MODELS B1PA024, 030 AND 036

Size: px
Start display at page:

Download "MODELS B1PA024, 030 AND 036"

Transcription

1 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: N1Y (892) N1Y (893) MODELS B1PA024, 030 AND GENERAL YORK Model B1PA units are factory assembled heat pumps designed for outdoor installation on a roof top or a slab. Field-installed electric heater accessories are available to provide supplemental electric heat combined with electric cooling and heating. The units are completely assembled on rigid, permanently attached base. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require only electric power and duct connections at the point of installation. The electric heaters have nickel-chrome resistance wire elements and utilize single point power connection. INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier s freight bill. A separate request for inspection by the carrier s agent should be made in writing. Refer to Form NM for additional information. REFERENCE Additional information on the design, installation, operation and service of this equipment is available in the following reference forms: N1 -General Installation N2 -Pre-start & Post-start Check List N1.1V -Electric Heater Accessory Renewal Parts: Refer to the Renewal Parts Manual for complete listing of replacement parts on this equipment. All forms referenced in this instruction may be ordered from: Publications Distribution Center Central Environmental Systems P.O. Box 1592, York, Pa Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly. CAUTION THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE W ITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES. WARNING INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.

2 N1Y LIMITATIONS INSTALLATION LOCATION These units must be installed in accordance with the following national and local safety codes: 1. National Electrical Code ANSI/NFPA No Local electric utility requirements. 3. Canadian Electrical Code C Canadian Installation Codes CAN1-B149. Refer to Table 1 for Unit Application Data and to Table 5 for Electric Heat Application Data. If components are to be added to a unit to meet local codes, they are to be installed at the dealer s and/or the customer s expense. Size of unit for proposed installation should be based on heat loss/heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA). TABLE 1 - UNIT APPLICATION DATA Model BPA Voltage Variation Min. / Max.* 187 / 253 Wet Bulb Temperature ( F) of Air on Indoor 57 / / / 72 Cooling Coil, Min. / Max. Dry Bulb Temperature ( F) of Air on Outdoor 50 / / / 115 Coil, Min. / Max. Dry Bulb Temperature ( F) of Air on Indoor 50 / / / 80 Heating Coil, Min./Max. Dry Bulb Temperature ( F) of Air on Outdoor -10 / / / 75 Coil, Min./Max. *Utilization range A in accordance with ARI Standard 110. Use the following guidelines to select a suitable location for these units. 1. Unit is designed for outdoor installation only. 2. Outdoor coil must have an unlimited supply of air. 3. For ground level installation, use a level concrete slab with a minimum thickness of 4 inches. The length and width should be at least 6 inches greater than the unit base rails. Do not tie slab to the building foundation. 4. Roof structures must be able to support the weight of the unit and its accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame. 5. Maintain level tolerance to 1/8" maximum across the entire length or width of the unit. RIGGING AND HANDLING Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreaders, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit. BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY. Units may also be moved or lifted with a fork-lift. LENGTH OF FORKS MUST BE A MINIMUM OF 42". Remove the nesting brackets from the four corners on top of the unit. All screws that are removed when taking these brackets off must be replaced on the unit. Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity. PRODUCT CATEGORY B = Single Package Heat Pumps (Air Cooled) PRODUCT GENERATION 1 = NEW or Current Design PRODUCT NOMENCLATURE B 1 P A A 0 6 VOLTAGE CODE 06 = 208/ FACTORY INSTALLED ELECTRIC HEAT A = No Electric Heat Installed PRODUCT IDENTIFIER PA = Heat Pump NOMINAL COOLING CAPACITY 024 = 2 Ton 030 = 2-1/2 ton 036 = 3 Ton 2 Central Environmental Systems

3 APPROXIMATE CENTER OF GRAVITY FRONT FILTERS N1Y A high velocity filter must be field supplied. Filters must always be used ahead of indoor coil and must be kept clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. 32-1/ / / CONDENSATE DRAINS The drain connection (indoor coil) is 3/4" FPT and must be trapped a minimum of 1 inch to provide proper drainage. Plumbing must conform to local codes. FIG. 1 - CENTER OF GRAVITY CLEARANCES All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for combustible construction, servicing, and proper unit operation. WARNING:Do not permit overhanging structures or shrubs to obstruct outdoor air discharge outlet. DUCT WORK Duct work should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA). A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize noise. CAUTION: When fastening duct work to side duct flanges on unit, insert screws through duct flanges only. DO NOT insert screws through casing. Outdoor duct work must be insulated and waterproofed. SERVICE ACCESS Access to all serviceable components is provided by three removable panels: Electric heat compartment access panel. Control compartment access panel. Blower service compartment access panel. Refer to Figure 3 for location of these access panels. THERMOSTAT The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer s instructions enclosed with thermostat for general installation procedure. Seven color coded insulated wires (#18 AWG) should be used to connect thermostat to unit. See Figure 2 for wiring details. CAUTION: Make the low voltage wiring connection for the defrost control in the outdoor unit by stripping the wire to 3/8" and placing it in the wire channel. Do not wrap it around the screw. Make sure there is no wire insulation under the screw head. Do not over tighten. TABLE 2 - PHYSICAL DATA MODELS BPA INDOOR CENTRIFUGAL BLOWER (Dia. x Wd. in.) 9 x 6 10 x 8 10 x 10 BLOWER FAN MOTOR HP ROWS DEEP INDOOR FINS PER INCH FACE AREA (Sq. Ft.) (24 x 24) 4 (24 x 24) 4 (20 x 24) 3.3 PROPELLER DIA. (in.) OUTDOOR FAN MOTOR HP FAN NOM. CFM TOTAL 2,200 2,400 2,600 ROWS DEEP OUTDOOR FINS PER INCH FACE AREA (Sq. Ft.) (26 x 64) 11.5 (26 x 64) 11.5 (26 x 64) 11.5 CHARGE REFRIGERANT 22 (lbs./oz.) 6/12 6/8 8/0 UNIT WEIGHT Lbs Central Environmental Systems 3

4 N1Y POWER AND CONTROL WIRING Field wiring to the unit must conform to provisions of the National Electrical Code, ANSI / NFPA 70 and/or local ordinances. The unit must be electrically grounded in accordance with N.E.C. ANSI / NFPA 70 or local codes. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1. The wiring harness furnished with this unit is an integral part of a UL and C.S.A. design certified unit. Field alteration to comply with electrical codes should not be required. A disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. Refer to Figure 3 for installation locations. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram. Electrical line must be sized properly to carry the load. USE COPPER CONDUCTORS ONLY. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused. Refer to Figure 2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information. Refer to Table 3 for electrical data. UNIT HIGH VOLTAGE TERMINAL BLOCK POWER WIRING CRANKCASE HEATER The crankcase heater is energized whenever the compressor is not running. Check for proper operation by feeling for heat on the compressor where the heater is installed. The heater should be energized for at least 8 hours before the thermostat is set to operate the compressor. CAUTION: An attempt to start the compressor without at least 8 hours of crankcase heat will damage the compressor. A warning label pertaining to supplying power to the crankcase heater is supplied with the installation instruction packet of the unit. This should be attached to the disconnect switch where the occupant is most likely to see it. IMPORTANT IF POWER HAS BEEN OFF FOR 8 HOURS OR LONGER, DISCONNECT SWITCH MUST BE TURNED ON 8 HOURS BEFORE THERMOSTAT IS SET TO HEAT, COOL OR AUTO A COMPRESSORS On some units the compressor is mounted on springs which have been tightened down for shipment only. After this unit is installed, back out the compressor bolts until the sleeve clears the top grommet. CAUTION: Do Not loosen compressor mounting bolts. REFER TO TABLE 3 OR 4 TO SIZE THE DISCONNECT SWITCH, WIRING AND OVERCURRENT PROTECTION FIELD-SUPPLIED DISCONNECT POWER 208/ CONTROL WIRING DEFROST CONTROL THERMOSTAT 2TH TH ET ET FIG. 2 - TYPICAL FIELD WIRING DIAGRAM 4 Central Environmental Systems

5 TABLE 3 - ELECTRICAL DATA (BASIC UNIT) N1Y MODEL BPA POWER VOLTAGE LIMITATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FAN MOTOR, FLA MIN. MAX. RLA LRA AIR BLOWER MOTOR, FLA TOTAL UNIT AMPACITY, MAX. FUSE SIZE, (SEE NOTE 2) MAX. HACR BREAKER SIZE, MIN. WIRE SIZE, AWG (SEE NOTE 3) / / / NOTES: 1. Utilization Range A in accordance with ARI Standard Dual element, time delay type. 3. Based on 75 C copper conductors. TABLE 4 - ELECTRICAL DATA (COOLING / ELECTRIC HEAT) MODEL BPA POWER COMPRESSOR RLA LRA OUTDOOR FAN MOTOR FLA AIR BLOWER MOTOR, FLA / / / Dual element, time delay type. 2 Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused. 3 Based on 75 C copper conductors. ELECTRICAL HEATERS TOTAL MODEL NO. KW 2PH ELECTRIC HEAT CORRECTION FACTORS 3.8/ / / / / / / / / / / / / / / / / / / / / / / / / / / /62.5 TOTAL UNIT AMPACITY, 39.1/ / / / / / / / / / / / / /102.8 MAX. FUSE SIZE, 1 40/50 50/50 50/50 80/80 90/90 80/80 90/90 90/100 MAX. HACR 2 BREAKER SIZE, 40/45 30/50 50/50 80/80 90/90 80/80 90/90 90/100 MIN. WIRE SIZE, 3 AWG 8/8 6/6 6/4 4/4 8/8 6/6 4/4 4/3 3/2 6/6 6/4 4/4 4/3 3/2 NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER Central Environmental Systems 5

6 N1Y ALTERNATE LOCATION FOR FIELD SUPPLIED DISCONNECT SWITCH CONDENSER HIGH VOLTAGE CONN. KNOCKOUT LOW VOLTAGE CONN. KNOCKOUT All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request EVAPORATOR (RETURN AIR OPENING) REAR VIEW AIR OPENING HEATER SERVICE ACCESS COMPARTMENT PANEL 29 (OVERALL) CONDENSER 27 2 BLOWER SERVICE ACCESS COMPARTMENT PANEL HIGH VOLTAGE CONN. 7 8 DIA. KNOCKOUT (OVERALL) (OVERALL) ELECTRICAL SERVICE ACCESS COMPARTMENT PANEL FRONT VIEW LOW VOLTAGE CONN. 7 8 DIA. KNOCKOUT CLEARANCES Front 36" Back 6" Left Side (Filter Access) 24" Right Side 24" Below Unit 1 0" Above Unit 2 48" (For Condenser Air Discharge 1 Units may be installed on combustible floors made from wood or class A, B or C roof covering material. 2 Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. NOTE: A 1" clearance must be provided between any combustible material and the supply air ductwork. The products of combustion must not be allowed to accumulate within a confined space and recirculate. FIG. 3 - DIMENSIONS & CLEARANCES (B1PH024, 030, 036) 6 Central Environmental Systems

7 WITH POWER TO UNIT AND THERMOSTAT IN COOLING POSITION. Cooling operation is the same as any conventional air conditioning unit. SEQUENCE OF OPERATION N1Y 4. System will cycle with thermostat demand to provide cooling as needed. WITH POWER TO UNIT AND THERMOSTAT IN HEATING POSITION The following checks may be made to determine if the system is operating properly: 1. The outdoor fan should be running, with warm air being discharged from the top of the unit. 2. The indoor blower will be operating, discharging cool air from the supply duct. 3. The vapor line at the outdoor will feel cool to the touch. 4. The liquid line at the outdoor will feel warm to the touch. See Figure 4 to trace the flow of refrigerant through the system. 1. Reversing valve is energized through thermostat system switch to position refrigerant circuit for cooling operation. In the cooling cycle, discharge gas is pumped to the outdoor coil which is the condenser. The indoor coil is the evaporator. 2. If fan switch is in ON position, a circuit is made through blower relay to provide continuous blower operation. 3. When thermostat cooling contact closes, a circuit is made to energize contactor and start the system. With fan switch in AUTO position, a circuit is made from thermostat cooling contact through blower relay to provide blower operation. See Figure 4 to trace the flow of refrigerant through the system. 1. Reversing valve is de-energized to position refrigerant circuit for heating operation. In the heating cycle, discharge gas is pumped to the indoor coil which is the condenser. The outdoor coil is the evaporator. 2. If fan switch is in ON position, a circuit is made through blower relay to provide continuous blower operation. 3. When first stage of thermostat heating contact closes, a circuit is made through the control to energize contactor and start the system. With fan switch in AUTO position, a circuit is made from thermostat heating contact through blower relay to provide blower operation. 4. The system will cycle in response to thermostat signal to provide heating as needed. 5. Supplemental electric heaters are energized by second stage of heating thermostat. DEFROST CYCLE Frost and ice which forms on the outdoor coil during the heating cycle must be defrosted when it blocks the air flow through the coil. Due to the arrangement of the refrigerant circuit within the outdoor coil of these units, frost may accumulate unevenly in COOLING CYCLE FLOW HEATING CYCLE FLOW * SHOWN IN COOLING POSITION 4-WAY REVERSING VALVE* INDOOR OUTDOOR SUCTION ACCUM. COMPRESSOR TXV STRAINER TXV FIG. 4 - HEAT PUMP FLOW DIAGRAM FILTER/ DRIER-CHECK VALVE Central Environmental Systems 7

8 different sections of the coil. However, a normal defrost may occur even though the coil is not completely covered with frost. Three requirements must be met before a defrost cycle can be initiated. 1. A minimum of 39 minutes must have elapsed since last defrost. CAUTION: Prior to any of the following maintenance procedures, shut off all power to the unit to prevent personal injury. Periodic maintenance normally required consists of changing or cleaning filters. FILTERS (Field Installed) - Inspect once a month. Replace disposable or clean permanent type as necessary. DO NOT replace permanent type with disposable. MAINTENANCE 2. The liquid line temperature must be less than 40 F. 3. The coil temperature must be below the defrost initiation temperature for 4.5 minutes continuously. Defrost will terminate when the coil temperature reaches 75 F or after 14 minutes defrost time. NOTE: Exercise care when cleaning the coil so that the coil fins are not damaged. Do not permit the outdoor air discharge to be obstructed by overhanging structures of shrubs. NOTICE TO OWNER: If lock-out occurs, check the following before calling a serviceman: MOTORS - Indoor blower motor and outdoor fan motors are permanently lubricated and require no maintenance. OUTDOOR - Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean coil, be sure power to the unit is shut off prior to cleaning. 1. Indoor section for dirty filter. 2. Outdoor section for snow accumulation. 3. Outdoor section for leaf or debris blockage. Eliminate problem, turn off the thermostat for 10 seconds and attempt start. Wait 5 minutes. If system does not start, call serviceman. Unitary Products Group P.O. Box 1592, York, Pennsylvania USA Subject to change without notice. Printed in U.S.A. Copyright by York International Corporation All Rights Reserved N1Y

Supersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER)

Supersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER) CHAMPION SERIES SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.18-N2Y (8) 511.18-N2Y (7) MODELS B1HH018 THRU 00 1.5 THRU 5 TON (12 SEER) 035-1707-000 GENERAL YORK Model B1HH units are

More information

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER)

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER) INSTALLATION MANUAL CONTENTS GENERAL...................................... 3 INSPECTION.................................... 3 INSTALLATION.................................. 3 REFERENCE....................................

More information

Supersedes: N1Y (1099) N1Y (0500) MODELS B1HA018 THRU THRU 5 TON (10 SEER)

Supersedes: N1Y (1099) N1Y (0500) MODELS B1HA018 THRU THRU 5 TON (10 SEER) CHAMPI SERIES SINGLE PACKAGE HEAT PUMPS INSTALLATI INSTRUCTI Supersedes: 5.8NY (099) 5.8NY (0500) MODELS BHA08 THRU 060.5 THRU 5 T (0 SEER) 0356004 GENERAL YORK Model BHA units are factory assembled heat

More information

Supersedes: N2W (398) N2Z (1298) MODELS BCCB 090 & 120, MODELS BECB090 & 120 (9 EER) 208/230/460 VOLT MODELS ONLY

Supersedes: N2W (398) N2Z (1298) MODELS BCCB 090 & 120, MODELS BECB090 & 120 (9 EER) 208/230/460 VOLT MODELS ONLY INSTALLATION SINGLE PACKAGE HEAT PUMPS 71/2 & 10 TON INSTRUCTION Supersedes: (398) 511.06N2Z (1298) MODELS BCCB 090 & 120, MODELS BECB090 & 120 (9 EER) 03516199 208/230/460 VOLT MODELS ONLY 208/230/575

More information

MODELS D1EH018 THRU 060, 1-1/2 THRU 5 TON (12 SEER) AND MODELS D1EM036 THRU 060, 3 THRU 5 TON (13 SEER)

MODELS D1EH018 THRU 060, 1-1/2 THRU 5 TON (12 SEER) AND MODELS D1EM036 THRU 060, 3 THRU 5 TON (13 SEER) INSTALLATI INSTRUCTI CHAMPI SERIES SINGLE PACKAGE AIR CDITIERS ELECTRIC/ELECTRIC, AIR-COOLED Supersedes: 6666-YIM-A-0404/035-5679-00-A-0404 6666-YIM-B-004 MODELS DEH08 THRU 060, -/ THRU 5 T ( SEER) AND

More information

SUNLINE 2000 ELECTRIC / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N7Y (993) 530.

SUNLINE 2000 ELECTRIC / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N7Y (993) 530. SUNLINE 00 ELECTRIC / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: 530.18N7Y (993) 530.18N7Y (295) MODELS D3CE 036, 048 & 060 ( SEER) MODEL D1CE 072 (9 EER) (STYLE B &

More information

MODELS B3CH 090 & 120A25, A46 MODELS B4CH090 & 120A58 (9 EER) 208/230/575 VOLT MODELS ONLY 208/230/460 VOLT MODELS ONLY

MODELS B3CH 090 & 120A25, A46 MODELS B4CH090 & 120A58 (9 EER) 208/230/575 VOLT MODELS ONLY 208/230/460 VOLT MODELS ONLY SUNLINE 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.06N2Y (1191) 511.06N2Y (293) MODELS B3CH 090 & 120A25, A46 MODELS B4CH090 & 120A58 (9 EER) 03510256 208/230/460 VOLT MODELS

More information

MODELS B3CH 048 AND 060 (WORLD 50 HZ)

MODELS B3CH 048 AND 060 (WORLD 50 HZ) SUNLINE 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 5.3-NYI (900)/035-2984-000 035-2984-00-A-0204 MODELS B3CH 048 AND 060 (WORLD 50 HZ) GENERAL YORK Model BCH units are single package

More information

R-410A AFFINITY SERIES DEX DEY Ton

R-410A AFFINITY SERIES DEX DEY Ton R-410A AFFINITY SERIES 024-048 DEY060 2-5 Ton ISO 9001 Certified Quality Management System General.......................................... 1 Installation........................................ 3 Limitations......................................

More information

Supersedes: A-0202 MODELS B1HA018 THRU THRU 5 TON (10 SEER)

Supersedes: A-0202 MODELS B1HA018 THRU THRU 5 TON (10 SEER) CHAMPION SERIES SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 035600400A00 035600400A004 MODELS BHA08 THRU 060.5 THRU 5 TON (0 SEER) GENERAL YORK Model BHA units are factory assembled

More information

R-410A AFFINITY SERIES

R-410A AFFINITY SERIES R-410A AFFINITY SERIES BHZ024-060 2-5 Ton ISO 9001 Certified Quality Management System General.......................................... 1 Installation........................................ 3 Limitations......................................

More information

INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BP

INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BP INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BP 036-072 CONTENTS GENERAL................................ 4 SAFETY CONSIDERATIONS................. 4 INSPECTION..............................

More information

INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BCH 036, 048 & 060

INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BCH 036, 048 & 060 INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BCH 036, 048 & 060 CONTENTS GENERAL................................ 4 SAFETY CONSIDERATIONS................. 4 INSPECTION..............................

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS 13CHPX SERIES UNITS PACKAGED HEAT PUMPS (2 5 TONS) 505,136M (38152A071) 12/09 Supersedes 05/09 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation,

More information

STELLAR 2000 SINGLE PACKAGE AIR CONDITIONERS GAS/ELECTRIC, AIR-COOLED INSTALLATION INSTRUCTION

STELLAR 2000 SINGLE PACKAGE AIR CONDITIONERS GAS/ELECTRIC, AIR-COOLED INSTALLATION INSTRUCTION STELLAR 2000 SINGLE PACKAGE AIR CONDITIONERS GAS/ELECTRIC, AIR-COOLED INSTALLATION INSTRUCTION Supersedes: 530.44-N4Y (893) 530.44-N4Y (1294) MODELS D3GA018 THRU 042 (10 SEER) 035-12496 GENERAL YORK Model

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling

More information

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72 ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY, 16, 26, 36 & 72 FOR SPLIT-SYSTEM AIR CONDITIONERS 5, 7-1/2, & 15 TONS SPLIT-SYSTEM HEAT PUMPS 7-1/2 & TONS GENERAL This instruction covers the

More information

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ) Technical Guide SUNLINE 2000 SPLIT-SYSTEM EVAPORATOR BLOWER K4EU180 15 NOMINAL TONS (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................

More information

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED (491) SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU, K3EU & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes

More information

MODELS E1FB180 & E1FB240

MODELS E1FB180 & E1FB240 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: 035-16192-000 (0601) 035-16192-001-A-1001 MODELS E1FB180 & E1FB240 GENERAL The outdoor units are completely piped and wired at

More information

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS SUNLINE 2000ô MODELS: H5CE090, H3CE120 & H1CE150 7-1/2, 10, & 12-1/2 NOMINAL TONS 9.0-9.5 EER DESCRIPTION These Sunline 2000ô units are completely

More information

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons 560.20-TG1Y (388) EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons Each circuit includes a fully hermetic compressor with a crankcase

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION MODULAR AIR HANDLER MODEL: N*AH CONTENTS GENERAL... 1 INSPECTION... 2 REFERENCE... 2 LIMITATIONS... 2 LOCATION... 2 BLOWER/COIL ASSEMBLY UPFLOW AND HORIZONTAL INSTALLATIONS...

More information

MODELS W1LC220, 260 AND 320 STYLE B

MODELS W1LC220, 260 AND 320 STYLE B LIQUID CHILLER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 570.05-NY (494) 570.05-N3Y (495) MODELS WLC0, 60 AND 30 STYLE B 035-3053 Only -5 and -46 voltage codes GENERAL YORK s WLC Packaged Air-Cooled

More information

MODELS K2EU060A, K4EU090A, & K3EU120A

MODELS K2EU060A, K4EU090A, & K3EU120A AIR COOLED SPLIT-SYSTEM AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: 550.23-N2Y (589) 550.23-N2Y (399) MODELS K2EU060A, K4EU090A, & K3EU120A 035-16672 GENERAL These completely assembled 5, 7-1/2

More information

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ E3FB090/E1FB120/F3EH090 & 120 7-1/2 & 10 NOMINAL TONS (60 HZ) 7 & 9 NOMINAL TONS (50 HZ) (9.0-9.2 EER) 208/230/460 VOLT ONLY 208/230 VOLT ONLY DESCRIPTION YORK has

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2011 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS 13HPP UNITS PACKAGED HEAT PUMP UNIT (2 5 TONS) 506750 01 06/11 Supersedes 03/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE

More information

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: Nothing 515.41-N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) 035-09648 EFB090 SHOWN GENERAL Renewal Parts: 208/230/460 VOLT ONLY

More information

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS Technical Guide SPLIT-SYSTEM EVAPORATOR BLOWERS 7-1/2 and 10 NOMINAL TONS LA090 & LA120 DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ) (994) SPLIT-SYSTEM EVAPORATOR BLOWER K5EU090 and K4EU120 50 Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX coil

More information

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: 515.41-N1Y (497) 515.41-N1Y (998) MODELS E2FB090 & E1FB120 035-15410 EFB090 SHOWN 208/230/460 VOLT ONLY 208/230 VOLT ONLY GENERAL

More information

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492) CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 550.13-N4 (778) 550.13-N4Y (492) MODELS H2CA480 & 600 035-09563 GENERAL CHAMPION units are designed for outdoor

More information

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons Product Data 50HS Single-Package Heat Pumps 1 1 2 to 5 Nominal Tons Single-Package Heat Pump for Manufactured Housing/Residential and Light Commercial use. Features/Benefits One-piece heat pumps with optional

More information

INSTALLATION MANUAL SINGLE PACKAGE HEAT PUMP. MODELS: BA-15 and BA-20. ASHRAE 90.1 Compliant. Model BA-15. Model BA-20

INSTALLATION MANUAL SINGLE PACKAGE HEAT PUMP. MODELS: BA-15 and BA-20. ASHRAE 90.1 Compliant. Model BA-15. Model BA-20 INSTALLATION MANUAL CONTENTS GENERAL....................................4 SAFETY CONSIDERATIONS.....................4 INSPECTION..................................4 REFERENCE..................................4

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS 536306-UAI-B-1009 Electric Heat Accessory 10, 16, 20, 26, 32, 36 & 52kW For Split-System R-410A Air Handling Units Both Air Conditioners and Heat Pumps 7-1/2, 10,

More information

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT TECHNICAL GUIDE SPLIT-SYSTEM HEAT PUMPS EA090/FA090 DESCRIPTION YORK has combined the latest concepts in modern technology with time-proven quality standards to design a split-system heat pump to meet

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION ELECTRIC HEAT S THRU 05 5 THRU Supersedes: (9) (00) 0-5 FOR SINGLE PACKAGE CONDITIONERS THRU TON SINGLE PACKAGE HEAT PUMPS THRU 5 TON GENERAL This instruction contains all the

More information

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804 INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON CONTENTS GENERAL................................. 3 REFERENCE............................... 3 INSPECTION...............................

More information

SUNLINE 2000 SINGLE PACKAGE AIR-COOLED AIR CONDITIONERS DESCRIPTION FEATURES

SUNLINE 2000 SINGLE PACKAGE AIR-COOLED AIR CONDITIONERS DESCRIPTION FEATURES 50.TGY (95) SINGLE PACKAGE COOLED CONDITIONERS DCE 0, 0, 00 & DCE 07 0, 0, 00 & 07, AND 5 NOMINAL TONS (0 SEER) AND NOMINAL TONS (9 EER) SHOWN SUNLINE 000 DESCRIPTION YORK Sunline 000 units are convertible

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT: GENERAL SPECIFICATIONS OUTDOOR UNIT: TECHNICAL GUIDE COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM MODELS HB 180 & HB 240 MODELS LB 180 & LB 240 15 & 20 NOMINAL TONS 9.7 EER Two independent refrigerant

More information

INSTALLATION MANUAL - 50 Hz

INSTALLATION MANUAL - 50 Hz INSTALLATION MANUAL - 50 Hz SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................

More information

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons 0TJ06-03S Side Discharge Single-Package Rooftop Units 0/ Hz to 30 Nominal Tons Product Data The 0TJ-S series is a special side discharge version packaged unit with capacities of -30 Tons. This unit can

More information

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS Model: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-234 G Supersedes: 2100-234

More information

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195) STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: 535.02-N2Y (795) 535.02-N2Y (1195) HEAT PUMP MODELS F1RP / F1FP018 thru 060 and COOLING MODELS F1RC / F1FC018 thru 036 035-13620

More information

INSTALLATION MANUAL SUNLINE GAS/ELECTRIC SINGLE PACKAGE AIR CONDITIONERS D(CE, CG) 036, 048, 060 & 072 D(HE, HG) 036, 048 & 060

INSTALLATION MANUAL SUNLINE GAS/ELECTRIC SINGLE PACKAGE AIR CONDITIONERS D(CE, CG) 036, 048, 060 & 072 D(HE, HG) 036, 048 & 060 INSTALLATION MANUAL CONTENTS GENERAL................................ 5 SAFETY CONSIDERATIONS................. 5 INSPECTION.............................. 5 REFERENCE.............................. 6 RENEWAL

More information

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS INSTALLATION MANUAL TABLE OF CONTENTS GENERAL.................................... 3 REFERENCE................................. 3 INSPECTION.................................. 4 OPERATION.................................

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION TABLE OF CONTENTS GENERAL............................. 5 SAFETY CONSIDERATIONS.............. 6 SINGLE PACKAGE HEAT PUMP HIGH EFFICIENCY BP078, 090,102, 120 AND 150 6-1/2 TO 12-1/2

More information

SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N6Y (593) 530.

SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N6Y (593) 530. SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: 530.18-N6Y (593) 530.18-N6Y (1294) MODELS D2CG180 & 240 (STY. B) (8.4-8.5 EER) 035-12552 208/230/575 VOLT

More information

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION INSTALLATION INSTRUCTION CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS Supersedes: 550.44-N1Y (1194) 550.44-N1Y (495) MODELS H*DE018 THRU H*DE060 035-11029 WARNINGS are given to alert the installer

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

USER'S MANUAL/INSTALLATION INSTRUCTIONS

USER'S MANUAL/INSTALLATION INSTRUCTIONS TM USER'S MANUAL/INSTALLATION INSTRUCTIONS P Series Single Package Convertible Air Conditioner Single Package Convertible Air Conditioner IMPORTANT These instructions are primarily intended to assist qualifi

More information

Installation Instructions

Installation Instructions Installation Instructions PAM3 SERIES PACKAGE AIR CONDITIONERS TABLE OF CONTENTS SAFETY LABELING AND SIGNAL WORDS... 2 UNIT DIMENSIONS... 3 SAFE INSTALLATION REQUIREMENTS... 3 LOCATING THE UNIT... 3 CLEARANCES...

More information

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax AllStyle Coil Company, LP 7037 Brittmore Houston, TX 77041 Phone 713-466-6333 Fax 713-466-6363 April 2005 VL / VLX Series Air Handler VL / VLX Series Air Handlers Installation Operation Maintenance The

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS 15CHPX SERIES UNITS RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss

More information

2 shp 13 lc 1 36 t - 1 a

2 shp 13 lc 1 36 t - 1 a HEAT PUMPs 2SHP3 PRODUCT SPECIFICATIONS Dry Charge Split System - 60 HZ Bulletin No. 20645 July 203 Supersedes June 202 3 to 5 Tons MODEL NUMBER IDENTIFICATION 2 shp 3 lc 36 t - a Refrigerant Type 2 =

More information

MERIT SERIES Up Flow / Horizontal

MERIT SERIES Up Flow / Horizontal A I R H A N D L E R S CB26UH / CBX26UH MERIT SERIES Up Flow / Horizontal E N G I N E E R I N G D A T A Bulletin No. 210429 December 2006 Supersedes November 2006 Nominal Capacity 1.5 to 5 Tons Optional

More information

SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: Nothing N3Y (394) MODELS D*SC360 & 480 INSPECTION

SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: Nothing N3Y (394) MODELS D*SC360 & 480 INSPECTION SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: Nothing 530.25-N3Y (394) MODELS D*SC360 & 480 035-11820 208/230/575 VOLT ONLY 208/230/460 VOLT ONLY GENERAL This instruction

More information

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE INSTALLATION INSTRUCTION CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS Supersedes: Nothing 550.38-N6Y (1095) MODELS H*DB076 035-13578 WARNINGS are given to alert the installer that severe personal injury,

More information

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500 SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing 550.23-N4C-0500 MODEL L*BC240 035-16603 GENERAL This 20 ton evaporator blower is designed with two distinct modules

More information

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13 Tag Data - Split System Air Conditioning Units (Large) (Qty: 6) Item Tag(s) Qty Description Model Number A1 20 ton vfd 6 6-25 Ton Unitary Split Systems ( SSC2 TTA24004H00-TWE240E404A TTA Air Condensing

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

INSTALLATION MANUAL LIST OF SECTIONS. 1 General 1 3 Louvered Door Frame Assembly Installation 3 2 Safety 2 4 Coil Cabinet Installation 5

INSTALLATION MANUAL LIST OF SECTIONS. 1 General 1 3 Louvered Door Frame Assembly Installation 3 2 Safety 2 4 Coil Cabinet Installation 5 INSTALLATION MANUAL DOWNFLOW / HORIZONTAL COIL CABINET DOWNFLOW LOUVERED DOOR ASSEMBLY MODELS: 97-F SERIES LIST OF SECTIONS 1 General 1 3 Louvered Door Frame Assembly Installation 3 2 Safety 2 4 Coil Cabinet

More information

TECHNICAL GUIDE VARIABLE SPEED AIR HANDLERS DESCRIPTION FEATURES Rev. A (0105)

TECHNICAL GUIDE VARIABLE SPEED AIR HANDLERS DESCRIPTION FEATURES Rev. A (0105) TECHNICAL GUIDE VARIALE SPEED AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: N1VS 600-2000 CFM LOWERS 2-5 TON COILS OPTIONAL 1 & 3 φ ELECTRIC HEATERS ISO 9001 Certified Quality Management

More information

B24/C22/24 COILS BLOWER COIL UNITS ENGINEERING DATA. Bulletin # June 1994 Supersedes August B24 Blower Unit (With Optional Electric Heat)

B24/C22/24 COILS BLOWER COIL UNITS ENGINEERING DATA. Bulletin # June 1994 Supersedes August B24 Blower Unit (With Optional Electric Heat) ENGINEERING DATA COILS BLOWER COIL UNITS B24/C22/24 B24 SERIES ADD-ON BLOWER UNITS UP-FLO DOWN-FLO HORIZONTAL WITH C22FC/CR22/CH22 & C24FC/CH24 COILS 1-1/2 Thru 5 Ton (5.3 thru 17.6 kw) Capacity 6,400

More information

INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER MODEL: LA120 NOTES, CAUTIONS AND WARNINGS SAVE THIS MANUAL B-0203

INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER MODEL: LA120 NOTES, CAUTIONS AND WARNINGS SAVE THIS MANUAL B-0203 INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER CONTENTS NOMENCLATURE............................. 3 GENERAL.................................... 4 SAFETY CONSIDERATIONS.....................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2017 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS LRP16HP Packaged Units RESIDENTIAL PACKAGED UNITS Heat Pumps 3/2017 Table of Contents THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER

More information

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT USER S MANUAL AND INSTALLATION INSTRUCTIONS P3BD Series 13 SEER Single Package Air Conditioner IMPORTANT Read this owner information to become familiar with the capabilities and use of your appliance.

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE MANUAL INSTALLATION, OPERATION, & MAINTENANCE Vertical Concealed Fan Coil FCVC Series v100 Issue Date: 12/21/15 2015 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Safety

More information

ELECTRIC / ELECTRIC & GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTRUCTION. Supersedes: N11W (1095) N11W(399)

ELECTRIC / ELECTRIC & GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTRUCTION. Supersedes: N11W (1095) N11W(399) INSTALLATION ELECTRIC / ELECTRIC & GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTRUCTION Supersedes: 530.18-N11W (1095) 530.18-N11W(399) MODELS DBHB & DBUC300 (8.5 EER) 035-16601 208/230/575 VOLT

More information

R-410A ZS SERIES. 3-6 Ton 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

R-410A ZS SERIES. 3-6 Ton 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES R-410A ZS SERIES 3-6 Ton 60 Hertz General.......................................... 2 Installation........................................ 5 Installation Safety Information....................... 5 Limitations......................................

More information

PAJ3. Product Specifications

PAJ3. Product Specifications 13 SEER, R 410A PACKAGE AIR CONDITIONER FOR MANUFACTURED HOUSING, RESIDENTIAL, AND LIGHT COMMERCIAL APPLICATIONS 2 5 TONS Single Phase, 208/230 V, 60 Hz BUILT TO LAST, EASY TO INSTALL AND SERVICE Compact,

More information

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT -1SB 018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP S W/OPTIONAL ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINT 1997 Carrier

More information

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz Product Data 50HS Single-Package Heat Pump Units 50 Hz Nominal: 7 to 18 kw (2 to 5 Tons) Single-Package Heat Pump for Manufactured Housing/Residential and Light Commercial use. Features/Benefits One-piece

More information

SUNLINE PLUS GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: A A-0204

SUNLINE PLUS GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: A A-0204 SUNLINE PLUS GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: 035-14832-002-A-0302 035-14832-003-A-04 MODELS D2EG 048 & 060 and D3EG 036 (11 SEER) FOR YOUR SAFETY Do

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

48SS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

48SS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS -3SB 018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING S PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINT 1997 Carrier Corporation

More information

High Profile Evaporator

High Profile Evaporator PRODUCT DATA & INSTALLATION Bulletin K30-KHPA-PDI-5 Part # 1081585 PRODUCT SUPPORT web: k-rp.com/khp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: High Profile Evaporator High & Medium Temperature

More information

PAC SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (GEN 3, STYLE A)

PAC SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (GEN 3, STYLE A) www.source1parts.com HVAC SERVICE PARTS PAC SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (GEN 3, STYLE A) Supersedes:035-21137-001 Rev. E (1107) 035-21137-001 Rev. F (0611) 1 of 8 CONDENSER ROOF (SEE

More information

R-410A. DYQ Ton TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES. General

R-410A. DYQ Ton TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES. General R-410A DYQ024-060 2-5 Ton ISO 9001 Certified Quality Management System General.......................................... 1 Installation........................................ 3 Limitations....................................

More information

INSTALLATION INSTRUCTION Supersedes: N11Y (195) N11Y (399)

INSTALLATION INSTRUCTION Supersedes: N11Y (195) N11Y (399) SUNLINE 2000 ELECTRIC / ELECTRIC & GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS (Constant Air Volume) INSTALLATION INSTRUCTION Supersedes: 530.18-N11Y (195) 530.18-N11Y (399) MODELS D2CE & D2CG300 (8.5

More information

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2 Service Literature Corp. 0527 L10 Revised May 2011 CB26UH and CBX26UH Series Table of Contents CB26UH CBX26UH Model Number Information................... 2 Specifications / Electrical Data................

More information

R-410A MODELS: YD360 Thru Ton 60 Hertz

R-410A MODELS: YD360 Thru Ton 60 Hertz R-410A MODELS: YD360 Thru 600 30-50 Ton 60 Hertz Nomenclature..................................... 2 General.......................................... 2 Renewal Parts.....................................

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. VARIABLE SPEED ELECTRIC FURNACE INSTALLATION INSTRUCTIONS VARIABLE SPEED ELECTRIC FURNACE SAFETY...1 INSTALLATION REQUIREMENTS...2 Tools and Parts...2 Location Requirements...2 Installation Configurations...3

More information

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307 DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application

More information

MERIT Series R-410A - Upflow / Horizontal

MERIT Series R-410A - Upflow / Horizontal PRODUCT SPECIFICATIONS AIR HANDLERS CBX5UH (-0) MERIT Series R-0A - Upflow / Horizontal Bulletin No. 060 March 05 Supersedes November 0 Nominal Capacity -.5 to 5 Tons Optional Electric Heat -.5 to 0 kw

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TPA Series HEAT PUMPS 7.5 TO 10 TONS 506148 01 12/08 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act of 1990 bans the intentional

More information

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC ISO 9001 Certified Quality Management System SAFETY................................................

More information

Product Data. FF1DNA, FF1DNE Fan Coil Units. Sizes 018 thru 030 FEATURES/BENEFITS

Product Data. FF1DNA, FF1DNE Fan Coil Units. Sizes 018 thru 030 FEATURES/BENEFITS Product Data FF1DNA, FF1DNE Fan Coil Units Sizes 018 thru 030 FF1D FEATURES/BENEFITS The FF1DNA and FF1DNE Fan Coil units are designed as upflow indoor air handlers for split-system heat pumps and air

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

High Heat COP. High/Low Stage

High Heat COP. High/Low Stage SOUND REFRIGERANT ENVIRONMENTALLY PHN5 Product Specifications 15 SEER, 8.0 HSPF, PACKAGE HEAT PUMP, 2-5 TONS Single Phase, 208/230V, Hz. REFRIGERATION CIRCUIT R--410A refrigerant Copper tube/aluminum fin

More information

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION CONDITIONERS DRY CHARGE UNITS PRODUCT SPECIFICATIONS Bulletin No. 20636 May 204 Supersedes March 202.5 to 5 Tons MODEL NUMBER IDENTIFICATION L C S 3 DC - 036-230 - 2 Lennox Minor Revision Number Air Conditioner

More information

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units Advance Product Data 42WKN Hydronic Fan Coil Units 3 4 to 2 1 2 Tons UNIT SIZES 004-010 UNIT SIZES 016,020 The new Carrier Hydronic Cassette offers a modern solution for a wide variety of small and medium

More information