TECHNICAL DATA & SERVICE MANUAL
|
|
- Elinor Stewart
- 5 years ago
- Views:
Transcription
1 TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: GRF188R5TAA GRF228R5TAA GRF228R7TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. GRF188R5TAA GRF228R5TAA GRF228R7TAA GRF188R5TAA GRF228R5TAA - GRF228R7TAA July 2008 b
2 IMPORTANT! Please read before installation This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state and national electrical codes. Pay close attention to all warning and caution notices given in this manual. The unit must be supplied with a dedicated electrical line. This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage. If necessary, get help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions. In case of improper installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. SPECIAL PRECAUTIONS During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units. WARNING WARNING CAUTION When wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM /2007 Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury and death. Ground the unit following local electrical codes. The Yellow/Green wire cannot be used for any connection different from the ground connection. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line. When transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers. When installing In a ceiling or wall Make sure the ceiling/wall is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support.... In a room Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.... In moist or uneven locations Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.... In area with strong winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.... In a snowy area (for heat pump-type systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. When connecting refrigerant tubing Keep all tubing runs as short as possible. Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection. Check carefully for leaks before starting the test run. NOTE: Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas. When servicing Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. Ventilate the room during the installation or testng the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources. 2
3 Table of Contents Page 1. OPERATING RANGE 4 2. SPECIFICATIONS Unit specifications Major Component specifications Other Component specifications DIMENSIONAL DATA REFRIGERANT FLOW DIAGRAM PERFORMANCE DATA Performance Charts Cooling Capacity Heating Capacity ELECTRICAL DATA Electrical characteristics Electric Wiring Diagram System Wiring Diagram 24 3
4 1. OPERATING RANGE Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Cooling Maximum Minimum 32 C D.B. / 23 C W.B. 19 C D.B. / 14 C W.B. 43 C D.B. 19 C D.B. Heating Maximum Minimum 27 C D.B C D.B. / 18 C W.B. -8 C D.B. / -9 C W.B. 4
5 2. SPECIFICATIONS 2-1 Unit Specifications GRF188R5TAA Power source Voltage rating Performance * Capacity Air circulation (High) Moisture removal (High) MPAF188R5TAA kw BTU/h m³/h Liters/h V ~ 50Hz 230V Cooling Heating 5,00 5, ,5 - Electrical Rating Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A Features Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi db-a Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube (in.) tube diameter Wide tube (in.) Dimensions & Weight Unit dimensions Height Width Depth Package dimensions Height Width Depth Weight Net kg Shipping kg Shipping volume m 3 Remarks: Rating conditions are: Cooling: Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. Heating: Indoor air temperature 20 C D.B. Outdoor air temperature 7 C D.B. / 6 C W.B. Cooling Heating 198 ~ 264 7,00 6, ,23 3, (Hi) Rotary (Hermetic) R410A / 1280 Capillary tube 65 Flare type 7,5 6,35 (1/4) 12,7 (1/2) ,5 61,5 0,29 DATA SUBJECT TO CHANGE WITHOUT NOTICE * For other INDOOR UNITS' MODELS, please refer to catalogue 5
6 GRF228R5TAA Power source Voltage rating Performance * Capacity Air circulation (High) Moisture removal (High) MPAF228R5TAA kw BTU/h m³/h Liters/h V ~ 50Hz 230V Cooling Heating 6,60 7, ,0 - Electrical Rating Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A Features Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi db-a Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube (in.) tube diameter Wide tube (in.) Dimensions & Weight Unit dimensions Height Width Depth Package dimensions Height Width Depth Weight Net kg Shipping kg Shipping volume m 3 Remarks: Rating conditions are: Cooling: Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 27 C W.B. Heating: Indoor air temperature 20 C D.B. Outdoor air temperature 7 C D.B. / 6 C W.B. Cooling Heating 198 ~ 264 9,20 9, ,22 3, (Hi) Rotary (Hermetic) R410A / 1510 Capillary tube 66 Flare type 7,5 6,35 (1/4) 15,88 (5/8) ,0 77,0 0,37 DATA SUBJECT TO CHANGE WITHOUT NOTICE * For other INDOOR UNITS' MODELS, please refer to catalogue 6
7 GRF228R7TAA Power source Voltage rating Control Circuit Performance * Capacity Air circulation (High) Moisture removal (High) MPAF228R5TAA kw BTU/h m³/h Liters/h V 3N ~ 50Hz 400V 230V ~ 50Hz Cooling Heating 6,80 8, ,0 - Electrical Rating Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A Features Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi db-a Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube (in.) tube diameter Wide tube (in.) Dimensions & Weight Unit dimensions Height Width Depth Package dimensions Height Width Depth Weight Net kg Shipping kg Shipping volume m 3 Remarks: Rating conditions are: Cooling: Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 27 C W.B. Heating: Indoor air temperature 20 C D.B. Outdoor air temperature 7 C D.B. / 6 C W.B. Cooling Heating 342 ~ 418 4,10 4, ,24 3, (Hi) Rotary (Hermetic) R410A / 1510 Capillary tube 67 Flare type 7,5 6,35 (1/4) 15,88 (5/8) ,0 77,0 0,37 DATA SUBJECT TO CHANGE WITHOUT NOTICE * For other INDOOR UNITS' MODELS, please refer to catalogue 7
8 2-2 Major Component Specifications GRF188R5TAA Compressor Type Compressor model Nominal input Compressor oil Amount Coil resistance (Ambient temp. 20 C) Overload relay Safety devices W cc. Ω Type Operating Temp. Open C Close C Run capacitor µf VAC Fan & Fan Motor Type Q'ty. Dia. Fan motor model Q'ty No. Of poles rpm (230 V, High) Nominal output Coil resistance (Ambient temp. 25 C ) W Ω Safety devices Type Operating temp. Open C Close C Run capacitor µf VAC Heat Exch. Coil Coil Rows Fin pitch Face area m 2 External Finish Rotary (Hermetic) 5KS205EAA FV50S 670 C-R: 1,780 C-S: 2,175 Internal Thermal protector N/A N/A Propeller 1. Ø 400 KFG6-51SB5P BRN-WHT: 98.5 WHT-PNK: Thermal protector 130 ± 5 80 ± Aluminium plate fin / Copper tube 2 1,4 0,51 Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 8
9 GRF228R5TAA Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 20 C) Overload relay Safety devices W cc. Ω Type Operating Temp. Open C Close C Run capacitor µf VAC Fan & Fan Motor Type Q'ty. Dia. Fan motor model Q'ty No. Of poles rpm (230 V, High) Nominal output Coil resistance (Ambient temp. 25 C ) W Ω Safety devices Type Operating temp. Open C Close C Run capacitor µf VAC Heat Exch. Coil Coil Rows Fin pitch Face area m 2 External Finish Rotary (Hermetic) 5JS270DAA RB68A / Freol Alpha 68M 1130 C-R: 1,166 C-S: 1,534 Internal Thermal protector N/A N/A Propeller 1. Ø 460 Y7S623B WHT - PNK: 50,7 WHT - BRN: 88,9 Thermal protector 130 ± 5 N/A Aluminium plate fin / Copper tube 2 1,4 0,60 Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 9
10 GRF228R7TAA Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 20 C) Overload relay Safety devices W cc. Ω Type Operating Temp. Open C Close C Run capacitor µf VAC Fan & Fan Motor Type Q'ty. Dia. Fan motor model Q'ty No. Of poles rpm (230 V, High) Nominal output Coil resistance (Ambient temp. 25 C ) W Ω Safety devices Type Operating temp. Open C Close C Run capacitor µf VAC Heat Exch. Coil Coil Rows Fin pitch Face area m 2 External Finish Rotary (Hermetic) 5JS270PAA FV50S 1130 U-V: 5,786 U-W: 5,954 V-W: 5,562 Internal Thermal protector N/A N/A Propeller 1. Ø 460 Y7S623B WHT - PNK: 50,7 WHT - BRN: 88,9 Thermal protector 130 ± 5 N/A Aluminium plate fin / Copper tube 2 1,4 0,60 Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 10
11 2-3 Other Component Specifications GRF188R5TAA 4-way Valve (20S) Coil model Coil rating Coil resistance Ω (at 20 C) STF-0201G3 STF-01AJ504D1 AC 220/240 V, 50 Hz N/A High Pressure Switch (HP) set pressure electrical rating open close ACB-2UB ±1 bar 33 ±1,5 bar AC 250V - 1 ~ 6A GRF228R5TAA GRF228R7TAA 4-way Valve (20S) Coil model Coil rating Coil resistance Ω (at 20 C) V LDK-241 AC 208/240V, 50-60Hz, 4-5W N/A High Pressure Switch (HP) set pressure electrical rating open close ACB-2UB ±1 bar 33 ±1,5 bar AC 250V - 1 ~ 6A DATA SUBJECT TO CHANGE WITHOUT NOTICE 11
12 3. DIMENSIONAL DATA GRF188R5TAA dimension 4 - Ø12 for anchor bolt WIDE TUBE D.12,7 (1/2") NARROW TUBE D.6,35 (1/4") GRF228R5TAA GRF228R7TAA dimension NARROW TUBE D.6,35 (1/4") WIDE TUBE D.15,88 (5/8") 4 - Ø13 for anchor bolt 12
13 4. REFRIGERANT FLOW DIAGRAM cooling cycle outdoor unit GRF188R5TAA heating cycle indoor unit MPAF188R5TAA wide tube O.D. 12,7 (1/2") narrow tube O.D. 6,35 (1/4") outdoor unit GRF228R5TAA - GRF228R7TAA indoor unit MPAF228R5TAA wide tube O.D. 15,88 (5/8") narrow tube O.D. 6,35 (1/4") IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. 13
14 5. PERFORMANCE DATA 5-1 Performance charts GRF188R5TAA Cooling Characteristics Heating Characteristics 9,0 8,5 8,0 Indoor inlet air D.B. ( C) ,0 8,5 8,0 Indoor inlet air D.B. ( C) 27 Operating current (A) 7,5 7,0 6,5 19 Operating current (A) 7,5 7,0 6, ,0 6,0 19 5,5 0,74 5, Outdoor inlet air D.B. temp. ( C) 5,5 5, Outdoor inlet D.B. temp. ( C) 1,20 Indoor inlet air D.B. ( C) 4,00 Indoor inlet air D.B. ( C) Low pressure at wide tube service valve MPa 1,10 1, , , , /2007 0, Outdoor inlet air D.B. ( C) High pressure at wide tube service valve MPa 3, , , ,00 1,50 1, Outdoor inlet air D.B. ( C) Notes: Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode. Points of Rating condition Data referred to: MPAF188R5TAA 14
15 GRF228R5TAA Cooling Characteristics Heating Characteristics 11,5 11,0 Indoor inlet air D.B. ( C) 11,5 11,0 Indoor inlet air D.B. ( C) ,5 10,5 Operating current (A) 10,0 9,5 9,0 8, Operating current (A) 10,0 9,5 9,0 8, ,0 8,0 7,5 0,74 7, Outdoor inlet air D.B. temp. ( C) 7,5 7, Outdoor inlet D.B. temp. ( C) 1,10 Indoor inlet air D.B. ( C) 5 Indoor inlet air D.B. ( C) 1, ,5 Low pressure at wide tube service valve MPa 27 0, ,80 0,70 0, /2007 0, Outdoor inlet air D.B. ( C) High pressure at wide tube service valve MPa , ,5 2 1, Outdoor inlet air D.B. ( C) Notes: Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode. Points of Rating condition Data referred to: MPAF228R5TAA 15
16 GRF228R7TAA Cooling Characteristics Heating Characteristics 5,5 5,5 Indoor inlet air D.B. ( C) Indoor inlet air D.B. ( C) 27 5,0 32 5,0 20 Operating current (A) 4,5 4, Operating current (A) 4,5 4,0 15 3,5 3,5 0,74 3, Outdoor inlet air D.B. temp. ( C) 3, Outdoor inlet D.B. temp. ( C) 1,10 Indoor inlet air D.B. ( C) 4 Indoor inlet air D.B. ( C) Low pressure at wide tube service valve MPa 1, , ,80 0,70 0, /2007 0, Outdoor inlet air D.B. ( C) High pressure at wide tube service valve MPa 3, ,5 2 1, Outdoor inlet air D.B. ( C) Notes: Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode. Points of Rating condition Data referred to: MPAF228R5TAA 16
17 5-2 Cooling Capacity OUTDOOR UNIT: INDOOR UNIT: GRF188R5TAA MPAF188R5TAA V ~ 50Hz RATING CAPACITY 5,00 kw moisture removal 1,5 l/h COMP. POWER INPUT 1,377 kw max comp input 1,927 kw AIR FLOW RATE 760 m³/h EVAPORATOR ENT.TEMP. C CONDENSER OUTDOOR AMBIENT TEMP. C W.B. D.B TC 5,05 4,74 4,60 4,38 4,11 3,79 CM 0,59 0,83 1,06 1,29 1,53 1,76 21 SHC 3,50 3,25 3,18 3,08 2,95 2,79 23 SHC 3,96 3,68 3,61 3,50 3,37 3, SHC 4,40 4,10 4,02 3,91 3,78 3,63 27 SHC 4,85 4,54 4,45 4,34 4,11 3,79 29 SHC 5,05 4,74 4,60 4,38 4,11 3,79 31 SHC 5,05 4,74 4,60 4,38 4,11 3,79 TC 5,41 5,13 4,93 4,70 4,41 4,07 CM 0,63 0,87 1,10 1,34 1,57 1,80 21 SHC 3,02 2,84 2,76 2,65 2,52 2,36 23 SHC 3,48 3,27 3,17 3,07 2,93 2, SHC 3,93 3,70 3,60 3,49 3,36 3,20 27 SHC 4,39 4,13 0,74 3,90 3,77 3,62 29 SHC 4,85 4,56 4,43 4,33 4,20 4,03 31 SHC 5,28 4,99 4,85 4,70 4,41 4,07 TC 5,75 5,43 5,25 5,00 4,70 4,33 CM 0,68 0,91 1,14 1,38 1,61 1,84 21 SHC 2,54 2,38 2,30 2,20 2,07 1,91 23 SHC 2,99 2,80 2,73 2,62 2,49 2, SHC 3,45 3,21 3,14 3,03 2,91 2,75 27 SHC 3,88 3,62 3,57 3,95 3,33 3,17 29 SHC 4,34 4,02 3,98 3,87 3,75 3,59 31 SHC 4,80 4,45 4,40 4,29 4,16 4,01 TC 6,05 5,76 5,57 5,30 4,98 4,59 CM 1,09 1,25 1,41 1,57 1,73 1,89 23 SHC 2,48 2,35 2,27 2,16 2,03 1, SHC 2,94 2,75 2,68 2,59 2,46 2,30 27 SHC 3,39 3,17 3,11 3,00 2,88 2,72 29 SHC 3,85 3,57 3,52 3,42 3,29 3,14 31 SHC 4,28 3,99 3,95 3,84 3,72 3,57 TC 6,45 6,09 5,89 5,57 5,21 4,85 CM 1,51 1,60 1,68 1,76 1,84 1, SHC 2,42 2,28 2,21 2,09 1,96 1,83 27 SHC 2,88 2,67 2,62 2,50 2,37 2,24 29 SHC 3,33 3,07 3,04 2,92 2,79 2,66 31 SHC 3,79 3,51 3,47 3,34 3,21 3,09 TOTAL COOLING CAPACITY kw SHC: SENSIBLE HEAT CAPACITY kw CM: COMPRESSOR INPUT kw RATING CONDITIONS Cooling: Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. NOTE: Data referred to: MPAF188R5TAA 17
18 OUTDOOR UNIT: INDOOR UNIT: GRF228R5TAA MPAF228R5TAA V ~ 50Hz RATING CAPACITY 6,60 kw moisture removal 2 l/h COMP. POWER INPUT 1,82 kw max comp input 2,27 kw AIR FLOW RATE 3000 m³/h EVAPORATOR ENT.TEMP. C CONDENSER OUTDOOR AMBIENT TEMP. C W.B. D.B TC 6,67 6,26 6,07 5,78 5,42 5,01 CM 1,20 1,37 1,54 1,71 1,88 2,05 21 SHC 4,63 4,29 4,20 4,06 3,89 3,69 23 SHC 5,23 4,86 4,76 4,62 4,45 4, SHC 5,80 5,42 5,31 5,17 4,99 4,79 27 SHC 6,41 5,99 5,87 5,72 5,42 5,01 29 SHC 6,67 6,26 6,07 5,78 5,42 5,01 31 SHC 6,67 6,26 6,07 5,78 5,42 5,01 TC 7,14 6,77 6,51 6,20 5,83 5,37 CM 1,25 1,42 1,60 1,77 1,94 2,11 21 SHC 3,99 3,75 3,64 3,50 3,33 3,11 23 SHC 4,59 4,31 4,19 4,05 3,87 3, SHC 5,19 4,89 4,75 4,61 4,43 4,22 27 SHC 5,79 5,45 0,74 5,15 4,98 4,78 29 SHC 6,40 6,03 5,85 5,71 5,54 5,32 31 SHC 6,97 6,59 6,40 6,20 5,83 5,37 TC 7,59 7,17 6,93 6,60 6,20 5,71 CM 1,31 1,48 1,65 1,82 1,99 2,16 21 SHC 3,35 3,14 3,04 2,90 2,73 2,53 23 SHC 3,95 3,69 3,60 3,46 3,29 3, SHC 4,55 4,23 4,15 4,00 3,85 3,63 27 SHC 5,13 4,78 4,71 5,20 4,39 4,19 29 SHC 5,73 5,31 5,25 5,11 4,95 4,73 31 SHC 6,33 5,87 5,81 5,67 5,50 5,29 TC 7,99 7,60 7,35 7,00 6,57 6,05 CM 1,52 1,66 1,80 1,94 2,08 2,22 23 SHC 3,28 3,10 3,00 2,86 2,68 2, SHC 3,88 3,63 3,54 3,41 3,24 3,04 27 SHC 4,48 4,18 4,10 3,96 3,80 3,59 29 SHC 5,08 4,71 4,65 4,52 4,35 4,15 31 SHC 5,65 5,27 5,21 5,06 4,91 4,71 TC 8,51 8,03 7,78 7,35 6,87 6,40 CM 1,72 1,83 1,94 2,05 2,16 2, SHC 3,20 3,01 2,91 2,75 2,58 2,41 27 SHC 3,80 3,53 3,46 3,30 3,13 2,96 29 SHC 4,40 4,06 4,02 3,86 3,69 3,52 31 SHC 5,00 4,63 4,58 4,40 4,23 4,07 TOTAL COOLING CAPACITY kw SHC: SENSIBLE HEAT CAPACITY kw CM: COMPRESSOR INPUT kw RATING CONDITIONS Cooling: Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. NOTE: Data referred to: MPAF228R5TAA 18
19 OUTDOOR UNIT: INDOOR UNIT: GRF228R7TAA MPAF228R5TAA V 3N ~ 50Hz RATING CAPACITY 6,80 kw moisture removal 2 l/h COMP. POWER INPUT 1,87 kw max comp input 2,37 kw AIR FLOW RATE 3000 m³/h EVAPORATOR ENT.TEMP. C CONDENSER OUTDOOR AMBIENT TEMP. C W.B. D.B TC 6,87 6,45 6,25 5,96 5,59 5,16 CM 1,18 1,37 1,56 1,76 1,95 2,15 21 SHC 4,77 4,42 4,33 4,18 4,01 3,80 23 SHC 5,39 5,01 4,91 4,76 4,58 4, SHC 5,98 5,58 5,47 5,32 5,14 4,94 27 SHC 6,60 6,17 6,05 5,90 5,59 5,16 29 SHC 6,87 6,45 6,25 5,96 5,59 5,16 31 SHC 6,87 6,45 6,25 5,96 5,59 5,16 TC 7,36 6,98 6,71 6,39 6,00 5,53 CM 1,23 1,43 1,62 1,81 2,01 2,20 21 SHC 4,11 3,86 3,75 3,61 3,43 3,21 23 SHC 4,73 4,44 4,32 4,17 3,99 3, SHC 5,35 5,04 4,89 4,75 4,57 4,35 27 SHC 5,97 5,61 0,74 5,31 5,13 4,92 29 SHC 6,59 6,21 6,03 5,88 5,71 5,48 31 SHC 7,18 6,79 6,59 6,39 6,00 5,53 TC 7,82 7,39 7,14 6,80 6,39 5,88 CM 1,29 1,48 1,68 1,87 2,06 2,26 21 SHC 3,45 3,24 3,13 2,99 2,81 2,60 23 SHC 4,07 3,81 3,71 3,56 3,39 3, SHC 4,69 4,36 4,27 4,12 3,96 3,74 27 SHC 5,28 4,92 4,85 5,40 4,52 4,32 29 SHC 5,90 5,47 5,41 5,26 5,10 4,88 31 SHC 6,52 6,05 5,99 5,84 5,66 5,45 TC 8,23 7,83 7,57 7,21 6,77 6,24 CM 1,55 1,70 1,85 2,01 2,16 2,31 23 SHC 3,38 3,20 3,09 2,94 2,76 2, SHC 4,00 3,75 3,65 3,52 3,34 3,13 27 SHC 4,61 4,31 4,23 4,08 3,92 3,70 29 SHC 5,23 4,86 4,79 4,66 4,48 4,27 31 SHC 5,82 5,43 5,37 5,22 5,06 4,85 TC 8,77 8,28 8,01 7,57 7,08 6,59 CM 1,81 1,92 2,03 2,15 2,26 2, SHC 3,30 3,10 3,00 2,84 2,66 2,48 27 SHC 3,92 3,63 3,56 3,40 3,22 3,05 29 SHC 4,53 4,18 4,14 3,98 3,80 3,62 31 SHC 5,15 4,78 4,72 4,54 4,36 4,20 TOTAL COOLING CAPACITY kw SHC: SENSIBLE HEAT CAPACITY kw CM: COMPRESSOR INPUT kw RATING CONDITIONS Cooling: Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. NOTE: Data referred to: MPAF228R5TAA 19
20 5-3 Heating Capacity NOTE: 1) Point of rating condition Black dot in the chart indicate the following rating condition. indoor: 20 C D.B. outdoor: 7 C D.B. / 6 C W.B. 2) Above characteristics indicate instantaneus operation, which does not take into consideration defrost operation. 3) Fan speed: High 4) Because this air conditioner heats a room by drawing in the heat of the outside air (heat pump system). The heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, use another heating appliance in conjunction with it. Data referred to Hi-Wall models: MPAF188R5TAA MPAF228R5TAA 20
21 6. ELECTRICAL DATA 6-1 Electrical characteristics OUTDOOR UNIT: GRF188R5TAA COOLING Indoor Unit Outdoor unit Complete Unit Fan Motor Fan Motor Compressor performance at 230V 1-Phase 50 Hz Rating conditions Running Amps. A 0,40 0,41 6,19 7,00 Power input Kw 0,086 0,087 1,377 1,550 Full load conditions Running Amps. A 0,40 0,41 7,59 8,40 Power input Kw 0,086 0,087 1,927 2,100 Rating Conditions: Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load Conditions: Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 43 C D.B. HEATING Indoor Unit Outdoor unit Complete Unit Fan Motor Fan Motor Compressor performance at 230V 1-Phase 50 Hz Rating conditions Running Amps. A 0,40 0,41 5,89 6,70 Power input Kw 0,086 0,087 1,347 1,520 Full load conditions Running Amps. A 0,40 0,41 7,59 8,40 Power input Kw 0,086 0,087 1,927 2,100 Rating Conditions: Indoor Air Temperature 20 C D.B. Outdoor Air Temperature 7 C D.B. / 6 C W.B. Full Load Conditions: Indoor Air Temperature 27 C D.B. Outdoor Air Temperature 24 C D.B. / 18 C W.B. NOTE: Data referred to indoor unit MPAF188R5TAA model. For other indoor unit models there could be some differences. 21
22 OUTDOOR UNIT: GRF228R5TAA COOLING Indoor Unit Outdoor unit Complete Unit Fan Motor Fan Motor Compressor performance at 230V 1-Phase 50 Hz Rating conditions Running Amps. A 0,40 0,67 8,13 9,20 Power input Kw 0,086 0,144 1,820 2,050 Full load conditions Running Amps. A 0,40 0,67 9,93 11,00 Power input Kw 0,086 0,144 2,270 2,500 Rating Conditions: Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load Conditions: Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 43 C D.B. HEATING Indoor Unit Outdoor unit Complete Unit Fan Motor Fan Motor Compressor performance at 230V 1-Phase 50 Hz Rating conditions Running Amps. A 0,40 0,67 8,43 9,50 Power input Kw 0,086 0,144 1,920 2,150 Full load conditions Running Amps. A 0,40 0,67 9,93 11,00 Power input Kw 0,086 0,144 2,270 2,500 Rating Conditions: Indoor Air Temperature 20 C D.B. Outdoor Air Temperature 7 C D.B. / 6 C W.B. Full Load Conditions: Indoor Air Temperature 27 C D.B. Outdoor Air Temperature 24 C D.B. / 18 C W.B. NOTE: Data referred to indoor unit MPAF228R5TAA model. For other indoor unit models there could be some differences. 22
23 OUTDOOR UNIT: GRF228R7TAA COOLING Indoor Unit Outdoor unit Complete Unit Fan Motor Fan Motor Compressor performance at 230V 1-Phase 50 Hz Rating conditions Running Amps. A 0,40 0,67 3,03 4,1 Power input Kw 0,086 0,144 1,870 2,100 Full load conditions Running Amps. A 0,40 0,67 3,93 5,0 Power input Kw 0,086 0,144 2,370 2,600 Rating Conditions: Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load Conditions: Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 43 C D.B. HEATING Indoor Unit Outdoor unit Complete Unit Fan Motor Fan Motor Compressor performance at 230V 1-Phase 50 Hz Rating conditions Running Amps. A 0,40 0,67 3,23 4,30 Power input Kw 0,086 0,144 1,970 2,200 Full load conditions Running Amps. A 0,40 0,67 3,93 5,00 Power input Kw 0,086 0,144 2,370 2,600 Rating Conditions: Indoor Air Temperature 20 C D.B. Outdoor Air Temperature 7 C D.B. / 6 C W.B. Full Load Conditions: Indoor Air Temperature 27 C D.B. Outdoor Air Temperature 24 C D.B. / 18 C W.B. NOTE: Data referred to indoor unit MPAF228R5TAA model. For other indoor unit models there could be some differences. 23
24 6-2 Electric Wiring Diagram GRF188R5TAA GRF228R5TAA GRF228R7TAA 6-3 Wiring System Diagram 1-phase 3-phase MPAF228R5TAA GRF228R7TAA MPAF188R5TAA MPAF228R5TAA GRF188R5TAA GRF228R5TAA model GRF188R5TAA GRF228R5TAA GRF228R7TAA A B power supply control line m 2 m , ,5 delayed fuse 16 A 24
25 R.D. 28 Reyrieux BP Trévoux CEDEX France Tél Fax R.C.S. Bourg-en-Bresse B
TECHNICAL DATA & SERVICE MANUAL
TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE726SCL AE752SCL AE71SCL3 AE735SCL AE752SCL3 AE100SCL3 AE764SCL3 AE125SCL3 SPLIT SYSTEM AIR CONDITIONER Model No. AE726SCL AE735SCL AE752SCL AE752SCL3 AE764SCL3
More informationTECHNICAL DATA & SERVICE MANUAL
TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT:. TRIAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.102. 0.8180.611.02 09/2012 IMPORTANT! Please read before installation This air conditioning
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH
TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AE22AH 387031006 AE28AH 387031007 AE38AH 387031008
More informationTECHNICAL DATA & SERVICE MANUAL
TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: DUAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.098 38.7107.103 38.7107.106 0.8180.597.03 09/2012 IMPORTANT! Please read before installation
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW22AL 387030005 AW28AL 387030006 AW38AL 387030007 AW42AL 387030094 0.8180.467.0
More informationTECHNICAL DATA & SERVICE MANUAL
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF97R5IAA CAF98MR5IAA CAF127R5IAA CAF128MR5IAA CAF187R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. CAF97R5IAA CAF127R5IAA CAF187R5IAA CAF98MR5IAA CAF128MR5IAA
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CLM97 CLM7 CLM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No.
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS1872 + C1872 + CL1872 KS2472 + C2472 + CL2472 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS1872 KS2472 Product
More informationTECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF94R5 CAF124R5 SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. CAF94R5 387106979 CAF124R5 387106980 0.8180.361.0 07/2005 IMPORTANT! Please read before
More informationTECHNICAL DATA & SERVICE MANUAL
TECHNICAL DATA & SERVICE MANUAL XH7R / CH7R, C7R XH7R / CH7R, C7R XH7R / CH7R, C7R TH7R / CH7R, C7R TH7R / CH7R, C7R TH7R / CH7R, C7R THH7R / CH7R THH7R / CH7R FILE NO. KH7R / CH7R, C7R KH07R / CH07R,
More informationTECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513
TECHNICAL & SERVICE MANUAL SA 123A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-123A 1 851 006 95 Australia SA 123A REFERENCE NO. SM700513 IMPORTANT! Please Read Before
More informationTECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A
TECHNICAL & SERVICE MANUAL SA 183A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. SA-183A 1 851 006 96 Destination Australia SA 183A REFERENCE NO. SM700514 IMPORTANT! Please Read Before
More informationTECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338
TECHNICAL & SERVICE MANUAL SA 128S5 FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-128S5-A 1 851 004 09 General (50Hz) & Europe SA 128S5 REFERENCE NO. SM700338 IMPORTANT!
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: ASR609CL ASR612CL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. ASR609CL 387006970 ASR612CL 387006971 0.8180.250.0 05/2002 IMPORTANT! Please read
More informationTECHNICAL DATA & SERVICE MANUAL
TECHNICAL DATA & SERVICE MANUAL HEAT PUMP MODELS INDOOR UNIT: MPAF188R5TAA MPAF228R5TAA COOLING MODELS MPAF188C5TAA MPAF228C5TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MPAF188R5TAA 38.7104.033
More informationTECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510
TECHNICAL & SERVICE MANUAL SA 93AH FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-93AH 1 851 006 97 Australia SA 93AH REFERENCE NO. SM700510 IMPORTANT! Please Read Before
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS - Wall-mount indoor unit - OPERATING LIMITS Cooling Maximum conditions Heating Maximum conditions Outdoor temperature : 122 F (50 C) D.B. Outdoor temperature : 75 F (24 C) D.B.
More informationSPLIT SYSTEM AIR CONDITIONER
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MRAF99R5IAA MRAF129R5IAA MPAF99R5IAA MPAF129R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MRAF99R5IAA 38.7104.065 MRAF129R5IAA 38.7104.062 MPAF99R5IAA
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL XHS1271 & PNR-XS1872 + CH1271 XHS1872 & PNR-XS1872 + CH1872 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS1271
More informationTECHNICAL DATA & SERVICE MANUAL MULTI-SPLIT SYSTEM AIR CONDITIONER
TECHNICAL DATA & SERVICE MANUAL Outdoor Unit GR54M2C Indoor Unit MCA27MC (X2) MULTI-SPLIT SYSTEM AIR CONDITIONER Indoor Unit Outdoor Unit MCA27MC GR54M2C 0.8180.195.0 04/2001 IMPORTANT! Please Read Before
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL XS171 & PNRXS187 + C171 XS171 & PNRXS187 + CL171 XS187 & PNRXS187 + CH187 XS187 & PNRXS187 + CL187 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER
More informationTECHNICAL DATA & SERVICE MANUAL MTF94C5TAA
TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA 0.8180.472.0 07/2005 Page 1. SPECIFICATIONS 3 1-1 Unit Specifications 3 1-2 Major Component Specifications 4 2. DIMENSIONAL DATA 6 2-1 Unit Dimensions 6 3. ELECTRICAL
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU
More informationTECHNICAL & SERVICE MANUAL SAP K181A + SAP C181A
TECHNICAL & SERVICE MANUAL SAP K181A SAP K241A + SAP C181A + SAP C241A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K181A S 1 852 068 06 SAP K241A
More informationTECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL AWR222CLE - AER222SC AWR222CLE - AER222SC3 SPLIT SYSTEM AIR CONDITIONER 0.8180.076.0 03/00 Important! Please Read Before Starting This air conditioning system meets strict safety
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF94R5IAA + GRF97R5I MCAF124R5IAA + GRF127R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF94R5IAA
More informationTECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia
AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K303A + SAP C303A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K303A A 1 852 098 83 Outdoor Model No.
More informationTECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K301AH + SAP C301AH FILE NO. SAP K301AH SAP C301AH REFERENCE NO.
TECHNICAL & SERVICE MANUAL SAP K301AH + SAP C301AH FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K301AH S 1 852 071 34 Outdoor Model No. Product Code
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KE30NKU + CU-KE30NKU CS-KE36NKU + CU-KE36NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KE30NKU CS-KE36NKU Product Code No. 1 852 360 88
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA-
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA- SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MCAF72R5TA- 387104015 MCAF92R5TA- 387104016 MCAF122R5TA- 387104017
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS0971 + C0971 + CL0971 KS1271 + C1271 + CL1271 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS0971 KS1271 Product
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL KHS308 + CH308 KHS368 + CH368 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KHS308 KHS368 Product Code No. 85 354 8 85 354 9 Outdoor
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL XHS7 & PNRXS87 + CH7 XHS87 & PNRXS87 + CH87 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS7 (PNRXS87) XHS87 (PNRXS87)
More informationTECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA
TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245C / 3SC Cooling only model ARGO 235H / 3HP Heat pump model 0.8180.405.2 09/2006 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF88R5I + GRF86R5I MCAF48R5I + GRF46R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF88R5I MCAF88R5IAA
More informationSPLIT SYSTEM AIR CONDITIONER
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MPAFIA0R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MPAFIA0R5IAA 38.7104.074 0.8180.590.01 10/2012 IMPORTANT! Please read before installation
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Solenoid Valve Kit For 3WAY VRF System CZ-PXXXHR3 () IMPORTANT! Please Read Before Starting This solenoid Valve kit must be installed by the sales dealer or installer. This information
More informationSERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-A Models MUZ-SF25VE - E1 MUZ-SF42VE
More informationSERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E
Revision E: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH629 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-E Models
More informationMULTI-SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL SAP KM97AHA ( 2) + SAP CM1827AHA FILE NO. Destination: Australia MULTI-SPLIT SYSTEM AIR CDITIER Indoor Model No Product Code No. Outdoor Model No. Product Code No. SAP KM97AHA
More informationSERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC
Revision F: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH590 REVISED EDITION-E. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED EDITION-F
More informationSERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC
Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624
More informationWall Mounted Split Systems
MWM - 2005 Wall Mounted Split Systems Models: MWM 007F/FR MWM 010F/FR MWM 015F/FR MWM 020F/FR MWM 025F/FR MWM 030F/FR Contents Features... 1 Nomenclature... 2 Specifications... 3 Performance Table... 11
More informationMUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589)
SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 Models MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service
More informationSERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2
Revision F: "How to check miswiring and serial signal error" has been corrected (11-5. M ). OBH648 REVISED EDITION-E is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH648 REVISED EDITION-F Models
More informationSERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE
More informationSPLIT SYSTEM AIR CONDITIONER
TECHNICAL DATA & SERVICE MANUAL Indoor Unit MCA201R MCA271R MCA351R Outdoor Unit GR201R GR271R GR351R SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT 0.8180.263.1 06/2002 Important! Please Read Before
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : KMS0772 FILE NO. KMS0972 KMS1272 KMS1872 KMS2472 Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU
More informationTECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA
TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245SCH2O( I ) Cooling only model ARGO 235HPH2O( I ) Heat pump model 0.8180.519.1 11 / 2007 Table of contents Page A SPECIFICATIONS 1) Unit specifications
More informationCU-3E23CBPG, CU- 4E27CBPG,
Order No. PHAAM0810051C2 Air Conditioner Indoor Unit Outdoor Unit CS-E7JKEW CU-E7JKE CS-E9JKEW CU-E9JKE CS-E12JKEW CU-E12JKE CS-E15JKEW CU-E15JKE CS-E15JKEW CU-E15JKE-1 CS-E7JKEW-3 CU-E7JKE-3 CS-E9JKEW-3
More informationSERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC
Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.
More informationSERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
More informationSERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1
SPLIT-TYPE AIR CONDITIONERS Revision D: Changing defrost finish temperature has been corrected (10-1.). Please void OBH516 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED
More informationAUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET
AUTO COOL DRY MODE TIMER ON OFF TIMER OFF/ON TEMP ON TIMER FAN SPEED AIR SWING SET 1 2 3 FAN SPEED AIR SWING OFF CANCEL AC RC SET CHECK CLOCK RESET Order No: PAPAMY1611008CE Indoor Unit CS-MPS9SKH CS-MPS12SKH
More informationSERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A
OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES
More informationTECHNICAL & SERVICE MANUAL
TECHNICAL & SERVICE MANUAL INDOOR UNIT: MCAF94MR5IAA MCAF124MR5IAA MCAF184MR5IAA MCAF244MR5IAA NOV.2003 Destination: General area (50Hz) Europe (50Hz) Australia (50Hz) General area (60Hz) DC INVERTER MULTI-SYSTEM
More informationSERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A
SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART
More informationConcealed Ducted Split Series R-407C MBH
Concealed Ducted Split Series R-407C 4-60 MBH Ducted Split with Hermetic Compressor Tropical 50 Hz For more technical information please visit Table of Contents INTRODUCTION NOMENCLATURE UNIT RATING SUMMARY
More informationTABLE OF CONTENTS. Air Conditioner
Order No. MAC0804027A2 Air Conditioner CS-E9GFEW-2 CU-E9GFE-2 CS-E12GFEW-2 CU-E12GFE-2 CS-E18GFEW-2 CU-E18GFE-2 CU-2E15GBE CU-3E18EBE CU-3E23CBPG CU-4E27CBPG Please file and use this manual together with
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE9NB4U & CZ-18BT1U CS-MKE12NB4U & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 9,000BTU / h 11,900BTU / h 17,500BTU
More informationINVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL SAP-KRV91EH + SAP-CRV91EH FILE NO. INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. Outdoor Model No. Product Code No. Destination SAP-KRV91EH 1 852 065
More informationTEST RUN SERVICE MANUAL
TEST RUN SERVICE MANUAL Model No. Outdoor Unit ME Class Model Name HP U-MEE 0HP U-0MEE HP U-MEE HP U-MEE HP U-MEE HP U-MEE 0HP U-0MEE U-MEEE U-0MEEE U-MEEE U-MEEE U-MEEE U-MEEE U-0MEEE Indoor Unit Class
More informationDestination Europe WARNING
Order No: PAPAMY1406071CE Indoor Unit CS-E12QD3EAW Outdoor Unit CU-E12QD3EA Destination Europe Please file and use this manual together with the service manual for Model No. CU-2E15PBE CU-2E18PBE CU-3E18PBE
More informationRoom Air Conditioner CONTENTS CS-E9BKP CU-E9BKP5 CS-E12BKP CU-E12BKP5. Order No: MAC C2
Order No: MAC008C Room Air Conditioner CS-E9BKP CU-E9BKP5 CS-EBKP CU-EBKP5 CONTENTS Page Page Features Functions Product Specifications 6 Dimensions 0 5 Refrigeration Cycle Diagram 6 Block Diagram 7 Wiring
More informationAir Conditioners. Technical Data RZQG-L
Air Conditioners Technical Data O u t d o o r u n i t s o p t i m i z e d f o r s e a s o n a l e f f i c i e n c y w w w. d a i k i n. e u RZQG-L Air Conditioners Technical Data O u t d o o r u n i t
More informationSERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B
More informationAIR-CONDITIONER SERVICE MANUAL
FILE NO. A90-9608 SERVICE MANUAL AIR-CONDITIONER S SPLIT BUILT-IN DUCT TYPE RAV-362B-PE/ RAV-462B-PE/ SPLIT CEILING TYPE RAV-362C-PE/ RAV-462C-PE/ SPLIT CASSETTE TYPE RAV-362U-PE/ RAV-462U-PE/ PRINTED
More informationSERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC
Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : MCAF78MR5I MCAF98MR5I MCAF128MR5I MCAF188R5I MCAF248R5I FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity
More informationSERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A
Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA
More informationTABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13
R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.
More information1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units
Features O u t d o o r U n i S p l i t S k y R Y N - E V B R - 4 0 a Outdoor units for pair application Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply
More informationInstaller manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50
-30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation
More informationContent. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...
R410A Tropical Split Type AC Technical Manual Content Content Part 1 General Information... 2 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 88 Part 4 Installation... 120 Part 5 Control... 154 Indoor
More informationPUHZ-SHW140YHA PUHZ-SHW230YKA
1 Specifications Model Name PUHZ-SHW1YHA PUHZ-SHWYKA Power supply (phase, cycle, voltage) 3φ, 0V, Hz 3φ, 0V, Hz Max. current A 13.0 6.0 Breaker size A 16 3 Outer casing Galvanized plate Galvanized plate
More informationSELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS
SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS Cooling Capacity from 115,000 to 670,000 Btu/hr Btu/hr Smartwise Innovations... Towards Green, Quality & Reliability Solutions SERIES INTRODUCTION
More informationSUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP
VEP075N432G Job Name: Location: Schedule No.: System Designation: Engineer: Architect: Date: For: Reference Approval Review Construction FEATURES Two-pipe heat pump Access to electrical box for ease of
More informationUP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM
EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors
More information2-WAY ECO-i MULTI SYSTEM
SERVICE MANUAL 2-WAY ECO-i MULTI SYSTEM CHDX07263 CHDXR07263* CHDX09663 CHDXR09663* Outdoor Units Class 72 96 C ECO-i W-2WAY CHDX07263 CHDX09663 CHDXR07263* CHDXR09663* Refrigerant R410A is used in the
More informationMAC N-407 Air-Cooled Chiller
MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=
More informationTECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)
DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage
More informationDESIGN & TECHNICAL MANUAL
AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product
More informationUCV CONDENSING UNITS SPECIFICATIONS 1. Specifications
UCV CONDENSING UNITS SPECIFICATIONS 1. Specifications Model UCV-76C UCV-96C Code 220075900040 220075900020 Power supply V- Ph-Hz 380-415~3~50 Capacity Btu/h 76000 96000 Cooling Input W 8100 10000 Rated
More informationSERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH
Revision D: Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-D Models MUZ-FH06NA MUZ-FH09NA
More informationCondensing Units CUS 15-60
Condensing Units CUS 15-60 General Description UNIT IDENTIFICATION AIR COOLED CONDENSING UNIT CUS... Condensing Unit with Propeller Fan and Scroll Compressor 15-60... Model Size D... Double Circuit e.g....
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU / h 11,900BTU / h 17,500BTU / h 24,200BTU / h
AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKS7NKU CS-MKS9NKU CS-MKS12NKU CS-MKS18NKU CS-MKS24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU
More informationHigh Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)
High Ambient / High Efficiency Series R - 410a 50Hz Ducted Split Air Conditioners (5.0 kw - 17.5 kw) ISO 9001 : 2008 ISO 14001 : 2004 ISO 18001 : 2007 R - 410a 50Hz Introduction: Established in the year
More informationAIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE
-(1) SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-24UKHP-E3 / RAS-24UAH-E3 RAS-18UKHP-E3 / RAS-18UAH-E3 RAS-24UKP-E3 / RAS-24UA-E3 RAS-18UKP-E3 / RAS-18UA-E3 RAS-24UKP-AR3 / RAS-24UA-AR3 RAS-18UKP-AR3
More informationDESIGN & TECHNICAL MANUAL
AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications
More informationCU-B24DBE5 CS-F28DTE5 CU-B28DBE5 CS-F28DTE5 CU-B28DBE8 CS-F34DTE5 CU-B34DBE5 CS-F34DTE5 CU- B34DBE8 CS-F43DTE5 CU-B43DBE8 CS-F50DTE5 CU-B50DBE8,
Order No. MAC0605029C2 Air Conditioner CS-F18DTE5 CU-B34DBE5 CS-F18DTE5 CU-B34DBE8 CS-F24DTE5 CU-B43DBE8 CS-F28DTE5 CU-B50DBE8 Please file and use this manual together with the service manual for Model
More informationCommercial High-Efficiency Condensing Units
FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2
More informationAir Conditioner SVC MANUAL(Exploded View)
Internal Use Only http://biz.lgservice.com Air Conditioner SVC MANUAL(Exploded View) Type : Ceiling Concealed Duct MODEL : AMNW24GBGA0 [LMHN240HV] AMNW36GBGA0 [LMHN360HV] CAUTION Before Servicing the unit,
More informationLaunching of new SET-FREE Outdoor Units - RAS-FSXN1E Series (8-54HP)-
Suary PAGE: 1 / 47 1 This Technical Bulletin introduces the new outdoor units of the SET-FREE FSXN1E Series (8 to 54HP) using R410A. 2 The details are indicated in the description. Index 1. Main concepts...
More informationTABLE OF CONTENTS. Air Conditioner CS-MRE12MKE
Order No. PHAAM1103074C8 Indoor Unit CS-MRE7MKE CS-MRE9MKE CS-MRE12MKE Air Conditioner Outdoor Unit CU-2RE15MBE CU-2RE18MBE TABLE OF CONTENTS PAGE 1 Safety Precautions-----------------------------------------------
More informationCatalogue 2015 AMITIME ELECTRIC CO., LTD Add: Yandong 5th Rd, Dayan Industrial Zone, Huangpu Town, Zhongshan City, Guangdong, China Tel: 86-760-23973810 Fax: 86-760-23973813 Email: info@amitime.com Http://www.amitime.com
More informationWALL MOUNTED TYPE ROOM AIR-CONDITIONER
TECHNICAL MANUAL & PARTS LIST DRAFT WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK50HE-S, SRK56HE-S (Split system, air cooled cooling only type) SRK50CE-S, SRK56CE-S
More informationDESIGN & TECHNICAL MANUAL
AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LLCC AS G09LLCC AS G12LLCC OUTDOOR AO G07LLCC AO G09LLCC AO G12LLCC 1.INDOOR UNIT : AS G07LLCC AS G09LLCC AS G12LLCC DTR_AS087E_02
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Inverter Split System Air Conditioner COOL/ DRY Model This air conditioner uses the new refrigerant R40A. Refrigerant service valve size = 5/6" Contents Page Model Combinations
More information