EC 6-295P220S001. smart guide 2 OPERATION. 2.1 How to turn the instrument ON/OFF. If you have to turn the instrument ON/OFF:

Size: px
Start display at page:

Download "EC 6-295P220S001. smart guide 2 OPERATION. 2.1 How to turn the instrument ON/OFF. If you have to turn the instrument ON/OFF:"

Transcription

1 EC 6-295P220S001 smart guide ON-OFF digital controller for ventilated refrigerating units Version 1.01 of 15 th March 2005 File ec6295p220s001_eng_v1.01.pdf PT EVCO S.r.l. Via Mezzaterra 6, Sedico Belluno ITALY Phone Fax ENGLISH 1 PREPARATIONS 1.1 How to install the instrument On DIN rail (it is not supplied by the builder). 2 OPERATION 2.1 How to turn the instrument ON/OFF If you have to turn the instrument ON/OFF: for 2 s During the normal operation the instrument shows the cabinet temperature. 2.2 How to silence the buzzer If you have to silence the buzzer: 2.3 How to activate the defrost by hand If you have to activate the defrost by hand: for 4 s Unless the evaporator temperature is below the defrost end temperature you have set with the parameter d2, the defrost will not be activated. 2.4 How to turn the cabinet light ON/OFF If you have to turn the cabinet light ON/OFF: 2.5 Compressor thermal protection The activation of this input forces the compressor OFF by hardware and software. 3 REAL TIME CLOCK 3.1 How to set the clock Press for 2 s : the instrument Press or for selecting If you have to modify the value of the hour: and or If you have to modify the value of the minutes: release and press it again during the modification of the hour, then... Evco S.r.l. EC P220 S001 Sheet 1/3 DIN rail installation (it is not supplied by the builder). or If you have to quit the procedure: or as long as the instrument shows the cabinet temperature or do not operate for about 30 s.

2 4 WORKING SETPOINT 4.1 How to set the working setpoint If you have to modify the working setpoint value: and or (1) (2) (1) you can set the working setpoint between the limits you have set with the parameters r1 and r2 (2) unless the parameter r5 has value 0, you can not modify the working setpoint. 5 CONFIGURATION PARAMETERS 5.1 How to set the configuration parameters Configuration parameters are arranged on two levels. If you have to gain access the first level: and for 4 s : the instrument If you have to select a parameter: or If you have to modify the value of the parameter: and or If you have to gain access the second level: gain access the first level or for selecting and or for setting -19 and for 4 s : the instrument If you have to quit the procedure: and for 4 s or do not operate for about 60 s. 6.2 Evaporator temperature showing If you have to show the evaporator temperature: or for selecting 6.3 Temperature storage If you have to show the temperature the instrument has stored during the lower temperature : or for selecting (3) If you have to show the temperature the instrument has stored during the upper temperature : or for selecting (4) If you have to erase the temperature the instrument has stored during the lower or upper temperature : or for selecting or for 4 s : the instrument (3) unless the parameter A8 has value 1 or 3, the label AL will not be showed (4) unless the parameter A8 has value 2 or 3, the label AH will not be showed. 7 SIGNALS 7.1 Signals (16) do not set more instruments as master (17) the time between the master implements a control and the slave implements the same control is n1 x n4 (18) except the control turning ON and OFF; it will immediately be implemented (19) if among the remote controls the slave has to implement there is the defrost activation, the parameter d5 will set a time you will have to add to the one you have set with the parameters n1 and n4 (the slave will implement the control even if the conditions will not allow the master of activating the defrost); if the master is in the STAND-BY mode and among the remote controls the slave has to implement there is not the turning ON and OFF, the slave will work with the local settings. 11 ELECTRICAL CONNECTION 11.1 Electrical connection 6 ADDITIONAL FUNCTIONS 6.1 How to gain access the additional functions LED Compressor LED MEANING If you have to gain access the additional functions: for 2 s : the instrument If you have to quit the procedure: or as long as the instrument shows the cabinet temperature or do not operate for about 30 s. if it is lighted, the compressor will be ON if it flashes, a compressor delay will be running (look at the parameters C0, C1, C2, C4, n1 and n4) Defrost LED if it is lighted, the defrost output will be activated if it flashes: a defrost delay will be running (look at the parameters C0, C1, C2, C4, n1 and n4) (20) short-circuit terminals 1 and 5 and/or 1 and 7 if you do not use the lock input and/or the compressor thermal protection (21) the position of the probe for compressor thermal protection could compromise the insulation between low voltage and high voltage parts. the dripping will be running (look at the parameter d7) the freezing fluid heating will be running (look at the parameter dp)

3 na remote control the slave has to implement (0 = no controls, 1 and 9 = compressor status, Evaporator fan LED 8 ALARMS 2 and 10 = defrost activation, 3 and 11 = compressor status and defrost activation, if it is lighted, the evaporator fan will be ON 8.1 Alarms 4 and 12 = turning ON and OFF, 5 and 13 = compressor status and turning ON and OFF, if it flashes, the after dripping evaporator fan delay will be running (look CODE REASONS REMEDIES EFFECTS 6 and 14 = defrost activation and turning ON and OFF, 7 and 15 = compressor status, at the parameter F5) there is the corruption switch off the power you can not gain defrost activation and turning ON and OFF, 8 = reserved) (19) Cabinet light LED corrupted of the configuration supply of the instru- access the setting if it is lighted, the cabinet light will be ON memory data of the memory of ment: unless the procedures LABEL MIN. MAX. U.M. DEF. ENERGY SAVING (the working setpoint becomes r8) if it flashes, the multifunction input will be active (look at the parameters data the instrument disappears, you will all outputs will be Hr h.damin (6) 0.0 Energy Saving cycle activation time i0, i1 and i7) have to change the forced OFF Hr h.damin (6) 0.0 Energy Saving cycle length Lock input/thermal protection LED instrument if it is lighted, there will have been a number of lock input/thermal pro- the lock input/thermal deactivate the inputs the compressor will LABEL MIN. MAX. U.M. DEF. REAL TIME DEFROST tection s such as to give the lock of the instrument (turn the instru- person protection and the (look at the param- be forced OFF Hd h.damin (6) first defrost activation time (it is important if de = 3; = it will never be activated) (7) ment OFF and turn it ON again, look at the parameters i2, i3, i4 and i5) into the multifunction input are eters i0, i1, i2, i3, i4 if the defrost is run- Hd h.damin (6) second defrost activation time (it is important if de = 3; = it will never be activated) (7) if it flashes, the lock input/thermal protection will be active (look at the cabinet active and i5) ning, it will immedi- Hd h.damin (6) third defrost activation time (it is important if de = 3; = it will never be activated) (7) parameters i2, i3, i4 and i5) (you can turn the instrument ately end Hd h.damin (6) fourth defrost activation time (it is important if de = 3; = it will never be activated) (7) ON STAND-BY LED not OFF and turn it ON the defrost will Hd h.damin (6) fifth defrost activation time (it is important if de = 3; = it will never be activated) (7) if it is lighted, the instrument will be in the STAND-BY mode silence again never be activated Hd h.damin (6) sixth defrost activation time (it is important if de = 3; = it will never be activated) (7) if it flashes, the instrument will be set as slave but it will not be author- the you will get the ac- (5) the unit of measure depends on the parameter /8 ized to implement the remote controls coming from the master (look at buzzer) tion you have cho- (6) damin = 10 minutes the parameter n3) sen with the param- (7) unless the evaporator temperature is below the defrost end temperature you have set with the parameter d2, the defrost will not be activated if it flashes every two seconds, the instrument will be set as slave and eter i0 (8) if the time the compressor is ON is lower than 30 s, the compressor will never be ON; if the cabinet probe failure takes place during a compressor delay, the compressor will be among the remote controls, coming from the master, the slave has to the lock input/thermal deactivate the input the compressor will forced OFF for 1 min; the parameter C1 sets the minimum delay between the end of the cabinet probe failure and the following activation of the compressor (if the parameter implement, there will be the turning ON and OFF (look at the param- lock protection is active. (look at the param- be forced OFF C1 has value 0, the compressor will be forced off for 2 min) eter na) input/ If there has been a eters i2, i3, i4 and i5) if the defrost is run- (9) if at the moment of the defrost activation the cabinet temperature is below the value working setpoint + r0, the instrument will not show temperatures above that value; if thermal number of lock input/ turn the instrument ning, it will immedi- at the moment of the defrost activation the cabinet temperature is above the value working setpoint + r0, the instrument will not show the increases of the temperature (if INDICAT. MEANING protection thermal protection OFF and turn it ON ately end the increase takes place below the value working setpoint + r0, look at the previous case); the instrument restores the normal operation once the after dripping evaporator the instrument will be set as slave and among the remote controls, com- s such as to give again the defrost will fan delay ends and the cabinet temperature falls below the freeze temperature ing from the master, the slave has to implement, there will be the com- the lock of the instru- never be activated (10) if at the moment of the defrost activation the compressor is ON since a time lower than the one you have set with the parameter, the compressor will be forced ON for a time pressor status (look at the parameter na). ment, for 3 s such as to finish the time you have set with the parameter If you have to show the cabinet temperature, press every 4 (if you (11) if the lower temperature takes place during the count of the delay, this last will be cleared the instrument will be set as slave, among the remote controls, coming have to restore the (12) if the temperature does not disappear at the end of the times you have set with the parameters A3 and AA, it will further be excluded for the time you have set with the every 2 s from the master, the slave has to implement, there will be the compres- normal operation, turn parameter A6; if the temperature takes place during the defrost and does not disappear at the end of the time you have set with the parameter A7, it will further be sor status but there will not be the turning ON and OFF, both the master the instrument OFF excluded for the time you have set with the parameter A6; if the temperature takes place during the multifunction input activation, it will be excluded for the time "A5 + A6" since the input activation or for the time you have set with the parameter A6 since the input deactivation (13) the evaporator fan stop temperature is cabinet temperature - F1 ; you always have to consider the parameter F1 with positive sign (14) the instrument will automatically verify the maximum value of the parameter; it always has to be lower than the value you have set with the parameter i4 (15) when there is 1 min to the end of the time you have set with the parameter, the cabinet light will be turned OFF just for 1 s; press during the time you have set with the parameter to turn the cabinet light ON and to exclude the function, press again before the end of the time you have set with the parameter to recover the function (if the remaining time of the parameter is higher than 1 min, the time will be forced at 1 min and the cabinet light will be turned OFF just for 1 s) Evco S.r.l. EC P220 S001 Sheet 2/3 and the slave will be in the STAND-BY mode (look at the parameter na). If the master is in the STAND-BY mode and the slave is ON, the indication will be showed alternated with the cabinet temperature cabinet probe and turn it ON again) the kind of cabinet probe you have connected is not right the cabinet probe plays up look at the parameter /0 test the integrity of the probe test the instrumentprobe connection the compressor will work in accordance with the parameters C5 and C6

4 the connection in- test the temperature if the defrost is run- there has been an up- look at the parameters LABEL MIN. MAX. U.M. DEF. DIGITAL INPUTS strument-cabinet close to the probe (it ning, it will immedi- for 3 s per temperature A0, A1b, A2b, A8 and i action given by the multifunction input activation (0 = inactive, 1 = once d5 has passed, the probe is wrong has to be between ately end every 4 A9 defrost will be activated (7), 2 = the cabinet light will be turned ON, 3 = the compressor will be the cabinet tempera- the limits allowed by the defrost will forced ON for A5 and the cabinet light will be turned ON, 4 = the compressor and the ture is outside the the working range) never be activated evaporator fan will be forced OFF for A5 and the cabinet light will be turned ON, limits allowed by the the cabinet tempera- test the temperature 5 = the evaporator fan will be forced OFF for A5 and the cabinet light will be turned ON, working range of lower ture is outside the limit close to the probe 6 = the working setpoint becomes r8, 7 = the working setpoint becomes r8 and the cabinet the instrument tempera- you have set with the (look at the parameters light will be turned OFF); look at i7 as well the kind of evapora- look at the param- if the parameter de ture parameter A1A A0, A1A and A2A) i kind of contact of the multifunction input (it is important if i0 0; 0 = NO, 1 = NC) evapora- tor probe you have eter /0 has value 2, the in- there has been a lower look at the parameters i action given by the lock input/thermal protection activation (1 = the compressor will be forced tor probe connected is not test the integrity of strument will work for 3 s temperature A0, A1A, A2A, A8 and OFF, 2 = in accordance with i3, i4 and i5) right the probe as if the parameter every 4 A9 i lock input/thermal protection s number such as to give the lock of the instrument (it is the evaporator test the instrument- had value 0 important if i2 = 2; 0 = the lock of the instrument will never take place) probe plays up probe connection if the parameter F7 i4 i5 240 min 0 time without lock input/thermal protection s able to clear the lock input/thermal pro- the connection in- test the temperature has value 3 or 4, the there is the corruption set the clock again if the parameter de tection s counter (it is important if i2 = 2) strument-evaporator close to the probe (it evaporator fan will real time of the data of the clock has value 3, the in- i (14) min 0 minimum delay between the lock input/thermal protection deactivation and the following probe is wrong has to be between work in accordance clock of the instrument strument will work compressor activation (it is important if i2 = 2) the evaporator tem- the limits allowed by with the compres- as if the parameter i indication Ain flashing on the display during the multifunction input activation (it is impor- perature is outside the working range) sor, except what had value 0 tant if i0 0) the limits allowed by you have set with the Energy Saving i min 0 delay between the multifunction input deactivation and the cabinet light gets OFF (it is the working range the parameters F4 cycle will never be important if i0 = 2, 3, 4 or 5) (15) of the instrument and F5 activated the defrost will end the instrument will be if you have to show look at the effects of LABEL MIN. MAX. U.M. DEF. SERIAL NETWORK (EVCOBUS) by time (parameter slave set as slave, among the code, that case L instrument address d3) the remote controls, press L instrument group the multifunction input deactivate the input you will get the action coming from the mas- look at the remedies L baud rate (0 = 1,200 baud, 1 = 2,400 baud, 2 = 4,800 baud, 3 = 9,600 baud) multi- is active. (look at the parameters you have chosen with ter, the slave has to of that case function Unless the parameter i0, i1 and i6) the parameter i0 implement there will input i6 has value 1, the in- be the comp. status strument will not show and there will be one any indication of the s you saw LABEL MIN. MAX. U.M. DEF. SERIAL NETWORK (EVCONET) the cabinet tempera- test the temperature in the previous cases. n operation of the instrument in the network (0 = instrument not enabled to work in the upper ture is outside the limit close to the probe If the master is in the network, 1 = master, 2 = slave) (16) tempera- you have set with the (look at the parameters STAND-BY mode and n address of the instrument in the network (it is important if n0 0; 0 = master address, ture parameter A1b A0, A1b and A2b) the slave is ON, the in = first... eighth slave address) dication will be n authorization to implement the remote controls coming from the master (it is important if showed every 2 s alter- n0 = 2 and n1 0; 1 = YES) nated with the n s 0 time between the master implements a control and the slave implements the same control (it code (17) (18) is important if n0 = 2 and n1 0); look at na as well

5 LABEL MIN. MAX. U.M. DEF. ALARMS A C/ F (5) 2.0 hysteresis (differential, it is relative to A1A and A1b, it is important if A2A and/or A2b 0) the value of the pa- look at the param- the instrument will relay working in accordance with the instrument mode (the relay will be activated if the serial rameters n0, n1 and eters n0, n1 and n3 work with the local instrument is ON and it will be deactivated if the instrument is in the STAND-BY mode, A1A C/ F (5) -10 lower temperature threshold; look at A2A as well A2A kind of lower temperature (0 = it will never be activated, 1 = lower temperature relative to the working setpoint, 2 = absolute lower temperature ) A1b C/ F (5) 10.0 upper temperature threshold; look at A2b as well network n3 is wrong test the connections settings change-over contact). the connections of of the instrument Kind of defrost: electric and hot gas defrost. the instrument are Defrost control: defrost interval, defrost end temperature, defrost maximum length wrong and defrost interval count mode (automatic, by hand and remote). A2b kind of upper temperature (0 = it will never be activated, 1 = upper temperature relative to the working setpoint, 2 = absolute upper temperature ) A min 120 upper temperature exclusion time since you turn the instrument ON (it is important if A2b 0) (11) A min 30 buzzer exclusion time since the multifunction input activation (it is important if i0 0; -1 = the buzzer will never be activated) A min 5 temperature exclusion time (it is important if A2A and/or A2b 0) (12) A min 15 upper temperature exclusion time since the end of the after dripping evaporator fan delay (since the end of F5, it is important if A2b 0) (11) A kind of temperature the instrument has to store (it is important if A2A and/or A2b 0; 0 = it will never be stored, 1 = lower temperature, 2 = upper temperature, 3 = both the lower temperature and the upper one) A s 1 time between two records of the temperature in succession (it is important if A2A and/or A2b 0 and A8 0) AA min 0 temperature s relative to the working setpoint exclusion time since the multifunction input activation/deactivation (it is important if i0 = 6 or 7) and since the activation/end of the Energy Saving cycle The instrument shows the indications above alternated with the cabinet temperature, except the indication E2 (it flashes), E0 (it is alternated with the indication ) and net (slave, it is a fixed indication) and the buzzer utters an intermittent beep. 9 TECHNICAL DATA 9.1 Technical data Box: self-extinguishing grey. Size: 106 x 90 x 58 mm (4.17 x 3.54 x 2.28 in, 6 DIN modules). Installation: on DIN rail (it is not supplied by the builder). Frontal protection: IP 40. Connections: screw terminal blocks with pitch 5 mm (0.19 in) for cables up to 2.5 mm² (0.38 sq in, power supply, inputs and outputs), 5 poles single line female connector with pitch 2.5 mm (0.09 in, serial port). Ambient temperature: from 0 to 55 C (32 to 131 F, % of relative humidity without condensate). Power supply: 230 Vac, 50/60 Hz, 4 VA. Clock data maintenance without power supply: 24 hours (the instrument must Serial port: TTL with EVCOBUS communication protocol, adapt for serial interface EC IFC 02. have been ON for 2 min at least). LABEL MIN. MAX. U.M. DEF. EVAPORATOR FAN F C/ F (5) -1.0 evaporator fan stop temperature (evaporator temperature, it is important if F7 = 3 or 4); look at F6 as well F C/ F (5) 2.0 hysteresis (differential, it is relative to F1, it is important if F7 = 3 or 4) F evaporator fan action during the defrost and dripping (0 = it will be forced OFF, 1 = it will be forced ON, 2 = it will work in accordance with F7) F min 2 after dripping evaporator fan delay Alarm buzzer: included. Measure inputs: 2 (cabinet and evaporator probe) for PTC or NTC probes. Digital inputs: 2 inputs: one multifunction input (NO or NC contact) and one lock input, without voltage (they work with 5 ma). Working range: from -50 to 99.9 C (-58 to 212 F) for PTC probe, from -40 to 99.9 C (-40 to 212 F) for NTC probe. Setpoint range: from -99 to 99.9 C (-99 to 99 F). Resolution: 1 F with unit of measure in Fahrenheit, 0.1 or 1 C with unit of measure F kind of evaporator fan stop temperature (it is important if F7 = 3 or 4; 0 = absolute evaporator fan stop temperature, 1 = evaporator fan stop temperature relative to the cabinet temperature) F evaporator fan action during the normal operation (0 = it will be forced OFF, 1 = it will be forced ON, 2 = it will work in accordance with the compressor, 3 = it will work in accordance with F1 and F2, 4 = if the compressor is ON, it will work in accordance with F1 and F2, if the compressor is OFF, it will be forced OFF) Evco S.r.l. EC P220 S001 Sheet 3/3 in Celsius. Display: one red LED 3-digit display 13.2 mm (0.51 in) high, output status indicators, instrument mode indicator. Outputs: 5 relays: one Vac relay for one 1½ 230 Vac compressor control (NO contact), one Vac relay for evaporator fan control (NO contact), one Vac relay for defrost system control (change-over contact), one Vac relay for cabinet light control (NO contact) and one Vac

6 10 WORKING SETPOINT AND CONFIGURATION PARAMETERS 10.1 Working setpoint LABEL MIN. MAX. U.M. DEF. WORKING SETPOINT r1 r2 C/ F (5) 0.0 working setpoint 10.2 First level parameters LABEL MIN. MAX. U.M. DEF. PASSWORD LABEL MIN. MAX. U.M. DEF. REGULATOR r C/ F (5) 2.0 hysteresis (differential, it is relative to the working setpoint) r1-99 r2 C/ F (5) -50 minimum value you can assign to the working setpoint r2 r C/ F (5) 50.0 maximum value you can assign to the working setpoint r working setpoint modification lock-out (1 = YES) r C/ F (5) 0.0 auxiliary working setpoint (it is the working setpoint during the multifunction input activation if i0 = 6 or 7 and during the Energy Saving cycle) PA password LABEL MIN. MAX. U.M. DEF. COMPRESSOR PROTECTION LABEL MIN. MAX. U.M. DEF. MEASURE INPUTS /1A C/ F (5) 0.0 cabinet probe calibration /1b C/ F (5) 0.0 evaporator probe calibration LABEL MIN. MAX. U.M. DEF. REGULATOR r C/ F (5) 2.0 hysteresis (differential, it is relative to the working setpoint) C min 0 minimum delay between you turn the instrument ON and the first compressor activation C min 5 minimum delay between two compressor activation in succession C min 3 minimum delay between the compressor gets OFF and the following activation C fixed delay since the compressor gets ON and OFF (1 = YES, for 3 s) C min 10 cycle time for the compressor activation during the cabinet probe C % 50 percentage of C5 the compressor is ON during the cabinet probe failure (8) LABEL MIN. MAX. U.M. DEF. SERIAL NETWORK (EVCONET) n authorization to implement the remote controls coming from the master (it is important if n0 = 2 and n1 0; 1 = YES) LABEL MIN. MAX. U.M. DEF. ENERGY SAVING (the working setpoint becomes r8) Hr h.damin (6) 0.0 Energy Saving cycle activation time Hr h.damin (6) 0.0 Energy Saving cycle length LABEL MIN. MAX. U.M. DEF. REAL TIME DEFROST Hd h.damin (6) first defrost activation time (it is important if de = 3; = it will never be activated) (7) Hd h.damin (6) second defrost activation time (it is important if de = 3; = it will never be activated) (7) Hd h.damin (6) third defrost activation time (it is important if de = 3; = it will never be activated) (7) Hd h.damin (6) fourth defrost activation time (it is important if de = 3; = it will never be activated) (7) Hd h.damin (6) fifth defrost activation time (it is important if de = 3; = it will never be activated) (7) Hd h.damin (6) sixth defrost activation time (it is important if de = 3; = it will never be activated) (7) 10.3 Second level parameters LABEL MIN. MAX. U.M. DEF. MEASURE INPUTS / kind of probe (1 = PTC, 3 = NTC) /1A C/ F (5) 0.0 cabinet probe calibration /1b C/ F (5) 0.0 evaporator probe calibration / temperature resolution (it is important if /8 = 1; 0 = 1 degree, 1 = 0.1 degrees) LABEL MIN. MAX. U.M. DEF. DEFROST d h 8 defrost interval (it is important if de 3); look at de as well (7) (0 = the defrost will never automatically be activated) d kind of defrost (0 = electric defrost, 1 = hot gas defrost) d C/ F (5) 2.0 defrost end temperature (evaporator temperature) d min 30 defrost maximum length (0 = the defrost will never be activated) d defrost activation every time you turn the instrument ON (1 = YES) (7) d min 0 delay between you turn the instrument ON and the defrost activation (it is important if d4 = 1) d freeze of the temperature showed by the instrument during the defrost (1 = YES) (9) d min 2 dripping time d compressor protections cleaning at the moment of the defrost activation (it is important if d1 = 1; 1 = YES) de defrost interval count mode; look at d0 as well (0 = the instrument counts the working time, 1 = the instrument counts the sum of the times the compressor is ON, 2 = the instrument counts the sum of the times the evaporator temperature is below df, 3 = real time defrost, the defrost will be activated at the times you have set with the parameters Hd1... Hd6) df C/ F (5) 0.0 defrost interval count freeze threshold (evaporator temperature, it is important if de = 2) dp 0 99 min 0 minimum time the compressor must have been ON at the moment of the defrost activation in order that the defrost can be activated (it is important if d1 = 1) (10) / temperature unit of measure (0 = Fahrenheit degree, 1 = Celsius degree)

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173) Evco S.p.A. Code 104K204E05 page 1/5 EVK204 Digital controller for ventilated refrigerating units, with HACCP and Energy Saving functions version 1.05 GB ENGLISH 1 PREPARATIONS 1.1 Important Please read

More information

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature EVCO S.p.A. EV3B24 Data sheet ver. 1.0 Code 1043B24E104 Page 1 of 6 PT 12/15 EV3B24 Basic controller for low temperature bottle coolers, cabinets, refrigerated cabinets, tables and pizza counters, with

More information

Dixell Installing and Operating Instructions release 7.0

Dixell Installing and Operating Instructions release 7.0 XR160C - XR160D - XR170C - XR170D - XR162C - XR172C CONTENTS 1. GENERAL WARNING 2 1.1 Please read before using this manual 2 1.2 Safety Precautions 2 2. GENERAL DESCRIPTION 2 3. CONTROLLING LOADS 2 3.1

More information

ST Wiring diagram. Product description. Standard temperature controller. Order number

ST Wiring diagram. Product description. Standard temperature controller. Order number ST64-31.10 Standard temperature controller Order number 900197.007 Old Id.Nr.: 386169 Wiring diagram Product description The controller ST64-31.10 was developed for simple thermostatic controls. The round

More information

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12 CAREL ir33 Quick reference Handbook Pag.1/12 MAIN FEATURES OF THE INSTRUMENT USER INTERFACE 1. ON/OFF switch button UP button to increase temperature values 2. DOWN button to decrease values - Activates/deactivates

More information

Bottle cooler controllers Solutions for static, ventilated and open coolers

Bottle cooler controllers Solutions for static, ventilated and open coolers Bottle cooler controllers Solutions for static, ventilated and open coolers XRB Bottle cooler controllers The XRB series is the high-efficiency range of products available in 2 versions, standard and advanced

More information

ER52 - Evaporator Controller

ER52 - Evaporator Controller ER52 - Evaporator Controller Electronic Refrigeration Line Product Bulletin Devices are standalone digital controller for static or ventilated refrigeration units working at positive temperatures. They

More information

EVF815 Installer manual ver. 2.0 Code 144F815E204 EVF815

EVF815 Installer manual ver. 2.0 Code 144F815E204 EVF815 EVF815 Split execution controller for temperature-controlled blast chillers (with capacitive touch-key user interface, which can be integrated into the unit) ENGLISH INSTALLER MANUAL ver. 2.0 CODE 144F815E204

More information

Refrigerated air dryers

Refrigerated air dryers Refrigerated air dryers OPERATING AND MAINTENANCE MANUAL Original instructions 38178800319 OPERATING AND MAINTENANCE MANUAL - Contents 1 CONTENTS CONTENTS... 1 Chapter 1 IDRY ELECTRONIC CONTROLLER...

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

EVF818 Installer manual ver. 1.0 Code 144F818E104 EVF818. Split execution controller for temperaturecontrolled

EVF818 Installer manual ver. 1.0 Code 144F818E104 EVF818. Split execution controller for temperaturecontrolled EVF818 Split execution controller for temperaturecontrolled blast chillers (with capacitive touch-key user interface, which can be integrated into the unit) ENGLISH INSTALLER MANUAL ver. 1.0 CODE 144F818E104

More information

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number ST71-KHJV.3 Temperature controller Order number 921.8 Wiring diagram Product description The switching outputs of the thermal controller can be programmed as -two-point controller with alarm -three-point

More information

MODEL URS-1: FACTORY RETROFIT PROGRAM

MODEL URS-1: FACTORY RETROFIT PROGRAM MODEL URS-1: FACTORY RETROFIT PROGRAM The USR-1 unit has gone through extensive testing in order to attain maximum performance. It has been determined that in order to set the unit for all weather operation,

More information

Thermometers and temperature controllers

Thermometers and temperature controllers D144H002 Ed.07 GB Thermometers and temperature controllers User Manual Contents AKO Electromecánica thanks and congratulates you for purchasing our product, in whose development and manufacture the most

More information

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring 1. GENERAL DESCRIPTION Model XWA11V-KIT, 100x64 mm format, is a microprocessor based light and alarm management controller,

More information

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO 06-10616. File name: URS-1 Service Manual up to 06-10616 Last revised: Jan. 30th 2009 TROUBLESHOOTING AND SERVICE GUIDE: The following is intended as

More information

PARAGON Commercial Refrigeration Controls

PARAGON Commercial Refrigeration Controls PARAGON Commercial Refrigeration Controls ERC 2 Electronic Refrigeration Control The ERC 2 Electronic Refrigeration Control is a microprocessor-based electronic controller designed to control both the

More information

XLH210: controller for gas leak detectors

XLH210: controller for gas leak detectors pag. 1 / 7 XLH210: controller for gas leak detectors Dixell introduces the new digital controllers designed to be combined with 4 20mA gas leak detectors. XLH210 is a microprocessor based controller, designed

More information

CATALOGUE 2017 ELECTRICAL BOARDS FOR REFRIGERATION

CATALOGUE 2017 ELECTRICAL BOARDS FOR REFRIGERATION CATALOGUE 2017 ELECTRICAL BOARDS FOR REFRIGERATION PRODUCTS INDEX EXPERT NANO 1LT 06 PLUS200 EXPERT THR 34 EXPERT NANO 3CF 08 PLUS300 EXPERT U THR 36 EXPERT NANO 4CK 10 PLUS1000 THR 38 EXPERT NANO 2ZN

More information

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Modular Standard HP Chiller 1/4 screw compressor with Carel driver Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?

More information

REMOTE CONTROL FOR CHILLER MYCHILLER

REMOTE CONTROL FOR CHILLER MYCHILLER REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN

More information

ST Wiring diagram. Product description. Four-stage controller. Order number

ST Wiring diagram. Product description. Four-stage controller. Order number ST96-35.16 Four-stage controller Order number 99.2 Wiring diagram Product description The four-stage controller with 4-digit setpoint and actual value display, 3 keys and 4 relays was developed for the

More information

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7

More information

TDF 15 MICROPROCESSOR-BASED DIGITAL ELECTRONIC THERMOCONTROLLER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR TECNOLOGIC S.p.A.

TDF 15 MICROPROCESSOR-BASED DIGITAL ELECTRONIC THERMOCONTROLLER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR TECNOLOGIC S.p.A. TDF 15 MICROPROCESSOR-BASED DIGITAL ELECTRONIC THERMOCONTROLLER INDEX 1 1.1 1.2 2 2.1 2.2 3 3.1 3.2 3.3 3.4 4 4.1 4.2 4.3 4.4 4.5 4.6 5 5.1 5.2 6 6.1 6.2 6.3 7 7.1 7.2 7.3 7.4 7.5 INSTRUMENT DESCRIPTION

More information

TOQUE BLANCHE GRANDE CARTE

TOQUE BLANCHE GRANDE CARTE REFRIGERATED BASES TOQUE BLANCHE GRANDE CARTE MAINTENANCE MANUAL MANUFACTURERS SPECIFICATION BONNET GRANDE CUISINE Rue des Frères Lumière - Z.I. Mitry Compans 77292 MITRY MORY cedex Tél. 01 60 93 70 00

More information

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort User manual CLIMATIC 2/4 - Controller Providing indoor climate comfort MUL35E-56 9-26 INDEX CONTENTS PAGE INDEX 1 GENERAL DESCRIPTION 2 THE KEYPAD, Climatic 2 3 THE KEYPAD, Climatic 4 4 THE KEYPAD REMOTE

More information

ERC2 Control Instructions

ERC2 Control Instructions Programg ERC2 Control Instructions The ERC 2 control initially powers up displaying 12: AM otherwise it will show the last configured selection (time or temperature). If a power outage occurs during normal

More information

JDDT1 - Single Stage Digital Thermostat

JDDT1 - Single Stage Digital Thermostat JDDT1 - Single Stage Digital Thermostat CAUTION NOTICE: The thermostat must be installed by authorized professionals. It should be located in a place free of vibrations, impacts, and corrosive gases. SET

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

XWA11V. Walk-In Temp / Door /Alarm / Light Module

XWA11V. Walk-In Temp / Door /Alarm / Light Module XWA11V Walk-In Temp / Door /Alarm / Light Module 1. GENERAL DESCRIPTION Model XWA11V, 100x64 mm format, is a microprocessor-based controller, suitable for temperature monitoring and alarming in a walk-in

More information

MasterCase. User Manual

MasterCase. User Manual MasterCase User Manual PRELIMINARY VERSION 24 January 2003 CONTENTS 1. Introduction...5 1.1 Main characteristics of the MasterCase...5 2. Layout of the hardware...7 2.1 Meaning of the inputs and outputs...7

More information

IN NOURISHING SECURITY.

IN NOURISHING SECURITY. HOJA TÉCNICA 1400H171 Edición 02 (01 de 08) Electronic controllers for refrigeration R NEW leads the way Furthermore to control the CCPs Critical Control Points, in the HACCP Hazard Analysis Critical Control

More information

Operating Instructions XWA11V XWA11V. Walk-In Temp / Door /Alarm / Light Module

Operating Instructions XWA11V XWA11V. Walk-In Temp / Door /Alarm / Light Module XWA11V Walk-In Temp / Door /Alarm / Light Module 1. GENERAL DESCRIPTION Model XWA11V, 100x64 mm format, is a microprocessor-based controller, suitable for temperature monitoring and alarming in a walk-in

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301 Refrigeration and Air Conditioning Technical leaflet Electronic controller EKC 201 and EKC 301 RC.5L.A1.02 RC.5L.A2.02 09-1998 Introduction EKC 201 and 301 are used for temperature control compressor control

More information

plug-in, electronic digital thermostat with defrost control User manual

plug-in, electronic digital thermostat with defrost control User manual , electronic digital thermostat with defrost control User manual We wish to save you time and money! We can assure you that a thorough reading of this manual will guarantee correct installation and safe

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

CAREL CONTROLLER. Programming Instructions HOW TO CHANGE LEVEL 1 CONTROL SETTINGS HOW TO CHANGE LEVEL 2 CONTROL SETTINGS

CAREL CONTROLLER. Programming Instructions HOW TO CHANGE LEVEL 1 CONTROL SETTINGS HOW TO CHANGE LEVEL 2 CONTROL SETTINGS CAREL CONTROLLER Programming Instructions The Carel controller has a two-level menu system for programming the operation of the case. Level 1 program settings are the most frequently accessed parameters.

More information

Follett Performance Plus

Follett Performance Plus Follett Performance Plus touchscreen user guide The next level of control in undercounter refrigeration Controller Operation - Performance Plus touchscreen Use and care of the LCD Performance Plus touchscreen

More information

Operating Instructions XWA11V. XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

Operating Instructions XWA11V. XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring 1. GENERAL DESCRIPTION Model XWA11V-KIT, 100x64 mm format, is a microprocessor based light and alarm management controller,

More information

User Manual Ichill 200 L/D (Firmware version 1.7)

User Manual Ichill 200 L/D (Firmware version 1.7) User Manual Ichill 2 L/D (Firmware version 1.7) Pag. 1 of 142 INDEX 1. GENERAL FEATURES...8 1.1 Main Function... 8 2. ICHILL 2L/D TABLE OF THE FEATURES...1 3. USER INTERFACE...11 4. REMOTE KEYBOARD...15

More information

Digital regulator for refrigeration and defrosting, 3 relays.

Digital regulator for refrigeration and defrosting, 3 relays. Installation guide ERC 213 Digital regulator for refrigeration and defrosting, 3 relays. 520H11062 The ERC 213 is a smart, multipurpose refrigeration controller with temperature and defrost management,

More information

Advanced temperature controller for cold rooms

Advanced temperature controller for cold rooms GB 1652H4A02 Ed.03 AKO-16524A Advanced temperature controller for cold rooms User manual Index Page Presentation...3 Warnings...3 Maintenance...3 Description...4 Installation...6 Wiring...7 Installation

More information

REFRIGERATED ROOM & TEMPERATURE/HUMIDITY CONTROLLERS

REFRIGERATED ROOM & TEMPERATURE/HUMIDITY CONTROLLERS SECTION INDEX FUNCTIONS MODELS XLR100 COOL MATE - NT, MT AND LT APPLICATIONS - SERIAL OUTPUT Advanced multifunction controllers for NT refrigerated rooms XLR130 Advanced multifunction controllers for MT

More information

02/11/2015

02/11/2015 CTH 46 - CTD 43 / 46 CTD 46 Part number 89422108 CTH 46 Heating / cooling function Measurement and setpoint display CTD 43 Heating or cooling function Measurement display Measurement deviation display-setpoint

More information

CAREL IR33+ CONTROLLER

CAREL IR33+ CONTROLLER CAREL IR33+ CONTROLLER Programming Instructions The Carel IR33+ controller has a two-level menu system for programming the operation of the case; Level 1 and Level 2 program settings. Unlike IR33, the

More information

POCKET GUIDE 2011 ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS

POCKET GUIDE 2011 ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS POCKET GUIDE 2011 ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS products index 2 expert nano 06 plus200 EXPERT DATALOGGER 24 ecp_ base4 u vd 40 PEV pulse 60 expert nano 200 NANO 1CF 08 Plus300 EXPERT

More information

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL WATER HEATER ELECTRONIC CONTROLLER USER MANUAL UPPER LED READOUT LED ICONS LOWER LED READOUT PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - Web www.pvi.com - Phone 1-800-433-5654 Page 1 / 7 PV500-40 03/17

More information

eed quality electronic design USER s MANUAL

eed quality electronic design USER s MANUAL eed quality electronic design www.dem-it.com eed www.qeed.it info@qeed.it ANALOG SIGNAL DISPLAY Q-DISP-T USER s MANUAL The displays Q-DISP-T, prepared for mounting on the back panel, 96x48mm, will allow

More information

EM300(LX) electronic digital indicator. Alarm (IF PRESENT) ON for active alarm; blinking for silenced alarm that is still present

EM300(LX) electronic digital indicator. Alarm (IF PRESENT) ON for active alarm; blinking for silenced alarm that is still present EM3(LX) GB code 9IS4349 rel. 66 electronic digital indicator USER INTERFACE The user has a display and four buttons for controlling instrument status and programming. BUTTONS AND MENUS ACCESSING UP Button

More information

FX BLAST CHILLER ISO ISO 9001

FX BLAST CHILLER ISO ISO 9001 FX BLAST CHILLER ISO 14001 ISO 9001 Contents Environmental Management Policy 1 Disposal Requirements 1 Cabinet description 2 Controller Description Controller Operation 2 to 3 Alarms & Warnings 4 Parameter

More information

<IMG INFO> 339,95 195, ,35 14,15-1. ENERGY 400 Four Steps Chiller Heat Pump Controller

<IMG INFO> 339,95 195, ,35 14,15-1. ENERGY 400 Four Steps Chiller Heat Pump Controller 339,95 195,85 0 2 89,35 14,15-1 Four Steps Chiller Heat Pump Controller 1 CONTENTS 1 Contents...2 2 How to use this manual...4 3 Introduction...5 3.1 Components...5 3.1.1 Basic Module...5 3.1.2

More information

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17 Q-SMART MODBUS KIT Modbus Protocol & Parameters Cod.001085120EN rev.a ed.08/2018 Q-SMART Software Version AE17 Index 1 Modbus Protocol on Q-SMART... 4 1.1 Broadcasting... 4 1.2 Data Protection... 4 1.3

More information

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL Microener- Copyright 2010 FW 2.1 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

User Guide ems25plus. Page 1. Normal operation. Product interface

User Guide ems25plus. Page 1. Normal operation. Product interface Page 1 Product interface rmal operation During normal operation, EMS controllers display the information below. Assuming the product temperature is correct when the outlet is open, this means that the

More information

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack Master Catalog 125 Temperature Controls Section A Product/Technical Bulletin Issue Date 1098 MR4PMUHV Electronic Temperature/Defrost Control with Relay Pack The MR series temperature controls are designed

More information

QUICK REFERENCE GUIDE SERIES IC100CX FW 1.8 (rel. 1.0)

QUICK REFERENCE GUIDE SERIES IC100CX FW 1.8 (rel. 1.0) QUICK REFERENCE GUIDE SERIES IC1CX FW 1.8 (rel. 1.) INDEX 1. General Advices 3 2. User Interface 4 3. Remote Keyboard VICX61 5 4. Display visualization 6 5. Silencing the Buzzer 6 6. First Installing

More information

T14 AS1 T20 T40 T24. ISO 9001 Cert. N 0412/2 SERVICE MANUAL. Cod /0-03/ Rev. 000

T14 AS1 T20 T40 T24. ISO 9001 Cert. N 0412/2 SERVICE MANUAL. Cod /0-03/ Rev. 000 B L A S T C H I L L E R S T4 MT AS T T24 T4 T2 ISO 9 Cert. N 42/2 SERVICE MANUAL Cod. 736/ - 3/24 - Rev. WARNING!!! THE FOLLOWING OPERATIONS AND THOSE HIGHLIGHTED BY THIS SYMBOL MUST NOT BE PERFORMED BY

More information

Digital Controller XR70CX. Operating Manual. 5/10 Rev. B

Digital Controller XR70CX. Operating Manual. 5/10 Rev. B Digital Controller XR70CX Operating Manual 5/10 Rev. B 139734 Contents General Warnings 3 General Description 3 Regulation 3 Defrost 3 Fans 4 Front Panel Commands 4 Parameters 6 Installation and Mounting

More information

(12) Patent Application Publication (10) Pub. No.: US 2004/ A1

(12) Patent Application Publication (10) Pub. No.: US 2004/ A1 (19) United States US 20040206110A1 (12) Patent Application Publication (10) Pub. No.: US 2004/0206110 A1 Lifson et al. (43) Pub. Date: (54) VAPOR COMPRESSION SYSTEM WITH BYPASS/ECONOMIZER CIRCUITS (76)

More information

ECH 985. Electronic controller for heat pumps used in residential hot water application

ECH 985. Electronic controller for heat pumps used in residential hot water application ECH 985 Electronic controller for heat pumps used in residential hot water application Introduction General Description ECH 985 is a heat pump for the following kinds of applications: water-water water-air

More information

TLY 35 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER. OPERATING INSTRUCTIONS cod.: ISTR MTLY35ENG02 Ver. 02

TLY 35 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER. OPERATING INSTRUCTIONS cod.: ISTR MTLY35ENG02 Ver. 02 TLY 35 MICROPROCESSOR-BASED DIGITAL ELECTRIC FREEZER CTROLLER OPERATING INSTRUCTIS cod.: ISTR MTLY35ENG02 Ver. 02 ASC TECNOLOGIC S.r.l. VIALE INDIPENDENZA 56 27029 VIGEVANO (PV) ITALY TEL.: +39 0381 69871

More information

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB Summary 1 CONNECTIONS... 8 1.1 TEMPERATURE PROBES...8 1.2 PRESSURE PROBES...9 1.3 LOW VOLTAGE DIGITAL INPUTS...10 1.4 LIVE DIGITAL INPUTS...11 1.5 RELAY OUTPUTS...12 2 VOLTAGE/FREQUENCY INPUT...13 3 POWER

More information

ENERGY 200 Electronic Control for mono & bi- Compressor CHILLERS. User Manual

ENERGY 200 Electronic Control for mono & bi- Compressor CHILLERS. User Manual Electronic Control for mono & bi- Compressor CHILLERS User Manual 2/55 1 CONTENTS 1 Contents...3 2 How to use this manual...5 3 Introduction...6 3.1 Components...6 3.1.1 Basic module...6 3.1.2 Keyboards...6

More information

L SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M

L SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M Litho U.S.A. 2 L SERIES UNITS 54,52M /2 Supersedes 54,4M M 6 VERSION 4. INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M 6 VERSION 4. INTEGRATED MODULAR CONTROL USED IN L SERIES THROUGH TON UNITS TABLE

More information

OPERATING INSTRUCTIONS. G214 Software - Version 4

OPERATING INSTRUCTIONS. G214 Software - Version 4 OPERATING INSTRUCTIONS G214 Software - Version 4 Control Panel (G-214 Controller) 1 2 3 4 5 6 7 8 19 9 10 11 12 13 14 15 16 17 18 Control Panel Description 1. Probe shown in Main screen 2. Probe temperature

More information

Index. 1. General description of the application Types of units controlled Types of regulation Condensation...

Index. 1. General description of the application Types of units controlled Types of regulation Condensation... LCS pco ADVANCED MICROPROCESSOR USER MANUAL GB Index 1. General description of the application... 4 1.1. Types of units controlled...4 1.2. Types of regulation...4 1.3. Condensation...4 1.4. Safety devices

More information

Technical Support Bulletin Nr. 3 Heating

Technical Support Bulletin Nr. 3 Heating Technical Support Bulletin Nr. 3 Heating Contents! Introduction 1! Heating Traditional applications for Eliwell products 1! Space heating: 2! Heat pumps 2! Types of heat pump machine 3! Water to water

More information

Temperature and moisture controller for cold room store

Temperature and moisture controller for cold room store GB 1662H402 Ed.01 AKO-16624 Temperature and moisture controller for cold room store User Manual Index Page Warnings...3 Wiring...3 Maintenance...3 Description...4 Installation...6 Initial configuration...7

More information

Operation manual. Rooftop Packaged Unit

Operation manual. Rooftop Packaged Unit Operation manual Rooftop Packaged Unit odels: UATYQ20ABAY1 UATYQ25ABAY1 UATYQ30ABAY1 UATYQ45ABAY1 UATYQ50ABAY1 UATYQ55ABAY1 UATYQ65ABAY1 UATYQ75ABAY1 UATYQ90ABAY1 UATYQ110ABAY1 UATYQ115ABAY1 UATYQ20AFC2Y1

More information

technical bulletin Control Link RSC Installation Instructions

technical bulletin Control Link RSC Installation Instructions COMPU TER PROCE SS CONTRO L S Overview The Control Link Refrigeration System Controller (CL-RSC) is an electronic device that can control all functions of a single-compressor refrigeration system, including

More information

TER Active Room Temperature Sensor (Controller),

TER Active Room Temperature Sensor (Controller), Product sheet SN1.415 Type TER TER Active Room Temperature Sensors (Controllers) The TER active sensors are designed to detect temperature in the room spaces. The TER sensors have linear 0..10V signals

More information

EasyTech.One Temperature Controller for Pellet Burner

EasyTech.One Temperature Controller for Pellet Burner EasyTech.One Temperature Controller for Pellet Burner Burner 1 INTRODUCTION... 3 2 ELECTRICAL CONNECTIONS... 3 3 CONTROL PANEL: USE AND FUNCTIONS... 5 3.1 LED... 5 3.2 BUTTONS... 5 3.3 ALARMS... 5 3.1

More information

ER65 - Mini Rack Controller Electronic Refrigeration Line

ER65 - Mini Rack Controller Electronic Refrigeration Line PB_ER65_ 00 ER65 - Mini Rack Controller Electronic Refrigeration Line Device is a multi-stage digital controller. It is typically applied to small refrigeration rack units piloting compressors or condenser

More information

DFZ. Cabin Control Description and operation

DFZ. Cabin Control Description and operation I DFZ Cabin Control Description and operation Index 1. Description of the control unit 1.1. Switching on the control unit 1.2. Diesel operation setting-up 1.3. Setting-up of the operation set point 1.4.

More information

LCF Touch Modbus Datasheet Application Security Advice Caution

LCF Touch Modbus Datasheet Application Security Advice Caution LCF Touch Modbus Electronic Fan Coil Thermostat with Touch Display (Flush mounting) Datasheet Subject to technical alteration Issue date: 3.11.214 Application Modern design flush mounting fan coil room

More information

IPC108D - IPC108E (V.2.0)

IPC108D - IPC108E (V.2.0) IPC108D - IPC108E (V.2.0) APPLICATION GUIDE INDEX 1. IMPORTANT RECOMMENDATIONS 6 1.1 PRODUCT DISPOSAL (WEEE) 7 2. GENERALITIES 8 3. AVAILABLE APPLICATION CONFIGURATIONS 8 3.1 MAIN FUNCTIONS 9 4. SUPERVISION

More information

EXD-HP1/2 Stand-alone Superheat/Economizer Controller

EXD-HP1/2 Stand-alone Superheat/Economizer Controller Technical Bulletin EXD-HP1/2 are stand-alone universal superheat and or economizer controllers for heat pumps, heating units, air conditioning and precision cooling such as telecom and shelter applications.

More information

IP 65 FRONT. Serial programming. Protection level FAST FREEZING (ON/OFF) TC-900e POWER ECONOMIC SETPOINT(ON/OFF) DEFROST (ON/OFF) FUNCTIONS LOCKDOWN

IP 65 FRONT. Serial programming. Protection level FAST FREEZING (ON/OFF) TC-900e POWER ECONOMIC SETPOINT(ON/OFF) DEFROST (ON/OFF) FUNCTIONS LOCKDOWN ONENT evolution Have this manual in the palm of your hand by FG Finder application. TCe POWER Ver. Fast Freezing DIGITAL CONTROLLER FOR REFRIGERATION AND OST Functions lockdown Control functions shutdown

More information

TLW 24 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER OPERATING INSTRUCTIONS. 1.1 General description

TLW 24 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER OPERATING INSTRUCTIONS. 1.1 General description TLW 24 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER OPERATING INSTRUCTIONS Vr. 03 (ENG) - 15/07 - cod.: ISTR-TLW24-ENG03 ASCON TECLOGIC S.r.l. Viale Indipendenza 56 27029 VIGEVA (PV) ITALY

More information

Krypton K CL2. Measuring and control system for free chlorine. applications. description. Low maintenance by automatic sensor cleaning

Krypton K CL2. Measuring and control system for free chlorine. applications. description. Low maintenance by automatic sensor cleaning Low maintenance by automatic sensor cleaning Pressure-proof up to 6 bar at 20 C Higher safety by integrated flow monitoring applications Drinking Water / Beverages Food Industry Disinfection Cooling And

More information

dixel Installing and Operating Instructions PRELIMINAY

dixel Installing and Operating Instructions PRELIMINAY . GENERAL WARNING XW6K - AFV PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument shall not be used

More information

New LAE controller for Plug-in cabinets

New LAE controller for Plug-in cabinets From: Lonardi [MC] To: Price-list owners Ref.: P-6.006/01 Date: 19/03/01 New LAE controller for Plug-in cabinets Dear Sirs, with the aim of a continuous improvement we are going to introduce our new LAE

More information

EWTB 1000(/C,/S) rel. 1/97 ing freezer controls

EWTB 1000(/C,/S) rel. 1/97 ing freezer controls EWTB 1(C,S) rel. 197 ing freezer controls WHAT IT IS The EWTB 1, EWTB 1C (Clock) and EWTB 1S (Serial) are microprocessor based digital instruments used for refrigerator and freezer control; the are designed

More information

INSTALLATION & USER MANUAL

INSTALLATION & USER MANUAL INSTALLATION & USER MANUAL HC Digital Automatic Humidistat (Y3760) CONTROLS 506808-01 3/2016 Supersedes 6/2011 picture goes here THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE NOTICE

More information

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions Worldwide upplier of Gas Detection olutions GfG Instrumentation 1194 Oak Valley Drive, uite 20 Ann Arbor, MI 48108 800-959-0329 tel 734-769-1888 fax email: info@gfg-inc.com GMA4100-DP Control Panel Operation

More information

TMEF Series. SKOPE Vertical Freezer. User Manual

TMEF Series. SKOPE Vertical Freezer. User Manual TMEF Series SKOPE Vertical Freezer MAN10132 Rev. 1.0 Oct. 2010 TMEF Series SKOPE Vertical Freezer Type: (CAREL ir32 Controller) MAN10132 Rev. 1.0 Oct. 2010 2010 SKOPE Industries Limited. All rights reserved.

More information

PCR-300 PCR-300 RC. Installation and Operating Instructions

PCR-300 PCR-300 RC. Installation and Operating Instructions PCR-300 PCR-300 RC Installation and Operating Instructions Electronic refrigeration control EB-PCR-04 EN1H-1924GE23 R1207 TABLE OF CONTENTS 11 Unpacking the unit and conditions of use 3 12 General instructions

More information

Temperature - Humidity - Pressure

Temperature - Humidity - Pressure TEMPERATURE-HUMIDITY-PRESSURE INDICATORS XA100C Configurable digital indicators for temperature, humidity or pressure C: 32x74mm DC- TBXABDA100 XA100C -0C0PU PTC NTC inputs 12V DC- TBXABCA100 XA100C -0C0TU

More information

MR3CCUHV Temperature/Defrost Control

MR3CCUHV Temperature/Defrost Control Master Catalog 125 Temperature Controls Section A Product/Technical Bulletin Issue Date 0401 MR3CCUHV Temperature/Defrost Control The MR3CCUHV Temperature/Defrost Control is designed to control the temperature

More information

TLY 25 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR TECNOLOGIC S.p.A.

TLY 25 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR TECNOLOGIC S.p.A. TLY 25 MICROPROCESSOR-BASED DIGITAL ELECTRIC FREEZER CTROLLER OPERATING INSTRUCTIS Vr. 01 (ENG) - cod.: ISTR 06454 TECNOLOGIC S.p.A. VIA INDIPENDENZA 56 27029 VIGEVANO (PV) ITALY TEL.: +39 0381 69871 FAX:

More information

Gas Detection System TOX ALARM DG2000-Garage

Gas Detection System TOX ALARM DG2000-Garage Gas Detection System TOX ALARM DG2000-Garage Gas Detection System 32 independent programmable channels 2 programmable alarm levels for each gas = up to 6 for each channel LCD alphanumeric display of gas

More information

TLY 27 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR TECNOLOGIC S.p.A.

TLY 27 MICROPROCESSOR-BASED DIGITAL ELECTRONIC FREEZER CONTROLLER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR TECNOLOGIC S.p.A. TLY 27 MICROPROCESSOR-BASED DIGITAL ELECTRIC FREEZER CTROLLER FOREWORD OPERATING INSTRUCTIS Vr. 01 (ENG) - cod.: ISTR 06656 TECNOLOGIC S.p.A. VIA INDIPENDENZA 56 27029 VIGEVANO (PV) ITALY TEL.: +39 0381

More information

MultiMeter 44. Transmitter-regulator with 1, 2 or 3 channels. Quality at a reasonable price

MultiMeter 44. Transmitter-regulator with 1, 2 or 3 channels. Quality at a reasonable price MultiMeter 44 Transmitter-regulator with 1, 2 or 3 channels MultiMeter 44 is a modular meter that can be configured with one, two or three channels. It can be delivered with only one measuring channel,

More information

DFZ. In Cab Control Description and Operation

DFZ. In Cab Control Description and Operation DFZ In Cab Control Description and Operation Index 1. Description of the control unit 1.1. Switching on the control unit 1.2. Diesel operation setting-up 1.3. Setting-up of the operation set point 1.4.

More information

Series Temperature Controller Instruction Sheet

Series Temperature Controller Instruction Sheet Series Temperature Controller Instruction Sheet Thank you very much for purchasing DELTA A Series. Please read this instruction sheet before using your A series to ensure proper operation and please keep

More information

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction. Introduction The UL listed Phone-A-Stat (model # 7632 ) is designed and approved for the safe operation of remotely controlling four independent loads, such as a sprinkler system or a water heater via

More information

dixel Installing and Operating Instructions

dixel Installing and Operating Instructions XW20K AND T620 V620 CX620 1. GENERAL WARNING PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument

More information