APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1)
|
|
- Juniper Pope
- 5 years ago
- Views:
Transcription
1 Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1) Table 1. European Reciprocating Chiller (CR1). Point Type Description Range/Units 01 LAO Device Address 02 LAO Application Number LAI Circuit 1 Condenser Approach Temperature F 04 LAI Condenser 1 Pressure psig 05 LAI Current Alarm Circuit 1 Condenser Pressure psig 06 LAI Current Alarm Circuit 1 Evaporator Pressure psig 07 LAI Current Alarm Circuit 1 Liquid Line Temperature F 08 LAI Current Alarm Circuit 1 Suction Temperature F 09 LAI Circuit 1 Alarm See Table 2 10 LAI Evaporator 1 Pressure psig 11 LAI Circuit 1 Liquid Line Temperature F 12 LAI Circuit 1 Previous Alarm See Table 2 13 LAI Circuit 1 Status See Table 3 14 LAI Circuit 1 Subcooling F 15 LAI Circuit 1 Suction Temperature F 16 LAI Circuit 1 Superheat F 17 LAI Circuit 2 Condenser Approach Temperature F 18 LAI Condenser 2 Pressure psig 19 LAI Current Alarm Circuit 2 Condenser Pressure psig 20 LAI Current Alarm Circuit 2 Evaporator Pressure psig 21 LAI Current Alarm Circuit 2 Liquid Line Temperature F 22 LAI Current Alarm Circuit 2 Suction Temperature F 23 LAI Circuit 2 Alarm See Table 2 24 LAI Evaporator 2 Pressure psig 25 LAI Circuit 2 Liquid Line Temperature F continued on next page... Siemens Building Technologies, Inc. Page 1 of 6
2 Table 1. European Reciprocating Chiller (CR1). Point Type Description Range/Units 26 LAI Circuit 2 Previous Alarm See Table 2 27 LAI Circuit 2 Status See Table 3 28 LAI Circuit 2 Subcooling F 29 LAI Circuit 2 Suction Temperature F 30 LAI Circuit 2 Superheat F 31 LAI Compressor 1 Operating Hours Hours 32 LAI Compressor 1 Starts Starts 33 LAI Compressor 2 Operating Hours Hours 34 LAI Compressor 2 Starts Starts 35 LAI Compressor 3 Operating Hours Hours 36 LAI Compressor 3 Starts Starts 37 LAI Compressor 4 Operating Hours Hours 38 LAI Compressor 4 Starts Starts 39 LAI Entering Condenser Water Temperature F 40 LAI Leaving Condenser Water Temperature F 41 LAI Entering Evaporator Water Temperature F 42 LAI Leaving Evaporator Water Temperature F 43 LAI Outside Air Temperature F 44 LAI Stage Of Cooling LAI Percent Motor Curent 0 100% 46 LAI Unit Status See Table 4 47 LDO Network Command Enable/Disable Enable/Disable 48 LAO Network Demand Limit 0 100% 49 LAO Network Evaporator Leaving Temperature Reset 0 100% 50 LDO Clear Circuit 1 Alarm No/Yes 51 LDO Clear Circuit 2 Alarm No/Yes 52 LAO Entering Evaporator Temperature Set Point F 53 LAO Evaporator Leaving Water Temperature Set Point F 54 LAO Maximum Chilled Water Reset Set Point 0 90 F 55 LAO Reset Option Set Point See Table 5 99 LDI Communication Failure Normal/Failed Page 2 of 6 Siemens Building Technologies, Inc.
3 Table 2. Alarms (Points 9, 12, 23 and 26). Value Description for Circuit 1 Description for Circuit 2 0 None. Also, Set Point to This Value to Clear Alarms. None. Also, Set Point to This Value to Clear Alarms. 1 High Condenser Pre-alarm Hold Stage (Cleared) High Condenser Pre-alarm Hold Stage (Cleared) 2 High Condenser Pre-alarm Stage Down (Cleared) High Condenser Pre-alarm Stage Down (Cleared) 3 Freeze Refrigerant Pre-alarm Stage Down (Cleared) Freeze Refrigerant Pre-alarm Stage Down (Cleared) 4 Loss of Chilled Water Flow (Cleared) Loss of Chilled Water Flow (Cleared) 5 No Pump-down (Cleared) No Pump-down (Cleared) 6 Refrigerant Freeze Protect (Cleared) Refrigerant Freeze Protect (Cleared) 7 Low Evaporator Pressure (Cleared) Low Evaporator Pressure (Cleared) 8 Compressor 4 Motor Protect (Cleared) Compressor 4 Motor Protect (Cleared) 9 Compressor 3 Motor Protect (Cleared) Compressor 3 Motor Protect (Cleared) 10 Compressor 2 Motor Protect (Cleared) Compressor 2 Motor Protect (Cleared) 11 Compressor 1 Motor Protect (Cleared) Compressor 1 Motor Protect (Cleared) 12 Compressor 4 Low Oil Pressure (Cleared) Compressor 4 Low Oil Pressure (Cleared) 13 Compressor 3 Low Oil Pressure (Cleared) Compressor 3 Low Oil Pressure (Cleared) 14 Compressor 2 Low Oil Pressure (Cleared) Compressor 2 Low Oil Pressure (Cleared) 15 Compressor 1 Low Oil Pressure (Cleared) Compressor 1 Low Oil Pressure (Cleared) 16 High Condenser Pressure (Cleared) High Condenser Pressure (Cleared) 17 Mechanical High Pressure (Cleared) Mechanical High Pressure (Cleared) 18 Bad Evaporator Pressure Sensor (Cleared) Bad Evaporator Pressure Sensor (Cleared) 19 Bad Condenser Pressure Sensor (Cleared) Bad Condenser Pressure Sensor (Cleared) 20 Bad Phase/Volts (Cleared) Bad Phase/Volts (Cleared) 21 Chilled Water Freeze Protect (Cleared) Chilled Water Freeze Protect (Cleared) 22 Bad Voltage Ratio Sensor (Cleared) Bad Voltage Ratio Sensor (Cleared) 23 Bad Evaporator Leaving Temperature Sensor (Cleared) Bad Evaporator Leaving Temperature Sensor (Cleared) 129 High Condenser Pre-alarm Hold Stage (Active) High Condenser Pre-alarm Hold Stage (Active) 130 High Condenser Pre-alarm Stage Down (Active) High Condenser Pre-alarm Stage Down (Active) 131 Freeze Refrigerant Pre-alarm Stage Down (Active) Freeze Refrigerant Pre-alarm Stage Down (Active) 132 Loss of Chilled Water Flow (Active) Loss of Chilled Water Flow (Active) 133 No Pump-down (Active) No Pump-down (Active) 134 Refrigerant Freeze Protect (Active) Refrigerant Freeze Protect (Active) 135 Low Evaporator Pressure (Active) Low Evaporator Pressure (Active) 136 Compressor 4 Motor Protect (Active) Compressor 4 Motor Protect (Active) continued on next page... Siemens Building Technologies, Inc. Page 3 of 6
4 Table 2. Alarms (Points 9, 12, 23 and 26). Value Description for Circuit 1 Description for Circuit Compressor 3 Motor Protect (Active) Compressor 3 Motor Protect (Active) 138 Compressor 2 Motor Protect (Active) Compressor 2 Motor Protect (Active) 139 Compressor 1 Motor Protect (Active) Compressor 1 Motor Protect (Active) 140 Compressor 4 Low Oil Pressure (Active) Compressor 4 Low Oil Pressure (Active) 141 Compressor 3 Low Oil Pressure (Active) Compressor 3 Low Oil Pressure (Active) 142 Compressor 2 Low Oil Pressure (Active) Compressor 2 Low Oil Pressure (Active) 143 Compressor 1 Low Oil Pressure (Active) Compressor 1 Low Oil Pressure (Active) 144 High Condenser Pressure (Active) High Condenser Pressure (Active) 145 Mechanical High Pressure (Active) Mechanical High Pressure (Active) 146 Bad Evaporator Pressure Sensor (Active) Bad Evaporator Pressure Sensor (Active) 147 Bad Condenser Pressure Sensor (Active) Bad Condenser Pressure Sensor (Active) 148 Bad Phase/Volts (Active) Bad Phase/Volts (Active) 149 Chilled Water Freeze Protect (Active) Chilled Water Freeze Protect (Active) 150 Bad Voltage Ratio Sensor (Active) Bad Voltage Ratio Sensor (Active) 151 Bad Evaporator Leaving Temperature Sensor Active) Bad Evaporator Leaving Temperature Sensor (Active) 137 Compressor 3 Motor Protect (Active) Compressor 3 Motor Protect (Active) 138 Compressor 2 Motor Protect (Active) Compressor 2 Motor Protect (Active) 139 Compressor 1 Motor Protect (Active) Compressor 1 Motor Protect (Active) 140 Compressor 4 Low Oil Pressure (Active) Compressor 4 Low Oil Pressure (Active) 141 Compressor 3 Low Oil Pressure (Active) Compressor 3 Low Oil Pressure (Active) 142 Compressor 2 Low Oil Pressure (Active) Compressor 2 Low Oil Pressure (Active) 143 Compressor 1 Low Oil Pressure (Active) Compressor 1 Low Oil Pressure (Active) 144 High Condenser Pressure (Active) High Condenser Pressure (Active) 145 Mechanical High Pressure (Active) Mechanical High Pressure (Active) 146 Bad Evaporator Pressure Sensor (Active) Bad Evaporator Pressure Sensor (Active) 147 Bad Condenser Pressure Sensor (Active) Bad Condenser Pressure Sensor (Active) 148 Bad Phase/Volts (Active) Bad Phase/Volts (Active) 149 Chilled Water Freeze Protect (Active) Chilled Water Freeze Protect (Active) 150 Bad Voltage Ratio Sensor (Active) Bad Voltage Ratio Sensor (Active) 151 Bad Evaporator Leaving Temperature Sensor Active) Bad Evaporator Leaving Temperature Sensor (Active) Page 4 of 6 Siemens Building Technologies, Inc.
5 Table 3. Circuit Status (Points 13 and 27). Value Description for Circuit 1 Status Description for Circuit 2 Status 0 Off S-1 System Switch Off S-1 System Switch 1 Off Manual Set Point Off Manual Set Point 2 Off Alarm Off Alarm 3 Off Pump-down Switch Off Pump-down Switch 4 Off Wait for Cycle Off Wait for Cycle 5 Off Ready to Start Off Ready to Start 6 Start Pump-down Start Pump-down 7 Pump-down Pump-down 8 Wait for Cooling Pressure Wait for Cooling Pressure 9 Cooling Cooling Table 4. Unit Status (Point 46). Value Description 0 Off Manual Set Point 1 Off S-1 Switch 2 Off Remote Communication 3 Off Remote Switch 4 Off Time Schedule 5 Off Alarm 6 Off Pump-down Switches 7 Off Ready to Start 8 Starting 9 Waiting for Flow 10 Waiting for Load 11 Cooling Stage-up 12 Cooling Stage-down 13 Cooling Staging 14 Manual Cooling Staging Siemens Building Technologies, Inc. Page 5 of 6
6 Table 5. Reset Option (Point 48). Value Description 0 No Chilled Water Reset (Default) 1 Return Chilled Water Reset. Constant Return Chilled Water Temperature Set Point maintained ma Chilled Water Reset. Resets Chilled Water Set Point based on 4 20 ma signal. A signal less than 4 ma results in no reset of Chilled Water Temperature Set Point. A signal greater than 4 ma results in a linear reset between Chilled Water Set Point and the Maximum Chilled Water Reset Set Point plus the Chilled Water Set Point. 3 Network Chilled Water Reset. Resets Chilled Water Set Point based on the network evaporator leaving temperature reset (Point 49). A signal of 0 100% results in a linear reset between the Chilled Water Set Point and the maximum Chilled Water Reset Set Point plus the Chilled Water Set Point. 4 Ice Chilled Water Reset. Resets the Chilled Water Set Point (typically 23 F) based upon a 4 20 ma Signal. A signal less than 4 ma results in no reset of Chilled Water Temperature Set Point. A signal greater than 4ma results in a Chilled Water Set Point equal to the set point plus the maximum Chilled Water Reset Set Point (typically 22 F). Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. Printed in the U.S.A Deerfield Parkway Buffalo Grove, IL Page 6 of 6 U.S.A.
APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller
Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Table 1. Series 200 Centrifugal Chiller. Point Type Range/Units 01
More informationMcQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)
Point Map December 1, 2004 Systems Integration McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV) Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller
More informationMultistack Modbus Driver: Standard Unit
Point Map October 27, 2006 Systems Integration Multistack Modbus Driver: Standard Unit Table 1. Multistack Modbus Standard APOGEE Points, Application Number: 4726. 1 LAO Address 2 LAI Application 3 LDI
More informationAPOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit
Point Map Rev. 2, July, 2002 Systems Integration APOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit Table 1. CCT DX Unit, Analog Points. 01 LAI Return Air Temperature F 02 LAI Supply Air
More informationMcQuay BACnet Solution: Microtech II Self-contained Unit Controller with Discharge Air Control (DAC)
Point Map December 1, 2004 Systems Integration McQuay BACnet Solution: Microtech II Self-contained Unit Controller with Discharge Air Control (DAC) Table 1. Microtech II Self-contained Unit Controller
More informationMcQuay Microtech III BACnet MS/TP Application 4181 Point Map
Point Map June 2009 Systems Integration McQuay Microtech III BACnet MS/TP Application 4181 Point Map APOGEE Open Processor with McQuay Microtech III BACnet MS/TP Driver: Microtech III Applied Rooftop Unit
More informationHoneywell Modbus Solution: 7800 Series Burner Controller through S7810M Modbus Module
Point Map August 1, 2006 Systems Integration Honeywell Modbus Solution: 7800 Series Burner Controller through S7810M Modbus Module Table 1. 7800 Series Burner Controller through S7810M Modbus Moduler APOGEE
More informationLONWORKS Solution for Orion PT-LON-Link
Point Map February 5, 2008 Systems Integration LONWORKS Solution for Orion PT-LON-Link Table 1. Orion PT-Link-LON APOGEE Points, Application Number: 9158, Program ID: 90:00:95:47:1E:02:04:B3. 1 LAI AppSoftVer
More informationMicroTech Water-Cooled Screw Chiller Controller
BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software
More informationMicroTech Series-200 Flooded Screw Chiller
Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D
More informationOpen Protocol Data Communications
MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way
More informationMicroTech Series 200 Centrifugal Chiller
Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History
More informationFieldServer Driver - Serial FS McQuay Microtech Open Protocol
Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls
More informationPneumercator Driver: TMS 2000/3000
Point Map November 21, 2006 Systems Integration Pneumercator Driver: TMS 2000/3000 System Table 1. System Point Map. Application 5235. 1 AI Address Point (Read Only) 2 AI Application Point (Read Only)
More informationCase 8 Basic Performance of Screw Compressor
Case 8 Basic Performance of Screw Compressor Copy Right By: Thomas T.S. Wan ) June 24, 2010 All Rights Reserved Case Background: The basic rating and performance given by a compressor manufacturer is usually
More informationHVAC Fundamentals & Refrigeration Cycle
HVAC Fundamentals & Refrigeration Cycle Change of State of Water & the Refrigeration Cycle Change of State Water The Basic Refrigeration Cycle Types of DX Systems The Chilled water System The Cooling Tower
More informationPOWERS Pneumatic Thermostat Covers
Technical Instructions Document No. A6V11225047 Pneumatic Thermostat s 192-2xx Plastic 192-2xxW Plastic 192-3xx 856-0xx D Series Description Proven to provide fast response and highly accurate temperature
More informationThe Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.
The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative
More informationAir-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a
Air-Cooled Variable Speed Drive Screw Chillers Super Efficient Super Quiet Cooling Capacity Range 540-1405 kw R134a World s first low sound Air-Cooled variable speed drive screw chiller The recognition
More informationPOWERS CONTROLS Pneumatic Thermostat Covers
Document No. A6V11225047 CONTROLS Pneumatic Thermostat s 192-2xx Plastic 192-2xxW Plastic 192-3xx 856-0xx D Series Description Proven to provide fast response and highly accurate temperature control, Powerstar
More informationSECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING
SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit
More informationBASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)
BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION Business Name Site physical address (Street, Suburb, City) Nature of site / business operation Electricity Supplier Power factor
More informationSuction Line Accumulators
A n I S O 9 0 0 : 2 0 0 0 O r g a n i z a t i o n Refrigeration Technologies Suction Line Accumulators With or without heat exchanger R4a R404A R07A R407C R22 R40A R08b R77 CO 2 Approved by European standards
More informationSales and Engineering Data Sheet ED
Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet
More informationCONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN
CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER Table of Contents - 2 - INTRODUCTION... 3 OPERATING LIMITS:... 4 CONTROLLER FEATURES... 4 GENERAL DESCRIPTION... 5 CONTROL
More informationSECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS
SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure
More informationSECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES
SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure
More information30GN FLOTRONIC II AIR-COOLED CHILLERS
30GN-19SB 30GN040-110 FLOTRONIC II AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GN-19SB Supersedes 30GN-6SB, 30GN-7SB, 30GN-8SB, Printed
More informationModular Chiller Systems. Application Guide
Modular Chiller Systems Application Guide Table of Contents Introduction.... 1 References/Nomenclature Conventions... 2 Terms & Definitions.... 2 Module Size Selection...3 Water Source, Cooling Only and
More information30GT FLOTRONIC AIR-COOLED CHILLERS
30GT-41SB 30GT040-110 FLOTRONIC AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GT-41SB Supersedes 30GT-21SB, 30GT-22SB, 30GT-23SB, Printed
More informationHVAC Water chiller selection and optimisation of operation
HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water
More informationFigure 1: Schematic of internal heat exchanger vapor-injection cycle
Vapor-injection technique Development Guideline 1. Introduction This guideline shows the advantage and characteristics of Mitsubishi vapor injected-scroll compressor. The vapor injected-scroll compressor
More informationOPERATING MANUAL Enertronic Control System 2
OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861
More informationGeneSys Air-Cooled Screw Compressor Chiller
Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through
More informationAir-Cooled Global Chiller
Product Manual PM 970 Group: Chiller Effective: June 1997 Supersedes: None Air-Cooled Global Chiller Type AGR 055AS through 100AS Reciprocating Compressor with R-22 60 hertz 1997 McQuay International Table
More informationMetasys Integrator McQuay Application
Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator McQuay Application Introduction Page * Application Details * Component
More informationCommercial and Technical Data
Chillers Commercial and Technical Data Air Cooled Single Circuit Condensing Unit» Wide capacity range (120 kw - 490 kw)» One refrigerant circuit with single screw compressor» Two sound versions available»
More informationMidwest Industrial Initiative Webinar: Industrial Refrigeration
Midwest Industrial Initiative Webinar: Industrial Refrigeration Opportunities for Energy Efficiency and Cost Savings Thursday, June 6, 2013 www.kw-engineering.com Bryan Hackett, PE kw Engineering What
More informationAir-Cooled Scroll Compressor Chiller
Air-Cooled Scroll Compressor Chiller Operation Manual OM AGZC-1 Group: Chiller Part Number: 331376301 Effective: February 2010 Supercedes: April 2009 AGZ 030CH through 190CH, Packaged AGZ 030CB through
More informationSales and Engineering Data Sheet ED
Sales and Engineering Data Sheet ED 15121-6 Group: Controls Part Number: ED 15121 Date: March 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHAE 135-2004, BACnet
More informationQ-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air
Document No. 155-755 Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air Description Features Application The Q-Series Relative Humidity and
More informationTechnical Bulletin (TB-0037)
Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant
More informationCONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN
CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN Table of Contents INTRODUCTION... 2 CONTROLLER OPERATING LIMITS:... 3 CONTROLLER FEATURES... 3 GENERAL
More informationREFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis
REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system
More informationProdigy Flaked and Nugget Ice Machines Technical Review
CM 3 Control System Update Prodigy Flaked and Nugget Ice Machines Technical Review Evaporator Assembly Behind Ice Chute Assembly Fan Blade Control Panel Water Reservoir Air Filter Compressor Ice Chute
More informationCONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN
CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN - 2 - Table of Contents INTRODUCTION... 2 CONTROLLER OPERATING LIMITS:... 3 CONTROLLER FEATURES... 3
More informationSmardt vs. McQuay Comparison of Standard Options and Other Benefits < 400 tons
Smardt vs. McQuay Comparison of Standard Options and Other Benefits < 400 tons Mike Hayes Director of Sales Smardt vs. McQuay Staging valves for models with 3 or more compressors Level sensor exv control
More informationThomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.
Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration
More informationTechnical Instructions Document No. CE1N1961 March 17, Room CO 2 and Air Quality Sensors. Description. Features. Application
Document No. CE1N1961 QPA20 Room CO 2 and Air Quality Sensors Description The Q-Series Room Carbon Dioxide (CO 2 ) and Air Quality Sensors are especially suited for applications where precise, stable carbon
More informationCase 13 Food Storage & Processing Center
Case 13 Food Storage & Processing Center Copy Right By: Thomas T.S. Wan ( ) Feb. 2, 2002 All Rights Reserved Case Background: The refrigeration system is for a food processing and storage facility. The
More informationBasic Principals of Air conditioning By Dr. Esam Mejbil Abed
REPUBLIC OF IRAQ Ministry of Higher Education & Scientific Research University of Babylon College of Engineering Mechanical Engineering Department Basic Principals of Air conditioning By Dr. Esam Mejbil
More informationMob: +44 7855435384 Fax: Mob: +44 7855435385 +44 (0) 3300884721 TIMESHEET REPORT COFELY GDF SVEZ PAUL HOWARD - CONT. SURVEYOR SITE NAME & ADDRESS (PLANT OWNER F-GAS) ENGINEER STEVE ORLANDO CLIENT ASSET
More informationSabroe Factory NetTraining COMP1 and sales tools
SABROE FACTORY Sabroe Factory NetTraining COMP1 and sales tools By Michael A. Jensen Sabroe Factory NetTraining COMP1 Select and templates 2 Johnson Controls PowerPoint Guidelines February 8, 2008 - basics
More informationEC3-X33 Stand-alone Superheat Controller Technical Data
Technical Data EC3-X33 is a stand-alone universal superheat controller for air conditioning, refrigeration and industrial applications such as chillers, industrial process cooling, rooftops, heat pumps,
More informationChilled Water system
Chilled Water system Introduction For large installations the Condenser, Evaporator, Compressor and Expansion device can be purchased as a package unit, known as a Chiller. The usual package consists of
More informationPartial Load Performance Of Refrigeration System
Chapter 11 Partial Load Performance Of Refrigeration System Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Hot Gas Bypass & Liquid Injection: When the compressor is under surge condition,
More informationCarnot. 2. (a) Discuss the advantages of the dense air refrigeration system over an open air refrigeration system?
UNIT-1 1. What is the difference between a refrigerator and heat pump? Derive an expression for the cop for both if they are running on reversed Carnot cycle? The above figure shows the objectives of refrigerators
More informationPowers Controls Low Temperature Detection Thermostat
Document No. 155-016P25 ET 134-22 Rev. 1, February, 2000 Powers Controls Low Temperature Detection Thermostat Description The electric Low Temperature Detection Cut-out and Alarm Thermostat is a remote
More informationFor an administrative fee of $9.97, you can get an un-locked, printable version of this book.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of
More informationMicroTech Unit Ventilator
Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This
More informationPathfinder Air-Cooled Chillers
Operating & Maintenance Manual OMM 1123 Group: Chiller Part Number: OMM 1123 Date: January 2012 Supercedes: December 2011 Rev 00 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes Models
More informationAir-Cooled Scroll Compressor Chiller
Operating and Maintenance Manual OMM 1087-1 Air-Cooled Scroll Compressor Chiller Group: Chiller Part Number: OMM 1087 Effective: May 2012 Supersedes: April 2012 AGZ-D 25 to 190 Tons 50-60-Hertz, -410A
More informationExclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA
Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant
More informationProduct Data. Features/Benefits ComfortLink control
Product Data 30GTN,GTR Air-Cooled Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Nominal Capacities: 60 to 410 Tons 205 to 1445 kw Features/Benefits ComfortLink control Your link to a
More informationSystem Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller
System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and
More informationSection 1: Theory of Heat Unit 3: Refrigeration and Refrigerants
Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.
More informationFigure 17-1 Residential air conditioner (Image courtesy of Bryant Heating & Cooling Systems)
Figure 17-1 Residential air conditioner (Image courtesy of Bryant Heating & Cooling Systems) Figure 17-2 Commercial refrigeration Unit Figure 17-3 Industrial process chiller Figure 17-4 Basic refrigeration
More informationMAC N-407 Air-Cooled Chiller
MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=
More informationNEW CHILLER SCHEDULE
TITLE: REPLACE CHILLER MACC MAXIMO # 4542690 PROJECT # 14M108CN MACC # 14-0459 ATTACHMENTS: 1. MAXIMO Equipment update form SCOPE OF WORK: The contractor shall provide all material, labor, equipment, and
More informationA. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.
SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate
More informationINITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER
INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME ADDRESS JOB NO. MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS BRINE FLOW RATE
More informationSERVICE ASSISTANT OVERVIEW FDSI Online Training
Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...
More informationPRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division
INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During
More informationTable of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)
Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High
More informationTRIDENT GS SERIES Central Chiller
Blending Conveying Drying Process Cooling Heat Transfer Size Reduction TRIDENT GS SERIES Central Chiller Compact Innovative Scalable Innovative and compact designs with 50 to 120 individual circuit chilling
More informationEnergy consumption storage facilities examined in ICE-E
Energy consumption storage facilities examined in ICE-E August 2012 Edited by Lars Reinholdt Danish Technological Institute = ICE-E Audit report 1 Contents EXECUTIVE SUMMARY 3 INTRODUCTION 4 THE ISSUES
More informationPathfinder Air-Cooled Chillers
Operating & Maintenance Manual OMM 1168 Group: Chiller Part Number: OMM 1168 Date: September 2012 Rev 00 Supercedes: OMM 1123, July 2012 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes
More informationWater-Cooled Scroll Compressor Chillers
Operating and Maintenance Manual OMM 1130 Group: Chiller Part Number: OMM 1130 Effective: March 2012 Supercedes: November 2011 Water-Cooled Scroll Compressor Chillers WGZ030DW to WGZ200DW, Packaged Water-Cooled
More informationDESIGN STANDARDS SECTION 15600
PART 1 - GENERAL 1.1 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.2 General requirements: A. Reciprocating
More informationTechnical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.
Document No. 155-021P25 ET 141-5 ET 141 High Limit Control Thermostat Description Application The ET 141 high limit control thermostat is duct mounted and has a rigid bulb, bi-metal rod and tube construction.
More informationWater-Cooled Scroll Compressor Chillers
Operating Manual OM WGZC Group: Chiller Part Number: 331374501 Effective: January 2008 Supercedes: New Water-Cooled Scroll Compressor Chillers WGZ 030CW to WGZ 200CW, Packaged Water-Cooled Chiller WGZ
More informationWater-Cooled Scroll Compressor Chillers
Operating Manual OM WGZC-2 Group: Chiller Part Number: 331975301 Effective: August 2011 Supercedes: November 2010 Water-Cooled Scroll Compressor Chillers WGZ 030CW To WGZ 200CW, Packaged Water-Cooled Chiller
More informationChapter-8 Capacity Control of Refrigeration Systems
Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control
More informationAIR CONDITIONING. Carrier Corporation 2002 Cat. No
AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)
More informationEXD-HP1/2 Stand-alone Superheat/Economizer Controller
Technical Bulletin EXD-HP1/2 are stand-alone universal superheat and or economizer controllers for heat pumps, heating units, air conditioning and precision cooling such as telecom and shelter applications.
More informationUser Guide. Tracer CH530 Control System for Scroll Chillers CGAN/CXAN CGCL CGWH/CCUH CGWN/CCUN RAUL
User Guide Tracer CH530 Control System for Scroll Chillers CGAN/CXAN 209-214 CGCL 200-600 CGWH/CCUH 115-250 CGWN/CCUN 205-215 RAUL 190-800 General information Foreword These instructions are given as a
More informationORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS
ORTEC Compressed Air, Gas & Fluid Technologies HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS Energy Lean Planet Green Cycling and Non-Cycling Design Energy Efficient s Fluctuating and Intermittent Loads Capacity,0
More informationSECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.
SECTION 15650 REFRIGERATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. 4. Air
More informationINSTRUCTION AND MAINTENANCE MANUAL
Code 007758 0 Edit. 0/009 INSTRUCTION AND MAINTENANCE MANUAL DRYERS A A A A READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. Cod. 007758 0 - Edition 0/009 - CONTENTS PART A:
More informationAE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors
October 2017 1.5 to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury
More informationSECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower
SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal
More informationINITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER
INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME JOB NO. ADDRESS MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS BRINE FLOW
More informationWarm Case Troubleshooting Guide 9/18/2014
Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last
More informationAC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT
AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT Central Chiller Plant (with Cooling Tower and Chilled Water distribution) The other AC configuration is called a Chilled Water or Larger Cooler system. It
More informationRead and save these instructions
Split Water-Cooled Central-Ducted Cooling System Operation Care Installation Manual CT14TSHWC CT13TSHWC CT12TSHWC CT34TSHWC CT1TSHWC www.apexwinecellars.com 17631 S Susana Road Rancho Dominguez, CA 90221
More informationKelvin air conditioning. KELVIN Clim W280. Cooling Capacity: 280 ~ 1840 kw
Cooling Capacity: 280 ~ 1840 kw Water cooled liquid chillers in A class energy efficiency for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded
More informationTEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled
More informationCOOLPLUS KENYA LIMITED. The "Only Manufacturer" of Uninterrupted Cold Stores & Trough Cooling Systems for post Harvest solution Recycling.
COOLPLUS KENYA LIMITED The "Only Manufacturer" of Uninterrupted Cold Stores & Trough Cooling Systems for post Harvest solution Recycling. Our History Founded in 1998 and incorporated the same year as a
More informationWaterFurnace FX10 Application Guide Reversible Chiller
2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water
More informationPOLICY BULLETIN Tecumseh Compressor Company Compressor Group
PAGE: 1 of 4 A rotary compressor is a precision piece of equipment, designed and manufactured to very close tolerances. For superior performance and long term reliability the following parameters must
More information