hydronics WHAT S WRONG WITH THIS SCHEMATIC?

Size: px
Start display at page:

Download "hydronics WHAT S WRONG WITH THIS SCHEMATIC?"

Transcription

1 BY JOHN SIEGENTHALER WHAT S WRONG WITH THIS SCHEMATIC? In the September/October 2005 issue of HPAC Magazine, methods to draw hydronic piping schematics were discussed. These drawings are an efficient way of communicating the intricacies of modern hydronic systems from designer to installer to troubleshooter. Learning to spot design errors in the schematic phase of a project and making the necessary corrections is much easier and far less costly than correcting as built errors. Three of the schematics shown in this article contain serious design errors. All are based on actual installations that have no doubt disappointed the owners of these systems. If you are well versed in hydronic heating and have been following HPAC articles on hydronic heating you may spot the design error(s) in the schematics shown in Figures 1, 3 and 5. Most involve the violation of the basic design principles summarized at the end of the article. If the errors are not as apparent, carefully study the differences between Figures 1 and 2, 3 and 4, and 5 and 6. ACROSS THE HEADERS Take a look at the schematic in Figure 1. It represents part of a $200,000 mechanical system installed in a $6.5-million house. The owners were convinced they were buying top shelf comfort in the form of radiant floor heating. What they got was a heating system with a mind of its own in regards to when and where comfort would exist in this trophy house. After looking at the installation it appeared that the installer s intent was to create a primary/secondary (P/S) system. That is the way the system started out in the mechanical room. However, once the was outside the mechanical room, the secondary circuits were attached across the mains rather than by closely-spaced tees. Perhaps the installer was so used to connecting branch loads across headers in previous installations that he lost faith in the concept of P/S at that decisive moment when tees meet tubing. When you design-as-you-solder sudden impulses to change what you are about to do occur frequently. The piping system in Figure 1 creates a significant pressure differential on all zone circuits whenever the primary circulator is running. In this system that circulator operated whenever the outdoor temperature was below 65F. The flowcheck valves present in each branch circuit could only hold back about 0.3 psi. The pressure differential created across the and return of the branch circuits by the primary circulator was many times higher than this. The result was overheating due to unanticipated flow in nearly all zones. The fact that the heating curve (e.g. reset ratio) on the boiler reset control was set higher than necessary only exacerbated the situation. One way to correct the situation is shown in Figure 2. This approach creates true secondary circuits that are hydraulically isolated from each other as well as the primary circulator. This eliminated the previously described heat migration. Several crossover bridges now connect between the and return mains. The total flow divides up across these bridges based on their individual flow resistance, the same as it would in a twopipe distribution system. Each crossover is supplied with water at about the same temperature. When a given secondary circulator operates, flow is routed from the first of the closely-spaced tees, through the circuit, and back to the downstream tee. No flow develops in secondary circuits in which the circulator is not operating. This approach also allowed the existing installation to be corrected with minimal invasive surgery. Case solved. CONTINUED ON PAGE 26 FIGURE 1 FIGURE 2 zone manifold station parallel isolation valves closely-spaced tees (primary / secondary connection) "primary circulator" "secondary circulator" flow-check higher pressure here lower pressure here partially open ball valve heat input primary circulator zone manifold station heat input NOTE: the zone circuits are connected across the mains flow balancing valve 24 HPAC NOVEMBER/DECEMBER 2005

2 Circle #18

3 CONTINUED FROM PAGE 24 REALLY MIXED UP The piping schematic in Figure 3 represents the original installation of a radiant floor heating system in a new 7,000 square foot municipal office building. During its first winter this building could not be maintained above the mid-50s. Rather than a typical 15 to 20F, the temperature difference between the and return ends of some radiant floor circuits was in the range of 60F. Can you spot the cause of this? FIGURE 4 outdoor sensor injection mixing controller zone circulators FIGURE 3 flow-check valve return temp. sensor 3-way thermostatic mixing valve purging valves temp. sensor piping offset between injection tee and sensor to ensure good mixing prior to flow past sensor T T zone circulators One major problem was that the zone circulators were not installed between the mixing valves and the manifold stations. This is why the circuit flow rate was so low and the temperature drop along the circuits was so high. Another design flaw is that the oil-fired boiler has no protection against flue gas condensation. Assuming the circulators were properly relocated upon recognizing the error described above, another problem would instantly show up sustained flue gas condensation within the boiler. Still another issue is that the circulators are all pumping toward rather than away from the location where the expansion tank tees into the system. Hence, the circulators are attempting to suck rather than push water around the system. This often makes it hard to purge the system of air and, given the right circumstance, can lead to pump cavitation. The fix for this system was to remove the individual mixing valve and install a variable speed injection mixing system. The latter can provide fully reset water temperature control to the zone circuits while at the same time protecting the boiler from sustained flue gas condensation. The circulators pump into their respective zone circuits and away from the injection riser location, which is the pressure reference back to the primary loop. Purging valves on all circuits ensures efficient air removal. Interestingly the corrected piping/control design would have been far less expensive than the original installation. Live and learn. WHAT TO WATCH FOR Here is a summary of things to watch out for as you design and document your hydronic systems, as well as when you look over schematics from other sources. Many of them have been discussed in previous articles. Once you have taken your system schematics and the associated calculations through this list the schematic is ready for take off. Always protect conventional boilers from sustained flue gas condensation. Do not create flow bottlenecks. Do not create heat transfer bottlenecks. Use closely spaced tees for primary/secondary piping. Provide purging for all secondary circuits. Provide proper thermal traps for variable speed injection mixing. Control differential pressure when zoning with valves. Provide hydraulic separation of high flow resistance devices. Do not circulate heated water through unfired heat sources. Do not oversize primary circulators. Pump away from expansion tank connection point. Protect against thermal migration due to buoyancy of hot water. Be sure there is flow past temperature sensors when their associated control is active. Be sure to sense the final blended temperature for mixing systems. Do not use gas- or oil-derived heat to maintain a solar storage tank or buffer tank for a wood-fired boiler at an elevated temperature. 26 HPAC NOVEMBER/DECEMBER 2005

4 This works fine in modest applications, but when the shower stall comes equipped with a seat belt you had better get serious about producing lots of DHW. ALL BOTTLED UP The schematic in Figure 5 might be found in a number of highend custom homes. A multiple boiler system is being used to provide plenty of power for space heating, snowmelting and, FIGURE 5 anti-scald rated tempering valve cold water sensor for boiler staging controller closely spaced tees primary circulator 1/25 hp circulator 3/4" copper presumably, high capacity domestic water heating. Assume the total heat output of the three boilers is 450,000 Btuh. When there is a call for domestic water heating the designer s intent is to focus the full output of the multiple boiler system on the DHW tank, treating it as a priority load over space heating. The designer may have all the necessary control actions for this to take place, but take a look at the piping details secondary circuits (and sizes) used for the DHW subsystem and make note of what you think is a problem. If you can t find anything that appears to be wrong let me ask another question: Do you think that 450,000 Btuh will make it from the boiler plant to the DHW tank through 3/4 copper tubing with the assistance of a 1/25 horsepower (hp) zone CONTINUED ON PAGE 28 Circle #19 NOVEMBER/DECEMBER 2005 HPAC 27

5 CONTINUED FROM PAGE 27 FIGURE 6 FIGURE 7 circulator? If you do you are going to be very disappointed. This situation represents a severe bottleneck to flow. Even if the tank s internal heat exchanger had a very large surface area, the flow developed through the piping connecting the heat exchanger with the rest of the system would be woefully incapable of ing the necessary flow rate. For example, if we assume the temperature drop across the heat exchanger at design rate of heat transfer was a typical 20F, the necessary flow rate would be: FLOWRATE = BTUH = 450,000 = 45 GPM 500 X T 500 X 20 This flow would be pushing the velocity limits of a two-inch copper tube. It is also well beyond the flow capability of a 1/25 hp zone circulator, even if the piping connecting the tank to the system was two-inch or larger. So why does this happen? The answer is that many installers are accustomed to piping smaller indirect water heaters that handle the load of a typical three-bedroom house with 3/4-inch tubing and a zone circulator. This works fine in modest applications, but when the shower stall comes equipped with a seat belt you had better get serious about 28 HPAC NOVEMBER/DECEMBER 2005 plenty! of pump plenty of pump closely-spaced tees sensor downstream of P/S interface w/ boilers closely-spaced tees sensor downstream of P/S interface w/ boilers check to prevent heat migration plenty of heat exchanger strainer check to prevent! heat migration plenty! of heat exchanger bronze or stainless steel circulator!! anti-scald rated! tempering valve! cold! water! secondary circuits anti-scald rated tempering valve cold water secondary circuits producing lots of DHW. The wet-side corrections for this situation are shown in Figure 6. It includes an upgrade in both pipe size and circulator capacity, as well as a calculation to verify that the DHW heat exchanger can handle the full heat output rate of the boiler plant while working at an acceptable temperature drop. If the latter calculation shows the indirect tank cannot keep up with the boiler plant you will need to go to a properly-sized external heat exchanger as shown in Figure 7. Another error in Figure 5 is the sensor placement for the boiler staging control. If installed as shown, there will be times when the boiler staging control is satisfied that the water temperature leaving the boilers is adequate for the load. When this occurs the boilers and the boiler circulators will be turned off. This stops flow past the sensor. The controller thinks everything is fine based on the temperature of the sensor and does not fire the boilers or operate the boiler circulators. Meanwhile the loads may be screaming for heat. The correction is to place the sensor downstream of the closely-spaced tees that interface the boiler piping to the load piping as shown in Figures 6 and 7. Do these details right and you will have one mean hot water making machine. AN INVITATION If you have run across a bad system design (and few who have been in this industry for any length of time have not), send it to me via . Perhaps there will be another round of these challenged hydronic system designs in the future. No names or identifiable specifics will be used, just fundamental design information that can help others avoid a similar problem down the road. John Siegenthaler, P.E. is the author of Modern Hydronic Heating. Visit his website at for reference information and software to assist in hydronic system design. He can be reached at john@hydronicpros.com. RATE THE ARTICLE! Will this information be useful? Please circle the appropriate number on the Reader Postcard. Thank you. VERY USEFUL USEFUL NOT USEFUL

A Primary Concern by John Siegenthaler, P.E. October 1, 2005

A Primary Concern by John Siegenthaler, P.E. October 1, 2005 A Primary Concern by John Siegenthaler, P.E. October 1, 2005 When does a parallel primary loop make sense? It s hard to have a discussion on modern hydronic heating and not talk about primary/secondary

More information

"Best Practices in Modern Hydronic Heating - THE DETAILS

Best Practices in Modern Hydronic Heating - THE DETAILS "Best Practices in Modern Hydronic Heating - THE DETAILS 190 supply water temperature (ºF) 170 150 130 110 90 fin-tube convector (RR=1.38) panel radiator (RR=1.0) thin slab rad. floor (RR=0.69) slab r

More information

HYDRONICS BY JOHN SIEGENTHALER

HYDRONICS BY JOHN SIEGENTHALER HYDRONICS BY JOHN SIEGENTHALER ALTERNATIVES TO PRIMARY/SECONDARY PIPING Most people who have been involved with modern hydronic heating have heard of primary/secondary (P/S) piping. For many it is now

More information

Radiant Heating. Systems

Radiant Heating. Systems O p t i m i z i n g t h e P e r f o r m a n c e o f Radiant Heating Systems Minimizing costly mistakes and maximizing a radiant project s performance by focusing on building and system efficiency Radiant

More information

Hydraulic Separation Moving Beyond Priamry / Secondary Piping...

Hydraulic Separation Moving Beyond Priamry / Secondary Piping... Hydraulic Separation Moving Beyond Priamry / Secondary Piping... load! #1 load! #2 load! #3 primary! circulator presented by: John Siegenthaler, P.E. Appropriate Designs Holland Patent, NY www.hydronicpros.com

More information

Flow Reversal in Primary/Secondary Systems by John Siegenthaler, P.E. April 17, 2007

Flow Reversal in Primary/Secondary Systems by John Siegenthaler, P.E. April 17, 2007 Flow Reversal in Primary/Secondary Systems by John Siegenthaler, P.E. April 17, 2007 When flow reversal occurs, the heat transfer from the secondary circuit is mostly unaffected, as are the other secondary

More information

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall. Chapter 4 Variable-speed pumps. A variable-speed pump varies the flow rate by maintaining a constant pressure differential as zone valves open and close. A sensor measures the difference in pressure between

More information

Outdoor Reset Control Theory FULL versus PARTIAL reset

Outdoor Reset Control Theory FULL versus PARTIAL reset Outdoor Reset Control Theory FULL versus PARTIAL reset Conventional boilers must be protected against sustained operation at low temperatures. If not, they will be damaged by sustained flue gas condensation.

More information

Caleffi Hydronic Solutions Contact: Rex Gillespie, Director of Marketing Phone: (414)

Caleffi Hydronic Solutions Contact: Rex Gillespie, Director of Marketing Phone: (414) Caleffi North America, Inc. 3883 W. Milwaukee Road Milwaukee, WI 53208 T: 414.238.2360 F: 414.238.2366 LITERATURE RELEASE Caleffi Hydronic Solutions June 10, 2010 Contact: Rex Gillespie, Director of Marketing

More information

Accomplish Maximum Green Results in Commercial Buildings #

Accomplish Maximum Green Results in Commercial Buildings # Accomplish Maximum Green Results in Commercial Buildings #7 9.8.10 Nearly everyone agrees that multiple small boiler systems provide optimum efficiency when compared to a single larger boiler system in

More information

HPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations

HPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations Series 600 LFI / CFI Series 700 HFS Zone Control Stations Heating and Radiant Floor Zone Control Stations Installation Instructions Thank you for purchasing the finest in heating and radiant floor Control

More information

Selecting Circulators TD10 EFFECTIVE: SUPERSEDES:

Selecting Circulators TD10 EFFECTIVE: SUPERSEDES: TACO COMFORT SOLUTIONS : HOME HEATING BASICS Selecting Circulators TD EFFECTIVE:.3. SUPERSEDES:.. This article shows you how to select a Taco circulator that lets the hydronic system you re designing perform

More information

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money. How hydronic heating systems work

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money. How hydronic heating systems work EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links How hydronic heating systems work Advantages Disadvantages Design alternatives Baseboard convectors Residential Hydronic Heating A residential

More information

Best Practices for Condensing Boilers

Best Practices for Condensing Boilers ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cleaverbrooks.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For

More information

The electrical wattage needed by the circulator is:

The electrical wattage needed by the circulator is: The electrical wattage needed by the circulator is: w e = 0.4344 f P n w/w A current-generation wet-rotor circulator has a maximum wire-towater efficiency in the range of 25 percent. If we put the data

More information

INSTALLATION INSTRUCTIONS WINTER/SUMMER KIT

INSTALLATION INSTRUCTIONS WINTER/SUMMER KIT INSTALLATION INSTRUCTIONS WINTER/SUMMER KIT HYDRONIC HEATING WITH THE SOLAR WATER HEATER This winter/summer kit provides the necessary components for connections to a boiler. Through the proper installation

More information

Applications and Piping Strategies for Condensing Boilers - Introduction

Applications and Piping Strategies for Condensing Boilers - Introduction Applications and Piping Strategies for Condensing Boilers - Introduction Foil 2, 10/2015 Viessmann Manufacturing Applications and Piping Strategies for Condensing Boilers Webinar Objectives: 1. Control

More information

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve VENT APPENDIX A: PIPING SYMBOL LEGEND GENERIC COMPONENTS CALEFFI COMPONENTS circulator circulator w/ ThermoBloc union circulator w/ swing check spring loaded balancing balancing w/ gate check globe s purging

More information

Hydronic Mechanical Panels

Hydronic Mechanical Panels Hydronic Assemblies Inc. 56 Horse Hill Rd Concord NH 2015-2016 Hydronic Mechanical Panels Contact 4805 Main St. Waitsfield, Vermont 05673 Phone : 802-583-5500 WWW.Houseneeds.com Hydronic Assemblies Inc.

More information

Installation & Operation Manual Models: TSU

Installation & Operation Manual Models: TSU TSU-I-O Rev A Installation & Operation Manual Models: TSU 150-940 CAUTION: This appliance is not intended for potable water. This manual must only be used by a qualified heating installer / service technician.

More information

know exactly what you are getting before you order it. You can order with confidence knowing th each panel is completely tested before it ships.

know exactly what you are getting before you order it. You can order with confidence knowing th each panel is completely tested before it ships. y y y Imagine know exactly what you are getting before you order it. You can order with confidence knowing th each panel is completely tested before it ships. Quick-ship panels are available for almost

More information

Partner. Peerless. Indirect-Fired. Water Heater. Installation, Operation & Maintenance Manual

Partner. Peerless. Indirect-Fired. Water Heater. Installation, Operation & Maintenance Manual Peerless Indirect-Fired Partner Water Heater Installation, Operation & Maintenance Manual Product Selection 1. The following guidelines apply to residential systems only. For commercial or institutional

More information

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?

More information

ARTESIAN 220 & 340 Instantaneous Indirect Water Heater By Dunkirk Boilers INSTALLATION AND OPERATING INSTRUCTIONS ENGINEERING MANUAL

ARTESIAN 220 & 340 Instantaneous Indirect Water Heater By Dunkirk Boilers INSTALLATION AND OPERATING INSTRUCTIONS ENGINEERING MANUAL ARTESIAN 220 & 340 Instantaneous Indirect Water Heater By Dunkirk Boilers INSTALLATION AND OPERATING INSTRUCTIONS ENGINEERING MANUAL Manufacturer's Warning To reduce the possibility of injury due to scalding,

More information

- Essay Control Functions and Benefits

- Essay Control Functions and Benefits - Essay Control Functions and Benefits E 005 07/01 A hydronic heating control system performs many complex and important functions. Each of these functions provide benefits that make the system comfortable,

More information

- Application A Boiler Control 262 & One Stage Setpoint Control 150. Mechanical Remote Display Module (D1) 040 MODE 1

- Application A Boiler Control 262 & One Stage Setpoint Control 150. Mechanical Remote Display Module (D1) 040 MODE 1 - Application Boiler Control & One Stage Setpoint Control 150 A -1 07/99 echanical Remote Display odule () 040 Outdoor Sensor () 070 150 ODE 1 Class II Transformer 120 V (ac) 24 V (ac) R1 A2 Z1 Z2 Z3 T1

More information

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating

More information

- Data Brochure Boiler Control 274

- Data Brochure Boiler Control 274 - Data Brochure Boiler Control 274 274_D 03/17 The Boiler Control 274 operates up to four on/off boilers to provide outdoor reset operation, domestic hot water and setpoint operation with priority. When

More information

Medium Mass Boilers. Maxim Power VT

Medium Mass Boilers. Maxim Power VT Medium Mass Boilers Maxim Power VT What is a Medium Mass Boiler? Sufficient Mass (Boiler water capacity) to act as a built in buffer tank. Sufficient Mass to handle varying system design flows without

More information

6 PIPING ARRANGEMENTS

6 PIPING ARRANGEMENTS 6 PIPING ARRANGEMENTS The design of a panel radiator based heating system involves selection of a piping system, pipe sizes, overall design temperature drop, required flow rates and desired type of system

More information

HPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations

HPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations Series 600 LFI / CFI Series 700 HFS Zone Control Stations Heating and Radiant Floor Zone Control Stations Installation Instructions Thank you for purchasing the finest in heating and radiant floor Control

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

- Data Brochure Mixing Control 361

- Data Brochure Mixing Control 361 TIME PRGM 1 2 AMPM UN OVR S M T W T F S - Data Brochure Mixing Control 361 D 361 05/00 The Mixing Control 361 is designed to control the supply water temperature to a hydronic system in order to provide

More information

propanel Series Installation Manual

propanel Series Installation Manual propanel Series Installation Manual propanel Series Installation Manual is published by Uponor Wirsbo 5925 148th Street West Apple Valley, MN 55124 (952) 891-2000 2003 Uponor Wirsbo All rights reserved

More information

- Data Brochure Mixing Control 360

- Data Brochure Mixing Control 360 - Data Brochure Mixing Control 360 D 360 03/09 The Mixing Control 360 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or setpoint operation. The

More information

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control. Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717 The first totally integrated multiple boiler management control. USING THIS MANUAL USING THIS MANUAL A. INSTALLATION SEQUENCE Follow

More information

prestige Control Application Supplement - ACVMax

prestige Control Application Supplement - ACVMax 2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory

More information

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 422 - Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

Boiler Demand Mix 1 Demand Mix 2 Demand DHW Demand Setpoint Demand

Boiler Demand Mix 1 Demand Mix 2 Demand DHW Demand Setpoint Demand Date Code - Data Brochure Universal Reset Control 374 D 374 10/03 The tekmar Universal Reset Control 374 is designed to maximize the comfort and effi ciency provided by a hydronic heating system. The control

More information

Trials Tribulations & Rewards High T Heating Systems

Trials Tribulations & Rewards High T Heating Systems Trials Tribulations & Rewards High T Heating Systems ASHRAE Cleveland Chapter October 18 2010 Presented by Norman Hall R. L. Deppmann Company THE CALL OF THE DAY ASHRAE 90.1 Green technology High Efficiency

More information

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler WARNING: Improper installation, setup, modification, operation or maintenance of the heating system can cause personal injury and property damage. Follow each appliances' instructions precisely. For assistance

More information

Control Application. Supplement - ACVMax

Control Application. Supplement - ACVMax prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

ERGOMAX 7 INSTALLATION

ERGOMAX 7 INSTALLATION ERGOMAX 7 INSTALLATION INSTALLATION MUST CONFORM TO LOCAL CODES 1. WITH HYDRONIC BOILERS All ERGOMAX 7 units must be installed vertically. Adjustable feet for levelling are provided. PRESSURE RELIEF VALVE:

More information

OPERATION AND INSTALLATION UTILISATION ET INSTALLATION

OPERATION AND INSTALLATION UTILISATION ET INSTALLATION OPERATI AND INSTALLATI UTILISATI ET INSTALLATI Electric Modulating Micro-Boiler» HydroShark 7» HydroShark 0» HydroShark» HydroShark» HydroShark 9» HydroShark» HydroShark 9» HydroShark HydroShark 7 - HydroShark

More information

- Data Brochure Universal Reset Module 423

- Data Brochure Universal Reset Module 423 - Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

ProRadiant Controls, Valves and Actuators

ProRadiant Controls, Valves and Actuators 214 Controls, Valves and Actuators Stock Controls, Valves and Actuators BASIC HEATING CONTROL Features: Modulating mixing valve control Supply temperature high limit Seasonal pump activation Boiler activation

More information

Threaded. Flanged. Model PSH. Primary Secondary Header A-451

Threaded. Flanged. Model PSH. Primary Secondary Header A-451 Threaded Flanged Model PSH Primary Secondary Header A-451 The History of Primary-Secondary Pumping Did you know that Bell & Gossett invented Primary-Secondary Pumping? This widely popular pumping arrangement

More information

Allcan TM Installation Manual

Allcan TM Installation Manual Allcan TM Installation Manual NOTICE: READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO FOLLOW INSTRUCTIONS VOIDS WARRANTY. Introduction: The PHP Allcan (USA patent pending) is a complete primary/secondary

More information

Fundamentals of Hydronic Design

Fundamentals of Hydronic Design Radiant Based HVAC Systems www.healthyheating.com Dynamic Pressure www.healthyheating.com This educational material is copy written by Robert Bean, R.E.T., All Rights Reserved. If you wish to use this

More information

Mascot. Gas-Fired Residential and Commercial Wall-Mounted Boiler. Easy Installation, 96% Efficiency, Fully Condensing

Mascot. Gas-Fired Residential and Commercial Wall-Mounted Boiler. Easy Installation, 96% Efficiency, Fully Condensing Mascot Gas-Fired Residential and Commercial Wall-Mounted Boiler Easy Installation, 96% Efficiency, Fully Condensing Mascot is a high-efficiency, wall-mounted boiler available in three BTU sizes 126, 167,

More information

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS Copyright 2011. R. Trethewey, All rights reserved. No part of this document or file may be used without permission of the author. All diagrams are conceptual

More information

A Review of Hydronic Balancing of Cooling Water Circuit

A Review of Hydronic Balancing of Cooling Water Circuit A Review of Hydronic Balancing of Cooling Water Circuit Abhilash Shetty Department Of Mechanical Engineering SIES Graduate School of Technology, Nerul, Navi Mumbai-400706, Maharashtra, India Deepak Pandey

More information

... Green Building Details

... Green Building Details Combining Solar HW with Radiant Floor using a Demand Water Heater back-up and a Tempering Tank with a line voltage three-way valve to prevent heating the solar storage with the gas DHW... A short list

More information

BHSAPPMAN 08/00 USA. Applications Manual. Ecomatic / Logamatic Controls. Save These Instructions!

BHSAPPMAN 08/00 USA. Applications Manual. Ecomatic / Logamatic Controls. Save These Instructions! BHSAPPMAN 08/00 USA Applications Manual Ecomatic / Logamatic Controls Save These Instructions! TABLE OF CONTENTS 1 2 3 4 5 6 7 8 Introduction 1 Terms 2-4 Description of Wiring Terminals 5-7 Application

More information

Water Piping and Pumps

Water Piping and Pumps Technical Development Program DISTRIBUTION SYSTEMS Water Piping and Pumps PRESENTED BY: Michael Ho carriertdp@gmail.com 424-262-2144 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section

More information

Modular Panel System for Radiant Floor Heating MICRO-BOILERS MODULAR PANEL SYSTEMS

Modular Panel System for Radiant Floor Heating MICRO-BOILERS MODULAR PANEL SYSTEMS Modular Panel System for Radiant Floor Heating MICRO-BOILERS MODULAR PANEL SYSTEMS Comprehensive technology, energy-saving performance, plus compact professional design make HydroShark s modular panel

More information

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal Similar to traditional boiler systems, condensing boiler systems have many designs they can operate

More information

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

Product Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen

Product Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen Hydronic Mixing Block Version 1.104 The Hydronic Mixing Block is a mixing device and boiler control, with a built in circulator and system controller. The block can provide either a fixed or reset water

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

Distribution Efficiency: The Under-appreciated Benefit of Hydronics

Distribution Efficiency: The Under-appreciated Benefit of Hydronics International Centre, Mississauga, Ontario good craftsmanship, wrong approach Distribution Efficiency: The Under-appreciated Benefit of Hydronics Btu / hr presented by: John Siegenthaler, P.E. Appropriate

More information

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION As when installing or using any high voltage electrical appliance, basic safety precautions should always

More information

Instruction Sheet X Pump Block (XPB)

Instruction Sheet X Pump Block (XPB) R Instruction Sheet X Pump Block (XPB) 02-202 SUPERSEDES: July, 200 EECTIVE: October, 200 Plant ID#: 00-3883 General WARNING SYMBOL: THIS SYMBOL INDICATES THE PRESENCE O HAZARDS WHICH CAN CAUSE SEVERE

More information

heat interface units A BOILER WITHOUT A FLAME

heat interface units A BOILER WITHOUT A FLAME A BOILER WITHOUT A FLAME heat interface units Communal Heat Networks A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.

More information

Trim Pump Impellers. Fredrick/Weinman Engineered Products 2-1/2 KH, 2-1/2 x 3 x 12

Trim Pump Impellers. Fredrick/Weinman Engineered Products 2-1/2 KH, 2-1/2 x 3 x 12 Head, ft. w.c. Trim Pump Impellers TRIM THE PUMP IMPELLER SO THE FLOW PRODUCED MATCHES THE DESIGN REQUIREMENT WITH THE DISCHARGE SERVICE VALVE WIDE OPEN. IN MOST CASES, THIS WILL REDUCED THE PUMP ENERGY

More information

- Data Brochure Universal Reset Control 364

- Data Brochure Universal Reset Control 364 70 7 8 9 - Data Brochure Universal Reset Control 364 D 364 07/01 The Universal Reset Control 364 is designed to maximize the comfort and efficiency provided by a hydronic heating system. The control automatically

More information

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL The SF-10 Temperature Control () is an efficient boiler operator with a digital LCD display with backlight, a boiler pump output, and an alarm. The

More information

HPS Controls Ltd. Series 100 LTV / CTV Zone Control Stations. Heating and Radiant Floor Zone Control Stations. Installation Instructions

HPS Controls Ltd. Series 100 LTV / CTV Zone Control Stations. Heating and Radiant Floor Zone Control Stations. Installation Instructions Series 100 LTV / CTV Zone Control Stations Heating and Radiant Floor Zone Control Stations Installation Instructions Thank you for purchasing the finest in heating and radiant floor Control Stations. We

More information

Solar & Hydronic Heating

Solar & Hydronic Heating TECHNICAL FEATURE This article was published in ASHRAE Journal, February 2012. Copyright 2012 American Society of ing, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This

More information

- Data Brochure D 260. Boiler Control /09

- Data Brochure D 260. Boiler Control /09 - Data Brochure Boiler Control 260 D 260 03/09 The Boiler Control 260 is designed to control a single stage heat source in order to provide outdoor reset or Domestic Hot Water () operation. The control

More information

Models CHB/CCB APPLICATION GUIDE WALL MOUNTED GAS BOILER

Models CHB/CCB APPLICATION GUIDE WALL MOUNTED GAS BOILER Models CHB/CCB APPLICATION GUIDE WALL MOUNTED GAS BOILER This manual has been prepared for use with the appropriate Installation, Operation and Maintenance Manual. For use with CCB/CHB Boilers ONLY. Manufactured

More information

1 Exam Prep Solar Water and Pool Heating Manual (UCF) Questions and Answers (Plumbing Contractor)

1 Exam Prep Solar Water and Pool Heating Manual (UCF) Questions and Answers (Plumbing Contractor) 1 Exam Prep Solar Water and Pool Heating Manual (UCF) Questions and Answers (Plumbing Contractor) 1. For year-round use, a collector tilt of degrees works best for a project located in Tampa, Florida.

More information

WM97+ Wall Mount Boiler

WM97+ Wall Mount Boiler WM97+ Wall Mount Boiler Questions & Answers Models 70, 110 & 155 INSTALLATION 1. Can the boiler be installed in a living area? Yes, the WM97+ is a wall mounted boiler. The sealed combustion and internal

More information

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III MAXIMIZING HYDRONIC SYSTEM DESIGN PART III Presented by Cleaver Brooks Steve Connor & DCEs David Grassl June 21, 2017 TODAY S TOPICS Dispelling common myths about condensing boilers Supply water temperature

More information

- Application Boiler Control 260

- Application Boiler Control 260 - Application Control A -1 03/09 echanical Outdoor Sensor (S2) 070 120 V (ac) 24 V (ac) T3 T2 T1 Sensor (S1) 082 Electrical = Pump S1 = Sensor 082 S2 = Outdoor Sensor 070 T1,..., T3 = Thermostats U1 =

More information

DISTRIBUTION SYSTEMS. Water Piping and Pumps

DISTRIBUTION SYSTEMS. Water Piping and Pumps DISTRIBUTION SYSTEMS Water Piping and Pumps Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are targeted

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

A complete, compact steam heat exchange solution for process and domestic water heating requirements.

A complete, compact steam heat exchange solution for process and domestic water heating requirements. Precisely matched steam controls. Electric or pneumatic actuated valves. Highly efficient steam plate heat exchanger. Minimal scaling. Integral recirculation pump Can operate partially flooded. Condensate

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

Systems and Tanks. 40 H/V 60 H/V 80 V 115 V 139 V Gallon. Applications Sizing System Design

Systems and Tanks. 40 H/V 60 H/V 80 V 115 V 139 V Gallon. Applications Sizing System Design Systems and Tanks Model size 0 H/V 60 H/V 80 V 5 V 9 V Gallon Applications Sizing System Design Systems In recent years there have been many energy-saving improvements to controls and hydraulics associated

More information

Innovative Boiler & Heat Exchanger Concepts

Innovative Boiler & Heat Exchanger Concepts www.wea-inc.com Wallace Eannace Associates Presents: Innovative Boiler & Heat Exchanger Concepts for Plumbing Applications Bob Barrett, CEM, LEED AP Sales Engineer Wallace Eannace Associates, Inc. www.wea-inc.com

More information

prestige Control Application Supplement WARNING

prestige Control Application Supplement WARNING prestige Control Application Supplement WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this

More information

TURBOMAX USE & CARE MANUAL WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR

TURBOMAX USE & CARE MANUAL WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR TURBOMAX Instantaneous Indirect Water Heater USE & CARE MANUAL WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR Your TURBOMAX Instantaneous Indirect Water Heater has been carefully assembled and factory

More information

THERMAL ICE STORAGE: Application & Design Guide

THERMAL ICE STORAGE: Application & Design Guide THERMAL ICE STORAGE: Application & Design Guide Table of Contents: 1. Introduction A. History of Thermal Energy Storage B. Operating and Cost Benefits 2. Applications A Fundamental System B. HVAC Cooling

More information

Instruction Sheet. Press & Hold: Item, to view settings, to test. 24 V ±10% 50/60 Hz 3 VA 120 V (ac) 5 A 1/6 hp pilot 240 VA 20 to 260 V (ac) 2 VA

Instruction Sheet. Press & Hold: Item, to view settings, to test. 24 V ±10% 50/60 Hz 3 VA 120 V (ac) 5 A 1/6 hp pilot 240 VA 20 to 260 V (ac) 2 VA Instruction Sheet PC2 1 Two Stage Reset & Control SUPERSEDES : 102-106, dated June 1, 2000 EFFECTIVE: March 1, 2004 Plant ID# 9300-1059 Item 102-106 The PC2-1 is a microprocessor-based control designed

More information

Taco 00 Series Cartridge Circulators

Taco 00 Series Cartridge Circulators Water Circulation Pumps & Circulators Taco 00 Series Cartridge Circulators For over 70 years, Taco has led the industry with the highest quality circulators you can buy. Designed for a wide range of residential

More information

Automatic Temperature Controller (ATC)

Automatic Temperature Controller (ATC) NEW FROM APOLLO...THE FIRST MULTIPLE-FIXTURE HI-LO MIXING VALVE THAT MEETS ASSE 1017 AND THE NEW ASSE 1069 STANDARD Only Apollo offers fast delivery on the first water temperature mixing assembly to meet

More information

MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL

MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL The EM-10 Boiler Temperature Control (BTC) is an efficient boiler operator with a digital LCD display with backlight, a boiler pump

More information

Installation & Operation Manual Models: SIT030, SIT040, SIT050, SIT065, SIT080, & SIT119

Installation & Operation Manual Models: SIT030, SIT040, SIT050, SIT065, SIT080, & SIT119 SIT-I-O Rev B Installation & Operation Manual Models: SIT030, SIT040, SIT050, SIT065, SIT080, & SIT119 WARNING This manual must only be used by a qualified heating installer / service technician. Read

More information

prestige Control Application Supplement - Type 5 MCBA WARNING

prestige Control Application Supplement - Type 5 MCBA WARNING prestige Control Application Supplement - Type 5 MCBA WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE SPECIFICATIONS... 1 OVERVIEW... 2 PRECAUTIONS... 2 MOUNTING LOCATION... 2 CONNECTION TO BOILER PRIMARY PIPING:... 3 ELECTRICAL CONNECTION... 4 FLUSHING THE

More information

DIGITAL MODULATING BOILERS

DIGITAL MODULATING BOILERS DIGITAL MODULATING BOILERS FOR HEATING AND SANITARY HOT WATER CMX15 CMX18 CM15 CM18 INSTALLATI INSTRUCTIS AND USER GUIDE Please read these instructions before installing or using this appliance for the

More information

NCB-E Combi-boilers. The first high efficiency condensing combi boilers that can do it all... for larger homes

NCB-E Combi-boilers. The first high efficiency condensing combi boilers that can do it all... for larger homes The Leader in Condensing Technology NCB-E Combi-boilers The first high efficiency condensing combi boilers that can do it all... for larger homes New NaviLink Wi-Fi remote control system... Available as

More information

Brazed Plate Heat Exchangers TTP s Series

Brazed Plate Heat Exchangers TTP s Series Brazed Plate Heat Exchangers TTP s Series PRODUCT INFORMATION- APPLICATIONS INSTALLATION - MAINTENANCE GUIDE Before proceeding with installation and operation, read entire manual carefully. Failure to

More information

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR 5:1 FIRING RATE MODULATION LESS THAN 20 ppm NOx DIRECT VENT FLEXIBILITY TO 100 FEET 96% AFUE

More information

Combined Space and Water Heating: Making it Work

Combined Space and Water Heating: Making it Work Combined Space and Water Heating: Making it Work High Efficiency Heating in a Single Package Ben Schoenbauer, Center for Energy and Environment Jake McAlpine, Sustainable Resource Center February, 26 th,

More information

Using ECM Smart Circulator Pumps in Primary Pump Applications in Hydronic Systems

Using ECM Smart Circulator Pumps in Primary Pump Applications in Hydronic Systems Monday, November 27, 2017 Using ECM Smart Circulator Pumps in Primary Pump Applications in Hydronic Systems Monday Morning Minutes by Norm Hall, November 27, 2017 Last week I featured the ECM High-Efficiency

More information

GOLD Plus 30/40/60/80

GOLD Plus 30/40/60/80 PLUS Line Indirect-Fired Water Heaters Series 3 Manual Installation Startup Maintenance Parts PLUS 100/110/119 GOLD Plus 30/40/60/80 Plus 40/60/80 This manual must only be used by a qualified heating installer/service

More information

COMMON WATERSIDE ECONOMIZER APPLICATIONS:

COMMON WATERSIDE ECONOMIZER APPLICATIONS: APPLICATION MANUAL WATERSIDE ECONOMIZER TABLE OF CONTENTS Safety Approvals...1 Common Waterside Economizer Applications...1 Sequence of Operation (Single)...1 Cooling Mode...2 Heating Mode...2 Sequence

More information