Elitec. DTG 1300 Eco.NOx/V. English 23/06/05. Gas-fired boilers. Technical instructions

Size: px
Start display at page:

Download "Elitec. DTG 1300 Eco.NOx/V. English 23/06/05. Gas-fired boilers. Technical instructions"

Transcription

1 Elitec DTG 1300 Eco.NOx/V Gas-fired boilers English 23/06/05 Technical instructions

2 Contents Compliance Introduction Important recommendations Regulations Symbols used Description Introduction Composition of the range Certifications Main parts Technical characteristics Main dimensions Package list Installation Implementation Levelling Control panel assembly Connecting the furnace Hydraulic connections Connecting the gas channel Connecting to a chimneye Electrical connections Adapting to another gas Attaching the label Changing the burner injectors Changing the ignition burner injector Setting the injector pressure Pressure settings and calibrated injector markings Commissionning Refilling the installation Final checks before commissioning Commissionning Furnace operation equipped with safety box 577 DBC Checks and adjustments after commissioning Maintenance Cleaning main burner and ignition burner Cleaning heater body Maintenance Incidents and solutions Spare parts Warranty DTG 1300 Eco.NOx/V 23/06/ B

3 Declaration of compliance Declaration of compliance A.R. 8/1/ BE Manufacturer DE DIETRICH THERMIQUE S.A.S. 57 rue de la gare F MERTZWILLER Issued by See end of notice We hereby certify that the range of equipment specified below is in accordance with the format stated in the EC declaration of comformity, that it is manufactured and distributed in accordance with the regulations and requirements in European Directives and with the regulations and requirements defined in the Royal Decree dated 8th January 2004.: Product type Formats 18, 24, 30 kw Floor-standing gas boiler DTG 1300 Eco.NOx/V Standard applied - Royal Decree dated 8th January /396/EEC Gas Appliance Directive Reference Standard : EN 297 ; EN /23/EEC Low Voltage Directive Reference Standard : EN /336/EEC Electromagnetic Compatibility Directive Reference Standard : EN ; EN /42/EEC Efficiency Directive * * Low temperature gas boiler Inspecting organisation Gas Wärme Institut / DVGW PV N (06/01/2004) Measured values NOx: < 70 mg / kwh CO: < 10 mg / kwh Date: 22 juin 2004 Signature Technical Director Mr. Bertrand Schaff 23/06/ B DTG 1300 Eco.NOx/V 3

4 Introduction 1 Important recommendations For a proper operating of the boiler, follow carefully the instructions. Any intervention on the appliance and heating equipment must be carried out by a qualified technician. The manufacturer is not liable for any improper use of the appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified fitter). Check that the equipment is properly set for the type of gas used. Keep to the polarity shown on the terminals : phase (L), neutral (N) and earth. Check the seal on the gas and water pipe connections. 2 Regulations Certificate of compliance For the application of article 25 of the modified decree dated 02/08/ 1977 and of article 1 of the modifed decree dated 05/02/1999, the installation engineer must be in possession of the certificates of compliance approved by the Ministries in charge of construction and gas safety: - Different forms (forms 1, 2 or 3) for a new gas installation - "Model 4" in particular after replacing a furnace with a new one Residential buildings Statutory terms and conditions of installation and maintenance: The installation and maintenance of the appliance must be carried out by a qualified professional in compliance with the statutory texts of the codes of conduct in force, particularly: - Order of 2 August 1977 Technical and safety rules applicable to combustible gas and liquefied hydrocarbon installations situated inside residential buildings and their annexes. - NF P standards Gas installation, (formerly DTU 61-1, gas installations: April 1982, addendum no 1: July 1984). - Local Sanitary Regulations For appliances connected to the electricity network: - NF C standards Low voltage electrical installation - Rules.. Establishments open to the public Statutory terms and conditions of installation: The installation and maintenance of the appliance must be carried out in compliance with the statutory texts and rules of the codes of conduct in force, particularly: - Safety regulations against fire and panic in establishments open to the public: a. General regulations For all appliances: - Articles GZ - Installations operating on combustible gases and liquefied hydrocarbons. Then, depending on use: - Articles CH-Heating, ventilation, refrigeration, air conditioning and production of steam and domestic hot water. b. Instructions specific to each type of establishment open to the public (hospitals, stores, etc.) 4 DTG 1300 Eco.NOx/V 23/06/ B

5 3 Symbols used Symbols used Caution danger Risk of injury and damage to equipment. Attention must be paid to the warnings on safety of persons and equipment. Specific information Reference Information must be kept in mind to maintain comfort. Refer to another manual or other pages in this instruction manual. 23/06/ B DTG 1300 Eco.NOx/V 5

6 Description 1 Introduction The ELITEC DTG 1300 Eco.NOx/V boiler is a floor-standing cast iron gas-fired boiler with an atmospheric burner with very low pollutant emission with integrated domestic hot water production. The boiler must only be connected to a chimney. The design of the cast iron heater body with interleaved spurs gives very high performance. Also, the baffling in the smoke circuits limits the natural chimney effect and gives high performance yields. The boilers are equipped with an anti smoke release safety device ; they may therefore be installed in inhabited areas. It consists of a thermostat located in the anti-blowback which causes the burner to stop for 15 minutes. This is indicated by an alarm light flashing on the control panel. The boiler automatically restarts after 15 minutes if the cause of the cut off has been removed. The tightly packed insulation of the boiler equipment reduces losses into the atmosphere to very low levels. 2 Composition of the range Heating and domestic hot water - DTG 1300 Eco.NOx/V or H Panel B: Boiler with (110 ou 130 l) domestic hot water tank and electronic command panel - DTG 1300 Eco.NOx/V or H Panel E: Boiler with (110 ou 130 l) domestic hot water tank and electronic command panel with extractable or built-in Easymatic regulator - DTG 1300 Eco.NOx/V or H Panel D: Heater with (110 ou 130 l) domestic hot water tank and DIEMATIC 3 electronic command panel The command panel gives priority to producing domestic hot water. 3 Certifications 3.1 Introduction 97/23/CE Directive Gas and oil boilers with a maximum operating temperature of 110 C and hot water tanks with a maximum operating pressure of 10 bar pertain to article 3.3 of the directive, and therefore, cannot be CEmarked to certify compliance with the directive 97/23 EC. De Dietrich boilers and DHW tanks conform to the regulations in article 3.3 of the 97/23/CEE Directive and is backed by the CE mark for the 90/396/CEE, 92/42/CEE, 72/73 CEE and 89/336/CEE directives. CE identification no: CE-0085BP0002 Type B11 BS boiler The boilers leave the factory operating with H natural gas. To operate with L Natural gas or with propane: see chapter "Adapting to another gas" France: Thermal performance level (according to NFD ): B300 Performance class III boiler according to ATG B 84 recommendations. Switzerland: Boilers are tested under the LRV-92 standard. 6 DTG 1300 Eco.NOx/V 23/06/ B

7 3.2 User country 4 Main parts User country Gas category Gas type Connection pressure (mbar) FR II 2ESi3P G25 25 G20 20 G31 37 ES, PT, IE, CH, GB, DK, CZ, GR II 2H3P G20 20 G31 30/37 IT, SE, NO, FI, IS I 2H G20 20 AT II 2H3P G20 20 G31 50 DE II 2ELL3P G25 20 G20 20 G31 50 NL II 2L3P G25 25 G31 50 LU II 2E3P G25 20 G20 20 G31 50 HU II 2ES3P G G20 25 G31 30/ N070 Gas regulation block: It has a progressive opening, 2 regulation valve and safety valve in series which is controlled by the boiler adjustment dial. 3 Gas inlet 4 Burner 5 Flame inspection window Ignition electrode: This ensures ignition burner ignition using 6 a high voltage spark. Ionisation probe: This detects the presence of a burner 7 ignition flame through ionisation. 8 Ignition burner 9 Ignition burner gas supply pipe Anti-smoke release thermostat (located on the rear wall of the anti-blowback device): In the event of smoke release, the burner is cut and the boiler goes into standby for 15 minutes. It 10 must not be switched off or moved at any time.the boiler restarts normally after this thermostat has cooled and the 15 minutes has finished (indicated by an alarm indicator flashing on the command panel). 11 Sensor tube 18 Domestic hot water tank 19 Flange for the domestic hot water tank 1 Safety box: Mounted on the gas block to ensure and check ignition sequences, plus burner operation and extinguishing sequences. 23/06/ B DTG 1300 Eco.NOx/V 7

8 5 Technical characteristics DTG... Eco.NOx Nominal power Pn kw Power input kw 13,4 20,1 26,7 Gas flow rate - Natural gas H (G20) (1) m 3 /h 1,42 2,13 2,83 - Natural gas L (G25) (1) m 3 /h 1,65 2,47 3,29 - Propane (G31) kg/h 1,04 1,56 2,07 Number of cast iron parts Number of nozzles Mass flue gas flow rate (G20) kg/h Smoke temperature C Minimal ionisation current (2) µa 0,3 0,3 0,3 Required depressurisation at the nozzle mbar 0,05 0,05 0,05 Min water temperature C Max water temperature C Maximum admissible operating pressure bar Electrical connection V-HZ Absorbed electrical power (Heating mode) W Gas connection inch R 1/2 R 1/2 R 1/2 Water connection inch R 1 R 1 R 1 Smoke connection (internal diameter) mm 110 / 111 (3) 110 / 111 (3) 125 / 130 (3) Water capacity l 7,1 8,8 10,5 Loss of hydraulic circuit load at T = 15 K mbar Net weight kg Shipping weight kg Tank storage capacity l Hourly flow at T = 35 K l/h Specific flow à T = 30 K selon EN 625 (4) (6) l/min 19,0 19,0 22,0 Flow in 10 minutes à T = 30 K (4) (6) l/min (1) 15 C / 1013 mbar (2 ) In order to measure the ionisation current, take out the ionisation cable connector and insert a micro-ammeter. (3) According to the national standard (possible adaptation of the two diameters). (4) Domestic cold water à 10 C (5) Domestic hot water at 45 C Primary input temperature at 80 C (6) Set DHW temperature chaudière à 80 C Domestic hot water à 40 C Tank load temperature at 60 C 1 mbar = 10 mmce = 10 dapa = 100 Pa 8 DTG 1300 Eco.NOx/V 23/06/ B

9 6 Main dimensions (1) Adjustable feet : basic sizes : 40 mm. Can be adjusted from 40 mm to 55 mm. All height dimensions are given with a feet setting of 40 mm (see chapter Levelling). (2) According to the national standard (possible adaptation of the two diameters) R = Thread G = Exterior cylinder thread, sealed by flat joint Heating outlet 1 R 1 (1") for one single boiler G1 (1") for boiler with DHW tank Heating return 2 R 1 (1") for one single boiler G1 (1") for boiler with DHW tank Filling and emptying tap (connection for 14 mm interior diameter 3 pipe) 4 Gas inlet ø K 5 Smoke nozzle ø B 6 Hot water outlet R 3/4 (3/4") 7 Circulation R 3/4 (3/4") 8 Cold water inlet R 3/4 (3/4") IN ORDER TO FACILITATE BLEEDING, the installation must be filled via the drainage/filling valve. Formats DTG...Eco.NOx/V øb 110 / 111 (2) 125 / 130 (2) 150 / 153 (2) C D E H øk (inch) R 1/2 R 1/2 R 1/2 M P Package list Description Reference Pack no. Refer to the applicable price list for any optional features used. Boiler assembly Control panel DTG 1304 Eco.NOx/V DTG 1305 Eco.NOx/V DTG 1306 Eco.NOx/V B (Base) E (Easymatic) ER (Easyradio) D (Diematic 3) GL 30 GL 11 GL 12 GL 25 GL 26 GL 35 GL 27 23/06/ B DTG 1300 Eco.NOx/V 9

10 Installation 1 Implementation The boiler can be installed : - in the kitchen, - in the cellar, - in the boiler house. It is necessary to have in every case : - 5 cm on one of the boiler sides, - 70 cm minimum in front, - and 5 at the rear. Also have the required space for installing the expansion reservoir and the heating circulator. 5 cm from the w 5 cm to the left or right Furniture 1.1 Ventilation The ventilation section, obligatory in the location where the heater is installed where there is a direct air inlet must conform with the DTU 61.1 (P45-204) standard and in particular with the instruction on general management (Book 1764, April 1982). In order to avoid damage to the boilers, it is necessary to prevent the contamination of combustion air by chlorine and/or fluoride compounds, which are particularly corrosive. These compounds are present, for example, in aerosol sprays, paints, solvents, cleaning products, washing products, detergents, glues, snow clearing salts, etc. Therefore : - Do not suck in air evacuated from premises using such products: hairdressing salons, dry cleaners, industrial premises (solvents), premises containing refrigeration systems (risk of refrigerant leakage), etc. - Do not stock such products close to the boilers. If the boiler and/or peripheral equipment are corroded by such chloride or fluoride compounds, the contractual guarantee cannot be applied. 10 DTG 1300 Eco.NOx/V 23/06/ B

11 2 Levelling Levelling is done using the 4 feet located on the heater socket and using a flat screwdriver. Lift the tank slightly with a lever to adjust the feet. (1) Adjustable feet : Basic dimension 40 mm. Can be adjusted from 40 mm to 55 mm. 23/06/ B DTG 1300 Eco.NOx/V 11

12 Control panel assembly The command panel is attached as follows : 1. Unscrew the 2 mounting screws at the back of the column head. 2. Remove the upper casing of the boiler. 3. Unscrew the 2 mounting screws from the screen. 4. Take out the shutter + screen assembly. 5. Take the command panel out of its packaging. 6. Slide the panel along the front plate. Push the 1 tubes through the lower opening on the panel case. 12 DTG 1300 Eco.NOx/V 23/06/ B

13 7. Take out the heater door. 8. Place the bulbs in the sensor tube in front of the boiler. Push them into the funnel until it butts against it. 9. Use the contact spring 5 for the sensor tube if bulbs 6 are on number 2. Keep the position of the contact spring with relation to the bulbs. Tighten the assembly before engaging the glove finger. If there are 4 bulbs, the sensor tube contact spring is useless. 10. Then carefully fold the tubes and replace the traction stop tongue in the funnel. 11. Push the screen support against the front plate. 12. Tighten the 2 pre-assembled plate screws after having pushed the support fixing wings against the screws. 23/06/ B DTG 1300 Eco.NOx/V 13

14 13. Attach the burner cable to the 12 connector studs located on the inner face of the command panel. 14. Connect the earth cable to the clip located on the front plate. 15. Open the side of the panel. 16. Attach the anti-release safety device onto the 3 connector studs on the command panel. Connect the panel's electrical connections according to the panel's instructions 17. Close the panel front. 18. Re-assemble the shutter * screen assembly. 19. Thread the connection label into the screen slots. Correctly place the label using the truncated corner DTG 1300 Eco.NOx/V 23/06/ B

15 20. Screw the panel front onto the screen using a mounting screw. Re-assemble the door and the column head. 23/06/ B DTG 1300 Eco.NOx/V 15

16 Connecting the furnace 1 Hydraulic connections Installation must be carried out in accordance with the prevailing regulations, the codes of practice and the recommendations in these instructions. 1.1 Important recommendations for connecting the boiler to the heating circuit There must be no total or partial closing mechanism between the boiler and the safety valves (France: DTU , NF P ). Heating installations must be designed and implemented to prevent heating circuit water and products contained in it returning to the drinking water system (article 16-7 Departmental Health Regulations). A CB disconnector (area disconnector for different uncontrollable pressures)must be installed for filling the heating circuit according to the NF P standard. Prior connecting the heating circuit hydraulic connections, it is vital that the heating circuits are rinsed to prevent articles that may damage certain parts from being introduced (safety valves, pumps, non return valve...). 1.2 Hydraulic connection of the water circuit for domestic use Please see the document delivered with the domestic hot water preparer. 2 Connecting the gas channel Each time, a blocking tap will be located as near as possible to the heater. Pipe diameters must be defined in accordance with ATG's (Association Technique de Gaz) B171 specifications. The load loss between the meter and heater must be lower than 1 mbar (heater operating). Equipment pressure supply values : - Natural gas H/E (G20) : 20 mbar - Natural gas L/LL (G25) : 25 mbar - Propane (G31) : 37 mbar The boilers leave the factory operating with H/E natural gas. For operating with natural gas L or propane, carry out the actions described in the chapter "Adapting to another gas". In the event where the burner is located at the highest point in the installation, a dry running or water pressure control device my be fitted. Take care to ensure the hydraulic isolation of the primary and secondary circuits using stop valves in order to facilitate maintenance operations on the calorifier. These are used to carry out maintenance on the tank and its systems without draining the entire installation. These valves are also used to isolate the calorifier when conducting a pressurised check on the leak tightness of the installation if the test pressure for the calorifier is greater than the admissible operating pressure. IN ORDER TO FACILITATE BLEEDING, the installation must be filled via the drainage/filling valve 16 DTG 1300 Eco.NOx/V 23/06/ B

17 3 Connecting to a chimneye The equipment must be installed following the codes of practice using sealed stainless steel, aluminium or internally meshed tubing capable of withstanding hot combustion gases and any likely acid condensation. The pipe must be laid out to allow any likely condensation to drain. It must be in accordance with existing regulations for pipes used for this purpose. Standard meshed connection pipes are to be avoided. The pipe connecting the outlet conduit must also be as short as possible and without a reduced diameter. The vertical section of the draught diverter outlet must be a minimum length 3x the diameter of the nozzle before an elbow joint is fitted. The pipe must have a diameter not less than the heater's nozzle diameter along its whole length. This pipe must be able to be easily disassembled and must not have a sudden change in diameter. The outlet conduit must be maintained in a good condition, checked and cleaned at least once a year. Boiler Good Boiler Poor 4 Electrical connections Connections must be made by a qualified technician. Connections inside the command panel must not be modifed in any way. Keep to the polarity shown on the terminals : phase (L), neutral (N) and earth. 23/06/ B DTG 1300 Eco.NOx/V 17

18 . Adapting to another gas Operations to be carried out to allow the change from H/E natural gas to L/LL natural gas or to propane and vice versa. The actions described below must be carried out by a qualified technician. Check the seals for the gas. Natural gas H/E Natural gas L/LL Propane Conversion kits Package GL Package GL Package GL Attaching the label This indicates the type of gas for which the burner is set. 2 Changing the burner injectors Lift out the injector with a number 12 spanner assemble the new injectors with their new joint. Nozzle marking Nozzle diameter (mm) Natural gas H/E 210B 2,10 Natural gas L/LL 245B 2,45 Propane 140A 1,40 Prior to re-assembling the injector for each burner also replace the aluminium joint. First tighten the injectors by hand and carefully lock them using a spanner. 3 Changing the ignition burner injector Unscrew the connecting nut (14 spanner), Pull the gas supply pipe towards yourself. Take out the ignition burner nozzle. Fit the new nozzle. Re-attach the supply tube (14 spanner) Nozzle marking Nozzle diameter (mm) Natural gas H/E 4 0,40 Natural gas L/LL (France) 4 0,40 Natural gas L ( France) 5 0,50 Propane 3 0,30 France:The 40 mm ignition burner injection fitted in the factory is suitable for operation on natural gas H/E and L/LL (no conversion necessary for switching from H/E to L/LL and vice versa). 18 DTG 1300 Eco.NOx/V 23/06/ B

19 4 Setting the injector pressure Connect a manometer to the pressure socket located on the manifold. Remove the protective cover C on the regulator by unscrewing it using a screwdriver. Set the pressure on the injectors by moving the gas regulator on the valve. Manifold pressure (mbar) Natural gas H 15 Natural gas L 12,1 Propane 29 5 Pressure settings and calibrated injector markings Number of parts in the heater Nozzle H/E 210B 210B 210B Nozzle L/LL 245B 245B 245B Nozzle Propane 140A 140A 140A Manifold pressure H/E mbar Manifold pressure L/LL mbar 12,1 12,1 12,1 Manifold pressure Propane mbar Gas flow rate H/E m 3 /h 2,13 2,83 3,52 Gas flow rate L/LL m 3 /h 2,47 3,29 4,10 Flow rate Propane Kg/h 1,56 2,07 2,59 E Protective hood F Ionisation probe connection G Ignition electrode connection Start up pressure may be set if necessary using a flat screwdriver, after the protection has been removed E. Start up pressure is set in the factory on minimum. If it is necessary to optimise heater start up, it may be set on another value between 0º and 270º. Downstream pressure Gas valve opening diagram Flows are stated at 15 C mbar. Setting the start up pressure Time (seconds) 23/06/ B DTG 1300 Eco.NOx/V 19

20 Commissionning 1 Refilling the installation Firstly, fill the tank with domestic hot water. Domestic hot water circuit - Fill the calorifier via the cold water input pipe. If necessary, rinse the domestic circuit (particularly when commissioning), allowing the water to flow for a certain amount of time. - Bleed the domestic circuit (tank and distribution network); to do this: - Completely fill the calorifier with water, leaving the hot water valve open; close this valve only when the flow is regular and there is no noise in the pipes. - Then successively degas all the hot water pipes by opening the corresponding valves in order to prevent the noise caused by air movement when drawing off water. - Check the safety devices (particularly the valve or safety unit), referring to the instructions provided with these components. When reheating domestic hot water, a certain amount of water may escape via the valve or the safety unit because of the expansion of the water in the calorifier. There is no cause for concern at this absolutely normal phenomenon, which must in no event be hindered. Heating circuit Unstick the load pump in necessary: to do this, unscrew the protection cap in front of the pump and insert a screwdriver into the slit (V) on the pump center line. Turn several times to the right and left. - Cold run the pump for a few minutes to enable priming. - The heating circuit must be bled from the highest point of the installation using a suitable bleeding device (not provided). Automatic bleed valve The heating circuit (boiler and tank exchanger) must be filled using the drainage tap to the rear of the tank. When filling the heating circuit, correctly bleed the exchanger on the domestic water calorifier as follows:: Dhw pump V Unscrew the cap on the automatic bleed valve by a few turns Ensure that the non-return angle valve is in the automatic position Ensure that the drainage tap is in the open position Fill the low flow heating circuit using the drainage tap in order to favor the bleed After filling the installation, close the drainage tap Automatic position 2 Final checks before commissioning Check the following points before starting the heater : - Check that the equipment is properly set for the type of gas used. The boilers leave the factory operating with H/E natural gas. - Check the gas pressure upstream from the boiler. - Check the seals on the gas and water connections. 20 DTG 1300 Eco.NOx/V 23/06/ B

21 3 Commissionning The first start-up is to be performed by your installation engineer. - Open the gas blocking tap. - Check that the safety thermostat has not triggered. Remove the safety thermostat hood and press the reset button with a screwdriver. - Place the stop/start switch on On. - Create a requirement for heat. Please consult the document delivered with the command panel before carrying out any action with it. - The safety box carries out its ignition cycle. Switching off : Place the start/stop switch on Off. 4 Furnace operation equipped with safety box 577 DBC Operating principle Operating cycle on safety (start up without flame signal) The ignition and burner surveillance sequences are ensured by the safety box. Normal operating cycle Required input signals Box output signals Contact closed The box closes the TCH contact when there is a requirement for heat. The ignition transformer TA integrated into the safety control box and the ignition burner valve VBA (supply to the ignition burner) are switched on. Gas from the ignition burner is ignited by the ignition electrode and within the time interval ts; a minimum current of 0.3 µa appears on the ionisation sensor SF and the gas valve regulation flap (supplying the principal burner) opens. - If a flame is not detected before the safety time ts, the box makes 2 more ignition attempts. If, at the end of the last attempt, there is still no flame signal, the box goes into safety and the safety indicator comes on. To restart the heater, press the reset button on the safety box. - If there is a loss of flame in normal operation, the box automatically repeats the start up sequence. Resetting : The box is reset after going into safety by pressing the reset button. If the reset button does not work, wait at least 15 seconds before trying a second time. Required input signals Box output signals Contact closed The box may be on safety on its first start up : press the reset button to release it. If the reset button is pressed in normal operation, the gas valves close and the box starts a new ignition sequence. 23/06/ B DTG 1300 Eco.NOx/V 21

22 Operating cycle with the anti-smoke release thermostat cut off Required input signals Box output signals Contact closed In the event of smoke release, the burner is cut and the boiler goes into standby for 15 minutes. This timed phase is indicated by an alarm indicator flashing. The 15 minute timed period can only be interrupted by a sector cut. 5 Checks and adjustments after commissioning Key : A A 1 A 2 B C C 1 C 2 D E F SF VA TA TAF TCH VBA VBP ts tn vary) t TAF Start of operation Second ignition attempt Third ignition attempt Formation of flame in ignition burner End of first ignition attempt End of second ignition attempt On safety through absence of flame signal Smoke anti-release thermostat cut Resetting Restart of heater Burner flame signal Alarm indicator Ignition transformer Anti-backflow thermostat Heat requirement Ignition burner valve Main burner valve Safety time : about 55 seconds Anti-smoke release thermostat cooling time (times Box standby time : 15 minutes 5.1 Checking pressure to the nozzle Check the seal again Checking burner safety Manifold pressure (mbar) Natural gas H/E 15 Natural gas L/LL 12,1 Propane 29 Cut the gas by closing the stop tap. Check the reaction of the safety system. (Safety box on safety because of ionisation fault). Checking the safety thermostat Unscrew the screw inside the nozzle pressure socket a few turns. Connect a manometer to the pressure socket and check that the pressure to the socket corresponds to the pressure stated below. Adjust the pressure to the injectors if necessary. Tighten the pressure socket screw. Place the Summer/Winter switch on to cut the heating accelerator to prevent the temperature rising in the installation. Place the 3 position switch " - AUTO - TEST STB" on the TEST STB position. The burner starts regardless of the setting. Keep the switch in this position until the safety thermostat cuts (110ºC). To restart the heater, press the safety thermostat reset button and repeat the starting operations. 22 DTG 1300 Eco.NOx/V 23/06/ B

23 Checking the anti-smoke release thermostat In the event of smoke release by the anti-blowback device, the antirelease safety device switches off the burner with the safety box on standby for 15 minutes (this is indicated by an alarm indicator flashing). Checking procedure : Turn of the heater and take out the smoke duct linking the heater to the chimney. Close off the smoke duct to the heater using a metal sheet (or other heat proof material). On start up, combustion products are evacuated to the back of the heater by the anti-blowback device opening inside. The anti-blowback thermostat triggers for a few seconds, cuts the burner and starts the safety box timer (alarm indicator flashing). After checking, re-assemble the smoke duct connecting the heater to the chimney. Wait for about 5 minutes (thermostat cooling time) the cut and reconnect the current using the Start/Stop switch. The boiler restarts. 23/06/ B DTG 1300 Eco.NOx/V 23

24 Maintenance 1 Cleaning main burner and ignition burner The main burner and the ignition burner injector with its filter must be regularly cleaned to ensure good performance. Il est conseillé de le faire au moins 1 fois par an. 1 Ionisation probe 2 Ignition electrode 3 Flame diffuser 4 Earth electrode Main burner Switch off the boiler electrical power supply Cut the gas supply. Open the heater door Disconnect the burner connector under the command panel Unscrew the union joint on the gas inlet pipe Unscrew the screws Take out the burner earth wire Disassemble the burner drawer Clean the burner with a brush, a vacuum cleaner or a blower Do not use a metal brush! - Re-assemble the burner earth wire Ignition burner Unscrew the connecting screw, then pull the gas supply pipe towards you Take out the injector and the filter Remove ionisation probe 1 and the earth electrode 4 deposits (for example using sand paper) - Re-attach the supply tube (14 spanner), - Check the position of the ionisation probe 1, the ignition electrode gap 2 and the position of the flame diffuser 3 in terms of the sizes indicated on the drawing (required in the event of heater malfunction). Check the seals for the gas. 24 DTG 1300 Eco.NOx/V 23/06/ B

25 2 Cleaning heater body Sweep the heater. Take out the burner drawer from the heater body. Do not block the gas ramp openings. With the burner out : Take out the column head fixed by 2 screws and toothed washers Take out the insulation Open the sweeping trap by unscrewing the 2 screws Clean the heater body with the special brush delivered with the product. To re-assemble, perform the above actions in reverse order. 3 Maintenance Maintenance and cleaning of the heater must be carried out at least once a year by a qualified technician. Water level Ice Stages We advise you against draining the system unless it is absolutely necessary (For example : Several months' absence with the risk of ice in the building). 4 Periodic checks on the domestic hot water tank Actions Regularly check the level of water in the system and top up if required, taking care that cold water is not added suddenly into the boiler when it is hot. This operation must be carried out several times per season ; if not, look for the probable leak and immediately fix it. In the event that the heating stops during winter, increasing the risk of ice (holiday home for example), it is recommended that sufficient anti-freeze is used to stop the heating water from freezing. As a default, completely empty the installation (check with your installation engineer). It is recommended that you take out a maintenance contract with a qualified installation engineer. In the event that this is not possible, sign a maintenance contract with an after-sales service company recommended by your installation engineer or De Dietrich. Sweeping the smoke conduct and the purge tank must be carried out at least once a year during boiler maintenance. Titane anode No maintenance operations The panel must be switched on to ensure that the anode is working Magnesium anode The titanium anode can be replaced by a magnesium anode. The magnesium anodes must be checked at least every 2, years. After the first check, determine the frequency of future checks on the basis of anode wear. The anodes can be checked by two methods: - Inspection: the anode must be replaced if its diameter is less than 15 mm (original diameter = 33 mm) - Function test: - disconnect the earth wire from the anode 23/06/ B DTG 1300 Eco.NOx/V 25

26 - measure the strength of the current between the tank and the anode ; if the current measured is less than 0.1 ma, the anode should be replaced. Valve or safety unit The safety unit must be periodically manoeuvred (at least once a month). To do this, put the safety unit in the drainage position. This manoeuvre evacuates any desposits which may in time block the safety unit valve. Failure to comply with this maintenance rule may cause damage to the tank structure. Descaling In hard water regions, we recommend descaling the tank annually in order to maintain its performance. - Remove limescale deposits in the form of sludge or strips in the bottom of the tank. On the other hand, do not touch limescale adhering to the walls of the tank as it provides effective protection against corrosion and improves the insulation of the DHW tank. - The exchanger will have to be descaled, if need be, in order to maintain optimum performance. 4.1 Operations to be carried out to check or replace the anode and descale the installation The TAS titanium anode (standard) The magnesium anode (optional) 1. Fit a new watertight seal to the calorifier flange 2. Cut the power supply to the boiler 3. Cut off the cold water supply and drain the DHW tank. To drain though the safety unit, turn the unit to drain and turn on a hot water tap (or a bleed valve) to allow air to enter. 4. Remove the front panel and the sensors. 5. Remove the cover (13 mm spanner). 6. Check the anode and replace it if necessary. 7. When reassembling, replace the watertight seal; to do this: - Replace the lip seal and position it in the visit opening, making sure that you place its lug outside the DHW tank. - Position the retainer ring around the seal, making sure you place the lug above the retainer ring. - Fix the cover to the flange using *1 screws, tightening them uniformly in a cross pattern. 8. Proceed with filling according to the instruction in the chapter "Commissioning". Check the seal and the safety devices on the calorifier after reassembly. The flange mounting bolts must not be excessively tight: 6N.m± : use a torque wrench. Nota: Approximately 6 Nm is obtained by holding the box spanner by the small lever. 26 DTG 1300 Eco.NOx/V 23/06/ B

27 Incidents and solutions Symptoms Probable causes Solution The heater does not start and the safety box is not affected (red alarm indicator off) The burner does not ignite and the safety box is not affected (red alarm indicator off) - The heater thermostat is requiring heat - Setting (option) is not requiring heat. - The safety thermostat has been triggered after overheating. - Create a demand by moving the heater thermostat or the setting level (option). - Solve the cause of overheating and reset the safety thermostat. - No current - Place the Stop/Start switch on "On" - On safety because of a lack of gas - Purge the gas supply pipe then reset the heater using the panel reset button - Faulty gas valve - Check the gas valve and replace if necessary. - No spark from the electrode - Check the electric cable connection to the safety box and the electrode - No ionisation current - Check the ionisation probe and earth wire connection. - Check the position of the ionisation probe and the flame diffuser in the ignition burner - Blocked filter or ignition burner - Clean the filter and the ignition burner injector injector The burner ignites and the safety box goes into standby (burner cut and - Anti-blowback thermostat cut - Check the draught in the chimney connection, check the condition of the anti-blowback thermostat, then press the Start/Stop button to cancel the 15 timer and restart the heater the alarm indicator - Please note the seriousness of unplanned intervention on the combustion flashes) product evacuation checking device : evacuation faults must be solved by improving the draught in the chimney. - In the event of a thermostat fault, it must be replaced by a part stated on our "Spare parts list". Its position must not be modified, which is defined by the 2 bosses on the holding bracket which are located in the 2 holes on the draught diverter. The thermostat must not be placed out of service. The burner ignites and - Inversion of the phase and - Connect the phase to terminal 1 and neutral to 2. the safety box is affected (alarm indicator on) neutral wires on the heater's command panel The burner ignites but - Upstream pressure too weak - Check gas supply with reduced power - Dirty filter - Clean the filter - Unsuitable injectors (See Table - Check them "Pressure setting and marking of calibrated injectors") - Faulty gas valve - Check gas valve and replace if necessary - Injectors too small - Check them (See Table "Pressure setting and marking of calibrated injectors") Dirty cast iron body - Upstream pressure too high - Revoir l alimentation en gaz (hearth) - Dirty burner - Clean the burner - Insufficient or poorly placed air - Enlarge air supply, smoothen airation holes supply - Faulty gas valve - Check gas valve and replace if necessary Noisy heater - Poor purge - Purger correctement - Body has scale - Détartrer le circuit chauffage - Unsuitable injectors (Whistling) - Check injectors - Burner clogged by building dust 23/06/ B DTG 1300 Eco.NOx/V 27

28 Heater too hot or too cold for requirements Flame returns Whistling Symptoms Probable causes Solution - 3 position switch on position - Check the position of the 3 position switch - Wrong setting for the heater thermostat - Injectors too large - Check pressure injectors - Pressure too weak - Injectors too small - Check pressure injectors - Pressure too high - Set the heater thermostat if the heater has SV-matic setting or an ambient thermostat 28 DTG 1300 Eco.NOx/V 23/06/ B

29 To order a spare part, quote the reference number next to the part required. Domestic hot water tanks 23/06/ B DTG 1300 Eco.NOx/V 29

30 . Spare parts - DTG 1300 Eco.NOx/V 23/06/ A Boiler body + Draught diverter + Insulation DE DIETRICH THERMIQUE S.A.S. - Spare parts centre 4, rue d Oberbronn - F REICHSHOFFEN - Tél. : (+33) Fax : (+33) cpr dedietrichthermique.com

31 Gas line Cladding 23/06/ B DTG 1300 Eco.NOx/V 31

32 Linking kit 32 DTG 1300 Eco.NOx/V 23/06/ B

33 Rep Code no. Description Tank LI130 foam for DTG 1304 and 1305 Eco.NOx/V LI130 foam for DTG 1306 Eco.NOx/V mm seal kit Complete buffer tank Complete Anode x8.5x2 vitron seal Nylon spacer Connector Sensor attachment lug Adjustable foot Insulation, buffer tank Upper angle fastening, length Upper angle fastening, length Gasket 29x19x Gasket 29x15x TAS anode cable, length 2 m Titan_Active_System_ simulation connector Boiler body Assembled boiler body - 4 sections Assembled boiler body - 5 sections Assembled boiler body - 6 sections Front mounting square Sensor tube Body lifter Straight 1" pipe Nipple N280 1" ElbowNr. 92 1" Draught diverter Draught diverter complete - 4 sections Draught diverter complete - 5 sections Draught diverter complete - 6 sections Flue gas nozzle Ø 110/ Staged smoke nozzle Ø 125/ Staged smoke nozzle Ø 150/ Inspection hatch - 4 sections Inspection hatch - 5 sections Inspection hatch - 6 sections Anti-backflow thermostat complete Mounting square Rep Code no. Description Electric circuit - Anti-backflow thermostat Body screws packet + Draught diverter Insulating material for body Complete insulating material for body - 4 sections Complete insulating material for body - 5 sections Complete insulating material for body - 6 sections Insulation under burner - 4 sections Insulation under burner - 5 sections Insulation under burner - 6 sections Insulation back of hearth - 4 sections Insulation back of hearth - 5 sections Insulation back of hearth - 6 sections Silicone filler tube Brush Gas circuit Gas circuit complete - 4 sections Gas circuit complete - 5 sections Gas circuit complete - 6 sections FURIGAS burner drawer - 4 sections FURIGAS burner drawer - 5 sections FURIGAS burner drawer - 6 sections FURIGAS burner + Screws Pressure socket Earth cable Complete ignition burner sections Ignition burner gas supply pipe sections Valve Elbow flange 1/2" + Gasket Gasket Box + Wiring Burner cable N174 1/2" x 1" nut Moving part N371 1/2" Green joint 30 x 21 x Gas inlet pipe - 3 to 6 sections Burner drawer insulation kit 4 sections Burner drawer insulation kit 5 sections Burner drawer insulation kit 6 sections Screws Conversion set H/E - Package GL Static thermostat 23/06/ B DTG 1300 Eco.NOx/V 33

34 Rep Code no. Description Cladding Cladding - 4 sections Rep Code no. Description KVT sensor DHW connector Cladding - 5 sections Cladding - 6 sections Front plate - 4 sections Front plate - 5 sections Front plate - 6 sections Complete right hand side panel Complete left hand side panel Catch Upper rear panel - 4 sections Upper rear panel - 5 sections Upper rear panel - 6 sections Lower back panel - 4 sections Lower back panel - 5 sections Lower back panel - 6 sections Complete rear tank panel Ll Complete rear tank panel Ll Complete door Bolt Complete header column Additional part set Funnel Narrow screen Narrow shutter Narrow body Linking kit " connection cross UP15-30 circuit Stainless steel hose, length Power supply cable load pump DHW connector pump Complete G1 connector + nut Elbow Non-return valve Brass reducer Automatic air vent Emptying tap without joint 1/2" Solid plug 1/2" Gasket 29x19x Plug laiton G Green seal 30x21x2 34 DTG 1300 Eco.NOx/V 23/06/ B

35 Warranty You have just purchased a DE DIETRICH appliance and we thank you for the trust you have placed in our products. Please note that your appliance will provide good service for a longer period of time if it is regularly checked and maintained. Your fitter and the DE DIETRICH customer support network are at your disposal at all times. Warranty terms Starting from the purchase date shown on the original fitter's invoice, your appliance has a contractual guarantee against any manufacturing defect. The length of the guarantee is mentioned in the price catalogue. The manufacturer is not liable for any improper use of the appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified fitter). In particular, the manufacturer shall not be held responsible for any damage, loss or injury caused by installations which do not comply with the following: - applicable local laws and regulations - specific requirements relating to the installation, such as national and/or local regulations - the manufacturer's instructions, in particular those relating to the regular maintenance of the unit - the rules of the profession The warranty is limited to the exchange or repair of such parts as have been recognised to be faulty by our technical department and does not cover labour, travel and carriage costs. The warranty shall not apply to the replacement or repair of parts damaged by normal wear and tear, negligence, repairs by unqualified parties, faulty or insufficient monitoring and maintenance, faulty power supply or the use of unsuitable fuel. Sub-assemblies such as motors, pumps, electric valves etc. are guaranteed only if they have never been dismantled. France The preceding dispositions are not exclusive of benefits for the purchaser of the legal guarantee as stated in Civil Code articles 1641 to Belgium The preceding dispositions about the contractual guarantee are not exclusive of profit if the need arises for the purchaser in Belgium of the applicable legal dispositions on hidden defects. Switzerland The application of the warranty is subject to the terms and conditions of sale, delivery and warranty of the company marketing DE DIETRICH products. Other countries The above provisions do not restrict the benefit of the legal laws regarding hidden defects applicable in the buyer's country. 23/06/ B DTG 1300 Eco.NOx/V 35

WHE 2.24 / WHE 2.24 FF

WHE 2.24 / WHE 2.24 FF EN Wall-hung gas boilers WHE 2.24 WHE 2.24 FF User Guide 300011777-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

DTG X.. N. Low temperature gas furnace. Instructions for use. English 14/11/2005

DTG X.. N. Low temperature gas furnace. Instructions for use. English 14/11/2005 DTG X.. N Low temperature gas furnace English 14/11/2005 Instructions for use Contents Important recommendations...................................................................3 1 Aeration.................................................................................................3

More information

Range GT GTU C GT 220

Range GT GTU C GT 220 Range GT 120 - GTU C 120 - GT 220 Low temperature fuel oil boiler Oil-fired condensation boiler English 21/09/06 Instructions for use Contents Important recommendations...................................................................3

More information

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A Remeha Fuel oil/gas boilers EN Installation and Service Manual 300016859-001-A 63115 Declaration of conformity The appliance complies with the standard model described in declaration of compliance. It

More information

Wood-burning boiler CBB. User Guide E

Wood-burning boiler CBB. User Guide E EN Wood-burning boiler User Guide 300008541-001-E . Contents 1 Symbols used...........................................................................3 2 Important recommendations...............................................................3

More information

DTG Eco / V130

DTG Eco / V130 ECODENS Gas fired condensing boiler EN User Guide 300010111-001-B Contents 1 Introduction.............................................................................3 1.1 Symbols and abbreviations................................................................................3

More information

Wall-hung gas boilers. Instructions for use. English 31/08/05

Wall-hung gas boilers. Instructions for use. English 31/08/05 City 1.24/II Chimney and VMC - City 1.24/II FF City 2.24/II Chimney and VMC - City 2.24/II FF - City 2.28 FF City 3.24/II Chimney - City 3.24/II FF City 24 BIC/II - City 24 BIC/II FF City Condens 1.24,

More information

B 150p to B 500p. Independent domestic hot water tanks. Installation instructions. Instructions for use. Technical instructions.

B 150p to B 500p. Independent domestic hot water tanks. Installation instructions. Instructions for use. Technical instructions. B 150p to B 500p Independent domestic hot water tanks English 25/04/06 Installation instructions Instructions for use Technical instructions 94870007 Contents Introduction.................................................................................3

More information

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI Vivadens EN Wall-hung gas condensing boilers MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI User Guide 300015874-001-B Contents 1 Introduction...4 1.1 Used symbols...4 1.2 Abbreviations...4 1.3 General...4

More information

Oil-fired condensing boiler GTU C 330. User Guide B

Oil-fired condensing boiler GTU C 330. User Guide B EN Oil-fired condensing boiler GTU C 330 User Guide 300017846-001-B . Contents 1 Introduction.............................................................................3 1.1 Symbols and abbreviations................................................................................3

More information

Gas Instantaneous Water Heater

Gas Instantaneous Water Heater 6 720 607 823 GB (06.06) SM Installation and Operating Instructions Gas Instantaneous Water Heater WR10..B... WR11..B... With electronic ignition and triple safety system consisting of ionisation detector,

More information

Gas-fired boilers DTG 230. User Guide D

Gas-fired boilers DTG 230. User Guide D EN Gas-fired boilers DTG 230 User Guide 300011506-001-D . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

SOLNEO SGC 24 SOL. User Guide. Gas fired condensing boiler C

SOLNEO SGC 24 SOL. User Guide. Gas fired condensing boiler C SOLNEO EN Gas fired condensing boiler SGC 24 SOL User Guide 300017555-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols and abbreviations................................................................................3

More information

ZENA PLUS EASYLIFE WALL-HUNG GAS BOILERS

ZENA PLUS EASYLIFE WALL-HUNG GAS BOILERS ZENA PLUS WALL-HUNG GAS BOILERS MSL FF: from. to 1 kw for heating only MSL FF + BMR 80 and MSL FF + SR 10: from. to 1 kw for heating and DHW produced by an 80-litre calorifier placed beside the boiler,

More information

Vivadens. Wall-hung gas condensing boilers MCR 24/28 BIC. User Guide B

Vivadens. Wall-hung gas condensing boilers MCR 24/28 BIC. User Guide B Vivadens EN Wall-hung gas condensing boilers MCR 24/28 BIC User Guide 300024112-001-B Contents 1 Introduction...4 1.1 Symbols used...4 1.2 Abbreviations...4 1.3 General...4 1.3.1 Manufacturer's liability...4

More information

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 HG 675 X 60 HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 1 2 1. : 93/68: 90/396: 2006/95/CE: 2004/108/CE: - 1935/2004:. 2002/95/CE: RoHS 2.,.,,,,...,. (,..)..,,.,. ( ),,, ;,,.,.....,.,,,,,,...,. (..),,.,..,.,,,,

More information

Remeha. Fuel oil/gas boilers P 420. Installation and Service Manual

Remeha. Fuel oil/gas boilers P 420. Installation and Service Manual Remeha Fuel oil/gas boilers P 420 en Installation and Service Manual 300016839-02 Declaration of conformity The appliance complies with the standard model described in declaration of compliance. It is

More information

Remeha. Fuel oil/gas boilers P 320. Installation and Service Manual

Remeha. Fuel oil/gas boilers P 320. Installation and Service Manual Remeha Fuel oil/gas boilers P 320 en Installation and Service Manual 300016243-02 Declaration of conformity The appliance complies with the standard model described in declaration of compliance. It is

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc Mikrofill Ethos Condensing combination boiler Maintenance Instructions 24cc IMPORTANT Benchmark Installation, Commissioning and Service Record Log Book is enclosed in your customer information pack. This

More information

INSTALLATION AND MANINTENANCE INSTRUCTIONS

INSTALLATION AND MANINTENANCE INSTRUCTIONS INSTALLATION AND MANINTENANCE INSTRUCTIONS Appr. Nr. A 9503 T - 0085 AQ 0765 PEGASUS F2 T HIGH EFFICIENCY GAS-FIRED CAST-IRON BOILERS Models 51-68 - 85-102 2 Contents 1. General technical data 2. Dimensional

More information

Domestic hot water tank SR130. Installation, User and Service Manual

Domestic hot water tank SR130. Installation, User and Service Manual EN Domestic hot water tank SR130 Installation, User and Service Manual 300009755-001-03 Contents 1 Introduction...4 1.1 Symbols used...4 1.2 Abbreviations...4 1.3 Liabilities...4 1.3.1 Manufacturer s liability...4

More information

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL STREBEL GENEVA CE ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL INDEX TABLE 1 TECHNICAL DATA SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION 7 SECTION 8 SECTION

More information

Package FT 74. X control panel. Installation and Service Manual

Package FT 74. X control panel. Installation and Service Manual en Package FT 74 X control panel Installation and Service Manual 7647029-03 . Contents 1 Safety instructions.......................................................................3 1.1 Important recommendations................................................................................3

More information

RMG IT ES PT GB FR BE

RMG IT ES PT GB FR BE RMG IT ES PT GB FR BE INSTALLER INSTRUCTIONS ENGLISH CONTENTS 1 DESCRIPTION OF THE BOILER........................................................................ pag. 38 2 INSTALLATION.......................................................................................

More information

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600 I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d Model code: BORA600 Contact Caple on 0844 8003830 or for spare parts www.4caple.co.uk 1 Y O U R A P P L I A N C E Thank you for buying your

More information

1 VICTRIX ZEUS Superior kw I features

1 VICTRIX ZEUS Superior kw I features Wall-hung condensing VICTRIX ZEUS Superior kw I is the new range of wall-hung condensing boilers with 54 litre stainless steel storage tank available in two versions with nominal heat output of 26 kw and

More information

WARNING FOR YOUR SAFETY FOR YOUR SAFETY. Outback Patio Heaters. Patio Heaters

WARNING FOR YOUR SAFETY FOR YOUR SAFETY. Outback Patio Heaters. Patio Heaters Patio Heaters Outback Patio Heaters A regulator of an approved type is required to operate this unit. A regulator of 28-30mbar must be used for butane and 37mbar for propane. For more details on compatible

More information

HOT WASHER MODEL NO: KING150

HOT WASHER MODEL NO: KING150 WARNING: Do not use the hot washer without reading this manual HOT WASHER MODEL NO: KING150 PART NO: 7320175 OPERATION & MAINTENANCE INSTRUCTIONS LS1215 INTRODUCTION Thank you for purchasing this CLARKE

More information

Low temperature gas boiler DTG 330 S. User Guide

Low temperature gas boiler DTG 330 S. User Guide en Low temperature gas boiler DTG 330 S User Guide 300011852-02 . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

Proline GAS HOB Model TCG40IX Instruction Book

Proline GAS HOB Model TCG40IX Instruction Book Proline GAS HOB Model TCG40IX Instruction Book GB Operating and Installation Instructions Index Technical data and specifications...... 3 Installation...................... 3-6 Ventilation........................

More information

Parts Available from

Parts Available from Montage und Bedienungsanleitung Manuel d entretien Installation, use and maintenance instructions Installatie-, gebruiks- en onderhoudsvoorschriften Oδηγίες εγκατάστασης, χρήσης και συντήρησης D F GB NL

More information

HOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance

HOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance Installation Operation Commissioning Maintenance HOT AIR GENERATOR WITH GAS BURNER GGS NA11.45 A 06-2011 04-2011 CONTENTS 1. DESCRIPTION OF THE UNIT 2. INSTALLATION & CONNECTION 3. COMMISSIONING 4. CARE

More information

Operating instructions

Operating instructions Operating instructions Gas condensing boiler WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

More information

51AKS I S O OWNER S MANUAL

51AKS I S O OWNER S MANUAL LLOYD'S REGISTER QUALITY ASSURANCE 51AKS I S O 9 00 1 OWNER S MANUAL This manual applies to the following models Stand-alone Split 51AKS 085--- 51AKS 010--- 51AKS 185--- 51AKS 013--- 51AKS 113--- 51AKS

More information

S3 standard control panel

S3 standard control panel S3 standard control panel Package MD4 English 23/01/06 Installation instructions Technical instructions Contents Symbols used................................................................................3

More information

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 is the new wall-hung condensing boiler for room heating only, set-up for independent functioning and for that in cascade mode

More information

HOW TO USE YOUR 4500 RANGE L.P.G. COOKER OR HOB UNIT

HOW TO USE YOUR 4500 RANGE L.P.G. COOKER OR HOB UNIT HOW TO USE YOUR 4500 RANGE L.P.G. COOKER OR HOB UNIT If the appliance does not operate correctly contact your supplier Or Leisure Products (Bolton) Ltd Holly Street, Bolton, BL1 8QR. England. ~~~~ For

More information

2.1 BOILER ROOM BOILER ROOM DIMENSIONS 2.3 CONNECTING UP SYSTEM 2.4 CONNECTING UP FLUE 2.5 ELECTRICAL CONNECTION

2.1 BOILER ROOM BOILER ROOM DIMENSIONS 2.3 CONNECTING UP SYSTEM 2.4 CONNECTING UP FLUE 2.5 ELECTRICAL CONNECTION FONDERIE SIME S.p.A. of Via Garbo 27 - Legnago (VR) - Italy declares that its diesel-burning boilers are produced in accordance with the requirements of article 3 paragraph 3 of Directive PED 97/23/EEC

More information

Light oil burners. One stage operation

Light oil burners. One stage operation Installation, use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3505 RDB CF 38 50 T3 350050 RDBR CF 6 50 TR 35050 RDBR CF 33 50 TR 35050 RDBR CF 38 50 T3R 350650 RDBR

More information

COMBY 4000 & 9000 STEAM CLEANER OPERATOR MANUAL

COMBY 4000 & 9000 STEAM CLEANER OPERATOR MANUAL COMBY 4000 & 9000 STEAM CLEANER OPERATOR MANUAL Clemas & Co. Unit 5 Ashchurch Business Centre, Alexandra Way, Tewkesbury, Gloucestershire, GL20 8NB. Tel: 01684 850777 Fax: 01684 850707 Email: info@clemas.co.uk

More information

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1 A AD Oil burners fuel unit deltapumps.com DE116-0709 A-AD_en_0709.pdf - 16.11.09 Page 1/1 Oil burners fuel unit Type A, AD 1- Applications The DELTA aluminium fuel unit type A is an efficient and modern

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit Service instructions for contractors VIESMANN Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit VITOLADENS 300-T 1/2007 Please keep safe. Safety instructions Safety instructions

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions GB Forced draught gas burner One stage operation CODE MODEL TYPE 3751782 GAS 5 517T80 291 (4) - 07/2015 Declaration of conformity in accordance with ISO /

More information

Read installation manual prior to installation of this unit! Read user manual before putting this unit in operation!

Read installation manual prior to installation of this unit! Read user manual before putting this unit in operation! Gas Instantaneous Water Heater WR 11/14/18.G... Installation Manual and Operating Instructions ZA Read installation manual prior to installation of this unit! Read user manual before putting this unit

More information

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 EN OPERATING MANUAL OIL HEATER TRT-BA-IDE20-30-50-60-80-TC-001-EN Table of contents Information on the use of this manual... 1 Scope of delivery... 1 General safety...

More information

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL Heating, Air Conditioning, Ventilation Отопление-Кондиционеры-Вентиляция MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL 1. Usage MTM 8-30 universal oil heater is designed for heating commercial rooms

More information

Gas Fire Patio Heater Q9

Gas Fire Patio Heater Q9 Gas Fire Patio Heater Q9 Instruction Manual Please read the manual BEFORE you unpack or install the fire TABLE OF CONTENTS Warning 3 Getting Started 4 What s Included 5 Assembly Procedures 6 Product Drawing

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

Propane Heater REMKO PGM 30 REMKO PGM 60

Propane Heater REMKO PGM 30 REMKO PGM 60 Propane Heater REMKO PGM 30 REMKO PGM 60 Operation Technology Spare Parts Edition GB L07 REMKO strong as a bear. Operating instructions Make sure to read these instructions carefully before starting/using

More information

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI200EN 09/2017

More information

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N 238-44219-00 (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! You have just purchased one of the finest water heaters on

More information

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80 Installation, use and maintenance instructions Heavy oil burner CODE MODEL TYPE 3434985 PRESS 60 N 616 T80 3434986 PRESS 60 N 616 T80 291 (2) - 01/2009 Thermal power - Output Operation Fuel Electrical

More information

USERS MANUAL FOR GAS BOILERS

USERS MANUAL FOR GAS BOILERS USERS MANUAL FOR GAS BOILERS PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE MODELS: NOVADENS 24 NOVADENS 24C NOVADENS

More information

Safety. Operating instructions Ionization pilot burners ZAI, ZMI, ZKIH DANGER. Contents WARNING CAUTION Edition 12.11

Safety. Operating instructions Ionization pilot burners ZAI, ZMI, ZKIH DANGER. Contents WARNING CAUTION Edition 12.11 050560 Edition. D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Ionization pilot burners,, Translation from the German 0 Elster GmbH Contents Checking the usage.....................

More information

Oil burners fuel unit with solenoid valve

Oil burners fuel unit with solenoid valve Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Germany VM_e.pdf - 18.05.08 Page 1/6 Oil burners fuel unit with solenoid valve

More information

Friwa Compact. Operating instructions EN

Friwa Compact. Operating instructions EN Operating instructions EN Version 1.1 / Edition 09/2013 Contents 1 Key background information... 3 1.1 Limitation of liability... 3 1.2 Responsibilities of the operator... 3 1.3 Documentation... 3 1.3.1

More information

Installation and maintenance instructions

Installation and maintenance instructions 6304 4995 0/004 GB For installer Installation and maintenance instructions Flue gas heat exchanger WT50/60 Please read thoroughly prior to installation and maintenance. Summary About this manual This equipment

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS Benchmark 3.0LN 24-Month Maintenance Kit# 58015-04 This kit applies to units with an Ignitor and a separate gas injector. For units with an Ignitor-Injector (P/N 58023), see Kit

More information

VERTICAL COOKING PRECISIO/PRECIJET COMBI OVEN PRECISIO/ PRECIJET OVENS S.A.V. MAINTENANCE AND REPAIR

VERTICAL COOKING PRECISIO/PRECIJET COMBI OVEN PRECISIO/ PRECIJET OVENS S.A.V. MAINTENANCE AND REPAIR VERTICAL COOKING S.A.V. PRECISIO/ PRECIJET OVENS MAINTENANCE AND REPAIR 27/03/2012 PPS-3BEFM10PC GENERAL Tools Every time this symbol appears, it is imperative to have the appropriate tool in order to

More information

Synergy Grill User & Engineer Installation & Conversion Guide

Synergy Grill User & Engineer Installation & Conversion Guide Synergy Grill 1300 User & Engineer Installation & Conversion Guide 1 Index: Description Page Number/Section Important Information 3 Installation 4-6 / Section 1 Commissioning 6 / Section 2 Converting Gas

More information

s y ens Av Avensys FIN EST RUS SLO RUS UAE

s y ens Av Avensys FIN EST RUS SLO RUS UAE 34 224 34 225 Avensys Avensys GB D...1...5 I...5 N...9 GR...13 TR...17 BG...21 RO...25 GB...2 NL...6 FIN...10 CZ...14 SK...18 EST...22 RUS CN...26 F...3 S...7 PL...11 H...15 SLO...19 LV...23 RUS...27 E...4

More information

Cooker Hood Instruction Manual

Cooker Hood Instruction Manual Cooker Hood Instruction Manual Model number(s): RHSCH601SS/B & RHSCH901SS/B IMPORTANT: RETAIN FOR FUTURE REFERENCE Contents Safety Instructions. 3-6 Product Overview. 7 Positioning. 8 Operational modes.

More information

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS G 2000-S 25-35 - 45-55 60-70 - 100 (V13) 1 Index WARNINGS GAS FLOW RATE DIMSIONS SETTINGS PARAMETERS SERVICING THE URNER 3 8 13 OPERATING DESCRIPTION

More information

NANEO EMC-M WALL-HUNG GAS CONDENSING BOILERS

NANEO EMC-M WALL-HUNG GAS CONDENSING BOILERS NANEO EMC-M WALL-HUNG GAS CONDENSING BOILERS EMC-M : from 6.1 to.8 kw, for heating only EMC-M /BS 8 and EMC-M /BS 13: from 6.1 to.8 kw, for heating and hot water preparation by associated DHW tank, 8 or

More information

Operating instructions

Operating instructions The energy you need Operating instructions Betacom 3 24c -A (H-GB) 30c -A (H-GB) GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information...

More information

Oil burners fuel unit with solenoid valve

Oil burners fuel unit with solenoid valve Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Italy - DE112/0404 Oil burners fuel unit with solenoid valve Type VM The DELTA

More information

Light oil / kerosene burner

Light oil / kerosene burner Installation, use and maintenance instructions Light oil / kerosene burner One stage operation CODE MODEL TYPE 374445 G5 444T50 290238 (5) - 05/20 TECHNICAL DATA Thermal power output 28 60 kw 2.3 5 kg/h

More information

TAHITI CONDENSING KR 55 - KR 85

TAHITI CONDENSING KR 55 - KR 85 IST 03 C 351-01 TAHITI CONDENSING KR 55 - KR 85 GB INSTALLATION USE AND MAINTENANCE Dear Customer, Thank you for choosing and buying one of our boilers. Please read these instructions carefully. They will

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS 24-Month Maintenance Kit P/N 58025-06 For BMK2.0LN Boilers Description of Document: This TID provides the procedures to perform recommended 24-Month maintenance on the following

More information

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No 53 416 06 Publication No. ZZ 180/17 May 2000 These appliances are tested and certified by B G Technology for

More information

WALL-HUNG GAS CONDENSING BOILERS MCR-P 24/28 BIC. HOMOLOGATION B 23P - C 13x - C 33x - C 93x -C 53 - C 43x - C 83x *

WALL-HUNG GAS CONDENSING BOILERS MCR-P 24/28 BIC. HOMOLOGATION B 23P - C 13x - C 33x - C 93x -C 53 - C 43x - C 83x * VIVADENS MCR-P WALL-HUNG GAS CONDENSING BOILERS MCR-P 24: from 6.3 to 25.0 kw, for heating only MCR-P 24/BS 80 and MCR-P 24/BS 130: from 6.3 to 25.0 kw, for heating and domestic hot water production by

More information

Oil burners Brûleurs fioul Stookoliebranders

Oil burners Brûleurs fioul Stookoliebranders Installation, use and maintenance instructions Manuel d entretien Installatie-, gebruiks- en onderhoudsvoorschriften GB F NL Oil burners Brûleurs fioul Stookoliebranders One stage operation Fonctionnement

More information

Gas fired condensing boiler C 230 ECO. User Guide C

Gas fired condensing boiler C 230 ECO. User Guide C EN Gas fired condensing boiler C 230 ECO User Guide 300015144-001-C Contents 1 Introduction.............................................................................3 1.1 Used symbols...........................................................................................3

More information

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI500EN 09/2017

More information

BG2000S PRE-MIX GAS BURNER

BG2000S PRE-MIX GAS BURNER BG000S PRE-MIX GAS BURNER INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 08707 707 77 FAX: 08707 707 767 E-MAIL:info@stokvisboilers.com

More information

Operating instructions

Operating instructions Operating instructions Capriz 2 24c 28c GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information... 4 2 Notes on the documentation...

More information

Heat Exchanger Block Replacement Instructions

Heat Exchanger Block Replacement Instructions Series 1-4 Gas-fired water boiler Heat Exchanger Block Replacement Instructions Ultra-80 S1-4 Heat Exchanger Block Replacement Kit, Part No. 383-500-773 Ultra-105 S1-4 Heat Exchanger Block Replacement

More information

Light oil - kerosene burner

Light oil - kerosene burner Installation, use and maintenance instructions Light oil - kerosene burner One stage operation CODE MODEL TYPE 374374 G3B 437T 90 (4) - 05/0 TECHNICAL FEATURES TYPE 437T Thermal power output 9 35 kw.6

More information

Servicing Instructions Type C Boilers G.C.N: LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER

Servicing Instructions Type C Boilers G.C.N: LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER Servicing Instructions Type C Boilers G.C.N: 4-6-0 47-6-08 47-6-09 47-6-3 LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER TABLE OF CONTENTS Page No.. SERVICING INSTRUCTIONS. Replacement of Parts 3.2

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS INSTALLATION AND OPERATING INSTRUCTIONS HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS INDEX 1. Technical information... page 3 2. Dimensional and technical characteristics... page 3 3. Packing

More information

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw Subject to modification Contents 1. Important Information 4 1.1. Documentation 4 1.2. Guarantee

More information

BSC...E - BSP...E - BESC...E

BSC...E - BSP...E - BESC...E INISOL DUO E DIETRISOL DUO E Solar hot water calorifer BSC...E - BSP...E - BESC...E EN User Guide 0007781-001-01 Contents 1 Introduction.............................................................................

More information

Condensing, pre-mixed, wall-hung gas boilers with water tank

Condensing, pre-mixed, wall-hung gas boilers with water tank C 271-01 made in Italy Nias condensing Condensing, pre-mixed, wall-hung gas boilers with water tank Life-enhancing heat GB Condensing, pre-mixed, wall-hung boilers with water tank Nias CONDENSING HIGH

More information

Installation and Operating Instructions

Installation and Operating Instructions Installation and Operating Instructions Models: Verso 4G Hob As part of Parmco Appliances commitment to improving and updating product ranges, we reserve the right to alter, change and update technical

More information

ENERGY TOP. Condensing boiler solutions

ENERGY TOP. Condensing boiler solutions ENERGY TOP Condensing boiler solutions 1 ENERGY TOP > ENERGY TOP RANGE A wide array of flexible solutions both for centralised residential application and big commercial plants The increasing need for

More information

Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS

Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS PW1370TD 2 EN Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS 3 E3 E1 C3 A1-A2-A3-A4 B4 B1 B5 B2 C1 B3 D 1 4 1 2 3 4 5 6 7 Ø13

More information

SAFIRE 2000A FUEL OIL HEATER INSTALLATION, OPERATION AND MAINTENANCE

SAFIRE 2000A FUEL OIL HEATER INSTALLATION, OPERATION AND MAINTENANCE SAFIRE 2000A FUEL OIL HEATER INSTALLATION, OPERATION AND MAINTENANCE You have selected the new generation SAFIRE oil heater as your heating solution. Although our goal is to take into account all problems

More information

E-COMBI EVO E-SYSTEM EVO

E-COMBI EVO E-SYSTEM EVO E-COMBI EVO E-SYSTEM EVO User s manual CONDENSING WALL-HUNG GAS BOILER G.C.N.:47-116-68 (24 kw) G.C.N.:47-116-69 (30 kw) G.C.N.:47-116-70 (38 kw) G.C.N.:41-116-39 (24 kw) G.C.N.:41-116-40 (30 kw) Country

More information

A/23 MFFI - A/27 MFFI

A/23 MFFI - A/27 MFFI A/23 MFFI - A/27 MFFI G.C.N. 47-6-0 / 47-6-2 Servicing Instructions Type C Boilers LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER TABLE OF CONTENTS Page No.. SERVICING INSTRUCTIONS. Replacement of

More information

ir-range 8G /03.15 Changes reserved.

ir-range 8G /03.15 Changes reserved. U s e r m a n u a l ic-range is-range ir-range 8G.52.80.00/03.15 Changes reserved. Contents 1. Introduction...3 2. Safety...5 3. Boiler description...6 4. Display and functions...7 4.1 DHW and Heating

More information

Operating instructions

Operating instructions Operating instructions For the operator Operating instructions HOME SYSTEM GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel. +49 21 91 18 0 Fax +49 21 91 18 28 10 info@vaillant.de

More information

GAS FR25 IR FRYERS. Grande Carte SPECIFICATIONS CONSTRUCTEUR. Part A: Technical characteristics Part B: Technical instructions for installation

GAS FR25 IR FRYERS. Grande Carte SPECIFICATIONS CONSTRUCTEUR. Part A: Technical characteristics Part B: Technical instructions for installation Grande Carte GAS FR25 IR FRYERS SPECIFICATIONS CONSTRUCTEUR Part A: Technical characteristics Part B: Technical instructions for installation - WARNING - Installation and repairs must be carried out by

More information

Instructions for installation and use English. More documents on: H B /09

Instructions for installation and use English. More documents on:  H B /09 TM Instructions for installation and use English EN More documents on: www.zodiac-poolcare.com H0538700.B - 2015/09 Read this manual carefully before installing, maintaining or repairing this appliance!

More information

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler Gas boiler UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM. INSTALLER MUST REVIEW

More information

MAINTENANCE AND SERVICE GUIDE

MAINTENANCE AND SERVICE GUIDE c Dimensions MAINTENANCE AND SERVICE GUIDE System II 80 and 100 Central Heating Fanned Flue Boiler Sizes in mm Flue types: C 12 or 42: horizontal C 32 xx: vertical concentric C 32 xy: Twin flue Boiler

More information

Instructions for use

Instructions for use Instructions for use These instructions are also available on the website: www.kitchenaid.eu Important instructions for safety 4 Installation 6 Safeguarding the environment 6 Troubleshooting guide 7 After-sales

More information