SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1.

Size: px
Start display at page:

Download "SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1."

Transcription

1 / JA14 SECTION GENERAL DESCRIPTION See Figure 1 for a schematic diagram of the. See the Nova LFS parts manual for a detailed schematic of the. The function of the vehicle s is to provide clean, dry compressed air to different air systems at a pressure of between 110 and 135 psi (758 and 931 kpa). Compressed air s provide an adequate supply of compressed air that is available for the immediate operation of brakes, the pneumatic suspension system and other pneumatic equipment, leveling and kneeling, doors and other pneumatic equipment. Compressed air s are also used to cool down and condensate oil and water vapors contained in compressed air. The configuration of the supply system may vary depending on the type of air dryer installed on the vehicle. The main part of this section addresses the supply system components that are common to all types of air dryers. For the general description and the operation of the relative to the air dryer actually installed, see the corresponding module at the end of this section: module A: Supply system with a Haldex single air dryer. module B: Supply system with a Haldex double air dryer. module C: Supply system with a Bendix air dryer. module D: Supply system with a SludgeBraker. module E: Supply system with an SKF air dryer. See section : air dryer and condenser in this manual for information on the air-drying system. COMPRESSED AIR RESERVOIRS PURGING THE COMPRESSED AIR RESERVOIRS For safe and proper use, the pneumatic components of the vehicle must be supplied at all times with clean, dry compressed air. The pneumatic circuits are designed for this purpose, by the installation of components, such as the air dryers, Expello type purge valves, as well as others. However, these components may fail and/or become less efficient. It is therefore recommended to frequently perform a manual purge of the compressed air s, in order to eliminate any contaminants, which can remain there and to verify the proper functionality of the air dryer. See section : air dryer and condenser for additional information on this system. Transit authorities should determine the frequency of these manual purges according to the operating conditions of the vehicle (temperature, relative humidity, etc.), and the performance of the system. To prevent problems, the manufacturer recommends that manual purges be performed at regular intervals. The following procedure indicates how to remove all the liquid from the s without completely purging the air from the system. + WARNING: To avoid injury to the eyes, always wear eye protection at all times during maintenance or repair of the vehicle. + WARNING: Remove air pressure from the system completely before disconnecting any component. Air under pressure can cause serious bodily injuries. GENERAL MAINTENANCE All compressed air assembly bolts should be checked regularly for looseness and should be tightened as needed. Check air s for corrosion or other damage. Replace any air that has been weakened by such damage. Air s may be cleaned inside and out with steam or hot water. + WARNING: Park the vehicle on a level surface. Block the wheels to prevent any unexpected movement of the vehicle. Support the vehicle underneath with stands. See section 18: hoisting and towing in this manual for more information on lifting the vehicle.

2 2011JA14 2 / Start with the supply. With the system pressure at its operating value, open the purge valve momentarily and verify for any trace of humidity, in the form of spray or droplets. a. No presence of humidity: close the valve. b. Presence of humidity: open the purge valve repeatedly during several seconds, until no more humidity is emitted. Wait for several seconds between two of the openings to allow the humidity to return inside the purge valve. When there is no further trace of humidity, close the purge valve and go to the next. 2. If, during the procedure to remove humidity, the air pressure falls to zero, leave the valve open for several seconds, then close it again. It is unlikely that the supplementary humidity has been purged while leaving the valve open. 3. Repeat this procedure on each of the compressed air s. 4. If humidity is found in the system each day: a. Verify the system for leaks; b. Replace the air dryer cartridge; c. Verify if the proper components are installed on the vehicle. Compressed air LINES Flexible and nylon lines, as well as a copper line (coil), are installed on the vehicle. All fittings should be checked for leaks at each 5,000 mi (8,000 km) at least and they should be tightened or replaced as needed. Any line that is scratched, worn or kinked must be replaced. See section 99: General practices in this manual for additional information. COPPER LINES (cooling coils) When replacing the coils, make sure the replacement line is free from burrs, cuts and dirt. Clean by blowing compressed air. Any metal or dirt particle may seriously damage the sealing contact seats of pneumatic control units. A new line must have the same dimensions as the old one it replaces. Always use a new compression ring when replacing a line. When tightening tube fitting bolts, apply torque values indicated in Table 1 to ensure a tight fit. A leak will result if too much, or insufficient torque is applied. Apply S.A.E. 10 oil to ball sockets, to tubes and to external thread, then tighten to minimum torque and check for leaks. If there is a leak, back off the tube nut by about half a turn, then tighten to more than minimum torque. FLEXIBLE LINES + CAUTION: The path of flexible lines has been carefully designed, in order to minimize the risk of damage. This path should never be modified for any reason whatsoever. Line damages may result if a line is installed at any location other than the original Nova Bus location. NYLON Compressed air LINES Each flexible-line circuit is identifiable by its own particular color: Green: Primary braking and air dryer circuits; Red: Secondary braking circuit; Brown: Parking and emergency braking circuit; Blue: Air suspension circuit; Black: Doors circuit; hose diameter torque value DRY HUMID ¼ in. 6.4 mm 105 ±45 lb-in (12 ±5 N m) 40 ±10 lb-in (4.5 ±1 N m) 3 / 8 in. 9.5 mm 155 ±70 lb-in (17.5 ±8 N m) 40 ±10 lb-in (4.5 ±1 N m) ½ in mm 17.5 ±4.5 lb-ft (23.5 ±6 N m) 8.5 ±0.5 lb-ft (11.5 ±0.5 N m) 5 / 8 in mm 25 ±8 lb-ft (34 ±11 N m) 9.5 ±0.5 lb-ft (13 ±0.5 N m) ¾ in. 19. mm 31 ±6 lb-ft (42 ±8 N m) 15.5 ±2.5 lb-ft (21 ±3 N m) 1 in mm 35 ±5 lb-ft (47.5 ±7 N m) 17.5 ±2.5 lb-ft (24 ±3 N m) Table 1 Hose Diameter and Respective Torques

3 / JA14 + CAUTION: Nylon compressed air lines should be installed only at locations where nylon lines have been previously used. Nylon lines should never be installed at locations where temperatures may exceed 200 F (93 C). Replacement 1. Cut the correct diameter nylon line to the required length. Replacement lines must be of an appropriate length and diameter and should be fitted with end connectors. No special tools are required to install the end connectors. 2. Place the nut and then the sleeve at the end of the line. 3. Insert the stainless steel liner inside the line, pushing until the flange comes in contact with the line s cut end. 4. Place the adjacent fitting on the cut end of the line and tighten the nut until only one thread is still visible. 5. Install the other fitting at the other end of the nylon line. Make sure the line has no kinks after it has been installed on the vehicle. Avoid using a welding torch near nylon compressed air lines. Spare lines should be stored in a clean location with their ends plugged. 3. Connect a manometer (AG or equivalent that reads psi [ kpa]) on the rear supply drain, accessible through the rear engine compartment door. + CAUTION: If there is a check valve on the purge valve, make sure the manometer reads the pressure. 4. Supply the pneumatic system with an exterior compressed air supply. Connect the source to the left rear towing coupling. See Figure Pull the main door control valve up on the Operator s side console and check that the door control lever is in the closed position. 6. Release the parking brake and install a block of wood on the brake pedal to keep it fully applied. 7. When the system pressure reaches between 110 and 135 psi (758 and 931 kpa), spray soapy water on all pneumatic system component connections located under the vehicle (e.g. air dryer, ping tank, coil, etc.). See Figure 2. + CAUTION: This step validates the airtightness of the pneumatic system for the components in the rear portion of the vehicle. Make sure the left rear towing coupling valve remains open to maintain the air supply. NORMAL CONDITION OPERATIONAL TEST When any symptom, such as a slow brake application, or slow brake release, indicates a plugged or fouled compressed air line, disconnect the suspected tube or line at both ends and blow air through it to make sure that it is not completely plugged up. Check the tube or line, looking for any partial obstruction caused by dents or wrinkles. If any of those defects is found, the tube or line should be replaced. LEAK TEST Perform a leak test to ensure that there are no air leaks in the entire pneumatic system. 1. Ensure that the electrical system is off. 2. Ensure sure that the s purge valve is fully open. See Figure 1. Figure 1 - Location of Supply Reservoir Drain Valve

4 2011JA14 4 / SINGLE OR tandem CONFIGURATION Figure 2 - Left Rear Tow Coupling 8. Identify and repair any air leaks. 9. Repeat step #7, to ensure that the system pressure reaches between 110 and 135 psi (758 and 931 kpa), then shut off the external air supply. 10. Wait two minutes for the system pressure to stabilize. 11. Record the air pressure indicated by the manometer. 12. Wait 15 minutes and take another air pressure reading. Compare it with the reading taken previously. The difference should be less than or equal to 5 psi (35 kpa). This step validates the airtightness of the pneumatic system inside the vehicle (s, door mechanisms, etc.) and various sections under the vehicle (driver s seat, brake pedal, ABS valves, axle bellows, etc.) 13. If the pressure has dropped by more than 5 psi (35 kpa), check, identify and repair any air leaks (spraying soapy water as required.) Check the valves, s, hoses, connections, etc. It is possible that some valve drains have slight leaks (e.g. the R14 or R15 relay valve and the E-10 brake valve.) 14. Repeat these steps until results are satisfactory. Sometimes, a leak can be corrected by just tightening the fitting. If tightening will not stop the leak, new fittings or a new flexible line or new nylon line must be installed. Air Pressure Gauges See Figure 3. The air pressure gauge located in the instrument panel is connected by an air line to the primary supply tank (green hand) and by another line to the secondary supply tank (yellow hand). The vehicle should never start moving before indicated air pressure reaches at least 80 psi (552 kpa). When pressure falls below 80 psi (552 kpa) the low air indicator light turns on and the low pressure alarm sounds. The operator must stop the vehicle immediately and determine the cause of the pressure loss. The pressure indicator must be checked regularly with a precise test gauge. Replace the gauge by a new unit if reading differences reach or exceed 4 psi (28 kpa). Calibration Checking Check at 120 and 150 psi (827 and 1034 kpa) with increasing pressure. Check at 60 and 0 psi (414 and 0 kpa) with decreasing pressure. The hands must be positioned within the limits shown on the dial [4 psi (28 kpa)]. Lightly tap the gauge when checking at 60, 120, and 150 psi (414, 827 and 1034 kpa). Both hands must return to 0 psi (0 kpa) without having to tap on the gauge. Low-Pressure Warning Switches Low-pressure warning switches are safety devices designed to automatically trigger a warning signal whenever the compressed air system pressure falls below a pre-determined safe limit for the braking system operation. Each low-pressure warning switch is, in fact, a pneumatically controlled switch within an electrical circuit that automatically controls an indicator light and a warning horn.

5 / JA DO NOT OPERATE BELOW 80 PSI AIR REAR HAND (YELLOW) FRONT HAND (GREEN)REAR front view rear view Figure 3 -Air Pressure Gauge PREVENTIVE MAINTENANCE 1. Every 300 hours or 8,000 mi (12,800 km), check electrical connections. 2. Each year or every 100,000 mi (160,000 km), replace worn or damaged parts. tests Operational Test The low-pressure warning switch operation can be checked by reducing the system pressure while making sure that contacts close when the tank pressure is between 74 psi (510 kpa) and 86 psi (593 kpa). Contacts are closed when the indicator light is on and the buzzer sounds. Leak Test The low air pressure switch cover is equipped with a small vent that allows for checking the membrane condition. Cover the vent with a film of soapy water. If bubbles appear, indicating a leak, this means that the membrane is not airtight and the pressure switch must be replaced. Replacement Removal Release the system air pressure. Disconnect wires from the switch terminals and remove the switch from the compressed air line. Installation Install the switch in the compressed air line. Connect wires to the switch terminals. Let the air pressure rise in the system and proceed to the switch test as previously described under the heading normal condition operational tests. Anti-return (CHECK) VALVE The spring-type anti-return valves allow the compressed air to circulate in only one direction. The valves are located in the air lines between the pressure-maintaining valve and the suspension air. The anti-return valves should be removed, disassembled and cleaned regularly. These check valves should be replaced if they show evidence of wear. When installing a valve, make sure that the arrow on the cap is oriented toward the.

6 2011JA14 6 / SAFETY VALVE See Figure 4. The safety valve protects the air braking system whenever the pressure exceeds 150 psi (1034 kpa). When this pressure is reached, the safety valve opens to release excess pressure. It automatically shuts as soon as the pressure is reduced. SEQUENCE VALVE See Figure 5. The sequence valve allows the filling of the accessory when the primary and the secondary s are pressurized at 65 psi (448 kpa). Preventive MAINTENANCE Inspect the safety valve periodically and check for leaks by wetting the discharge port with soapy water. A leak is acceptable if it forms one bubble of no more than 1 in. (25 mm) in diameter, in no less than 5 seconds. Once a year, or every 50,000 mi (80,000 km), whichever occurs first, the safety valve should be disassembled and cleaned with solvent. The safety valve cannot be adjusted. The sequence valve is located on the accessory. Preventive MAINTENANCE It is recommended to check the valve operation every 6 months or 30,000 mi (48,000 km), whichever occurs first, by connecting a test gauge to the distribution line and monitoring the closing valve pressure, while air is being expelled from the distribution system. Make the necessary adjustments. Once a year or every 100,000 mi (160,000 km), whichever occurs first, disassemble the valve and clean all its parts. Replace all rubber parts showing signs of wear. 1 adjustment cap spring Piston 7 nut Piston plug grommet inlet port grommet body valve stem valve spring 1. STEM 2. BALL-CHECK VALVE 3. CASING 4. SPRING CAGE 5. DISCHARGE PORT 6. SPRING CUP 7. SPRING valve guide Figure 4 - Safety Valve Figure 5 - Sequence Valve

7 / JA14 TESTS Bench Test 1. The valve must be connected with lines providing an adjustable air supply and a small distribution volume. 2. Connect precision gauges to both lines. 3. Increase the supply pressure until both gauges indicate the same pressure. 4. Shut off the supply line and drain the distribution line. 5. Register the supply pressure as the valve closes, as indicated on the distribution line gauge. Leak Test With a supply pressure of about 100 psi (690 kpa), coat the adjusting cap slot and adjacent area with a soapy solution. Drain air from the distribution line and check again for leaks. No leaks are allowed throughout this procedure. Adjustment Pressure adjustment is determined by the tension of the spring above the piston. 1. Loosen the locking nut and turn the cap clockwise to increase the pressure. Turn it counterclockwise to decrease it. 2. Tighten the lock-nut. REPLACEMENT 1. Block or immobilize the vehicle by means other than the compressed air brakes. 2. Completely drain the. 3. Disconnect all compressed air lines from the valve. 4. Remove fastening bolts and remove the valve. 5. Repeat these steps in reverse order for reinstallation. INSPECTION 1. Immerse plastic and metallic parts in solvent for cleaning. 2. Rubber parts must also be cleaned. 3. Inspect all parts and check for wear and damages. 4. Inspect springs and check for cracks, corrosion and distortion. 5. Replace all rubber parts showing cracks and signs of wear and damage. ASSEMBLY 1. Repeat the disassembly procedure steps in the reverse order. 2. Coat rubber parts and metal-to-metal contact surfaces with a silicone-based grease. Air strainer See Figure 6. An optional single air strainer is used for the vehicle s compressed air lines. The air filter is located on the accessory equipment. The filter should be removed, disassembled and cleaned annually. Replace the seals, if necessary. Immerse the filtering material in solvent. Dry out the material and reassemble the filter. Tighten the bushings. overhaul DISASSEMBLY 1. Loosen the lock-nut. 2. Remove the adjustment cap, then the lock-nut. 3. Remove the spring, the piston and the valve from the body. 4. Remove the valve, the retainer and the spring from the stem. 5. Rotate the piston and fully depress the inlet valve stem. This will loosen the piston plug with its o-ring from the piston center. 6. Remove the piston o-ring. air strainer (optional) Figure 6 - Installation of the Optional Air Strainer on the Accessory Reservoir

8 2011JA14 8 / Supply valves These optional valves for compressed air lines are used primarily to keep the pneumatic suspension system inflated during long periods when the vehicle is not operating. The valve installed at the supply may be used to check the air pressure within this. A tire gauge calibrated to 150 psi (1034 kpa) may be used. When an external compressed air supply is required, make sure that the supply source is clean before connecting it to the vehicle s pneumatic system. General system maintenance Test methods for adjusting and maintaining brake system components are described under individual categories within this section. The entire pneumatic system should be checked for leaks on a regular basis. With the engine stopped and the brakes released, check the air pressure falling rate on the air pressure gauge located in the instrument panel. This rate should not exceed 5 psi (35 kpa) for a three-minute period. Perform the same test with the motor stopped, but with the brakes firmly on. The rate of the pressure drop should not exceed 5 psi (35 kpa) for a three-minute period. If the leak is excessive, leak tests should be carried out on air brake couplings and on each air brake control unit. PREVENTIVE MAINTENANCE See Table 2. The actual operational activities of the buses covered by this maintenance manual vary widely. Under these circumstances, it is impossible to establish maintenance intervals, whether time or mileage. Therefore, the intervals given in the preventive maintenance table must be used in relation to the operational conditions to which a particular bus is subjected. The given intervals are the manufacturer s recommendations and must be considered as maximum periods. It is preferable to maintain the vehicles using shorter intervals than shown, rather than longer intervals. Section : braking system can provide information on the maintenance of the components of the air braking system. +CAUTION: This table is not an exhaustive list of all maintenance required; it is preferable to conduct more frequent inspections. Each time an assembly is removed and disassembled for maintenance, it is recommended to replace all grommets, seals, O-rings, etc., and any other worn or damaged part.

9 PREVENTIVE MAINTENANCE TABLE / 9 COMPONENTS INTERVAL( 1 ) ) INTERVAL(1) 2011JA14 Transducers Safety valve a. 300 hours - 12,000 km (8,000 mi) a. Check electrical connections. b. 3,600 hours - 160,000 km (100,000 mi) b. Remove, clean, inspect. 6 months - 80,000 km (50,000 mi) Remove, disassemble, clean, inspect. Compressed air line 8,000 km (5,000 mi) Check for leaks; tighten as needed. Purge valve 1,800 hours - 80,000 km (50,000 mi) - 6 months Remove, disassemble, clean, inspect. Pressure-maintaining valve 3,600 hours - 160,000 km (100,000 mi) - 1 yr Remove, clean, inspect. Inversing valve 3,600 hours - 160,000 km (100,000 mi) - 1 yr Remove, clean, inspect. Interlock Valve 3,600 hours - 160,000 km (100,000 mi) - 1 yr Remove, clean, inspect. Air compressor See Note 2. Governor Clean carbon deposits from valves and discharge lines. Check fastening bolts and tighten as needed. Check lines for leaks. a. 500 hours - 24,000 km (15,000 mi) a. Clean or replace the filters. b. 3,000 hours - 160,000 km (100,000 mi) - 1 yr b. Remove, disassemble, clean, inspect, adjust. (1) When two or more intervals are mentioned, the operation must be performed at the first interval. (2) Depending on how severe the operating conditions. Table 2 - Preventive Maintenance

10 2011JA14 10 / TROUBLESHOOTING GUIDE PROBABLE CAUSE SLOW PRESSURE ACCUMULATION IN TANKS 1. Dirty air filter. 2. Air leak. 3. Faulty compressor. 4. Open or leaking drain tank valves. 5. Faulty compressor governor. CORRECTIVE ACTION 1. Clean or replace. 2. Find and repair. 3. Repair (refer to the manufacturer s manual). 4. Shut off, repair or replace. 5. Repair or replace. ABOVE NORMAL AIR PRESSURE 1. Faulty gauge. 2. Out-of-adjustment or faulty governor. 3. Obstructed line between governor and compressor. 1. Replace. 2. Adjust, repair or replace. 3. Remove obstruction or replace line. QUICK LOSS OF PRESSURE AFTER ENGINE SHUTDOWN (BRAKES UNAPPLIED) 1. Leaking lines or connection fittings. 2. Compressor discharge valve or one-way pressure-retaining valve worn or leaking. 3. Leaking governor. 4. Leaking brake-applying valve. 5. Open or leaking drain tank valve. 6. Faulty parking brake control valve. 1. Repair or replace. 2. Repair or replace. 3. Repair or replace. 4. Repair or replace. 5. Shut off, repair or replace. 6. Repair or replace.. QUICK LOSS OF PRESSURE AFTER ENGINE SHUTDOWN (BRAKES FULLY APPLIED) 1. Leaking brake chamber. 2. Leaking braking valve. 3. Faulty brake line. 4. Leaking brake chamber hoses. 5. Faulty quick-release valve. 6. Faulty normal duty braking relay valve. 7. Faulty parking brake control valve. 1. Replace. 2. Repair or replace. 3. Repair or replace. 4. Repair or replace. 5. Clean or replace membrane. 6. Repair or replace. 7. Repair or replace. AIR BLEEDING OUT FROM SAFETY VALVE 1. Out-of-adjustment safety valve. 2. Out-of-adjustment governor. 1. Adjust. 2. Adjust. Table 3 - Troubleshooting Guide

11 / 11 SECTION A (haldex single) 2011JA14 GENERAL DESCRIPTION See Figure 1A for a schematic diagram of the air-drying system for the Nova LFS vehicle equipped with a Haldex single air dryer. See the Nova LFS parts manual for a detailed schematic of the. The for a Nova LFS vehicle, equipped with a Haldex single air dryer, is comprised of: An air compressor, installed on the engine, that compresses the air and supplies the pneumatic system; An integrated or external air dryer governor that controls the air pressure in the system; A ping tank (optional) that absorbs the shock waves of air compression by the compressor, thus reducing the noise produced by this shock; Copper coils that cool the compressed air; A condenser with a purge valve that removes oil and other contaminants from the air before they can enter the air dryer; An air dryer with a purge tank that removes any remaining contaminants from the compressed air; A supply that stores the compressed air; A primary, a secondary, an accessory and an emergency that serve the different pneumatic systems; An external air supply connector and a tow connector (an additional air supply connector may be installed). OPERATION The compressor compresses the air and supplies the pneumatic system. The governor integrated in the air dryer automatically controls the air pressure in the system and commands the compressor by activating or deactivating the compressor discharge mechanism whenever the minimum or maximum pressure of the supply is reached. The ping tank (optional), located between the compressor and the cooling coils, absorbs the shock produced by the alternating compression cycle of the compressor and reduces the noise associated with this shock. The air then passes through the cooling coils. These cooling coils lower the temperature of the compressed air, in order to start the condensation of the humidity vaporized in the air by the compressor. The air from the compressor or an external source is then treated by the condenser to extract most of the impurities in the air. The compressed air is then treated by the air dryer that removes the humidity. Whenever the maximum pressure of the supply circuit is reached, the contaminants in the dryer are purged and the humidity remaining is expelled by the dry air from the purge tank that recirculates in the dryer. See section : air dryer and condenser in this manual for additional information on the airdrying system. Once dry and devoid of contaminants, compressed air is sent to the supply, which acts as an air reserve for the other components of the pneumatic system. The contaminants accumulated in the supply can be purged by a manual purge valve installed at one end of the, or electronically by an optional automatic purge valve. The automatic valve purges the contaminants approximately every five minutes. A 50 W element maintains the temperature of the valve between 45 ºF and 105 ºF (7 ºC and 41 ºC) in order to prevent freezing of the water during the winter season. Compressed air is then sent in a prioritized sequence to the primary, the secondary and to the emergency. Before reaching the accessory, the air passes through a sequence valve, which delays the movement of air to the accessory in order to prioritize the pressurizing of the s for the braking system. Once the pressure in the system reaches 448 kpa (65 psi), the sequence valve opens and allows the accessory to be filled. An anti-return valve, also installed at the entrance to the accessory, prevents the depressurization of the in case of a major leak in the supply system. A safety valve expels any overproduction of compressed air in case of a breakdown of the air flow control within the system. This valve expels the compressed air once the pressure is above that required for normal operation of the system. If the pressure falls below this value, the safety valve closes, in order for the system to continue to be fed with compressed air. Finally, an optional towing connector is installed to supply the brakes and other pneumatic accessories during a towing operation.

12 2011JA14 12 / Réservoir de purge auto Purge optional Condenser air dryer supply primary coils ping tank (optional) secondary Compressor governor external or integrated emergency accessory check valve air supply connector automatic purge valve manual purge valve safety valve sequence valve COMPRESSED AIR (PRESSURE): 110 to 135 psi (758 to 931 kpa) Air is: a. compressed by the compressor, whenever it receives a signal from the governor b. cooled as it passes through the copper coils c. expelled with most of the water and impurities in the condenser d. filtered and dried by the air dryers e. accumulated in the supply, feeding in turn the primary, the secondary, the emergency, and the accessory. Figure 1A - Schematic Diagram of the Pneumatic Supply System with Haldex Single Air Dryer

13 / 13 SECTION B (haldex double) 2011JA14 GENERAL DESCRIPTION See Figure 1B for a schematic diagram of the air-drying system for the Nova LFS vehicle equipped with a Haldex double air dryer. See the Nova LFS parts manual for a detailed schematic of the. The for a Nova LFS vehicle, equipped with a Haldex double air dryer, is comprised of: An air compressor, installed on the engine, that compresses the air and supplies the pneumatic system; An external air dryer governor that controls the air pressure in the system; A ping tank that absorbs the shock waves of air compression by the compressor, thus reducing the noise produced by this shock; Copper coils that cool the compressed air; A condenser with a purge valve that removes oil and other contaminants from the air before they can enter the air dryer; A wet tank with automatic purge valve, where the air is recondensed; Two air dryers mounted in tandem and two purge tanks that remove any remaining contaminants from the compressed air; A supply that stores the compressed air; A primary, a secondary, an accessory and an emergency that serve the different pneumatic systems; Two external air supply connectors and a tow connector. OPERATION The compressor compresses the air and supplies the pneumatic system. The governor integrated in the air dryer automatically controls the air pressure in the system and commands the compressor by activating or deactivating the compressor discharge mechanism whenever the minimum or maximum pressure of the supply is reached. The ping tank, located between the compressor and the cooling coils, absorbs the shock produced by the alternating compression cycle of the compressor and reduces the noise associated with this shock. The air then passes through the cooling coils. These cooling coils lower the temperature of the compressed air, in order to start the condensation of the humidity vaporized in the air by the compressor. The air from the compressor or an external source is then treated by the condenser to extract most of the impurities in the air. The air is then stored and recondensed in the wet tank before passing to the air dryer. The compressed air is then treated by the one of the air dryers, which removes the humidity. Whenever the maximum pressure of the supply circuit is reached, the contaminants in the dryer are purged and the humidity remaining is expelled by the dry air from the purge tank that recirculates in the dryer. See section : air dryers and condenser in this manual for additional information on the air-drying system. Once dry and devoid of contaminants, compressed air is sent to the supply, which acts as an air reserve for the other components of the pneumatic system. The contaminants accumulated in the supply can be purged by a manual purge valve installed at one end of the, or electronically by an optional automatic purge valve. The automatic valve purges the contaminants approximately every five minutes. A 50 W element maintains the temperature of the valve between 45 ºF and 105 ºF (7 ºC and 41 ºC) in order to prevent freezing of the water during the winter season. Compressed air is then sent in a prioritized sequence to the primary, the secondary and to the emergency. Before reaching the accessory, the air passes through a sequence valve, which delays the movement of air to the accessory in order to prioritize the pressurizing of the s for the braking system. Once the pressure in the system reaches 448 kpa (65 psi), the sequence valve opens and allows the accessory to be filled. An anti-return valve, also installed at the entrance to the accessory, prevents the depressurization of the in case of a major leak in the supply system. A safety valve expels any overproduction of compressed air in case of a breakdown of the air flow control within the system. This valve expels the compressed air once the pressure is above that required for normal operation of the system. If the pressure falls below this value, the safety valve closes, in order for the system to continue to be fed with compressed air. Finally, a tow connector is installed to supply the brakes and other pneumatic accessories during a towing operation.

14 2011JA14 14 / purge tank air dryer Condenser wet tank supply air dryer primary coils ping tank purge tank secondary Compressor external governor emergency accessory COMPRESSED AIR (PRESSURE): 110 to 135 psi (758 to 931 kpa) auto purge optional check valve air supply connector automatic purge valve manual purge valve safety valve sequence valve Air is: a. compressed by the compressor, whenever it receives a signal from the governor b. cooled as it passes through the copper coils c. expelled with most of the water and impurities in the condenser d. recondensed in the wet tank e. filtered and dried by the air dryer (the purge tank eliminates humidity from the air dryer) f. accumulated in the supply, feeding in turn the primary, the secondary, the emergency, and the accessory. Figure 1B - Schematic Diagram of the Pneumatic Supply System with Haldex Double Air Dryer

15 SECTION C (bendix) / JA14 GENERAL DESCRIPTION See Figure 1C for a schematic diagram of the air-drying system for the Nova LFS vehicle equipped with a Bendix air dryer. See the Nova LFS parts manual for a detailed schematic of the. The for a Nova LFS vehicle, equipped with a Bendix air dryer, is comprised of: An air compressor, installed on the engine, that compresses the air and supplies the pneumatic system; An external air dryer governor that controls the air pressure in the system; A ping tank that absorbs the shock waves of air compression by the compressor, thus reducing the noise produced by this shock; Copper coils that cool the compressed air; An air dryer that removes any remaining contaminants from the compressed air An oil separator that removes the remaining contaminants; A supply that stores the compressed air; A primary, a secondary, an accessory and an emergency that serve the different pneumatic systems; Two external air supply connectors and a tow connector. OPERATION The compressor compresses the air and supplies the pneumatic system. The governor integrated in the air dryer automatically controls the air pressure in the system and commands the compressor by activating or deactivating the compressor discharge mechanism whenever the minimum or maximum pressure of the supply is reached. The ping tank, located between the compressor and the cooling coils, absorbs the shock produced by the alternating compression cycle of the compressor and reduces the noise associated with this shock. The air then passes through the cooling coils. These cooling coils lower the temperature of the compressed air, in order to start the condensation of the humidity vaporized in the air by the compressor. The compressed air is then treated by the air dryer that removes the humidity. Whenever the maximum pressure of the supply circuit is reached, the contaminants in the dryer are purged. See section : air dryer and condenser in this manual for additional information on the airdrying system. When equipped, the air passes through an oil separator to extract the remaining dirt and oil particles before it enters the supply s. Once dry and devoid of contaminants, compressed air is sent to the supply, which acts as an air reserve for the other components of the pneumatic system. The contaminants accumulated in the supply can be purged by a manual purge valve installed at one end of the, or electronically by an optional automatic purge valve. The automatic valve purges the contaminants approximately every five minutes. A 50 W element maintains the temperature of the valve between 45 ºF and 105 ºF (7 ºC and 41 ºC) in order to prevent freezing of the water during the winter season. Compressed air is then sent in a prioritized sequence to the primary, the secondary and to the emergency. Before reaching the accessory, the air passes through a sequence valve, which delays the movement of air to the accessory in order to prioritize the pressurizing of the s for the braking system. Once the pressure in the system reaches 448 kpa (65 psi), the sequence valve opens and allows the accessory to be filled. An anti-return valve, also installed at the entrance to the accessory, prevents the depressurization of the in case of a major leak in the supply system. A safety valve expels any overproduction of compressed air in case of a breakdown of the air flow control within the system. This valve expels the compressed air once the pressure is above that required for normal operation of the system. If the pressure falls below this value, the safety valve closes, in order for the system to continue to be fed with compressed air. Finally, a tow connector is installed to supply the brakes and other pneumatic accessories during a towing operation.

16 2011JA14 16 / external governor air dryer oil separator (optional) supply primary coils secondary Compressor emergency accessory check valve air supply connector automatic purge valve manual purge valve safety valve sequence valve COMPRESSED AIR (PRESSURE): 110 to 135 psi (758 to 931 kpa) Air is: a. compressed by the compressor, whenever it receives a signal from the governor b. cooled as it passes through the copper coils c. expelled with the remaining contaminants in the oil separator d. filtered and dried by the air dryer e. accumulated in the supply, feeding in turn the primary, the secondary, the emergency, and the accessory. Figure 1C - Schematic Diagram of the Pneumatic Supply System with Bendix Dryer

17 / 17 SECTION D (sludgebraker) 2011JA14 GENERAL DESCRIPTION See Figure 1D for a schematic diagram of the air-drying system for the Nova LFS vehicle equipped with a SludgeBraker air dryer. See the Nova LFS parts manual for a detailed schematic of the. The for a Nova LFS vehicle, equipped with a SludgeBraker air dryer, is comprised of: An air compressor, installed on the engine, that compresses the air and supplies the pneumatic system; An external air dryer governor that controls the air pressure in the system; A ping tank that absorbs the shock waves of air compression by the compressor, thus reducing the noise produced by this shock; An air dryer that removes any remaining contaminants from the compressed air A supply that stores the compressed air; A primary, a secondary, an accessory and an emergency that serve the different pneumatic systems; Two external air supply connectors and a tow connector. OPERATION The compressor compresses the air and supplies the pneumatic system. The governor integrated in the air dryer automatically controls the air pressure in the system and commands the compressor by activating or deactivating the compressor discharge mechanism whenever the minimum or maximum pressure of the supply is reached. The ping tank, located between the compressor and the cooling coils, absorbs the shock produced by the alternating compression cycle of the compressor and reduces the noise associated with this shock. The compressed air is then treated by the air dryer that removes the humidity. Whenever the maximum pressure of the supply circuit is reached, the contaminants in the dryer are purged. Once dry and devoid of contaminants, compressed air is sent to the supply, which acts as an air reserve for the other components of the pneumatic system. The contaminants accumulated in the supply can be purged by a manual purge valve installed at one end of the, or electronically by an optional automatic purge valve. The automatic valve purges the contaminants approximately every five minutes. A 50 W element maintains the temperature of the valve between 45 ºF and 105 ºF (7 ºC and 41 ºC) in order to prevent freezing of the water during the winter season. Compressed air is then sent in a prioritized sequence to the primary, the secondary and to the emergency. Before reaching the accessory, the air passes through a sequence valve, which delays the movement of air to the accessory in order to prioritize the pressurizing of the s for the braking system. Once the pressure in the system reaches 448 kpa (65 psi), the sequence valve opens and allows the accessory to be filled. An anti-return valve, also installed at the entrance to the accessory, prevents the depressurization of the in case of a major leak in the supply system. A safety valve expels any overproduction of compressed air in case of a breakdown of the air flow control within the system. This valve expels the compressed air once the pressure is above that required for normal operation of the system. If the pressure falls below this value, the safety valve closes, in order for the system to continue to be fed with compressed air. Finally, a tow connector is installed to supply the brakes and other pneumatic accessories during a towing operation. See section : air dryer in this manual for additional information on the air-drying system.

18 2011JA14 18 / air dryer supply primary secondary ping tank Compressor external governor emergency accessory check valve air supply connector automatic purge valve manual purge valve safety valve COMPRESSED AIR (PRESSURE): 110 to 135 psi (758 to 931 kpa) Air is: a. compressed by the compressor, whenever it receives a signal from the governor b. filtered and dried by the air dryer c. accumulated in the supply, feeding in turn the primary, the secondary, the emergency, and the accessory. sequence valve Figure 1D - Schematic Diagram of the Pneumatic Supply System with SludgeBraker Dryer

19 SECTION E (SKF) / JA14 GENERAL DESCRIPTION See Figure 1E for a schematic diagram of the air-drying system for the Nova LFS vehicle equipped with an SKF or SKF air dryer. See the Nova LFS parts manual for a detailed schematic of the. The for a Nova LFS vehicle, equipped with an SKF air dryer, is comprised of: An air compressor, installed on the engine, that compresses the air and supplies the pneumatic system; An external air dryer governor that controls the air pressure in the system; A ping tank that absorbs the shock waves of air compression by the compressor, thus reducing the noise produced by this shock; Copper coils that cool the compressed air; A condenser that removes oil and other contaminants from the air before they can enter the air dryer; An air dryer that removes any remaining contaminants from the compressed air A supply that stores the compressed air; A primary, a secondary, an accessory and an emergency that serve the different pneumatic systems; Two external air supply connectors and a tow connector. OPERATION The compressor compresses the air and supplies the pneumatic system. The governor integrated in the air dryer automatically controls the air pressure in the system and commands the compressor by activating or deactivating the compressor discharge mechanism whenever the minimum or maximum pressure of the supply is reached. The ping tank, located between the compressor and the cooling coils, absorbs the shock produced by the alternating compression cycle of the compressor and reduces the noise associated with this shock. The air then passes through the cooling coils. These cooling coils lower the temperature of the compressed air, in order to start the condensation of the humidity vaporized in the air by the compressor. The air from the compressor or an external source is then treated by the condenser to extract most of the impurities in the air. The compressed air is then treated by the air dryer that removes the humidity. Whenever the maximum pressure of the supply circuit is reached, the contaminants in the dryer are purged. See section : air dryer and condenser in this manual for additional information on the airdrying system. Once dry and devoid of contaminants, compressed air is sent to the supply, which acts as an air reserve for the other components of the pneumatic system. The contaminants accumulated in the supply can be purged by a manual purge valve installed at one end of the, or electronically by an optional automatic purge valve. The automatic valve purges the contaminants approximately every five minutes. A 50 W element maintains the temperature of the valve between 45 ºF and 105 ºF (7 ºC and 41 ºC) in order to prevent freezing of the water during the winter season. Compressed air is then sent in a prioritized sequence to the primary, the secondary and to the emergency. Before reaching the accessory, the air passes through a sequence valve, which delays the movement of air to the accessory in order to prioritize the pressurizing of the s for the braking system. Once the pressure in the system reaches 448 kpa (65 psi), the sequence valve opens and allows the accessory to be filled. An anti-return valve, also installed at the entrance to the accessory, prevents the depressurization of the in case of a major leak in the supply system. A safety valve expels any overproduction of compressed air in case of a breakdown of the air flow control within the system. This valve expels the compressed air once the pressure is above that required for normal operation of the system. If the pressure falls below this value, the safety valve closes, in order for the system to continue to be fed with compressed air. Finally, a tow connector is installed to supply the brakes and other pneumatic accessories during a towing operation.

20 2011JA14 20 / air dryer supply primary coils secondary ping tank Compressor external governor emergency accessory check valve air supply connector COMPRESSED AIR (PRESSURE): 110 to 135 psi (758 to 931 kpa) automatic purge valve manual purge valve safety valve sequence valve Air is: a. compressed by the compressor, whenever it receives a signal from the governor b. cooled as it passes through the copper coils c. filtered and dried by the air dryer d. accumulated in the supply, feeding in turn the primary, the secondary, the emergency, and the accessory. Figure 1E - Schematic Diagram of the Pneumatic Supply System with SKF Dryer

ModulAir Air Dryer with External Purge Tank - Changeover from Bendix AD-IS for Peterbilt Installation. Air Dryer Mounting Bracket (Item 1)

ModulAir Air Dryer with External Purge Tank - Changeover from Bendix AD-IS for Peterbilt Installation. Air Dryer Mounting Bracket (Item 1) Instruction Guide L31259 11/10 ModulAir Air Dryer with External Purge Tank - Changeover from Bendix AD-IS for Peterbilt Installation Air Dryer Mounting Bracket (Item 1) Tank Mounting Bracket (Item 19)

More information

PURest Air Dryer Installation and Maintenance

PURest Air Dryer Installation and Maintenance PURest Air Dryer Installation and Maintenance L31170 Rev. 4/04 The Haldex PURest is a desiccant type dryer that effectively removes moisture, oil and contaminants from the compressed air system. This reduces

More information

SuperKlean Washdown Products

SuperKlean Washdown Products February 2012 DURAMIX 8000 INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** WARNING HIGH PRESSURE AND HOT

More information

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC. Fig. 2: Blower & Evaporator Unit Specifications 2004 HVAC SYSTEMS Manual HVAC System - Sorento GENERAL SPECIFICATIONS AIR CONDITIONER Fig. 1: Air Conditioner Specifications BLOWER AND EVAPORATOR UNIT HEATER

More information

SD Bendix Dryer Reservoir Module with AD-IS Air Dryer DESCRIPTION

SD Bendix Dryer Reservoir Module with AD-IS Air Dryer DESCRIPTION SD-98-9808 Bendix Dryer Reservoir Module with AD-IS Air Dryer INTEGRATED MOUNTING BOLTS (3) DESICCANT CARTRIDGE AUXILIARY DELIVERY PORTS (5) SECONDARY GOVERNOR AD-IS AIR DRYER PART NUMBER STAMPED HERE

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

HEATING AND VENTILATION

HEATING AND VENTILATION SECTION 14-102.04 14-102.04/ 1 2007OC19 DESCRIPTION The heating, ventilation and air conditioning (HVAC) system is designed to optimize passenger comfort. The system regulates interior vehicle atmosphere,

More information

SD Bendix AD-1 and AD-2 Air Dryers

SD Bendix AD-1 and AD-2 Air Dryers SD-08-2403 Bendix AD-1 and AD-2 Air Dryers AD-1 AIR DRYER AD-2 AIR DRYER FIGURE 1 The air dryer collects and removes moisture and contaminants before the air reaches the first reservoir. It is distinctly

More information

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314)

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314) DRY AIR SYSTEMS, INC. 2655 Metro Boulevard Maryland Heights, Missouri 63043 (314) 344-1114 fax (314) 344-0677 HD SERIES DRIERS TABLE OF CONTENTS WHY AN AIR DRYER 3 WHAT IS A DESICCANT AIR DRYER 3 Desiccant

More information

WHEELED STORED PRESSURE

WHEELED STORED PRESSURE OWNERS SERVICE MANUAL NO. 19795 INSTALLATION, OPERATING & SERVICING INSTRUCTIONS All fire extinguishers should be installed, inspected and maintained in accordance with the National Fire Protection Association

More information

SD Bendix AD-IS and AD-IS PuraGuard (Oil Coalescing) Air Dryer and Reservoir Systems

SD Bendix AD-IS and AD-IS PuraGuard (Oil Coalescing) Air Dryer and Reservoir Systems Bendix AD-IS and AD-IS PuraGuard (Oil Coalescing) Air Dryer and Reservoir Systems SD-08-2418 RES GOVERNOR (2) VALVE PRESSURE PROTECTION VALVES (4) DESICCANT CARTRIDGE (STANDARD SHOWN) DESICCANT CARTRIDGE

More information

Bulletin No.: PRO Effective Date: 7/15/94 Cancels: PRO dated 5/1/92 Page: 1 of 6

Bulletin No.: PRO Effective Date: 7/15/94 Cancels: PRO dated 5/1/92 Page: 1 of 6 Technical Bulletin Bulletin No.: PRO-08-19 Effective Date: 7/15/94 Cancels: PRO-08-19 dated 5/1/92 Page: 1 of 6 Subject: The Holset Type E & QE Compressor Air Supply System with Bendix Air Dryer & Holset

More information

Module 7: Air Supply System

Module 7: Air Supply System Terms and Definitions Components of the Air Supply System Basic Functions of the Air Supply System Parts of a Compressor Characteristics of Compressors Loading and Unloading Process Characteristics of

More information

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE FOAM FIRE EXTINGUISHERS MODEL 254-6 LITER AFFF FOAM WITH SPRAY NOZZLE Model 250 2 ½ GAL.LON AFFF FOAM WITH ASPIRATED NOZZLE MODEL 252 2 ½ GAL.LON FFFP (ALCOHOL RESISTANT) FOAM WITH ASPIRATED NOZZLE OWNER'S

More information

Instruction Manual - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity

Instruction Manual - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity 100 PPD (2 kg/h) Chlorine or Sulfur Dioxide 250 & 500 PPD (5 & 10 kg/h) Chlorine or Sulfur Dioxide Anti-Siphon Ejector

More information

System Saver HP Air Dryer

System Saver HP Air Dryer Maintenance Manual MM-1736 System Saver HP Air Dryer Revised 12-17 Service Notes About This Manual This manual provides service and repair procedures for Meritor WABCO s System Saver HP air dryer. Before

More information

Heating and ventilation system,

Heating and ventilation system, Page 1 of 24 87-151 Heating and ventilation system, servicing Instrument panel air outlets and air guide ducts CAUTION! Before working on the electrical system: Obtain security code for anti-theft radio.

More information

BMW E36 Thermostat Removal And Coolant Flush

BMW E36 Thermostat Removal And Coolant Flush BMW E36 Thermostat Removal And Coolant Flush Disclaimer: The cooling system is critical to the proper operation of your car. Failure to properly install all of the components of the cooling system could

More information

SD Bendix AD-IS EverFlow Assembly BENDIX AD-IS EVERFLOW ASSEMBLY

SD Bendix AD-IS EverFlow Assembly BENDIX AD-IS EVERFLOW ASSEMBLY SD-08-2417 Bendix AD-IS EverFlow Assembly EVERFLOW MODULE BENDIX EVERFLOW ELECTRONIC MODULE RES (2) BENDIX AD-IS EVERFLOW ASSEMBLY BENDIX AD-IS AIR DRYER PURAGUARD MEDALLION VALVE PRESSURE PROTECTION VALVES

More information

HT650 TM FAN DRIVE SERVICE INSTRUCTIONS

HT650 TM FAN DRIVE SERVICE INSTRUCTIONS HT650 TM FAN DRIVE SERVICE INSTRUCTIONS When unpacking your product, remove all components and inspect them to ensure that no damage occurred during shipping. If any components are missing or damaged,

More information

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING Series 47 and 247 Mechanical Water Feeders McDonnell & Miller Installation & Maintenance Instructions MM-316(C) Series 47-2 and 247-2 Combination Mechanical Water Feeder/Low Water Cut-Off Series 47 Water

More information

NO LONGER IN PRODUCTION

NO LONGER IN PRODUCTION M7-00 thru -00 Service and Parts Manual Self-Contained Steam Sterilizer Serial Number Prefixes: RB, CR, CP, CS, FM, FN -00 M7 thru -00 NO LONGER IN PRODUCTION Some service parts may not be available for

More information

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL NO. 05602 FOR AMEREX STORED PRESSURE, HAND PORTABLE DRY CHEMICAL FIRE EXTINGUISHERS. ABC (Ammonium Phosphate Base)

More information

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER OPERATING MANUAL MODEL AIR 500TM AIR DRYER Puregas, LLC 226-A Commerce St. Tel: 800-52-535 Broomfield, Colorado Fax: 303-657-2205 P/N P0255 REV A, 02/9/4 TABLE OF CONTENTS.0 GENERAL... 3 2.0 SPECIFICATIONS...

More information

Audi-Larm Audible Alarm

Audi-Larm Audible Alarm Audi-Larm Audible Alarm MAINTENANCE AND REPAIR TAL 1706 (L) Rev. 7 MSA 2017 Prnt. Spec. 10000005389(I) Mat. 10093084 Doc. 10093084 REPLACEMENT KITS AND PARTS LIST TAL 1706 (L) Rev. 7-10093084 2 Exploded

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BUILT-IN BOTTOM MOUNT REFRIGERATOR/FREEZER DBRTGK72SS-GRILLE KIT (FOR designer SERIES ONLY) VIKING RANGE CORPORATION 111 Front Street Greenwood, Mississippi (MS) 38930 USA (662)

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

Section 4-3. Service - Air Dryer

Section 4-3. Service - Air Dryer Section 4-3 Service - Air Dryer UPPER UPPER OUTER SHELL OUTER SHELL LOWER LOWER END COVER END COVER CONTROL CONTROL SUPPLY SUPPLY DELIVERY WIRING HARNESS CONNECTION DELIVERY WIRING HARNESS CONNECTION EXTENDED

More information

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL H-Series & 203 THRU 223 SERIES ARROW PNEUMATICS, INC. REGENERATIVE DRYER DIVISION 2111 WEST 21ST STREET BROADVIEW, IL 60155 708-343-9595 708-343-1907

More information

System Saver TWIN Air Dryer. Maintenance Manual 35 Revised 11-02

System Saver TWIN Air Dryer. Maintenance Manual 35 Revised 11-02 System Saver TWIN Air Dryer Maintenance Manual 35 Revised 11-02 Service Notes This publication provides maintenance and service procedures for Meritor WABCO s System Saver TWIN air dryers. The information

More information

M O D E L G W T OPERATIONS MANUAL TABLE OF CONTENTS

M O D E L G W T OPERATIONS MANUAL TABLE OF CONTENTS M O D E L G W T - 202 OPERATIONS MANUAL TABLE OF CONTENTS INTRODUCTION... 1 SECTION 1 1.0 SAFETY... 1-1 1.1 EMERGENCY... 1-1 1.2 Know your machine... 1-1 1.3 Power Supply... 1-1 1.4 Keep guards in place....

More information

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3.

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3. 4.4 SUPPLY PUMPAK ASSEMBLY NOTE: This section applies only to systems, which include a supply pumpak. Only the H6, XA, and XC series systems contain a supply pumpak. If your system is a single zone, H6

More information

Tornado Operations & Maintenance Manual

Tornado Operations & Maintenance Manual TORNADO INDUSTRIES 7401 W. LAWRENCE AVENUE CHICAGO, IL 60706 (708) 867-5100 FAX (708) 867-6968 www.tornadovac.com Tornado Operations & Maintenance Manual MODEL NO. 99690 BD 22/14, 99720 BD 26/14 L9722

More information

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual 008094 All fire extinguishers should be installed, inspected and maintained in accordance with

More information

Installation & Operating Guide

Installation & Operating Guide 5-036 HOT WATER TANK Installation & Operating Guide Read all instructions thoroughly. Keep this guide for future reference. Proof of purchase is required for Warranty. Staple receipt or proof of purchase

More information

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1 A AD Oil burners fuel unit deltapumps.com DE116-0709 A-AD_en_0709.pdf - 16.11.09 Page 1/1 Oil burners fuel unit Type A, AD 1- Applications The DELTA aluminium fuel unit type A is an efficient and modern

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION Series 61 Low Water Cut-Off Typical Applications: - Primary or secondary low water cut-off for hot water and steam boilers. - Low water cut-off - High water cut-off - Alarm actuator OPERATION Maximum Boiler

More information

TK-1001, 1101, 1201, 1301, 1601

TK-1001, 1101, 1201, 1301, 1601 TK-1001, 1101, 1201, 1301, 1601 Pneumatic Room Thermostats General Instructions DEVICE INFORMATION Identification Thermostats of this family may be easily identified by referring to the part number located

More information

DRYAIRE DESICCANT SYSTEM MODEL 6760

DRYAIRE DESICCANT SYSTEM MODEL 6760 MODEL 6760 THE SPRAY GUN PEOPLE FOR PRODUCT INFORMATION CALL: 1-800-742-7731 System Description Sharpe s DRYAIRE Desiccant Air Drying System is the painter s insurance for removing dirt, water, oil, and

More information

20 TON AIR/MANUAL SHOP PRESS

20 TON AIR/MANUAL SHOP PRESS 20 TON AIR/MANUAL SHOP PRESS Instruction Manual 1 Please read this instruction manual carefully before use. IMPORTANT PLEASE READ THESE INSTRUCTIONS CAREFULLY. NOTE THE SAFETY INSTRUCTIONS N WARNINGS.

More information

1 Specifications. 2 Operation. PHOENIX 300 Operation & Service Instructions. 2.1 Transporting the Phoenix. 2.2 Location

1 Specifications. 2 Operation. PHOENIX 300 Operation & Service Instructions. 2.1 Transporting the Phoenix. 2.2 Location Therma-Stor Products A Division of DEC International Box 8050 Madison, WI 53708 Toll Free 1-800-533-7533 Local 1-608-222-5301 PHOENIX 300 Operation & Service Instructions Table of Contents 1. Specifications...

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-200 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA B140.02003

More information

Fan Drive Maintenance Training Manual

Fan Drive Maintenance Training Manual Fan Drive Maintenance Training Manual TABLE OF CONTENTS INTRODUCTION... 2 General Information... 2 LESSON 1: FAN DRIVE SYSTEM... 3 1. Operation... 3 2. Control System... 4 LESSON 2: CONTROL COMPONENTS...

More information

Brakemaster air dryers. The complete fleet guide to operation, trouble-shooting, and service procedures

Brakemaster air dryers. The complete fleet guide to operation, trouble-shooting, and service procedures Brakemaster air dryers The complete fleet guide to operation, trouble-shooting, and service procedures The problem is moisture and contamination. The solution is SKF Brakemaster air dryers. With the ongoing

More information

HEATING AND AIR CONDITIONING

HEATING AND AIR CONDITIONING WJ HEATING AND AIR CONDITIONING 24-1 HEATING AND AIR CONDITIONING TABLE OF CONTENTS page SERVICE PROCEDURES REFRIGERANT OIL LEVEL...1 REFRIGERANT RECOVERY....1 REFRIGERANT SYSTEM CHARGE...1 REFRIGERANT

More information

INSTRUCTION AND REPAIR MANUAL

INSTRUCTION AND REPAIR MANUAL SECTION 6 ITEM 390 DATED JANUARY 2003 SUPERSEDES SECTION 6 ITEM 390 DATED OCTOBER 2000 INSTRUCTION AND REPAIR MANUAL SERIES 390 6 The 390 Series is a superior commercial Multi-Stage Vertical In-Line Centrifugal

More information

02 COOLING SYSTEM 02 COOLING SYSTEM COOLING SYSTEM INDEX. 1. General Specifications... 65

02 COOLING SYSTEM 02 COOLING SYSTEM COOLING SYSTEM INDEX. 1. General Specifications... 65 REV. 02 / 01.11.13 COOLING SYSTEM INDE 1. General... 64 2. Specifications... 65 3. Structure and Operation... 65 3.1. Cooling System... 65 3.2. Radiator... 65 3.3. Water Pump... 65 3.4. Thermostat... 65

More information

PRO 2000i LOW LEVEL DEPOSITOR

PRO 2000i LOW LEVEL DEPOSITOR DEPOSITORS AND AUTOMATED CAKE PRODUCTION SYSTEMS PRO 2000i LOW LEVEL DEPOSITOR OPERATION AND SPARE PARTS MANUAL Serial No. PR2L- (Please quote this number when ordering spares, and making service calls)

More information

GETZ EQUIPMENT INNOVATORS PART NO.: 9G58619 MODEL: SV1 150 PR VACUFILL SYSTEM (Revised 2/25/14)

GETZ EQUIPMENT INNOVATORS PART NO.: 9G58619 MODEL: SV1 150 PR VACUFILL SYSTEM (Revised 2/25/14) GETZ EQUIPMENT INNOVATORS PART NO.: 9G58619 MODEL: SV1 150 PR VACUFILL SYSTEM (Revised 2/25/14) !!WARNING!! SEVERE DAMAGE AND/OR INJURY MAY RESULT DO NOT DISCHARGE ANY EXTINGUISHER CYLINDER EXCEEDING 195

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

Venco 75mm (3 ) Standard and De-airing Pugmill

Venco 75mm (3 ) Standard and De-airing Pugmill Owner s manual for Venco 75mm (3 ) Standard and De-airing Pugmill Venco Products 29 Owen Road Kelmscott, Western Australia 6111 ph +61 8 9399-5265 fax +61 8 9 497 1335 email: venwest@iinet.net.au www.venco.com.au

More information

Installation & Service Guide

Installation & Service Guide Reverse Osmosis Ontario Soft Water.ca Kitchener, Canada 519-579-0500 Installation & Service Guide Pentair 75 gpd Encapsulated Membrane System Standard System 75gpd Membrane Your New Reverse Osmosis System

More information

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6 OWNERS MANUAL BOSS COMPRESSED AIR DRYER Distributed by Air & Vacuum Process, Inc. Phone: 281-866-9700 Fax: 281-866-9717 Email: sales@airvacuumprocess.com SAFETY... Page 2 MAINTENANCE... Page 5 INSTALLATION...

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

DF400/DF600. Construction Heaters. Installation and Maintenance Manual

DF400/DF600. Construction Heaters. Installation and Maintenance Manual 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. DF400/DF600 Construction

More information

PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL

PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL FloorHeat PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL Thank you for purchasing this radiant control panel assembly. Following are some important notes that will make the installation successful.

More information

SERIES 'HE' PLASTIC HORIZONTAL PUMP MODEL: H2 x1½

SERIES 'HE' PLASTIC HORIZONTAL PUMP MODEL: H2 x1½ SERIES 'HE' PLASTIC HORIZONTAL PUMP MODEL: H2 x1½ OPERATION AND SERVICE GUIDE O-820_R FEBRUARY 2013 Refer to Bulletin P-201 and Parts Lists: P-7200, P-7250. SAFETY PRECAUTIONS BEFORE STARTING PUMP 1. Read

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO

AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO English......................5 2 Safety and compliance 3 4 English Instruction Manual English Patio Heater Contents Make sure that the package

More information

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions ASSEMBLY PUMPS WITH MOTORS 1. No assembly required. Unpack the pump and motor and examine for any

More information

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL 3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL EFFECTIVE JULY 30, 2014 Superseding All Previous Parts Lists. The Company reserves the right to make substitution in the event that items specified

More information

GETZ MANUFACTURING PART NO.: MODEL: SV1 100 PR VACUFILL SYSTEM (Revised 6/7/05)

GETZ MANUFACTURING PART NO.: MODEL: SV1 100 PR VACUFILL SYSTEM (Revised 6/7/05) GETZ MANUFACTURING PART NO.: 58616 MODEL: SV1 100 PR VACUFILL SYSTEM (Revised 6/7/05) GETZ SV1-100-PR VACU-FILL SYSTEM TABLE OF CONTENTS PAGE # 1... GETZ SV1-100-PR VACU-FILL SYSTEM 2... PARTS LIST 3...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BUILT-IN BOTTOM MOUNT REFRIGERATOR/FREEZER BRTGK72SS-GRILLE KIT (FOR PROFESSIONAL SERIES ONLY) VIKING RANGE CORPORATION 111 Front Street Greenwood, Mississippi (MS) 38930 USA

More information

PS-2/ES Automated pack & tag machine with IndES fastening system

PS-2/ES Automated pack & tag machine with IndES fastening system English Manual PS-2/ES Automated pack & tag machine with IndES fastening system Contents 1. Introduction 2. Important Safety Instructions 3. PS-2/ES 4. Unpacking the machine 5. Setting up the machine 6

More information

TROUBLESHOOTING VANGUARD

TROUBLESHOOTING VANGUARD TROUBLESHOOTING VANGUARD IMPORTANT: Only a qualified Service Person should service internal components or electrical wiring. WARNING: Disconnect electrical power to the Unit to prevent personal injury

More information

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)

More information

INSTALLATION and OPERATION BALL WASHER MODEL NO: BW-022

INSTALLATION and OPERATION BALL WASHER MODEL NO: BW-022 Easy Picker Golf Products, Inc. 415 Leonard Blvd. N., Lehigh Acres, FL 33971 PH: 239-368-6600 FAX: 239-369-1579 Service: 800-982-4653 SALES: 800-641-4653 www.easypicker.com salesdept@easypicker.com INSTALLATION

More information

IMAGE V. Parts and Service Manual

IMAGE V. Parts and Service Manual IMAGE 0V Section II Parts and Service Manual (88B) CLARKE TECHNOLOGY Image Operator's Manual Page AUTHORIZED PERSONNEL MAINTENANCE To Access Pump Motor. Remove brush housing from machine. See "Brush Motor

More information

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS STORED PRESSURE, WHEELED & STATIONARY 50 POUND DRY CHEMICAL FIRE EXTINGUISHERS ABC (AMMONIUM PHOSPHATE BASE), REGULAR (SODIUM BICARBONATE BASE), PURPLE K (POTASSIUM BICARBONATE BASE) OWNERS SERVICE MANUAL

More information

Model Series Series

Model Series Series PumpAgents.com - Click here for Pricing/Ordering Model 36800-Series 36900-Series ELECTRIC WATER SYSTEM PUMPS Automatic Multi-Outlet FEATURES Self-Priming Diaphragm Design Allows Dry Running Built-in Discharge

More information

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System 1 Revised 11/18/10 2320 Lakecrest Drive, Pekin IL 61554 PH. (888) 747-4389 Fax (309) 495-0625 Website: www.getzequipment.com LIMITED

More information

COOLING SYSTEM. Page CO-2 TROUBLESHOOTING... CO-4 CHECK AND REPLACEMEANT OF ENGINE COOLANT... WATER PUMP... DESCRIPTION...

COOLING SYSTEM. Page CO-2 TROUBLESHOOTING... CO-4 CHECK AND REPLACEMEANT OF ENGINE COOLANT... WATER PUMP... DESCRIPTION... COOLING SYSTEM DESCRIPTION... Page CO-2 TROUBLESHOOTING... CO-4 CHECK AND REPLACEMEANT OF ENGINE COOLANT... WATER PUMP... CO-5 CO-6 THERMOSTAT... CO-8 RADIATOR... CO-9 CO-2 COOLING SYSTEM - Description

More information

MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM

MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM SECTION 7B MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM CAUTION: Disconnect the negative battery cable before removing or installing any electrical unit or when a tool or equipment

More information

DRYAIRE MEMBRANE AIR DRYING SYSTEM MODEL 6770

DRYAIRE MEMBRANE AIR DRYING SYSTEM MODEL 6770 DRYAIRE MEMBRANE AIR DRYING SYSTEM MODEL 6770 System Includes: Air Filter w/overnight Drain (Part No. 22601) Coalescer w/overnight Drain (Part No. 22605) Air Regulator Assembly (Part No. 1640) Membrane

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

Owner s manual for. Venco 87mm & 100mm. (3 1/ 2 & 4 ) De-airing Pugmill

Owner s manual for. Venco 87mm & 100mm. (3 1/ 2 & 4 ) De-airing Pugmill Owner s manual for Venco 87mm & 100mm (3 1/ 2 & 4 ) De-airing Pugmill Venco Products 29 Owen Road Kelmscott, Western Australia 6111 ph +61 8 9399-5265 fax +61 8 9 497 1335 email: venwest@iinet.net.au www.venco.com.au

More information

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz DAGNY LK Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 110V~60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any

More information

PMT200A SERIES DEHYDRATOR USER MANUAL. Bulletin AE01B-A NOV 05

PMT200A SERIES DEHYDRATOR USER MANUAL. Bulletin AE01B-A NOV 05 PMT200A SERIES DEHYDRATOR USER MANUAL Bulletin AE01B-A0523-001 Rev: B 18 NOV 05 1 TABLE OF CONTENTS SECTION 1 General Information 3 Introduction 3 Description 3 Operation 3 Alarm 3 Multiple Alarm Option

More information

Owner s Manual Refrigerated Compressed Air Dryers Model F-100

Owner s Manual Refrigerated Compressed Air Dryers Model F-100 Owner s Manual Refrigerated Compressed Air Dryers Model F-100 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

OTO BONDER OWNER S MANUAL WITH CIRCULATING SYSTEM MACHINERY DIVISION - - L to R Unit Shown

OTO BONDER OWNER S MANUAL WITH CIRCULATING SYSTEM MACHINERY DIVISION - - L to R Unit Shown GBAC RROTO OTO BONDER BONDER WITH CIRCULATING SYSTEM G B MACHINERY DIVISION OWNER S MANUAL L to R Unit Shown - - IMPORTANT FOREWORD 1) To ensure efficiency, the GBAC must be properly maintained. Carefully

More information

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS INGERSOLLrAND AIR COMPRESSORS HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS CAUTION: For HMD Models 84 Through 385 ONLY 1. Remove Dryer Chambers And Protective

More information

CONSTANT SUCTION UNIT

CONSTANT SUCTION UNIT CONSTANT SUCTION UNIT OPERATOR/MAINTENANCE M A N U A L Squire-Cogswell/Aeros Instruments Inc 1111 Lakeside Drive Gurnee, IL 60031-4099 1-800-662-5822/847-855-0800 Fax: 847-855-6218 www.aerosinstruments.com

More information

Tornado Operations & Maintenance Manual

Tornado Operations & Maintenance Manual Tornado Industries, LLC 333 Charles Court West Chicago, IL 60185 www.tornadovac.com Tornado Operations & Maintenance Manual MODEL NO. 99414 Form No. L9740AB Tornado Industries, LLC. All rights reserved

More information

Patio Heater_ _V4_ENG.book Page 1 Tuesday, September 2, :00 AM. AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO

Patio Heater_ _V4_ENG.book Page 1 Tuesday, September 2, :00 AM. AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO Patio Heater_14-0979_V4_ENG.book Page 1 Tuesday, September 2, 2014 10:00 AM AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO Patio Heater_14-0979_V4_ENG.book Page 2 Tuesday, September 2, 2014

More information

Elite Primer Baldor Series External Pond Pump

Elite Primer Baldor Series External Pond Pump Elite Primer Baldor Series External Pond Pump ( 5250PPB21, 6440PPB23, 7550PPB26, 9600PPB28) Installation and User s Guide IMPORTANT SAFETY INSTRUCTIONS, READ AND FOLLOW ALL INSTRUCTIONS. SAVE THESE INSTRUCTIONS

More information

SuperKlean Washdown Products

SuperKlean Washdown Products DURAREEL DR8 & DR8S INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** GENERAL WARNINGS High pressure and hot

More information

POWERS TM Controls HU 186 Room And Duct Hygrostats

POWERS TM Controls HU 186 Room And Duct Hygrostats POWERS TM Controls HU 186 Room And Duct Hygrostats Technical Instructions Document No. 155-027P25 HU 186-1 Figure 1. Room Hygrostat. Figure 2. Duct Hygrostat. Description The HU 186 Room and Duct Hygrostats

More information

Oil burners fuel unit with solenoid valve

Oil burners fuel unit with solenoid valve Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Italy - DE112/0404 Oil burners fuel unit with solenoid valve Type VM The DELTA

More information

Instruction Manual HWR MODEL RESISTO-FLO ELECTRIC BOILER

Instruction Manual HWR MODEL RESISTO-FLO ELECTRIC BOILER Page 1 of 16 Instruction Manual HWR MODEL RESISTO-FLO ELECTRIC BOILER Page 2 of 16 FOREWORD The HWR Resisto-Flo Electric Hot Water Boiler is designed to provide a compact packaged unit requiring a minimum

More information

Hydraulic Crimping Heads and

Hydraulic Crimping Heads and Hydraulic Crimping Heads 58422-1 and 2161730-1 Instruction Sheet 408-9535 30 MAY 17 REV D 1. INTRODUCTION Figure 1 This instruction sheet covers application, inspection and maintenance procedures for Crimping

More information

SAFETY AND OPERATING MANUAL

SAFETY AND OPERATING MANUAL SAFETY AND OPERATING MANUAL HOT WATER ELECTRIC WATER BLASTERS Read Safety & Operating Instructions Before Commencing Operation THESE INSTRUCTIONS MUST BE READ AND ADHERED TO BEFORE OPERATING THIS MACHINE.

More information

Operation, Maintenance and Installation Manual

Operation, Maintenance and Installation Manual Manual No. FS-OM1-5 1-16 in. FloodSafe Inflow Preventer Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 CONSTRUCTION...

More information

OPERATING AND MAINTENANCE MANUAL FOR INSTANTANEOUS STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL F

OPERATING AND MAINTENANCE MANUAL FOR INSTANTANEOUS STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL F OPERATING AND MAINTENANCE MANUAL FOR INSTANTANEOUS STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL F Edition 2013 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation

More information

Installation & Maintenance Instructions KAPTIV ZERO AIR LOSS CONDENSATE DRAIN 04/08

Installation & Maintenance Instructions KAPTIV ZERO AIR LOSS CONDENSATE DRAIN 04/08 Installation & Maintenance Instructions KAPTIV ZERO AIR LOSS CONDENSATE DRAIN 04/08 GENERAL OPERATION The KAPTIV is a zero-air-loss, electronic level sensing condensate drain. By installing the KAPTIV

More information

EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252

EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252 EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252 ARROW PNEUMATICS, INC. REGENERATIVE DRYER DIVISION 500 NORTH OAKWOOD RD LAKE ZURICH, IL,60047 PHONE # (847)

More information

TECHNICAL DATA. Wet 26a. February 22, 2009

TECHNICAL DATA. Wet 26a. February 22, 2009 February 22, 2009 Wet 26a 1. DESCRIPTION The Viking Alarm Check Valve serves as a check valve by trapping pressurized water above the clapper and preventing reverse flow from sprinkler piping. The valve

More information

SCHWAN INSTALLATION GUIDE

SCHWAN INSTALLATION GUIDE 1 SCHWAN INSTALLATION GUIDE For Schwan SC60 FOR SERVICE OR ASSISTANCE CALL MERQUIP ON 0800 636 0 636. Schwan recommends that a qualified tradesperson installs your Schwan system. 2 INFORMATION AND SAFETY

More information

PHOENIX 200 MAX. 1 Specifications. 2 Operation. Therma-Stor Products. Phoenix 200 Max Operation & Service Instructions

PHOENIX 200 MAX. 1 Specifications. 2 Operation. Therma-Stor Products. Phoenix 200 Max Operation & Service Instructions PHOENIX 200 MAX LOW GRAIN REFRIGERANT HIGH CAPACITY DEHUMIDIFIER Table of Contents Therma-Stor Products Box 8050 Madison, WI 53708 Toll Free 1-800-533-7533 Local 1-608-222-5301 Phoenix 200 Max Operation

More information