A Treatise on Liquid Subcooling

Size: px
Start display at page:

Download "A Treatise on Liquid Subcooling"

Transcription

1 A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance and efficiency, is what makes it a relevant topic of discussion. As a refrigerant flow control, the TEV s sole purpose is to provide the evaporator with the precise mass flow of heat transfer medium (refrigerant) necessary to transfer the heat load from the refrigerated space. This vital function elevates the TEV to the status of heart of the refrigeration system. The advantage of the TEV, in comparison to fixed orifice expansion devices, is its ability to respond to changes in the heat load and system conditions while maintaining the proper refrigerant mass flow entering the evaporator. Most refrigeration applications are subject to wide load variations walk in box door openings, loading warm product in the refrigerated space, recovery after defrost, the indecisive shopper who requires the frozen food display case glass door to be open while browsing there is no such thing as a constant heat load. As the heat load increases/decreases, the TEV will open/close in an effort to maintain its superheat set point, thereby maintaining the correct refrigerant mass flow to the evaporator inlet. Variations in the heat load may be small or large. However; a heat load that is constantly varying results in a TEV that is constantly in a state of readjusting itself to meet the new heat load demand. When rapid and significant changes to the heat load occur, the previously adequate TEV opening (stroke) becomes completely inadequate for maintaining the correct refrigerant mass flow with respect to the change in load. While the TEV regulates refrigerant mass flow at the evaporator inlet, it is the superheat condition at the evaporator outlet which determines the valve opening. To say it more plainly: The TEV is a superheat control only, and it only responds to the superheat condition at the evaporator outlet. In a sense, the TEV is using old information as the basis for its control. There is a lag in time between the liquid refrigerant entering the evaporator, its change of state into a vapor as the heat load is transferred to it, and its eventual exit to the suction line. For example: Picture a walk in box, whose door is opened to load newly received product into the refrigerated space. The ambient air entering the space, along with the warm product, would cause a rapid increase to the heat load. Ideally, the increased heat load would trigger an increase in TEV opening (stroke), resulting in the necessary increase in refrigerant mass flow to meet the demand of the new heat load. In reality the TEV can only accomplish this after the superheat condition at the

2 evaporator outlet increases. The process which makes this happen is as follows: Additional heat enters the refrigerated space, and is transferred to the saturated refrigerant in the evaporator. The refrigerant then boils faster, completely vaporizing closer to the evaporator inlet, resulting in a higher superheat condition at the evaporator outlet. The increased superheat then causes the TEV to open, supplying more refrigerant to the evaporator in an effort to reduce the superheat back to the TEV set point. The built in time lag between an increase in the heat load and the resulting change in TEV stroke makes it difficult for the TEV to maintain a constant superheat condition at the evaporator outlet. Rapid load changes are one of several conditions that can lead to TEV hunting. TEV Capacity TEV capacity can be best described as the refrigeration effect (heat transfer capacity of the refrigerant at the condition the system is operating at, in Btu/lb) multiplied by the liquid refrigerant mass flow (in lb/min) delivered by the TEV to the evaporator inlet. The heat load being transferred to the saturated liquid refrigerant in the evaporator constitutes the greatest portion of the refrigeration effect. This causes the refrigerant to undergo a change of state; a latent heat transfer process. Refrigerant vapor experiencing a sensible heat gain (temperature increase) provides a very insignificant contribution to the refrigeration effect. The TEV, as a superheat control which regulates refrigerant mass flow at the evaporator inlet, also performs the function of converting the high pressure liquid refrigerant at its inlet to a low pressure mixture of liquid and vapor at its outlet. In a typical system where the four major components (compressor, condenser, TEV, and evaporator) are properly sized, the resulting low pressure mixture of liquid and vapor entering the evaporator should be at a saturation temperature that will be close to the design evaporator condition. When a liquid refrigerant experiences a reduction in pressure, it must also undergo a reduction in temperature and assume the new saturation temperature for the new pressure. This is accomplished as a percentage of the liquid refrigerant flowing through the TEV port flashes into a vapor, removing heat from the remaining liquid refrigerant in the process, achieving the temperature reduction. The difference between the temperature of the liquid refrigerant entering the TEV and refrigerant saturation temperature in the evaporator will determine what percentage of flashing occurs. It should be very clear that TEV capacity is not determined by the liquid refrigerant mass flow entering the TEV, but rather the usable refrigerant mass flow

3 exiting the TEV (and entering the evaporator). Given that refrigerant vapor contributes very little towards the refrigeration effect, the usable refrigerant mass flow should be defined as the mass flow of saturated liquid refrigerant. The mass flow of saturated liquid refrigerant available at the evaporator inlet (the TEV capacity) is determined by 3 things: (1) The thermodynamic properties of the refrigerant in use. (2) The physical dimensions of the TEV: pin angle, port diameter, and stroke. (3) The application conditions of the refrigerant. Any system condition which influences the amount of liquid flashing during the expansion process is relevant; the amount of flashing will determine the quality of refrigerant present at the evaporator inlet, which then determines the actual TEV capacity. The specific refrigerant conditions which determine the TEV capacity for a given refrigerant are: (1) Pressure Drop (ΔP) through the valve port. Mass flow through an orifice is proportional to the pressure drop experienced across the port. (2) Evaporator Temperature (saturation temperature of the refrigerant in the evaporator). This will partially determine the amount of flashing which occurs as the liquid refrigerant expands through the TEV port. As the difference between liquid temperature entering the TEV and the refrigerant saturation temperature in the evaporator increases, the percentage of liquid flashing will increase. (3) Liquid Refrigerant Temperature. As stated above, this also partially determines the amount of flashing that will occur across the TEV port. In addition, liquid refrigerant temperature at the TEV inlet will also determine the density of the liquid refrigerant. Lowering the liquid temperature will increase the density (lb/cu. ft.), which will increase the refrigerant mass flow as the refrigerant volume flow remains consistent at a given ΔP. The ARI rating condition for determining TEV capacity (for high pressure refrigerants such as R 22, R 404A, and R 507) is a 100 psi ΔP, 40ºF evaporator

4 temperature, and 100ºF liquid temperature. The nominal TEV capacity stamped on each valve and listed on the box is simply the valve s capacity at the ARI rating condition. If the conditions change, the valve capacity will also change. Referring to the Pressure Enthalpy diagram in Figure 1, refrigerant quality is amongst the many refrigerant properties which are displayed. It appears within the saturated region of the diagram (between the saturated liquid line on the left, and saturated vapor line on the right), and represents the percentage of vapor present for any given point plotted therein. The refrigerant quality will change as the system operating conditions change, and will be shown to have significance in determining TEV capacity. Figure 1 Refrigerant Properties The pressure enthalpy diagram in Figure 2 shows two systems plotted; a +40ºF airconditioning application and a 40ºF refrigeration application, both condensing at 100ºF. As stated above, the greater the percentage the quality is, the greater the percentage of vapor present in the saturated liquid/vapor mixture. The refrigerant quality at the evaporator inlet for the +40ºF and 40ºF applications are 33.5% and 60% respectively. Another way to look at this is in terms of how much liquid refrigerant remains after the expansion process. If the quality is 33.5% at +40ºF, then 66.5% of the

5 saturated mixture will be liquid. If the quality is 60% at 40ºF, then 40% of the saturated mixture will be liquid. To illustrate this point more plainly: For every 10 lbs/min of refrigerant in circulation, the evaporator inlet of the +40ºF and 40ºF applications will receive 6.65 lbs/min and 4 lbs/min respectively. This is the mass flow of saturated liquid refrigerant at the evaporator inlet, and is the only useful heat transfer medium in reducing the temperature of the refrigerated space. Figure 2 Comparative Refrigerant Qualities The amount of saturated liquid refrigerant remaining after the expansion process determines what the TEV capacity is. Referring to the TEV capacity chart in Figure 3, the nominal capacity of the SSE 4 is 4.08 tons at +40ºF, and 2.45 tons at 40ºF. The ratio of refrigerant quality between the 40ºF and +40ºF applications is.601 (40/66.5). This means that the available liquid mass flow at the inlet of the 40ºF evaporator is 60.1% of the liquid mass flow available at the inlet of the +40ºF evaporator. This should translate into a TEV capacity at 40ºF that is 60.1% of the capacity at +40ºF. Quickly

6 doing the math verifies this to be true; Figure 3 shows the capacity of the SSE 4 at +40ºF to be 4.08 tons. Multiplying 4.08 x 60.1% = 2.45 tons; precisely what is shown at the SSE 4 capacity at 40ºF. Valve Type Nominal Capacity 404A SC, SCP115 SZ. SZP 40º 20º 0º " 10º " 20º " 40º C S O Figure 3 TEV Capacity So, if you require a 4 ton TEV at the 40ºF evaporator condition, the nominal 4 ton TEV is too small. This is due to the large amount of liquid refrigerant flashing required to reduce the 100ºF saturated liquid at the TEV inlet to a 40ºF saturation temperature. After the flashing process the available liquid mass flow at the evaporator inlet is insufficient to provide 4 tons of heat transfer capacity, even though the refrigerant mass flow through the TEV port is greater than what is required for 4 tons of heat transfer. To realize 4 tons of refrigerant mass flow at the evaporator inlet for this application, more refrigerant must flow through the TEV port, and a larger port size is required for this to occur. Figure 2 shows the OSE 9 as having a capacity of 4.43 tons at a 40º evaporator temperature. As stated above, the amount of liquid refrigerant which flashes into a vapor during the TEV expansion process increases as the difference between the TEV entering liquid temperature and the evaporator refrigerant saturation temperature increases. Therefore, if the difference between these two temperatures can be reduced, the amount of usable liquid refrigerant available at the evaporator inlet will increase. When this is accomplished, it will allow the design heat transfer load to be achieved with a reduction in refrigerant mass flow, as the reduced liquid flashing provides for a more efficient use of the refrigerant entering the evaporator. A reduction in mass flow translates into a reduction in the required compressor capacity to achieve the

7 design condition. This reduction in compressor capacity can be achieved by: (1) operating a compressor sized for the design condition in an unloaded mode, (2) operating a smaller compressor instead of a larger compressor on a multi compressor rack, or (3) using a variable frequency drive on a compressor sized for the design load and reducing its capacity by reducing its motor speed. All of these methods result in a reduction in an increase in efficiency, coupled with a reduction in electrical consumption With most applications there isn t much of an opportunity to raise the saturated suction temperature; this is defined by the temperature requirement of the refrigerated space and the TD that the evaporator was selected to operate at (with TD being defined as the temperature difference between the evaporator entering air temperature, and the refrigerant saturation temperature in the evaporator). This fact leaves the lowering of the liquid refrigerant temperature entering the TEV as the only realistic means of reducing the amount of liquid flashing during the TEV expansion process which brings us to the subject of liquid subcooling. Liquid Subcooling By definition, a liquid exists in a subcooled state when its temperature is lower than the saturation temperature for its pressure. For example, the saturation temperature for R 404A at psig (at sea level) is 100ºF. It would be correct to state that liquid R 404A, at psig and 80ºF, is subcooled 20º; meaning that it is 20º below the saturation temperature for that pressure. There are various methods available to provide subcooled liquid for a given piece of refrigeration equipment; liquid to suction heat exchangers, dedicated refrigeration circuits/heat exchangers, or subcooling the liquid refrigerant in the condenser during periods of reduced ambient temperatures. While subcooling the liquid refrigerant before it enters the TEV will reduce the amount of liquid flashing required during the expansion process, if the benefit of the increased amount of liquid at the evaporator inlet does not offset the energy requirement to provide the subcooling, there is no net gain in system efficiency. For example, the liquid to suction heat exchanger shown in Figure 4 simply transfers some of the heat content of the liquid refrigerant to the suction vapor, resulting in a lower liquid temperature, but also a higher vapor temperature. This is a classic rob Peter to pay Paul scenario; the subcooled liquid does result in less flashing during the expansion process, which reduces the refrigerant mass flow requirement of the system..but

8 It is important to remember that a compressor is a volume pump, and will pump a constant volume of refrigerant consistent with the displacement of the compressor. Figure 4 Liquid to Suction Heat Exchanger The mass flow pumping capacity of the compressor in lbs/min is based on compressor displacement, compressor speed, and the refrigerant density. The resulting temperature increase of the suction vapor will result in an increase to the refrigerant s specific volume (or a reduction in density). To illustrate the importance of this, let s assume a compressor with a 300 cu. in. displacement operating at 3600 RPM. It will have a volume pumping capacity of 1,080,000 cu. in./min (300 X 3600). Dividing 1.080,000 by 1728 (1 cu. ft. = 1728 cu. in.) will convert the volume pumping capacity to 625 cfm. R 404A at approximately 35 psig has a saturation temperature of 40ºF, and a specific volume of cu. ft./lb. At 35 psig and the 65ºF suction vapor temperature that compressors are rated at, the specific volume is approximately 3 cu. ft./lb. Dividing the volume pumping capacity by the specific volume will yield the mass flow pumping capacity in lbs/min; 272 lb/min at 40ºF, and 208 lb/min at 40ºF. And therein lies the dilemma with the liquid to suction heat exchanger. While it does provide a lower liquid temperature, it comes at the expense of reduced compressor capacity no net efficiency gain. Its only benefit is the insurance that the liquid refrigerant entering the TEV is vapor free. A separate circuit on the compressor rack can be used to provide the refrigeration capacity needed to deliver subcooled liquid to the expansion valves. Again, this will provide the benefits of subcooled liquid as described above; reduced mass flow due

9 to less refrigerant flashing in the expansion process, and vapor free liquid at the TEV inlets. And once again, it will come with no net efficiency gain, as the equipment experiencing the benefit of the subcooled liquid is also providing the capacity to accomplish the subcooling once again it s a wash. Now, a typical supermarket will employ a rack of low temperature compressors which will operate at approximately 4 5 horsepower per ton, and a rack of medium temperature compressors, which will operate at approximately 2 3 horsepower per ton. It is a fact that lowering the liquid temperature will reduce the required refrigerant mass flow necessary to provide the design Btu capacity for all of the evaporators on a given system. When utilizing a subcooler for the low temperature rack, there is a great potential for efficiency gains when the medium temperature rack is used to provide the refrigeration capacity for the subcooler on the low temperature rack (See Figure 4). For example, if the subcooler load is 120,000 Btu for the low temperature rack, it would require approximately 45 horsepower from this same rack to provide the refrigeration capacity to achieve it ( hp/ton). The same subcooler load could be handled by 25 horsepower on the medium temperature rack. And there is the gain in efficiency; the medium temperature rack is providing 10 tons of refrigeration capacity for the low temperature rack, but accomplishing it with 20 horsepower less. Subcooler control configurations: Given the wide range of conditions..changes in loading, periods when refrigerated circuits have cycled off on temperature and/or defrost, and varying ambient temperatures that the refrigeration equipment will operate under throughout the year, the actual subcooler load will frequently be much less than the design subcooler load. Because of this, some flexibility in TEV application is required so that during those periods when the subcooler load is reduced, the heat exchanger will not operate with erratic superheat or floodback at its outlet. The typical piping/valve arrangement for a subcooler is shown in Figure 4, and consists of a single heat exchanger (typically a plate heat exchanger), with two TEVs piped in parallel supply refrigerant to the inlet of the heat exchanger. Each TEV has a solenoid valve at its inlet, which are controlled by the energy management system (in response to the heat exchanger outlet liquid temperature). Common practice is for one TEV to be sized to supply 1/3 of the heat exchanger s Btu capacity, with the other TEV supplying 2/3 of the heat exchanger s Btu capacity. An EPR valve is used to keep the saturation temperature in the heat exchanger constant. At its best, this arrangement is a compromise, and the poor liquid temperature control is illustrated in Figure 5.

10 Figure 4 Subcooler for L/T Rack, Refrigeration Provided by M/T Rack, Utilizing EEV Control Figure 5 Liquid Temperature Control from Two TEV Arrangement

11 A more reliable method for maintaining a constant liquid temperature at the heat exchanger outlet can be found in using a state of the art electronic controller, along with an electric expansion valve (see Figure 6). This method is somewhat unique; the controller utilizes a temperature probe and pressure transducer at the heat exchanger outlet to control the superheat, and a second temperature probe at the liquid outlet of the heat exchanger to control the leaving liquid temperature. Providing the actual superheat at the heat exchanger outlet is above the superheat set point, the controller will then drive the EEV open or closed in an attempt to maintain the liquid temperature set point. While not shown, an EPR can be used to maintain a constant saturation temperature in the heat exchanger, further enhancing the electronic controller s ability to maintain a constant liquid outlet temperature. Field testing has shown liquid temperatures maintained within +/ 3ºF (see Figure 7). Figure 6 Electronic Controller and EEV for Subcooler Maximizing System Evaporator Operation: As stated earlier, the heat load on the evaporator will undergo wide fluctuations throughout the day, and/or year this is not to be avoided. Every time the actual load varies from the design load condition, the TEV loading (ratio of the actual load divided by the TEV capacity) will change too. This affects the TEV superheat set point, and the ability of the TEV to maintain the desired superheat set point at all times, resulting in an evaporator operating less efficiently than desired.

12 In addition, whenever the TEV s entering liquid refrigeration temperature and/or the pressure drop across the TEV port changes, this too will change the TEV capacity, and in turn change the TEV loading, once again affecting the TEV superheat setpoint. Unlike the changes in the load condition, these system conditions can be controlled. And doing so, will allow for system TEVs and distributor tubes/nozzles that can be selected very precisely, and a very stable superheat condition a the evaporator outlet, resulting in exemplary evaporator performance and maximum efficiency. Figure 7 Liquid Temperature Control From Electronic Controller/EEV Arrangement This can be accomplished by using the above mentioned electronic superheat controller package, along with an outlet pressure regulator in the liquid line (at the receiver outlet). The combination of a fixed liquid pressure and constant liquid temperature of the refrigerant entering the TEV will yield the result described above.

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During

More information

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation Form 30-217 / January 2007 Heat Reclaim Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation While the vapor-compression cycle has

More information

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Copy Right By: Thomas T.S. Wan ) Dec. 28, 2012 All Rights Reserved Case Background: Ammonia is one of the important elements to

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL BY DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL In the September/October 2005 issue of HPAC Magazine, the case was made for reducing head pressure to increase compressor efficiency, thereby lowering its

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

System Considerations for Refrigerant Blends with Temperature Glide

System Considerations for Refrigerant Blends with Temperature Glide System Considerations for Refrigerant Blends with Temperature Glide Theory and Practical Retrofit Guidance Table of Contents 1 2 3 4 5 Blend and Glide Basics... 3 1.1 Superheat and Subcooling of Refrigerant

More information

Sporlan Valve Division Parker Hannifan/CIC Group

Sporlan Valve Division Parker Hannifan/CIC Group www.parker.com/cic Sporlan Valve Division Parker Hannifan/CIC Group Matt McGrath, SW Regional Sales Manager Bob Dolan, Sales Engineer - Atlanta www.parker.com/cic Why Discuss TEVs Today? Expansion Valves

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION

DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION BY DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION It is said that necessity becomes the mother of invention. As energy prices soared in the 1970s, supermarket owners sought ways to reduce their enormous utility

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Psychrometry One of the Fundamental Series D C B A C B D A July 2012 TRG-TRC001-EN Psychrometry One of the Fundamental Series A publication of Trane Preface Psychrometry A Trane

More information

TWO- AND THREE-STAGE CASCADE REFRIGERATION SYSTEM By: Paul B. Reed

TWO- AND THREE-STAGE CASCADE REFRIGERATION SYSTEM By: Paul B. Reed INTRODUCTION Service Application Manual Mechanical refrigerating systems in most common use fall into three classes as far as the temperatures of the evaporators are concerned: 1. High temperatures, with

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system. Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs the unwanted heat, this raises the refrigerant

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1 Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,

More information

Case 8 Basic Performance of Screw Compressor

Case 8 Basic Performance of Screw Compressor Case 8 Basic Performance of Screw Compressor Copy Right By: Thomas T.S. Wan ) June 24, 2010 All Rights Reserved Case Background: The basic rating and performance given by a compressor manufacturer is usually

More information

Sustainable Techniques in Refrigerated Space

Sustainable Techniques in Refrigerated Space Sustainable Techniques in Refrigerated Space Sustainability and high performance of refrigerated space used for the preservation of perishable product capitalizes on conservation techniques which reduce

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

MASS. MARITIME ACADEMY

MASS. MARITIME ACADEMY MASS. MARITIME ACADEMY REFRIGERATION LAB OUTLINE Rev.3 Fall 2015 Table of Content Page Lab #1: Introduction to refrigeration system components, tools and procedures 1 Lab #2: Familiarization, operation,

More information

Bulletin , March Electric Hot Gas Bypass Valves

Bulletin , March Electric Hot Gas Bypass Valves Bulletin 100-60, March 2018 Electric Hot Gas Bypass Valves PAGE 2 / Bulletin 100-60 10 FEATURES AND BENEFITS SDR-4 Direct temperature control Tight shutoff when closed Can be interfaced with direct digital

More information

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A900-22007), 120/208/240/1/60, R404A, LT/MT APPS Introduction The superheat controller is designed

More information

Use this Construction/HVAC Glossary to answer the questions below.

Use this Construction/HVAC Glossary to answer the questions below. www.garyklinka.com Page 1 of 21 Instructions: 1. Print these pages. 2. Circle the correct answers and transfer to the answer sheet on the second last page. 3. Page down to the last page for the verification

More information

KE2 EvaporatorEfficiency Theory of Operation

KE2 EvaporatorEfficiency Theory of Operation Theory T.1.1 June 011 TM thermsolutions ENTER BACK KE Therm Solutions, Advanced Energy Saving Technology for Commercial Refrigeration and AC Systems Page Table of Contents Basic Refrigeration System Evaporator

More information

A/C Cooling Load calculation and measurement

A/C Cooling Load calculation and measurement Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying

More information

RTP Technical Bulletin

RTP Technical Bulletin RTP Technical Bulletin Category: REFRIGERATION REGISTERED TECHNICIANS PROGRAM Volume 1 Bulletin 2 the information contained in this bulletin contains some important c o n c e p t s regarding pressure/

More information

CO2 TRANSCRITICAL BOOSTER SYSTEMS

CO2 TRANSCRITICAL BOOSTER SYSTEMS CO2 TRANSCRITICAL BOOSTER SYSTEMS William Katz Sr. Technical Writer Hillphoenix 2016 Gees Mill Road Conyers, GA 30013 Tel: 678-613-9364 Email: william.katz@hillphoenix.com Refrigeration systems for supermarkets

More information

THERMOSTATIC EXPANSION VALVES Part 1

THERMOSTATIC EXPANSION VALVES Part 1 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 THERMOSTATIC EXPANSION VALVES Part 1 Revised by Loren Shuck, CMS INTRODUCTION The thermostatic expansion valve (frequently

More information

USING THE P-T CARD AS A SERVICE TOOL

USING THE P-T CARD AS A SERVICE TOOL Service Application Manual SAM Chapter 620-115 Section 2 USING THE P-T CARD AS A SERVICE TOOL Reprinted with permission from Sporlan Division, Parker Hannifin Corporation INTRODUCTION Manufacturers of

More information

B. A. T. Basic Appliance Training

B. A. T. Basic Appliance Training B. A. T. Basic Appliance Training BASIC REFRIGERATION presented by Phil Whitehead Program Objective The objective of this program is to give you some of the basic elements that are essential to understanding

More information

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES November 2006 / BULLETIN -60 ELECTRIC DISCHARGE BYPASS VALVES PAGE 2 / Bulletin -60 10 FEATURES AND BENEFITS Direct temperature control Tight shutoff when closed Can be interfaced with direct digital controls

More information

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points Name: Start time: End time: FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points 1. What are the units of the following quantities? (10 points) a. Enthalpy of a refrigerant b. Dryness fraction of

More information

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS ENERGY CONSUMPTION HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS Introduction Those in charge of specifying and purchasing equipment for industrial compressed air systems have many

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA242H WA36H NOTE: Electrical data presented in this manualsupersedes any other data for the above listed models. Bard Manufacturing

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

The Saturation process

The Saturation process SOUTH METROPOLITAN TAFE WA The Saturation process Dennis Kenworthy 8/5/2016 A student study guide to measuring and interpreting the saturation process of refrigeration and air-conditioning equipment System

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS HVAC Systems What the Rater Needs to Know in the Field This presentation used CASE* studies from the following *CASE Copy And Steal Everything HVAC Systems - What the Rater Needs to Know in the Field This

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

What Is Liquid Subcooling?

What Is Liquid Subcooling? VA Lake City Florida Rob, Though I still haven t received the information from the contractor for this project, I have done some preliminary work on it. One thing of concern to me is something that you

More information

HVAC/R Refrigerant Cycle Basics

HVAC/R Refrigerant Cycle Basics HVAC/R Refrigerant Cycle Basics This is a basic overview of the refrigeration circuit and how it works. It isn t a COMPLETE description by any means, but it is designed to assist a new technician or HVAC/R

More information

Steam: Yesterday, Today and Tomorrow The Use of Steam as an Efficient Heat Source

Steam: Yesterday, Today and Tomorrow The Use of Steam as an Efficient Heat Source Steam: Yesterday, Today and Tomorrow The Use of Steam as an Efficient Heat Source Tech Sheet #ST 103 The mention of steam conjures up the thought of days gone by when steam was used to power engines, to

More information

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled

More information

Technical Information

Technical Information Date of last update: 02-08 Ref: Application Engineering Europe COPELAND SCROLL COMPRESSORS USING VAPOUR INJECTION FOR REFRIGERATION CONTENTS 1 Introduction...1 2 Principle of Operation...1 3 Capacity Effect...2

More information

System Design, Commissioning, Operation

System Design, Commissioning, Operation PART 3: CO 2 as a Refrigerant System Design, Commissioning, Operation Service This series continues with the introduction of transcritical, cascade and secondary systems; how each system works; and compares

More information

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs Abstract Fan and coil evaporators as used in the industrial refrigeration industry can be certified for performance per ANSI/AHRI Standard 420-2008, Performance Rating of Forced-Circulation Free-Delivery

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING UNIT OBJECTIVES After studying this unit, the reader should be able to Describe how refrigerant is charged into systems in

More information

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case: Case-16 Cascade Refrigeration System for LPG Subcooling Copy Right By: Thomas T.S. Wan ( ) Mar. 28, 2003 All Rights Reserved Case Background: This is a case of using a cascade refrigeration system to subcool

More information

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers - ERRATA SHEET FOR AHRI STANDARD 1250 (I-P)-2009, PERFORMANCE RATING OF WALK-IN COOLERS AND FREEZERS December

More information

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job. June 01 / BULLETIN - 3-Way Valves The right solenoid valve for any job. Page 2 / Bulletin - Advantages Sporlan 3-Way Valves 3-Way Pilot eliminates costly high- to low-side leaks. "B" reduces total installed

More information

(Refer Slide Time: 00:00:40 min)

(Refer Slide Time: 00:00:40 min) Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide

More information

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs Lesson 1 - Introduction to Refrigeration and Air Conditioning Define refrigeration. Identify the basic components of a refrigeration cycle. Identify the various gas laws and their importance to a basic

More information

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps

More information

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the XSTREAM Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International Psychrometrics: The Science of Moisture in Air Presented by Tom Peterson, CEO and Founder Climate by Design International www.cdihvac.com Owatonna, MN 507-451-2198 4 02/2014 1 Psychrometrics or psychrometry

More information

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A Installation & Service Manual S E C T I O N 26 Enviroguard III ENVIROGUARD III is a patented refrigerant control system that utilizes floating head technology (Nature s Cooling). The amount of liquid refrigerant

More information

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the MYSTICOOL Max Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

Head Pressure Control Application Guide

Head Pressure Control Application Guide Head Pressure Control Application Guide for Air-Cooled Condensers and Condensing Units Bulletin T40-HPC-AG-1 1101111 GENERAL When air-cooled condensers or condensing units are installed outdoors, they

More information

How to Diagnose a TXV Failurek

How to Diagnose a TXV Failurek How to Diagnose a TXV Failurek There has been much written and many jokes made about the misdiagnosis of TXV (Thermostatic expansion valves) and rightly so. This article will cut straight to the point

More information

PPL Electric Utilities Energy Efficiency and Conservation Program

PPL Electric Utilities Energy Efficiency and Conservation Program Installation of High-Efficiency High Efficiency Evaporator Fans Evaporator Fans That have Highfor Walk-ins Efficiency Permanent Split $50/fan motor Capacitor (PSC) Motor or ECM High Efficiency Compressors

More information

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Executive Summary. Number of Low Number of High Number of Faults , Number of OK Unit Lower limit Upper limit Air on Model no evap. F Air off evap. F dt air evap. F Executive Summary Evapo. F This is a summary chart for quick reference and view of all the systems tested. Red boxes

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN Air Conditioning Clinic Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES BUSINESS REPLY MAIL FIRST-CLASS MAIL PERMIT NO. 11 LA CROSSE,

More information

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM 551B 581B DuraPac Plus Series Sizes 036-150 3to12 1 / 2 Tons Cancels: New PAD 551B.36.2 10/1/04 CONTENTS Page INTRODUCTION.................................

More information

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source

More information

Selecting an Environmental Test Chamber

Selecting an Environmental Test Chamber Selecting an Environmental Test Chamber Eric Berchtold, Cincinnati Sub-Zero Cincinnati Sub-Zero Products, LLC 12011 Mosteller Road Cincinnati, Ohio 45241 513-772-8810 www.cszindustrial.com 1 Selecting

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014 Class 1: Basic Refrigera0on Cycle October 7 & 9, 2014 Refrigeration Cycle 4 key components needed in a basic refrigera0on cycle: 1. Compressor 2. Condenser 3. Evaporator 4. Metering Device Compressor Compressor

More information

Technical Information

Technical Information Date of last update: May-12 Ref: : Application Engineering Europe ENHANCED VAPOUR INJECTION (EVI) FOR ZH*KVE SCROLL COMPRESSORS 1 Introduction... 2 2 Principle of operation... 2 3 Capacity effect... 3

More information

SERVICE ASSISTANT OVERVIEW FDSI Online Training

SERVICE ASSISTANT OVERVIEW FDSI Online Training Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

THERMAL MASS CYCLING REFRIGERATED AIR DRYERS. GTRC Series

THERMAL MASS CYCLING REFRIGERATED AIR DRYERS. GTRC Series THERMAL MASS CYCLING REFRIGERATED AIR DRYERS GTRC Series GARDNER DENVER GTRC REFRIGERATED AIR DRYERS Why Dry Compressed Air? Compressed air has long been described as the fourth utility after electricity,

More information

AE R1 March 1993 Reformatted November Compressor Overheating

AE R1 March 1993 Reformatted November Compressor Overheating AE17-1260 R1 March 1993 Reformatted November 2010 Compressor Overheating It is ironic that in an industry whose product is cooling and refrigeration, the most serious field problems arise from overheating

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

5. ASSESSMENT RECOMMENDATIONS

5. ASSESSMENT RECOMMENDATIONS 5. ASSESSMENT RECOMMENDATIONS AR No. 1 Reduce Discharge Pressure Recommended Action Reduce the minimum condensing temperatures on your warehouse refrigeration systems from 110 F to 60 F. In order to reduce

More information

THERMOSTATIC EXPANSION VALVES

THERMOSTATIC EXPANSION VALVES SPORLAN EXPANSION VALVES Selective Thermostat Charges Designed to provide optimum performance for all applications air conditioning and heat pump, medium and low temperature refrigeration. Thermostatic

More information

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units ANSI/AHRI Standard 510-2006 (Formerly ARI Standard 510-2006) Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units Price $10.00 (M) $20.00 (NM) Printed

More information

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P) 2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment AHRI Guideline T (I-P) IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

Carwin COMPRESSOR SELECTION PROGRAM

Carwin COMPRESSOR SELECTION PROGRAM Carwin COMPRESSOR SELECTION PROGRAM IMPORTANT! READ CAREFULLY BEFORE USING By using this disk covering a software program entitled CARLYLE SELECTION PROGRAM WINDOWS (Software), you indicate your acceptance

More information

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to

More information

Refrigeration/Troubleshooting Manual

Refrigeration/Troubleshooting Manual Refrigeration/Troubleshooting Manual P.O. Box 245 Syracuse, NY 13211 www.roth-america.com 888-266-7684 P/N: 2300100910 Table of Contents: Section 1: Geothermal Refrigeration Circuits Overview... 2 Water-to-Air

More information

Superheat charging curves for technicians

Superheat charging curves for technicians This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block.

More information

General information on refrigerant controllers

General information on refrigerant controllers General information on refrigerant controllers Condensing pressure controller The condensing or condenser pressure controller is a back pressure controller and its task is to maintain the condensing pressure

More information

THERMAL ICE STORAGE: Application & Design Guide

THERMAL ICE STORAGE: Application & Design Guide THERMAL ICE STORAGE: Application & Design Guide Table of Contents: 1. Introduction A. History of Thermal Energy Storage B. Operating and Cost Benefits 2. Applications A Fundamental System B. HVAC Cooling

More information