1 Lindab Compact air handling unit COMPAIR CF Transport, installation, start-up, maintenance and service manual

2 CompAir CF 1 General 1.1 Types of functional sections 1.2 Functional elements 1.3 Housing checking and maintenance 2 Transportation 3 Installation 3.1 Servicing area 3.2 Construction of a foundation 3.3 Mounting of an AHU without foundation 3.4 AHU mounting procedure 3.5 Installation of outdoor units 4 Functional sections 4.1 Fan section Plug fan Electric motor connection Commissioning Safe operation, testing and maintenance 4.2 Heater section with water heater Installation and commissioning Filling and draining procedure transfer medium: warm, hot water Operation Maintenance 4.3 Heater section with electric heater Installation and commissioning Operation Maintenance 4.4 Cooling section with water cooler Installation and commissioning Filling and draining procedure Antifreezing protection of the cooler Maintenance 4.5 Direct evaporator Installation and commissioning Operation Maintenance Outlet Siphon Sizing and installation 4.6 Filter section Number of filter cells per unit cross section horizontal version Number of filter cells per unit cross section vertical version Installation and commissioning Operation Maintenance Counterflow plate recuperator Installation and commissioning Maintenance 5 Controls 5.1 Sensors 5.2 Functional diagram with counterflow heat exchanger Functional description 5.3 Functional element regulation Electrical preheater regulation Heat exchanger regulation Filters Heater frost protection Frost protection of heat exchanger Inlet and outlet fan 5.4 Managing with air handling unit Displays Connection to external units Connection to cloud 6 Use of controller and display 6.1 LED 6.2 Buttons 6.3 Navigating the menus 6.4 Changing parameters 6.5 Running mode 6.6 Temperature 6.7 Deicing exchanger 6.8 Air control 6.9 Time setting 6.10 Extended running 6.11 Holidays 6.12 Other functions 6.13 Indication leds 6.14 Status indication 6.15 Alarms 6.16 Electrical board 6.17 Connecting of display 6.18 Electrical connections splitted units 7 Standard wiring diagrams 8 Symbols We reserve to make changes without prior notice 2

3 CompAir CF 1 General During the transport, installation, commissioning, operation, testing and maintenance of the air handling units, please observe the following: Prior to any work on the unit, please study carefully the instructions in full. The air handling unit may only be installed, checked, commissioned and maintained by trained personnel, who must during the operation observe the statutorily provided engineering standards and local safety regulations applicable at the time of the unit installation. If installing, commissioning and maintenance of functional elements, are produced by manufacturers other than Lindab, the manufacturer s instruction shall be followed. The instructions and electrical diagrams shall be stored and kept available for the person, who operate the unit. The air handling unit shall only be used for the purpose and under the operating conditions specified in this manual and the order confirmation. Any other use deviating from the intended use relieves the manufacturer from any obligation. The unit manufacturer shall not be kept liable in case of failure to observe the information provided in the instructions, during the air handling unit installation, commissioning, testing and maintenance, or in cases of alterations of electrical or mechanical unit components without a prior specific approval by the manufacturer. Any unauthorised intervention to the unit voids the warranty. Addresses of the manufacturer and authorised service Manufacturer: Lindab IMP Klima d.o.o. Godovič 150, 5275 Godovič Slovenia Tel.: +386 (0) imp-klima@lindab.com Authorised service: Lindab IMP Klima d.o.o. Godovič 150, 5275 Godovič Slovenia Tel.: +386 (0) imp-klima@lindab.com 3 We reserve to make changes without prior notice

4 1.1 Types of functional sections Designation VF EW KW KD EE EEV FK FTT RPDG Description Fan section EC radial fan backwards curved without housing Heater section with water heater Cooling section with water cooler Cooling section with DX cooler Heater section with electrical heater Heater section with electrical pre-heater Filter section bag filter Filter section panel filter Recuperation section with counter flow plate recuperator diagonal design 1.2 Functional elements Protection hood fresh air Fresh air filter Preheater By-pass damper drive By-pass damper Electro control cabinet Outlet fan Roof Protection hood outlet Fresh air damper Inlet air flexible connection Outlet flexible connection Outlet air damper Outlet air filter Siphon Drain pan Inlet fan After heater Cooler Feet Counterflow plate recuperator Handle Figure 1 Functional elements CompAir CF with side connections and all optional sections We reserve to make changes without prior notice 4

5 Exhaust Fresh Extract Supply Damper Air filterfresh Flexible connection Air filterextract Outlet fan Inlet fan Cooler Electro control cabinet Heater Drain pan Handle By-pass damper drive Siphon Counterflow plate recuperator Siphon Figure 2 Functional elements of CompAir CF with top connections and all optional sections 1.3 Housing checking and maintenance The checking and maintenance shall be done according to the schedule set out in the following table. Air handling unit housing checking and maintenance schedule Action Inspect for contamination, damage and corrosion of the housing interior Inspect for water formation within the housing Check the hygiene condition Time interval (months) x x According to the hygiene inspection x 5 We reserve to make changes without prior notice

6 2 Transportation Protect each compact section (shipment units) to prevent damaging, during loading, transportation and unloading due to tumbling, sliding or uncontrolled release from the vehicle. Futhermore, to protect staff against any safety and health hazards. Until delivery at the installation site, each compact section of the air handling unit must remain secured with all guards and protective means (diagonal restraints, wooden supports pallets under the structural frame, protective foil etc.). During transportation, any handling of the unit must be carried out by means of the structural frame no pressure on the housing! Any crane hoisting of the compact sections is to be done only by means of the structural frame provided underneath the section. Insert appropriate tubes (thick wall tube of outside diameter ø 48.3 mm and wall thickness of 10 mm) through the circular leads in the structural frame. For lifting, apply steel hoisting ropes or chains; in all cases, apply two spacer supports (Figure 5, detail A). The tubes must be provided with appropriate guards at both ends (Figure 5, detail B). DETAIL A A B DETAIL B Figure 5 Allowed transport Figure 6 Not allowed transport Hoisting without spacer supports (Figure 6) is not allowed, since this might damage the housing. All shipment units are factory protected by: o wooden beams (unit with support base frame) size CompAir 6000 to or o wooden pallets (unit without support base frame) size CompAir 1000 to 4000 When transport is carried out by forklift, always observe the weight and the position of the centre of gravity of the compact shipment unit. Pay special attention not to excert any pressure to the bottom cover of the unit. Forks may only excert pressure to the bottom frame whereby the forks should reach beyond the last part of the section frame Figure wooden beams or palette 2. forks 3. transport unit Figure 5 We reserve to make changes without prior notice 6

7 Always place the shipment unit on even ground. Lift the shipment unit applying the hoisting procedure described in this chapter. No stripping of props or aids is allowed during transportation; in an event of such stripping, the person carried it out must be held fully liable for any adverse consequences. Do not remove the props untill right before the installation on site. Until installation, store the air handling units in a roofed and dry area. 3 Installation 3.1 Servicing area To allow maintenance interventions and operation (e.g. withdrawal of a heat exchanger), always provide a clear area of a minimum width of 1.3 x unit width on the air handling unit servicing side. To facilitate the installation, a clearance area of a minimum width of 0.5 m should be provided on the non-servicing side as well (Figure 6). Figure 6 Servicing area 7 We reserve to make changes without prior notice

8 In case of installation on an elevated platform, provide safe access to the platform and the necessary servicing area on the platform. Also provide appropriate guards for the maintenance technician, in accordance with applicable regulations on safety at work. In the design and construction of electric installation and piping connections to the functional sections, the designer and the constructing contractor must refrain from leading such installations and connections through servicing doors or servicing hatches. Failure to observe this requirement may render the servicing of air handling unit functional sections impracticable. 3.2 Construction of a foundation Mount the air handling unit onto an appropriately high and level concrete or steel foundation (or base). Level out any irregularities in the foundation surface. The minimum foundation height is determined by the elevation of the drain siphon in the section set and shall be 150 mm. Drain siphon Air conditioning unit Foundation Figure 7 Unit on foundation Structural noise insulation In acoustically demanding applications, separate the foundation plate from the rest of the building structure by means of a structural noise insulation layer of appropriate thickness. 3.3 Mounting of an air handling unit without a foundation The foundation may be substituted by the mounting unit onto Lindab type base legs fitted with a structural noise and vibration insulation bolt: - Unit without support base frame size CompAir 1000 to 4000 (Fig. 8) - Unit with support base frame size CompAir 6000 to (Fig.9) Figure 8 We reserve to make changes without prior notice 8

9 Figure Air handling unit mounting procedure Transport the unit to the installation site. Remove protective screening and guards (diagonal restraints, wooden supports pallets under the structural frame, protective foil etc.). Check the evenness and levelling of the foundation. The section front faces must be exactly perpendicular to the foundation and parallel one to another. Apply self-adhesive EPDM rubber sealing tape of 19 x 5 mm cross-section (supplied with the unit) onto the contact front faces (housing frame). Draw the individual sections together by means of the tightening clamps, which you have mounted into the structural frame openings. After having drawn the sections together, join them by means of eccentric clamps (Fig.10) or unit connections fitted on the section frames. The eccentric clamps are fitted inside on the unit, The unit connections (Fig.11) are fitted outside of the unit which have to be connected with M8x40 screw. SEALING TAPE 19x5 ISOWA Figure 10 Figure 11 9 We reserve to make changes without prior notice

10 3.5 Installation of outdoor units Mount the air handling unit on a foundation of adequate height. In specifying the foundation height, take into account all factors that may potentially affect the unit operation: mounting location, depth of snow cover, requirements regarding the quality of suction of outside air, position of intake and exhaust air duct connections, design of heat exchanger piping connections, installation of power cables etc. The foundation height should not be less than 500 mm. Construct the foundation, so as to protect the unit or its components against sliding or tumbling over under wind gusts. Check the wind strength for this purpose. Following the attaching and joining of the air handling unit compact sections, mount the roof sections onto the outer frame ceiling side according to the unit design specification, and seal the roof joints watertight. The roof is delivered mounted on the unit, no mounting on site is necessary. However, seal the section joints watertight and mount ridge as it is shown on Figure 12. Rivet 4,8x10 Ridge Figure 12 Check whether the protection grilles and hoods are properly mounted on the air suction and exhaust openings. If not, install them according to the unit design specification. Seal watertight all vertical joints between compact sections. All the joints between AHU connections and air ducts must be watertight. In the case of installing the unit on the roof or at an elevation, arrange for safe access to the unit and construct a thread-on platform as required. The thread-on platform on the unit servicing side or around the unit should be designed so as to prevent the build-up of snow on the platform in front of the air suction opening, which might result in heavy suction of snow into the unit interior. The platform must be fitted with a safe ascend and descend footpath and should ensure safe operation and maintenance of the unit. We reserve to make changes without prior notice 10

11 4 Functional sections Access to the elements - doors with handles: - Open the cover of the handle (Fig. 13 a,b) - Open the door by pulling the handles (Fig. 14) Figure 13a Figure 13b Figure 14 Access to the elements - panels with blockers: To remove / fasten the blocators use Imbus key size 4 for the blockers (Fig. 15). Figure Fan section Plug fan The fan (Figure 16) is driven by an electric motor directly, by means of a shaft. The electric motor is installed mounted on the fan frame by means of a base plate. Base frame Fan impeller Fan motor Figure We reserve to make changes without prior notice

12 4.1.2 Electric motor connection Prior to commissioning, check the conformity of the connection parameters specified on the electric load nameplates or in the a/c installation control cabinet with the site power mains parameters. The electric motor connection shall be carried out by a qualified technician in accordance with the technical regulations and standards, in accordance with the electric design specifications for the building in which the air handling unit with the fan section is to be installed, and following the electric motor manufacturer's instructions. The electric motor grounding is mandatory. The fan should not be operated with the fan section door open. Motor connection box located on the bottom of fan unit section (Fig. 17) Figure 17 Motor connection Commissioning Before start-up remove any tools and other material from the section, check the tightness of screw joints and the condition of electric connections, mount all covers and wall panels, removed during the intervention into the section, and close the servicing door and secure them against any unauthorised opening by means of the mechanical lock. Check: the fastening of the fan to the frame; fastening of the rotor and its uninterrupted rotation in the housing; correct grounding; correct electric connections and their function; presence of any tools or other materials in the housing; fastening of all covers and doors Safe operation, testing and maintenance Prior to any intervention into the fan section, switch off the repair switch of the fan section being the subject of the check, and lock it in the off state to disconnect the power supply to the drive electric motor. The fan should not be operated with the fan section door open. Proper maintenance is also a guarantee for the safe operation of the unit. Regularly check the tightness of all screw joints, electric connections, grounding and section housing sealing. Observe the electric motor manufacturer's instruction for the motor maintenance. We reserve to make changes without prior notice 12

13 Check monthly: tightness of all screw joints; impeller run; fan electric motor assembly vibration insulators. The checking and maintenance shall be done according to the schedule set out in the following table. Fan section checking and maintenance schedule Action Inspect for contamination, damage and corrosion Cleaning of parts of the fan in contact with air and also the water drain to maintain functioning Check the hygiene condition Time interval (months) x x According to the hygiene inspection x 4.2 Heater section with water heater Water connection pipes are made through the insulated panel. Connections are alyaws threaded. The heater coil temperature sensor is mounted inside the heater coil. The connection cable for heater coil temperature sensor has to be connected in a connection box inside the basic unit. Water connection - out Heater coil temperature sensor Connection cable for heater coil temperature sensor Water connection - in Figure 18 Water heater unit 13 We reserve to make changes without prior notice

14 4.2.1 Installation and commissioning Depending on the working medium, the heater connection piping and the collector may reach high surface temperatures (over 70 C); therefore, avoid contact with these surfaces when working close to the heater, wear personal protection means (leather gloves), or stop the air handling unit and shut off the supply of hot water and let the heater and the piping cool down prior to any work. When installing the water heater, make sure to properly connect the piping installation (Figure 19) and observe the following: Provide the transfer medium / air counterflow configuration. Connect the piping and fittings so as to allow unobstructed access to and drawing out of the heat exchanger for revision and maintenance works, without obstructing access to the adjacent sections. When tightening threaded joints, apply counterforce with an appropriate tool (pipe wrench padded), to avoid damaging the heater piping circuit. For easier dismounting, connect the heater by means of two pairs of flanges. Do not weld the connection. Arrange the two piping connections to the water heater observing the air flow direction, so that the air inflow to the heater is closer to the return pipe, to ensure medium/air counterflow. This applies for either horizontal or vertical air flow configuration. The pump may be installed in either the horizontal or in the vertical piping leg, provided that the pump shaft is horizontal. The control/distribution or mixing valve may be installed in either the supply or return pipe; the distance between the supply and return pipe and the distance between the control valve and the bypass pipe should not be less than 500 mm. Upstream the heater intake, install a dirt trap in the supply pipe to protect the control valve and the circulation pump. In the supply pipe downstream the connection stop valve, at the heater intake and outlet, install thermometers. At the lowest point of the piping installation, provide drain cocks for the transfer medium, to allow the heat exchanger draining. At the highest point of the piping system, provide a bleeding device to ensure uninterrupted flow of the medium through the heater (as a rule, the heaters are supplied already fitted with the bleeding valve and drain cock at the highest / lowest point of the collector / distribution pipe). Clean the piping system of filings and other debris. Figure 19 Water heater installation We reserve to make changes without prior notice 14

15 Prior to the commissioning, check: the tightness of different screw joints; tighten them as required; proper operation of the heater automatic anti-freezing protection prior to the filling of the heater with the circulation medium; tightness of piping connections; proper operation of the automatic heating medium supply shut-off function, designed to protect the electric motor against overheating, at the heating medium temperature exceeding 70 C Filling and draining procedure transfer medium: warm, hot water Filling: partly open the transfer medium supply valve; let the fin register to heat up or cool down uniformly to avoid thermal stresses; fully open the transfer medium supply valve; bleed the system to ensure its achieving the full rated thermal capacity; switch the fan on. Draining: close the medium supply valve; slowly open the drain cock until the heat exchanger is depressurised; then fully open both the bleeding valve and the drain cock Operation In the event of the air temperature falling below the set value, the thermostat and the automatic controller shall carry out the following operations: switch the fan off; close the fresh air control louvres; fully open the heating medium valve; switch on the circulation pump, if not already on Maintenance Prior to any intervention in the water heater, shut the entire air handling unit down by switching off the main switch on the electric control cabinet. Lock the switch in the off position. Prior to the startup, clean the device s interior and firmly attach and seal all air joints (covers, duct flanges, guards etc.). To ensure proper functioning, regularly carry out the following operations: Check the tightness of all water connections and air joint tightness. Check the operation of the bleeding valve. In an event of disturbed medium flow through the exchanger, or presence of air in the circuit, bleed the piping system. Check the proper operation of the heater automatic anti-freezing protection. Periodically, check the proper operation of the heating medium supply automatic shut-off upon the unit shutdown. To prevent the electric motor overheating, check the fan prolonged operation (at least 3 minutes). following the unit shutdown. 15 We reserve to make changes without prior notice

16 Regularly check any dust build-up on the heater fins. Dust or scale build-up on the fins result in a reduced heat exchanger capacity. Periodically approximately every 500 hours of operation clean the fins. Clean the fins by blowing compressed air in the direction opposite to the air flow direction. If this cleaning method is not sufficient, dismount the heater and wash it with low pressure water or steam. Do not use high pressure water or steam, to avoid deforming the aluminium fins. When washing with water, the water pressure shall not exceed 15 bar, and the water jet shall be strictly perpendicular to the fin surfaces. Water jet at an angle will damage the fins. This applies in particular for the fins along the edges, which are more sensitive. Never use any hard object for cleaning. The checking and maintenance shall be done according to the schedule set out in the following table. Water heater section checking and maintenance schedule Action Inspect for contamination, damage and corrosion Check the hygiene condition Time interval (months) x According to the hygiene inspection x 4.3 Heater section with electric heater Heating unit with electric heater consists of a unit housing, electrical air heaters and cabinets with the associated control elements (Figure 20). Electrical heater housing Junction box Heaters elements Figure 20 Electrical heater Installation and commissioning Connect electric cables through cable sleeves in the junction box wall; make sure that their laying does not obstruct the servicing of the adjacent functional sections of the air handling unit. Air flow velocity across the heater shall not be less than 1,5 m/s; the air flow shall be evenly distributed across the entire cross section. The electric air heater shall start only with the fan already running and an adequate air flow volume established. Upon the heater switching off, the fan shall continue to operate for another at least 3 minutes to cool down the heater coils. We reserve to make changes without prior notice 16

17 The electric air heater is not of a water-tight construction; hence the electric heater section shall not be installed so as to be exposed to water or steam Operation Connection of the electric heater to the mains shall be done by a properly qualified electrician, in conformance with the applicable regulations Heaters are connected to a 3 400V or 2x400V power supply During operation, their surface of heating elements reaches temperatures up to ~ 350 C Maintenance Prior to any intervention in the electrical air heater, shut the entire air handling unit down by switching off the main switch on the electric control cabinet. Lock the switch in the off position. Prior to the startup, clean the device interior and firmly tighten all electric connections, seal all air joints and attach guards (covers, duct flanges, protection grilles etc.). Once a month, check: tightness of electric connections and joints; operation of the air flow rate monitoring device; operation of the relays for the early switching on of the fan and the delayed switching off of the electric heater; proper and secure attachment of the guards (servicing cover, connection box cover, protection grilles etc.). 4.4 Cooling section with water cooler Water connection pipes are made through the insulated panel. Connections are always threaded. Stoppers Water cooler cover Water cooler Handle Drain pan Siphon Figure 21 Water cooler unit 17 We reserve to make changes without prior notice

18 4.4.1 Installation and commissioning Make sure an adequately sized siphon is installed in the condensate collection pan drain line. The method of connecting the piping to the heating circuit depends on the piping diameter, as follows: When installing the water cooler, make sure to properly connect the piping installation and observe the following: Provide the transfer medium / air counterflow configuration. Connect the piping and fittings so as to allow unobstructed access to and drawing out of the heat exchanger for revision and maintenance works, without obstructing access to the adjacent sections. When tightening threaded joints, apply counterforce with an appropriate tool (pipe wrench padded), to avoid damaging the cooler piping circuit. For easier dismounting, connect the water cooler by means of two pairs of flanges. Do not weld the connection. Arrange the two piping connections to the water cooler observing the air flow direction, so that the air inflow to the cooler is closer to the return pipe, to ensure medium / air counterflow. This applies for either horizontal or vertical air flow configuration. The pump may be installed in either the horizontal or in the vertical piping leg, provided that the pump shaft is horizontal. The distribution or mixing control valve, if specified, may be installed in either the supply or the return line. The distance between the supply and return pipe and the distance between the control valve and the bypass pipe should not be less than 500 mm. Upstream the cooler intake, install a dirt trap in the supply pipe to protect the control valve and the circulation pump. In the supply pipe downstream the connection stop valve, at the cooler intake and outlet, install thermometers. Install the transfer medium drain cocks at the lowest point of the piping installation. This enables the draining of the heat exchanger. At the highest point of the piping system, install a bleeding device to ensure uninterrupted fluid flow through the cooler. As a rule, the water cooper is delivered with the bleeding / draining valves already installed at the highest / lowest point of the distribution / collection pipe. Clean the piping system of filings and other debris. An example of proper connection is illustrated in Figure 22. Figure 22 Water cooler installation We reserve to make changes without prior notice 18

19 Prior to the commissioning, check: the tightness of different screw joints; tighten them as required; proper operation of the cooler automatic anti-freezing protection prior to the filling of the cooler with the circulation medium; tightness of piping connections; cleanliness of the piping system and the installation of the dirt trap Filling and draining procedure: Filling: fully open the transfer medium supply valve; bleed the system to ensure its achieving the full rated cooling capacity; switch the fan on. Draining: close the transfer medium supply valve; slowly open the drain cock until the cooler is depressurised; then fully open both the bleeding valve and the drain cock Operation Protection of the cooler against freezing a) Cooling circuit filled with water: anti-freezing protection by means of the anti-freezing protection function of the heater section which shall be installed upstream the cooler section; anti-freezing protection is provided by fully draining the system before the cold (winter) period of non-operation. b) Cooling circuit filled with glycol and water mixture: anti-freezing protection is provided with an appropriate concentration of the glycol and water mixture. In handling glycol, observe the glycol filling safety sheet. In an event of a prolonged power blackout, the unit shutdown or interruption of the cooling medium supply, drain the cooler to avoid its freezing. To further eliminate the risk of freezing, blow the pipe register with compressed air after draining Maintenance The checking and maintenance shall be done according to the schedule set out in the following table. Water cooler section checking and maintenance schedule Action Inspect for contamination, damage and corrosion Inspect wet coolers, condensate tanks and demisters for contamination, corrosion and functioning Functionally test the siphon CIean wet cooler, demister and condensate tank Check the hygiene condition 19 We reserve to make changes without prior notice x Time interval (months) x x x According to the hygiene inspection x

20 4.5 Direct evaporator DX may be divided into two or more cooling circuits and cools the air by means of a freon based cooling medium R 407c or R 410a) Installation and commissioning When installing a DX section, make sure to properly connect the piping installation and observe the following: Connect the piping and fittings so as to allow unobstructed access to and drawing out of the cooler for revision and maintenance works, without obstructing access to the adjacent sections. When tightening threaded joints, apply counterforce with an appropriate tool (pipe wrench padded), to avoid damaging the DX piping circuit. Arrange the two piping connections to the DX observing the air flow direction, so that the air inflow to the DX is closer to the return pipe, to ensure medium / air counterflow. This applies for either horizontal or vertical air flow configuration. The most common joining method consists of soldering; connection by means of fast joints is even more preferable, since this method saves operational costs associated with blade cleaning. The evaporator outlet pipe should be thermally insulated with the insulation fitted with vapour stopping according to applicable standards. Install the thermostat expansion valve following the manufacturer's instructions, to a horizontal piping leg as close as practicable to the DX, upstream the pressure equalisation equipment and at a proper angle according to the pipe thickness. The sensor shall be insulated to avoid the ambient air interference with the measurement. The same applies to the pressure equalisation valve sensor. Application of external pressure equalisation valves is recommended, to avoid the interference of the pressure drop across the evaporator. The distribution head should be mounted vertically; if this is not practicable, make sure to install Venturi head. Since the evaporator is not fitted with blade defrosting, arrange the electric connection so as to prevent the compressor from operating with the DX fan not in operation. If larger inlet air temperature variations (higher share of outside air) are expected during the DX operation, i.e. the DX operation at loads lower than the rated load, we recommend the installation of a cooling capacity controller with a hot DX bypass line to prevent blade freezing. Clean the piping system of filings and other debris. In the connection of a DX to a compressor-condenser section, the required accessories include, in addition to a thermal expansion valve: a drying cartridge; a solenoid valve (high-low pressure boundary); inspection opening; collection pan, in particular in cases of long piping installations. In the laying of pipelines, pay attention to oil return and other freon flow associated phenomena. An example of proper connection is illustrated in Figure 23. We reserve to make changes without prior notice 20

21 distribution head 2. thermostat expansion valve 3. temperature sensor 4. TEV capillary 5. pressure equalisation line 6. moisture indicator 7. solenoid valve Figure drying cartridge 9. collection pan Rotolock valve 10. collection pan The cooling system connection and filling with the cooling medium may only be carried out by a qualified person. Apply copper pipes for the connection, the pipes having been cleaned, dried, purged with dry nitrogen and sealed on both ends. Observe the following points during the installation: the maximum allowable distance of the DX to the other cooling circuit part is 25 m; the condenser may be located maximum 2 m below the compressor; the outlet piping layout should be along the shortest practicable route, with the minimum number of bends (bend radius R > 3.5 times pipe diameter). In selecting the combination, pay attention to the compatibility of the compressor, the DX and other cooling circuit components. Prior to the commissioning, check: the conformance of the electric connection with the electrical switching diagram the condensate outlet the successful completion of the freon line testing, drying, connection to an air cooled condenser and filling with cooling medium proper setting of the cooling circuit protection elements, such as the high/low pressure protection switch. The same applies to the condensation pressure control switch During the commissioning, check: tightness of the soldered joints adequate quantity of freon (no droplets in the inspection opening) dryness of the equipment (inspection opening colour indicator; dry moist; following the manufacturer's instructions) achievement of the proper evaporation and condensation pressures During the commissioning, make sure that the sump heater heats freon enough to ensure the evaporation of any accumulated liquid freon (continuous operation during the unit shutdown or switching on preceding the unit startup). 21 We reserve to make changes without prior notice

22 DX filling Prior to the filling, vacuum the system. The vacuuming should continue until the piping system is dry and a proper vacuum is established (see instructions for the filling of cooling systems). Normally, the system is filled through the compressor suction connection larger compressors are fitted with special connectors. Having opened the freon cylinder valve to admit the gas to the system, start the compressor and continue the filling until the specified evaporation pressure is achieved and no more bubbles are seen in the inspection opening. DX evacuation Shut off the compressor-condensation section isolation valves and exhaust freon from the DX section through a valve fitted specifically for this purpose (employing an environment compliant exhaust equipment according to the Montreal protocol) Operation Observe the instructions for safe operation, starting and maintenance of cooling equipment, which are included in these instructions Maintenance Prior to any intervention in the DX, shut the entire air handling unit down by switching off the main switch on the electric control cabinet. Lock the switch in the off position. Prior to the startup, clean the device interior, firmly attach and seal all air and water joints (covers, duct flanges, guards etc.) and install the drain siphon and connect it to the sewage system. To ensure proper functioning of the DX, regularly carry out the following operations: check the condition of the soldered joints periodically, check the inspection opening for bubbles and humidity check the cooling circuit protection elements mechanical and electrical in a case of a prolonged shutdown, check the operation of the compressor sump heater check the DX fan operation regularly check dust build-up on the DX fins. Dust or scale build-up on the fins results in a reduced heat exchanger capacity. Periodically approximately every 500 hours of operation clean the fins. Clean the fins by blowing compressed air in the direction opposite to the air flow direction. If this cleaning method is not sufficient, dismount the heat exchanger and wash it with water or low pressure steam. Do not use high pressure water or steam, to avoid deformation of aluminium fins. When washing with water, the water pressure shall not exceed 15 bar, and the water jet shall be strictly perpendicular to the fin surfaces. Water jet at an angle will damage the fins. This applies in particular for the fins along the edges, which are more sensitive. Never use any hard object for cleaning. The checking and maintenance shall be done according to the schedule set out in the following table. Direct evaporator section checking and maintenance schedule Action Inspect for contamination, damage and corrosion Inspect wet direct evaporator, condensate tanks and demisters for contamination, corrosion and functioning Time interval (months) x x According to the hygiene inspection We reserve to make changes without prior notice 22

23 Functionally test the siphon Ciean wet direct evaporator, demister and condensate tank Check the hygiene condition x x x Outlet siphon Sizing and installation Difference between the pressure inside the section and the atmospheric pressure p (Pa): p = pn pz pn = pressure in the section pz = atmospheric pressure The following cases are possible: p < 0 negative pressure in the unit p = 0 pressure in the section equal to the atmospheric pressure p > 0 positive pressure in the unit An undersized siphon leads to jerky outflow of air and water. If the available height difference from the drain pipe connection point to the machine room floor is less than the required siphon height, lead the condensate outlet deep into an outlet funnel. Do not connect the negative pressure and positive pressure siphon drain pipe directly to the sewage system piping. The outflow of condensate from the siphon to the sewage piping shall be free, through an open funnel. Never connect a positive pressure siphon and a negative pressure siphon to a common drain pipe. Mount the siphon on the section outside. Outflow piping should be laid at a minimum 2% inclination in the outflow direction. Figure 24 Negative pressure siphon The measure "A" corresponds to the total pressure drop in the section, specified in the section nameplate or in the fan nameplate. Divide the nameplate readout value (in Pa) by 10 to obtain the measure "A" in mm. C* Required foundation height for proper operation of the siphon. Prior to the startup, make sure to flood the siphon with water. Flood it every beginning of the summer season, prior to the startup of the air handling unit. 23 We reserve to make changes without prior notice

24 maks. 285 Figure 25 Negative pressure siphon with ball The negative pressure siphon (Figure 25) does not require flooding with water, since the siphon automatically fills up with condensate as this starts to accumulate. Figure 26 Positive pressure siphon The measure "A" corresponds to the total pressure drop in the section, specified in the section nameplate or in the fan nameplate. Divide the nameplate readout value (in Pa) by 10 to obtain the measure "A" in mm. C* Required foundation height for proper operation of the siphon. Prior to the startup, make sure to flood the siphon with water. Flood it every beginning of the summer season, prior to the startup of the air handling unit. Figure 27 Positive pressure siphon The positive pressure siphon Lindab (Figure 27) does require flooding with water. 4.6 Filter section Types of filters: Panel filter: F7 on supply and M5 (optional: F7) on exhaust air; length 96 mm Bag lilter: F7 on supply and M5 (optional: F7) on exhaust air; length 300 mm We reserve to make changes without prior notice 24

25 filter guide sealing tape lock section Figure 28 filter unit Number of filter cells per unit cross section, by unit sizes for horizontal version Air handling unit size Filter cell dimensions x x x x Number of filter cells per unit cross section, by unit sizes for vertical version Filter cell dimensions Airhandling unit size x x x We reserve to make changes without prior notice

26 4.6.3 Installation and commissioning If not already installed, insert the filters into the structural frame, according to the following procedure: insert filters into the structural frame push the filters by means of the lock section against the guide with the sealing tape applied make sure that sealing tape is applied to the L section against which the door will lean, and apply the tape onto the door as well if required remove any tools and other solid particles from the section close the servicing door check the connection of pressure gauge pipes to the pressure measurement outlets and connect as required Operation The filter shall keep its efficiency throughout its service lifetime. To ensure its functionality regarding the hygiene of the handled air, periodically check filters in each filter stage for: pressure drop operating hours visual appearance (check any cracks in the filter material, leakage between the filter and its frame) In a case of any contamination, cracks in the filter material or leakage between the filter and its frame, replace the filter regardless of the actual pressure drop or lifetime stage Maintenance Replace the filter in the following cases: the allowable pressure drop has been reached the service lifetime has been reached the filter performance is inadequate, in mechanical or hygienic terms during the installation or modification of the air handling unit, the filter has been contaminated the replacement is ordered by the hygiene inspection All the filters of a filter stage or filter section shall be replaced at the same time. Replacing of only one filter of a filter stage is allowable only in a case of damage and provided that the time since the last replacement does not exceed 6 months. Prior to installing new filters, always check the complete, uniform and air-tight mounting of the sealing tape on the sealing seat between the filter and its frame. Make sure the filter is not damaged upon installation in the filter frame. Only use filters declared conformant with the SIST EN 779 standard by their manufacturers. Handle the contaminated filters in compliance with applicable environment protection regulations. With outdoor installation air handling units, there is a risk of the filter stage (prefilter) clogging with snow in extreme climate conditions. There is also a risk of filters freezing. In such an event, immediately clean the filters of snow or replace. Connect the pressure gauge to the measurement outlets upstream and downstream of the filter. The filter change procedure is as follows: open the servicing door loosen all the lock section(s) (Fig.29) withdraw the contaminated filter (Fig.30) clean the section housing as required We reserve to make changes without prior notice 26

27 check the condition of the sealing tape on the sealing seat and repair or replace it as required always install fresh and undamaged filters only push all the lock section(s) on the filters again close the servicing door Figure 29 Figure 30 The checking and maintenance shall be done according to the schedule set out in the following table. Procedure for bag filter installation is the same as it is described above. Note: type of filter must be defined at unit selection. Later it is not possible to replace type of filter (bag with the cassete or inversely). Figure 31 Bag filter Filter section checking and maintenance schedule Action Inspect for impermissible contamination and damage (Ieaks) Replace the defective air filter if the most recent filter stage replacement took place less than 6 months ago, otherwise replace the complete filter stage Check the differential pressure Filters Check the hygiene condition Time interval (months) x x x According to the hygiene inspection x 27 We reserve to make changes without prior notice

28 4.7 Counterflow plate recuperator Motor drive Electro control cabinet By-pass damper Plate recuperator Condensate collection and draining pan By-pass Figure 32 Counterflow plate recuperator unit Installation and commissioning Prior to the commissioning, check the tightness of different screw joints and tighten them as required. Also check the fitting and linking of the control louvre to the electric motor drive and its operation. Make sure an adequately sized siphon is installed in the condensate collection pan drain line Maintenance Regularly clean the plate recuperator. In a case of fouling with dry dust, the insert can be cleaned without dismounting, by blowing it with compressed air with a pressure up to 10 bar maximum through the servicing openings; always wear personal protection equipment during such an operation. If fouled with greasy or sticky debris, the insert shall be withdrawn from the recuperator section housing and cleaned by means of a hot water jet (temperature up to 90 o C, pressure up to 6 bar) with appropriate cleaning detergent added. Since the insert filler is made of very thin aluminium foil, be careful not to damage the insert face surface during dismounting. The sequence of dismounting an insert from the section housing is as follows Figure 33: remove the servicing covers at backside remove the partition sections on the backside side, by unscrewing the fixing screws remove the rubber seal unscrew the top guide section fixing screws, loosen the side guide section screws and remove the top guide section draw the insert out of the section housing after cleaning, install the inserts back in the section in the opposite order We reserve to make changes without prior notice 28

29 Figure 33 Removal of counterflow plate recuperator The checking and maintenance shall be done according to the schedule set out in the following table. Functionally test the siphon Check the hygiene condition Plate recuperator section checking and maintenance schedule Action Inspect for contamination, damage and corrosion Check the seal between the incoming air and outgoing air Inspect the condensate tank and demister for contamination, corrosion and functioning x Time interval (months) x x x According to the hygiene inspection x 29 We reserve to make changes without prior notice

30 5 Controls 5.1 Sensors Humidity sensor for measuring outlet/room humidity Figure 34 Sensor for measuring outlet/room CO2. It also measures room temperature. Differential pressure switches for fresh and outlet filters. Figure 35 Pressure sensors unit with two differential pressure sensors. In CompAir it is used for measuring pressure in duct and also for measuring air flow of inlet and outlet fans. Communication with controller is via EXOline communication. Figure 36 Tube connector for measuring duct pressure. User has to connect the attached tube to connector. The other end has to be connected to outlet air duct. The same procedure is required on inlet side. Inside Compair, tubes must be connected to inside connectors. Figure 37 Figure 38 We reserve to make changes without prior notice 30

31 Temperature sensor for inlet air temperature. It has to be connected in the connection box located behind supply fan (green connector Fig.40). Figure 39 Figure 40 Hygrostat switch Figure 41 Actuator for the dampers: Figure We reserve to make changes without prior notice

32 5.2 Functional diagram with counterflow heat exchanger Valve size depends on unit size. Figure Functional description The duct temperature sensor measures air temperature in the room and the controller N1 compares this value to the desired value. In the case of a downward deviation (heating) followed by control output signals, the controller starts to open the bypass dampers of the plate recuperator, then opens the heater valve and turns on the water heater pump. The pump runs for few minutes after the valve has been closed. In case of upward deviation (cooling) the plate heat exchanger is activated (the recuperator bypass damper opens, depending on the ambient temperature and outside temperature) and the cooling valve opens. The duct temperature sensor measures the value of the supply air temperature and the controller N1 compares this value to the desired value. In case that the measured supply temperature is lower or higher than the lower or upper limit values set in the controller N1, the controller starts to regulate the supply air temperature (limiting temperature between set Tmin - 16 C and T max - 40 C). The duct temperature sensor is used for measuring of the outside temperature. 5.3 Functional element regulation Electrical preheater regulation Electrical preheater is used to preheat outside air to specific value (setpoint). Setpoint (it can be set from 5 C to 30 C) can be set in controller, then it is compared with sensor value (sensor measures temperature behind preheater). If temperature is too low, electrical preheater is turned ON and works until setpoint is reached. Safety thermostat is used to prevent damage from overheating. First point of safety thermostat is set to 80 C, second on 110 C Heat exchanger regulation The outside temperature is measured with NTC sensor. Exhaust/outlet temperature is measured with NTC sensor. Both sensors send signal to controller, where both values are compared. Thus the temperature value of outside and outlet air is estimated. In dependance of this estimation, output signal is lead to the actuator of plate heat exchanger. Maximum of disposable energy (of outside or outlet air) is used. In case of heat energy additional signal is lead to electric preheater and/or water heater (if electric/water heaters are installed into the unit). We reserve to make changes without prior notice 32

33 5.3.3 Filters Filters are used as protection against dirt particles inside of the air handling unit, ensuring clean air. Filters are controlled by pressure switches, additionally, the alarm»check filters«is shown every 1000 working hours. In case of filter replacement the direction of air flow through filters must be considered. Air handling unit must be turned off at the time of filter replacement! Heater frost protection The frost protection sensor measures the temperature after water heater. If at any point the temperature of water falls below the set value (5 C), the controller reports an error, the heater valve is fully opened, heater pump is turned on, both fans are turned off, dampers are closed. When the error is fixed, the air conditioning switches on automatically and the error is automatically reset Frost protection of plate exchanger Frost protection sensor is designed to measure the temperature value behind recuperator. If the temperature falls below set value, the controller will close recuperator dampers and open by-pass dampers so that the cold outside air will go directly into the room and warmer inside air will defrost recuperator dampers Inlet and outlet fan EC fans are driven by a reference signal (0-10V), which is sent from the controller. The controller has two speed options. Fans can also be driven by CO2 sensor (mounted in duct or room) or by pressure sensors (constant pressure or airflow in duct). Figure 44 Temperature sensor NTC060HP00 Figure 45 Pressure sensor Figure 46 Duct CO2 sensor Figure 47 Graphic display 33 We reserve to make changes without prior notice

34 5.4 Managing with air handling unit The main switch on the front side of electro cabinet must always be in ON position, because only in that case you may be assured that the controller and all safety functions work correctly. FOR SERVICE ON ANY PART OF AIR HANDLING UNIT SUITABLE FUSE MUST BE TURNED OFF (check wiring diagram)! Displays The controller is delivered together with a display as standard, which allows easy monitoring and changing of all parameters of the compact air handling unit. Figure 48 Controller Figure 49 Standard display Figure 50 Swipe&Touch Display The Swipe&Touch display can be used as a remote display and is delivered in case of ordering of the Advanced controls version. It's used for local monitoring and control of the main functions of the unit Connection to external units Connection is possible to external units such as DX coolers, humidifiers or electrical heaters. The air handling unit can control such external units with analog and digital signals Connection to cloud If advanced option is chosen, the cloud solution is possible the documentation is made separately. We reserve to make changes without prior notice 34

35 Figure 51 6 Use of controller and display 6.1 LED There are two LEDs on the front: The alarm LED marked with the symbol. The write enable LED marked with the symbol. The four LEDs placed next to the upper terminal strip will be described later. 6.2 Buttons Figure 52 There are seven buttons: four arrow buttons which will be called UP, DOWN, RIGHT and LEFT. The menus in the Regula are organized in a horizontal tree structure. The UP/DOWN buttons are used to move between menus at the present menu level. The RIGHT/LEFT buttons are used to move between menu levels. When changing parameters the UP/DOWN buttons are used to increase/decrease the value of the parameter and the RIGHT/LEFT buttons to move between digits within the parameter. The OK button is used to confirm the choice of a parameter setting. The C button is used to abort an initiated parameter change and restore the original value. The ALARM button, marked with a red button top, is used to access the alarm list. 35 We reserve to make changes without prior notice

36 6.3 Navigating the menus The choice of access level/user access determines which menus are shown in the menu system. The start display, the display normally shown, is at the root of the menu tree. Running mode Temperature Air control Humidity control Time settings Access rights Pressing DOWN will move you through the menu choices at this, the lowest level. UP will move you back through the choices. Which menus are shown depends on which access level you are using. Using Normal access, the access which normally does not require logging on, only a few basic menus are shown. In the menu "Running mode", you can view and set the unit s running mode, view selected control functions and view the alarm events. In the menus "Temperature", "Air control" and "Humidity control", you can view actual values and setpoint values. Setpoints can only be changed if you have Operator or Admin access. In "Time settings", the time, date and set running times are shown. Values can only be changed if you have Operator or Admin access. Without logging on to Operator or System level, you are only authorised to change the unit s running mode and acknowledge alarms. With Operator access, you can access more information and change other operation parameters like setpoints and time functions. With Admin access, you have full access to the complete menu system and can change all parameters. To enter a higher menu level, use UP or DOWN to place the display marker opposite the menu you wish to access and press RIGHT. At each level there may be several new menus through which you may move using the UP and DOWN buttons. Sometimes there are further submenus linked to a menu or menu item. This is indicated by an arrow symbol at the right-hand edge of the display. To choose one, use RIGHT again. To back down to a lower menu level, use LEFT. 6.4 Changing parameters In some menus there are parameters that can be set. This is A quick blinking (2 times/s) indicates that the parameter can be changed using the present user access. A slower blinking (1 time/s) indicates that a higher user access is required to change the parameter. To change a parameter, first press the OK button. If you need higher authority than you have to change the parameter, a log on menu will be displayed, see chapter eight below. Otherwise, a cursor will appear at the first settable value. If you wish to change the value, do so by pressing the UP and DOWN buttons. In numbers containing several digits you can move between the We reserve to make changes without prior notice 36

37 digits using the LEFT / RIGHT- buttons. When the desired value is displayed press OK. If there are further settable values displayed the cursor will automatically move to the next one. To pass a value without changing it, press OK. To abort a change and return to the initial setting, press and hold the C-button until the cursor disappears. 6.5 Running mode Running mode Temperature Time settings Access rights Collected here are a number of menus showing running mode, selected functions, alarm events and status of inputs and outputs. Running mode Selected functions Alarm events Input/Output Running mode, unit Running mode Auto The unit s running mode can be changed without logging on. Running time SAF: 14.6 h Running time EAF: 14.6 h Selected functions Control function Cascade room ctrl Fan control Frequency manual Shows the present configuration. These are read-only menus. No changes can be made here. Heating: Water Exchanger: Plate exc Cooling: Dx 37 We reserve to make changes without prior notice

38 Free cool active: No Support control Active: No CO2/VOC active Never Fire damper funct Not active Operation when alarm Stopped Frost protection Active Cooling recovery Yes External setpoint Not active Alarm events 24 Nov 14:32 Malf. SAF Acknowledged B Alarm log which contains the 40 latest alarm events. The most recent event is listed first. The alarm log can only be used for viewing the alarm history Inputs/outputs AI DI UI AO DO This is a read-only menu block showing the present values for all configured inputs and outputs. If correction factors have been applied to input values, the corrected values will be shown. This is a read-only menu. No changes can be made here. 6.6 Temperature Running mode Temperature Time settings Access rights Here you can view all actual and setpoint values for temperature control. The menu is visible to all users, regardless of log on level. However, to make changes you need at least Operator authority. The below menus are available, providing the corresponding input has been activated. Setpoints are available with a separate value for reduced speed. This is achieved using a temperature offset when the unit runs in We reserve to make changes without prior notice 38

39 reduced speed. The temperature is available in either Celsius ( C) or Fahrenheit ( F) Setpoint Control mode: outdoor temperature-dependent supply or extract air control. Extract air temp Actual: 21.0 C Setp: 22.0 C -> In control mode six, the setpoint is used when cascade connected extract air control is active. Submenu for setting the min. and max. limitation temperatures for the supply air. If cascade control max/min supply setp Max: 40.0 C Min: 16.0 C Frost protection temperature Frost protection Actual: 30.9 C 6.7 Deicing exchanger Deicing exchanger Actual: 11.2 C Setp: -3.0 C Hysteresis: 1.0 C Heat exchanger efficiency monitoring Efficiency exch Actual: 93% Output exchanger Actual: 100% 6.8 Air control Frequency control manual SAF Output: 75% 39 We reserve to make changes without prior notice

40 6.8.1 Manual frequency control saf (there are corresponding menus for eaf) Frequency control manual SAF Output 1/1: 75% Output 1/2: 50% Submenu "Setpoint" Outdoor comp. outp. -20 C = 0 % 10 C = 0 % Act comp: 0 % Submenu "Outdoor compensation" Comp sens:roomtemp1 15 C = 0 % 20 C = 0 % 25 C = 0 % Submenu "Extra compensation curve" Controller output comp if cooling 0 at HCOUT= 0% 100 at HCOUT= 0% Submenu Controller output compensation if cooling Controller output comp if heating 0 at HCOUT= 0% 100 at HCOUT= 0% Controller output compensation Not active Compensation only when: 1/1-speed: No defrosting: No Submenu Controller output compensation if heating The compensation follows the current control quantity, in this case %. The function should not be used when fan setpoint is set to %, as the fans will then risk stopping in some modes. Submenu Controller output compensation Submenu Compensation only when 6.9 Time settings Running mode Temperature Time settings Access rights General Time/Date Timer normal speed Timer reduced speed Extended running Timer output1 Timer output2 Timer output3 Timer output4 Timer output5 Holidays Regula has a year-base clock function. This means that a weekschedule with holiday periods for a full year can be set. The clock has an automatic summertime/wintertime change-over. Individual schedules for each week-day plus a separate holiday setting. Up to 24 individual holiday periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday schedules take precedence over other schedules. Each day has up to two individual running periods. For two-speed fans and pressure controlled fans there are daily individual We reserve to make changes without prior notice 40

41 schedules for normal speed and reduced speed, each with up to two running periods. Up to 5 digital outputs can be used as timer controlled outputs. Each with individual week- schedules with two activation periods per day. These outputs can be used to control lighting, doorlocks etc Time / date Time: 18:21 Date: Weekday: Wednesday This menu shows and permits the setting of time and date. Time is shown in 24-hour format. Date is shown in the format YY:MM:DD Timer normal speed Normal speed Monday Per 1: 07:00 16:00 Per 2: 00:00-00:00 Normal speed Monday Per 1: 07:00 16:00 Per 2: 22:00-24:00 Normal speed Tuesday Per 1: 00:00 09:00 Per 2: 00:00-00:00 There are eight separate setting menus, one for each weekday and one extra for holidays. Holiday schedules take precedence over other schedules. For 24 hour running, set a period to 0:00 24:00. To inactivate a period, set the time to 00:00 00:00. If both periods of a day are set to 0:00 0:00, the unit will not run at 1/1-speed that day. If you want to run the unit from one day to another, e.g. from Mon 22:00 to Tue 09:00, the desired running time for both days must be entered Timer reduced speed These settings will be ignored if single speed fans are configured. Should periods for normal speed and periods for reduced speed overlap, normal speed takes precedence. There are eight separate setting menus, one for each weekday and one extra for holidays. Holiday schedules take precedence over other schedules. For 24 hour running, set a period to 00:00 24:00. To disable a period, set it to 00:00 00:00. If both periods of a day are set to 00:00 00:00, the unit will not run at "Reduced speed" that day. 41 We reserve to make changes without prior notice

42 6.10 Extended running Extended running 60 min Time in ext running 0 min Digital inputs can be used to force the unit to start although the timer says the running mode should be Off. For 2-speed fans and pressure/flow controlled fans, inputs for normal speed and reduced speed can normally be used. The unit will run for the set time. If the running time is set to zero the unit will only run as long as the digital input is closed Holidays Holidays (mm:dd) 1: : : Up to 24 separate holiday periods for a full year can be set. A holiday period can be any number of consecutive days from The dates are in the format: MM:DD. When the present date falls within a holiday period, the scheduler will use the settings for the weekday Holiday Other functions Alarm handling Sensor error supply air temp 24 Aug 10:43 Class:B Reset If an alarm condition occurs, the red Alarm LED on the front panel of units with display or the Alarm LED on a connected display unit will start flashing. The LED will continue to flash as long as there are unacknowledged alarms. Alarms are logged in the alarm list. The list shows type of alarm, date and time for the alarm and the alarm class (A, B or C alarm). To access the alarm list, press the alarm button, the front panel button with the red button-top, on the front of the Regula / E3-DSP. If there are multiple alarms, this is indicated by up/down arrow symbols at the right-hand edge of the display. Use the UP and DOWN buttons to access the other alarms. At the left end of the bottom display line the alarm status is shown. For active, unacknowledged alarms the space is blank. For alarms that have reset the text Reset is shown. Acknowledged, still active or blocked alarms are indicated by Acknowledged or Blocked. Alarms are acknowledged by pressing the OK button. You are then given the choice of acknowledging the alarm or blocking the alarm. Acknowledged alarms will remain on the alarm list until the alarm input signal resets. The LED is then lit. Blocked alarms remain on the alarm list until the alarm has reset and the block has been removed. New alarms of the same type will not be activated as long as the block remains. Since blocking alarms can be potentially hazardous, you need a master user Class A and B alarms will activate alarm output(s) if these have been configured. Class C alarms are removed from the alarm list when the alarm input resets even if the alarm has not been acknowledged. We reserve to make changes without prior notice 42

43 6.13 Indication leds Status indication can be found in the upper left corner of the master controller. For controllers with display, the alarm indication and change mode LEDs are located in the keypad area Status indication Designation Color Description Tx Green Port 1, Transmitting Rx Green Port 1, Receiving Serv ( LON models) Yellow Service LED LON, commissioning LAN ( W models) Yellow/Green Green: Connected to other network equipment Blinking green: Network traffic Blinking yellow: For identifying P/B (Power/Battery) Green/Red Power on/battery error Controllers with built-in display Red Yellow Alarm indication Change mode 43 We reserve to make changes without prior notice

44 6.15 Alarms Alarm list The alarm text and priority columns show the factory set values. Alarm text Prio Description 1 Malfunction supply air fan B Malfunction supply air fan 2 Malfunction extract air fan B Malfunction extract air fan 3 Malfunction P1 heater B Malfunction pump, heating circuit 4 Malfunction P1 cooler B Malfunction pump, cooling circuit 5 Malfunction P1 exchanger B Malfunction pump, liquid connected exchanger 6 Filter alarm 1 B Filter guard pressure switch or analogue filter switch activated. The analogue filter switch may be flow dependent. 7 Flow guard B Flow switch activated 8 External frost guard A External frost protection thermostat activated 9 Deicing pressure guard - Exchanger de-icing pressure switch activated 10 Fire alarm A Fire alarm activated 11 External switch C "External switch" activated 12 External alarm B External alarm activated 13 Supply air control error B Supply air temp deviates too much from the setpoint for too long. 14 Humidity control error - The room humidity deviates too much from the setpoint. 15 High supply air temp B Supply air temp too high 16 Low supply air temp B Supply air temp too low 17 Supply air temp max limit - Maximum limiting of supply air temp active 18 Supply air temp min limit - Minimum limiting of supply air temp active 19 High room temp B Room temp too high during room temp control 20 Low room temp B Room temp too low during room temp control 21 High extract air temp B High extract air temp during extract air control 22 Low extract air temp B Low extract air temp during extract air control 23 Electric heating is overheated A Heater high temperature limit switch activated 24 Frost risk B Frost protection function is overriding the control of the heater output 25 Low frost guard temp A Frost protection temperature below frost limit value 26 Low efficiency B Heat exchanger efficiency below limit value 27 Sensor error outdoor temp B Malfunction in connected sensor We reserve to make changes without prior notice 44

45 Alarm text Prio Description 28 Analogue deicing - Exchanger de-icing activated by de-icing sensor 29 Rotation sentinel exchanger B Exchanger rotation sentinel alarm activated 30 Malfunction fire damper B Fire damper exercise test failed 31 Supply air fan control error - Supply air pressure deviates too much from the set point for too long. 32 Extract air fan control error - Extract air pressure deviates too much from the set point for too long. 33 Supply air fan external operation 34 Extract air fan external operation C C SAF run-signal received when unit is stopped EAF run-signal received when unit is stopped 35 Ventilation manual mode C The unit is in manual mode 36 Manual supply air control C Supply air temp controller in manual control 37 Manual supply air fan mode C Supply air fan in manual control 38 Manual supply air fan freq control C The SAF is in manual mode 39 Manual extract air fan mode C Extract air fan in manual control 40 Manual extract air fan freq control C The EAF is in manual mode 41 Manual heater control C The heater is in manual mode 42 Manual exchanger control C Heat exchanger output in manual control 43 Manual cooler control C Cooling output in manual control 44 Manual P1 heater C Heating circulation pump in manual control 45 Manual P1 exchanger C Exchanger circulation pump in manual control 46 Manual P1 cooler C Cooling circulation pump in manual control 47 Manual fire damper C Fire dampers in manual control 48 Internal battery error A Internal battery needs replacing 49 Sensor error supply air temp B Malfunction in connected sensor 50 Sensor error extract air temp B Malfunction in connected sensor 51 Sensor error room temp 1 B Malfunction in connected sensor 52 Sensor error room temp 2 B Malfunction in connected sensor 53 Sensor error exhaust air B Malfunction in connected sensor 54 temp Sensor error extra sensor 1 B Sensor error Extra sensor 1 55 Sensor error SAF pressure B Malfunction in connected sensor 56 Sensor error EAF pressure B Malfunction in connected sensor 57 Sensor error deicing temp B Malfunction in connected sensor 58 Sensor error frost protection temp 45 We reserve to make changes without prior notice B Malfunction in connected sensor 59 Sensor error CO2 B Malfunction in connected sensor 60 Sensor error humidity room B Malfunction in connected sensor 61 Sensor error humidity duct B Malfunction in connected sensor

46 Alarm text Prio Description 62 Sensor error extra unit temp B Malfunction in connected sensor 63 Sensor error external control SAF 64 Sensor error external control EAF B B Malfunction in connected sensor Malfunction in connected sensor 65 Sensor error SAF pressure 2 B Malfunction in connected sensor 66 Sensor error outdoor B Malfunction in connected sensor 67 humidity Sensor error intake temp B Malfunction in connected sensor 68 Sensor error extra sensor 2 B Malfunction in connected sensor 69 Sensor error extra sensor 3 B Malfunction in connected sensor 70 Sensor error extra sensor 4 B Malfunction in connected sensor 71 Sensor error extra sensor 5 B Malfunction in connected sensor 72 Sensor error extra SAF pressure 73 Sensor error extra EAF pressure B B Malfunction in connected sensor Malfunction in connected sensor 74 Sensor error backup 8 B Malfunction in connected sensor 75 Sensor error backup 9 B Malfunction in connected sensor 76 Sensor error backup 10 B Malfunction in connected sensor 77 Alarm frequency converter SAF 78 Alarm frequency converter EAF 79 Communication error frequency SAF 80 Alarm frequency converter EAF 81 Communication error expansion unit 82 1 Communication error expansion unit 83 2 Warning frequency converter SAF 84 Warning frequency converter EAF A A C C C C C C Malfunction of frequency converter SAF Malfunction of frequency converter EAF Communication error Vacon NXL/Lenze SMV/Omron V1000/Emerson Communication error Vacon NXL/Lenze SMV/Omron V1000/Emerson Communication problem with connected expansion unit Communication problem with connected expansion unit Alarm from frequency converter via Modbus communication Alarm from frequency converter via Modbus communication 85 Output in manual mode C Analogue or digital output in manual mode 86 Time for service C Time for service 87 Y4 extra sequence control manual 88 Restart blocked after power- on 89 Y5 extra sequence control manual C B C Y4-Extra sequence in manual control Restart blocked due to earlier power failure Y5 Extra sequence in manual control 90 Filter guard 2 B Filter guard pressure switch or analogue filter switch activated. The analogue filter switch may be flow dependent. 91 High temp extra sensor 1 - High temperature extra sensor 1 We reserve to make changes without prior notice 46

47 92 Low temp extra sensor 1 - Low temperature extra sensor 1 93 High temp extra sensor 2 - High temperature extra sensor 2 Alarm text Prio Description 94 Low temp extra sensor 2 - Low temperature extra sensor 2 95 High temp extra sensor 3 - High temperature extra sensor 3 96 Low temp extra sensor 3 - Low temperature extra sensor 3 97 High temp extra sensor 4 - High temperature extra sensor 4 98 Low temp extra sensor 4 - Low temperature extra sensor 4 99 High temp extra sensor 5 - High temperature extra sensor Low temp extra sensor 5 - Low temperature extra sensor Extra alarm 1 - Extra alarm 1 on digital input 102 Extra alarm 2 - Extra alarm 2 on digital input 103 Extra alarm 3 - Extra alarm 3 on digital input 104 Extra alarm 4 - Extra alarm 4 on digital input 105 Extra alarm 5 - Extra alarm 5 on digital input 106 Extra alarm 6 - Extra alarm 6 on digital input 107 Extra alarm 7 - Extra alarm 7 on digital input 108 Extra alarm 8 - Extra alarm 8 on digital input 109 Extra alarm 9 - Extra alarm 9 on digital input 110 Extra alarm 10 - Extra alarm 10 on digital input 111 Extra unit in manual mode - Extra controller in manual mode 112 Malfunction motor control 1 - Malfunction in motor control Malfunction motor control 2 - Malfunction in motor control Motor control 1 external operation 115 Motor control 2 external operation - External operation of motor control 1 - External operation of motor control 2 47 We reserve to make changes without prior notice

48 6.16 Electrical board Electrical board is mounted (integrated) on the top of the unit (for unit sizes ) or mounted on the front side (for unit sizes ). The electrical board can be drawn out, but not completely. 230V/AC to 24V/AC transformer Fuses for: - heating pump, - supply and extract fan, - power supply for Lindab Regula controller Lindab Regula controller Figure 53 ECC cabinet There is a sticker HIGH VOLTAGE on the front of electrical board so when drawing it out, be aware of high voltage! Board should be drawn out only 15 cm max, so that the controller can be seen and parameters can be changed. Figure 54 Warning sticker We reserve to make changes without prior notice 48

49 6.17 Connecting of display The screen on the display is a copy of the screen on the controller and is used to facilitate the managing of air handling unit since the controller itself is usually hidden and sometimes hard to access Electrical connection in splitted units If the air handling unit consists of 3 parts it is necessary for proper operation to connect connectors which are connected to motors, sensors, etc.. before unit assembling. Connect the connectors to each other with the same numbers as shown in Figure 55. Figure 55 Connector connection in splitted units Connected connectors must be inserted in a connection box, as shown in Figure 56. Figure 56 Connectors in connection box 49 We reserve to make changes without prior notice

50 Connection box with contacts for: - main power supply, - heater pump power supply, - heating valve, - cooling valve, - fire central, - BMS connection Figure 57 Connection box Figure 58 Connection box - open We reserve to make changes without prior notice 50

lindab we simplify construction Lindab Compact air handling unit compair CF Transport, installation, start-up, maintenance and service

lindab we simplify construction Lindab Compact air handling unit compair CF Transport, installation, start-up, maintenance and service lindab we simplify construction Lindab Compact air handling unit compair CF Transport, installation, start-up, maintenance and service Transport, installation, start-up, maintenance and service manual

More information

lindab we simplify construction Lindab Modular air handling units Transport and assembly manual

lindab we simplify construction Lindab Modular air handling units Transport and assembly manual lindab we simplify construction Lindab Modular air handling units Transport and assembly manual Transport and assembly manual 1 General... 3 2 Warnings & Tips... 3 3 Transportation... 3 3.1 Truck loading

More information

lindab we simplify construction AIR HANDLING UNITS INSTRUCTIONS FOR: TRANSPORT INSTALLATION COMMISSIONING OPERATION TESTING MAINTENANCE

lindab we simplify construction AIR HANDLING UNITS INSTRUCTIONS FOR: TRANSPORT INSTALLATION COMMISSIONING OPERATION TESTING MAINTENANCE AIR HANDLING UNITS INSTRUCTIONS FOR: TRANSPORT INSTALLATION COMMISSIONING OPERATION TESTING MAINTENANCE 2 Table of contents 1 General... 4 2 Addresses of the manufacturer and authorised services... 5 2.1

More information

lindab we simplify construction Lindab Modular air handling units Connection, start-up and commissioning manual

lindab we simplify construction Lindab Modular air handling units Connection, start-up and commissioning manual Lindab Modular air handling units Connection, start-up and commissioning manual Connection, start-up and commissioning manual 1 General... 3 2 Warnings and Tips... 3 3 Functional sections... 3 3.1 Fan

More information

lindab we simplify construction Lindab Modular air handling units Service and maintenance manual

lindab we simplify construction Lindab Modular air handling units Service and maintenance manual Lindab Modular air handling units Service and maintenance manual Service and maintenance manual General... 3 2 Warnings and Tips... 3 3 Functional sections... 3 3.1 Fan section... 3 3.2 Heater section

More information

lindab we simplify construction Lindab Compact air handling unit CompAir CF Transport, installation, start-up, maintenance and service

lindab we simplify construction Lindab Compact air handling unit CompAir CF Transport, installation, start-up, maintenance and service lindab we simplify construction Lindab Compact air handling unit CompAir CF Transport, installation, start-up, maintenance and service Transport, installation, start-up, maintenance and service manual

More information

39 HQ Air Handling Units AiroVision

39 HQ Air Handling Units AiroVision VDI 6022 39 HQ Air Handling Units AiroVision Assembly/Installation, Commissioning, Maintenance Manual Type tested Production monitored AHU N : 08.02.251 Range: 39HQ DIN 1946-4 EN 13053 2 Code No: B.8.1.3i

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute

More information

DUCT COOLERS KWK KFK OPERATION MANUAL. KWK_KFK_v2(4)_EN.indd :35:29

DUCT COOLERS KWK KFK OPERATION MANUAL. KWK_KFK_v2(4)_EN.indd :35:29 DUCT COOLERS KWK KFK EN OPERATION MANUAL KWK_KFK_v2(4)_EN.indd 1 13.06.2016 13:35:29 CONTENTS 3 Introduction 3 General 3 Safety rules 3 Transportation and storage regulations 3 Manufacturer s warranty

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

LONGONI ENGINEERING SRL

LONGONI ENGINEERING SRL INDEX 1.1 Classification of heat exchanger and components 1.1.2 Type of heat exchanger and components 1.2 Purpose and scope of the manual 1.3 General instruction 1.4 Warning installation 1.5 Notes for

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater SUPPLY UNITS Series VENTS PA E Series VENTS PA W A13 control panel A13 control panel Suspended air supply units with the air capacity up to 3350 m 3 /h in the sound- and heat-insulated casing with the

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with Intellidrain Condensate Drain Trap. Operation & Maintenance Manual

MDX. Non-Cycling Refrigerated Compressed Air Dryers with Intellidrain Condensate Drain Trap. Operation & Maintenance Manual MDX Non-Cycling Refrigerated Compressed Air Dryers with Intellidrain Condensate Drain Trap Operation & Maintenance Manual MODELS MDX 1500 1800 2400 3000 TABLE OF CONTENTS 1.0 GENERAL 2 1.1 How to use this

More information

FUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP

FUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP OPERATION INSTRUCTIONS MANUAL DUCTED FAN COILS UNIT FUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP 1 CONTENTS 1. GENERAL... 3 2. INSTALLATION... 4 3. AIR CONNECTIONS... 5 4. WATER CONNECTIONS...

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

COMPACT AIR HANDLING UNIT. CompAir RW. Technical Brochure

COMPACT AIR HANDLING UNIT. CompAir RW. Technical Brochure COMPACT AIR HANDLING UNIT CompAir RW Technical Brochure Version 1.4 January 2013 INDEX: 1 GENERAL... 4 2 COMPAIR RW 2000... 8 2.1 Technical specification... 8 2.2 External static pressure/air volume diagram...

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250 MDX Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap Operation & Maintenance Manual MDX MODELS 18 THRU 250 TABLE OF CONTENTS HOW TO USE THIS MANUAL 2 SYMBOLS 2 WARRANTY

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

Drop-In Refrigeration System

Drop-In Refrigeration System Drop-In Refrigeration System Original Instructions Installation, Operation and Maintenance Manual This manual is updated as new information and models are released. Visit our website for the latest manual.

More information

CENTRIFUGAL AIR CONDENSERS

CENTRIFUGAL AIR CONDENSERS OPERATING INSTRUCTIONS INSTALLATION COMMISSIONING OPERATING MAINTENANCE (must be given to the end user in order to complete the operating manual during the equipment service life) CAC and SIROCCO CENTRIFUGAL

More information

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual DOMEKT ReGO 400VE(W)-B Series Air Handling Units EN Content Safety Requirements...3 Transportation...3 Brief Description of the Unit...5 Installation...6 Maintenance...11 Technical Information......13

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

CPC PRODUCT DESCRIPTION

CPC PRODUCT DESCRIPTION CPC 40 60 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPC 40-60 compressor is a quiet, complete and readyfor-use unit for the production of compressed air in industrial applications. OVERVIEW The CHICAGO

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

ACT Cartridge Dust Collector

ACT Cartridge Dust Collector IOM-101-1 ACT Cartridge Dust Collector Installation and Operation Manual ACT Dust Collectors CAUTION! Accidents happen, be careful and always follow all local and federal regulations! Fires and explosions

More information

MJC Cartridge Filter Unit Operation & Maintenance

MJC Cartridge Filter Unit Operation & Maintenance 1 of 19 Hodge Clemco Ltd MJC Cartridge Filter Unit Operation & Maintenance Owner s Manual Date of Issue: 19.07.04 TSSM536.1a Hodge Clemco Ltd Orgreave Drive Sheffield S13 9NR Tel: 0114 254 8811 Fax: 0114

More information

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment

More information

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT 90% EFFICIENCY HIGHEST EFFICIENCY AIR HANDLING UNIT Packaged energy recovery solutions for Green Buildings Integrated Accumulator, controls and DX Cooling System CLEAN AIR SINCE 1963 Euroclima is a company

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX MDX Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Operation & Maintenance Manual MODELS MDX 800 1000 1200 TABLE OF CONTENTS HOW TO USE THIS MANUAL 2 SYMBOLS 2 WARRANTY 2 1.0

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

InterSeptor Centrifugal Separators Operating & Maintenance Manual

InterSeptor Centrifugal Separators Operating & Maintenance Manual General Information: This manual was prepared to assist in the installation, operation, and maintenance of PEP ICS centrifugal separator systems. For immediate response to questions not covered in this

More information

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV ClearFire Economizer Model ECF Integral or External Addendum to manuals 750-295 CFH and 750-269 CFV CB-8466 08/2011 1-GENERAL The Model ECF economizer is a stainless steel coil tube arrangement using

More information

Functional sections of air handling units

Functional sections of air handling units 02 Fan section Heating section Humidification section Cooling section Filter section Heat recovery section 36 Control system Air Handling Units Fan, heating, humidification, cooling, air regulating, filter,

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

NEWGATE TECHNOLOGIES, INC.

NEWGATE TECHNOLOGIES, INC. www W.newgatetechnologies.com NEWGATE TECHNOLOGIES, INC. Installation & Operations Manual SYNERGY Series High Inlet Temperature Refrigerated Air Dryers Models SYNERGY 025 ~ SYNERGY 125 Includes Safety

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

Installer manual GreenMaster-HP

Installer manual GreenMaster-HP Installer manual GreenMaster-HP Transport and installation Ventilation unit IHB EN 1747-2 8017172 2 GreenMaster-HP Transport and installation Introduction Here you can read about how best to handle the

More information

Danfoss Air Heating Surfaces

Danfoss Air Heating Surfaces MAKING MODERN LIVING POSSIBLE Installation Guide www.heating.danfoss.com Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English

More information

Chemical Motor Pump Unit BN

Chemical Motor Pump Unit BN Operating & Maintenance Instructions BW 5 02 01 / 1 The operating instructions of the centrifugal pump and the accessories should be located close to the pump. These instructions should be read carefully

More information

Niles Steel Tank Hot Water Generator Installation and Operation Manual

Niles Steel Tank Hot Water Generator Installation and Operation Manual Niles Steel Tank Hot Water Generator Installation and Operation Manual Contents: Contents 1 Hazard definitions 1 1. General Information.... 2 Availability... 3 Optional Control Packages... 5 2. Installation....

More information

HEATING AND VENTILATION

HEATING AND VENTILATION SECTION 14-102.04 14-102.04/ 1 2007OC19 DESCRIPTION The heating, ventilation and air conditioning (HVAC) system is designed to optimize passenger comfort. The system regulates interior vehicle atmosphere,

More information

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

VERSO Air Handling Units

VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P air handling units equipped with recuperation system

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

CENTRAL AIR CONDITIONER SPLIT SYSTEM

CENTRAL AIR CONDITIONER SPLIT SYSTEM CENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES: DS INSTALLATION INSTRUCTIONS INDEX GENERAL... 2 UNIT LOCATION CRITERIA... 2 DIMENSIONAL DRAWINGS... 3 INDOOR UNIT INSTALLATION... 5

More information

CoolTeg Plus XC40. AC-TXC Direct expansion Air-conditioning unit with integrated compressor

CoolTeg Plus XC40. AC-TXC Direct expansion Air-conditioning unit with integrated compressor CoolTeg Plus XC40 AC-TXC Direct expansion Air-conditioning unit with integrated compressor Application CoolTeg Plus XC40 is a revolutionary air-conditioning unit specifically designed for installation

More information

Swedish design and manufacture since 1967

Swedish design and manufacture since 1967 Swedish design and manufacture since 167 PVP MA20-14 rev.2 Manual User manual Copyright 2017 Pahlén AB, Box 728, SE-14 27 Upplands Väsby, Sweden Tel. +46 8 54 110 50, Fax +46 8 50 868 80, e-mail: info@pahlen.se,

More information

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS 6720 Columbus Road Mississauga, Ontario Canada, L5T 2G1 Tel: (905) 670 3595 Fax: (905) 670 3592 www.temspec.com Vertical Stack Fan Coil Units Models: TVA, TVE, TVS INSTALLATION, OPERATION AND MAINTENANCE

More information

INVERTER SPLIT - TYPE

INVERTER SPLIT - TYPE INVERTER SPLIT - TYPE ISSUE No 2 DATE 04/09/08 P/No 2020323A2868 CONTENTS SAFETY PRECAUTIONS Warning 2 Operating temperature 2 BEFORE INSTALLATION Tools needed for installation 3 Items required for installing

More information

Ventilation and air conditioning QUALITY FOR LIFE. Refrigerating systems and heat pumps. Operating manual

Ventilation and air conditioning QUALITY FOR LIFE. Refrigerating systems and heat pumps. Operating manual Ventilation and air conditioning QUALITY FOR LIFE GB Refrigerating systems and heat pumps Operating manual Refrigerating systems and heat pumps 3052967 I 07/2010 Refrigerating systems and heat pumps Table

More information

Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE. Regenerative Type Heatless Desiccant Dryer

Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE. Regenerative Type Heatless Desiccant Dryer Adsorption dryer Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE Regenerative Type Heatless Desiccant Dryer WE REDEFINE COMPRESSED AIR TREATMENT SYSTEMS 5/232 KNG Pudur road, Somayampalayam

More information

Installation and operating instructions. DK energy storage and DK energy buffer

Installation and operating instructions. DK energy storage and DK energy buffer Installation and operating instructions DK energy storage and DK energy buffer Edition: 08-2015 1 Preliminary note With this DK energy storage / DK energy buffer you purchased a DK quality product. The

More information

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300 USER S MANUAL Heat Recovery Ventilator Vents Brig HRV 200 Vents Brig HRV 300 2 Brig HRV 200 (300) CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key... 4 Basic unit dimensions...

More information

STARBOX - CONDENSER UNITS

STARBOX - CONDENSER UNITS EN STARBOX - CONDENSER UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Table of Contents 1. General Information 1 2. Handling and Storage.. 1 3. Installation. 1 4. Electrical Connections.. 4

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

T-Series Air Conditioner T20 Model

T-Series Air Conditioner T20 Model INSTRUCTION MANUAL T-Series Air Conditioner T20 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

C5.1. VERSO Pro S / R / P / RHP / PCF. EN Installation and Maintenance Service Manual

C5.1. VERSO Pro S / R / P / RHP / PCF. EN Installation and Maintenance Service Manual C5.1 VERSO Pro S / R / P / RHP / PCF EN Installation and Maintenance Service Manual Content 1. VERSO AIR HANDLING UNITS... 5 1.1. VERSO Air Handling Units marking... 6 1.2. VERSO-S Air Supply Units...

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance

More information

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original) Montageanleitung (Original) (Translation of the original) DE MA_ 1.0 06/2014 Taperlock Clamping-bush system _0 _1 Fixed hub Inlet nozzle with IMV 1. Revision index Revision Date MA_ 1.0 06/2014 2. Safety

More information

CPVS PRODUCT DESCRIPTION

CPVS PRODUCT DESCRIPTION CPVS 20 30 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPVS 20-30 compressor is a quiet, complete and ready-for-use unit for the production of compressed air for light and medium industrial applications.

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR DRY PAK PACKAGED COMPRESSED AIR TREATMENT SYSTEM MODEL: DPP-150 WARNING

INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR DRY PAK PACKAGED COMPRESSED AIR TREATMENT SYSTEM MODEL: DPP-150 WARNING January 207 80-572 Rev - 2950 Mechanic Street Lake City, PA 6423 USA Phone: -800-840-9906 Fax: 84-774-0778 Email: info@vanairsystems.com www.vanairsystems.com INSTALLATION, OPERATION & MAINTENANCE MANUAL

More information

Air heater/cooler in combination with ground source heat pump

Air heater/cooler in combination with ground source heat pump Swegon CASA Air heater/cooler in combination with ground source heat pump Installation, operation and maintenance instructions for design engineers, installation engineers and service personnel SDHWM_c_EN

More information

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier OM001 Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier These operating and maintenance instructions are for standard semi-storage calorifiers (vessels fitted with

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Climaster ZerAx. Eco-designkrav. Climaster ZerAx type ZCN-M guide GB

Climaster ZerAx. Eco-designkrav. Climaster ZerAx type ZCN-M guide GB Climaster ZerAx Climaster ZerAx type ZCN-M guide 924784-0 GB Eco-designkrav Important This document is made available as it is. Novenco reserves the right to make changes without prior notice due to further

More information

Atlas Copco Refrigerant compressed air dryers

Atlas Copco Refrigerant compressed air dryers Atlas Copco Refrigerant compressed air dryers FXe 1, FXe 2, FXe 3, FXe 4, FXe 5 Instruction book Atlas Copco Refrigerant compressed air dryers FXe 1, FXe 2, FXe 3, FXe 4, FXe 5 From following serial No.

More information

AZN ATEX INSTALLATION AND MAINTENANCE

AZN ATEX INSTALLATION AND MAINTENANCE ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature

More information

Series VENTS VUT R WH ЕС

Series VENTS VUT R WH ЕС AIR HANDLING UNITS WITH HEAT RECOVERY Series VENTS EH ЕС Series VENTS WH ЕС Air handling units with the air capacity up to 1500 m 3 /h in soundand heat-insulated casing with integrated electric heater.

More information

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA 18- AH39D1-4 Cased Aluminum "Convertible" Coils 2/4TXCA018BC3HCA 2/4TXCA024BC3HCA 2/4TXCB025BC3HCA 2/4TXCB031BC3HCA 4TXCB032BC3HCA 2/4TXCB036BC3HCA ALL phases of this installation must comply with NATIONAL,

More information

MANUAL. Dryspell INSTALLATION OPERATION MAINTENANCE. Regenerative Type Heatless Desiccant Dryer

MANUAL. Dryspell INSTALLATION OPERATION MAINTENANCE. Regenerative Type Heatless Desiccant Dryer MANUAL INSTALLATION OPERATION MAINTENANCE Regenerative Type Heatless Desiccant Dryer Dryspell Contents 1. Introduction 2 1.1 Design 1.2 Relevant Units 1.3 Statement of Conformity 1.4 Description 1.5 Adsorbant

More information

Air handling units Compair. Technical Catalogue

Air handling units Compair. Technical Catalogue Air handling units Compair Technical Catalogue Overview CompAir CF, CompAir RW, CompAir CF FREE CompAir CompAir is a family of air handling units in seven sizes, designed for volume air flow from 500 up

More information

CHILLER. Operator s & Installation Manual

CHILLER. Operator s & Installation Manual CHILLER MODEL: CFF-500 Operator s & Installation Manual Release Date: November 3, 1996 Publication Number: 90667 Revision Date: May 10, 2010 Revision: E Visit the IMI Cornelius web site at www.cornelius.com

More information

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort Application guide FLATAIR - FLCK/FLHK Providing indoor climate comfort MSL60E-0701 12-2006 Congratulations you have made a wise choice and we feel sure that it will meet your expectation INDEX CONTENTS

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

HEAT RECOVERY VENTILATOR

HEAT RECOVERY VENTILATOR HEAT RECOVERY VENTILATOR HRV H 00 ERV H 00 HRV H 300 ERV H 300 EN OPERATION MANUAL HRV /ERV H 00(300) www.blaubergventilatoren.de CONTENTS Application... Delivery set...3 Unit designation key...3 Basic

More information

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS 6720 Columbus Road Mississauga, Ontario Canada, L5T 2G1 Tel: (905) 670 3595 Fax: (905) 670 3592 Web: www.temspec.com TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS INSTALLATION AND MAINTENANCE

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

We simplify construction

We simplify construction lindab compact air handling units We simplify construction At Lindab we are driven by a strong desire to continuously generate improvements and to simplify construction. We do that by developing products

More information

FDT11 FDT15 FDT18. DUCTED TYPE SPLIT SYSTEMS (3 Phase, Fixed Speed)

FDT11 FDT15 FDT18. DUCTED TYPE SPLIT SYSTEMS (3 Phase, Fixed Speed) OPERA TION & I NSTALLAT I O N FDT11 FDT15 FDT18 MANUAL DUCTED TYPE SPLIT SYSTEMS (3 Phase, Fixed Speed) Read this operating & installation instruction carefully and keep it for future reference DUCTED

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information