Guide Specifications

Size: px
Start display at page:

Download "Guide Specifications"

Transcription

1 Guide Specifications Hot Water fired Adsorption Liquid Chillers Bry-Air Adsorption Chiller Overview The chiller shall be a Bry-Air ADC series. The chiller shall consist of a robust, compact, packaged chiller suitable for indoor or outdoor installation. Proprietary desiccant gel shall be used as the adsorbent, and standard tap water shall be used as the refrigerant. The desiccant gel shall be regenerated by low temperature 50 C to 96 C (120 F to 205 F) hot water. The chiller shall include electronic controls capable of stand-alone operation. The main components of the Adsorption Chiller shall be comprised of two adsorbent chamber/heat exchangers, an evaporator for chilled water, and a water-cooled condenser. Leak testing, charging with refrigerant, and performance testing of each adsorption chiller shall be completed in the factory prior to shipment. Quality a. Chiller shall be tested in accordance with ARI standard b. Chiller shall be manufactured in accordance with ANSI/ASHRAE 15 Safety Code for Mechanical Refrigeration. c. Each chiller shall undergo a series of factory tests during production to ensure that the unit is hermetically sealed for operating under vacuum, electrical connections are properly made, all components operate as intended, and the proper level of quality production standards are maintained as directed by ISO d. The chiller shall be leak tested using helium gas. e. Model number, serial number, and manufacturing date shall be shown on the chiller. Delivery, Storage, and Handling a. The unit shall ship as one piece. b. The chiller shall be stored and handled according to the manufacturer s installation and rigging instructions. c. If stored outdoors, the unit shall be protected from corrosive environments and to prevent condensation inside the control panel or other electrical cabinets. Warranty The chiller shall carry a 12 month parts warranty from the date of manufacture, or 18 months from the date of shipment, whichever comes first. This warranty does not include labour. Equipment a. The chiller shall be designed to produce chilled water using a double chamber adsorption / regeneration process fueled by low grade hot water. The chiller shall consist of an evaporator, dual adsorption chambers, condenser, refrigerant piping and pump(s), and a vacuum purge system. b. The chiller shall be factory charged with desiccant gel and water. c. The unit shall not require any field installation of refrigerant, chemicals, or additional start up procedures such as removing nitrogen gas or operating a vacuum pump for an extended length

2 of time. As an option to reduce shipping weight, the chiller may ship without refrigerant water. Tap water then shall be required to be added on site to function as refrigerant. d. The unit shall operate with low grade, regeneration hot water temperatures of 50 C to 96 C (120 F to 205 F). Solar thermal and condensing boiler heat recovery shall be optimized for operation at 96 C (160 F) or lower hot water temperature. e. Condenser water shall range from 10 C to 39 C. The chiller shall be able to operate at reduced capacity with condenser water up to 54 C (130 F) without damage. f. Chilled water shall range from 3 C to 20 C (37 F to 68 F). g. Condenser, adsorber, and evaporator heat transfer surfaces shall be copper tubes rated for 10 bar (150 psig) pressure. h. NIH waterboxes shall be provided rated for 4.82 bar (70 psig). Waterboxes shall be provided with vent and drain connections. Waterboxes shall be painted with a protective finish able to withstand installation in an outdoor, non-corrosive environment. ANSI 150 psig flanged connections shall be furnished on all waterbox nozzle connections. i. The cycling process will be achieved by the use of 12 pneumatically operated butterfly valves on the hot water and condenser water lines. The life of the valve seats shall not be less than 200,000 cycles. A source of constant air pressure at 5 to 8 bar ( psig) at the air pressure regulator/filter inlet shall be required. An air compressor shall be a factory option. j. A hermetic pump shall be provided to return the excess refrigerant from the evaporator to the distribution header. A bearing monitor shall be provided factory installed on the pump. k. A vacuum pump shall be provided to evacuate non-condensable gases from the chiller. The vacuum pump shall operate one hour per 40 hours of machine operation. l. Production of flammable hydrogen gas shall not occur; therefore, a palladium cell shall not be provided for the removal of hydrogen gas. m. Eyebolts for lifting the chiller shall be provided. n. Functional witness testing shall be provided in the factory with customer representatives in attendance. Travel costs shall the responsibility of the customer. Performance testing shall be done at site. o. Chiller electrical consumption shall be less than 1.5 kw for units up to 250 tonnes of capacity. Options 1. Standard waterside ratings are 4.82 bar (70 psig). 2. Chillers may be ordered with critical application configuration to eliminate shutdown during safety alarms. The warranty shall be voided if this option is selected. 3. As an option, the chiller may be configured for outdoor installation. 4. An air compressor may be factory installed to actuate the pneumatic valves. 5. Shipment without refrigerant. 6. Control and vacuum cabinets may be mounted on the side or rear of the unit depending on site space constraints. 7. Touch-screen display shall be optional. 8. NEMA 4X control cabinet shall be optional. 9. Extended factory testing at part load conditions of the customer s choosing shall be optional.

3 10. Power supplies other than shall be optional with the use of a factory provided transformer and inverter. Controls a. The chiller shall include a factory-installed and factory-wired microprocessor control system with modular component construction. The controls shall be of the PID type and shall continuously monitor the operation of the chiller and perform self-diagnostic checks to maintain control limits. The controls shall be housed in a NEMA 4 control panel for indoor use. As an option, a NEMA 4X panel shall be available for outdoor use in harsh environments. b. The control system shall be open source with an Ethernet protocol for integration to the Building Management System. c. Operator display shall include English language textual outputs for programming and alarm signals. The display shall indicate power on, run status, safety circuit, and alarm status. d. An Ethernet port shall be provided to communicate with the PLC controller to view status, setpoint, and make any changes in the field. A human-machine interface featuring a touch panel monitor as an option. e. The following inputs shall be monitored: a. Hot water tank level b. Chilled water level c. Condenser water level d. Air pressure level e. Float level f. Vacuum pump operation g. Vacuum level h. Inverter operation i. Evaporator temperature j. Refrigerant level k. Refrigerant pump l. Chilled water entering temperature m. Chilled water leaving temperature n. Evaporator temperature o. Condenser water temperature p. Cycle time q. Chilled water flow f. The refrigeration capacity of the adsorption chiller shall have seven steps of unloading controlled by inlet chilled water temperature. This control shall modify the cycle time so that only the required hot water flows through the adsorption chiller when cooling is required. Multiple adsorption chiller installations (piped in series or parallel) shall be controlled to operate at the most effective cycle time by the control panel. g. Three way valves shall not be required to control capacity. h. The cooling tower fan shall be controlled by an on/off switch in the control panel so that it cycles ON at any design temperature. The sensor for the cooling water temperature shall be in the

4 cooling water outlet of the adsorption chiller. Three way valves for the cooling water shall not be required to control capacity. i. The chiller shall run no risk of crystallizing the desiccant since no liquid desiccants (including lithium bromide) are used. j. The user shall be able to select between two different modes of operation. The first mode shall optimize the cycle time to produce the maximum chiller capacity. The second mode of operation shall optimize the cycle time to produce the maximum efficiency (COP). The user shall be able to select the mode of operation at the control panel. k. The following safeties shall be monitored. Faults shall be displayed with an English language error code. An abnormal condition of the following faults shall shut down the operation of the chiller and create an alarm: a) Hot water tank level abnormal (high or low) b) Chilled water level abnormal c) Condenser water level abnormal d) Air pressure level abnormal e) Inverter operation abnormal f) Evaporator temperature abnormal g) Refrigerant level abnormal h) Refrigerant pump abnormal The following fault shall shut down the operation of the chiller and create an alarm and shut down the chilled water pump regardless of chiller operating status: a) Float level abnormal The following faults shall provide an alarm signal only. The chiller will continue to run if it is in operating status: a) Vacuum pump abnormal b) Vacuum level abnormal l. A chilled water flow switch shall be factory installed. If flow is not present, the chiller shall not operate so as to prevent freezing the evaporator. m. The contractor shall field install factory provided float level switches on the field provided and field installed hot water tank (by others). n. Start-up shall be instantaneous with no delay. An extended startup sequence shall not be acceptable. Full capacity shall be reached within 10 minutes following a shutdown. Electrical 1. Power supply to the unit shall be 3 ph, 50 Hz, 415 voltages. If power supply exceeds 415 volts, a stepdown transformer shall be required. 60 Hz frequency shall be available as an option. 2. Power supply to the unit shall be the responsibility of the installing contractor. 3. Installation of external controls, safeties, switches, and sensors shall be the responsibility of the installing contractor. 4. A control transformer shall be provided to supply power to the control panel. 5. The chiller shall have single point power supply.

5 Piping Requirements 1. Installation of external piping shall be provided by the installing contractor. 2. A rupture disk shall not be required since no hydrogen gas is produced by an adsorption chiller, and the refrigerant used is water. Any costs associated with the installation of a rupture disk and required piping to an exterior building penetration (if installed indoors) shall be the responsibility of the installing contractor. 3. No refrigerant detectors or refrigerant piping shall be required since the refrigerant in use is potable water. Sound Level 1. The overall sound pressure level of the chiller shall not exceed 80 db (A) when measured per ARI standard Installation 1. The adsorption chiller shall be installed on a level surface. The leveling bolts shall be placed on the mounting plates and adjusted for longitudinal and transverse alignment of the chiller shell. If the chiller is not installed level, the refrigerant will not properly wet the entire evaporator heat exchanger surface, thus reducing the chiller capacity. 2. Each adsorption chiller shall be installed in a location where there is access to all side and top panels. A minimum of 30 inches clearance shall be provided in front of the equipment. The piping configuration shall allow clear access to the adsorption chiller for service. 3. Installation of balancing valves shall not be required. 4. Three-way control valves shall not be necessary in any water line. 5. Insulation of the external surfaces of the evaporator, refrigerant pump, chilled water, condenser water, hot water piping, and headers shall be field supplied by the installing contractor and installed on the machine. Refer to product literature for insulation quantities recommended. Start Up 1. Start-up services shall be provided by a factory-trained representative to perform and/or supervise start-up procedures as recommended in the Bry-Air Chiller Installation, Operation, and Maintenance manual. The contractor shall provided personnel familiar with the system design and controls to assist during the startup. 2. Owner training shall be provided immediately following startup for a period of four hours. 3. The following documentation shall be provided: Maintenance a. Installation, Operation, and Maintenance Manuals b. Submittals c. Wiring diagrams 1. The maintenance required by the end user shall be to check the oil level in the vacuum pump and replace it as needed. 2. The belt for the vacuum pump shall be checked annually and replaced as needed. 3. The valve seats for the pneumatic butterfly valves shall be replaced as needed. For a chiller in continuous operation, this is estimated at year 5. For a seasonal application, this is estimated at year 10 or longer.

6 4. No chemical analysis, warm-up time, dilution period, or other intensive daily maintenance shall be required. 5. Vacuum level in the chiller shall be checked periodically by placing the vacuum pump into Manual mode for 10 minutes and confirming the vacuum level at that time using the gauge in the vacuum cabinet. The vacuum pump must then be returned to Automatic mode. 6. A visual inspection of the refrigerant water quality shall be made through the multiple sight glasses on the chiller. 7. If an open circuit cooling tower is used, the customer may brush the tubes annually to remove any tube buildup that may be present. The water quality in the chilled water, cooling water, and heat medium circuits shall be maintained to prevent scale formation and tube corrosion.

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki model CH- Gas Fired,

More information

Technical Data Sheet

Technical Data Sheet Technical Data Sheet Bulletin : BAA:D0054 Effective : April. 06, 2015 Supercedes Date : ADSORPTION CHILLER ADC Series C-FRAME FEATURE HIGHLIGHTS * Ultra low electricity consumption * Ease of maintenance

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas Fired DOUBLE-EFFECT Chiller-Heater Absorption Principle Yazaki MG-Series

More information

Product Data. Features/Benefits. 16TJ Single-Effect, Steam Hermetic Absorption Liquid Chiller. 100 to 700 Nominal Tons

Product Data. Features/Benefits. 16TJ Single-Effect, Steam Hermetic Absorption Liquid Chiller. 100 to 700 Nominal Tons Product Data 16TJ Single-Effect, Steam Hermetic Absorption Liquid Chiller 100 to 700 Nominal Tons Carrier-Sanyo s 16TJ single-effect hermetic absorption liquid chiller is an efficient and functional alternative

More information

TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series

TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series Absorption Chillers TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series Stable Chilled Water Outlet Temperature PID control is applied to maintain constant chilled water outlet temperature. When the cooling

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

16TJ Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw

16TJ Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION GB/T-191-2 to ISO91/2 16TJ 11-53 Nominal cooling capacity 352-2461 kw The Carrier Corporation has more than 1 years experience in providing

More information

16LJ Single-Effect Hot Water-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw

16LJ Single-Effect Hot Water-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw Single-Effect Hot Water-Fired Absorption Chillers SUPER ABSORPTION GB/T-191-2 to ISO91/2 16LJ 11-53 Nominal cooling capacity 264-1846 kw The Carrier Corporation has more than 1 years experience in providing

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

16TJ Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw

16TJ Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION GB/T-191-2 to ISO91/2 16TJ 11-53 Nominal cooling capacity 352-2461 kw The Carrier Corporation has more than 1 years experience in providing

More information

SECTION AIR COMPRESSORS AND ACCESSORIES

SECTION AIR COMPRESSORS AND ACCESSORIES PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

Technical Catalog SAB-LW Series Single Effect Double Lift Hot Water Driven Absorption Chiller 65 to 1,300 Nominal Tons (229 to 4,571 kw)

Technical Catalog SAB-LW Series Single Effect Double Lift Hot Water Driven Absorption Chiller 65 to 1,300 Nominal Tons (229 to 4,571 kw) Technical Catalog SAB-LW Series Single Effect Double Lift Hot Water Driven Absorption Chiller 65 to 1,300 Nominal Tons (229 to 4,571 kw) 1 SAB-LW, Single Effect Double Lift Hot water driven absorption

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

MODELS LIST. Nominal Capacity RT

MODELS LIST. Nominal Capacity RT 1. MODELS LIST. NOMENCLATURE 3. FEATURES 4. PRODUCT DATA 5. PERFORMANCE CORRECTION 6. ANTIFREEZE 7. INSTALLATION 8. ELECTRICAL DATA 9. SCHEMATIC WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.APPLICATION

More information

100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER 1. General Description The Contractor shall furnish and install (QTY) Yazaki model CH-K100 Gas-Fired, Double-Effect

More information

SECTION CHILLERS

SECTION CHILLERS SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings

More information

Product Data. Features/Benefits. 16JB Steam/Hot Water Single Effect, Hermetic Absorption Liquid Chiller 50/60 Hz

Product Data. Features/Benefits. 16JB Steam/Hot Water Single Effect, Hermetic Absorption Liquid Chiller 50/60 Hz Product Data 16JB Steam/Hot Water Single Effect, Hermetic Absorption Liquid Chiller 50/60 Hz 108 to 680 Nominal Tons (380 to 2392 kw) Carrier s 16JB single effect hermetic absorption liquid chiller offers

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 2505-4005 SUGGESTED SPECIFICATIONS Catalog No.: 6000.70 Effective: 09-15-16 Replaces: NEW WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes condensing, gas-fired

More information

SCA 620C AIR COOLED SCREW CHILLER

SCA 620C AIR COOLED SCREW CHILLER DUNNAIR I N T E R N A T I O N A L L I M I T E D SCA 620C AIR COOLED SCREW CHILLER MV6 CONTROL Refrigerant: R22 Standard NOMINAL CAPACITY 620 kw(r) DUNNAIR INTERNATIONAL LIMITED Subject to change without

More information

Technical Catalog. SAB-HW Series Hot Water Driven Absorption Chiller 15 to 1000 Nominal Tons (52 to 3516 kw) ISO 9001 ISO CHP Solution Inc.

Technical Catalog. SAB-HW Series Hot Water Driven Absorption Chiller 15 to 1000 Nominal Tons (52 to 3516 kw) ISO 9001 ISO CHP Solution Inc. Technical Catalog SAB-HW Series Hot Water Driven Absorption Chiller 15 to 1000 Nominal Tons (52 to 3516 kw) ISO 9001 ISO 14001 CHP Solution Inc. USA 1 SAB-HW, Hot water driven absorption chillers, provides

More information

Adsorption Chillers Energysmart Green Cooling

Adsorption Chillers Energysmart Green Cooling Adsorption Chillers Energysmart Green Cooling New Partners in innovation Leaders in Dehumidification... Worldwide Power Partner Inc USA www.bryair.com Recover Low Grade Process Waste Heat For Energy Smart

More information

THE FOLLOWING CHANGES/ADDITIONS TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED:

THE FOLLOWING CHANGES/ADDITIONS TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED: Business Services Procurement and Contracting 16550 SW Merlo Road Beaverton, OR 97003 (503) 356-4324 February 20, 2018 SOLICITATION ADDENDUM NO. 2 ITB 18-0003 Kinnaman-Hiteon Chiller Replacement THE FOLLOWING

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 1005A-2005A SUGGESTED SPECIFICATIONS Catalog No.: 6000.63B Effective: 3-01-15 Replaces: 9-01-09 WATER-TUBE POOL HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes condensing,

More information

Gas-Fired Double-Effect Chiller-Heater

Gas-Fired Double-Effect Chiller-Heater Gas-Fired Double-Effect Chiller-Heater CH-K Series: 30, 40, 50, 60, 80, 100 RT Cooling with Standard Heating Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas-Fired Double-Effect Chiller-Heater

More information

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS MVB, TYPE WH - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 3500.952C Effective: 06-25-15 Replaces: 12-22-09 DIVISION 23 34 36.29 COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

DESICCANT AIR DRYERS. BD + CD + CD series

DESICCANT AIR DRYERS. BD + CD + CD series DESICCANT AIR DRYERS BD + CD + CD series AIR TREATMENT, A CRUCIAL INVESTMENT WHY YOU NEED QUALITY AIR Compressed air contains oil, solid particles and water vapors. Together, they form an abrasive, often

More information

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS XPAK FT TYPE H - MODELS 088AR-398A SUGGESTED SPECIFICATIONS Catalog No.: 2100.91 Effective: 05/01/15 Replaces: new DIVISION 23 52 33.13 WALL-HUNG STAINLESS STEEL HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

Product Data. Features/Benefits. 16JT Double-Effect Hermetic. Absorption Liquid Chillers Provide. With Product Integrated Controls (PIC)

Product Data. Features/Benefits. 16JT Double-Effect Hermetic. Absorption Liquid Chillers Provide. With Product Integrated Controls (PIC) Product Data 16JT Double-Effect Hermetic Absorption Liquid Chiller With Product Integrated Controls (PIC) Nominal 100 to 1700 Tons (352 to 5980 kw) Carrier s 16JT Double-Effect Hermetic Absorption Liquid

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Product Data Catalog Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Variable Speed Total Access Modules MS010W, MS020W, MS030W, MS050W MS010V, MS020V,

More information

30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER 1. General Description The Contractor shall furnish and install (QTY) Yazaki model CH-K Gas-Fired, Double- Effect

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 2000.932C Effective: 04-01-14 Replaces: 07-15-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil.

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil. 1 1 1 1 1 1 1 1 0 1 0 1 SECTION 1 PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES A. Chiller package. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F Temperature Control Units Water & Oil - F Portable Chillers Air & Water-Cooled - 7 F Central Chillers Air & Water-Cooled Packages & Modules - 7 F Pump Tank Stations Chilled or Tower Water - gallons Cooling

More information

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS)

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS) SECTION 23 64 01 AIR COOLED WATER CHILLERS (LESS THAN 150 TONS) PART 1: GENERAL 1.1 GENERAL A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS HI DELTA, TYPE WH - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 3500.932A Effective: 04-01-17 Replaces: 10-31-16 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY A.

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: ,

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: , DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: +971-6-5432526, Fax#: +971-6-5432415, Email: dolcool@emirates.net.ae, web site: www.dolphinheattransfer.com NOMENCLATURE: INTRODUCTION DOLCOOL branded

More information

Central Chillers TS Series

Central Chillers TS Series www.thermalcare.com Central Chillers TS Series With over 40 years of process cooling experience, Thermal Care is the dependable choice for industrial process chillers. Our TS Series is just one of several

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS XTHERM, TYPE WH - MODELS 1005A- 2005A Catalog No.: 3500.801 Effective: 11-15-14 Replaces: NEW PART 1 - GENERAL 1.1 SUMMARY DIVISION 23 34 36.29 COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 2503-4003 SUGGESTED SPECIFICATIONS Catalog No.: 2000.934A Effective: 04-01-14 Replaces: 06-01-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000 CENTRIFUGAL LIQUID CHILLERS INSTALLATION Supersedes: 160.78-N1 (611) Form 160.78-N1 (512) YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER LD14000 R-134a Issue Date: May 30, 2012 IMPORTANT! READ BEFORE PROCEEDING!

More information

APC Refrigeration Distribution Unit (RDU) Guide Specifications

APC Refrigeration Distribution Unit (RDU) Guide Specifications APC Refrigeration Distribution Unit (RDU) Guide Specifications PART 1 GENERAL 1.01 SUMMARY A. These specifications describe requirements for a system designed for cooling of IT equipment. The system shall

More information

SULLAIR DESICCANT DRYERS

SULLAIR DESICCANT DRYERS SULLAIR DESICCANT DRYERS Sullair An industry leader Leadership Since 1965, Sullair has been recognized worldwide as an innovator and leader in rotary screw compression and vacuum technology. Sullair designs

More information

DESICCANT AIR DRYERS. BD + CD + CD series

DESICCANT AIR DRYERS. BD + CD + CD series DESICCANT AIR DRYERS BD + CD + CD series AIR TREATMENT, A CRUCIAL INVESTMENT WHY YOU NEED QUALITY AIR Compressed air contains oil, solid particles and water vapors. Together, they form an abrasive, often

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

More information

twin tower desiccant compressed air dryers flow capacity: 200-9,000 scfm (340-15,300 Nm3/hr)

twin tower desiccant compressed air dryers flow capacity: 200-9,000 scfm (340-15,300 Nm3/hr) D twin tower desiccant compressed air dryers flow capacity: 200-9,000 scfm (340-1,300 Nm3/hr) D D D twin tower desiccant compressed air dryers flow capacity: 200-9,000 scfm (340-1,300 Nm 3 /hr) Leading

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES 60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,

More information

For Modules: ASM002X, ASM003X, ASM005X, ASM008X, ASM010X, ASM015X, ASM020X, ASM030X. Air Cooled Medical Chiller Product Data Catalog

For Modules: ASM002X, ASM003X, ASM005X, ASM008X, ASM010X, ASM015X, ASM020X, ASM030X. Air Cooled Medical Chiller Product Data Catalog For Modules: ASM002X, ASM003X, ASM005X, ASM008X, ASM010X, ASM015X, ASM020X, ASM030X Air Cooled Medical Chiller Product Data Catalog Product Introduction Multistack products are ideal for many mission

More information

LQ AQ SQ. Air-cooled and water-cooled portable chillers

LQ AQ SQ. Air-cooled and water-cooled portable chillers LQ AQ SQ Air-cooled and water-cooled portable chillers Choose from a complete line of dependable Accuchiller portable chillers LQ Series AQ Series SQ Series No other manufacturer can offer you a larger

More information

DOUBLE EFFECT ABSORPTION CHILLERS

DOUBLE EFFECT ABSORPTION CHILLERS DOUBLE EFFECT ABSORTION CHILLERS STEAM CONSUMTION RATE3.9kg/(hUSRt) 3.95kg/(hUSRt) Model in this catalog is our model code. MODEL REW is; The double effect chiller is high efficiency model, The chiller

More information

SECTION CENTRIFUGAL WATER CHILLERS

SECTION CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Chiller package. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Condenser water connections. F. Variable

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS HI DELTA, TYPE H - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 2000.953 Effective: 10-31-16 Replaces: NEW DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS - GENERAL 1.1 SUMMARY A. Section includes

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 502C-902C SUGGESTED SPECIFICATIONS Catalog No.: 6000.601A Effective: 07-12-18 Replaces: 10-31-16 FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 6000.611 Effective: 10-31-16 Replaces: NEW FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System PART 1 SYSTEM DESCRIPTION 1.1 The HVAC system is based on the CGC HYBRID Hydronic Heat Pump System. 1.2 The system will automatically

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 236426.11 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years. TURBOCOR COMPRESOR CHILLERS General Description Microprocessor controlled, water chiller using HFC 134a refrigerant, two stage centrifugal oil free variable speed compressor's and electronic expansion

More information

Screw Water Cooled Chiller SCW210

Screw Water Cooled Chiller SCW210 Screw Water Cooled Chiller SCW210 Nominal Cooling Capacity 185.1 to1480.8 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1 UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS GPE 802 Kc + CF + GP + MV + P1 130 Above picture is only indicative and is not binding. AIR R-410A

More information

Precise Temperature Control; Compact Footprint

Precise Temperature Control; Compact Footprint Precise Temperature Control; Compact Footprint The Conair EP1 Series Portable Chillers are designed for 1 to 3 ton applications. Available as air-cooled or water-cooled, with pump sizes from 1/4 to 3 Hp

More information

ACMVTECH HIGH EFFICIENCY UNITARY AHU

ACMVTECH HIGH EFFICIENCY UNITARY AHU HIGH EFFICIENY UNITARY AHU 50 / 60 Hz R-134A, R407c R-407F, R-410A ACMVTECH HIGH EFFICIENCY UNITARY AHU WATER COOLED CONDENSERS VARIABLE and CONSTANT SPEED VSD FANS ; VSD COMPRESSORS ACMCVTECH UNITARY

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

LQ AQ SQ. Air-cooled and water-cooled portable chillers

LQ AQ SQ. Air-cooled and water-cooled portable chillers LQ AQ SQ Air-cooled and water-cooled portable chillers Choose from a complete line of dependable Accuchiller portable chillers LQ Series AQ Series SQ Series No other manufacturer can offer you a larger

More information

Nirvana. Cycling Refrigerated Dryers

Nirvana. Cycling Refrigerated Dryers Nirvana Cycling Refrigerated Dryers Nirvana Cycling Refrigerated Dryers Reliability Is Our Design Ingersoll Rand's Nirvana Cycling Refrigerated Dryer provides reliability like no other dryer in its class:

More information

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B.

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw AIR-COOLED LIQUID CHILLER REVERSIBLE AIR-TO-WATER HEAT PUMP PRO-DIALOG PLUS 30RB/RQ 039S-60S Refrigerant HFC-40A Nominal cooling capacity 40-58 kw Nominal heating capacity 4-59 kw The new generation of

More information

EZT Series Integra Med Touch Area Alarm & Zone Valve Box with EZ Backfeed

EZT Series Integra Med Touch Area Alarm & Zone Valve Box with EZ Backfeed Submittal Data Sheet Features The Powerex Med Touch area alarm zone valve panel digitally displays gas pressure (1 psi increments) and provides alarm conditions as required by the latest edition of NFPA

More information

YOUR PROCESS DEMANDS THE MOST DEPENDABLE TEMPERATURE CONTROL UNIT AVAILABLE.

YOUR PROCESS DEMANDS THE MOST DEPENDABLE TEMPERATURE CONTROL UNIT AVAILABLE. Temperature Control Units Water & Oil 0-00 F Portable Chillers 0 - F Central Chillers Packages & Modules 0 - F Pump Tank Stations Chilled or Tower Water 00-0 gallons Cooling Tower Cells 4-40 tons Filters

More information

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost LL Chillers and Outdoor Mechanical Rooms Air-Cooled Features: Air-cooled condenser chillers with capacities from 35-345 tons Evaporative-cooled condenser chillers with capacities from 35-540 tons Variable

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

FORM EG1 (1008) YIA Single-Effect Absorption Chillers Steam And Hot Water Chillers Style A TONS ( kw)

FORM EG1 (1008) YIA Single-Effect Absorption Chillers Steam And Hot Water Chillers Style A TONS ( kw) FORM 155.16-EG1 (1008) YIA Single-Effect Absorption Chillers Steam And Hot Water Chillers Style A 120-1377 TONS (420-4840 kw) Table of Contents FORM 155.16-EG1 (1008)... 1 Nomenclature... 3 Introduction...

More information

SpaceKeeper Console (SKC)

SpaceKeeper Console (SKC) SpaceKeeper Console (SKC) With finished cabinet or custom enclosure SKC 008-015 ¾ - 1¼ tons 12 W x 25¼ H x 48 L CGC-09 SpaceKeeper Console R410A MODEL NO. SKC _ 008 010 012 015 Net Cooling Capacity - Rated

More information

SECTION PACKAGED HEAT TRANSFER SYSTEM

SECTION PACKAGED HEAT TRANSFER SYSTEM PACKAGED HEAT TRANSFER SYSTEM Page 1 of 6 SECTION PACKAGED HEAT TRANSFER SYSTEM 1 GENERAL 1.1 SUMMARY A. Packaged steam-to-water heat transfer system 1.2 REFERENCES A. ASHRAE American Society of Heating,

More information