McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)
|
|
- Walter Lee
- 5 years ago
- Views:
Transcription
1 Point Map December 1, 2004 Systems Integration McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV) Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller Point Map, Application Point Type Description Range/Units a,b,c 1 LAO Address 2 LAO Application LAI Active Setpoint F 4 LAI Actual Capacity % 5 LAI Capacity Limit % 6 LAO Capacity Limit Setpoint % 7 LDO Chiller Enabled Disable/Enable 8 LDI Chiller Limited No/Yes 9 LDI Chiller Remote/Local Remote/Local 10 LAO Chiller Mode 1=Heat 3=Cool 5=Pre-cool 11=Ice 11 LDI Chiller On/Off Off/On 12 LAI Chiller Status 1=Off 2=Start 3=Run 4=Pre-shutdown 5=Service 13 LAI Compressor Discharge Temperature F 14 LAI Compressor Percent RLA % RLA 15 LAI Compressor Run Hours hr 16 LAO Compressor Select 17 LAI Compressor Starts starts 18 LAI Compressor Suction Line Temperature F 19 LAI Condenser Entering Water Temperature F Siemens Building Technologies, Inc. Page 1 of 10
2 Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller Point Map, Application (continued) Point Type Description Range/Units a,b,c 20 LAI Condenser Leaving Water Temperature F 21 LDI Condenser Flow Switch Status No Flow/Flow 22 LAI Condenser Pump Run Hours hr 23 LAI Condenser Refrigerant Pressure psi 24 LAI Condenser Saturated Refrigerant Temperature F 25 LDI Condenser Water Pump Status Off/On 26 LAO Cool Setpoint 10 to 120 F to LAI Evaporator Entering Water Temperature F 28 LAI Evaporator Leaving Water Temperature F 29 LDI Evaporator Flow Switch Status No Flow/Flow 30 LAI Compressor Evaporator Leaving Water Temperature F 31 LAI Evaporator Pump Run Hours hr 32 LAI Evaporator Refrigerant Pressure psi 33 LAI Evaporator Saturated Refrigerant Temperature F 34 LDI Evaporator Water Pump Status Off/On 35 LAI Heat Recovery Entering Water Temperature F 36 LAI Heat Recovery Leaving Water Temperature F 37 LAO Heat Setpoint 50 to 120 F 10.0 to LAO Ice Setpoint 15 to 35 F -9.4 to LAI Liquid Line Refrigerant Temperature F 41 LAI Oil Feed Pressure psi 42 LAI Oil Feed Temperature F 43 LAI Oil Sump Pressure psi 44 LAI Oil Sump Temperature F 46 LAO Pump Select 47 LAI Warning Alarms SeeTable2 Page 2 of 10 Siemens Building Technologies, Inc.
3 Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller Point Map, Application (continued) Point Type Description Range/Units a,b,c 48 LAI Problem Alarms SeeTable2 49 LAI Fault Alarms SeeTable2 50 LDO Clear Alarm No/Yes a Values noted for LDIs and LDOs are in the following format: OFF text/on text. b This column indicates the value/range or engineering units or both if known. c The default English value is not italicized. An italicized entry indicates an SI value. Alarm Messages (Points 47 through 49) Use Table 2 to interpret the Warning (Point 47), Problem (Point 48), and Fault (Point 49) alarm messages. Values 1 through 4 are of a Warning class and apply to Point 47. Values 5 through 50 are of a Problem class and apply to Point 48. Values 52 through 224 are of a Fault class and apply to Point 49. Table 2. Chiller Alarm Values (Points 47, 48, and 49). 1 W NO ACTION Condenser Entering Water Temperature Sensor Failure 2 W NO ACTION Evaporator Entering Water Temperature Sensor Failure 3 W NO ACTION Liquid Line Refrigerant Temperature Sensor Failure 4 W NO ACTION (STOP if Heat) Condenser Leaving Water Temperature Sensor Failure 5 P RESTART DELAYED Power Loss While Running 6 P RESTART DELAYED Power Loss While Running 7 P RESTART DELAYED Power Loss While Running 8 P RESTART DELAYED Power Loss While Running 10 P START INHIBITED Ambient Temperature Low 11 P INHIBIT LOAD Condenser Pressure High 12 P INHIBIT LOAD Condenser Pressure High 13 P INHIBIT LOAD Condenser Pressure High 14 P INHIBIT LOAD Condenser Pressure High 15 P UNLOAD Condenser Pressure High 16 P UNLOAD Condenser Pressure High 17 P UNLOAD Condenser Pressure High 18 P UNLOAD Condenser Pressure High 19 P UNLOAD Condenser Pressure High 20 P CONDENSER PUMP ON Condenser Water Freeze Protection 21 P CONDENSER PUMP ON Condenser Water Freeze Protection Siemens Building Technologies, Inc. Page 3 of 10
4 24 P PUMP START ATTEMPTED Condenser Pump Failure 25 P PUMP START ATTEMPTED Condenser Pump Failure 26 P LOAD Discharge Temperature High 27 P LOAD Discharge Temperature High 30 P NO EWT RESET Entering Evaporator Temperature Sensor Failure 31 P INHIBIT LOAD Evaporator Pressure Low 32 P INHIBIT LOAD Evaporator Pressure Low 33 P INHIBIT LOAD Evaporator Pressure Low 34 P INHIBIT LOAD Evaporator Pressure Low 35 P INHIBIT LOAD Evaporator Pressure Low 36 P UNLOAD Evaporator Pressure Low 37 P UNLOAD Evaporator Pressure Low 38 P UNLOAD Evaporator Pressure Low 38 P UNLOAD Evaporator Pressure Low 38 P UNLOAD Evaporator Pressure Low 41 P UNLOAD Compressor Motor Current High 42 P UNLOAD Compressor Motor Current High 43 P UNLOAD Compressor Motor Current High 44 P UNLOAD Compressor Motor Current High 45 P EVAPORATOR PUMP ON Evaporator Water Freeze Protection No P EVAPORATOR PUMP ON Evaporator Water Freeze Protection No P PUMP START ATTEMPTED Evaporator Pump Failure 50 P PUMP START ATTEMPTED Evaporator Pump Failure 52 F COMPRESSOR SHUTDOWN Outside Air Temperature Sensor Fault 61 F COMPRESSOR SHUTDOWN Motor Current Low 62 F COMPRESSOR SHUTDOWN Motor Current Low 63 F COMPRESSOR SHUTDOWN Motor Current Low 64 F COMPRESSOR SHUTDOWN Motor Current Low 65 F UNIT SHUTDOWN Motor Protector Trip 66 F COMPRESSOR SHUTDOWN Motor Protector Trip 67 F COMPRESSOR SHUTDOWN Motor Protector Trip 68 F COMPRESSOR SHUTDOWN Motor Temperature High 69 F COMPRESSOR SHUTDOWN Motor Temperature High 70 F COMPRESSOR SHUTDOWN Motor Temperature High Page 4 of 10 Siemens Building Technologies, Inc.
5 71 F COMPRESSOR SHUTDOWN Motor Temperature High 72 F COMPRESSOR SHUTDOWN Phase Loss 73 F COMPRESSOR SHUTDOWN Phase Loss 74 F COMPRESSOR SHUTDOWN Phase Loss 75 F COMPRESSOR SHUTDOWN Phase Loss 88 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 89 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 90 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 91 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 92 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 93 F COMPRESSOR SHUTDOWN Condenser Water Flow Loss 94 F COMPRESSOR SHUTDOWN Condenser Pressure High 95 F COMPRESSOR SHUTDOWN Condenser Pressure High 96 F COMPRESSOR SHUTDOWN Condenser Pressure High 97 F COMPRESSOR SHUTDOWN Condenser Pressure High 98 F COMPRESSOR SHUTDOWN Condenser Pressure High 99 F COMPRESSOR OFF Current High with Compressor OFF 100 F COMPRESSOR OFF Current High with Compressor OFF 103 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor Fault 104 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor Fault 105 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor Fault 106 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor Fault 107 F COMPRESSOR SHUTDOWN Discharge Temperature High 108 F COMPRESSOR SHUTDOWN Discharge Temperature High 109 F COMPRESSOR SHUTDOWN Discharge Temperature High 110 F COMPRESSOR SHUTDOWN Discharge Temperature High 111 F COMPRESSOR SHUTDOWN Condenser Entering Water Temperature Sensor Fault 112 F COMPRESSOR SHUTDOWN Evaporator Water Flow Loss 113 F COMPRESSOR SHUTDOWN Evaporator Leaving Water Temperature Low (Freeze) Siemens Building Technologies, Inc. Page 5 of 10
6 114 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 115 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 116 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 117 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 118 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 119 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 120 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 121 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 122 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 123 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 124 F COMPRESSOR SHUTDOWN Ground Fault Trip 125 F COMPRESSOR SHUTDOWN Ground Fault Trip 126 F COMPRESSOR SHUTDOWN Ground Fault Trip 127 F COMPRESSOR SHUTDOWN Ground Fault Trip 128 F COMPRESSOR SHUTDOWN Lift Pressure Low 129 F COMPRESSOR SHUTDOWN Lift Pressure Low 130 F COMPRESSOR SHUTDOWN Lift Pressure Low 131 F COMPRESSOR SHUTDOWN Lift Pressure Low 132 F COMPRESSOR SHUTDOWN Liquid Line Pressure Sensor Fault 133 F COMPRESSOR SHUTDOWN Liquid Line Pressure Sensor Fault 134 F COMPRESSOR SHUTDOWN Liquid Line Pressure Sensor Fault 135 F COMPRESSOR SHUTDOWN Liquid Line Pressure Sensor Fault 136 F COMPRESSOR SHUTDOWN Liquid Line Temperature Sensor Fault 137 F COMPRESSOR SHUTDOWN Liquid Line Temperature Sensor Fault 138 F COMPRESSOR SHUTDOWN Liquid Line Temperature Sensor Fault 139 F COMPRESSOR SHUTDOWN Liquid Line Temperature Sensor Fault 140 F UNIT LOCKOUT Number of Allowed Re-starts Exceeded Page 6 of 10 Siemens Building Technologies, Inc.
7 141 F COMPRESSOR LOCKOUT Number of Allowed Re-starts Exceeded 142 F COMPRESSOR LOCKOUT Number of Allowed Re-starts Exceeded 143 F COMPRESSOR LOCKOUT Number of Allowed Re-starts Exceeded 144 F COMPRESSOR LOCKOUT Number of Allowed Re-starts Exceeded 145 F COMPRESSOR SHUTDOWN Evaporator Leaving Water Temperature Sensor Fault 146 F COMPRESSOR SHUTDOWN Evaporator Leaving Water Temperature Sensor Fault 147 F COMPRESSOR SHUTDOWN Evaporator Leaving Water Temperature Sensor Fault 150 F UNIT STOP Mechanical High Pressure Trip 151 F COMPRESSOR SHUTDOWN Mechanical High Pressure Trip 152 F COMPRESSOR SHUTDOWN Mechanical High Pressure Trip 153 F COMPRESSOR SHUTDOWN Mechanical High Pressure Trip 154 F COMPRESSOR SHUTDOWN Mechanical High Pressure Trip 155 F COMPRESSOR SHUTDOWN Oil Net Pressure Low 156 F COMPRESSOR SHUTDOWN Oil Net Pressure Low 159 F COMPRESSOR SHUTDOWN Oil Feed Temperature High 160 F COMPRESSOR SHUTDOWN Oil Feed Temperature High 163 F COMPRESSOR SHUTDOWN Oil Feed Temperature Low 164 F COMPRESSOR SHUTDOWN Oil Feed Temperature Low 167 F COMPRESSOR SHUTDOWN Oil Feed Temperature Sensor Fault 168 F COMPRESSOR SHUTDOWN Oil Feed Temperature Sensor Fault 171 F COMPRESSOR SHUTDOWN Oil Level Low 172 F COMPRESSOR SHUTDOWN Oil Level Low 173 F COMPRESSOR SHUTDOWN Oil Level Low 174 F COMPRESSOR SHUTDOWN Oil Level Low 175 F COMPRESSOR SHUTDOWN Oil Filter Delta Pressure High 176 F COMPRESSOR SHUTDOWN Oil Filter Delta Pressure High 177 F COMPRESSOR SHUTDOWN Oil Filter Delta Pressure High 178 F COMPRESSOR SHUTDOWN Oil Filter Delta Pressure High 179 F COMPRESSOR SHUTDOWN Oil Feed Pressure Sensor Fault Siemens Building Technologies, Inc. Page 7 of 10
8 180 F COMPRESSOR SHUTDOWN Oil Feed Pressure Sensor Fault 183 F COMPRESSOR SHUTDOWN Oil Sump Pressure Sensor Fault 184 F COMPRESSOR SHUTDOWN Oil Sump Pressure Sensor Fault 187 F COMPRESSOR SHUTDOWN Oil Sump Temperature Sensor Fault 188 F COMPRESSOR SHUTDOWN Oil Sump Temperature Sensor Fault 191 F COMPRESSOR SHUTDOWN Starter Fault Compressor 192 F COMPRESSOR SHUTDOWN Starter Fault Compressor 193 F COMPRESSOR SHUTDOWN Starter Fault Compressor 194 F COMPRESSOR SHUTDOWN Starter Fault Compressor 195 F COMPRESSOR SHUTDOWN Starter Fault Compressor 196 F COMPRESSOR SHUTDOWN No Starter Transition 197 F COMPRESSOR SHUTDOWN No Starter Transition 200 F COMPRESSOR START ABORT Oil Pressure Low 201 F COMPRESSOR START ABORT Oil Pressure Low 204 F COMPRESSOR SHUTDOWN Subcooling Low 205 F COMPRESSOR SHUTDOWN Subcooling Low 206 F COMPRESSOR SHUTDOWN Subcooling Low 207 F COMPRESSOR SHUTDOWN Subcooling Low 208 F COMPRESSOR SHUTDOWN Surge Suction Superheat High-Running 209 F COMPRESSOR SHUTDOWN Surge Suction Superheat High-Running 212 F COMPRESSOR SHUTDOWN Surge Suction Superheat High-Starting 213 F COMPRESSOR SHUTDOWN Surge Suction Superheat High-Starting 216 F COMPRESSOR SHUTDOWN Suction Temperature Sensor Fault 217 F COMPRESSOR SHUTDOWN Suction Temperature Sensor Fault 218 F COMPRESSOR SHUTDOWN Suction Temperature Sensor Fault 219 F COMPRESSOR SHUTDOWN Suction Temperature Sensor Fault Page 8 of 10 Siemens Building Technologies, Inc.
9 220 F COMPRESSOR START ABORT Vanes Open or No Condenser Flow 221 F COMPRESSOR START ABORT Vanes Open or No Condenser Flow 224 F COMPRESSOR SHUTDOWN (Check Chiller Display for Cause) Siemens Building Technologies, Inc. Page 9 of 10
10 Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners Siemens Building Technologies, Inc. Siemens Building Technologies, Inc Deerfield Parkway Country of Origin: US Buffalo Grove, IL Page 10 of 10 U.S.A.
APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller
Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Table 1. Series 200 Centrifugal Chiller. Point Type Range/Units 01
More informationMcQuay BACnet Solution: Microtech II Self-contained Unit Controller with Discharge Air Control (DAC)
Point Map December 1, 2004 Systems Integration McQuay BACnet Solution: Microtech II Self-contained Unit Controller with Discharge Air Control (DAC) Table 1. Microtech II Self-contained Unit Controller
More informationAPOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1)
Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1) Table 1. European Reciprocating Chiller (CR1). Point Type Description
More informationMultistack Modbus Driver: Standard Unit
Point Map October 27, 2006 Systems Integration Multistack Modbus Driver: Standard Unit Table 1. Multistack Modbus Standard APOGEE Points, Application Number: 4726. 1 LAO Address 2 LAI Application 3 LDI
More informationHoneywell Modbus Solution: 7800 Series Burner Controller through S7810M Modbus Module
Point Map August 1, 2006 Systems Integration Honeywell Modbus Solution: 7800 Series Burner Controller through S7810M Modbus Module Table 1. 7800 Series Burner Controller through S7810M Modbus Moduler APOGEE
More informationMcQuay Microtech III BACnet MS/TP Application 4181 Point Map
Point Map June 2009 Systems Integration McQuay Microtech III BACnet MS/TP Application 4181 Point Map APOGEE Open Processor with McQuay Microtech III BACnet MS/TP Driver: Microtech III Applied Rooftop Unit
More informationAPOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit
Point Map Rev. 2, July, 2002 Systems Integration APOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit Table 1. CCT DX Unit, Analog Points. 01 LAI Return Air Temperature F 02 LAI Supply Air
More informationLONWORKS Solution for Orion PT-LON-Link
Point Map February 5, 2008 Systems Integration LONWORKS Solution for Orion PT-LON-Link Table 1. Orion PT-Link-LON APOGEE Points, Application Number: 9158, Program ID: 90:00:95:47:1E:02:04:B3. 1 LAI AppSoftVer
More informationMicroTech Series 200 Centrifugal Chiller
Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History
More informationOpen Protocol Data Communications
MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way
More informationFieldServer Driver - Serial FS McQuay Microtech Open Protocol
Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls
More informationPneumercator Driver: TMS 2000/3000
Point Map November 21, 2006 Systems Integration Pneumercator Driver: TMS 2000/3000 System Table 1. System Point Map. Application 5235. 1 AI Address Point (Read Only) 2 AI Application Point (Read Only)
More informationMicroTech Series-200 Flooded Screw Chiller
Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D
More informationSales and Engineering Data Sheet ED
Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet
More informationSales and Engineering Data Sheet ED
Sales and Engineering Data Sheet ED 15121-6 Group: Controls Part Number: ED 15121 Date: March 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHAE 135-2004, BACnet
More informationMicroTech Water-Cooled Screw Chiller Controller
BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software
More informationGeneSys Air-Cooled Screw Compressor Chiller
Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through
More informationCONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN
CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER Table of Contents - 2 - INTRODUCTION... 3 OPERATING LIMITS:... 4 CONTROLLER FEATURES... 4 GENERAL DESCRIPTION... 5 CONTROL
More informationAir-Cooled Scroll Compressor Chiller
Air-Cooled Scroll Compressor Chiller Operation Manual OM AGZC-1 Group: Chiller Part Number: 331376301 Effective: February 2010 Supercedes: April 2009 AGZ 030CH through 190CH, Packaged AGZ 030CB through
More informationINITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER
INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME ADDRESS JOB NO. MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS BRINE FLOW RATE
More informationINITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER
INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME JOB NO. ADDRESS MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS BRINE FLOW
More informationCONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN
CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN Table of Contents INTRODUCTION... 2 CONTROLLER OPERATING LIMITS:... 3 CONTROLLER FEATURES... 3 GENERAL
More informationCONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN
CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN - 2 - Table of Contents INTRODUCTION... 2 CONTROLLER OPERATING LIMITS:... 3 CONTROLLER FEATURES... 3
More informationAir-Cooled Scroll Compressor Chiller
Operating and Maintenance Manual OMM 1087-1 Air-Cooled Scroll Compressor Chiller Group: Chiller Part Number: OMM 1087 Effective: May 2012 Supersedes: April 2012 AGZ-D 25 to 190 Tons 50-60-Hertz, -410A
More informationWater-Cooled Scroll Compressor Chillers
Operating Manual OM WGZ-2 Group: Chiller Part Number: 331374501 Effective: March 2005 Supercedes: OM WGZ-1 Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 120AW, Packaged Water-Cooled Chiller
More informationEQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:
Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL
More informationPathfinder Air-Cooled Chillers
Operating & Maintenance Manual OMM 1123 Group: Chiller Part Number: OMM 1123 Date: January 2012 Supercedes: December 2011 Rev 00 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes Models
More informationMODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:
Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL
More informationMetasys Integrator McQuay Application
Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator McQuay Application Introduction Page * Application Details * Component
More informationPathfinder Air-Cooled Chillers
Operating & Maintenance Manual OMM 1168 Group: Chiller Part Number: OMM 1168 Date: September 2012 Rev 00 Supercedes: OMM 1123, July 2012 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes
More informationChapter-8 Capacity Control of Refrigeration Systems
Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control
More informationWater-Cooled Scroll Compressor Chillers
Operating Manual OM WGZC Group: Chiller Part Number: 331374501 Effective: January 2008 Supercedes: New Water-Cooled Scroll Compressor Chillers WGZ 030CW to WGZ 200CW, Packaged Water-Cooled Chiller WGZ
More information100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION
100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest
More information60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES
60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,
More informationSECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.
SECTION 15650 REFRIGERATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. 4. Air
More informationCascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:
Case-16 Cascade Refrigeration System for LPG Subcooling Copy Right By: Thomas T.S. Wan ( ) Mar. 28, 2003 All Rights Reserved Case Background: This is a case of using a cascade refrigeration system to subcool
More informationAir-Cooled Scroll Compressor Water Chillers
Installation, Operation and Maintenance Manual IOMM AGZ1 Group: Chiller Part Number: 330262001 Effective: October 2001 Supersedes: New Air-Cooled Scroll Compressor Water Chillers AGZ 010A AGZ 034A 10 to
More informationCONTROLS MANUAL. Touch Pilot Control. 30XA/XAS/XB/XBP/XW 30XA-ZE/XW-ZE AquaForce PUREtec with R-1234ze(E) Operation instructions.
CONTROLS MANUAL Touch Pilot Control 30XA/XAS/XB/XBP/XW 30XA-ZE/XW-ZE AquaForce PUREtec with R-1234ze(E) Operation instructions Original document CONTENTS 1 -.SAFETY CONSIDERATIONS... 5 1.1 - General description...
More informationCase 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage
Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Copy Right By: Thomas T.S. Wan ) Dec. 28, 2012 All Rights Reserved Case Background: Ammonia is one of the important elements to
More informationAir-Cooled Scroll Compressor Water Chillers
Installation, Operation and Maintenance Manual IOMM AGZ1-2 Group: Chiller Part Number: 331373801 Effective: February 2005 Supersedes: IOMM AGZ1-1 Air-Cooled Scroll Compressor Water Chillers AGZ 010A AGZ
More informationAir-Cooled Scroll Compressor Chiller
Operating & Maintenance Manual OMM 1166-1 Air-Cooled Scroll Compressor Chiller Group: Chiller Part No. OMM1166-1 Effective: March 2014 AGZ025D AGZ190D (ev 0A) 25 to 190 Tons 50-60-Hertz, -410A Software
More informationEngineered for flexibility and performance
Centrifugal Chillers 200 to 2700 tons Engineered for flexibility and performance Daikin McQuay Single Compressor Centrifugal Chillers A Life Cycle Return on Your Investment Centrifugal chillers are a significant
More informationAir-Cooled Screw Compressor Chillers
Catalog Cat AGSD-1 Air-Cooled Screw Compressor Chillers Models AGS 225D to AGS 450D 210 to 450 Tons, 740 to 1580 kw Packaged or with Remote Evaporator or Chilled Water Pump Package R-134a, Hz Engineered
More informationAir-Cooled Scroll Condensing Units
Installation, Operation and Maintenance Manual IOMM ACZ1 Group: Chiller Part Number: 330262002 Effective: December 2001 Supersedes: New Air-Cooled Scroll Condensing Units ACZ 010A ACZ 039A 10 to 43 Tons,
More informationTouch Pilot Control 30XA/XAS/XB/XBP/XW 30XA-ZE/XW-ZE. AquaForce PUREtec with R-1234ze(E) Original document
C O N T R O L S M A N U A L Touch Pilot Control 30XA/XAS/XB/XBP/XW 30XA-ZE/XW-ZE AquaForce PUREtec with R-1234ze(E) Original document CONTENTS 1 - SAFETY CONSIDERATIONS...5 1.1 - General description...5
More informationGeneSys. Air-Cooled Screw Compressor Chillers. Catalog
Catalog Cat AGS-2 GeneSys Air-Cooled Screw Compressor Chillers Models AGS 120C to AGS 210C 110 to 210 Tons, 420 to 740 kw Packaged and with Remote Evaporator R-134a, 60 Hz Engineered for flexibility and
More informationDate: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days
Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:
More informationWater-Cooled Screw Compressor Chillers
Operating Manual OM WGS-5 Water-Cooled Screw Compressor Chillers WGS 130AW to WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA to WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700
More informationWater-Cooled Scroll Compressor Chillers
Operating and Maintenance Manual OMM 1130 Group: Chiller Part Number: OMM 1130 Effective: March 2012 Supercedes: November 2011 Water-Cooled Scroll Compressor Chillers WGZ030DW to WGZ200DW, Packaged Water-Cooled
More informationWater-Cooled Scroll Compressor Chillers
Operating Manual OM WGZC-2 Group: Chiller Part Number: 331975301 Effective: August 2011 Supercedes: November 2010 Water-Cooled Scroll Compressor Chillers WGZ 030CW To WGZ 200CW, Packaged Water-Cooled Chiller
More informationCentrifugal Compressor Water Chillers Catalog 605 Models WSC, WDC, WCC, HSC
Centrifugal Compressor Water Chillers Catalog 605 Models WSC, WDC, WCC, HSC Engineered for flexibility and performance Cutaway view of McQuay Model CE 063 Compressor, Nominal 250 Tons MicroTech II Controller,
More informationIce Rink (Single and Dual Configurations) Custom Control Features
& M&M Refrigeration, Inc. Computer Control System Ice Rink (Single and Dual Configurations) Custom Control Features REVISION DATE DESCRIPTION - 4/20/05 Original release. A 09/21/98 Update Chiller Pump
More informationOPERATING MANUAL Enertronic Control System 2
OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861
More informationCentrifugal Compressor Water Chillers THE DISTINCTION SERIES
Product Manual PM WSCWDC-2 Centrifugal Compressor Water Chillers THE DISTINCTION SERIES Model WSC, Single Compressor, Cooling Model WDC, Dual Compressor, Cooling Model HSC, Single Compressor Heat Recovery
More informationCall us today! (800)
500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,
More informationC. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers
More informationCall us today! (800)
PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller
More information1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.
WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.
More informationCONTROLS MANUAL. Touch Pilot Control. 30XA/XAS/XW 30XA-ZE/XW-ZE AquaForce PUREtec with R-1234ze(E) Operation instructions.
CONTROLS MANUAL Touch Pilot Control 30XA/XAS/XW 30XA-ZE/XW-ZE AquaForce PUREtec with R-1234ze(E) Operation instructions Original document CONTENTS 1 -.SAFETY CONSIDERATIONS... 5 1.1 -.General description...
More informationTechnical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.
Document No. 155-021P25 ET 141-5 ET 141 High Limit Control Thermostat Description Application The ET 141 high limit control thermostat is duct mounted and has a rigid bulb, bi-metal rod and tube construction.
More informationDTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5
Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3
More informationThe McQuay DISTINCTION SERIES. Single/Dual Compressor Centrifugal Chillers. Installation and Maintenance Manual
Installation and Maintenance Manual IMM WSCWDC-5 Group: Chiller Part Number: 331374801 Effective: August 2007 Supersedes: July 2006 The McQuay DISTINCTION SERIES Single/Dual Compressor Centrifugal Chillers
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationAir-cooled chillers with single-screw compressor. Installation, operation and maintenance manual D - KIMAC EN. Original Instructions
Installation, operation and maintenance manual D - KIMAC00611-09EN Air-cooled chillers with single-screw compressor EWAD650-C17 C-SS EWAD650-C17 C-SL EWAD620-C16 C-SR EWAD760-C19 C-XS EWAD760-C19 C-XL
More informationWater-Cooled Screw Compressor Chillers
Catalog Cat WGS Water-Cooled Screw Compressor Chillers WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A,
More informationAir-Cooled Scroll Condensing Units
Installation, Operation and Maintenance Manual IOMM ACZ1-2 Group: Chiller Part Number: 331373901 Effective: June 2005 Supersedes: IOMM ACZ1-1 Air-Cooled Scroll Condensing Units ACZ 010A ACZ 039A 10 to
More informationTEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies
TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware
More informationPACKAGED AIR COOLED Product Data Catalog
PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES
More informationUser Guide. Tracer CH530 Control System for Scroll Chillers CGAN/CXAN CGCL CGWH/CCUH CGWN/CCUN RAUL
User Guide Tracer CH530 Control System for Scroll Chillers CGAN/CXAN 209-214 CGCL 200-600 CGWH/CCUH 115-250 CGWN/CCUN 205-215 RAUL 190-800 General information Foreword These instructions are given as a
More informationTEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072
TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 Application Note 140-1042 Building Technologies Table of Contents Overview... 4 Hardware
More informationCase 8 Basic Performance of Screw Compressor
Case 8 Basic Performance of Screw Compressor Copy Right By: Thomas T.S. Wan ) June 24, 2010 All Rights Reserved Case Background: The basic rating and performance given by a compressor manufacturer is usually
More informationCall us today! (800)
150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,
More informationMagnitude Frictionless Centrifugal Chillers
Operation & Maintenance Manual OMM 1034-1 Group: Chiller Part Number: 331499501 Effective: July 2011 Supersedes: June 2011 Magnitude Frictionless Centrifugal Chillers Model WME 0500-700 Software Version:
More informationNEW CHILLER SCHEDULE
TITLE: REPLACE CHILLER MACC MAXIMO # 4542690 PROJECT # 14M108CN MACC # 14-0459 ATTACHMENTS: 1. MAXIMO Equipment update form SCOPE OF WORK: The contractor shall provide all material, labor, equipment, and
More informationSECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower
SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal
More informationA. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.
15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional
More informationPOWERS CONTROLS Pneumatic Thermostat Covers
Document No. A6V11225047 CONTROLS Pneumatic Thermostat s 192-2xx Plastic 192-2xxW Plastic 192-3xx 856-0xx D Series Description Proven to provide fast response and highly accurate temperature control, Powerstar
More informationYCIV Hz & Hz
YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried
More informationWater-Cooled Screw Compressor Chillers
Water-Cooled Screw Compressor Chillers Catalog 617 WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A, 60
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationCentrifugal Compressor Water Chillers
Centrifugal Compressor Water Chillers Models WSC, WDC, WCC, HSC Includes Higher Voltage (10/11kV) WDC/WCC models People and ideas you can trust. Catalog 605-3 Contents Contents..................................
More informationThe Refrigeration Cycle
Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.
More informationThe McQuay DISTINCTION SERIES. Single/Dual Compressor Centrifugal Chillers. Installation, Operating and Maintenance Manual
Installation, Operating and Maintenance Manual IOMM WSCWDC-2 Group: Chiller Part Number: 736015420 Effective: April 2001 Supersedes: IOMM WSCWDC-1 The McQuay DISTINCTION SERIES Single/Dual Compressor Centrifugal
More informationTechnical Bulletin (TB-0037)
Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant
More informationENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL
ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance
More informationThe Refrigeration Cycle
Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.
More informationCondensing Unit Installation and Operating Instructions
Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.
More informationSome alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.
Alarm Descriptions This document describes all possible alarm types as listed in the alarm log. x indicates compressor circuit for compressor related alarms. Alarms are listed in alphabetical order. Some
More informationInstallation Manual IM
Installation Manual IM 1128-1 Group: Chiller Part Number: 331375601 REV: 01 Effective: April 2012 Supersedes: February 2012 WSC, WME and WMC-B Centrifugal Chillers Reassembly of Knockdown Shipments COMPRESSOR
More informationLife Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International
Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint Daryl Showalter ChillerApplications Manager McQuay International Equipment Using Different Kinds Of Equipment Or Different Performance
More informationCatalog Water-Cooled Scroll Compressor Chillers
Water-Cooled Scroll Compressor Chillers Model WGZ, D Vintage 30 to 200 Tons (100 to 700 kw) HFC-410A Refrigerant 60/50 Hz Packaged and Condenserless Units Catalog 613-3 Table of Contents Table of Contents
More informationPresented By: John Dolan, P.E.
Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com
More informationOPERATING MANUAL Enertronic Control System 2
OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic and Seconscrew ranges Manufacturer Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg
More informationDigital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS
Digital Refrigerant System Analyzer INSTRUCTION MANUAL ENGLISH LOW START PRS T-LOW SUPERHEAT MAXMIN kpa Bar MPa R TIME P T HIGH END PRS T-HIGH SUBCOOL VAC 1-800-547-5740 Fax: (503) 643-6322 www.ueitest.com
More informationTECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703
TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.
More informationWater-Cooled Screw Compressor Chillers
Water-Cooled Screw Compressor Chillers Catalog 617-4 WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A, 60
More informationMagnitude Magnetic Bearing Centrifugal Chillers
Operation & Maintenance Manual OMM 1034-4 Group: Chiller Part Number: 331499501 Effective: November 2012 Supersedes: July 2012 Magnitude Magnetic Bearing Centrifugal Chillers Model WME 0500-700 Software
More informationOT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems
OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL Technicold Marine Systems www.technicold.com Technicold by Northern Lights 1419 W. Newport Center Drive Deerfield Beach, FL 33442 Tel:
More informationProduct Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons
Product Data 07DA, DB 07EA, EB, ED Condensing Units 3 to 40 Nominal Tons 06D, 06E Compressors An excellent choice for your built-up system Carrier 07 Series condensing units built for the engineer who
More informationSECTION ROTARY-SCREW WATER CHILLERS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.
More information