DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

Size: px
Start display at page:

Download "DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION"

Transcription

1 PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. Design and specify refrigeration systems and equipment in accordance with "Energy Conservation Standards" stipulated in Section 15010, Basic Mechanical Requirements. 2. Specify refrigerants that are CFC free, meet the requirements for ARI 700. Refrigerants shall have an Ozone Depletion Potential (ODP) less than or equal to Specify that isolation valves shall be provided by manufacturer in order to allow servicing of major components (e.g., compressor, receiver, condenser, filter-dryer, expansion valve) with no loss of refrigerant; the filter dryer shall have a three-valve arrangement with bypass. 4. Review with DPS Project Manager the equipment-mounted gauges desired for diagnosis and service. 5. Specify that Contractor needs to label the amount of refrigerant in the system in pounds, as required by IMC. 6. Provide Refrigeration Room Ventialtion in accordance with the current IMC and ASHRAE Standard Specifically, DO NOT require that self-contained breathing apparatus (SCBA) to be provided. ASHRAE Standard does not require SCBA. 8. Provide low ambient controls and crankcas heaters for air cooled chillers. B. DX Condensers: 1. For units requiring operation down to -30 o F, provide low ambient control package to allow start-up and positive head pressure control. C. Controls: all equipment controllers and system controllers must use BACnet protocol to integrate into the building automation system. Refer to Section Integrated Building Automation System (IBAS). Provide all necessary hardware and software to connect control panels or controllers to DPS Integrated Building Automation System. Refer to Section Integrated Building Automation System (IBAS) for interface requirements. D. Demolition: specify that all refrigerant be removed, recovered and reclaimed prior to demolition of any equipment containing refrigerant, such as rooftop units, split-system condensing units, air conditioning units and chillers. Specify that Contractor notifies DPS HVAC shop supervisor prior to commencing demolition work. DPS personnel will either remove refrigerant from equipment or direct contractor to remove refrigerant. All handling of refrigerant will be by certified refrigeration technicians, approved by the U.S. EPA. PART 1 GENERAL 1.01 COMPLIANCE A. Specify that the contractor shall comply with Colorado Department of Health Regulation 15 and all applicable EPA rules and regulations regarding the purchase, disposal and handling of refrigerants SUBMITTALS A. Product Data: 1. Component and accessories list. a) Include mounting information. 2. Ratings and nameplate information. a) Include unit capacity, entering and leaving water temperatures, ambient air temperature, electrical connection requirements, clearances, unit weight. B. Quality Assurance Data: Page 1 of 8

2 1. Certified production test reports or mill test reports. 2. Test reports for previous design, and documentation showing previous design ratings and configurations. C. Project Record Documents: 1. Shop Drawings: a) Certified elevation and outline drawings with dimensions. b) Certified plan view drawings with dimensions. c) Wiring and termination drawings. D. Operation and Maintenance Data: 1. Operating and maintenance procedures. 2. Complete set of manufacturers drawings. 3. Complete documentation of inspections and tests performed, including any logs, curves, and certificates. Documentation shall note any replacement of equipment or components that failed during testing. 4. Spare parts lists. 5. Data sheets updated to reflect field installation conditions WARRANTY A. Provide compressor warranty information COMMISSIONING A. Require that a factory representative be employed for start-up of chiller COMPRESSOR REQUIREMENTS A. Compressors Over 100 ton Capacity: 1. Motors and Starters: a) Dual winding, wye-delta design with matching two-step, closed transition, time-delay starting switchgear is preferred. (An auxiliary timer in the starting circuit is required.) b) Specify that timer be set to limit starts to a minimum of 30 minutes apart, or greater as recommended by the manufacturer. c) An auto-transformer with reduced voltage start is an acceptable alternate starter. d) All motors shall have heat sensors in the windings for thermal protection. 2. Full-running Protection: a) Specify compressors equipped with high- and low-pressure safety cutouts, external overload protection, inherent thermal protection, and low oil pressure. b) Manual reset-type safeties which cause an electrical lock-out of the starting circuit when it has tripped, with an indication of which safety device has operated. 3. Gauges and Lubrication: a) Compressor package to include gauges indicating high side, low side and oil pressures. Not required if unit is equipped with microprocessor control that shows pressure at control panel. b) Forced-feed lubrication system with filter, cooler and visual inspection port in the oil reservoir. 4. Heaters: a) Specify crankcase heaters wired on a separate electrical circuit. b) Specify oil pump starter wired on a separate electrical circuit Page 2 of 8

3 5. Refrigerant Transfer: a) Unit should have provisions for pump out/down into unit-mounted receiver if application warrants it. (DPS Project Manager authorization is required for exception). 6. Pressure Relief: a) Show on drawings safety valve pressure relief piping vented to outdoors in accordance with ANSI/ASHRAE Standard Pressure relief valves shall be self-closing, resealing type. 7. Hail Guards: a) Specify hail guards to protect exposed coils in unit (DPS Project Manager authorization required for exception). B. Compressors of 60 to 100 ton Capacity: 1. Semi-hermetic, reciprocating-type, helical rotor or scroll. 2. Full running protection as described for larger compressors. 3. Suction, discharge and oil pressure gauges. 4. Crankcase heaters. 5. Oil reservoir sight glass. 6. Replaceable refrigerant filter dryers in liquid line. 7. Hydraulic capacity control by cylinder unloading for adjustments to load fluctuations. 8. Positive unloaded start. 9. An adequate discharge muffler. 10. Internal vibration isolation to provide minimum vibration transmission. 11. Closed-transition starting switchgear, determined by the electrical requirements for the particular sizes of motors. Part-winding start is acceptable. 12. As described on larger air-cooled units, specify a receiver on the condenser and provisions for pumping the full refrigerant charge into the receiver. If condenser will hold the full charge, this is an acceptable alternative. 13. Extended five (5) year warranty on compressor(s). C. Compressors under 60 but over 15 ton Capacity: 1. Hermetic or semi-hermetic reciprocating, scroll or helical rotor. 2. Inherent thermal overload protection for motors. 3. Suction, discharge and oil pressure gauges. 4. Crankcase heaters. 5. Oil reservoir sight glass. 6. Replaceable refrigerant filter-dryers. 7. Hydraulic capacity control by cylinder unloading or staging of multiple compressors. 8. Positive unloaded start. 9. Adequate discharge muffler. 10. Internal vibration isolation. 11. Closed-transition starting switchgear determined by the electrical requirements for the particular sizes of motors. 12. A receiver on the condensers and provisions for pumping the full refrigerant charge into the receiver. If condenser will hold the full charge, this is an acceptable alternative Page 3 of 8

4 13. Extended five (5) year warranty on compressor(s). D. Compressors between 7-½ and 15 ton Capacity: 1. Same requirements as 15 to 60 ton compressors, except that cylinder unloading and unloaded start features are not required on these units. E. Compressors below 7-½ tons Capacity: 1. Same requirements as 7-½ to 15 ton compressors, except that gauges are not required. PART 2 PRODUCTS 2.01 RECIPROCATING COMPRESSORS (HERMETIC) 1. Bohn 2. Bristol 3. Carrier 4. Copeland 5. Tecumseh 6. Trane 7. York B. Unit performance certified in accordance with latest edition of ARI Standard 520. C. Unit construction in accordance with ANSI B9.1 Safety Code RECIPROCATING COMPRESSORS (OPEN DRIVE) 1. Bohn 2. Carrier 3. Trane 4. York 2.03 WATER-COOLED CONDENSING PACKAGED UNITS A. Acceptable Manufacturers 1. Bohn 2. Carrier 3. McQuay 4. Trane 5. York B. Unit performance certified in accordance with latest edition of ARI Standard 520. C. Unit construction in accordance with ANSI B9.1 Safety Code and ASME Code AIR-COOLED CONDENSING UNITS Page 4 of 8

5 1. Submit recommendation. B. Unit performance certified in accordance with latest edition of ARI Standards 210 and 270. C. Unit construction in accordance with ANSI B9.1 Safety Code and ASME Code WATER-COOLED RECIPROCATING CHILLER (REMOTE CONDENSER) 1. Submit recommendations. B. Unit performance certified in accordance with latest edition of ARI Standard 590. C. Unit construction in accordance with ANSI B9.1 Safety Code and ASME Code. F. Units UL-listed and CSA certified WATER-COOLED CONDENSERS A. Acceptable Manufacturers 1. Bohn 2. Carrier 3. Refrigeration Services 4. Trane 5. York B. Unit performance certified in accordance with latest edition of ARI Standard 450. C. Unit construction in accordance with ANSI B9.1 Safety Code and ASME Code AIR-COOLED CONDENSERS 1. Submit recommendations. B. Unit performance certified in accordance with latest edition ARI Standard 460. C. Unit construction in accordance with ANSI B9.1 Safety Code. F. Units UL-listed and CSA certified. G. In units with multiple fans, isolate each fan section CENTRIFUGAL OR ROTARY-SCREW WATER CHILLER 1. Carrier Page 5 of 8

6 2. McQuay (with sound abatement kit) 3. Trane 4. York B. Chiller performance rated in accordance with latest edition of ARI Standard 550. C. Factory-wired control panel in accordance with NEC. D. Connect to Integrated Building Automation System. Refer to Section Integrated Building 2.09 COOLING TOWER (INDUCED DRAFT, VERTICAL DISCHARGE) 1. Tower-Tech 2. Baltimore Aircoil 3. Evapco 4. Marley 5. CCT B. Capacity rating in accordance with CTI Standards. Include altitude effects. C. Cooling Towers: 1. Specify the following for induced-draft towers: a) Fiberglass-reinforced polyester (or equivalent) or galvanized steel throughout. b) A propeller-type fan, on which blade pitch can be adjusted. c) A gear reducer drive for anything beyond 10 HP, if applicable. d) Motors situated outside the tower's humid airstream. e) Fill manufactured of fire-retardant PVC material (minimum 15 mil. thickness). f) Hot return water basin covers. g) Safety railings and ladder to fan deck. h) Safety cage on ladder. i) Oversized sump outlet for gravity flow to inside remote sump. j) Extended lube and oil fill lines with sight glass or dipstick. k) Stainless steel hardware, and brass or stainless steel fittings, within wet area. l) Vibration switch COOLING TOWERS (FORCED DRAFT) 1. Tower-Tech 2. Baltimore Aircoil 3. Evapco 4. Marley 5. CCT B. Provide the following for forced-draft towers: 1. "Baltibond" (Baltimore Air Coil trademark) or equivalent coating. 2. Galvinized steel sump with blow-through prevention kit Page 6 of 8

7 C. If installed indoors, relief dampers shall have stainless steel knuckles REMOTE SUMP TANK A. Furnish and install welded stainless steel or fiberglass sump tank of size and capacity shown on Drawings. B. Remote sump tank. Incorporate the following requirements in sump tank design: 1. Allow minimum water level of four (4) feet of suction head under operating conditions, or greater if required to meet NPSH of pump. And provide redundant (stand-by) condenser water pump. 2. Provide a minimum of 150 percent of drain down storage capacity in addition to the above operating level. 3. Drain down capacity to consist of volume of cooling tower water retention plus all piping exposed to freeze conditions. 4. Design vortex breaker and screen at suction outlet. 5. Provide taps on tank for sump filtration cleaning system. 6. Include inspection ladder on tank to monitor water conditions. C. Provide adequate ventilation in sump room to control humidity COOLING TOWER SUMP FILTRATION SYSTEM 1. Submit recommendations. 2. For sand-type filtration, consider PEP Model SMF-24. B. Description: pumped recirculation of water from cooling tower sump or drain down sump through filter and back to sump as shown on drawings. Include use of distribution piping to sweep floor of tower sump towards the outlet. C. Cooling Tower Sump Filtration System: 1. To improve and maintain good water conditions in condenser water, specify and show on drawings a pumped system to re-circulate water from sump through a filter and back to sump. 2. Sand filters or cyclone filters are preferred, sized to filter entire system volume each hour or at 10 percent of tower flow rate, whichever is greater. Verify that floor drain can handle flow rate of backwash. PART 3 EXECUTION 3.01 INSTALLATION A. Chillers: 1. Install water chillers on concrete base. Concrete materials and installation requirements are specified in Division Vibration Isolation: Mount water chiller on vibration isolation equipment base as specified in Specification Section Mechanical Sound and Vibration Control. 3. Maintain manufacturer's recommended clearances for service and maintenance. 4. Charge water chiller with refrigerant if not factory charged. 5. Install separate devices furnished by manufacturer. B. Condensers: Page 7 of 8

8 1. Select air-cooled condensers with sufficient capacity to compensate for altitude deration of 5,400 feet and 105 F inlet air temperature. 2. Vertical blow-type condenser fans shall not be specified for systems that are operated during winter. 3. A horizontal blow with a weather-protecting shroud designed to prevent possible blade icing and unbalance during cold weather is required. 4. Orient fans to discharge eastward where practicable. C. Cooling Towers: 1. Install cooling towers on concrete base. 2. Vibration Isolation: Mount water cooling towers on a vibration isolation equipment base as specified in Specification Section Mechanical Sound and Vibration Control. 3. Maintain manufacturer's recommended clearances for service and maintenance. D. Loose Components: Install electrical components, devices, and accessories that are not factory mounted. E. Engage a factory-authorized service representative to perform startup service STARTUP SERVICE A. Engage a factory-authorized service representative to perform startup service. B. Inspect field-assembled components, equipment installation, and piping and electrical connections for proper assemblies, installations, and connections. C. Complete installation and startup checks according to manufacturer's written instructions and perform the following: a) Verify that refrigerant charge is sufficient and water chiller has been leak tested. b) Verify that pumps are installed and functional. c) Verify that thermometers and gages are installed. d) Operate water chiller for run-in period according to manufacturer's written instructions. e) Check bearing lubrication and oil levels. f) Verify that refrigerant pressure relief is vented outside (for water-cooled water chillers). g) Verify proper motor rotation. h) Verify static deflection of vibration isolators, including deflection during water chiller startup and shutdown. i) Verify and record performance of water chiller protection devices. j) Test and adjust controls and safeties. Replace damaged or malfunctioning controls and equipment. D. Prepare a written startup report that records results of tests and inspections. E. Occupancy Adjustments: when requested within 12 months of date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to site outside normal occupancy hours for this purpose DEMONSTRATION A. Engage a factory-authorized service representative to train owner's maintenance personnel to adjust, operate, and maintain cooling towers. Refer to Division 1 Section Demonstration and Training. END OF SECTION Page 8 of 8

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. SECTION 15650 REFRIGERATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. 4. Air

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal

More information

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B.

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller: SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC). 3. 15711 - Induced Draft Cooling Tower. B.

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. SECTION 15650 REFRIGERATION EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. B. Related Section: 1. 11400

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project

More information

C. Samples for Initial Selection: For units with factory-applied color finishes.

C. Samples for Initial Selection: For units with factory-applied color finishes. SECTION 238126- SPLIT-SYSTEM AIR-CONDITIONERS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION CHILLERS

SECTION CHILLERS SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings

More information

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS PITTSBURG STATE UNIVERSITY HVAC and BUILDING AUTOMATION SYSTEM STANDARDS CHILLERS In new construction, liquid-cooled models are preferred for systems larger than 100 ton. o Trane, York and McQuay brands

More information

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL Section 23 20 00 FLUID SYSTEMS EQUIPMENT PART 1 GENERAL 1. CHILLERS Page 23 20 00-1 A. Provide chiller packages with centrifugal compressors, or screw compressors, and water cooled condensers. B. Design

More information

1.2 REFERENCES - comply with the following codes and standards:

1.2 REFERENCES - comply with the following codes and standards: 15684 ROTARY SCREW AND SCROLL CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 SPECIFIER;

More information

Modified by MSU Physical Plant / Engineering and Architectural Services

Modified by MSU Physical Plant / Engineering and Architectural Services Page 236426-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

AIR COOLED PACKAGED CHILLER

AIR COOLED PACKAGED CHILLER AIR COOLED PACKAGED CHILLER UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil.

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil. 1 1 1 1 1 1 1 1 0 1 0 1 SECTION 1 PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES A. Chiller package. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-42 22 16.00 40 (August 2017) --------------------------------- Preparing Activity: NASA Superseding UFGS-42 22 16.00 40 (August 2014) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER

More information

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT SECTION 15300 - HVAC - MAJOR EQUIPMENT PART 1 - GENERAL 1.1 MECHANICAL GENERAL A. Section 15010 is applicable. PART 2 - PRODUCTS 2.1 FANS A. General: 1. All fans shall bear the AMCA Certified Performance

More information

HVAC Service Technicians Training Center

HVAC Service Technicians Training Center HVAC Service Technicians Training Center 48-03 32 nd Place, Long Island City, NY 11101 Tel: (718) 472-0404 (718) 472-0414 Fax: (718) 433-0676 Introduction to the Refrigeration Cycle: Part 1 (AC/R-1) This

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Catalog 221-1 Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Model RCS 025C to 135C R-22/R-407C Refrigerant Contents Introduction............................... 3 The Condensing

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 236426.11 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT SECTION 23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes packaged roof top unit, unit controls, remote panel, roof mounting curb and base, maintenance service,

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/ 1 of 3 Cooling Capacity [Btuh] 24,800 * Condensing Unit SEER: 13.0 ** Condensing Unit CFM: 1,600 Condenser Fan No./Type: 1/CENTRIFUGAL Diameter x Width [in]: 10x10 Drive: Adjustable Belt Motor HP: 0.5

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

SECTION AIR-SOURCE UNITARY HEAT PUMPS

SECTION AIR-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 81 43 AIR-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

30GT FLOTRONIC AIR-COOLED CHILLERS

30GT FLOTRONIC AIR-COOLED CHILLERS 30GT-41SB 30GT040-110 FLOTRONIC AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GT-41SB Supersedes 30GT-21SB, 30GT-22SB, 30GT-23SB, Printed

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 37,800* Design CFM: 1,200 Seasonal

More information

30GN FLOTRONIC II AIR-COOLED CHILLERS

30GN FLOTRONIC II AIR-COOLED CHILLERS 30GN-19SB 30GN040-110 FLOTRONIC II AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GN-19SB Supersedes 30GN-6SB, 30GN-7SB, 30GN-8SB, Printed

More information

Product Chillers A P P L I C AT I O N S

Product Chillers A P P L I C AT I O N S Product Chillers A P P L I C AT I O N S Wineries Bottling Product Storage Product Ripening Meat Processing Florist Boxes Packaging Rooms Walk-in Coolers Beverage Boxes CENTURY PRODUCT CHILLERS Unit Configuration

More information

Evaporative Cooling Equipment Installer / Contractor Pre Start-Up Checklist

Evaporative Cooling Equipment Installer / Contractor Pre Start-Up Checklist Evaporative Cooling Equipment Installer / Contractor Pre Start-Up Checklist CONTENTS 2 Safety and equipment precautions 4 Site information 4 pre Start-up Checklist The installer/contractor shall completely

More information

SECTION COOLING TOWERS

SECTION COOLING TOWERS SECTION 23 65 00 COOLING TOWERS PART 1 - GENERAL 1.1 DESCRIPTION A. Packaged, induced draft open circuit cooling tower complete with fill, fan, inlet louvers and associated accessories and equipment. 1.2

More information

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers Models RCS 025C through 135C 25 to 135 Tons R-22/R407C Refrigerant Catalog 221-1 Table of Contents Introduction.... 3 The Condensing

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:

More information

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water.

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water. Temperature Control Units Water & Oil 30-500 F Portable Chillers Air & Water-Cooled 20-70 F Central Chillers Air & Water-Cooled Packages & Modules 20-70 F Pump Tank Stations Chilled or Tower Water 200-3600

More information

SECTION CENTRIFUGAL WATER CHILLERS

SECTION CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Chiller package. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Condenser water connections. F. Variable

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. 15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution

More information

SECTION AIR COOLED WATER CHILLER

SECTION AIR COOLED WATER CHILLER Note: Shading in the body of the specification is to identify work that will be given to the installing contractor in the subsequent Request for Chiller Installation documents to be issued by the Owner.

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS XPAK FT TYPE H - MODELS 088AR-398A SUGGESTED SPECIFICATIONS Catalog No.: 2100.91 Effective: 05/01/15 Replaces: new DIVISION 23 52 33.13 WALL-HUNG STAINLESS STEEL HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

Michigan State University Construction Standards. COOLING TOWERS Page SECTION COOLING TOWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Michigan State University Construction Standards. COOLING TOWERS Page SECTION COOLING TOWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS Page 236500-1 SECTION 236500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Temptek Auxiliary Equipment

Temptek Auxiliary Equipment Temptek Auxiliary Equipment Mold Temperature Controllers - Water Units VT-275-LX VT Series Mold Temperature Controllers are used to process temperature control to 250 F. These units use an incoloy heater

More information

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6 DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6 1.1. REFERENCE STANDARDS 1.2. GENERAL 1.1.1. The units shall be listed by Electrical Testing Laboratories (ETL) and bear the ETL label. 1.1.2.

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw) Indoor Single Package Vertical, Air-Cooled Heat Pump Unit RetroAire Model Number: Capacity Range: VPRH 9,000 to 36,000 Btuh (2.6 to 10.5 kw) Part 1 General 1.01 UNIT DESCRIPTION A. Indoor, single package

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS SECTION 23 22 23 - STEAM CONDENSATE PUMPS PART I - GENERAL 1.1 SECTION INCLUDES A. Steam Condensate Return Units, Gravity Return Type 1. Receiver 2. Pumps 3. Control Panel 4. Accessories Note to PSC: Although

More information

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS)

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS) SECTION 23 64 01 AIR COOLED WATER CHILLERS (LESS THAN 150 TONS) PART 1: GENERAL 1.1 GENERAL A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish

More information

Laboratory Enclosed Rotary Screw Air Compressor System with Air Treatment Center Package

Laboratory Enclosed Rotary Screw Air Compressor System with Air Treatment Center Package System with Air Treatment Center Package Specification General The Powerex Laboratory Screw Compressor Enclosure package shall include multiple oil-free rotary screw air compressors modules and associated

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork. SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving

More information

SECTION ROOFTOP REPLACEMENT AIR UNITS

SECTION ROOFTOP REPLACEMENT AIR UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

DESIGN GUIDELINES SECTION HVAC

DESIGN GUIDELINES SECTION HVAC 3/15/17 Cooling Methodology Chiller Plants Configurations monitoring Preferred DESIGN GUIDELINES SECTION 15700 HVAC Air-cooled chillers < or = 300 tons; water-cooled chillers > 300 tons Variable volume

More information

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements. SECTION 15855 AIR HANDLING UNITS WITH COILS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Central Station Air Handling Units. B. Related Sections: 1.02 REFERENCES 1. Section 15010 - Basic Mechanical

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS 072, 090, 120, 180 & 240 MODELS C SERIES P SERIES HEAT PUMPS SPLIT L SERIES SYSTEMS LSA Condensing Units 6 Thru 20 Ton (21.1 Thru 70.3 ) Heat Pumps 7.5 & 10 Ton (26.4 & 35.2 ) Bulletin #210164 February

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016 SECTION 23 21 23 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section.

More information

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps Product Data OMNIZONE 50BV020-064 Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps 18 to 60 Nominal Tons omnizonebwlogo 50BVC,E,J,K,Q020-034 SINGLE PIECE OMNIZONE

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

Advance Release September 2009

Advance Release September 2009 Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous

More information