

Installation Instructions

Installation Instructions 214D, 215B, 225B Single -Stage Split System Heat Pump with Puronr Refrigerant 1 1/2 To 5 Nominal Tons Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

Installation Instructions

Installation Instructions 40MAQ / 38MAQ 619PB / 538PR High---Wall Ductless Split System Sizes 09 to 30 Installation Instructions TABLE OF CONTENTS PAGE PARTS LIST... 2 SAFETY CONSIDERATIONS... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS...

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Installation Instructions

Installation Instructions Evaporator Coil A Coil --- Cased Multipoise NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

Residential Piping and Long Line Guideline

Residential Piping and Long Line Guideline AC / HP R-410A Refrigerant Systems Single-Stage, Two-Stage and Variable Speed Models Residential Piping and Long Line Guideline TABLE OF CONTENTS Safety Considerations... 2 Definitions... 2 Introduction...

More information

Installation Instructions

Installation Instructions 25HBB, 25HBC Baset Series Heat Pumps with Puronr Refrigerant 1 --- 1/2 To 5 Nominal Tons Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Installation Instruction

Installation Instruction 40GRQ / 619FB / 38GRQ / 538FR High- Wall Ductless Split System Sizes 09-18 Installation Instruction NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY

More information

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. Installation NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION... 2 Inspect Equipment... 2 Select

More information

Installation Instructions

Installation Instructions 40MHH High Wall Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes only. Actual

More information

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215) National Comfort Products 539 Dunksferry Road Bensalem, PA 19020 (215) 244-1400 1-800-523-7138 Fax: (215) 244-9579 SPLIT-SYSTEM CONDENSING UNIT INSTALLATION INSTRUCTIONS 1000 3000 4000 SERIES 1. 2. 3.

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215) National Comfort Products 539 Dunksferry Road Bensalem, PA 19020 (215) 244-1400 1-800-523-7138 Fax: (215) 244-9579 R410a SPLIT-SYSTEM CONDENSING UNIT INSTALLATION INSTRUCTIONS 1000 3000 4000 SERIES 1.

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 10 SEER Standard Efficiency Split System These units have been designed and tested for capacity and efficiency in accordance with

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions Installation, Start-Up and Service Instructions 38HDF018-036 Duct Free Condensing Units 38HDR018-060 Ducted Condensing Units CONTENTS Page SAFETY CONSIDERATIONS...1 INSTALLATION... 1-10 Step 1 Complete

More information

Installation Instructions

Installation Instructions 40MBD Ducted Style Ductless System Sizes 09 to 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless System Sizes 09 to 36 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only. Actual models

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS SPLIT AIR CONDITIONER OUTDOOR SECTION Models: HAC481-B HAC602-B For Use With: Matching Indoor Blower Coil Units and Matching Add On Coil Units Only Bard Manufacturing Company,

More information

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N PROAIR Air Conditioner CR23 Model INSTRUCTION MANUAL Rev. D P/N 89112522 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax: TECHNICAL MANUAL CX(E) SPLIT SYSTEMS CONTENTS INDEX PART NUMBERS, OPTIONS, UNIT COMBINATIONS, DIMENSIONS & WEIGHTS 3 PERFORMANCE DATA & AIR FLOW 4 SOUND POWER AND SOUND PRESSURE LEVELS 5 ELECTRICAL DATA

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS STELLAR AIR CONDITIONING UNIT SPLIT-SYSTEM COOLING CONTENTS GENERAL..................................... 2 NOMENCLATURE........................... 2 SAFETY...................................

More information

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE GENERAL..............................................1 SAFETY................................................1

More information

38LB/38LF AIR COOLED CONDENSING UNIT

38LB/38LF AIR COOLED CONDENSING UNIT WORLD LEADER IN AIR CONDITIONING AND HEATING TECHNOLOGY INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38LB/38LF AIR COOLED CONDENSING UNIT CONTENTS PAGE PHYSICAL DATA 2 PHYSICAL DATA 2 DIMENSION DATA

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Installation Instruction

Installation Instruction Installation Instruction Upflow Downflow Heating Cooling CC5A Uncased Coil CD5A Cased Coil SUPPLY RETURN EVAPORATOR COIL DOWNFLOW UPFLOW SUPPLY Fig. 1 Typical Installation of CD5A Cased Coil A96244 NOTE:

More information

Horizontal/Side Discharge Condensing Units

Horizontal/Side Discharge Condensing Units INSTALLATION, OPERATION & MAINTENANCE MANUAL Horizontal/Side Discharge Condensing Units Models CMA12SD-0 CMA18SD-1 CMA24SD-1 CMA30SD-1 CMA36SD-1 CMA48SD-1 517.787.2100 www.marsdelivers.com Horizontal/Side

More information

User s Information/Installation Instructions

User s Information/Installation Instructions Outdoor Heat Pump User s Information/Installation Instructions 12 SEER High Efficiency Split System These units have been designed and tested for capacity and efficiency in accordance with A.R.I. Standards.

More information

Installation Instructions

Installation Instructions Baset Series Heat Pumps with Puronr Refrigerant 1---1/2 To 5 Nominal Tons (Sizes 18 to 60) Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS

More information

Safety Labeling and Signal Words

Safety Labeling and Signal Words These instructions must be read and understood completely before attempting installation. DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS RAWL HIGH EFFICIENCY R-410A COMMERCIAL CONDENSING UNITS NOMINAL SIZES 10, 12., 1 & 20 TONS 10 & 12. TON 1 & 20 TON! Recognize this symbol as an indication of Important Safety

More information

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M 2004 Lennox Industries Inc. Dallas, Texas KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04 Supersedes 503,249M Litho U.S.A. COMPRESSOR REPLACEMENT KIT INSTALLATION INSTRUCTIONS FOR COMPRESSOR

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Daikin Direct Expansion (DX) Cooling Coils

Daikin Direct Expansion (DX) Cooling Coils Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied Contents Introduction...

More information

Installation Instruction

Installation Instruction DLFCAB / DLCCAR / DLFCHB / DLCCHR DLFDAB / DLCDAR / DLFDHB / DLCDHR High- Wall Ductless Split System Sizes 09-36 Installation Instruction NOTE: Read the entire instruction manual before starting the installation.

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

Installation Instructions

Installation Instructions Installation Instructions Part No. 30RA-900---057 and 30RA-900---060 30RAP010-150 Remote Cooler Mounting Accessory SAFETY CONSIDERATIONS Installation of this accessory can be hazardous due to system pressures,

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons Models A and later Design Sequence CTA 090A***A 60 HZ 120A***A 60 HZ 120B***A 60 HZ 180B***A 60 HZ SS-SVN11A-EN

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C7BA Series Split System Indoor Cased Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N PROAIR Air Conditioner CR29 Model INSTRUCTION MANUAL Rev. I P/N 89104461 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioners

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioners INSTALLATION INSTRUTIONS R 410A Split System Air onditioners NXA5, R4A5, WA5 These instructions must be read and understood completely before attempting installation. SAFETY ONSIDERATIONS Improper installation,

More information

Refrigerant Recovery Unit, Model RRU134

Refrigerant Recovery Unit, Model RRU134 Installation, Operation & Maintenance Manual IOMM RRU134 Group: Refrigerant Effective: December 2000 Supersedes: New Refrigerant Recovery Unit, Model RRU134 1999 McQuay International Table of Contents

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance

More information

Installation Instructions

Installation Instructions 40MBCQ Cassette Ductless System Sizes 09 to 8 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS INDOOR... 5 CLEARANCES INDOOR...

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N PROAIR Air Conditioner CR43 Model INSTRUCTION MANUAL Rev. H P/N 10-1008-130 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

INSTALLATION INSTRUCTIONS R 410A

INSTALLATION INSTRUCTIONS R 410A R 410A Ductless Split System Air Conditioner and Heat Pump MODELS: DLC4(A/H) Outdoor, DLF4(A/H) SIZES: 9K, 12K, 18K, 24K, 30K, and 36K NOTE: Read the entire instruction manual before starting the installation.

More information

Air-Cooled Split-System Condensing Units for Rooftop Systems and Air Handlers Models RCS 10E to 20E 10, 12.5, 15 & 20 Tons

Air-Cooled Split-System Condensing Units for Rooftop Systems and Air Handlers Models RCS 10E to 20E 10, 12.5, 15 & 20 Tons Installation and Maintenance Manual IM 910 Group: Applied Systems Air-Cooled Split-System Condensing Units for Rooftop Systems and Air Handlers Models RCS 10E to 20E 10, 12.5, 15 & 20 Tons Part Number:

More information

Installation Instructions

Installation Instructions PA13NA; PA14N; PA15N; PA16NW SPLIT -SYSTEM AIR ONDITIONER WITH R-410A REFRIGERANT 1-1/2-5 TONS Installation Instructions SAFETY ONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

HS25 SERVICE UNIT INFORMATION

HS25 SERVICE UNIT INFORMATION SERVICE UNIT INFORMATION HS25 Corp. 9327-L3 Litho U.S.A. HS25 SERIES UNITS The HS25 is a high efficiency residential split system condensing unit which features a scroll compressor. It operates much like

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS RAWL HIGH EFFICIENCY R-410A COMMERCIAL CONDENSING UNITS NOMINAL SIZES 10, 12.5, 15 & 20 TONS 10 & 12.5 TON 15 & 20 TON! Recognize this symbol as an indication of Important Safety

More information

Installation Instructions

Installation Instructions 25HBB, 25HBC, 25HCD Comfortt Series Heat Pumps with Puronr Refrigerant 1 1/2 To 5 Nominal Tons Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY

More information

Corp L9 Revised HS27 SERIES UNITS SPECIFICATIONS. Model No. HS HS HS HS27-042

Corp L9 Revised HS27 SERIES UNITS SPECIFICATIONS. Model No. HS HS HS HS27-042 Service Literature Corp. 9619 L9 Revised 08 2004 HS27 SERIES UNITS HS27 The HS27 is a 14 SEER high efficiency residential split system condensing unit which features a scroll compressor. It operates much

More information

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T29 Model INSTRUCTION MANUAL Rev. I P/N 89104464 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE

More information

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE INSTALLATION INSTRUCTION CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS Supersedes: Nothing 550.38-N6Y (1095) MODELS H*DB076 035-13578 WARNINGS are given to alert the installer that severe personal injury,

More information

Installation Instructions

Installation Instructions CNPHP Cased N s Horizontal Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION...

More information

Safety Labeling and Signal Words

Safety Labeling and Signal Words Theseinstructionsmust bereadand understoodcompletelybeforeattemptinginstallation. DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard

More information

T-Series Air Conditioner T20 Model

T-Series Air Conditioner T20 Model INSTRUCTION MANUAL T-Series Air Conditioner T20 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

C7 Series Split System Uncased Indoor Coils

C7 Series Split System Uncased Indoor Coils Installation Instructions C7 Series Split System Uncased Indoor Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

Installation Instruction

Installation Instruction 40QAC / 38HDR 40QAQ / 38QRR Ceiling---Suspended Duct Free Split System Sizes 018 to 060 Installation Instruction 40QAC, QAQ Unit 38HDR, QRR Unit the environmentally sound refrigerant NOTE: Read the entire

More information

Liebert Prop Fan Condensing Unit

Liebert Prop Fan Condensing Unit Liebert Prop Fan Condensing Unit 50 Hz and 60 Hz Installer/User Guide Technical Support Site If you encounter any installation or operational issues with your product, check the pertinent section of this

More information

HEAT PUMP INSTALLATION MANUAL

HEAT PUMP INSTALLATION MANUAL DUCTLESS INVERTER HEAT PUMP INSTALLATION MANUAL Models: TERRA09HP230V1A TERRA12HP230V1A TERRA18HP230V1B TERRA24HP230V1B Thank you for choosing a Gree Terra Ductless Heat Pump for your customer. Please

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information