Service Settings. EASY PFA Universal Biomass Heating System Controller. Technical Documentation
|
|
- Verity Tyler
- 5 years ago
- Views:
Transcription
1 Service Settings EASY PFA Universal Biomass Heating System Controller Technical Documentation
2 Safety Precautions Caution! Schock Hazard! Risk of electrical schock which may cause serious injuries or death. Please disconnect the mains before servicing this equipment. Caution! Hot Surfaces! The boiler assembly and/or the temperature sensors may be extremely hot which may cause serious burns. Turn off the equipment then wait at least one hour before servicing. Caution! Moving Parts! Watch your hands while servicing the moving parts such as auger assembly which may cause serious injuries. Caution! This device is intended to be professionally installed. Incorrect installation and/or operating parameters may cause dangerous conditions.
3
4 Service Menu Service Settings Service Menu Map
5 Machine Settings This section adjusts the machine specific data which has already adjusted by Factory. Setting Unit Min. Max. Description Machine Type None HA HW Selects the main function of the control panel. HA: Hot Air furnace HW: Hot Water boiler Min. Power kw 1 < Max Power Max. Power kw > Min. Power Describes the minimum operational power of the burner. This value is machine specific and should not be changed before consulting the manufacturer. 99 Describes the maximum operational power of the burner. This value is machine specific and should not be changed before consulting the manufacturer. Efficiency % - 99 Describes the heat transfer ratio of the air furnace/boiler body. This value is machine specific and should not be changed before consulting the manufacturer. Feed Rate gr.min Describes the feeding capacity of the auger screw. See Feed Rate Calibration for further information. Clean Period h 4 18 Describes the maximum duration of heating cycle. After the clean period timer has been expired, software will stop the combustion and start over. Audible and/or visible warning message may appear on the display. Room Thermostat Function None LP STOP Selects the main function of room thermostat. LP (Low Power): Forces the burner to operate at lowest power if there is no heat demand. This function is recommended fora ir furnaces in order to save electricity consumption and fast start-up in case of instant heat demand. STOP: Flame outs the burner. This function is recommended for boilers. Room Thermostat Type None NO NC Control panel is compatible with all types of mechanical and electronic room thermostats. NO: Normally Opened type room thermostat NC: Normally Closed type room thermostat. Warning: Room thermostat input is DRY-CONTACT type. Do not energize the
6 input by mains. Feed Rate Calibration Software uses the Feed Rate value in order to calculate the dosage of the fuel. If you use standard DIN+ pellets, the Factory calibration will be enough. However the density of the pellets might be different. To initiate a Feed Rate calibration, a sensitive weigh scale and a stopwatch are required. Calibration Steps: Stop the boiler/air furnace and wait for cool down. Place a small container in the burner and make sure that all pellets delivered by the auger screw will captured by the container. Go to Service->I/O Test Turn on the auger screw by setting AUG = 1. Start the stopwatch at the same time. Let the auger screw run for 3 minutes. Stop the auger screw by setting AUG = 0. Scale the container. Divide the weight by 3 and set the Feed Rate with this value. Combustion Settings Setting Unit Min. Max. Description Fuel energy kwh.kg Describes the fuel energy. Refer to the pellet manufacturer s datasheet for more information. Some manufacturers describe the fuel energy in kcal.kg -1 If it is so, multiply the value by in order to convert to kwh.kg -1 Modulator None - - Control panel has three power regulation settings. PID: Proportional-Integral-Derivative Control (see Understanding PID for more information) Mod1..Mod5: Fixed output modes 5Step: 5 level modulation Modulation Window C - 10 See How does Modulation work for more information Hysterezis C - - See How does Modulation work for more information Feed Period Sec Time Base for auger screw. See Understanding Fuel Dosage for more information Exhaust Limit C - - Adjusts the maximum allowable emission temperature. If the chimney gas temperature exceeds this value, software will reduce the output power in order to prevent heat loss through the chimney.
7 Mod1 Mod5 kw See How does Modulation work for more information. Fan1 Fan5 none See How does Modulation work for more information. PID Settings Submenu See Understanding PID for more information Ventilation1 Ventilation5 none Adjusts the ventilation fan speed for air furnaces. Forced Air Cleaning none OFF ON See Forced Air Cleaning for more information. Understanding Fuel Dosage Software performs several calculations in order to deliver right amount of pellets to the burner. DC=(RP FP)/(FE FR 60 EF) Where DC: Auger screw duty cycle in seconds RP: Rated Power in kilowatts FP: Feed Period in seconds FE: Fuel Energy in kwh/kgs FR: Feed rate in gr/mins EF: Heat Exchanger Transfer Coefficient
8 How does Modulation work? Software adjusts the output power in order to maintain the boiler temperature constant. A brief information about modulation and settings in the modulation. Setpoint: Desired temperature Hysterezis: Maximum allowable overshoot of the desired temperature Modulation Window or Modulation Delta: The output power will be modulated by PID algorithm if the actual temperature is in between Setpoint-Mod.Window Setpoint. If the actual temperature is les then Setpoint-Mod.Window, the boiler will operate at maximum power. Understanding PID The PID control scheme is named after its three correcting terms, whose sum constitutes the manipulated variable (MV). The proportional, integral, and derivative terms are summed to calculate the output of the PID controller. Defining output, the final form of the PID algorithm is: as the controller where : Proportional gain, a tuning parameter : Integral gain, a tuning parameter : Derivative gain, a tuning parameter : Error : Time or instantaneous time (the present) : Variable of integration; takes on values from time 0 to the present.
9 Forced Air Cleaning Forced air cleaning helps burner to keep clean during the heating cycle by interrupting the fuel supply and blowing excess air to the burner. Applied for Waiting Time Minutes Air blasting time Seconds 0..20% of output F.A. Wait1 Observe the F.A.Clean1 Observe the % of output F.A. Wait2 combustion and F.A.Clean2 combustion and % of output F.A. Wait3 change the value F.A.Clean3 change the value % of output F.A. Wait4 if necessary F.A.Clean4 if necessary % of output F.A. Wait5 F.A.Clean5 Timing diagram: Wait Clean Wait Clean Primary fan speed and auger Auger OFF screw controlled by software Fan to MAX Ignition Settings Setting Unit Min. Max. Description Feed Time Sec - - Adjustes the initial fuel feed before ignition Timeout Min - - Adjustes the timeout for ignition. If boiler fails to ignite within Timeout a warning message will appear on the display. Fan Speed None - - Basic fan speed for ignition cycle Burn. Detect Delta C - - Temperature difference to detect flame in Burn-in Time Min - - Time delay after flame detection to routine operation Burn-in Fan Speed None - - Fan speed during the burn in time Burn-out time Sec - - Time delay to consume all pellets in the burner before shutdown Burn-out temp C - - Temperature threshold to detect flame out.
10 Flow Chart of the Ignition Cycle Pump Settings Setting Unit Min. Max. Description Startup Temp C - - Adjustes the startup threshold for pump Hysterezis C - - Adjustes the hysterezis for fump operation. Startup Temp. Hysterezis Temp. Pump Starts Pump Stops Boiler Temp.
11 I/O Test Warning! This menu is only for testing the outputs of the boiler for a short time. Leaving the boiler in Test Devices menu may cause dangerous conditions. IGN Igniter (1: ON) IN0 Not implemented PUMP Pump IN1 Limit Thermostat (1: Triggered) AUGER Auger Screw IN2 Room Thermostat (1: ON) * (1: Triggered) FAN1 Ventilation IN3 Pressure Switch Fan (0..255) (0: Triggered) FAN2 Combustion Fan (0..255) IN4 Back Burning Thermostat (0: Triggered) T1 Monitors the primary NTC sensor T2 Monitors the AUX NTC sensor TC Monitors the Chimney temperature TB Monitors the electronic board temperature * Auger motor is electrically connected to pressure switch and limit thermostat. If any of those triggered the motor will not work. Pressure switch is not available in all machines. Outputs Connector pin diagram 6.2 Sensor Connector pin diagram
12 Factory Defaults This option restores all the adjustments to Factory defaults
13 Notes:
HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER
This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER
More informationOPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19
OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER Version DC19 1. Application. Controller RK-2006LPP is designed for temperature control of solid fuel fired water boilers
More informationElectronic Pellet Burner Controller NPBC-V3M
Electronic Pellet Burner Controller NPBC-V3M SOFTWARE VERSION 3.3a/3.2 page of 27 CHANGES IN THE USER MANUAL OR IN THE CONTROLLER'S SOFTWARE Version of the user manual Changes Page 2.2. The software version
More informationElectronic Pellet Burner Controller NPBC-V3-1
Electronic Pellet Burner Controller NPBC-V3- SOFTWARE VERSION 3.2/3. page of 3 CHANGES IN THE TECHNICAL AND USER GUIDE OR IN THE SOFTWARE VERSION Technical and User Guide's version Changes Page 2.8. The
More informationPellet Stove Test Manual
Pellet Stove Test Manual Stricter Emission Standards Adopt stricter emission standards than the EPA. 1. Washington: 4.5 grams per hour for non-catalytic and pellet stoves; 2.5 grams per hour for catalytic
More informationB-40/B-41 Modulating Temperature Controller
INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N
More informationMODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL
MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL The SF-10 Temperature Control () is an efficient boiler operator with a digital LCD display with backlight, a boiler pump output, and an alarm. The
More informationCm Pelet-set (60-90 kw)
CENTROMETAL d.o.o. Glavna 12 40306 Macinec Croatia tel: +385 40 372 600; fax : +385 40 372 611 TECHNICAL INSTRUCTIONS FOR THE COMMISSIONING AND ADJUSTMENT Cm Pelet-set (60-90 kw) For boilers: EKO-CK P
More informationCm Pelet-set TECHNICAL INSTRUCTIONS FOR THE COMMISSIONING AND ADJUSTMENT. (14-35 kw) For boilers: EKO-CKB P (EKO-CKB 20-40)
TECHNICAL INSTRUCTIONS FOR THE COMMISSIONING AND ADJUSTMENT Cm Pelet-set (14-35 kw) For boilers: EKO-CK P 20-40 (EKO-CK 20-40) EKO-CKB P 20-40 (EKO-CKB 20-40) TUPS-M-11-2015-E-N-ENG CONTENTS 1. Introduction.....
More informationMonitoring Software for NPBC-V3M-1 User Manual
Monitoring Software for NPBC-V3M-1 User Manual User Manual ver 1.5 page 1 of 14 Contents: 1. Introduction... 3 2. Requirements... 3 3. Installing the software... 4 4. Connecting the devices... 4 5. Updating
More informationEasyTech.One Temperature Controller for Pellet Burner
EasyTech.One Temperature Controller for Pellet Burner Burner 1 INTRODUCTION... 3 2 ELECTRICAL CONNECTIONS... 3 3 CONTROL PANEL: USE AND FUNCTIONS... 5 3.1 LED... 5 3.2 BUTTONS... 5 3.3 ALARMS... 5 3.1
More informationOVEN INDUSTRIES, INC.
OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and
More informationMODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL
MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL The EM-10 Boiler Temperature Control (BTC) is an efficient boiler operator with a digital LCD display with backlight, a boiler pump
More informationJanfire Pellet Burner Boiler. for single / double burner management (Version 1.1)
SY325 Janfire Pellet Burner Boiler for single / double burner management (Version 1.1) TECHNICAL DATA SHEET V1.1 rev.12/2007 Contents INTRODUCTION...3 1 THE CONTROL PANEL...4 2 THE KEYS...4 3 THE LEDS...4
More informationPellet Stove Test Manual
Pellet Stove Test Manual Stricter Emission Standards Adopt stricter emission standards than the EPA. 1. Washington: 4.5 grams per hour for non-catalytic and pellet stoves; 2.5 grams per hour for catalytic
More informationOven Control System Operation - Ver 2.8
Version 2.8 - Pg:1 - Ver 2.8 This operation manual contains important information about your oven. All operators should review this manual before operating the oven. When you turn on the switch, the control
More informationSWEBO Bioenergy Manual pellet burner PB50 Rev no. Date Page PBM1: (37) Installation and maintenance instructions
PBM1:12 2008-10-16 1 (37) Installation and maintenance instructions PBM1:12 2008-10-16 2 (37) TABLE OF CONTENTS 1 GENERAL INFORMATION... 5 1.1 PELLET STORAGE... 6 1.2 CONSTRUCTION AND FUNCTION... 7 1.2.1
More informationElectronic pellet burner controller - NPBC-V3M. Electronic Pellet Burner Controller NPBC-V3M
Electronic Pellet Burner Controller NPBC-V3M page 1 of 11 INTRODUCTION NPBC-V3M is an advanced, functionally completed controller for pellet burners. All the mechanisms and sensors of the burner, as well
More informationprestige Control Application Supplement - TriMax
prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions
More informationLMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification
LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.
More informationEasyTech.Full Temperature Controller for Pellet Stove. Idro
EasyTech.Full Temperature Controller for Pellet Stove EasyTech.One is a Pellet stoves control system available in Air and Hydro version. Is characterised by: Installing and use simplicity Simple and direct
More informationINSTRUCTIONS FOR USE OF COMBINED BOILER INTENDED FOR COMBUSTION OF BOTH PELLETS AND SOLID FUEL ABC COMBO
INSTRUCTIONS FOR USE OF COMBINED BOILER INTENDED FOR COMBUSTION OF BOTH PELLETS AND SOLID FUEL ABC COMBO .Technical specifications Boiler power DESCRIPTION Water content in a boiler Required draft Supply
More informationNEW LINE BOILER CONTROLLERS
BOILER CONTROLLERS IGNEO NEW LINE BOILER CONTROLLERS We are pleased to present a new versatile line of boiler controllers from IGNEO with new unprecedented capabilities. The IGNEO family of controllers
More informationProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.
ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. The RVA 46 Zone Controller can only be used in conjunction with a RVA47 controlled boiler installation. The RVA46 controller
More informationControl Application. Supplement - ACVMax
prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions
More informationModel Universal Oil Primary Control
Model 70200 Universal Oil Primary Control Installation and Operating Instructions For Use By Qualified Service Technicians Only Universal Replacement for Carlin, Beckett, Honeywell and ICM Controls On-Board
More informationService Manual Models: 1.0, 1.3, and 1.5
AWX2-SER_100160837_2000000360_Rev F Service Manual Models: 1.0, 1.3, and 1.5 LOW LEAD CONTENT WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,
More informationKSM-Multistoker XXL With PCT400 O2 Controller
User manual. KSM-Multistoker XXL With PCT400 O2 Controller Save money! Install a KSM-Stoker Dealer: - 1 - EU Declaration of Conformity We the undersigned, PRODUCER: KSM-STOKER A/S ADDRESS: NAESSUNDVEJ
More informationSWEBO Bioenergy Manual pellet burner PB20 Rev no. Date Page PBM1: (36) Installation and maintenance instructions
PBM1:12 2018-01-22 1 (36) Installation and maintenance instructions PBM1:12 2018-01-22 2 (36) TABLE OF CONTENTS 1 GENERAL INFORMATION... 5 1.1 PELLET STORAGE... 5 1.2 CONSTRUCTION AND FUNCTION... 6 1.2.1
More informationService Manual. w/con X US Interface Models: Series: & WARNING
100208044_2000004590 Rev N w/con X US Interface Models: 751-6001 Series: 100-101 & 110-111 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,
More informationONX908MTW-0/24V MULTI STAGE THERMOSTAT
ONX908MTW-0/24V MULTI STAGE THERMOSTAT Application: 24VAC,2Heat/2cool Installation and operation instructions SPECIFICATION: Electrical Rating 24VAC Terminal Load 3.0 A per terminal (terminal Y1, W1, G:
More informationPELLET BURNER PV 350
PELLET BURNER PV 350 INSTRUCTION MANUAL v1.1 1 PRODUCT DESCRIPTION...3 2 SAFETY RULES...3 3 WARNINGS...4 4 INSTALLATION INSTRUCTIONS...5 4.1 BOILER REQUIREMENTS...5 4.2 PELLET CONTAINER...6 4.3 INSTALLATION
More informationLMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification
SCC Inc. LMV51 Control Product Description February 7, 2017 The LMV51 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft
More informationARITERM OY. Arimatic 500. User manual
ARITERM OY Arimatic 500 User manual Table of contents 1. General information... 3 2. Transport, storage and package opening... 3 3. Warranty... 3 4. Installation and commissioning... 4 5. System description...
More informationOperator: Save these instructions for future use!
50V64-743 Integrated Furnace Control for Furnaces with Variable Fan Speed INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
More informationprestige Control Application Supplement - ACVMax
2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory
More informationUSE AND MAINTENANCE. Cm Pelet-set (60-90 kw) TECHNICAL INSTRUCTIONS
CENTROMETAL d.o.o. Glavna 12 40306 Macinec Croatia tel: +385 40 372 600; fax : +385 40 372 611 TECHNICAL INSTRUCTIONS USE AND MAINTENANCE Cm Pelet-set (60-90 kw) For boilers: EKO-CK P 70-110 TUPS-90K-09-2015-E-N-eng
More informationEach burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning Control System.
Product Guide Specification Nexus Integrated Burner Control System 1. General 1.1 Overview Each burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More information1 DOCUMENT REVISION CONTROL ELEMENTS... 9
CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11
More informationprestige Control Application Supplement - TriMax
prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More informationMANUAL FOR INSTALLATION, OPERATION AND MAINTENANCE OF AN AUTOMATED PELLET BURNER FROM SERIES GP XX SC.
MANUAL FOR INSTALLATION, OPERATION AND MAINTENANCE OF AN AUTOMATED PELLET BURNER FROM SERIES GP XX SC http://www.greenecotherm.eu Pellet burner GP xx sc 1 Manufacturer Address ZMM Haskovo AD 67 Saedinenie
More informationService Manual. w/con X US Interface Models: WARNING
FB-SER_100161013_2000004598 Rev R Service Manual w/con X US Interface Models: 2500-6000 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,
More informationModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.
ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page
More informationForced draught gas burner
Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1
More informationService Manual Models:
KBXII-SER Rev A Models: 400-801 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Knight XL Installation
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More informationTECHNICAL INSTRUCTIONS USE AND MAINTENANCE
TECHNICAL INSTRUCTIONS USE AND MAINTENANCE Cm Pelet-set For boilers CentroPlus 25/35 and CentroPlus-B 25/35 (solid fuel and wood pellets fuel firing) TUPSCP-K-11-2016-ENG CONTENTS 1.Introduction 2. Status
More informationCombined boiler. for solid fuel and pellets
Combined boiler ATTACK WOOD&PELLET for solid fuel and pellets W W W. A T T A C K. S K MODEL STRUC TURE OF THE AT TACK BOILERS THE NEW LINE OF ATTACK BOILERS FOR WOOD AND PELLETS 3000 000 6000 4 ATTACK
More informationBIX B-One 100 kw INSTALLATION GUIDE
BIX B-One 100 kw INSTALLATION GUIDE Dear Customer, We thank you for choosing our product. The Bix B-One 100 Kw is a burner of advanced concept and technology, with a high reliability and construction quality.
More informationPV1000agri pellet burner
PV1000agri pellet burner User manual POOLELI - DRAFT PV1000agri pellet burner p 1/ 50 Description Main components 1 Contents 2 Description... 4 2.1 Main components... 5 2.2 Specifications... 7 3 Installation...
More informationService Manual Models: Series 100 & 101
100305279_2000558130 Rev A Service Manual Models: 55-285 Series 100 & 101 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this
More information- Data Brochure Universal Reset Module 423
- Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in
More informationService Manual Models:
FBII-SER Rev B Service Manual Models: 751-2001 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Crest Installation
More informationTHERMAX Efficiency Monitor
INSTALLATION & OPERATION INSTRUCTIONS THERMAX Efficiency Monitor Oil & Gas Fired Heating Equipment Efficiency Monitoring Instrument Important Safety Instructions Read and safe these instructions before
More informationSettings and Maintenance of the CombinAir
Atmos CombinAir Settings and Maintenance of the CombinAir Issue 13.8.10 Operation and commissioning: The control unit on the front of the CombinAir is used to adjust the settings during commissioning.
More informationRefrigerated air dryers
Refrigerated air dryers OPERATING AND MAINTENANCE MANUAL Original instructions 38178800319 OPERATING AND MAINTENANCE MANUAL - Contents 1 CONTENTS CONTENTS... 1 Chapter 1 IDRY ELECTRONIC CONTROLLER...
More informationEKO Line Pellet Boiler Wood Pellet Storage Solutions And Pellet Dosage Systems
EKO Line Pellet Boiler Wood Pellet Storage Solutions And Pellet Dosage Systems 1 EkoLine Wood Pellet Boilers EKOLINE boilers have been designed specifically for the purpose of heating water to temperatures
More informationINSTRUCTIONS FOR ASSEMBLY, USE, AND MAINTENANCE PELLET STOVE LUCA S/LUKA S8
WARNING: This user manual is an integral part of the product. It has to be kept and read carefully. EN INSTRUCTIONS FOR ASSEMBLY, USE, AND MAINTENANCE PELLET STOVE LUCA S/LUKA S8 1. Introduction Firstly,
More informationPellet Stove Test Manual
Pellet Stove Test Manual Stricter Emission Standards Adopt stricter emission standards than the EPA. 1. Washington: 4.5 grams per hour for non-catalytic and pellet stoves; 2.5 grams per hour for catalytic
More information50A Integrated Furnace Control
Goodman White-Rodgers 0130F00005 PCBBF110 PCBBF123 50A55-743 0130F00005S PCBBF110S PCBBF123S 50A55-289 B1809926 PCBBF112 50T55-289 B1809926S PCBBF112S 50A55-743 Integrated Furnace Control INSTALLATION
More informationElectronic Pellet Burner Controller NPBC-V3C-K NPBC-V4C-K
Electronic Pellet Burner Controller FOR DRY PELLET STOVE NPBC-V3C-K NPBC-V4C-K SOFTWARE VERSION 46/2 CHANGES IN MANUAL FOR THE WORK AND THE SOFTWARE OF THE CONTROLLER User Manual version 3.2 Changes 3.3
More informationPellet burner PV 180a. User manual
Pellet burner User manual Table of content Table of content...2 Description...5 Fuel...7 Installation...7 Boiler requirements...8 Pellet container...11 Burner...12 External auger...20 Electrical connections...21
More informationEBC20. Instructions for fitting, installation and operation. Read and save these instructions!
EBC20 UK Instructions for fitting, installation and operation Read and save these instructions! 2 3002878 EBC20 UK 290415 1. Product information............................................... 4 1.1 Delivery.............................................................
More information200i/KN2, KN4 Firmware Revision Sheet
200i/KN2, KN4 Firmware Revision Sheet Revision 2.9 Special Release 1- November 2013 1. Added an external boiler Failsafe feature. The J6 Analog Output can be used to enable a SSR which can be used to enable
More informationPROFIRE BMS Controller
PF3100 BMS Controller Shutdown Summary August 2017 BMS Controller Shutdown Summary solutions@profireenergy.com Page 1 of 6 PF3100 UV Pilot Card Product Manual 1. Introduction This document is a reference
More informationOperator: Save these instructions for future use!
21M51U-843 Universal Integrated Two-Stage 120Volt Hot Surface Ignition Control Kit INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
More informationPower Flame Incorporated
Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,
More informationCELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL
Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...
More informationDHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override
Date Code - Data rochure oiler Control 265 D 265 10/03 The tekmar oiler Control 265 can control the supply water temperature on up to three modulating boilers based on outdoor temperature or setpoint requirements.
More informationService Manual Models:
KBXII-SER_100161490_2000013413_Rev L Service Manual Models: 400-801 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual
More informationUSER MANUAL 9kW LILLY PELLET STOVE
USER MANUAL 9kW LILLY PELLET STOVE Table of Contents.Overview of Stove Parts... 2.Technical Characteristics... 3 3.Important Information... 4 4.Pellet Specification...5 5.Technology... 6 6.Installation...
More informationINSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
Instruction manual of the control equipment Program version: 2014-01-17 Benekov 04.00 C L I M A T I X 2-1 - CONTENTS 1. Introduction... 3 1.1. TERMINOLOGY AND ABBREVIATIONS... 3 1.2. NUMBER OF HEATING
More informationDryer Master DM510 Commissioning Guide
COMMISSIONING GUIDE Dryer Master DM510 Dryer Moisture Systems Inc. 640 Superior Drive Waterloo, Ontario Phone 519.725.4700 Fax 519.885.4300 USA & Canada Toll Free 1-888-318-0009 E-mail: info@dryermaster.com
More informationUser Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs
User Manual Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs Models 89800-03 and 89800-04 THE STANDARD IN PRECISION MEASUREMENT Table of Contents
More informationInstaller Manual KNX Touchscreen Thermostat
Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY
More informationMETAL INDUSTRY VRANJE
METAL INDUSTRY VRANJE st:radnička n-1 PELLET STOVE LUCA S / LUCA S8 WARNING:This user manual is an integral part of the product.it has to be kept and read carefully. INSTRUCTIONS FOR ASSEMBLY, USE, AND
More informationUSE AND MAINTENANCE. Cm Pelet-set TECHNICAL INSTRUCTIONS. (14-35 kw) For boilers: EKO-CK P (EKO-CK 20-40) EKO-CKB P (EKO-CKB 20-40)
TECHNICAL INSTRUCTIONS USE AND MAINTENANCE Cm Pelet-set (14-35 kw) For boilers: EKO-CK P 20-40 (EKO-CK 20-40) EKO-CKB P 20-40 (EKO-CKB 20-40) TUPS-K-02-2011-E-N-ENG CONTENTS 1. Introduction....... 2. Status
More informationConsiderations for INDUSTRIAL COMBUSTION
August 2016 Volume 23, Number 8 Considerations for INDUSTRIAL COMBUSTION Systems Follow us on: COMBUSTION CONTROLS FOR BOILERS Understand the advantages and disadvantages of combustion control schemes
More informationTECHNICAL AND OPERATIONAL DOCUMENTATION
METAL AND BOILER FACTORY 28-100 Busko-Zdrój, Owczary, ul Przemysłowa 3 Tel No +4841 378 46 19, fax +4841 370 83 10 TECHNICAL AND OPERATIONAL DOCUMENTATION SAS MULTI FLAME BURNER ADAPTED FOR BURNING OF
More informationheat interface units A BOILER WITHOUT A FLAME
A BOILER WITHOUT A FLAME heat interface units Communal Heat Networks A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.
More information- Data Brochure Universal Reset Module 422
- Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in
More informationDigi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input
User Manual 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with
More informationLa Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual
La Marche Manufacturing Company www.lamarchemfg.com Option 46 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain
More informationOperator: Save these instructions for future use!
50A65-843 Universal Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING
More informationTEMPERATURE CONTROL MODULE MODEL R3-TC2
INSTRUCTION MANUAL R3-TC2 TEMPERATURE CONTROL MODULE MODEL R3-TC2 CONTENTS BEFORE USE... 2 POINTS OF CAUTION... 2 COMPONENT IDENTIFICATION... 2 INSTALLATION... 2 EXTERNAL DIMENSIONS unit: mm (inch)...
More informationModel 60200FR Gas Primary Control Data Sheet
Programmable, Microprocessor Based Gas Burner Primary Controls On-Board LCD Screen Easy to Understand Icons for Inputs and Outputs Displays micro-amp Flame reading Display operational information Fault
More informationprestige Control Application Supplement - Type 5 MCBA WARNING
prestige Control Application Supplement - Type 5 MCBA WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions
More informationOPERATING INSTRUCTIONS with safety features
Solid fuel boiler TKK3 with wood pellet burner TERMEC 70-90 KW OPERATING INSTRUCTIONS with safety features Prhova ka bb 22310 imanovci, Srbija Tel/Fax. +381 22 480404 +381 63 259422 oce@termomont.rs www.termomont.rs
More informationRooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422
ºF / º C Rooftop Thermostat Controller Model TRT2422 Description The TRT2422 is a combination controller and thermostat with a built-in scheduler, which is designed for simple and accurate control of single
More informationAqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND
Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating
More informationEBC 12 Modulating Fan Control
Installation & Operating Manual EBC 12 Modulating Fan Control USA CAN Product Information... Chapters 1+2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...
More informationPulse Firing Doubles Capacity and Cuts Fuel Costs
Honeywell Combustion Safety 11699 Brookpark Road Cleveland, Ohio 44130 www.combustionsafety.com Pulse Firing Doubles Capacity and Cuts Fuel Costs Why Pulse Fire? Many industrial manufacturing leaders are
More informationSelf-learning Room Temperature Controller
2 257 Self-learning Room emperature Controller 5 operating modes and menu selection via roller selector REV16 Mains-independent room temperature controller Straightforward, self-explanatory menu selection
More informationWaterFurnace FX10 Application Guide Reversible Chiller
2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 50A55-474 & 50A55-571 Integrated Furnace Controls INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
More information100 step modulated Wood Pellet Boiler
100 step modulated Wood Pellet Boiler EN 303-5 approved by DTI (Danish Technological Institute) Approved for pressure expansion Energy class AA Approved www.kedco.ie Kedco Boiler Manual Version 1.3 Page
More informationmodern heating devices
PELLET AND WOOD-FIRED BOILERS modern heating devices www.hkslazar.pl PELLET BOILERS SMART FIRE thermal efficiency 92,1% ceramic burner The top-class materials used in the burner guarantee long-lasting
More informationPOWER VENTER SYSTEM. Model: PVO-300, PVO-600
POWER VENTER SYSTEM Model: PVO-300, PVO-600 Included is one ETL and cetl listed Power Venter to be used primarily with a single 120VAC controlled oil fired furnace, boiler, or water heater. The PVO may
More information