DRI-STEEM MODEL STS and STS- DI

Size: px
Start display at page:

Download "DRI-STEEM MODEL STS and STS- DI"

Transcription

1 DRI-STEEM MODEL STS and STS- DI STEAM-TO-STEAM HUMIDIFIERS Installation, Operation, For toll-free technical support call

2 TABLE OF CONTENTS To the purchaser and the installer and Maintenance Manual DRI-STEEM Humidifier Company General information Installation Operation Maintenance Notes Warranty

3 STS AND STS-DI HUMIDIFIER OVERVIEW Standard water models (STS) Automatic steam valve To steam supply Steam trap Condensate return Steam outlet Water seal Air gap Open drain Heat exchanger Manual drain or optional motorized drain valve OM-938 Deionized water models (STS-DI) Steam outlet Note: Float valve Automatic steam valve Heat exchanger Steam trap Manual drain valve Condensate return Water seal Air gap Open drain OM-939 Note:

4 STS AND STS-DI DIMENSIONS AND WEIGHTS STS and STS-DI, all sizes STS and STS-DI (single heat exchanger) sizes 25S, 25C, 50S, 50C, 100S, 100C, 200S, 400C, and 400SNC ¼" pipe thread (DN8) water makeup valve Side view Front view J K A* 5/16" (8 mm) diameter slotted mounting holes C OM-940a D E H B ¾" pipe thread (DN20) drain OM-940b Table 4-1: Humidifier weights Model number STS-25 Shipping weight lbs kg lbs Operating * w eight kg STS and STS-DI (dual heat exchanger) size 800C and 800SNC Front view ¼" pipe thread (DN8) water makeup valve STS-50 STS-100 STS-200 STS-400 STS-800 A* F G D J K E ½" (12 mm) diameter slotted mounting holes Note: H B ¾" pipe thread (DN20) drain OM-940c

5 STS AND STS-DI DIMENSIONS Table 5-1: Mechanical dimensions for STS and STS-DI units with copper heat exchanger(s) STS and STS-DI model numbers Description 25C 50C 100C 400C 800C inches mm inches mm inches mm inches mm inches mm A Overall height* B Face width C Face length D Distance from bottom to supply inlet E Distance from bottom to return outlet F G H J K Distance from bottom to supply inlet of second heat exchanger Distance from bottom to return outlet of second heat exchanger Distance from side to heat exchanger Pressurized steam supply inlet Pressurized steam return outlet Table note: Table 5-2: Mechanical dimensions for STS and STS-DI units with stainless steel heat exchanger(s) STS and STS-DI model numbers Description 25S 50S 100S 200S 400SNC 800SNC inches mm inches mm inches mm inches mm inches mm inches mm A Overall height* B Face width C Face length D Distance from bottom to supply inlet E Distance from bottom to return outlet F Distance from bottom to supply inlet of second heat exchanger G Distance from bottom to return outlet of second heat exchanger H Distance from side to heat exchanger J Pressurized inlet steam supply K Pressurized outlet steam return Table notes:

6 STS AND STS-DI CAPACITIES Table 6-1: Capacities for units with copper heat exchangers Output capacities with copper heat exchangers Model number psi kpa psi Steam pressure* kpa psi kpa psi kpa Table 6-2: Capacities for units with stainless steel heat exchangers O utputcapac ti ei s w tih sta ni el ss steelheatexchangers M odel num ber psi kpa psi Steam kpa pressure* psi kpa psi kpa Table 6-1 and 6-2 notes: Notes about heat exchangers and water type:

7 STS AND STS-DI LOCATION Locating the humidifier Figure 7-1: STS clearance recommendations Top: 18" (457 mm) Left side with control cabinet mounted: 36" (914 mm) Left side: 6" (152 mm) Rear: 6" (152 mm) Angle iron support leg Front: 36" (914 mm) Right side: 6" (152 mm) Bottom: 24" (610 mm) DC-1452

8 STS AND STS-DI MOUNTING IMPORTANT: Mounting methods Support legs (STS/STS-DI models 25, 50, 100 only) Trapeze hanger (STS/STS-DI models 25, 50, 100 only) H-legs (STS and STS-DI models 200, 400, 800 only) Wall brackets (STS/STS-DI models 25, 50, 100 only) A STS m odel 25C 25S 50C 50S 100C 100S ni ches A m m ni ch se 15½ B m m DRI-STEEM optional brackets (two required) B DC-1454

9 STS AND STS-DI PIPING Drain piping To allow normal operation and prevent steam from escaping through the drain line, the installer must provide a water seal of a sufficient height to contain the pressure developed in the humidifier system. Figure 9-1: Field piping overview Water supply shut-off valve, by installer Shock arrester recommended to eliminate water hammer, by installer ¾" pipe thread (DN20) dispersion unit condensate return inlet ¼" (DN8) water supply line; water pressure range 25 psi to 80 psi (172 kpa to 582 kpa); water conductivity minimum 2 grains/gallon (100 μs/cm) Steam vapor outlet Install level Condensate return piping from dispersion unit Air vent tube 6" (152 mm) minimum H2: Air vent height must be equal to or greater than H2 (see table on next page). Unions, by installer Vacuum breaker, by installer Strainer From steam source Condensate return to nonpressurized system, by gravity only ¾" (DN20) minimum condensate drain piping rated for 212 F (100 C) Trap 12" (305 mm) minimum drop to trap H1 Skim and overflow piping (see table on next page) Pitch 1 /8"/ft (1%) Install level Manual or electric drain valve If run is over 10' (3 m), increase pipe to 1¼" (DN32). Overflow line Water seal line Water seal line MUST be below drain valve to ensure humidifier drains correctly. 1" (25 mm) air gap Open floor drain. Refer to local governing codes for drain pipe size and maximum temperature requirements. DC-1451

10 STS AND STS-DI PIPING Drain piping, continued STS humidifier STS-DI humidifier Alternate water seal and drain valve piping Drain connection Open drain Skimmer outlet Air gap Dashed lines indicate provided by installer Top of water seal must be below skimmer outlet H1 (see table below) OM-945 Use when water seal must be elevated above flow line of drain connection, such as when the humidifier is mounted near the floor. Table 10-1: H1 and H2: Heights required to overcome humidifier internal pressure Unit output Water seal height (H1) All STS models STS models 25C, 25S, 50C, 50S, 100C, 100S, 200S, 400C Air vent height (H2) STS model 800C lbs/hr kg/h inches mm inches mm inches mm up to to to and greater

11 STS AND STS-DI PIPING Note: Water supply piping STS model STS-DI model VAPORLOGIC 3 Installation and Operation Manual

12 STS AND STS-DI PIPING Steam supply piping Note for STS-800 models: Figure 12-1: Steam supply piping Steam main Steam trap, required for proper operation (by DRI-STEEM ) Alternate vacuum breaker position 12" 12" Vacuum breaker (by installer) OM-941 End of branch trap (by installer) Swing check valves (by installer) Gravity condensate return

13 STS AND STS-DI WIRING Caution: Only qualified electrical personnel should perform installation procedures. Electrical wiring diagrams provided with humidifier and control cabinet Electrical installation Wiring requirements CAUTION:

14 STS AND STS-DI WIRING CAUTION: Control wiring Grounding requirements Figure 14-1: Humidifiers with LW417 To humidifier probe head on tank Brown, top probe rod (full water condition) Orange, middle probe rod (refill water condition) Violet, bottom probe rod (low water condition ) V O BR OM-829a Figure 14-2: Humidifiers with VAPOR-LOGIC 3 Brown or black, top probe rod (full water condition) Orange or white, middle probe rod (refill water condition) Violet or red, bottom probe rod (low water condition on standard water models) Probe wiring OM-VL3-11 IMPORTANT:

15 STS AND STS-DI STEAM DISPERSION INSTALLATION STS dispersion tube installation with condensate drain Vapor hose Hard piping Tube mounting Minimum condensate drain line sizing Figure 15-1: Single tube and escutcheon plates 2.5" (64 mm) 1.5" (38 mm) (83 mm) 3.25" 3.25" 3.25" (83 mm) 3.25" (83 mm) (83 mm) ¼" pipe thread (DN8) end Premolded high temperature resin steam inserts Mounting nut, 3 /8" (M10) ½" (DN15) O.D. copper tubing (condensate drain) Movable escutcheon plate (plate can be mounted within limits of 2.5" [64 mm]) OM-351a Figure 15-2: Single tube with condensate wasted to floor Vapor hose, tubing, or pipe 90% long sweep or two 45 elbows STS humidifier 5" (127 mm) water seal 1" (25 mm) air gap Pitch* 6" (152 mm) minimum Duct ¼" pipe thread (DN8) Condensate drain tube, by installer (¾" [DN20] minimum)** Open drain Single dispersion tube with condensate drain Mounting nut, 3 /8" (M10) Pitch tube toward drain 1/8"/ft (1%) ½" (DN15) O.D. condensate drain tube, pitch ¼"/ft (2%) DC-1473a continued...

16 STS AND STS-DI STEAM DISPERSION INSTALLATION STS dispersion tube installation with condensate drain, continued Figure 16-1: Multiple tube with condensate returned to humidifier Vapor hose, tubing, or pipe Duct Single dispersion tube with condensate drain Mounting nut, 3 /8" (M10) 90% long sweep or two 45 elbows Pitch* ½" (13 mm) air vent 6" (152 mm) minimum 6" (152 mm) minimum ¼" pipe thread (DN8) 5" (127 mm) water seal Pitch tube toward drain 1 /8"/ft (1%) ½" (DN15) O.D. condensate drain tube, pitch ¼"/ft (2%) STS humidifier ¾" (DN20) condensate return connection (on face plate) H2 (see table, Page 10) DC-1473b Condensate drain tube, by installer (¾" [DN20] minimum)** Figure 16-2: Multiple tube with condensate wasted to floor Duct Multiple dispersion tube Vapor hose, tubing, or pipe 90 long sweep or two 45 elbows STS humidifier Pitch* Water seal 5" (127 mm) 1" (25 mm) air gap 6" (152 mm) ¼" pipe thread (DN8) Open drain Pitch tube toward drain 1/8"/ft (1%) ½" (DN15) O.D. condensate drain tube, pitch ¼"/ft (2%) Condensate drain tube provided by installer, ¾" (DN20) minimum Mounting nut, 3 /8" (M10) DC-1048a Notes: 1. Dashed lines indicate provided by installer. 2. Review drawings and tables on all pages of this document.

17 STS AND STS-DI STEAM DISPERSION INSTALLATION Selecting the location Overhead installation Figure 17-1: Overhead installation Secure rods to overhead construction Provide 18" (457 mm) minimum clearance above cover Threaded rod 3/8" (M10) diameter Angle or channel sized to properly support humidifier Humidifier drain to appropriate building waste. Do not drain humidifier directly into drip pan. 1¼" (DN32) minimum 25% larger than humidifier Drip pan recommended in overhead installations (by installer) to DC-1453 prevent possible water damage

18 RAPID-SORB LOCATION Horizontal duct installation Before you start Locating the RAPID-SORB IMPORTANT: Note: Pitch Figure 18-1: RAPID-SORB installed in a horizontal airflow with header outside the duct 90 long sweep or two 45 elbows Vapor hose, tubing, or pipe 90 long sweep or two 45 elbows Vapor hose, tubing, or pipe L-bracket Dispersion tube Tubelets (steam orifices) Slip coupling or hose cuff Pitch: 1 /8"/ft (1%) STS humidifier Header ¾" pipe thread (DN20) condensate drain ¾" (DN20) copper 1" (25 mm) air gap Open drain Duct Airflow Support bracket 5" (127 mm) DC-1471 Figure 18-2: RAPID-SORB installed in a horizontal airflow with header inside the duct L-bracket Dispersion tube Tubelets (steam orifices) Slip coupling or hose cuff Pitch: 1 /8"/ft (1%) STS humidifier Header ¾" pipe thread (DN20) condensate drain ¾" (DN20) copper 1" (25 mm) air gap Open drain DC " (152 mm) Airflow Duct Support bracket 6" (152 mm) 5" (127 mm)

19 RAPID-SORB PIPING IMPORTANT: FAILURE to follow the recommendations on these pages and all enclosed documents can result in excessive back pressures on the humidification system. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from dispersion tube. When using vapor hose When using tube or pipe Figure 19-1: Drip tee installation (piping over obstruction) 90 long sweep or two 45 elbows Pitch* Dashed lines indicate provided by installer. Obstruction Insulate tubing and hard pipe to reduce steam loss STS humidifier To dispersion device 6" (150 mm) minimum Tubing or pipe drip tee, by installer 8" (200 mm) minimum ¾" (DN20) 1" (25 mm) air gap Funnel or floor drain DC-1470

20 RAPID-SORB PIPING Table 20-1: Steam loss of interconnecting vapor hose, tubing, and pipe Description Hose Tubing Pipe Nominal hose, tubing or pipe size inches DN Noninsulated lbs/hr/ft kg/h/ m Steam loss lbs/hr/ft Insulated kg/h/ m Insulation thickness inches Note: mm Table 20-2: Maximum steam carrying capacity and length of interconnecting vapor hose, tubing, and pipe* V aporhose C opperorsta ni el ss steeltub ni g and Schedu el 40 steelp pi e H ose D.I. M ax mi um capac tiy M ax mi um el ngth** Tube or p pi e s zi e*** M ax mi um capac tiy M ax mi um eve ol ped el ngth d ni ches D N bl s h/ r kg/ h ft m ni ches Notes: D N bl s h/ r kg/ h ft m

21 RAPID-SORB ASSEMBLY AND INSTALLATION Header outside the duct To assemble

22 RAPID-SORB ASSEMBLY AND INSTALLATION Header inside the duct To assemble

23 RAPID-SORB ASSEMBLY AND INSTALLATION Steam supply connections to RAPID-SORB header Condensate drain connections to RAPID-SORB header

24 STS AND STS-DI START-UP PROCEDURE Introduction Start-up and checkout procedures CAUTION: Only qualified electrical personnel should perform the start-up procedure. VAPOR-LOGIC Installation and Operation 3 Manual VAPOR-LOGIC Installation and Operation 3 Manual VAPOR-LOGIC 3 Installation and Operation Manual.

25 STS AND STS-DI START-UP PROCEDURE LW417 electronic water level control module (for standard water units only) Water refill Low water condition Electronic probe control for maintaining proper water level IMPORTANT: Timer logic input wire (see diagram on next page) must be connected per wiring diagram for proper automatic drain and flush and end-of-season drain operation. The Power light s blinking off twice at one-second intervals indicates that these functions have been disabled. Verify wiring with diagram supplied with unit. A Fill valve off B Fill valve on C Low water OM-211-2

26 STS AND STS-DI START-UP PROCEDURE Automatic drain and flush End-of-season drain Onboard diagnostics Test cycling the drain/flush system Failure to do so will result in a drain/flush cycle every 2 minutes IMPORTANT: Timer logic input wire (see diagram below) must be connected per wiring diagram for proper automatic drain and flush and end-ofseason drain operation. The Power light s blinking off twice at one-second intervals indicates that these functions have been disabled. Verify wiring with diagram supplied with unit. Figure 26-1: LW417 circuit board Bottom water probe input (violet) Middle water probe input (orange) Top water probe input (brown) Ready water output (blue) Fill valve output (tan) Timer logic input (red) Drain valve output (gray) 24 VAC common input (white) 24 VAC hot input (black) Ready water light Full light Variable skim times Ground mounting holes, 3 / 16 " diameter Power light Drain light Slide switch settings OM-918

27 STS AND STS-DI OPERATION AND MAINTENANCE INFORMATION STS water quality recommendations Water quality makes a difference Note: Adjusting skim duration STS-DI water requirements

28 STS OPERATION AND MAINTENANCE INFORMATION Standard water unit maintenance Cool down Standard drain valve: Alternative method with VAPOR-LOGIC option VAPOR-LOGIC 3 Installation and Operation Manual Manual Drain Auto Manual Drain Safety IMPORTANT: Standby OFF OFF Inspection Annual (also recommended when maintenance is performed) continued...

29 STS OPERATION AND MAINTENANCE INFORMATION Standard water unit maintenance, continued Seasonal (or as required, depending on water quality) Cleaning tank Cleaning the probes Cleaning skim overflow port -season maintenance

30 STS -DI MAINTENANCE INFORMATION Deionized water unit maintenance Cool down Standard drain valve: End-of-season drain option (VAPOR-LOGIC 3 only): VAPOR-LOGIC 3 Installation and Operation Manual Manual Drain Auto Manual Drain Safety IMPORTANT: Standby OFF OFF Inspection Annual (also recommended when maintenance is performed) -season maintenance On units with Teflon coated heat exchangers, do not use a sharp object when cleaning.

31 STS AND STS-DI TROUBLESHOOTING GUIDE Sym ptom Poss bi el cause R ecom m ended actoi n H um di fi ei rw lli notheat No control transformer output Verify control voltage. Set humidistat to call. Humidistat is not calling Inspect for faulty humidistat. Safety controls open (high limit, air proving, etc.) Check safety controls. Faulty control board S ee VAPOR-LOGIC o LW417 troubleshooting guide. 3 r Probe corrosion Replace probes.* Steam stop valve closed Verify valve is opened. Steam trap plugged Clean trap body. Low or no steam Verify steam is present. Steam strainer plugged Clean strainer. H um di fi ei rw lli notf lli No water pressure Verify manual water supply valve (172 kpa) supply pressure. is open, minimum 25 psi Faulty water fill valve Verify action of fill solenoid valve; verify contol voltage present at coil. Audible click should be heard as solenoid operates. Plugged water strainer Clean strainer. Plugged valve Clean valve. Faulty control board Verify control voltage. H um di f nilli g fi ei rdoes notstop Lack of tank-to-probes continuity Jumper wires violet, orange, and then brown to ground. If water stops, verify tank ground. Water conductivity less than 100 micromhos/cm minimum (2 grains per gallon) Check water supply conductivity; then consult factory. Manual drain not fully closed Close manual ball valve. Fill valve stuck open Check valve for foreign matter. Fill valve installed backward Check for correct water flow through valve; note arrow. Low output Automatic drain valve not seating Clean ball and seat of valve. Manual drain not fully closed Close manual ball valve. Excessive skimming amount Reduce skim time. Fill valve stuck open Check valve backward. for foreign matter. Check if valve installed Low supply steam pressure Check steam supply pressure. specified on unit. Provide steam pressure as Steam valve inoperable Valve not opening fully. Check signal to valve. Steam trap blocked. Trap not passing condensate. Scale coated heat exchanger Clean heat exchanger.

32 LW417* TROUBLESHOOTING GUIDE Sym ptom M odu el Fu ll ni d ci atni g R eady w ater gil hts D ra ni Poss bi el cause R ecom m ended actoi n H um di heat fi ei rw lli not C ontrol transforme r Verify control voltage across secondary leads of transformer. Reset transformer circuit breaker. On On H umidistat is not calling Set humidstat to call. Inspect for faulty humidistat or wiring. S afety controls open Check safety controls, airflow switch, high limit humidistat, etc. Ready Water indicator off but enough water in tank F aulty control board Verify control voltage between input terminals B & W. O ff Not enough water in tank; water supply closed Low water conductivity Open water valve. If water in tank, minimum). add salt (100μS/cm [2 grains/gallon] Probe corrosion Wiring or module Clean water probe tips.** Connect jumper wire from violet to white indicator remains off, replace module. wire. If Ready Water Blinking green LED power light (on 1 sec., off 1 sec.) H um f lli di fi ei rw lli not H um di fi ei rdoes not stop f nilli g Low output U n ti shortcyc el s On On On On On & On On On On Water detection wire System detected faulty probe rod assembly Faulty full relay on LW417 board Wiring System in end-of-seaso n drain mode Check that tank has common water with 24 VAC common white wire. Clean or replace probe rod. detection wire to ground Unplug probe plug from humidifier probe head. Fill LED light should be off. Check for 24 VAC across fill valve coil. If not present, FULL relay is defective. Replace module. Ensure that Fill valve is wired to drain valve output. Water detection probe wiring is correct. Wiring distance between humidifier tank and water level control is not greater than 30 feet (9 m). Create a call for humidity to reset the system and energize fill valve. A utodrain mode Ten minutes must complete first. Faulty fill valve relay in LW417 Control module wiring Faulty control logic from LW417 O ff Faulty Ready Water detection Controls and safeties No call from humidistat or duct high limit humidistat Airflow proving switch miswired or is defective. Probes incorrectly wired or need cleaning If Full LED light on control module is on energized, module is defective. Replace. Check wires diagram. and fill valve is for proper connections to control module; see Ensure wiring distance between humidifier tank level control is not greater than 30 feet (9 m). If Full LED light on control module module is defective. Replace. and water is off and tank is full, Install jumper wire between violet and white wire leads, which should activate Ready Water LED light and relay. If not activated, module is defective. Replace. Ensure wiring distance bewteen humidifier tank and water level control is not greater than 30 feet (9 m). Do not used shielded (screened) cable when wiring water detection probe system between humidifier and controller; use 2 18-gauge (1 mm ) individual stranded wire. Replace airflow proving switch. Confirm that unit is wired per diagram. Clean probe rod tips with steel wool. VAPOR-LOGIC 3 Installation and Operation Manual

33 STS AND STS-DI TANK REPLACEMENT PARTS Figure 33-1: Tank replacement parts OM-946

34 STS AND STS-DI TANK REPLACEMENT PARTS LIST Table 34-1: Tank replacement parts list Note: Components may be in different location or orientation than shown in drawing on previous page. No. Description Part number

35 STS AND STS-DI CONTROL CABINET Figure 35-1: Control cabinet replacement parts Note: Components may be in different location or orientation than shown in drawing. OM-949 No. Descrpi toi n Partnum ber 1 Control cabinet, 12 x Subpanel, STS C ontrol board, VAPOR-LOGI C 3 Control board, LW Transformer, 120V to 24V Terminal block Ground termina l Terminal jumper AREA-TYP E time delay relay /016/018 9 DIN-rail end cap Terminal spacer DIN-rail, 6.5" (165 mm) Ground lug P-E switch Interlock switch Interlock switch bracket VAPOR-LOGI C keypad VAPOR-LOGI C keypad cable, 5' (1.5 m) * Specify humidifier model and serial numbers when ordering.

36 STS AND STS-DI MAINTENANCE SERVICE RECORD Date inspected Personnel Observation Action performed

37 STS AND STS-DI MAINTENANCE SERVICE RECORD Date inspected Personnel Observation Action performed

38 NOTES

39 NOTES

40 TWO-YEAR LIMITED WARRANTY Corporate Headquarters Europe ice Continuous product improvement is a policy of DRI-STEEM Humidifier Company; therefore, product features and specifications are subject to change without notice. Form No. STS-C-0103-M DRI-STEEM Humidifier Company Part No Rev A

LTS Liquid-to-Steam Humidifier. Installation, Operation and Maintenance Manual

LTS Liquid-to-Steam Humidifier. Installation, Operation and Maintenance Manual LTS Liquid-to-Steam Humidifier Installation, Operation and Maintenance Manual Overview LTS models....3 Dimensions....4 Output capacities....6 Weights, connections and heated water properties.... 7 Installation

More information

STS Steam-to-Steam Humidifier

STS Steam-to-Steam Humidifier IMPORTANT: Read and save these instructions. STS Steam-to-Steam Humidifier Installation, Operation, and Maintenance Manual Warnings and cautions WARNING Indicates a hazardous situation that could result

More information

DRI-STEEM Models and LTS-DI

DRI-STEEM Models and LTS-DI READ AND SAVE THESE INSTRUCTIONS DRI-STEEM Models LTS and LTS-DI LIQUID-TO-STEAM HUMIDIFIERS Installation Instructions and Maintenance Operations Manual For Toll-Free Technical Support, Call: 1-800-328-4447

More information

DRI-STEEM Models LTS and LTS-DI

DRI-STEEM Models LTS and LTS-DI READ AND SAVE THESE INSTRUCTIONS DRI-STEEM Models LTS and LTS-DI LIQUID-TO-STEAM HUMIDIFIERS Installation Instructions and Maintenance Operations Manual For Toll-Free Technical Support, Call: 1-800-328-4447

More information

CRUV. Electric Humidifier. Installation, Operation, and Maintenance Manual

CRUV. Electric Humidifier. Installation, Operation, and Maintenance Manual CRUV Electric Humidifier Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical support 800-328-4447

More information

DRI-STEEM CRU SERIES ELECTRIC STEAM HUMIDIFIERS

DRI-STEEM CRU SERIES ELECTRIC STEAM HUMIDIFIERS READ AND SAVE THESE INSTRUCTIONS DRI-STEEM CRU SERIES ELECTRIC STEAM HUMIDIFIERS Installation Instructions and Maintenance Operations Manual For Toll-Free Customer Support, Call: 1-800-328-4447 UL RECOGNIZED

More information

VAPORSTREAM Models VLC and VLDI

VAPORSTREAM Models VLC and VLDI READ AND SAVE THESE INSTRUCTIONS VAPORSTREAM Models VLC and VLDI ELECTRIC STEAM HUMIDIFIERS Installation Instructions and Maintenance Operations Manual For Toll-Free Customer Support, Call 1-800-328-4447

More information

Vapormist Electric Humidifier. Installation, Operation and Maintenance Manual

Vapormist Electric Humidifier. Installation, Operation and Maintenance Manual Vapormist Electric Humidifier Installation, Operation and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical support 800-328-4447

More information

READ AND SAVE THESE INSTRUCTIONS STS. Steam-to-Steam Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS STS. Steam-to-Steam Humidifier. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS STS Steam-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNINGS AND CAUTIONS Warnings and cautions WARNING Indicates a hazardous situation that could

More information

Vaporstream Electric Humidifier. Installation, Operation, and Maintenance Manual

Vaporstream Electric Humidifier. Installation, Operation, and Maintenance Manual Vaporstream Electric Humidifier Installation, Operation, and Maintenance Manual Warnings and cautions WARNING Indicates a hazardous situation that could result in death or serious injury if instructions

More information

Vaporstream Electric Humidifier. Installation, Operation and Maintenance Manual

Vaporstream Electric Humidifier. Installation, Operation and Maintenance Manual Vaporstream Electric Humidifier Installation, Operation and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical support 800-328-4447

More information

XT Series Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

XT Series Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing humidifier. Leave manual with product owner. DRI-STEEM technical

More information

Steam Humidifier Models 1150 and 1160

Steam Humidifier Models 1150 and 1160 Humidifier Steam Humidifier Models 1150 and 1160 Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS PRODUCT OVERVIEW.............................. 3 Materials

More information

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access Interoperability via Modbus or optional BACnet or LonTalk

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access Interoperability via Modbus or optional BACnet or LonTalk VAPORSTREAM Electric-to-Steam Humidifier With Vapor-logic controller Web-enabled access Interoperability via Modbus or optional BACnet or LonTalk High-performance humidification APPLICATION VERSATILITY

More information

READ AND SAVE THESE INSTRUCTIONS HUMIDI-TECH. Electric Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS HUMIDI-TECH. Electric Humidifier. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS HUMIDI-TECH Electric Humidifier Installation, Operation, and Maintenance Manual WARNINGS AND CAUTIONS Warnings and cautions WARNING Indicates a hazardous situation that

More information

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS XT SERIES Electrode Steam Humidifiers Installation, Operation, and Maintenance Manual Warnings and cautions WARNINGS AND CAUTIONS WARNING Indicates a hazardous situation

More information

Ultra-sorb Models LV and LH

Ultra-sorb Models LV and LH Ultra-sorb Models LV and LH Steam Dispersion Panels Installation, Operation, and Maintenance Manual For applications using steam from a boiler or from any DRI-STEEM steam generating humidifier. Overview

More information

READ AND SAVE THESE INSTRUCTIONS VAPORMIST. Electric-to-Steam Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS VAPORMIST. Electric-to-Steam Humidifier. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS VAPORMIST Electric-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNINGS AND CAUTIONS Warnings and cautions WARNING Indicates a hazardous situation

More information

ES Series Electric Humidifier

ES Series Electric Humidifier Read and Save These Instructions Standard Water ES Series Electric Humidifier Installation Instructions Operation and Maintenance Manual ETL LISTED HUMIDIFIER Our results are comforting Form No: ESOM-08-08

More information

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual XTR Electrode Steam Humidifier Installation, Operation, and Maintenance Manual Safety precautions ATTENTION INSTALLER Read this manual before installing humidifier. Leave manual with product owner. DRI-STEEM

More information

DRI-STEEM Models GTS and GTS-DI

DRI-STEEM Models GTS and GTS-DI READ AND SAVE THESE INSTRUCTIONS This manual must be left with the owner and should be accessible for reference. DRI-STEEM Models GTS and GTS-DI TM GAS-TO-STEAM HUMIDIFIERS TM User's/Installation Instructions

More information

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers.

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers. Issued 2006/08/01 Section 15751 Humidifiers Page 1 of 7 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section 01810 Commissioning..4 Section

More information

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option XT SERIES Electrode Steam Humidifiers Easy to maintain Adaptable Comprehensive control with Vapor-logic option Cost-effective steam humidification XT Series electrode steam humidifiers from DriSteem provide

More information

READ AND SAVE THESE INSTRUCTIONS XTR. Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS XTR. Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS XTR Electrode Steam Humidifier Installation, Operation, and Maintenance Manual Warnings and cautions WARNINGS AND CAUTIONS WARNING Indicates a hazardous situation that

More information

Steam Injection Humidifiers for use with steam boilers. Installation, Operation, and Maintenance Manual

Steam Injection Humidifiers for use with steam boilers. Installation, Operation, and Maintenance Manual Steam Injection Humidifiers for use with steam boilers Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. Where to

More information

"ER" Series Electric Humidifier

ER Series Electric Humidifier ER-1 Standard Water "ER" Series Electric Humidifier The Electric Humidifier from PURE Humidifier Co. is loaded with features and options. All you need is tap water, electricity, and a sanitary drain the

More information

GTS Gas-to-Steam Humidifier

GTS Gas-to-Steam Humidifier IMPORTANT: Read and save these instructions. GTS Gas-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNING! If the information in this manual is not followed exactly, a fire or explosion

More information

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual Steam Injection Pressurized Steam Humidifiers Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical

More information

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS XT SERIES Electrode Steam Humidifiers Installation, Operation, and Maintenance Manual Warnings and cautions WARNINGS AND CAUTIONS WARNING Indicates a hazardous situation

More information

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option XT SERIES Electrode Steam Humidifiers Easy to maintain Adaptable Comprehensive control with Vapor-logic option Cost-effective steam humidification Model XTP XT Series electrode steam humidifiers from DriSteem

More information

Ultra-sorb Steam Dispersion Panels

Ultra-sorb Steam Dispersion Panels Ultra-sorb Steam Dispersion Panels PR0DUCT CATALOG Ultra-sorb Model LH Ultra-sorb Model LV Ultra-sorb Model XV DRI-STEEM takes the lead again with Ultra-sorb, establishing the industry standard for energy

More information

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual Steam Injection Pressurized Steam Humidifiers Installation, Operation, and Maintenance Manual Safety precautions ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner.

More information

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG Suitable for a wide range of applications Steam Injection humidifiers from DRI-STEEM use steam from an external source, such as an

More information

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG Suitable for a wide range of applications Steam Injection humidifiers from DRI-STEEM use steam from an external source, such as an

More information

Installation Instructions. Operation and Maintenance Manual

Installation Instructions. Operation and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS Standard Water SX Series Steam Heat Exchanger Humidifier Installation Instructions Operation and Maintenance Manual Our results are comforting PURE HUMIDIFIER and INTAC

More information

GTS Gas-to-Steam Humidifier

GTS Gas-to-Steam Humidifier IMPORTANT: Read and save these instructions. GTS Gas-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNING! If the information in this manual is not followed exactly, a fire or explosion

More information

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY TM READ AND SAVE THESE INSTRUCTIONS CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Flex connectors (by PURE) AHU/duct casing Injection tube Stainless

More information

GTS. Installation, Operation, and Maintenance Manual WARNING. Gas-to-Steam Humidifier

GTS. Installation, Operation, and Maintenance Manual WARNING. Gas-to-Steam Humidifier READ AND SAVE THESE INSTRUCTIONS GTS Gas-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNING Fire or explosion hazard If the information in this manual is not followed exactly,

More information

"SXDDR" Series Steam Heat Exchanger Humidifiers

SXDDR Series Steam Heat Exchanger Humidifiers SXDDR-1 Deionized, Demineralized, or Reverse Osmosis Water "SXDDR" Series Steam Humidifiers Looking for an alternative to electrically generated humidification? Concerned about using chemically treated

More information

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual XTR Electrode Steam Humidifier Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing humidifier. Leave manual with product owner. DRI-STEEM technical support

More information

Vapor-logic 3 to Vapor-logic4

Vapor-logic 3 to Vapor-logic4 Vapor-logic 3 to Vapor-logic4 Adaptor Board Installation Manual Warnings and c autions Warnings and cautions WARNING Indicates a hazardous situation that could result in death or serious injury if instructions

More information

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY Read and Save These Instructions Sheet No. EMIP INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Tube support AHU/duct Injection tube Typ. centers Flexible

More information

Installation Instructions. Operation and Maintenance Manual

Installation Instructions. Operation and Maintenance Manual TM READ AND SAVE THESE INSTRUCTIONS Deionized, Demineralized, or Reverse Osmosis Water SXDDR Series Steam Heat Exchanger Humidifier Installation Instructions Operation and Maintenance Manual Our results

More information

"ESDDR" Series Electric Humidifier

ESDDR Series Electric Humidifier ESDDR-1 Deionized, Demineralized, or Reverse Osmosis Water "ESDDR" Series Electric Humidifier The Electric Humidifier from PURE Humidifier Co. is loaded with features and options. All you need is deionized,

More information

Steam Injection. Humidification system

Steam Injection. Humidification system Steam Injection Humidification system Standard and CLEAN-STEEM TM models suitable for a wide range of applications DRI-STEEM s Steam Injection humidifiers use steam from an external source, such as an

More information

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panel. For pressurized steam applications

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panel. For pressurized steam applications READ AND SAVE THESE INSTRUCTIONS ULTRA-SORB MODEL XV Steam Dispersion Panel Installation, Operation, and Maintenance Manual For pressurized steam applications Table of contents MECHANICAL SPECIFICATIONS..................................................1

More information

DRI-STEEM Models GTS. and GTS -DI

DRI-STEEM Models GTS. and GTS -DI READ AND SAVE THESE INSTRUCTIONS This manual must be left with the owner and should be accessible for reference. DRI-STEEM Models GTS and GTS -DI GAS-TO-STEAM HUMIDIFIERS Installation, Operation and Maintenance

More information

REPAIR PART DIAGRAMS. Pages: 1-6

REPAIR PART DIAGRAMS. Pages: 1-6 REPAIR PART DIAGRAMS PRODUCT: MODEL: DISHWASHER LL S The information included in this Ariston Spare Parts List may change without notice please see our web site www.usservicenet.com for updates, corrections

More information

SECTION STEAM AND STEAM CONDENSATE SPECIALTIES

SECTION STEAM AND STEAM CONDENSATE SPECIALTIES SECTION 23 22 18 STEAM AND STEAM CONDENSATE SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Steam Traps. B. Flash Tanks. C. Condensate Return Units. D. Pressure Reducing Valves. E. Safety Valves.

More information

Installation and Maintenance

Installation and Maintenance IB-87-D Installation and Maintenance Series CS Steam-to-Steam Humidifiers PLEASE READ AND SAVE THESE INSTRUCTIONS The Armstrong Series CS-10 steam-to-steam humidifiers use existing steam to produce new,

More information

Humidifi er FAQ. Why is the humidifier not running? The following conditions need to be satisfied before the humidifier sequence can start:

Humidifi er FAQ. Why is the humidifier not running? The following conditions need to be satisfied before the humidifier sequence can start: Humidifi er FAQ UNIT OPERATION AND TROUBLESHOOTING Why is the humidifier not running? The following conditions need to be satisfied before the humidifier sequence can start: Must be in Auto mode No flashing

More information

READ AND SAVE THESE INSTRUCTIONS DRANE-KOOLER. Water Tempering Device. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS DRANE-KOOLER. Water Tempering Device. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS DRANE-KOOLER Water Tempering Device Installation, Operation, and Maintenance Manual Table of Contents Overview Features Summary...................................... 1

More information

Humidifiers Dealer Parts List

Humidifiers Dealer Parts List Effective Date: July, 204 Revised Date: March 20, 205 Humidifiers Dealer Parts List Model 400/400M Humidifiers 6A 6B MODEL 400 MODEL 400M NO. BLUE/GRAY UNITS - PART NAME QTY/CTN PART NO. PART NO. 4B Base

More information

HumidiClean. Series HC- 4100/4145/4300/4500 Humidifiers. Installation, Operation and Maintenance Instructions. Table of Contents.

HumidiClean. Series HC- 4100/4145/4300/4500 Humidifiers. Installation, Operation and Maintenance Instructions. Table of Contents. Bulletin 537-G HumidiClean Series HC- 4100/4145/4300/4500 Humidifiers Installation, Operation and Maintenance Instructions Table of Contents Page Installation 2-9 Start-Up Procedure and Operation 10-11

More information

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation

More information

Residential Steam Humidifier

Residential Steam Humidifier Residential Steam Humidifier Model HUMXXSTM3034 Residential Steam Humidifier Owner s Manual Includes Safety & Operating Instructions READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS Safety... 2 Introduction...

More information

Steam Humidification Light Commercial Applications. Better technology means better business.

Steam Humidification Light Commercial Applications. Better technology means better business. Steam Humidification Light Commercial Applications Better technology means better business. Aprilaire Steam Humidifiers are built to last. Through extensive research and over 50 years expertise in humidification

More information

Humidifiers Dealer Parts List Model 400/400M Humidifiers

Humidifiers Dealer Parts List Model 400/400M Humidifiers Effective Date: September 1, 2012 Humidifiers Dealer Parts List Model 400/400M Humidifiers MODEL 400 MODEL 400M NO. BLUE/GRAY UNITS - PART NAME QTY/CTN PART NO. PART NO. 4B Base (blue/gray) 1 4734 4734

More information

ULTRA-SORB STEAM DISPERSION TUBE HUMIDIFIER PANEL

ULTRA-SORB STEAM DISPERSION TUBE HUMIDIFIER PANEL READ AND SAVE THESE INSTRUCTIONS This manual must be left with the owner and should be accessible for reference. ULTRA-SORB STEAM DISPERSION TUBE HUMIDIFIER PANEL For Applications Using Steam From A Boiler

More information

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER J120 STEAM BOOSTER J120 Steam Booster Manual REVISION HISTORY Revision Letter Revision Date Made by Applicable ECNs Details A 10-27-04 CBW

More information

Owner s Manual. Keep with machine for reference PKC24 INSTALLATION & OPERATION REV Perlick Corporation 8300 W Good Hope Rd Milwaukee, WI 53223

Owner s Manual. Keep with machine for reference PKC24 INSTALLATION & OPERATION REV Perlick Corporation 8300 W Good Hope Rd Milwaukee, WI 53223 Owner s Manual Keep with machine for reference PKC24 INSTALLATION & OPERATION REV.11.09 Perlick Corporation 8300 W Good Hope Rd Milwaukee, WI 53223 800-558- 5592 FAX 414-353- 7069 perlick.com TABLE OF

More information

Ultra-sorb Steam Dispersion Tube Humidifier Panel

Ultra-sorb Steam Dispersion Tube Humidifier Panel Ultra-sorb Steam Dispersion Tube Humidifier Panel Installation, Operation, and Maintenance Manual For applications using steam from a boiler or from any DRI-STEEM steam generating humidifier. Table of

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

Humidifiers. Model 400/400M Humidifiers NO. BLUE/GRAY UNITS - PART NAME QTY/CTN PART NO. PART NO.

Humidifiers. Model 400/400M Humidifiers NO. BLUE/GRAY UNITS - PART NAME QTY/CTN PART NO. PART NO. Effective Date: January, 0 Humidifiers Model 00/00M Humidifiers B B B B B B Base (blue/gray) Cover (blue/gray) Automatic Digital Humidifier Control Name Plate (blue/gray) Hole Plug (blue/gray) MODEL 00

More information

Read and save these instructions. VAPOR-LOGIC 3. Microprocessor-based humidifier control system Installation and operation manual

Read and save these instructions. VAPOR-LOGIC 3. Microprocessor-based humidifier control system Installation and operation manual Read and save these instructions. VAPOR-LOGIC 3 Microprocessor-based humidifier control system Installation and operation manual VAPOR-LOGIC 3 table of contents PLEASE: read this manual This manual will

More information

SAM-e - Short Absorption Manifold Submittal Drawings

SAM-e - Short Absorption Manifold Submittal Drawings SAM-e - Short Absorption Manifold Submittal Drawings Date: Job Name: Contractor: Contractor or Order No.: Engineer: Agent: Agent P.O. No.: Date Ordered: Date Required: Walter Meier (Climate USA) Inc. 826

More information

VT Series. Service Kit Manual CAUTION

VT Series. Service Kit Manual CAUTION VT Series Electric Humidifier Service Kit Manual WARNING Indicates a hazardous situation that could result in death or serious injury if instructions are not followed. CAUTION Indicates a hazardous situation

More information

INSTY-PAC EXTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY

INSTY-PAC EXTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY Read and Save These Instructions Sheet No. LSIP-EM INSTY-PAC EXTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Tube Support AHU/Duct Injection Tube Strainer Typ.

More information

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panels

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panels READ AND SAVE THESE INSTRUCTIONS ULTRA-SORB MODEL MP Steam Dispersion Panels Installation, Operation, and Maintenance Manual For applications using steam from a boiler or from any DriSteem steam generating

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 8413 - HUMIDIFIERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Vapor-logic3 Humidifier Control System

Vapor-logic3 Humidifier Control System Vapor-logic3 Humidifier Control System Installation and Operation Manual from the Humidification Experts Table of contents Overview Product overview...1 Summary of features...2 Control input signals...3

More information

HumidiClean Series HC- 6100/6300/6500/6700 Humidifiers Installation, Operation and Maintenance Instructions

HumidiClean Series HC- 6100/6300/6500/6700 Humidifiers Installation, Operation and Maintenance Instructions Bulletin 539-C HumidiClean Series HC- 6100/6300/6500/6700 Humidifiers Installation, Operation and Maintenance Instructions Table of Contents Page Warning Labels 2-3 Description of Model Number 4 Installation

More information

GLC/GW-100 MANUAL INSTALLATION SERVICE PARTS REV.1.01

GLC/GW-100 MANUAL INSTALLATION SERVICE PARTS REV.1.01 Owner s Manual Keep with machine for reference GLC/GW-100 MANUAL INSTALLATION SERVICE PARTS REV.1.01 CMA DISHMACHINES 12700 KNOTT STREET GARDEN GROVE, CALIFORNIA 92841 800-854- 6417 FAX 714-895- 2141 www.cmadishmachines.com

More information

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION STEAM HUMIDIFIERS

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION STEAM HUMIDIFIERS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

FOGGING & HUMIDIFICATION PAPER STORAGE TEXTILE MILLS LIQUID STORAGE TANKS AIR DUCTS PRODUCE STORAGE ROOMS GREENHOUSES HATCHERIES CONCRETE PIPE CURING

FOGGING & HUMIDIFICATION PAPER STORAGE TEXTILE MILLS LIQUID STORAGE TANKS AIR DUCTS PRODUCE STORAGE ROOMS GREENHOUSES HATCHERIES CONCRETE PIPE CURING FOGGING & PAPER STORAGE TEXTILE MILLS LIQUID STORAGE TANKS AIR DUCTS PRODUCE STORAGE ROOMS GREENHOUSES HATCHERIES CONCRETE PIPE CURING E1 FOGGING & INTRODUCTION RELIABLE & COST-EFFECTIVE SOLUTIONS For

More information

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL 3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL EFFECTIVE JULY 30, 2014 Superseding All Previous Parts Lists. The Company reserves the right to make substitution in the event that items specified

More information

Quick Start Installation Guide

Quick Start Installation Guide Quick Start Installation Guide Nortec EL Electrode Steam Humidifier Overview Mounting Installation Requirements Standard Mounting Steam Distribution Installation Requirements Plumbing Water and Drainage

More information

Installation, Operation, Maintenance, Spare Parts, and Exploded Views Guide

Installation, Operation, Maintenance, Spare Parts, and Exploded Views Guide MES-U Electrode Steam Humidifiers Installation, Operation, Maintenance, Spare Parts, and Exploded Views Guide IMPORTANT: Read and save these instructions. This guide to be left with equipment owner. Form

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

Installation Instructions. Operation and Maintenance Manual

Installation Instructions. Operation and Maintenance Manual Read and Save These Instructions Deionized, Demineralized, or Reverse Osmosis Water ECDDR Series Electric Humidifier Installation Instructions Operation and Maintenance Manual Our results are comforting

More information

Statement of Responsibilities

Statement of Responsibilities Statement of Responsibilities This document is for use by experienced and trained Qualified Cleveland Range, LLC Authorized Service Representatives who are familiar with both the safety procedures, and

More information

VAPOR-LOGIC MICROPROCESSOR BASED HUMIDIFIER CONTROL SYSTEM

VAPOR-LOGIC MICROPROCESSOR BASED HUMIDIFIER CONTROL SYSTEM READ AND SAVE THESE INSTRUCTIONS VAPOR-LOGIC MICROPROCESSOR BASED HUMIDIFIER CONTROL SYSTEM Installation, Start-Up, and Operations Manual For Toll-free Technical Support, call 1-800-328-4447. Have the

More information

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE:

More information

VAPOR-LOGIC MICROPROCESSOR BASED HUMIDIFIER CONTROL SYSTEM

VAPOR-LOGIC MICROPROCESSOR BASED HUMIDIFIER CONTROL SYSTEM READ AND SAVE THESE INSTRUCTIONS VAPOR-LOGIC MICROPROCESSOR BASED HUMIDIFIER CONTROL SYSTEM Installation, Start-Up, and Operations Manual For Toll-free Customer Support, Call: 1-800-328-4447 TABLE OF CONTENTS

More information

INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY

INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY Read and Save These Instructions Sheet No. LSIP-IM INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Strainer Secure to AHU/duct casing with 3/8-16 UNC

More information

Vapor-logic3 Humidifier Control System. Installation and Operation Manual

Vapor-logic3 Humidifier Control System. Installation and Operation Manual Vapor-logic3 Humidifier Control System Installation and Operation Manual Table of contents Overview Product overview...1 Summary of features...2 Control input signals...3 TP modulation...5 SSR modulation...6

More information

DRI-STEEM STEAM INJECTION HUMIDIFIERS

DRI-STEEM STEAM INJECTION HUMIDIFIERS READ AND SAVE THESE INSTRUCTIONS DRI-STEEM STEAM INJECTION HUMIDIFIERS Installation Instructions and Maintenance Operations Manual TABLE OF CONTENTS TO THE PURCHASER AND THE INSTALLER Thank you for purchasing

More information

SE Series. Installation and Operation Manual

SE Series. Installation and Operation Manual Important: Read and save these instructions. This guide to be left with equipment. SE Series Installation and Operation Manual Includes installation, operation, maintenance, and troubleshooting information

More information

GTS. User Manual. Gas-to-Steam Humidifier. Affix product label here.

GTS. User Manual. Gas-to-Steam Humidifier. Affix product label here. Following installation of this steam-generating humidifier, the installer shall instruct the user in the operation of the steam-generating humidifier and the safety devices. The installer shall give at

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FCP2400D FCP3000D FCP3600D FCP4200D FCP4800D FCP6000D FCP2400C FCX2400C FCP3000C FCP3600C FCX3600C FCP4200C FCP4800C FCX4800C FCP6000C FCX6000C Require AMF001NHA Accessory No

More information

TYPICAL INSTALLATION Figure A. Condensate Return Line. Humidifier Cabinet. Drain Line

TYPICAL INSTALLATION Figure A. Condensate Return Line. Humidifier Cabinet. Drain Line READ AND SAVE THESE INSTRUCTIONS MODEL HRAA TECHNICAL MANUAL INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS CARNES COMPANY, 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 - Phone: 608/845-6411

More information

Safety, Installation, and Operation Manual

Safety, Installation, and Operation Manual Automatic Steam Humidifier Control Safety, Installation, and Operation Manual READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE STARTING. WARNING This product must be installed by a qualified heating and

More information

POWER PAK 480V Commercial Steam bath Generator

POWER PAK 480V Commercial Steam bath Generator Installation Instructions POWER PAK 480V Commercial Steam bath Generator THREE PHASE With Mechanical Timer For machine of manufacture post May 2001 DO NOT USE THIS PRODUCT UNLESS YOU HAVE CONSULTED YOUR

More information

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw SEMI-INSTANTANEOUS ENERGY: STEAM TO WATER U-TUBE SINGLE-WALL & DOUBLE-WALL HEAT EXCHANGERS FLOOR DRAIN Typical Construction Figure 34-1 FLOOR DRAIN 1. U-tube

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product

More information

SE Series. Installation and Operation Manual

SE Series. Installation and Operation Manual Important: Read and save these instructions. This guide to be left with equipment. SE Series Installation and Operation Manual Includes installation, operation, maintenance, and troubleshooting information

More information

SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL-

SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL- SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL- 8167 Byron Road Whittier, CA 90606 Phone: (562) 945-8971 Fax: (562) 696-0724 www.compu-aire.com Table of Contents

More information

Installation Instructions Owner s Manual

Installation Instructions Owner s Manual Installation Instructions Owner s Manual FOR USE WITH GAS, OIL and HYDRONIC FORCED AIR FURNACES SEQUENCE OF OPERATION The AUTOFLO Model s SC15 & 250 use the evaporative principal to add moisture to the

More information

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM BEST PRACTICE NO. 30 WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM Air and noncondensable gases are one of the major problems in a steam system that can cause production

More information

FOGGING & HUMIDIFICATION PAPER STORAGE TEXTILE MILLS LIQUID STORAGE TANKS AIR DUCTS PRODUCE STORAGE ROOMS GREENHOUSES HATCHERIES CONCRETE PIPE CURING

FOGGING & HUMIDIFICATION PAPER STORAGE TEXTILE MILLS LIQUID STORAGE TANKS AIR DUCTS PRODUCE STORAGE ROOMS GREENHOUSES HATCHERIES CONCRETE PIPE CURING FOGGING & PAPER STORAGE TEXTILE MILLS LIQUID STORAGE TANKS AIR DUCTS PRODUCE STORAGE ROOMS GREENHOUSES HATCHERIES CONCRETE PIPE CURING E1 FOGGING & INTRODUCTION RELIABLE & COST-EFFECTIVE SOLUTIONS For

More information