e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)
|
|
- Maximilian Kennedy
- 5 years ago
- Views:
Transcription
1 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send to building principal and facilities director asking staff to be instructed to keep vents clear at all times. Record locations here: 2. Ground Level Outdoor Inspection (weather permitting) a. Univent air intakes are free of obstructions. If false, record locations here: b. Filters i. Medium efficiency filters are installed in all univents. If false, list locations and create work orders to initiate corrective action. ii. High efficiency filters are installed in the air handling units. If false, list locations and create work orders to initiate correction action. iii. Filters are being changed every six months and the installed date is written on the outer filter casing. If filter is older than 6 months, list locations and create work orders to initiate corrective action. c. Insects, bird nests, or droppings are not evident near outdoor air intakes. If false, indicate locations here: d. Trash dumpsters are located away from doors, windows, and outdoor air intakes. e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) f. Trucks and buses are not allowed to keep their engines idling near the building. Page 1 of 9
2 g. No evidence of drainage problems exist. Water drains away from the building including roof downspouts. h. Sprinklers do not spray directly toward the building or into outdoor air intakes. i. Grass clippings from mowers are directed away from the building air intakes. j. Clean walk-off mats are present at exterior entrances. 3. Roof (Inspections conducted weather permitting) a. Roofing consultant has not found any issues requiring immediate repair. Most recent roofing inspection date/company: 5-year roofing plan completed 5/25/2010 with C. E. Crowley & Associates. b. There is no evidence of water ponding on the roof. This is a ballasted roof but no evidence of ponding was apparent. c. Intake ventilation units are operating properly and free of debris. d. All exhaust fans are operating properly and free of debris. e. Air intake dampers are set to allow air flow even at minimum setting. f. Insects, birds, animal nests or droppings are not evident near outdoor air intakes. g. Plumbing stacks and exhaust vents are located away from air intakes. 4. Attic a. There is no evidence of roof or plumbing leaks. No Attic Page 2 of 9
3 Page 3 of 9 b. There is no evidence in attic of insects, birds, animals, or nests. No Attic 5. General Considerations a. Classrooms, offices and/or common areas appear recently cleaned. If examples of poor housekeeping are found, record locations below: b. Only vacuums with HEPA filters are being used. c. All supply and exhaust ventilation units are working properly. d. Occupied space temperatures and relative humidity levels are within the standards listed below. i. Temperature range: Winter temperatures degrees. Summer temperatures in air-conditioned spaces and in non-air-conditioned spaces. Outdoor air temperature: 35.6 degrees. Highest temperature Location: 404; Reading of 75.9 degrees. Lowest temperature Location: 102; Reading of 71.4 degrees. ii. Relative humidity range is 30% to 60%. Non-air-conditioned spaces may be higher on rainy or humid summer humid days. All spaces may be less than 30% when the out-door air temperature is less than 32 degrees. Outdoor relative humidity: 41.1% Highest relative humidity Location: 102; Reading of 30.8% Lowest relative humidity Location: 302;Reading of 18.1% Readings not within acceptable standards will result in the creation of a work order, requesting maintenance to address. (Readings are noted on the attached test data sheet)
4 e. Occupied space readings of carbon monoxide (CO) levels are less than 9.0 PPM. Outdoor Air CO Reading:.0 Highest CO Location: Principal's office Reading: 1.0 Lowest CO Location: Several rooms Reading: 0.0 If the CO level is greater than 9.0 PPM in any space as measured with a handheld device or leave-in monitor, the space must be cleared of all occupants and steps taken to correct the problem. The issue will be immediately addressed by maintenance and the Fire Department. (Readings are noted on the attached test data sheet) f. CO2 levels in any occupied space are below threshold limits. i. Perform CO2 check with Gray Wolf or other portable device. Measure four times yearly or more often if needed. Measure only in fully occupied rooms. Reading should be less than 700 PPM plus outside air CO2 PPM. 700 PPM PPM = 1050 PPM Assume outside CO2 is 350 if temperature is below 41 degrees and air is not stagnant with no- wind. Record all occupied space CO2 levels on forms provided. Provide the outdoor CO2 level as well as the high and low CO2 extremes below: Outdoor reading: 373 PPM Highest CO2 reading Location: 315; Reading of 1028 PPM Lowest CO2 reading Location: 106; Reading of 443 PPM ii. If reading is above threshold, check univent and air handling dampers to ensure a value is set to provide at least 15 cfm of fresh air intake per student based on average space occupancies. If reading is consistently elevated, then use data logging to monitor CO2 concentrations over time and look for other sources of problems. Page 4 of 9
5 iii. CO2 levels were checked three months ago. iv. CO2 levels on leave-in devices, where present, where checked. NONE g. Offensive odors are not apparent. If false, list problem areas: h. Water damage is not evident. Check for roof leaks, pipe leaks, spills, stained ceiling tiles, etc, visually and with moisture meter. Look for the source of any water leaks and schedule repairs. Discard porous items such as ceiling tiles if wet for more than 24 hours. For carpeting, if less than 9 square feet of wet area, shampoo with germicide and fan dry. For areas greater than 9 square feet, replace carpet with tile in reasonable timeframe. If carpet is over ACM tile, replace during next unoccupied break time (winter break, spring break, summer). If false, record findings and locations here: i. Mold or mildew growth is not evident. If false, record findings and locations here: j. All pest management issues are being handled by Integrated Pest Management. k. No other unresolved concerns or complaints by building personnel are known. If false, list any pending issues not previously mentioned in this report here: l. There are no incomplete HVAC preventative maintenance (PM) work requests. If false, list any incomplete HVAC work request here: 6. Bathrooms and General Plumbing a. All locker or restroom exhaust fans are working. Inoperable or malfunctioning fans are listed as follows: Location: Problem: Page 5 of 9
6 b. All of the following drain-trap maintenance procedures are being conducted according to the frequency indicated. If false, indicate all deviations and locations: The custodial staff is reminded regularly on these procedures. i. Water is poured into floor drains once per week (approximately 1 quart of water) or water and a teaspoon of cooking oil poured into the drain once a month. ii. Water is poured into sinks at least once per week (about 2 cups of water). iii. Toilets are flushed at least once per week. 7. Lab Chemicals & Maintenance Supplies a. Lab chemicals are used with exhaust fans turned on. b. Lab chemical storage areas have been inspected yearly by ROE and Fire Department. Record last inspection dates below: ROE: 11/2011 LZFD: 11/2011 c. Flammables are not stored with igniters. d. All chemicals that may react or produce toxic or explosive by-products are separated and maintained in approved containers stored in approved storage. (e.g. lockable, with appropriate ventilation). e. Chemical disposal records for all lab chemicals are available for review. f. All cleaning products used in building contain no/low VOC. Page 6 of 9
7 List any exceptions: g. Increased ventilation is considered when installing new carpets, cleaning upholstered furniture, shampooing carpets, etc. h. Exhaust ventilation systems in chemical and trash storage areas are turned on and functioning properly. i. Portable fuel containers are properly closed. j. Power equipment, like snow blowers and lawn mowers, have been serviced and maintained according to manufacturers guidelines. k. Oil based paints are stored in approved storage cabinets. No oil based paint is allowed in the district. l. Green Cleaning products and processes are used in this building. 8. Combustion Appliances a. Combustion analysis is performed at the start of the heating season on all boilers. Adjustments are made to the burners to correct any abnormalities and improve efficiency. b. In rooms that contain combustion appliances, there is no evidence of combustion gas or fuel odors. If false, record locations here: c. No leaks, disconnections, and/or deterioration were found on exhaust hoods. d. Flue components are clean and free of soot. e. All combustion appliances have flues or exhaust hoods and vent NO2. i. If false, inspect cooking hoods, chemical hoods. Assure that cooking stoves and appliances are correctly installed, used, and maintained according to manufacturers specifications. Page 7 of 9
8 ii. If not vented, ensure that leave-in CO monitors are placed in room. Record locations here: NONE iii. CO levels in rooms with combustion appliances are measured and recorded with an IAQ monitor. CO readings outside of normal CO range will result in an immediate response by maintenance to reduce CO level or vacating the room/building, if necessary. Record locations here: 9. Other a. Paint No peeling and/or flaking paint found. If planned building renovation will damage paint or if peeling paint is discovered, lead testing may be necessary. If peeling paint is found, send to the building Principal and the Facilities Director alerting them of the problem. Staff and teachers need to pick up any flakes of paint to prevent children from being exposed. The Facilities Director will advise the Facilities Coordinator (a Certified Lead Paint Renovator) to test the paint for lead. Lead paint was discontinued in Buildings built after 1978 are exempt from lead paint testing. If lead is present, required repairs should be done immediately using lead-safe methods and, if necessary, a licensed lead contractor. Location(s) of known peeling paint in building: b. The following preventive measures are being taken to reduce lead exposure. i. Play areas and toys are cleaned nightly. ii. Floors are mopped nightly. iii. Dust at least weekly. c. Radon testing is recommended by IEMA every 5 years. Last testing date listed below: Date: 12/20-22/2012; Reading of <1.3 (Highest) pci/l in several rooms. Page 8 of 9
9 National concern: 4.0 pci/l or higher. d. The IAQ testing equipment used for this inspection was calibrated and is in good working order. Equipment Used: Gray Wolf Last date of calibration: Page 9 of 9
10 Site Location Date/Time Temperature F 395 W. Cuba Road. Indoor Air Quality Testing Readings Winter 2012 Relative Humidity %RH Carbon Monoxide ppm Carbon Dioxide ppm Occupants Taken by Taken With Issac Fox Elementary Outdoor Air 07-Feb-12 10:38:37 AM Denys Gray Wolf Issac Fox Elementary Feb-12 10:55:50 AM Denys Gray Wolf Issac Fox Elementary Feb-12 10:57:37 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:05:05 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:01:25 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:03:11 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:48:39 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:25:14 AM Denys Gray Wolf Issac Fox Elementary 202A 07-Feb-12 12:43:37 PM Denys Gray Wolf Issac Fox Elementary Feb-12 11:26:52 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:28:28 AM Denys Gray Wolf Issac Fox Elementary Feb-12 12:41:44 PM Denys Gray Wolf Issac Fox Elementary Feb-12 12:40:18 PM Denys Gray Wolf Issac Fox Elementary Feb-12 11:30:47 AM Denys Gray Wolf Issac Fox Elementary Feb-12 12:37:30 PM Denys Gray Wolf Issac Fox Elementary Feb-12 12:39:00 PM Denys Gray Wolf Issac Fox Elementary Feb-12 11:46:55 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:06:52 AM Denys Gray Wolf Issac Fox Elementary Feb-12 12:45:49 PM Denys Gray Wolf Issac Fox Elementary Feb-12 11:08:01 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:09:22 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:43:21 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:44:52 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:11:35 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:12:52 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:14:19 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:15:42 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:17:32 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:19:04 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:20:31 AM Denys Gray Wolf Issac Fox Elementary Feb-12 11:22:07 AM Denys Gray Wolf Issac Fox Elementary 400A 07-Feb-12 01:05:41 PM Denys Gray Wolf Issac Fox Elementary Feb-12 01:08:17 PM Denys Gray Wolf Issac Fox Elementary Feb-12 12:30:08 PM Denys Gray Wolf Issac Fox Elementary Feb-12 12:31:12 PM Denys Gray Wolf
11 Issac Fox Elementary Feb-12 12:32:51 PM Denys Gray Wolf Issac Fox Elementary Feb-12 12:34:56 PM Denys Gray Wolf Issac Fox Elementary Feb-12 01:09:24 PM Denys Gray Wolf Issac Fox Elementary 5 07-Feb-12 10:50:01 AM Denys Gray Wolf Issac Fox Elementary Cafeteria 07-Feb-12 11:38:39 AM Denys Gray Wolf Issac Fox Elementary Cafe office 07-Feb-12 11:41:15 AM Denys Gray Wolf Issac Fox Elementary Conference Room 07-Feb-12 12:49:51 PM Denys Gray Wolf Issac Fox Elementary Copyroom 07-Feb-12 10:51:16 AM Denys Gray Wolf Issac Fox Elementary Gym Feb-12 10:59:58 AM Denys Gray Wolf Issac Fox Elementary Nurse Feb-12 10:46:34 AM Denys Gray Wolf Issac Fox Elementary Office #4 07-Feb-12 10:48:42 AM Denys Gray Wolf Issac Fox Elementary Feb-12 10:52:31 AM Denys Gray Wolf Issac Fox Elementary Principal office 07-Feb-12 10:47:38 AM Denys Gray Wolf CO2 Formula = 1050
e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)
1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed
More informatione. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)
1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed
More informationWalkthrough Inspection Checklist
Walkthrough Inspection Checklist Name: School: Room or Area: Date Completed: Signature: Instructions 1. Read the IAQ Backgrounder and the Background Information for this checklist. 2. Keep the Background
More informationGreen Flag Level Two Survey: Indoor Air Quality Program
Green Flag Level Two Survey: Indoor Air Quality Program You have chosen to work on the Indoor Air Quality (IAQ) program to earn a Green Flag award. Answering these survey questions will take you on a tour
More informationINDOOR AIR QUALITY MANAGEMENT PLAN
INDOOR AIR QUALITY MANAGEMENT PLAN BEMIDJI AREA SCHOOLS INDEPENDENT SCHOOL DISTRICT #3 1 BEMIDJI, MINNESOTA Updated : 2/4/2015 Bemidji Area Schools Created or revised by: Steve Spindler Safety Manager
More informationIndoor Air Hazards in the Home Low- and No-cost Methods to Reduce Exposure
Indoor Air Hazards in the Home Low- and No-cost Methods to Reduce Exposure Community Outreach and Education Program Environmental Tobacco Smoke (AKA secondhand smoke) Do not smoke in your home or allow
More informationThe Ultimate Home Maintenance Schedule
The Ultimate Home Maintenance Schedule On-Going Quarterly Maintenance Schedule Check interior and exterior faucets for leaks. Clean aerators. Replace washers if Clean with baking soda. Pour water down
More informationOffice and classroom temperatures should average degrees when occupied.
Teacher/Staff Procedures Office and classroom temperatures should average 70-76 degrees when occupied. Staff members will be epected to properly manage their classrooms or work areas. This includes shutting
More informationWALK-AROUND INSPECTION LIST
WALK-AROUND INSPECTION LIST Page 1 of 18 BUILDING DESCRIPTION Location of building in relation to potential sources (industry, landfills, emissions, outside renovations, etc.) Original construction date
More informationBURLEIGH MANOR MIDDLE SCHOOL HOWARD COUNTY PUBLIC SCHOOL SYSTEM
BURLEIGH MANOR MIDDLE SCHOOL HOWARD COUNTY PUBLIC SCHOOL SYSTEM Built in 1992 108, 407 Square Feet 771 Student Population 91 Staff Population 2 Building Supervisors, 3 Custodians 102, 663 Square Feet of
More informationCustodial- General Cleaning Duties
Custodial- General Cleaning Duties This document is a general list of scheduled custodial routines. All cleaning is scheduled Sunday through Thursday nights with minimal coverage on weekends while classes
More informationPARISH SELF-INSPECTION GUIDE
PARISH SELF-INSPECTION GUIDE Gallagher Bassett Services, Inc. Risk Control Consulting Division June 2008 Gallagher Bassett Services, Inc. The information contained in this report was obtained from sources,
More informationabout your house Assessing the Comfort and Safety of Your Home s Mechanical Systems
about your house CE 28 k Assessing the Comfort and Safety of Your Home s Mechanical Systems The heating, ventilating and air conditioning (HVAC) systems are a vital part of every home. These mechanical
More informationTop of the World Tower
Workplace Building Preventive Maintenance Checklist conducted for Top of the World Tower Conducted on 22 Oct 2018 11:00 AM Prepared by Greg Langley Location 1247 Dartmouth St, Albany, CA 94706, USA Completed
More informationFood needs to be in sealed containers 03. FOOD: Unsealed, left in
01A. ODOR: Unusual or 6/14/2017 14:15offensive Boys room Urine smell 01A. ODOR: Unusual or 6/14/2017 15:16offensive Office Odor and poor air flow x 01B. TEMPERATURE: 6/14/2017 13:42Uncomfortable 202 Warm
More informationHEALTHY AIR / HEALTHY HOMES Home Walkthrough Checklist
This do-it-yourself will help you find ways to increase the indoor air quality in your home and make it a healthier place to live. INSTRUCTIONS 1. Walk around the outside and inside of your home using
More informationSafety Regulations and Procedures ENVIRONMENTAL HEALTH Indoor Air Quality - Work Practices - S New 1/95
Indoor Air Quality - Work Practices ALL EMPLOYEES Safety Regulations and Procedures Practice HAZCOM Know Yourself CUSTODIANS Filters Understand and apply the Hazard Communication (HAZCOM) Standard (see
More informationCustodial Worker I SAMPLE
Custodial Worker I SAMPLE Essential Function: Cleans general public areas as assigned straightens furniture, removes garbage, dusts, vacuums, mops, and operates various cleaning equipment Furniture in
More informationP.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces
P.O. Box 799900, Dallas, TX 75379-9900 USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals,
More informationFood Preparation and Service- Part 5 Self-Inspection Checklist
Optional Information Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Food Preparation and Service- Part 5 Self-Inspection Checklist Guidelines: This checklist
More informationML180UH SERIES GAS FURNACE WARNING WARNING
2017 Lennox Industries Inc. Dallas, Texas, USA 506525-01 04/2017 Supersedes 10/2015 ML180UH SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property damage,
More informationOperations Maintenance and Evaluations
Operations Maintenance and Evaluations Adequate exterior maintenance of a chapter house should include annual evaluations, using the following guidelines. The roof should be reviewed with regard to years
More informationCMHC HOME MAINTENANCE CHECKLIST
Make sure air vents indoors and outdoors (intake, exhaust and forced air) are not blocked by snow or debris. Check and clean range hood filters on a monthly basis. Test ground fault circuit interrupter(s)
More informationTighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance
Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December
More informationHome Maintenance Schedule
Home Maintenance Schedule Regular Maintenance is the Key Inspecting your home on a regular basis and following good maintenance practices are the best way to protect your investment in your home. Whether
More informationCENTRAL KITSAP SCHOOL DISTRICT BOARD PROCEDURE
MANAGEMENT SUPPORT SERVICES Utilities Management Introduction In support of Central Kitsap School District (CKSD) Utilities Conservation Policy, the following procedure is set forth to establish operating
More informationWhile most maintenance is seasonal, there are some things you should do on a frequent basis year-round:
Inspecting your home on a regular basis and following good maintenance practices are the best way to protect your investment in your home. Whether you take care of a few tasks at a time or several all
More informationSchool Fire Safety Checklist
Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights
More informationExisting Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1
L21366/101 090 00.00/Page 1 HVAC EXECUTIVE SUMMARY The North Middlesex Regional High School has received average maintenance of the HVAC systems over its occupied years. Even with adequate maintenance,
More informationLIMITED MICROBIAL & IAQ SURVEY CLOSING REPORT SOUTHEASTERN SCHOOL DISTRICT 02/12/2015
HOME OFFICE PO Box 326 MT AETNA PA 19544 MEMBERS OF: VOICE 717-933-9475 FAX 717-933-1403 TOLL FREE 877-255-0558 Web Page: proaccorp.com CLOSING REPORT SOUTHEASTERN DISTRICT 02/12/2015 PROJECT LOCATION:
More informationIndoor Air Quality Program
008-009 Indoor Air Quality Program Raymond J. Brosel Superintendent of Schools Dr. Frank T. DeBerardinis sistant Superintendent for Business/ Board Secretary October 008 We would like to acknowledge the
More information1. Accident Prevention
Office of Environmental Health & Safety Facility Inspection Program 333 S. Beaudry Avenue, 20 th Floor Los Angeles, Ca 90017 Phone: (213) 241-3199 Fax: (213) 241-6816 SCHOOL SAFETY COMPLIANCE CHECKLIST
More informationCUSTODIAL CUSTOMER SERVICE GUIDE
CUSTODIAL CUSTOMER SERVICE GUIDE INSIDE what we clean & how often we clean it 2. Classrooms & Teaching Labs 3. Research Labs & Halls & Lobbies 4. Offices & Restrooms 5. Stairwells & Conference Rooms 6.
More informationAllisonville Elementary School Facilities Highlights Built: 1960 Last Major Renovation: 28 years ago Capacity: 650 Current Enrollment: 767
Allisonville Elementary School Built: 1960 Last Major Renovation: 28 years ago Capacity: 650 Current Enrollment: 767 ADA improvements are Fire alarms need to be updated Playground equipment needs to be
More informationWILLIAM & MARY CUSTODIAL TASK & FREQUENCY LIST. PUBLIC SPACE: ENTRANCES, LOBBIES, AND CORRIDORS Daily Weekly Monthly Quarterly Yearly
WILLIAM & MARY CUSTODIAL TASK & FREQUENCY LIST PUBLIC SPACE: ENTRANCES, LOBBIES, AND CORRIDORS Daily Weekly Monthly Quarterly Yearly Collect & properly dispose of recycling as needed Dust, or wipe all
More informationNatural Gas Appliance Testing Action Guidelines (Non ESA/Low Income 5 )
Natural Gas Appliance Testing Action Guidelines (n ESA/Low Income 5 ) The purpose of these Action Guidelines is to describe the actions participating contractors and/or inspectors should take in the event
More informationTHIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL
SECTION 15100 PART 1 GENERAL THIS IS A DESIGN GUIDE NOT A SPECIFICATION Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL HVAC SYSTEMS APPLICATIONS 1.1 SCOPE: The intent of this
More informationUSER S INFORMATION MANUAL
2017 Lennox Industries Inc. Dallas, Texas, USA 506737-01 04/2017 Supersedes 03/2017 USER S INFORMATION MANUAL EL195UHE SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance
More informationMONTH-BY-MONTH GUIDE TO HVAC MAINTENANCE
Just like any critical piece of equipment, your heating and cooling systems require regular HVAC maintenance to keep them running properly. Home and business owners should stay on top of maintenance tasks
More informationEL195UHE SERIES GAS FURNACE WARNING WARNING
2012 Lennox Industries Inc. Dallas, Texas, USA 506737-01 12/2012 Supersedes 06/2011 EL195UHE SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property
More informationUser s Manual & Safety Instructions Read Carefully Before Use
Thank you for choosing Sunnydaze Decor. If you have any questions, comments or concerns please feel free to contact us by phone at: 888-881-4668, by email: customerservice@serenityhealth.com, or you could
More informationStanfield School District Cleaning Standards
Stanfield School District Cleaning Standards Universal Precautions Always wear protective gloves. Do not use gloves that have holes or tears. Treat all body fluid spills as if they were contaminated. Items
More informationMAINE. Downloaded g. Maintain an effective pest control program so that the facility is free of pests and rodents;
Housekeeping/Laundry/Maintenance Each licensed facility shall: MAINE Downloaded 01.15.11 g. Maintain an effective pest control program so that the facility is free of pests and rodents; 20.J.2. Soiled
More informationEL195DFE SERIES GAS FURNACE WARNING
2011 Lennox Industries Inc. Dallas, Texas, USA 506739 01 06/2011 EL195DFE SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in serious injury,
More informationSample Safety Inspection Checklist for Schools
INSPECTION Health and CHECKLIST Safety Committees 1 Sample Safety for Schools School: Date: Inspected By: Each No answer may indicate a problem. Floors and Walkways Are walkways and stairways kept clear
More informationWARNING FIRE OR EXPLOSION HAZARD.
2017 Lennox Industries Inc. Dallas, Texas, USA 506897-01 04/2017 Supersedes 10/2015 EL280DF SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property damage,
More informationSLP98UH SERIES VARIABLE CAPACITY GAS FURNACE WARNING WARNING
2015 Lennox Industries Inc. Dallas, Texas, USA 506443-01 01/2015 Supersedes 08/2012 SLP98UH SERIES VARIABLE CAPACITY GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can
More informationMANUAL WARNING FIRE OR EXPLOSION HAZARD. SL280UHNV SERIES WHAT TO DO IF YOU SMELL GAS:
U S E R S I N F O R M AT I O N MANUAL 2017 Lennox Industries Inc. Dallas, Texas, USA SL280UHNV SERIES 507650-01 10/2017 Improper installation, adjustment, alteration, service or maintenance can cause property
More informationCertificate of Inspection CHECKLIST
Neptune Township Code Enforcement 25 Neptune Boulevard Neptune, NJ 07753 732-988-5200 X211 Inspections@neptunetownship.org Rev. 05/23/18 Certificate of Inspection CHECKLIST For Residential & Commercial
More informationEL296UHV SERIES GAS FURNACE WARNING WARNING
2011 Lennox Industries Inc. Dallas, Texas, USA 506769 01 08/2012 Supersedes 10/2011 EL296UHV SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property
More informationUSER S INFORMATION MANUAL SLP98UHV SERIES
2017 Lennox Industries Inc. Dallas, Texas, USA 506443-01 04/2017 Supersedes 10/2015 USER S INFORMATION MANUAL SLP98UHV SERIES VARIABLE CAPACITY GAS FURNACE Improper installation, adjustment, alteration,
More informationEL195UH SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506597 01 11/2010 EL195UH SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in serious injury,
More informationSuburban Propane Notice of Public Awareness. Additional Information for Customer s Buried Piping
October 20, 2014 Suburban Propane Notice of Public Awareness Additional Information for Customer s Buried Piping In accordance with Federal Safety Standards, you are being notified of the following: The
More informationCustodial Guide
Custodial Guide 2018-2019 Table of Contents Page Number 1 General Items to Note 2-3 Maintenance for Office Areas 4-5 Maintenance for Classrooms and Hallways 6 Maintenance for Lounge Areas 7 Maintenance
More informationCleaning Service Levels
Restrooms Empty waste receptacles and change liner, as needed. Restock dispensers: soap, paper towel and toilet tissue. Clean mirrors; clean and disinfect urinals, toilets, and sinks. Polish stainless
More informationCarbon Monoxide Safety Information
Aurora Fire Rescue City of Aurora Fire Administration 15151 E. Alameda Parkway, Suite 4100 Aurora, Colorado 80012 303.326.8999 Worth Discovering auroragov.org Carbon Monoxide Safety Information Aurora
More informationAUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS
AUTOMATIC MAKE-UP AIR DAMPER WITH READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. Installation
More informationVacant Building Loss Prevention Best Practices
Vacant Building Loss Prevention Best Practices Vacant properties are susceptible to a unique set of hazards that should be considered and addressed to avoid losses. Occupants are often the eyes and ears
More informationINDOOR AIR QUALITY ASSESSMENT. Department of Revenue Office 218 South Main Street Fall River, MA
INDOOR AIR QUALITY ASSESSMENT Department of Revenue Office 218 South Main Street Fall River, MA Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor Air Quality
More informationVENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06
page 1 of 6 VENTING CLEARANCES The vents should not be obstructed and all joints properly fitted. Floors, ceilings and walls must be cut or framed to provide necessary clearance to vents. Metal strippings
More informationFIRE PREVENTION. Consider installation of a fire sprinkler system.
FIRE PREVENTION Preventing fire losses is largely dependent upon controlling sources of ignition and combustible materials. The most common causes of fire to church properties are from electrical and heating
More informationWARNING FIRE OR EXPLOSION HAZARD.
2017 Lennox Industries Inc. Dallas, Texas, USA 506698-01 04/2017 Supersedes 10/2015 SL280DFV SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property
More informationInside Out Home Inspections
Cover Page Inside Out Home Inspections Property Inspection Report Inspection prepared for: John Doe & Jane Doe Date of Inspection: 5/10/2014 Inspector: Lucas Sargent PO Box 514, Tioga, PA 16946 Phone:
More informationA GUIDE TO THE ROCK ISLAND HOUSING CODE. Prepared By: The City of Rock Island Inspection Division
A GUIDE TO THE ROCK ISLAND HOUSING CODE Prepared By: The City of Rock Island Inspection Division 2 P a g e THIS QUICK GUIDE TO ROCK ISLAND S PROPERTY MAINTENANCE CODE IS INTENDED FOR THE USE OF ALL RESIDENTS
More informationG61MPV SERIES GAS FURNACE WARNING
2003 Lennox Industries Inc. Dallas, Texas, USA 504,809M 03/2009 Supersedes 06/2003 G61MPV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result
More informationHEALTH/LIFE SAFETY ANNUAL INSPECTION CHECKLIST (ROE)
HEALTH/LIFE SAFETY ANNUAL INSPECTION CHECKLIST (ROE) Administrative and General Building Requirements Safety reference plans (1) Fire alarm audibility (10) Alcohol hand-rub-dispensers (19) School safety
More informationBeaufort County Community College. Maintenance and House Keeping Plan
Beaufort County Community College Maintenance and House Keeping Plan Summary: The College s facility management is handled by the Maintenance Department. The Director of Plant and Maintenance Operations
More informationIAQ Building Education and Assessment Model (I-BEAM)
Heating, Ventilation, and Airconditioning (HVAC) Text Modules IBEAM IAQ in L... http://www.epa.gov/iaq/largebldgs/ibeam/text/hvac.html Page 1 of 6 10/21/08 IAQ in Large Buildings http://www.epa.gov/iaq/largebldgs/ibeam/text/hvac.html
More informationCUSTODIAL SERVICES CUSTOMER SERVICE GUIDE
CUSTODIAL SERVICES CUSTOMER SERVICE GUIDE WHAT WE CLEAN AND HOW OFTEN WE CLEAN IT As part of an ongoing effort to improve custodial customer service, we developed the Custodial Services Customer Service
More informationLighthouse. Prepare for your LHA inspection. Inspection Guide
Guiding landlords to a successful relationship with LHA Lighthouse Inspection Guide (402) 434-5500 www.l-housing.com Prepare for your LHA inspection LHA adheres to HUD s Housing Quality Standards to ensure
More informationHome Performance Science
Home Performance Science Symptoms of a Sick House Too hot/too cold rooms Respiratory problems Headaches/nausea Smoky fireplace Foggy windows Stuffy air and lingering odors Peeling paint Constant dust problems
More informationNew Food Service Plan Review Checklist
New Food Service Plan Review Checklist The following items should be completed before you return your application. Read Starting a Food Service Brochure to help you in the process. Confirm whether property
More informationATTACHMENT A - Services Specifications
ATTACHMENT A - Services Specifications Notes- Annual services to be performed prior to the start of the school year (June 15-Aug 1) Schedules for clearing must be approved by each building s chief administrator
More informationFire Prevention Plan for Alumni Center 1507 Dana Avenue
University Relations Division Department of Physical Plant Human Resources Community Building Institute Office of University Communications and Administrative Office Building Fire Prevention Plan for Alumni
More informationVOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED
Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological
More informationIEQ SCHOOL DATA BASE
LOOK-FORS ROOM/LOCATION COMMENTS ADMIN FACILITIES WORK ORDER NUMBER of POTENTIAL IEQ ASSIGNED COMPLETION 30 DAY REVISIT CLOSED 1. No unusual or offensive odors, gym Too cold on walk through day 15171 12/21/16
More informationFacilities, Materials and Equipment Policies and Procedures-LCHS/EHS
Policies and Procedures-LCHS/EHS FME-1.. Playground Safety and Environment FME-2.. Daily Classroom Safety Checklists FME-3..Play Area Safety Checks FME-4 Drug and Tobacco-Free Environments FME-5.. Physical
More informationFire Prevention Plan for Cintas Center 1624 Musketeer Drive
Athletics Xavier Dining Cintas Center Operations Xavier Leadership Center for Cintas Center 1624 Musketeer Drive Xavier University November 1, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction...
More informationNFPA 101 Life Safety Code Culture change 2012
NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted
More informationUSER S INFORMATION MANUAL
USER S INFORMATION MANUAL UPFLOW & DOWNFLOW/HORIZONTAL CONDENSING GAS FURNACES SAFETY Recognize this symbol as an indication of Important Safety Information If not installed, operated and maintained in
More informationBSES IEQ Walkthrough Summary Spring Room Observations (Responses)
01A. ODOR: Unusual or offensive 55 01B. TEMPERATURE: Uncomfortable Kitchen Bathroom does not smell clean Kitchen was warm but it had not yet been opened for the day. in room, dirty lunch boxes 45 Need
More informationChimney Fire Prevention
Chimney Fire Prevention Ways to Avoid Chimney Fires Use seasoned wood Build smaller, hotter fires that burn more completely and produce less smoke Never burn cardboard boxes, wrapping paper, trash, rubber,
More informationSpray Polyurethane Foam and Open-Combustion Appliances
Spray Polyurethane Foam and Open-Combustion Appliances Before applying SPF (spray foam polyurethane) insulation in an attic or crawl space it is important to determine if there are any appliances present,
More informationCOMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES*
COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* *Vented appliances refer to natural draft appliances equipped with a barometric draft regulator or Category I appliances equipped with a draft
More informationCORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS
CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS FIRE EXTINGUISHER REQUIREMENTS 1. All commercial cooking operations require at least one 2A10BC rated (5 or 6 pound size) fire extinguisher.
More informationVentilation Techniques. Topic 5 - Audio 53
Topic 5 - Audio 53 Increasing Fresh Air Increasing fresh air make-up to a building can dilute radon and other indoor air contaminants. Increasing make-up air can reduce the negative pressures within a
More informationBraga Free Standing Floor Indoor Outdoor Ethanol Fireplace User s Manual Model: GF202100
Braga Free Standing Floor Indoor Outdoor Ethanol Fireplace User s Manual Model: GF202100 1 Moda Flame Braga Free Standing Floor Indoor Outdoor Ethanol Fireplace Included in delivery (Parts List): A. Fireplace
More information3. 21st Century Learning A. Districtwide Flexible Learning - Allowance for Flexible Furniture $600,000 Subtotal $600,000
1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades Allowance $300,000 C. Tilden Entrance Upgrades D. Door and Glass Improvements Allowance $500,000 E. Alert
More informationUSER S INFORMATION MANUAL
USER S INFORMATION MANUAL THESE INSTRUCTIONS APPLY TO THE MODEL GTM SERIES GAS- FIRED WARM AIR FURNACE. This symbol indicates important Safety Related Information FIRE OR EXPLOSION HAZARD Failure to follow
More informationOperation and Maintenance Manual
Operation and Maintenance Manual In compliance with the California Green Building Standards Code, this Operation and Maintenance Manual shall be available at final inspection and remain with the building
More informationUSER S INFORMATION MANUAL
USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this
More informationUSER S INFORMATION MANUAL
USER S INFORMATION MANUAL UPFLOW/HORIZONTAL & DOWNFLOW TWO STAGE INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this manual is not
More informationIEQ SCHOOL DATA BASE. School Name: Reservoir High School Principal: Patrick Saunderson DATE: 1/23/2017. WORK ORDER NUMBER of POTENTIAL IEQ
LOOK-FORS ROOM/LOCATION COMMENTS ADMIN FACILITIES WORK ORDER NUMBER of POTENTIAL IEQ DATE ASSIGNED COMPLETION DATE 30 DAY REVISIT CLOSED 1. No unusual or offensive odors, or temperature discomfort 316,
More informationModel Carbon Monoxide (CO) Alarm Response Policy
Published on MTAS (http://www.mtas.tennessee.edu) January 26, 2019 Model Carbon Monoxide (CO) Alarm Response Policy Summary: This model policy was created to provide procedures for personnel to follow
More informationHome Characteristics and Asthma Triggers Checklist for Home Visitors
Home Characteristics and Asthma Triggers Checklist for Home Visitors Using this Home Assessment Can Help Make Homes Healthier. A trained home visitor can help find common asthma triggers in homes and discuss
More informationHELENA PUBLIC SCHOOLS FRONT STREET LEARNING CENTER CLEANING OUTCOMES ASSESSMENT. May 2013
HELENA PUBLIC SCHOOLS FRONT STREET LEARNING CENTER CLEANING OUTCOMES ASSESSMENT May 2013 HPS FRONT STREET LEARNING CENTER CLEANING OUTCOMES ASSESSMENT PURPOSE During the week of May 20th, 2013 BRUCO INC.
More informationSection 8 Housing Choice Voucher Program. Housing Quality Standards (HQS) Inspection Checklist
Section 8 Housing Choice Voucher Program Housing Quality Standards (HQS) Inspection Checklist SECTION 8 PROGRAM RESIDENT AND OWNER'S HQS GUIDE THE HOUSING QUALITY STANDARDS INSPECTION The unit must pass
More informationGood Ideas For Propane Safety
Good Ideas For Propane Safety What You Don't Know CAN Hurt You Safety...It's Up to You Propane is a safe, reliable fuel. Like many other fuels, however, it is flammable. That means it can be dangerous
More informationPLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion
AUTOMATIC MAKE-UP AIR DAMPER WITH To register this product visit: www.broan.com MODELS MD6T MD8T MD10T READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE,
More informationAvila Contemporary Indoor Outdoor Ethanol Fireplace. User s Manual. Model: GF201500
Avila Contemporary Indoor Outdoor Ethanol Fireplace User s Manual Model: GF201500 1 Moda Flame Avila Contemporary Indoor Outdoor Ethanol Fireplace Included in delivery (Parts List): A. Fireplace body 1pc
More information