IOM 410. Installation Operation Maintenance Information. UNIT COOLERS Super-Flo (SD Models) Easy-Flo (EF Models) Table of Contents

Size: px
Start display at page:

Download "IOM 410. Installation Operation Maintenance Information. UNIT COOLERS Super-Flo (SD Models) Easy-Flo (EF Models) Table of Contents"

Transcription

1 IOM 410 Installation Operation Maintenance Information UNIT COOLERS Super-Flo (SD Models) Easy-Flo (EF Models) Air, Electric & Hot Gas Defrost Table of Contents Inspection General Safety Information Installation Piping Considerations Line Size Tables Hot Gas Piping Expansion Valve Installation Expansion Valve Selection Unit Cooler (Internal) Wiring Diagrams Typical Field Wiring, Sequence of Operations Start-Up Procedure Defrost Controls Maintenance TroubleShooting Chart Replacement Parts Super-Flo Easy-Flo WITT P.O. Box 580 Collierville, TN (901) Fax (901)

2 INSPECTION Equipment listed on the Bill of Lading but not received, along with any equipment damaged in transit, should be reported immediately to the carrier and a claim filed. Also, check unit nameplates to make sure the voltage is correct before installing. 1. Installation and maintenance are to be performed by qualified personnel who are familiar with this type of equipment. 2. Make sure all field wiring conforms to the equipment requirements and all applicable national and local codes. GENERAL SAFETY INFORMATION INSTALLATION 3. Avoid contact with sharp edges and coil surfaces. They are a potential injury hazard. 4. Disconnect all power sources before performing service or maintenance. Witt SD unit coolers are designed to draw air in through the coil and discharge it through the fans while Witt EF unit coolers are designed to draw air in through the fan guards and discharge it through the coil surface. For most efficient operation, units should be located so that air from an open door cannot be drawn directly into the fans. FIGURE 1: MODEL EF TOP VIEW Dimension Ft. A B C Minimum /2 Maximum FIGURE 2: MODEL SD TOP VIEW When mounting the units, lift and handle them by the cabinet or hanger flanges only. Do not attempt to lift the units by the tubing or fan guards or damage may result. See Figure 1 (EF) or Figure 2 (SD) for location recommendations. These two drawings show the air flow direction and recommended minimum clearances to walls or other obstructions or other unit coolers. The units should be lifted into position by grasping underneath at each end. Care should be taken so that the drain pan is not damaged. The units can be mounted directly to the ceiling using 5/16 lag bolts, or they may be hung below the ceiling using 5/16 threaded rod. If the unit is hung below the ceiling, adequate space must be provided to allow cleaning per UL Sanitation requirements. IMPORTANT: The units must be mounted level in order to drain properly. Use a spirit level to make sure the unit is level in both directions. Proper pitch is provided in the drain pan so the unit will drain when mounted level. Drain Line All units are furnished with a 3/4 FPT drain connection. The drain should be run with a minimum of 1/2 of slope per foot of horizontal run. Keep the length of drain line within the refrigerated space as short as possible. Provide a trap in the line outside of the refrigerated space. On freezer applications, the drain line within the refrigerated space must be wrapped with a heat tape and insulated to prevent water from freezing in the line during the defrost cycle.

3 Table Liquid Line Selection Table 2: Suction Line Selection Line Equiv. Unit Cooler Capacity Size Lgth. BTUH (O.D.) (Ft.) R-22 R404A & R ,000 30,000 3/ ,500 20, ,000 12, ,200 10, ,350 60,000 1/ ,450 38, ,100 26, ,650 21, , ,650 5/ ,350 73, ,000 53, ,450 40, , ,120 7/ , , , , , ,150 These line capacities are also suitable for R502 Line Equiv. Unit Cooler Capacity BTUH Size Lgth. R-22 R404a (HP-62), 507 (AZ-50) (O.D.) (Ft.) Suction Temperature F Suction Temperature F ,800 12,000 18,000 4,000 6,000 10,500 15,500 5/8 50 3,575 5,500 12,000 3,000 4,000 7,500 9, ,600 4,000 9,000 2,000 3,000 5,500 6, ,275 3,500 6,500 1,000 1,500 2,500 4, ,835 25,900 48,000 12,100 18,200 27,000 35,500 7/ ,700 18,000 30,200 6,500 12,200 18,500 24, ,880 15,200 24,100 4,000 6,200 14,500 18, ,865 12,100 18,200 3,500 4,200 10,500 15, ,700 68, ,650 20,000 36,200 58,100 88, / ,500 46,500 70,750 14,300 24,800 39,600 60, ,100 32,100 48,450 9,700 16,700 27,050 41, ,750 25,400 38,820 7,900 13,400 21,500 33, , , ,750 38,000 64, , , / ,000 81, ,120 25,750 44,100 69, , ,200 55,120 84,100 17,650 30,150 47,050 72, ,500 44,350 67,150 14,100 24,120 38,550 57, , , ,100 67, , , , / , , ,100 42,100 71, , , ,400 87, ,200 28,650 48,800 76, , ,120 69,500 98,750 23,100 38,500 61,150 91, , , , , , , , / , , ,100 90, , , , , , ,120 61, , , , , , ,110 49,150 82, , ,600 Refrigerant Piping Install all refrigeration components in accordance with accepted piping practices. Liquid and suction lines may be sized using the suggestions on Page 3, however ASHRAE recommendations must be considered the final authority. All horizontal suction lines should be sloped toward the compressor at the rate of 1/8 per foot for good oil return. Vertical suction risers of more than five feet should be trapped with a P-Trap at the bottom. Find the appropriate factor from Table 3. Divide the BTUH requirement by the Table 3 factor, then select the pipe size directly from Table 1 or 2. Example: Select the correct suction line size for 40,000 BTUH of MP-39 at +20 F. suction temperature and 100 equivalent feet of tubing. 1. Find the factor 0.60 in the R-22 (Suction) column opposite the MP-39 side heading of Table 3. Table 3: Other Refrigerants Capacity Multiplier Refrigerant Use R-22 Table Use R404a Table Liquid Suction Liquid Suction R-134a, MP HP R-401A R-402A 2. Divide 40,000 BTUH by 0.60 to find the corrected capacity. Corr. Capacity = 40,000 BTUH 0.60 = 66,667 BTUH (i.e., 100 equivalent feet of tubing large enough for 66,667 BTUH of R-22 will be suitable for 40,000 BTUH with MP-39). Table 3 lists the multipliers to convert R-22 piping capacities to R-134a or MP-39; and to convert R-404a piping capacities to HP-80. Use the following procedure to avoid tedious trial and error pipe sizing. 3. Refer to Table 2 and find 84,100 BTUH in the R-22 (+20 Suction Temp.) column opposite the 1-3/8 (100 Equiv. Lgth.) side heading. The correct line size is 3/8 OD. It will be noted that 100 of 1-1/8 is suitable for only 48,450 BTUH. 3

4 Hot Gas Piping Hot gas defrost systems can be described as either Re-Evap (three-pipe) or Reverse Cycle (two-pipe) types. Figures 4 thru 7 represent typical piping arrangements for hot gas defrost units. SDG and EFG units may be ordered for either of the two system types mentioned above. LOW TEMPERATURE SDG units only are equipped with a hot gas drain pan loop. Re-Evap System Uses three pipes as shown in Figures 6, 7 & 9 one for the liquid, one for the suction and one for the hot gas. In addition, a heat exchanger/re-evaporator (Figure 3) is used at the suction line outlet of the evaporator and is piped exactly the same as an ordinary liquid/suction heat exchanger. The hot gas is taken from the discharge line between the compressor and the condenser, through a hot gas solenoid valve, then through the hot gas line to the unit cooler. On low temperature SDG units (Fig. 6), the hot gas enters the unit at the drain pan loop before going to the side inlet of the distributor. On all medium temperature units the hot gas goes directly to the side inlet of the distributor. See Fig. 7 (SDG) and Fig. 9 (EFG). The hot gas for all units then goes thru the coil in the same direction as the normal refrigeration flow. The condensed refrigerant is trapped in the re-evaporator as it leaves the coil, there to be metered as a heavy vapor into the suction line flow back to the compressor. Reverse Cycle Is a technique in which the hot gas flows backwards (i.e. opposite to the normal refrigerating flow) through the evaporator. Systems employing the reverse cycle principle are divided into two types Alternating Evaporator and Heat Pump systems. Alternating Evaporator System This is the system commonly referred to as "Reverse Cycle Defrost". It must have multiple evaporator coils on the same system to operate. Evaporator coils are defrosted in groups of one or more coils per group. 65% to 75% of the coils will continue to refrigerate while 25% to 35% are on defrost. The defrosting coils produce liquid refrigerant which is used to operate the coils which are still refrigerating. The simplest design is a system with one condensing unit and three evaporator coils. One coil will defrost at a time, while the other two continue to refrigerate. FIGURE 3 Heat-Exchanger/Accumulator A hot gas line is run from the discharge line of the compressor close to the junction of the main suction line with the three individual suction lines. There the hot gas line branches into three hot gas lines. Each of these three lines has a hot gas solenoid valve; the leaving side of each solenoid valve is teed into one of the three branch suction lines. Each suction line has a suction-stop valve installed between the main suction line and the hot gas tee-in to keep hot gas from entering the main suction line to the compressor. In this way, each evaporator coil has a source for hot gas, controlled by its own defrost solenoid valve. A modular multi-circuit defrost timer is normally employed to synchronize the three defrosts. The timer initiates defrost on a given coil, opening its hot gas solenoid (and closing its suction-stop valve), allowing hot gas to flow backwards through the suction line towards the coil. On low temperature SDG units (Fig. 4), the hot gas enters the unit at the drain pan loop before going into the suction side of the coil itself. On all medium temperature units, the hot gas goes directly into the suction side of the coil. See Fig. 5 (SDG) and Fig. 8 (EFG). As it leaves the coil, the condensed liquid flows through a bypass line around the expansion valve into the liquid line. It flows backwards through the branch liquid line until it reaches the main liquid line, where it is re-introduced into the refrigerating part of the system. The main liquid line is made to operate at a lower pressure during defrost so that it will accept the liquid from the defrosting coil. A much larger Alternating Evaporator system will still operate in much the same way. Such a system might have a larger compressor or a parallel compressor rack operating with many more evaporator coils than described above. Now there will be a group of coils defrosting at once instead of just one. It is important, however, that no one defrost group is larger in refrigerating capacity than 25% to 35% of the total. A given hot gas line and solenoid valve will now service its evaporator group instead of only one evaporator. Heat Pump System Usually employs a single condensing unit and single evaporator. Primarily used in the HVAC industry to transform the (Summertime) DX cooling coil into a (Wintertime) heating coil. A DX coil can be defrosted in this way when used in a specialized system. CAPACITY AND DIMENSIONS EVAPORATOR MODEL A B C D CAPACITY NO. (OD) (OD) Up to 6,000 HEA-1A 9-3/4 5 7/8 3/8 6,000 to 12,000 HEA-2A 15-3/ /8 1/2 12,000 to 24,000 HEA-3A 27-3/ /8 1/2 24,000 to 36,000 HEA-4A 37-3/ /8 5/8 36,000 to 55,000 HEA-5A 45-3/ /8 5/8 55,000 to 80,000 HEA-6A 64-3/ /8 7/8 4 NOTE: Level-mount the Heat-Exchanger/Accumulator within refrigerated space as close to the evaporator as possible. The metering valve is to be in the down position as shown.

5 Figure 4 Low Temp. Units (With Drain Pan Loop) Super-Flo Units Reverse-Cycle (Two-Pipe) Systems Figure 5 Medium Temp. Units (without drain pan loop Figure 6 Low Temp. Units (With Drain Pan Loop) Re-Evap (Three-Pipe) Systems Figure 7 Medium Temp. Units (With Drain Pan Loop) Easy-Flo Medium Temp. (without drain pan loop) Figure 8 Reverse-Cycle (Two-Pipe) Systems Figure 9 Re-Evap (Three-Pipe) Systems 5

6 Expansion Valve Installation All units use an externally equalized type valve. See Table 4 and 5 for expansion valve selection. NOTE: All units have 1/2" OD male sweat inlet connections except Super-Flo Models 220L, 240L, 260L and 300L which are 7/8" OD male sweat. Locate the valve inside the end compartment of the unit. If the unit has a distributor, make sure it is in the vertical position for best refrigerant distribution. Some units are shipped with more than one size nozzle for the distributor. Follow instructions in unit for selecting and installing the correct nozzle before expansion valve installation. Sweat the outlet of the valve to the inlet of the distributor, or on one circuit coils, to the coil inlet connection. Connect the external equalizer to the valve. Follow valve manufacturers instructions for protecting the valve from overheating during installation. Locate valve sensing bulb (at 4 or 8 o'clock position) on a horizontal length of suction line as close to the unit as possible. Make sure that there is full length contact between the bulb and the suction tubing. If there is a P-trap in the suction line, locate the bulb between the unit and the trap. NOTE: Install a 1/4 inch male flare access fitting in the suction line near the unit to use when taking superheat readings. See "Super Heat Adjustment" section of this manual for information on super-heat check and adjustment. Table 4: Expansion Valve -20 F. Suction Temp. and 100 F. Liquid Temp. Sporlan Valves R-22 R-507 (AZ50) R-402A (HP80) Minimum Maximum Mean Sporlan Minimum Maximum Mean Sporlan Minimum Maximum Mean Sporlan BTU BTU BTU Valve Type BTU BTU BTU Valve Type BTU BTU BTU Valve Type EBFVEAAZP EBFREAAZP EBFREAAZP EBFVEAZP EBFREAZP EBFREAZP EBFVEBZP EBFREBZP EBFREBZP EBFVECZP EBFRECZP EBFRECZP EBSRE71/2ZP R-404A (HP62) Minimum Maximum Mean Sporlan BTU BTU BTU Valve Type EBFREAAZP EBFREAZP EBFREBZP EBFRECZP Alco Valves R-22 R-404A (HP-62) R-402A (HP-80) Minimum Maximum Mean Alco Minimum Maximum Mean Alco Minimum Maximum Mean Alco BTU BTU BTU Valve Type BTU BTU BTU Valve Type BTU BTU BTU Valve Type HFES1/4HW HFES 1/8SW HFES 1/4LW HFES1/2HW HFES 1/4SW HFES 1/2LW HFES1HW HFES 1/2SW HFES 3/4LW HFES1 1/2HW HFES 1 SW HFES 1LW HFES 2HW HFES1 1/4 SW HFES 1 1/4LW HFES2 1/2HW HFES1 1/2 SW HFES1 1/2LW HFES 3HW HFES 2 SW HFES 2LW HFES3 1/2 SW HFES 4 LW45 R-507 (AZ50) Minimum Maximum Mean Alco BTU BTU BTU Valve Type HFES 1/8RW HFES 1/4RW HFES 1/2 RW HFES 1 RW HFES 1 1/4RW HFES 1 1/2RW HFES 2 RW HFES3 1/2RW45

7 Table 5: Expansion Valve 25 F Suction Temp. and 100 F Liquid Temp. Sporlan Valves R-22 R-134a R-401A (MP39, R-12) Minimum Maximum Mean Sporlan Minimum Maximum Mean Sporlan Minimum Maximum Mean Sporlan BTU BTU BTU Valve Type BTU BTU BTU Valve Type BTU BTU BTU Valve Type EBFVEAAC EBFFEAAC EBFFEAAC EBFVEAC EBFFEAC EBFFEAC EBFVEBC EBFFEBC EBFFEBC EBFVECC EBFFECC EBFFECC R-404A (HP62) R-507 (AZ50) R-402A (HP80) Minimum Maximum Mean Sporlan Minimum Maximum Mean Sporlan Minimum Maximum Mean Sporlan BTU BTU BTU Valve Type BTU BTU BTU Valve Type BTU BTU BTU Valve Type EBFREAAC EBFREAAC EBFREAAC EBFREAC EBFREAC EBFREAC EBFREBC EBFREBC EBFREBC EBFRECC EBFRECC EBFRECC Alco Valves R-22 R-134a R-404A (HP-62) Minimum Maximum Mean Alco Minimum Maximum Mean Alco Minimum Maximum Mean Alco BTU BTU BTU Valve Type BTU BTU BTU Valve Type BTU BTU BTU Valve Type HFES1/4HC HFES 1/4MC HFES 1/8SC HFES1/2HC HFES 1/2MC HFES 1/4SC HFES1HC HFES 3/4MC HFES 1/2SC HFES1 1/2HC HFES 1 MC HFES 1 SC HFES 2HC HFES1 1/2MC HFES1 1/4 SC HFES2 1/2HC HFES1 3/4MC HFES1 1/2 SC HFES 3HC HFES2 1/2MC HFES 2 SC HFES 4MC HFES3 1/2 SC R-507 (AZ50) R-401 (MP-39, R12) Minimum Maximum Mean Alco Minimum Maximum Mean Alco BTU BTU BTU Valve Type BTU BTU BTU Valve Type HFES 1/8RC HFES 1/4XC HFES 1/4RC HFES 1/2XC HFES 1/2 RC HFES 3/4 XC HFES 1 RC HFES 1 XC HFES 1 1/4RC HFES 1 1/2 XC HFES 1 1/2RC HFES 2 XC HFES 2 RC HFES 2 1/2 XC HFES 3 1/2RC HFES 4 1/2 XC 7

8 FACTORY WIRING STANDARD UNIT COOLERS Air, Hot Gas and Electric Defrost The following 3 diagrams show the standard factory (internal) wiring for Air, Hot Gas and Electric Defrost Air Defrost Diagram 1 Electric Defrost Diagram 3 (EFE Units) * Units may have more than one motor multiple motors are wired in parallel. Hot Gas Defrost Diagram 2 * Units may have more than one motor multiple motors are wired in parallel and multiple heaters are wired in parallel. Note: Fan delay thermostat is on low temperature units only. Diagram 4 (SDE Units) * Units may have more than one motor multiple motors are wired in parallel. 8 Note: Fan delay thermostat is on low temperature units only. * Units may have more than one motor multiple motors are wired in parallel and multiple heaters are wired in parallel.

9 TYPICAL FIELD WIRING SEQUENCE OF OPERATION General Information IMPORTANT: All wiring must be done in accordance with applicable codes and local ordinances. Refer to the unit cooler nameplate to determine the required ampacities of motor and heater circuits. NOTE: The wiring diagrams on Pages 9 to 13 are shown to provide visual support for the field wiring considerations and sequence of operations discussed below. They are generic relative to the high-side, showing only the defrost timer. Refer to Page 8 for details of internal unit cooler wiring. The basic sequence of operation for electric defrost is given on Page 11 all other electric defrost diagrams refer back to that sequence with the exceptions noted. Wiring Legend The following is a legend of the wiring symbols and designations used in diagrams 15 through 23. Field terminal block connection in Witt condensing unit. Field terminal-block connection Field wiring Bold dashed wiring shows alternate methods of terminating defrost pressure control in condensing unit or thermostat in unit cooler. TC1 Room thermostat LLS Liquid line solenoid PC Pressure control M2 Heater contactor M3 Fan motor contactor M4 Heater contactor R1 Lockout relay R2 Sequencing relay R3 Sequencing relay Air Defrost SDA and EFA units will require the connection of power to the fan motor circuit. Wiring Diagram 4 Time Termination is done by setting the fail-safe dial of the timer to the desired defrost duration. An air defrost system is wired so that the evaporator fans run continuously unless manually de-energized. Whenever the compressor stops, the room air (minimum +34 degrees) warms the coil to room temperature, melting the frost. It is essential that the frost completely melts and drains each time the compressor cycles off. If it does not, a partial air defrost results, and the residual water and slush re-freeze into ice during the next run cycle. Ice removal usually requires manual defrost methods. Adequate off-cycle (defrost) time is a function of system capacity. If the system is too small for the application, ice build-up will usually result. Use of an air defrost timer is sometimes successful on undersized systems in avoiding coil icing. A temporary loss of room temperature will occur during defrost. Optional timers are available to assist in air defrost application. 9

10 TYPICAL FIELD WIRING SEQUENCE OF OPERATION Hot Gas Defrost Re-Evap Type Wiring Diagram volt or volt units wired directly to timer. The termination solenoid in the timer will switch the timer back into the normal (refrigerating) position, opening the contact to timer terminal #3 (de-energizing the HGS); and closing the contact to terminal #4 (energizing the LLS and bringing power to one side of the unit cooler fan motors). Pressure Termination The pressure control (by others) will sense the completion of defrost (recommended set point is the refrigerant pressure equivalent to 45 F.) and close its contact, supplying power to terminal "X" on the timer. The balance of the termination sequence is identical to Temperature Termination above. Note: EFG units do not have a fan delay thermostat. Wire the M3 holding coil directly to N1. Normal Refrigeration The liquid line solenoid valve (LLS) receives power from terminal #4 of the defrost timer through the room thermostat. The thermostat will close on rise of room temperature, energizing the LLS, allowing refrigerant flow to the unit cooler. Pressure will build up in the low-side and the low pressure control (not shown) will close, starting the compressor. The room thermostat will open when it reaches its cut-out set point, breaking power to the LLS. The LLS will close, stopping refrigerant flow to the unit cooler. The system will pump down and the compressor will stop. Defrost The defrost timer will switch to the defrost position at the preset time. Timer contact to terminal #4 will open, breaking power to the LLS and the unit cooler fan motor(s). Timer contact to terminal #3 will close at the same time, supplying power to the hot gas solenoid valve (HGS), allowing hot gas to flow to the unit cooler. A normally open solenoid valve installed in the discharge line to the condenser (not shown) is typically wired in parallel with the HGS. NOTE: Both temperature and pressure terminations are shown in the same wiring diagram for the sake of brevity only one would actually be employed. The pressure control would be eliminated for temperature termination the field wire from terminal "X" on the unit cooler to terminal "X" on the timer would be eliminated for pressure termination. Temperature Termination The Defrost Termination thermostat installed in the unit cooler will sense the completion of defrost and close its contact X-N2, supplying power to terminal "X" on the timer. Systems with SDG Units will begin to refrigerate without the unit cooler fans running. This prevents water droplets and steam from blowing into the room. The fan delay thermostat installed in the unit cooler will sense when the coil re-freezes and will close contact B1-N1 energizing the fan motors. Thus normal refrigeration is resumed. NOTE: SDG unit fans on systems operating above +20 evaporator temperature may experience excessive delay restarting after defrost. The fan delay thermostat may be de-activated as follows. Move the B1 end of the B1-B2 jumper to N1 (Diagram 5). Wire the M3 contactor holding coil to N1 & 4 (rather than B1 & 4 as shown in Diagram 6). Systems with EFG units are not furnished with fan delay thermostats, so the fans start operating immediately upon termination. Wiring Diagram 6 Units Wired with Fan Contactor Note: EFG units do not have a fan delay thermostat. Wire the M3 holding coil directly to N1. 10

11 TYPICAL FIELD WIRING SEQUENCE OF OPERATION Electric Defrost Single Unit Cooler Systems Wiring Diagram 7 One volt unit wired directly to timer. the timer. The termination solenoid in the timer will switch the timer back into the normal (refrigerating) position, opening the contact to terminal #3 (de-energizing the defrost heater); and closing the contact to terminal #4 (energizing the LLS and bringing power to terminal #4 of the unit cooler fan motors). Caution: Coolers warmer than 32 F. are susceptible to partial air defrost resulting in ice build-up. Time termination may be required. SDE Units will begin to refrigerate without the unit cooler fans running. This prevents water droplets and steam from blowing into the room. The fan delay thermostat will sense when the coil re-freezes and will close contact B1-N1, energizing the fan motors. Thus normal refrigeration is resumed. Note: EFE units do not have a fan delay thermostat. Wire a jumper from B2 to N1. NOTE: SDE unit fans on systems operating above +20 evaporator temperature may experience excessive delay restarting after defrost. The fan delay thermostat may be de-activated as follows: Move the B1 end of the B1-B2 jumper to N1 (Diagram 7). Wire the M3 contactor holding coil to N1 & 4 (rather than B1 & 4 as shown in Diagram 8). Normal Refrigeration The liquid line solenoid valve (LLS) receives power from terminal #4 of the defrost timer through the room thermostat. The thermostat will close on rise of room temperature, energizing the LLS and allowing refrigerant flow to the unit cooler. Pressure will build up in the low-side and the low pressure control (not shown) will close, starting the compressor. Wiring Diagram 8 One or 460 volt unit wired with fan motor and defrost heater contactors. The room thermostat will open when it reaches its cut-out set point, breaking power to the LLS. The LLS will close, stopping refrigerant flow to the unit cooler. The system will pump down and the compressor will stop. Defrost The defrost timer will switch to the defrost position at the pre-set time. Timer contact to terminal #3 will close, supplying power to the normally closed Lock-Out Relay R-1. The holding coil of R1 (not shown) is to be wired in parallel with the compressor contactor holding coil. R-1 will thereby remain open as long as the compressor is running, preventing the heaters from operating at the same time as the compressor. This eliminates the need for oversized wiring to the condensing unit. R-1 can also represent a normally closed auxiliary contact in the compressor contactor. Timer contact to terminal #4 will open at the same time, breaking power to the LLS and the unit cooler fan motors. Refrigerant flow to the unit cooler will stop. The compressor will continue to run until the system pumps down on the low pressure control, stopping the compressor. Relay R1 will close at that time, energizing the defrost heaters to defrost the coil. Temperature Termination The Defrost Termination thermostat installed in the unit cooler will sense the completion of defrost and close its contact N1-X, supplying power to terminal "X" on Note: EFE units do not have a fan delay thermostat. Wire the M-3 holding coil directly to N1. Identical to Diagram 7 except: 1. Terminal #4 on the defrost timer will supply power to the holding coil of motor contactor M3 instead of supplying power directly to the fan motors. 2. Terminal #3 on the timer will supply power to the holding coil of heater contactor M2 instead of supplying power directly to the defrost heater. 11

12 TYPICAL FIELD WIRING SEQUENCE OF OPERATION Electric Defrost Dual Unit Cooler Systems (Without Sequencing Relays Wiring Diagram 9 Two units wired directly to timer. Wiring Diagram 10 Two or 460 volt units wired with fan motor and defrost heater contactors. Note: EFE units do not have a fan delay thermostat. Run wires from B2 on each unit cooler to N1 on Unit Cooler A. Note: EFE units do not have a fan delay thermostat. Wire the M3 holding coil directly to N1 on Unit Cooler A. Sequence of operation is the same as Wiring Diagram 7, except: Identical to Diagram 9 except that fan motor and defrost heater power is supplied through contactors M3 and M2 respectively. 1. Defrost termination thermostat contacts N1-X are wired in series both unit coolers must terminate to terminate the timer. 2. The fan delay thermostat in Unit B is not used the fan delay function for both units is controlled by the fan delay on Unit A. 12

13 TYPICAL FIELD WIRING SEQUENCE OF OPERATION Electric Defrost Dual Unit Cooler Systems (With Sequencing Relays) Wiring Diagram 11 Two or 460 volt units wired with fan motor and defrost heater contactors. Identical to Wiring Diagram 10 except that termination is accomplished through sequencing relays R2 and R3. The heaters of one unit can de-energize when the coil is clean while the other unit can continue defrost if required. This eliminated steaming of the unit that completed defrost first. Note that separate heater contactors (M2 & M4) are required for each unit cooler. Unit A will energize R2 when it terminates. R2 normally closed (N.C.) contact will open, de-energizing heater contactor M2. R2 normally open (N.O.) contact closes. The timer cannot terminate, however, until both (N.O.) R2 and R3 contacts close they are wired in series to timer terminal "X". Unit B continues defrost until termination temperature is reached. R3 will then energize its (N.C.) contact opens (de-energizing M4) and its (N.O.) contact closes (bringing power to timer terminal "X") which terminates defrost. Note: Medium temperature units do not have a fan delay thermostat. Wire the M3 holding coil directly to N1 on Unit Cooler A. 13

14 START-UP PROCEDURE System Check Before starting the refrigeration system, check the following items: 1. Make sure the system is wired as shown in the diagrams in the Installation Section of this bulletin or the diagram in the unit. 2. Make sure all electrical connections are tight. 3. Make sure all piping is done as described in the Installation Section of this bulletin and in accordance with good piping practice. 4. Make sure all fan set screws are tight. 5. Make sure that the service valves on the compressor and receiver are open. 6. Make sure the unit is mounted securely and level. Pour water into the drain pan to make sure that the drain pan and drain line drain completely. 7. Make sure that the drain line is adequately heated on freezer applications. 8. Properly evacuate the system. 9. Follow proper procedures for handling and start-up of systems using polyester based lubricants. 10. Record the refrigerant type, system charge and oil type in the blanks provided on the unit nameplate. Initial Start-up Check the following items after initial unit start-up: 1. After the initial start-up, the fans on low temperature electric and hot gas defrost units will not start until the coil temperature pulls down to about 30 F. The fans may cycle several times until the room temperature is pulled down. 2. Check the system for proper refrigerant charge and oil level. 3. Make sure that the expansion valve superheat is set correctly. See the "Superheat Adjustment" section below. 4. Make sure the drain line heater is functioning properly. 5. During initial start-up it is not unusual to have very heavy frost loads. It may be necessary to manually initiate defrost cycles as needed until the moisture level in the room is reduced. 6. Observe the first defrost cycle on electric and hot gas defrost units to make sure that all system components are functioning properly. Check the amp draw of the defrost heaters on electric defrost units to make sure that they are working. Also make sure that the defrost cycle is terminated by the termination thermostat and not by the "fail-safe" on the timer. Superheat Adjustment The superheat must be adjusted properly for efficient unit cooler operation and to protect the compressor from floodback. The superheat should be set at 10 F to 12 F. 1. Allow the system to operate until the refrigerated space temperature has been reduced to the design temperature. 2. Connect an accurate low pressure gauge to the access fitting installed in the suction line at the unit cooler outlet. Caution: The evaporator pressure reading must be taken at a point no more than five feet from the unit cooler. For this reason, it is not normally suitable to use the compressor suction service valve for this purpose. 3. Tape the sensor from an electronic thermometer to the suction line as close to the expansion valve bulb as possible. Insulate the sensor. 4. Take evaporator pressure and temperature readings with the system operating. Determine the superheat using a Pressure-Temperature Saturation Table for the refrigerant being used. The following example will illustrate the procedure. Given: Measured pressure = 43 PSIG Measured temperature= 35 F From a Saturation Table, the saturation temperature for R-22 at 43 PSIG is 20 F. Compare the saturated suction temperature from the table to the actual suction temperature on the thermometer. The difference is the superheat. 35 F - 20 F = 15 F superheat A superheat of 15 F is too high so the valve must be opened up. See the expansion valve manufacturers recommendations for the adjustment procedure. Always wait for 20 to 30 minutes after adjustment for the system to stabilize. Take new readings and readjust the valve as required. 14

15 Defrost Controls Electric Defrost Timer The standard timer is an Paragon or equal. If a different timer is used, make sure that it has a "fail safe" feature. This is a setting on the timer that will terminate the defrost cycle after a set period of time, if the defrost thermostat fails to do so. This feature assures that the unit will not stay in defrost for an extended period of time. However, it is important that the "fail-safe" not be set for a time period that is too short. If this is done, the defrost may be terminated by the "fail-safe" and not by the termination thermostat. This can result in incomplete defrost cycles. For most applications, a "fail-safe" setting of 40 minutes should be used. Normally two defrost periods per day are adequate but more may be required if humidity levels are high. Hot Gas Defrost (SDG & EFG) An SPDT thermostat is used, closing on rise at 70 F. with a 10 differential. It is clipped to a return bend near the exit point of the defrosting refrigerant. The factory location should not have to be changed in the field. Safety Thermostat This is a fixed setting (thermal-disk style) thermostat that is furnished on all electric defrost units. It is an open-on-rise control set to open at 90 F. It provides additional protection against overheating the unit cooler and room should the primary termination fail. Defrost Termination/Fan Delay Thermostat Electric Defrost (SDE) This is an SPDT fixed setting (thermal-disk type) thermostat. It is mounted to the coil endplate with two sheetmetal screws. It can be easily moved to other endplate locations to meet unusual frosting conditions. The thermostat closes from Red to Brn at 55 F on rise in temperature to provide termination. It closes from Red to Blk at 35 F on a fall in temperature to provide fan delay. Defrost Termination Thermostat This is a fixed setting (thermal-disk type) control. Electric Defrost (EFE) An SPST thermostat is used, closing on rise at 50 F. with a 20 differential. It is clipped to a return bend at the best average location. It can be readily moved to meet unusual frosting conditions. Fan Delay Thermostat This is a fixed setting (thermal-disk style) thermostat that is furnished on hot gas defrost SDG units. It is a SPST open-on-rise thermostat which opens at +40 and closes at +30,sensing return bend temperature near the beginning of a coil circuit. Fan Delay Medium Temperature SDE & SDG unit fans on systems operating above -20 evaporator temperature may experience excessive delay restarting after defrost. The fan delay thermostat may be de-activated per the instructions on pages 10 and 11. General Check unit at least once a month for proper defrosting. The amount and pattern of frosting can vary greatly. It is dependent on room temperature, product being stored, turnover of product, percentage of time door is open and the temperature and humidity conditions surrounding the room. It may be necessary to periodically change the number or duration of defrost cycles. Cleaning The unit should be shut down and cleaned per NSF regulations at least once every six months. MAINTENANCE Clean the fins with an UL Sanitation approved cleaning agent. The drain pan and the end panels should then be opened and cleaned. The end panels may be removed and totally immersed in water for cleaning if so desired. The fan deck must be cleaned in place. The fan guards may be removed or cleaned in place. The fan blades can be cleaned when the fan guards are removed, but care must be taken not to bend the blades as this may cause an out-of-balance condition. All internal metal surfaces of the unit should also be cleaned. CAUTION: Make sure all electrical power to the unit is turned off and locked out before proceeding. 15

16 Maintenance (cont.) Check-Up All components should be checked at least every six months for proper operation as follows: 1. Tighten all electrical connections. 2. Tighten fan set screws. 3. Check the system refrigerant charge and oil level. 4. Make sure the defrost controls are functioning properly. 5. Check the drain pan and drain line for proper drainage. 6. Check the drain line heaters for proper operation. Fan And Motor Replacement Model SD WARNING: Make sure all electrical power to unit is disconnected before replacing fans or motors. The fan and motor can be accessed for replacement thru the fan venturi. 1. Remove the fan guard by removing the four screws which hold it in place. 2. Remove the fan blade by loosening the set screw with an allen wrench. 3. Disconnect the motor by unplugging the motor wires from the wiring harness. 4. Remove the nuts from the studs on the shaft end of the motor. 5. Grasp the motor, slide it out of the mount, and remove it through the fan venturi. To replace the motor, reverse the above steps. Make sure that all star washers are replaced to insure proper grounding of the motor to the unit. Fan Delay Thermostat Hot as Defrost (SDG) This is an SPDT fixed setting (thermal-disk type) thermostat that is furnished on hot gas defrost units. Fan Delay Medium Temperature SDE & SDG unit fans on systems operating above +20 evaporator temperature may experience excessive delay restarting after defrost. The fan delay thermostat may be de-activated per the instructions on pages 10 and Fan And Motor Replacement Model EF WARNING: Make sure all electrical power to unit is disconnected before replacing fans or motors. 1. Disconnect the drain line from the drain pan, remove the screws opposite the hinges and lower the drain pan. 2. Disconnect the motor by unplugging the motor wires from the wiring harness. 3. Remove the fan blade using an allen wrench. 4. Remove the 4 nuts from the shaft end of the motor. 5. Grasp the motor and slide it out of the mount and remove. To replace the assembly, reverse the above steps. Defrost Heater Replacement (EFE Units) WARNING: Make sure all electrical power to unit is disconnected before replacing defrost heaters. 1. Disconnect the drain line from the drain pan, remove the screws and lower the drain pan. 2. Unplug the heater wires from the wiring harness. 3. Model EF Low Velocity Units Only Use pliers to remove the heater clips which hold the heaters in place. 4. Slide the heater out of the unit. Reverse the above steps to reinstall the replacement heater. Defrost Heater Replacement (SDE Units) WARNING: Make sure all electrical power to unit is turned off. A. Insertion Heaters 1. Remove both unit end covers. 2. Disconnect heater leads from terminal block. 3. Straighten ends of heater. 4. Pull heater out of unit. Bend if necessary to avoid obstructions. 5. From TXV end of unit, insert heater leads into holes and push heater through coil. NOTE: Replacement heaters for 3-6 fan units are coiled for shipment. This allows heater to be installed even if end of unit is close to an obstruction. See Drawing Locate heater so that the ends extend 4.75 inches (over the rubber end seals) into the end compartment. 7. Connect leads to terminal blocks, bend heaters just enough at endplate so end cover can be installed and tie leads so they cannot contact hot parts of heaters. 8. Reinstall both end covers. B. Bottom Heaters 1. Remove electrical end cover. 2. Disconnect heater leads from terminal block. 3. Use pliers to remove clips that hold the heater in place and remove the heater. 4. Pull heater out of unit. Bend if necessary to avoid obstructions. 5. Note bends in hold heater. This is done to insure NG contact between the heater and the drain pan. 6. If the new heater is coiled, straighten it by rolling it out on the floor. 7. Connect heater leads to terminal block. 8. Reinstall drain pan and cover.

17 TROUBLESHOOTING CHART Symptoms Possible Causes Corrective Action Fan(s) will not operate. 1. Main switch open. 1. Close switch. 2. Blown fuses. 2. Replace fuses. Check for short circuits or overload conditions. 3. Defective motor(s). 3. Replace motor(s). 4. Defective fan delay thermostat (SD only) 4. Replace defective component. or defective timer. 5. Unit in defrost cycle. 5. Wait for completion of cycle. 6. Fan delay thermostat (SDG only) not sensing 6. Make sure t'stat is properly positioned coil temperature. so it senses the coil return bend temperature. 7. Evaporator temperature approaching 30 F. 7. Eliminate for delay. Room temperature too high. 1. Room thermostat set too high. 1. Adjust thermostat. 2. Superheat too high. 2. Adjust thermal expansion valve. 3. System low on refrigerant. 3. Add refrigerant. 4. Coil iced-up. 4. Manually defrost coil. Check defrost controls for malfunction. Defrost heaters will not 1. Main switch open. 1. Close switch. operate. 2. Blown fuses. 2. Replace fuses. Check for short circuits or overload conditions. 3. Defective heater(s). 3. Replace heater(s). 4. Defective timer. 4. Replace timer. Coil not clearing frost during 1. Defective heater(s). 1. Replace heater(s). defrost cycle. 2. Not enough defrost cycles per day. 2. Adjust timer for more defrost cycles. 3. Defective defrost termination t'stat 3. Replace thermostat. 4. Defrost termination thermostat not sensing 4. Relocate thermostat. coil area that is not clearing. 5. Fail-safe on timer set too short. 5. Lengthen fail-safe time setting- do not exceed 40 minutes. Ice accumulating in drain 1. Defective heater. 1. Replace heater. pan. 2. Unit not pitched properly. 2. Check and adjust if necessary. 3. Drain plugged. 3. Clean drain. 4. Defective drain line heater. 4. Replace heater. Units stays in prolonged 1. Defective timer or thermostat. 1. Replace defective component. defost cycle. 2. Defrost termination thermostat not sensing 2. Make sure t'stat is positioned to sense coil temperature. coil return bend temperature (EFE, EFG, SDG) or end plate temperature (SDE). 3. Fail-safe on timer set too long. 3. Shorten fail-safe setting. 17

18 MODEL SD REPLACEMENT PARTS FAN MOTORS AND BLADES Unit Motor Data Fan Data Model Voltage HP RPM Part No. Part No. Bore 115V /16 All 230V 1/20 SP Models 460V V 1/20 PSC V 1/20 PSC ELECTRIC DEFROST MODELS 18 Unit Size or Model No. Heater Data Qty Watts Volts Part No. 1-Fan Fan Except models listed below: 119H, 139H, 085M, 105M M, 065L, 089L, 120L 3-Fan Except models listed below: 3 230H, 168M, 210M L, 180L 4-Fan Fan Fan All SDE Defrost Termination & Fan Delay T'stat Defrost Heater Safety ALL SDG Defrost Termination Thermostat Low & Med. Temp. Fan Delay Thermostat, 1-3 Fans SDG Fan Delay Thermostat, 4-6 Fans DRAIN PANS Consult Factory for 460V Specifications FAN GUARDS Unit Size or Model No. Part No. Blade Size Part No. 1-Fan Units " Wire Fan Units " Plastic Except models listed below: 119H, 139H, 085M, 105M MOTOR MOUNT 124M, 065L, 089L, 120L Unit Size Part No. 3-Fan Units All Units Except models listed below: 230H, 168M, 210M L, 180L 4-Fan Units Fan Units Fan Units Air &electric defrost only contact factory for hot gas pan part number. NUMBER OF FANS vs. MODEL NUMBER 1-Fan Units SDA 054H-074H SDA, SDE, SDG 038M-060M SDE, SDG 036L-052L 2-Fan Units SDA 090H-139H SDA, SDE, SDG 080M-124M SDE, SDG 055L-120L 3-Fan Units SDA 171H-230H SDA, SDE, SDG 125M-210M SDE, SDG 110L-180L 4-Fan Units SDA 270H SDA, SDE, SDG 214M-254M SDE, SDG 181L-215L 5-Fan Units SDA 330H SDA, SDE, SDG 255M-305M SDE, SDG 220L-240L 6-Fan Units SDA 410H SDA, SDE, SDG 325M-350M SDE 260L & 300L

19 MODEL EF REPLACEMENT PARTS FAN MOTORS AND BLADES Unit Motor Data Fan Blade Data Model Voltage HP RPM Part No. Part No. Bore 115V 1/ /16" All V 1/ Models 460V 1/ /20 PSC V /16" +EFA, EFE and EFG Model 075 only ELECTRIC DEFROST MODELS Unit Cooler Heater Data Part Size Quantity Watts Volts Number 1-Fan Units Fan Units Fan Units Fan Units Fan Units Fan Units All Defrost Termination Thermostat EFE Defrost Heater Safety All EFG Defrost Termination Thermostat NUMBER OF FANS vs. MODEL NUMBER 1-Fan Units EFA, EFE, EFG Fan Units EFA, EFE, EFG Fan Units EFA, EFE, EFG DRAIN PANS Unit Size Part No. 1 Fan Units Fan Units Fan Units Fan Units Fan Units Fan Units Fan Units EFA, EFE, EFG Fan Units EFA, EFE, EFG Fan Units EFA, EFE, EFG 340 FAN GUARDS Blade Size Part No. 10"

20 SERVICE NOTES WITT P.O. Box 580 Collierville, TN (901) Fax (901) MP3000

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

KTL Two-Way Low Profile Evaporators

KTL Two-Way Low Profile Evaporators PRODUCT DATA & INSTALLATION Bulletin K30--PDI-16 Part # 87830 PRODUCT SUPPORT web: k-rp.com/ktl email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: Two-Way Low Profile Evaporators High, Medium and Low

More information

KR Electrical Defrost Unit Coolers (PN E108318_E)

KR Electrical Defrost Unit Coolers (PN E108318_E) KR Series Electric Defrost Unit Coolers Operating and Installation Manual KR Electrical Defrost Unit Coolers (PN E108318_E) TABLE OF CONTENTS 1 LOCATION RECOMMENDATIONS... 2 2 UNIT MOUNTING... 2 3 DRAIN

More information

KR Series Air Defrost Unit Coolers Operating and Installation Manual

KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Air Defrost Unit Coolers (PN E108317_L) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT... 2 1.1 INSPECTION... 2 1.2 LOSS OF GAS HOLDING

More information

High Profile Evaporator

High Profile Evaporator PRODUCT DATA & INSTALLATION Bulletin K30-KHPA-PDI-5 Part # 1081585 PRODUCT SUPPORT web: k-rp.com/khp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: High Profile Evaporator High & Medium Temperature

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin K40-THERM-PDI-15 Part # 1069130 PRODUCT SUPPORT web: k-rp.com/ts email: mdcu-lgcu@k-rp.com

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin B40-THERM-PDI-14 1069132 ThermoSaver TM Hot Gas Defrost System For use on select

More information

TLV Low Velocity Evaporators

TLV Low Velocity Evaporators PRODUCT DATA & INSTALLATION Bulletin T30-TLV-PDI-27 Part # 1073478 PRODUCT SUPPORT web: t-rp.com/tlv email: evaps@t-rp.com call: 1-844-893-3222 x520 scan: TLV Low Velocity Evaporators High Temperature

More information

SM/SV-Space Master Unit Coolers (E R.0)

SM/SV-Space Master Unit Coolers (E R.0) SM/SV Series Space Master Unit Coolers Operating and Installation Manual SM/SV-Space Master Unit Coolers (E316008 R.0) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS OF GAS HOLDING

More information

PRODUCT. TWB Two-Way Air Defrost Unit Coolers PRODUCT DATA & INSTALLATION. High Temperature (35 o F / 1.7 o C or Higher) Applications

PRODUCT. TWB Two-Way Air Defrost Unit Coolers PRODUCT DATA & INSTALLATION. High Temperature (35 o F / 1.7 o C or Higher) Applications DATA & INSTALLATION Bulletin RPDI0 04385 KEEPRITE TWOWAY UNIT COOLER UNIT SERIES B = ND GENERATION BTUH CAPACITY @ o F TD (0Hz) e.g. 450 = 4500 @ 0 o F TD TYPE OF DEFROST A = AIR DEFROST (HIGH TEMP) ELECTRICAL

More information

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill of lading

More information

STC Series Twin Unit Coolers (E329630_A)

STC Series Twin Unit Coolers (E329630_A) STC Series Twin Unit Coolers Operating and Installation Manual STC Series Twin Unit Coolers (E329630_A) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS OF GAS HOLDING CHARGE 3 2 ASSEMBLY

More information

Super-Flo Low Profile Unit Cooler

Super-Flo Low Profile Unit Cooler Publication No. WT-SAX-0516A Low Profile Unit Cooler Small to Medium Walk-Ins Coolers and Freezer Applications Air Defrost 3,900 to 39,000 BTUH Electric Defrost 3,600 to 28,000 BTUH Hot Gas Defrost 3,600

More information

REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill of lading to insure all

More information

LOW PROFILE UNIT COOLER

LOW PROFILE UNIT COOLER Publication No. RU-AAX-0516A All-Temp LOW PROFILE UNIT COOLER Small to Medium Walk-Ins Coolers and Freezer Applications Air Defrost 3,900 to 39,000 BTUH Electric Defrost 3,600 to 28,000 BTUH Hot Gas Defrost

More information

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s) Electrical Problems Fuse(s) blow or circuit breaker trips Does the unit use circuit breakers or fuses? Fuse(s) Circuit breakers Are the fuses dual element time delay? Is the circuit breaker HACR rated?

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

LOW PROFILE UNIT COOLER

LOW PROFILE UNIT COOLER Publication No. RU-AAX-1215A All-Temp 2 B LOW PROFILE UNIT COOLER Air Defrost - 3,900 to 39,000 BTUH Electric Defrost - 3,600 to 28,000 BTUH Hot Gas Defrost - 3,600 to 28,000 BTUH Small to Medium Walk

More information

WIBR SERIES. Unit Coolers - Technical Catalog Hunt St - Pryor, OK Fax

WIBR SERIES. Unit Coolers - Technical Catalog Hunt St - Pryor, OK Fax WIBR SERIES Unit Coolers - Technical Catalog 4492 Hunt St - Pryor, OK 74361-918.825.7222 - Fax 800.264.5329 - www.century-refrigeration.com Features/Applications Century Refrigeration s WIBR Series Unit

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

BTL Two-Way Low Profile Evaporators

BTL Two-Way Low Profile Evaporators PRODUCT DATA & INSTALLATION Bulletin B30-BTL-PDI-3 1087832 Latest product updates and further information at w ww.ballyrefboxes.com BTL Two-Way Low Profile Evaporators High, Medium and Low Temperature

More information

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

INSTALLATION and OPERATION INSTRUCTIONS

INSTALLATION and OPERATION INSTRUCTIONS INSTALLATION and OPERATION INSTRUCTIONS SINGLE DOOR freezer MODEL NOS. FN FS Finished Stainless Steel Top Non-Finished Top FS FN IMPORTANT INFORMATION This manual has been prepared to assist you in the

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

A Series T 3. Unit Coolers - Technical Catalog. Product Benefits: Comdustrial TM Refrigeration. Adaptability- Durability- Serviceability-

A Series T 3. Unit Coolers - Technical Catalog. Product Benefits: Comdustrial TM Refrigeration. Adaptability- Durability- Serviceability- A Series Unit Coolers - Technical Catalog Product Benefits: T 3 $ Adaptability- Century systems go where others can t. Your Century system is engineered to meet your specific project application and job

More information

Unit Coolers. Installation and Operations Manual. Table of Contents. H-IM-UC November 2017 Part No

Unit Coolers. Installation and Operations Manual. Table of Contents. H-IM-UC November 2017 Part No Installation and Operations Manual H-IM-UC November 2017 Part No. 25008201 Replaces ugust 2012 Unit Coolers Table of Contents General Safety Information...2 Inspection...2 Warranty Statement...2 Placement...2

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

T-Series Air Conditioner T20 Model

T-Series Air Conditioner T20 Model INSTRUCTION MANUAL T-Series Air Conditioner T20 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH 233 CWA2 NOMENCLATURE BREAKDOWN 2-Pipe Heat/Cool with Electric Heat Multiposition Fan Coil Nominal

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

Installation & Service Manual

Installation & Service Manual Installation & Service Manual NMFG Shown NMF / NMFG SINGLE DECK FROZEN MEAT MERCHANDISERS Low Temperature Self Serve Display Cases This manual has been designed to be used in conjunction with the General

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

KTL Two-Way Low Profile Unit Coolers

KTL Two-Way Low Profile Unit Coolers PRODUCT DATA & INSTALLATION Bulletin K30-KTL-PDI-2 1087830 KTL Two-Way Low Profile Unit Coolers High, Medium and Low Temperature Applications -10 F (-23.3 C) and above Air or Electric Defrost Electrical

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

LOW PROFILE UNIT COOLER. Technical Guide. Models RLC Air Defrost ELC/EFC Electric Defrost GLC Hot Gas Defrost. CH-LOPTB May,

LOW PROFILE UNIT COOLER. Technical Guide. Models RLC Air Defrost ELC/EFC Electric Defrost GLC Hot Gas Defrost. CH-LOPTB May, CH-LOPTB May, 2008 Replaces CH-B-15B, March 2004y 2007 LOW PROFILE UNIT COOLER Technical Guide s RLC Air Defrost ELC/EFC Electric Defrost GLC Hot Gas Defrost www.chandlerref.com Table of Contents Nomenclature...2

More information

SM/SV Series Space Master Unit Coolers Operating and Installation Manual

SM/SV Series Space Master Unit Coolers Operating and Installation Manual SM/SV Series Space Master Unit Coolers Operating and Installation Manual SM/SV-Space Master Unit Coolers (E316008_G) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS OF GAS HOLDING

More information

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N PROAIR Air Conditioner CR43 Model INSTRUCTION MANUAL Rev. H P/N 10-1008-130 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N PROAIR Air Conditioner CR23 Model INSTRUCTION MANUAL Rev. D P/N 89112522 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N T-SERIES Air Conditioner T50 Model INSTRUCTION MANUAL Rev. F P/N 10-1008-203 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N PROAIR Air Conditioner CR29 Model INSTRUCTION MANUAL Rev. I P/N 89104461 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

Low Profile Unit Coolers

Low Profile Unit Coolers BN-LOPTB AUGUST 2018 Replaces BN-LOPTB APRIL 2018 Low Profile Unit Coolers Technical Guide s ADT LET/LLE HGT Table of Contents Nomenclature... 2 Features & Benefits... 3 Performance Data & Specifications...

More information

CWA4 Chilled & Hot Water Fan Coil

CWA4 Chilled & Hot Water Fan Coil CWA4 Chilled & Hot Water Fan Coil 4-Pipe Heat & Cool Fan Coil 24,000-60,000 BTUH 259 CWA4 NOMENCLATURE BREAKDOWN 4-Pipe Heat & Cool Multiposition Fan Coil Nominal BTUH 24=24,000 36=36,000 48=48,000 60=60,000

More information

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA OWNER S MANUAL Vintage Classic HEAT COOL models Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support 888-475-7443 Manufacturing High Quality, High Efficiency Heat Pump

More information

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH 318 MHNCCX NOMENCLATURE BREAKDOWN 4-Pipe Heat/Cool Ceiling Concealed Fan Coil MHNCCW- XX - XX Ceiling Concealed

More information

T-Series Air Conditioner T53 Model

T-Series Air Conditioner T53 Model INSTRUCTION MANUAL T-Series Air Conditioner T53 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

Low Profile Unit Coolers

Low Profile Unit Coolers CH-LOPTB MAR 2015 Replaces CH-LOPTB JAN 2015 Low Profile Unit Coolers Technical Guide s RLC Air Defrost ELC/EFC Electric Defrost GLC Hot Gas Defrost Table of Contents Nomenclature 2 Features & Benefits

More information

Installation and Operation Manual

Installation and Operation Manual series Installation and Operation Manual FGCEID GLASS DOOR REACH-IN This refrigerator conforms to the Commercial Refrigerator Manufacturers Association s Health and Sanitation Standard. series Page 2 INSTALLATION

More information

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T29 Model INSTRUCTION MANUAL Rev. I P/N 89104464 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE

More information

NFW, NCW, NFWG, NCWG, NFWE, NCWE

NFW, NCW, NFWG, NCWG, NFWE, NCWE Installation & Service Manual WIDE ISLAND FROZEN FOOD & ICE CREAM MERCHANDISERS Low Temperature Self Serve Display Cases This manual has been designed to be used in conjunction with the General (UL/NSF)

More information

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T43 Model INSTRUCTION MANUAL Rev. I P/N 10-1008-145 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING

More information

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED (491) SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU, K3EU & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes

More information

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS WALK-IN COOLERS SERIES LS-LP-LA-LV

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS WALK-IN COOLERS SERIES LS-LP-LA-LV INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS WALK-IN COOLERS SERIES LS-LP-LA-LV 1 CONTENTS SAETY CONSIDERATIONS............. 3 INTRODUCTION................... 3 INSTALLATION STEP 1 COMPLETE PRE-INSTALLATION

More information

Reach-In Refrigerators and Freezers Service Manual

Reach-In Refrigerators and Freezers Service Manual Reach-In Refrigerators and Freezers Service Manual Part No. 80-0899-3 Rev. A 11/96 Safety Notices As you work on the Reach-In, be sure to pay close attention to the safety notices in this manual. Disregarding

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

DT/DTX Series Unit Coolers (R0 E316013)

DT/DTX Series Unit Coolers (R0 E316013) DT/DTX Series Unit Coolers Operating and Installation Manual DT/DTX Series Unit Coolers (R0 E316013) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS OF GAS HOLDING CHARGE 3 2 ASSEMBLY

More information

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931)

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931) DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee 37091 Phone (931) 359-6211 1-800-251-8990 www.doleref.com PHO WATER DEFROST OPERATION & MAINTENANCE MANUAL June 2002 PHO WATER DEFROST Table

More information

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers Installation & Operations Manual for BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers 2 TABLE OF CONTENTS INTRODUCTION..... 4 STORE CONDITIONS........ 4 WARNING LABELS AND

More information

JUMBO ISLAND FROZEN FOOD/ICE CREAM/MEDIUM TEMP MERCHANDISERS Low, Medium and Dual Temperature Self Serve Display Cases

JUMBO ISLAND FROZEN FOOD/ICE CREAM/MEDIUM TEMP MERCHANDISERS Low, Medium and Dual Temperature Self Serve Display Cases Installation & Service Manual JUMBO ISLAND FROZEN FOOD/ICE CREAM/MEDIUM TEMP MERCHANDISERS Low, Medium and Dual Temperature Self Serve Display Cases This manual has been designed to be used in conjunction

More information

Drop-In Refrigeration System

Drop-In Refrigeration System Drop-In Refrigeration System Original Instructions Installation, Operation and Maintenance Manual This manual is updated as new information and models are released. Visit our website for the latest manual.

More information

Installation & Service Manual

Installation & Service Manual Installation & Service Manual NFJGCX, NCJGCX, NTJGCX, NFMJGCX, NFJGECX, NCJGECX GLASS FRONT JUMBO ISLAND FROZEN FOOD/ICE CREAM/ MEDIUM TEMP MERCHANDISERS Low, Medium and Dual Temperature Self Serve Display

More information

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N V-SERIES Air Conditioner VA08 Model INSTRUCTION MANUAL Rev. F P/N 90164959 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

R E D I C O N T R O L S

R E D I C O N T R O L S R E D I C O N T R O L S File Literature Number 1144-01-1 Installation Operation & Maintenance Manual CONTINUOUS REFRIGERANT DEHYDRATOR Model: CD-120 For use with Refrigerants R-11, R-123, R-12, R-22, R-134a

More information

Low Velocity Center Mount Unit Cooler. Technical Guide. Models LWA - Air Defrost LWE - Electric Defrost LWG - Hot Gas Defrost.

Low Velocity Center Mount Unit Cooler. Technical Guide. Models LWA - Air Defrost LWE - Electric Defrost LWG - Hot Gas Defrost. LK-LVTB May 2008 Replaces LW-03, February 2003 FPO Low Velocity Center Mount Unit Cooler Technical Guide s LWA - Air Defrost LWE - Electric Defrost LWG - Hot Gas Defrost www.larkinproducts.com Table of

More information

REFRIGERATION SYSTEMS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

REFRIGERATION SYSTEMS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS REFRIGERATION SYSTEMS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS INSTALLATION 2-7 Wall Mounted Systems 2-3 General Instructions 2-3 Freezer Models 100 and 150 or Cooler Model

More information

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the XSTREAM Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION INDEX Introduction....................................... 3 Checking Product Received.......................... 3 Standard Unit Features.............................. 3 Unit Dimensions...................................

More information

A/C-HEATER SYSTEM - MANUAL

A/C-HEATER SYSTEM - MANUAL A/C-HEATER SYSTEM - MANUAL 1986 Isuzu Trooper II 1986 A/C-HEATER SYSTEM Isuzu A/C-Heater Systems - Manual P UP, Trooper II * PLEASE READ THIS FIRST * CAUTION: When discharging air conditioning system,

More information

Center Mount Unit Coolers

Center Mount Unit Coolers CC-CMTB JULY 2017 Replaces CC-CMTB JULY 2016 Center Mount Unit Coolers Technical Guide s TLC Air Defrost TLF Electric Defrost Table of Contents Nomenclature...2 Features & Benefits...3 Performance Data...4

More information

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR INDUSTRIAL COOLERS

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR INDUSTRIAL COOLERS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR INDUSTRIAL COOLERS SERIES MPA, HPA SERIES MPE, HPE & JPE SERIES MPG, HPG & JPG SERIES MPH, HPH & JPH AIR DEFROST APPLICATION ELECTRIC DEFROST APPLICATION

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling

More information

Installation & Service Manual

Installation & Service Manual Installation & Service Manual NFJCX, NCJCX, NTJCX, JUMBO ISLAND FROZEN FOOD/ICE CREAM/MEDIUM TEMP MERCHANDISERS Low, Medium and Dual Temperature Self Serve Display Cases This manual has been designed to

More information

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA OWNER S MANUAL Models: AC110, AC125, AC150 made from 2003 through 2010 Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support/ (888) 475-7443 Manufacturing High Quality,

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

TEMPERATURE & PRESSURE CONTROLS

TEMPERATURE & PRESSURE CONTROLS TEMPERATURE & PRESSURE CONTROLS RANCO LUBE OIL PROTECTION CONTROLS These lube oil protection controls guard pressure-lubricated refrigeration compressors against major damage due to loss of oil pressure.

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL an ISO 9001:2008 Registered Company 18865 GOLL ST. - SAN ANTONIO, TX. - 78266 - ph.210-654-7171 - fax 210-654-3113 MINI SPACE SAVER HEAT /COOL 01000-QUX-A 01000-VUX-A 900101-VUX-A REV C 3/5/14, MINI SPACE

More information

COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST

COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST INSTALLATION, OPERATION & MAINTENANCE MANUAL CAH CEH CDH High profile unit coolers COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST Index 1. Warranty statement 2 2. General Safety Information 3 3. Inspection

More information

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the MYSTICOOL Max Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement. AHF / AHK SERIES AIR HANDLING UNITS INSTALLATION GUIDE GENERAL The AHF / AHK series is designed for horizontal recessed installations in a furred down area, above a suspended ceiling or recessed in the

More information

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6 INTRODUCTION This service manual covers the installation, operation, maintenance and service of this ice machine. Table of Contents SPECIFICATIONS Page 2 FOR THE INSTALLER Page 3 FOR THE PLUMBER Page 4

More information

Installation & Operations Manual. Master-Bilt Products 908 Highway 15 North New Albany, MS Phone: (800) REV: LN PN

Installation & Operations Manual. Master-Bilt Products 908 Highway 15 North New Albany, MS Phone: (800) REV: LN PN Installation & Operations Manual Master-Bilt Products 908 Highway 15 North New Albany, MS 38652 Phone: (800) 684-8988 REV: LN PN 297-90000 2 TABLE OF CONTENTS INTRODUCTION.. 4 STORE CONDITIONS..... 4 WARNING

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N GENESIS Air Conditioners All Models INSTRUCTION MANUAL Rev. K P/N 89104462 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with

More information

RDT Refrigeration Book

RDT Refrigeration Book RDT Refrigeration Book Indoor / Outdoor Air-Cooled Systems Indoor Air-Cooled Systems 1. Shorter line runs. 2. Systems located off roof or dock space. 3. Weather covers are not required (saves cost). 4.

More information

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS Technical Guide SPLIT-SYSTEM EVAPORATOR BLOWERS 7-1/2 and 10 NOMINAL TONS LA090 & LA120 DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes

More information

& MAINTENANCE INSTRUCTIONS INSTALLATION, OPERATION INDUSTRIAL COOLERS & FREEZERS WALK-IN COOLERS SERIES: EK, EM, EH, EI, EB, EF

& MAINTENANCE INSTRUCTIONS INSTALLATION, OPERATION INDUSTRIAL COOLERS & FREEZERS WALK-IN COOLERS SERIES: EK, EM, EH, EI, EB, EF INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS INDUSTRIAL COOLERS & REEZERS WALK-IN COOLERS SERIES: EK, EM, EH, EI, EB, E MODELS: EKA, EKE, EKR, EKT EKA, EKE, EKR, EKT K = Compact Profile EMA, EME,

More information

INSTALLATION and OPERATION INSTRUCTIONS

INSTALLATION and OPERATION INSTRUCTIONS INSTALLATION and OPERATION INSTRUCTIONS Single Door cooler series MODEL NOS. CS32SB CS32SG CS32SS CS32ST IMPORTANT INFORMATION To register your product, visit our web site at (www.perlick.com). Click on

More information