SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

Size: px
Start display at page:

Download "SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500"

Transcription

1 SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500 MODEL L*BC GENERAL This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The units are shipped as single packages with the blower module mounted on top of the coil module, but the blower module can be repositioned in the field to meet almost any installation requirement. The blower module includes the blower wheels and room for a field--mounted motor and drive. The coil module includes direct expansion coils, 1" throwaway filters, liquid line solenoid valve for 50% capacity reduction, thermal expansion valves, distributors and a condensate drain pan. Each evaporator coil is pressurized with air to 325 psig and leak tested under water. After the headers are brazed onto the coil and the coil is installed in the unit, the coil will be pressurized with a combination of refrigerant--22 and nitrogen to 150 psig for pressure testing and additional leak testing. After the coil is evacuated and dehydrated, it will be pressurized with a holding charge of refrigerant--22 for storage and/or shipping. A supply air plenum, return air grille, steam coil, hot water coil, base section, suspension hardware, blower motors and drive accessories are available for field--installation to provide additional application flexibility. This evaporator blower, applied with a matching condensing unit, will provide years of quiet, efficient and dependable operation. PARTS Renewal Parts: Refer to Parts Manual for complete listing of replacement parts on this equipment. All forms referenced in this instruction may be ordered from: Standard Register 2101 West Tecumseh Road Norman, Oklahoma Toll Free Fax: (877) Toll Free Phone: (877) This instruction covers the installation and operation of the evaporator blower unit. For information on the installation and operation of the matching condensing unit, refer to Form N6Y. INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly.

2 TABLE OF CONTENTS General...1 Parts...1 Inspection...1 Nomenclature...2 INSTALLATION Limitations...3 Location...3 Rigging...3 Clearances...3 Foundations...3 Duct Connections Insulation...3 Supply Air Ducts...3 Return Air Duct Angles...3 Air Discharge Conversion...4 Capacity Reduction...7 Drain Connection...7 Blower Motor Mounting Location...7 Motor Arrangements...7 Refrigerant Mains...9 Installing Refrigerant Mains...9 Evaporator Section Piping...9 Air System Adjustment...10 Electrical Connections...10 Maintenance...12 TABLES No. Description Page 1 Unit Application Data Physical Data Operating Weight Distribution Accessory Operating Weight Distribution Accessory Static Resistance (IWG) Electrical Data Blower Motor and Drive Data Blower Performance FIGURES No. Description Page 1 Connecting Supply Ductwork Mounting Hardware Vertical & Horizontal Arrangement Plenum Base Accessories Unit Mounting Liquid Line Solenoid Valves Drain Piping Motor Mounting Location Motor Mounting Assembly Motor Arrangement Locations Motor Pulley Field Wiring Unit Dimensions PRODUCT CATEGORY L = Split-System Evaporator Blower PRODUCT NOMENCLATURE L D B C -N A NO MOTOR FACTORY INSTALLED HEAT A = Cooling only PRODUCT GENERATION D = 4th Generation PRODUCT IDENTIFIER BC = Evaporator Blower Unit NOMINAL COOLING CAPACITY 240 = 20 Tons 2 Unitary Products Group

3 LIMITATIONS This unit must be installed in accordance with all national and local safety codes. If no local codes apply, installation must conform with the appropriate national code. The unit is designed to meet National Safety Code Standards. If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense. See Table 1 for unit application data. LOCATION The LEU240 evaporator blower is not designed for outdoor installation. It must be located within the building structure, either inside or outside the conditioned space. The unit should be located as close to the condensing unit as practical and positioned to minimize bends in the refrigerant piping. Units being installed vertically or horizontally can be set directly on a floor or platform, or they can be supported by metal or wooded beams. Units being installed horizontally can be suspended from above as shown in Figure 5. Refer to Form N7.1U for more information on the installation of the suspension accessory and for the individual load on each hanger rod. RIGGING INSTALLATION Care must be taken when moving the unit. Do not remove any packaging until the unit is near the place of installation. SPREADER BARS SHOULD BE USED BETWEEN THE SLINGS TO PREVENT CRUSHING THE UNIT FRAME OR PANELS. When preparing to move the unit, always determine the center of gravity of the unit in order to equally distribute the weight. Rig unit by attaching chain or cable slings around the bottom skid. A lift truck may be used to raise a unit to a sus- TABLE 1 - UNIT APPLICATION DATA pended location. Refer to Table 2 for the total unit operating weight. CLEARANCES A 24 inch clearance is required on the end with the piping connections and the supply air blower motor to properly service and maintain the unit and to replace the filters. Some clearance will also be require for the duct and power wire connections. A clearance equal to the unit width will be required on one end of the unit if the blower shaft or the evaporator coil will have to be replaced without moving the unit. FOUNDATIONS The evaporator blower may be suspended from joists with isolation--type hangers or hooks. Refer to Figures 2 and 5 and Tables 3 and 4. All units may be set directly on a floor, pedestal, platform shelf or mounted on the suspension accessory used as a base. DUCT CONNECTIONS Ductwork should always be suspended with hangers or supported by legs. It should never be fastened directly to the building structure. Allow clearance around ducts for safety in the handling of heated air and for insulation when required. INSULATION -- Ductwork insulation should: 1. Be used when ducts pass through an unconditioned space during the cooling season or through an unheated space during the heating season. Voltage Supply Air Range Entering Air Temperatures, F Power Variation CFM Supply Cooling-db/wb Heating-db Min. Max. Min. Max. Min. Max. Min. Max. 208/ /57 95/72-150* * Both hot water and steam coils. (Do NOT use steam in hot water coils) TABLE 2 - PHYSICAL DATA Evaporator Coil Rows Deep Rows High Finned Length (in.) Fins/Inch Tube OD (in.) Face Area (Sq. Ft.) Wheel Dia. x Wd.(in.) (2 Per Unit) Quan. & Size (in.) Face Area (Sq. Ft.) / Centrifugal Blowers 15 x 12 Filters (8) 20 x 22 x 1 (Throwaway) 24.1 Operating Charge (Refrigerant.-22) Lbs.-Oz Weight (Lbs.) Shipping* 800 Operating 690 Accessory Operating Weights (Lbs.) * Less Motor and Drive. Motor & Drive 3 HP 90 5 HP 120 Supply Air Plenum 150 Base 120 Return Air Grille 15 Steam Coil 1-Row Deep 150 Hot Water Coil 150 FIG. 1 - SUGGESTED METHOD FOR CONNECTING SUPPLY AIR DUCTWORK Unitary Products Group 3

4 2. Include a vapor barrier around the outside to prevent the absorption of moisture. 3. Be no less than 2 inches thick with weather proof coating when applied to ducts exposed to outdoor conditions. SUPPLY AIR DUCTS See Figure 1 for suggested method of connecting supply air ductwork. Non--flammable material collars should be used to minimize the transmission of noise and/or vibration. RETURN AIR DUCT ANGLES Return air duct angles are shipped turned in. They are intended to be unscrewed and turned for connection of duckwork. Discard these angles when the return air grille accessory is used. The return air grille accessory attaches in the same manner as the panels. The supply air plenums and bases that are shown in Figure 4 are shipped knocked--down. Separate assembly instructions are packed with these accessories. Form N8.2U --Supply Air Plenum Form N8.1U --Base AIR DISCHARGE CONVERSION Units are shipped for upflow operation, but may be converted for any of the illustrated air discharge patterns shown in Figure 3. Convert a follows: 1. Remove the panels from the blower section. 2. Remove Phillips machine screws located inside casing corner angles which hold coil and blower sections together. FIG. 2 - MOUNTING HARDWARE NOTE: Before proceeding to Step 4, see the section on Blower Motor Mounting Locations and mount the blower motor in the desired position. 4. If accessory heating coils are used, mount heating coil between coil and blower sections. Screw fastening locations are the same for all sections and heating accessories. If heating coils are not used, refasten coil section to blower section with machine screws removed in Step Before replacing panels, see Duct Connections and Drain Connections. 6. Replace panels. 3. Rotate blower section for the air discharge pattern desired. 4 Unitary Products Group

5 VERTICAL ARRANGEMENT HORIZONTAL ARRANGEMENT FIG. 3 - VERTICAL AND HORIZONTAL ARRANGEMENT SUPPLY AIR PLENUM DECORATIVE BASE FIG. 4 - PLENUM AND BASE ACCESSORIES Unitary Products Group 5

6 NOTE: The following illustration shows how the channels should be secured to the unit using the hardware provided with the suspension accessory. 1] The same channels can be used in either position. When used to support a vertical unit, these channels should be cut to match the bottom dimension of the evaporator coil section. 2] The location of the supply air plenum. 3] The suspension channels have two sets of mounting holes to accommodate horizontal units with or without a heating coil. On a horizontal unit without a heating coil, the suspension channels will extend 3 inches beyond both ends of the unit. 4] The same channels can be used to support a horizontal, floor-mounted unit from below. 5] After these bottom channels are cut per Not 1, a new hole will have to be drilled at the cut end if the unit is to be mounted on isolators. FIG. 5 - UNIT MOUNTING TABLE 3 - OPERATING WEIGH DISTRIBUTION (Lbs.) Model Blower Motor Support Point Designation Horizontal Installation Vertical Installation W1 W2 W3* W4 W5 W6* W1 W2 W3* W4 W5 W6* 3 HP LEU240 5 HP * Blower Motor End Of Unit. TABLE 4 - ACCESSORY OPERATING WEIGHT DISTRIBUTION 1 (Lbs.) Accessory Model LEU240 Base 2 20 Supply Air Plenum 25 Return Air Grille 5 3 Hot Water Coil 25 Steam Coil 1 Row 25 1 These weights should be added to each point load (W1 thru W6) on the above table. 2 This accessory can only be applied on units installed in the vertical position. 3 This weight should only be added to point loads W1, W2 and W3. 6 Unitary Products Group

7 CAPACITY REDUCTION The evaporator coils for these blower units are intertwined and are equipped with one liquid line solenoid valve for capacity. As the external controller (thermostat) becomes satisfied, the control circuit of the condensing unit will unload its compressor and will de--energize (close) the solenoid valve for capacity reduction. DRAIN CONNECTIONS All drain lines MUST be trapped and located so they will not be exposed to freezing temperatures. The evaporator blower has 7/8 inch OD steel condensate stub at each end of a singe drain pan. Both ends are closed with plastic caps. A plastic ell with clamps is provided. Attach the ell to the desired end and run a full size 7/8 inch drain line to the nearest drain facility. Seal the cap at the unused end with suitable mastic. 2 ) # * ) 2 4 ) , 4 ) 1 2 ) FIG. 8 - TYPICAL MOTOR MOUNTING ASSEMBLY AND MOTOR more detailed view of the motor mounting assembly (the mounting plate and the channels) with a motor. MOTOR ARRANGEMENTS The recommended motor location for each blower arrangement is as follows. Refer to Figure 10. FOR LOCATION A Install the motor and drive package. The motor mounting assembly is already in the correct position ) 2 5 FOR LOCATION D 1.Move the motor mounting plate to the other end of the mounting channels. Do not rotate the mounting plate.. ) ; , FIG RECOMMENDED DRAIN PIPING The 3 inch dimension must equal or exceed the negative static pressure developed by the supply air blowers. If it does not, the condensate will not drain properly and may overflow the drain pan. The trap must be at least 2 inches deep to maintain a water seal under all operating conditions, especially when the blowers are starting up. BLOWER MOTOR MOUNTING LOCATIONS The blower units are always shipped from the factory less motor and drive. The motor mounting assembly, however, is always factory--installed as shown in Figure 8. Figure 9 shows a 2.Install the motor and drive package. FOR ALL OTHER LOCATIONS 1.Move the entire motor mounting assembly (both the mounting plate and the channels) so that the mounting plate will be in the correct location. NOTE: The blower section must be lifted off the evaporator section to gain access to the mounting channel fasteners. Since these sections have to be repositioned for arrangements 2,3,5,6,7,9,10 and 12 of Figure 3, the motor mounting assembly should be relocated before the two sections are rejoined. FIG 7. - SHIPPING LOCATION FOR MOTOR MOUNTING ASSEMBLY Unitary Products Group 7

8 ARRANGEMENT 1, 4, 8, OR 11 ARRANGEMENT 2, 6 OR 7 ARRANGEMENT 3, 5 OR 10 ARRANGEMENT 9 OR 12 NOTE: Since the motor mounting assembly cannot be secured to the panel with the blower openings, the motor cannot be installed in any of the normally recommended bottom positions. FIG MOTOR ARRANGEMENT LOCATIONS NOTE: Shipping location for the motor mounting plate on the mounting channels. 8 Unitary Products Group

9 2.Rotate the motor mounting plate 180 degrees on the mounting channels.(for locations C,F,H, and J only! Do not rotate the plate for location D,E,G, or I.) 3.Install the motor and drive package. REFRIGERANT MAINS A majority of service troubles are caused by lack of adequate precautions to provide an internally clean and dry system. It is extremely important that all field--supplied materials conform with established standards. Hard drawn copper tubing should be used where no appreciable amount of bending around pipes or other obstructions is necessary. Use long radius ells wherever possible. If soft copper is used, care should be taken to avoid sharp bends which may cause a restriction. Where refrigerant lines pass through a wall, pack fiber glass insulation and a sealing material such as permagum around the refrigerant lines to reduce vibration and to retain some flexibility in the lines. The refrigerant lines should be supported by suitable hangers, brackets or clamps. Braze all copper to copper joints with Silfos--5 or equivalent brazing material. Do not use soft solder. Never braze or solder the liquid and suction lines together. The complete suction line should be insulated with no less than 1/2 inch ARMAFLEX or equivalent. If it is desirable to tape or wire the liquid and suction lines together for support purposes, they must be completely insulated from each other. INSTALLING REFRIGERANT MAINS The units are shipped with a holding charge of Refrigerant--22. The connections are terminated with a copper disc brazed over the ends. Before starting installation of the mains, be sure the unit has not developed a leak in transit by connecting a pressure gauge to the service access port. If pressure still exits, the circuit may be considered leak free. If pressure does not exist, the unit must be evacuate along with the field installed refrigerant piping. NOTE: To minimize the possibility of system failure due to dirt and moisture, a filter--drier must be installed in each liquid line as close to the evaporator as possible. Filter--dryers are not supplied with the evaporator blowers. They are supplied with the matching condensing units. The temperature required to make or break a brazed joint is sufficiently high to cause oxidation of the copper unless an inert atmosphere is provided. CAUTION: Dry nitrogen should flow through the system at all times when heat is being applied and until the joint has cooled. The liquid, suction and drain connections inside the unit must be piped to the outside. Refer to Unit Dimensions or the locations and the dimensions of the access openings in the unit panel. Copper liquid and suction line elbows and plastic drain elbow with hose clamps are shipped with the unit for field installation. The refrigerant piping and the condensate drain can be connected from either end of unit. The evaporator coil section is shipped with the side panels suitable for right hand piping connections when viewed from the return air end of the section. If left hand piping connections are required, the large and the small panels on the right side of the coil section can be interchanged with the single panel on the left side. The small panel has the holes for the refrigerant lines and the condensate drain line, and it is interchangeable for left hand or right hand piping connections. When left hand piping connections are installed, the suction line must be insulated to prevent moisture from condensing on it and being carried into the blower section. Grommets are supplied by the factory for field mounting in the holes provided in the narrow panel. These grommets are packed in the same carton with the other piping connections, and the carton is shipped in the unit's evaporator coil section. Remove the evaporator holding charge and any caps or discs on the liquid and suction connections that will not permit a free flow of nitrogen. CAUTION: After recovering the R--22 holding charge, use a small drill bit to puncture sealing caps and discs before unbrazing to prevent the pressure in the line from blowing them off. EVAPORATOR SECTION PIPING Connect a supply of dry nitrogen through a reducing regulator to an access valve or charging tail. Choose a procedure that will allow nitrogen to flow continuously through the system and reach all joints to be brazed. Begin the refrigerant mains by installing the liquid line from the condensing unit liquid stop valve to the evaporator liquid connection, maintaining a flow of nitrogen during all brazing operations. The filter--drier and sight glass must be located in this line, close to the evaporator. Make the suction line connection at the evaporator and run the line to the condensing unit. After puncturing the sealing caps with a small drill bit, unbraze the condensing unit suction disc and connect the line. Maintain a flow of nitrogen from the liquid valve access connection through the liquid line to the evaporator, through the evaporator, back to the condensing unit and out the suction valve access connection. CAUTION: The liquid line solenoid valves are shipped in the manually open position. After brazing is completed, close the valves by turning the stem clockwise. NOTE: Size the suction line outside the evaporator casing per the line sizing information provided in condensing unit instruction Form N6Y. EXPANSION VALVE BULB The bulb for the first stage TX valve on each of these blower units is not factory--installed in its final location; it's only temporarily taped for shipment. It must be fastened in a four o'clock position to the common suction line out of the evaporator coil after piping connections are made. Use the bulb clamps from the bag tape to the suction connection inside the blower unit. AIR SYSTEM ADJUSTMENT Unitary Products Group 9

10 Refer to Table 7 and 8 to adjust air system. TWIN BELT DRIVE ADJUSTMENT Check to see if both belts drive at the same speed. Do this by making a mark across both belts. Turn the drive several revolutions by hand. If mark hasn't separated, the belts are traveling at the same speed. Twin groove blower motor pulleys should be installed with the shaft set screw (A) towards the motor. See Figure 11. If necessary to align pulleys, the housing of the twin groove motor pulley may extend 25% of its length beyond end of motor shaft. TABLE 6 - ELECTRICAL DATA-SUPPLY AIR MOTOR Nominal HP Rating 3 5 Power Supply Name -plate Amps Locked Rotor Amps Min. Wire Size 1, AWG Based on three 60 deg. C, insulated copper conductors in steel conduit. 2 Based on an 80% power factor and a 3% voltage drop. Max. Wire Lg. 2, Feet Max. Fuse Size, Amps Always align twin groove pulleys using the stationary web. The blower motor pulleys are adjustable by half turns. Select required RPM from Table 7 and adjust pulley. Check belt tension. Drive packages are supplied with Fiberglass belts which must be properly tensioned at installation because they do not stretch. The belt should deflect 3/16 inch per foot of belt span with a 2 or 3--pound force. Alignment of the resilient motor mount can be corrected by adjustment at the slots on the end opposite the pulleys. 0! + - # " - 7 &! 2 0 ) ) / ; / 4 7, 7 /. 4 / 4 7, ,! 6 * +, * " 4 : ; * ; " 8, ), / * ;. 1-,! 2 0 ) ) / ; - 8 ) 2 4 ) 6 4 * ) NOTE: There are two (2) flats on the pulley head at 180 degrees against which the set screws may be tightened " / ) 8 ) ) : 4 + ; ; / ) " % " 0! + - " " - 7 "! 2 0 ) ) / ;, ), / * ;. 1-,! 2 0 ) ) / ; / 4 7, 7 /. 4 / 4 7, , , , 8 ) 8-5! +, * 6 * " 4 : ; * ; " 8-8 ) 2 4 ) 6 4 * ) " / ) 8 ) ) : 4 + ; ; / , ) ; 6 * ) 14 0 ), FIG DOUBLE GROOVE PULLEY ELECTRICAL CONNECTIONS Refer to matching condensing section wiring diagrams. Install a power supply to meet the requirements listed in Table 5. Refer to Figure 12 for typical field wiring. Provide a disconnect switch and fusing as required. Install interconnecting control wiring between condensing section, evaporator blower and room thermostat ) " % " FIG FIELD WIRING ) + + 4, ) ) + ) ), ) 6 1 ) ) +, , / ) / - + ) / ) / - + ) / TABLE 5 - ACCESSORY STATIC RESISTANCE, IWG CFM Supply Air Plenum Return Air Grille Non- Freeze Steam Coil Hot Water Coil Unitary Products Group

11 TABLE 7 - BLOWER MOTOR AND VARIABLE V-BELT DRIVE DATA (Factory Supplied) Drive Motor Blower Pulley Motor Pulley Package Belt Model No. RPM Range HP Frame Speed Shaft Size Mfg.. No. Size Mfg.. No. Size 1LD /8 A55 AK x 1-3/16 1VM x 7/8 1LD /8 A51* 2AK94 9 x 1-3/16 2VP x 1-1/8 * Two matched belts. All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. ACCESSORIES Heating Coil - Add 6 inches to overall height when used. Supply Air Plenum - Add 24-5/8 inch to overall height when used. Base - Add 23-3/8" to overall height when used A B C D E F G 89-1/ /8 29-1/2 2-7/16 2-7/ /8 H J K L M N P 12-7/ / /4 1 1/5/8 FIG UNIT DIMENSIONS Filters must be cleaned or replaced as often as necessary to assure good air flow and filtering action. 1.To remove filters through the sides of the unit, remove either the solid side panel on the piping end, or the larger side panel on the end opposite the piping. 2.To remove filters from the front of the unit, loosen two screws and raise the top filter retainer. The upper filters can be lifted over the center filter lip. Three wing nuts are provided under the center filter retainer. Remove these and a part of the center filter support, giving access to the bottom filters. On sections using the Return Air Grille, first remove the grille and then follow procedure for removing filters from front of unit. Drain pan(s) should be inspected regularly to assure proper drainage. MAINTENANCE The evaporator blower bearings and blower motor bearings are permanently lubricated. Unitary Products Group 11

12 TABLE 8 - BLOWER PERFORMANCE-AVAILABLE EXTERNAL STATIC PRESSURE-IWG FOR ACCESSORIES AND DUCT SYSTEM STATIC RESISTANCE (Allowance made for wet coil and filters) CFM RPM ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW Unitary Products Group 5005 York Drive, Norman, Oklahoma Subject to change without notice. Printed in U.S.A Copyright by York International Corporation 2002 All Rights Reserved. Supersedes: Nothing Code: SBC N4C-0500

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION SPLIT-SYSTEM EVAPORATOR BLOWER ( COOLED) CONTENTS NOMENCLATURE... 3 GENERAL... 3 NOTES CAUTIONS AND WARININGS... 3 PARTS... 3 INSPECTION... 3 LIMITATIONS... 3 INSTALLATION... 3

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS 036-21096-001 (0101) SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The

More information

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS 550.23-TG5Y (893) CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L2EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility.

More information

MODELS K2EU060A, K4EU090A, & K3EU120A

MODELS K2EU060A, K4EU090A, & K3EU120A AIR COOLED SPLIT-SYSTEM AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: 550.23-N2Y (589) 550.23-N2Y (399) MODELS K2EU060A, K4EU090A, & K3EU120A 035-16672 GENERAL These completely assembled 5, 7-1/2

More information

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307 DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application

More information

INSTALLATION INSTRUCTION-50 Hz

INSTALLATION INSTRUCTION-50 Hz INSTALLATION INSTRUCTION-50 Hz GENERAL...3 NOTES, CAUTIONS AND WARNINGS...3 INSPECTION...3 NOMENCLATURE...4 MAINTENANCE...19 SPLIT-SYSTEM EVAPORATOR BLOWER MODELS: LA300 LB360 LB480 LB600 (50 Hz) SEE THE

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER MODEL: LA120 NOTES, CAUTIONS AND WARNINGS SAVE THIS MANUAL B-0203

INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER MODEL: LA120 NOTES, CAUTIONS AND WARNINGS SAVE THIS MANUAL B-0203 INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER CONTENTS NOMENCLATURE............................. 3 GENERAL.................................... 4 SAFETY CONSIDERATIONS.....................

More information

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES R-410A MODELS: 7.5-20 Ton, 60 Hertz NH-07 thru -20, 2-Pipe NJ-10 thru -20, 4-Pipe General.......................................... 2 Safety Considerations............................... 2 Reference......................................

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 canbepositionedinupto12differentpositionsandsuspended

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT: GENERAL SPECIFICATIONS OUTDOOR UNIT: TECHNICAL GUIDE COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM MODELS HB 180 & HB 240 MODELS LB 180 & LB 240 15 & 20 NOMINAL TONS 9.7 EER Two independent refrigerant

More information

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES R-410A MODELS: 7.5-20 Ton, 60 Hertz NH-07 thru -20, 2-Pipe NJ-10 thru -20, 4-Pipe General.......................................... 2 Safety Considerations............................... 2 Reference......................................

More information

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED (491) SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU, K3EU & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes

More information

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ) Technical Guide SUNLINE 2000 SPLIT-SYSTEM EVAPORATOR BLOWER K4EU180 15 NOMINAL TONS (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION MODULAR AIR HANDLER MODEL: N*AH CONTENTS GENERAL... 1 INSPECTION... 2 REFERENCE... 2 LIMITATIONS... 2 LOCATION... 2 BLOWER/COIL ASSEMBLY UPFLOW AND HORIZONTAL INSTALLATIONS...

More information

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC ISO 9001 Certified Quality Management System SAFETY................................................

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling

More information

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492) CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 550.13-N4 (778) 550.13-N4Y (492) MODELS H2CA480 & 600 035-09563 GENERAL CHAMPION units are designed for outdoor

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ) (994) SPLIT-SYSTEM EVAPORATOR BLOWER K5EU090 and K4EU120 50 Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX coil

More information

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ E3FB090/E1FB120/F3EH090 & 120 7-1/2 & 10 NOMINAL TONS (60 HZ) 7 & 9 NOMINAL TONS (50 HZ) (9.0-9.2 EER) 208/230/460 VOLT ONLY 208/230 VOLT ONLY DESCRIPTION YORK has

More information

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS Technical Guide SPLIT-SYSTEM EVAPORATOR BLOWERS 7-1/2 and 10 NOMINAL TONS LA090 & LA120 DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes

More information

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195) STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: 535.02-N2Y (795) 535.02-N2Y (1195) HEAT PUMP MODELS F1RP / F1FP018 thru 060 and COOLING MODELS F1RC / F1FC018 thru 036 035-13620

More information

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214 INSTALLATION MANUAL FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: MC FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: FC PARTIAL-CASED UPFLOW FOR COOLING/HEAT PUMP MODELS: PC ISO

More information

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons 560.20-TG1Y (388) EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons Each circuit includes a fully hermetic compressor with a crankcase

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE INSTALLATION INSTRUCTION CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS Supersedes: Nothing 550.38-N6Y (1095) MODELS H*DB076 035-13578 WARNINGS are given to alert the installer that severe personal injury,

More information

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: ORIFICE METERING DEVICE - G*FD024S14 - G*FD060S24 FACTORY INSTALLED TXV - G*FD024S14T - G*FD060S24T

More information

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: ORIFICE METERING DEVICE - G*FD024S14 - G*FD060S24 FACTORY INSTALLED TXV - G*FD024S14T - G*FD060S24T

More information

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION INSTALLATION INSTRUCTION CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS Supersedes: 550.44-N1Y (1194) 550.44-N1Y (495) MODELS H*DE018 THRU H*DE060 035-11029 WARNINGS are given to alert the installer

More information

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: 515.41-N1Y (497) 515.41-N1Y (998) MODELS E2FB090 & E1FB120 035-15410 EFB090 SHOWN 208/230/460 VOLT ONLY 208/230 VOLT ONLY GENERAL

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION SINGLE PIECE AIR HANDLERS Supersedes: 535.02-N2V (598) 535.02-N2V (199) HEAT PUMP MODELS F+RP / F+FP018 thru 060 and COOLING MODELS F+RC / F+FC024 thru 036 035-14363 GENERAL This

More information

40 RM/RMS Packaged Air-Handling Units

40 RM/RMS Packaged Air-Handling Units ConcepcionCarrier Air conditioning Company Philippines 40 RM/RMS 008034 Packaged AirHandling Units INSTALLATION MANUAL, STARTUP & SERVICE INSTRUCTIONS Contents Page Page Safety Considerations 1 40RM Physical

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804 INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON CONTENTS GENERAL................................. 3 REFERENCE............................... 3 INSPECTION...............................

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT TECHNICAL GUIDE SPLIT-SYSTEM HEAT PUMPS EA090/FA090 DESCRIPTION YORK has combined the latest concepts in modern technology with time-proven quality standards to design a split-system heat pump to meet

More information

MODELS E1FB180 & E1FB240

MODELS E1FB180 & E1FB240 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: 035-16192-000 (0601) 035-16192-001-A-1001 MODELS E1FB180 & E1FB240 GENERAL The outdoor units are completely piped and wired at

More information

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY INSTALLATION MANUAL FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: MC FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: FC PARTIAL-CASED UPFLOW FOR COOLING/HEAT PUMP MODELS: PC ISO

More information

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: Nothing 515.41-N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) 035-09648 EFB090 SHOWN GENERAL Renewal Parts: 208/230/460 VOLT ONLY

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

INSTALLATION MANUAL - 50 Hz

INSTALLATION MANUAL - 50 Hz INSTALLATION MANUAL - 50 Hz SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

VariCool VAV Engineering Guide

VariCool VAV Engineering Guide Engineering Guide Effective September 2017 Water-Cooled and Chilled Water, Variable Air Volume Contents Product Features... 3 UNIT FEATURES... 3 Product Features... 4 Marvel Plus Microprocessor Control

More information

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS SUNLINE 2000ô MODELS: H5CE090, H3CE120 & H1CE150 7-1/2, 10, & 12-1/2 NOMINAL TONS 9.0-9.5 EER DESCRIPTION These Sunline 2000ô units are completely

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE SUBMITTAL DATA SHEET SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE JOB NAME: LOCATION: PURCHASER: ORDER NO: ENGINEER: SUBMITTED TO: FOR: REF:

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS INSTALLATION MANUAL TABLE OF CONTENTS GENERAL.................................... 3 REFERENCE................................. 3 INSPECTION.................................. 4 OPERATION.................................

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER ASPEN MANUFACTURING 373 ATASCOCITA RD. HUMBLE, TX 77396 TEL (281) 441-6500 FAX (281) 441-6510 > INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT: "The

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION SINGLE PIECE AIR HANDLERS Supersedes: 535.02-N2V (600) 535.02-N2U (900) HEAT PUMP MODELS F2RP / F2FP018 thru 060 and COOLING MODELS F2RC / F2FC024 thru 036 035-14520-000 Rev. B

More information

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION INDEX Introduction....................................... 3 Checking Product Received.......................... 3 Standard Unit Features.............................. 3 Unit Dimensions...................................

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT MASSAGE TO INSTALLER: "The United States Environmental Protection Agency ("EPA") has issued various regulations regarding the

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS STELLAR AIR CONDITIONING UNIT SPLIT-SYSTEM COOLING CONTENTS GENERAL..................................... 2 NOMENCLATURE........................... 2 SAFETY...................................

More information

Installation Instructions

Installation Instructions CNPHP Cased N s Horizontal Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS RHGM COMMERCIAL AIR HANDLERS NOMINAL 7.5 AND 10 TON AIR CONDITIONING FEATURING EARTH-FRIENDLY R-410A REFRIGERANT e arth fr rie endl y r e f r i g e r a n t! Recognize this symbol

More information

MODELS W1LC220, 260 AND 320 STYLE B

MODELS W1LC220, 260 AND 320 STYLE B LIQUID CHILLER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 570.05-NY (494) 570.05-N3Y (495) MODELS WLC0, 60 AND 30 STYLE B 035-3053 Only -5 and -46 voltage codes GENERAL YORK s WLC Packaged Air-Cooled

More information

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH AVS-ACL-IM (08/15) Copyright 2015 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4

More information

Installation Instructions

Installation Instructions CNPHP Cased N Coils Horizontal Heating --- Cooling NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

VertiCool Aurora Engineering Guide

VertiCool Aurora Engineering Guide Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8

More information

Installation Instructions

Installation Instructions Split System Indoor Coils Installation Instructions! CAUTION: Read the Installation Instructions supplied with furnace/air handler and observe all safety requirements outlined in instructions and/or furnace/air

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF INSTALLATION MANUAL FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: CF FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CM ISO 9001 Certified Quality Management System GENERAL..............................................

More information

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA 18- AH39D1-4 Cased Aluminum "Convertible" Coils 2/4TXCA018BC3HCA 2/4TXCA024BC3HCA 2/4TXCB025BC3HCA 2/4TXCB031BC3HCA 4TXCB032BC3HCA 2/4TXCB036BC3HCA ALL phases of this installation must comply with NATIONAL,

More information

Installation Instructions

Installation Instructions Installation Instructions Fan Coil Units FG3A NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Improper

More information

High Profile Evaporator

High Profile Evaporator PRODUCT DATA & INSTALLATION Bulletin K30-KHPA-PDI-5 Part # 1081585 PRODUCT SUPPORT web: k-rp.com/khp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: High Profile Evaporator High & Medium Temperature

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions Installation, Start-Up and Service Instructions - Q- S- Packaged Air-Handling Units 50/60 Hz CONTENTS Page SAFETY CONSIDERATIONS...1 PRE-INSTALLATION...1,2 Moving and Storage...2 Rigging...2 INSTALLATION...

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES ISO 9001 Certified Quality Management System GENERAL.............................................. 1 SAFETY................................................

More information

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X Installation Truck Refrigeration & Commissioning Manual: INSTALLATION AND COMMISSIONING MANUAL for Neos 100S Integra 20X, 30S, 35X, 40X, 50X Direct Drive Refrigeration Units 2017 Carrier Corporation Printed

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATION AND OPERATING INSTRUCTIONS HIGH-EFFICIENCY CONDENSING UNITS RAWD- 6 1 2 & 7 1 2 TON RAWE - 6 1 2 & 7 1 2 TON! RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!! WARNING

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS HOT WATER AND STEAM COIL ACCESSORIES MODELS 1HW0410, 0411, 0412 and 1NF0456, 0457, 0458 For 7.5 Thru Ton Generation 2 Split System Indoor Units 643960-UAI-A-0910

More information

INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES GENERAL.............................................. 1 SAFETY................................................ 1 UNIT INSTALLATION.....................................

More information

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

Cased Aluminum Convertible Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC** 18- AH44D1-4 Cased Aluminum "Convertible" Coils 4TXCB003CC3HC 4TXCB004CC3HC 4TXCC005CC3HC 4TXCC006CC3HC 4TXCC007CC3HC 4TXCC008CC3HC 4TXCD009CC3HC 4TXCD010CC3HC May be "A" or "B" ALL phases of this installation

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Litho U.S.A. 2012 WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by

More information

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72 ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY, 16, 26, 36 & 72 FOR SPLIT-SYSTEM AIR CONDITIONERS 5, 7-1/2, & 15 TONS SPLIT-SYSTEM HEAT PUMPS 7-1/2 & TONS GENERAL This instruction covers the

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,1,_2008 Lennox Industries Inc, Dallas, Texas, USA INSTALLATION INSTRUCTIONS CR33 Series Coils EVAPORATOR COILS _ Technical 505,056M LL.L[ Publications 04108 Litho U.S.A. Supersedes 05/05 CR33 Series Coils...

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Series Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life,

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 25,240* Design CFM: 800 Seasonal

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION CONTENTS GENERAL............................................ 2 NOMENCLATURE..................................... 2 PRODUCT CATEGORY.................................. 2 PRODUCT

More information