1 ARO Series Universal Room Controller s Models ARO24T ARO24TH ARO24TGH ARO24TGVH Temp RH CO2 VOC Networkable* AROB24T AROB24TH AROB24TGH AROB24TGVH * Networkable: BACnet MS/TP or Modbus (selectable using menu) Description IAQ and ECM fan control applications made easy! Introducing the new ARO series universal room controller with onboard CO 2, VOC, temperature and humidity sensors, selectable application control profiles, up to 4 simultaneous control loops, and seamless control of a 0-10 Vdc ECM fan. All of this in one wall-mounted room controller. The AROB series networkable controller operates over an RS 485 network using the BACnet MS/TP or Modbus protocol to exchange information with a Building Management System. Features Onboard Sensors Temperature sensor ( C/ F) Humidity sensor (%RH), select models VOC sensor (volatile organic compounds) select models Carbon dioxide sensor (CO 2 ), select models Functions Built-in application profiles to automatically configure the controller for the selected application. Up to 4 simultaneous control loops capable of controlling, in real time: o Humidification and Dehumidification o Heating and Cooling o CO 2 levels o VOC levels o Integrated ECM fan control mode Display or hide all the required access for user interaction Four fully configurable outputs (2 AO and 2 BO) Two universal inputs (2 UI) Backlit LCD with simple icon and text-driven menus Selectable Fahrenheit or Celsius scale Precise temperature control with programmable PI functionn Independent cool and heat setpoint for No Occupancy Configurable proportional control band and dead band Network Communication (AROB series only) BACnet MS/TP or Modbus communication port (selectable using menu) Select MAC address using menu or network Automatic baud rate detection BACnet MS/ /TP at 9600, 19200, 38400, or bps Automatic device instance configuration Copy and broadcast configuration to other controllers Network service port through on-board mini USB connector Modbus ARO Series Modbus at 9600, 19200, or bps RTUU Slave, 8 bits (configurable parity and stop bits) Connects to any Modbus master ARO Series_Installation docx Page 1

2 ARO Series Universal Room Controller s Technical Specifications Description ARO Series Temperature Sensor Setpoint range 10ºC to 40ºC [50ºF to 104ºF] Control accuracy Temperature: ±0.4ºC [0.8ºF] Display resolution ± [0.2ºF] Humidity Sensor (select models) Setpoint range 10 to 65%RH Control accuracy ±3.5% RH Display resolution 0.1% CO2 Sensor (select models) Operating principle Self-calibrating, Non-Dispersive Infrared (NDIR) Sensor range 400 to 2000 ppm Accuracy ±30 ppm ±3% of reading (Accuracy is defined after minimum 3 weeks of continuous operation) Response time 2 minutes by 90% VOC Sensor (select models) Operating principle Self-calibrating, Non-Dispersive Infrared (NDIR) Sensor range ppb isobutylene equivalent tvocs Response time < 5 seconds for tvoc Start up time 15 minutes Other Inputs 2 Universal analog inputs: 0-10Vdc, Thermistorr (10k Type 3), or digital input (dry contact) Outputs 2 Binary outputs (BO1 and BO2), dry contracts 24Vac, 1A max 3A in-rush 2 Analog outputs (cooling and heating 0 to 10Vdc BACnet BACnet 9600, 19200, 38400, or bpss (B-ASC) Modbus RTU 9600, 19200, or Selectable parity and stop bit configuration: Modbus No parity, 2 stop bit Even parity, 1 stop bit Odd parity, 1 stop bit Communication 24 AWG twisted-shield cable (Belden 9841 or equivalent) Connections Electrical connectionn 0.8 mm2 [18 AWG] minimum Operating temperature 0ºC to 50ºC [32ºF to 122ºF] Storage temperaturee -30º ºC to 50ºC [-22ºF to 122ºF] Relative humidity 5 to 95 % non-condensing Enclosure protection IP 30 (EN 60529) Weight 120 g. [0.25 lb] Dimensions A = mm B = mm C = mm D = mm E = mm B E D ºF / º C Certifications A C Conforms to UL STD 873 Certified to CSA STD C22.2 No Page 2

3 Wiring We strongly recommend to wire all controllers to a separate grounded transformer, and that transformer shall service only these products. This precaution prevents interference with and possible damage to incompatible equipment. VOC sensor (select models) CO 2 sensor (select models) BO signal selector jumpers (JP1 and JP2) Mode selector jumper (JP3) End of Line jumper (JP5) A B C JP3 PGM RUN Avoid touching the VOC and CO2 sensors as this may cause incorrect readings JP1 A B C JP2 A B C TB Terminal Description Details 1 COM 2 24Vac / 24Vdc 3 COM for BO1 (ext 24V) If JP2 is set to A+B 4 Binary Output 1 (BO1) 5 COM for BO2 (ext 24V) If JP1 is set to A+B 6 Binary Output 2 (BO2) 7 COM 8 Analog Input (AI1) 9 COM 10 Binary Input 1 (BI1) 11 Analog Output 1 (AO1) 12 COM 13 Analog Output 2 (AO2) 14 BACnet/Modbus A+ 15 BACnet/Modbus B- Temperature and Humidity sensors JP5 A B C EOL Jumpers Jumpers Description A&B = External: BO2 uses external 24 Vac at pin 3 (different than thermostat) JP1 BO2 Signal Selection B&C = Internal: BO2 uses internal 24 Vac (same as thermostat) A&B = External: BO1 uses external 24 Vac at pin 3 (different than thermostat) JP2 BO1 Signal Selection B&C = Internal: BO1 uses internal 24 Vac (same as thermostat) JP3 Mode Selection PGM RUN A&B = RUN: Standard operation mode PGM RUN B&C = PGM: Programming/configuration mode A&B: No EOL (end of line) JP5 End of Line B&C: 120 Ohm end of line (on the last ARO of the RS-485 communication bus) Page 3

4 Mounting Instructions CAUTION: Remove power to avoid a risk of malfunction. A. Remove the captive screw that is holding the base and the front cover of the unit together. B. Lift the front cover of the unit to separate it from the base. C. Pull all wires through the holes in the base. D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections. E. Mount the control module on the base and secure using the screw. A B C D E Programming Mode Set the Mode Selector Jumper JP3 to the PGM mode (Programming Mode). For more information, see "Wiring. To exit, set the Jumper JP3 back to the RUN mode (Operation Mode). All changes are saved. Indicates the Programming Mode Setting description (For example,"app PROFIL") Setting value Advance to next setting Change value Return to previous setting Page 4

5 Symbols used in this Manual Icon Description Icon Description Icon Description Icon Description Temperature Heating Cooling Humidification Dehumidification Fan CO2 VOC Analog Output 1 Analog Output 2 Binary Output 1 Binary Output 2 Analog Input 1 Binary Input 1 Communication Time Occupancy Night Set Back Application Profiles 1. "APP PROFILE" 0 to 2 1 Built-in application profiles automatically configure the controller for the selected application. 0 = No profile; manual configuration (For advanced users) 1 = Outside Air Applications (Temperature only) See APP PROFILE 1 on page 25 2 = Conference room application (Temperature, Humidity, and CO 2 ) See APP PROFILE 2: on page 26. Currently there are two profiles and more will be made available. Temperature Setpoint and User Control 2. "Intrn temp offset" Offset: 0ºC to 50ºC Max. ± 5ºC [32ºF to 122ºF] [± 41ºF] Compare the displayed temperature reading with a known value from a thermometer or other temperature sensing device. To offset or calibrate the sensor, use the arrow buttons to set the desired temperature reading. This setpoint is useful for controllers installed in areas where the temperature read is slightly different than the room s actual temperature. 3. " cool setpnt min " 10ºC 0ºC to 125ºC [50 ºF] [32ºF to 257ºF] 4. In the Operation mode, you cannot decrease the setpoint to less than the value set as the minimum cooling setpoint. The minimum value is restricted by the maximum value set at Step 3, " cool setpnt max ". In other words, the value that is set as the minimum cannot be greater than the maximum value. The cooling symbol is also displayed. Page 5

6 5. " cool setpnt max " 40ºC 0ºC to 125ºC [104ºF] [32ºF to 257ºF] ARO Series Universal Room Controller In the Operation mode, you cannot increase the setpoint to more than the value set as the maximum cooling setpoint. The maximum value is restricted by the minimum value set at Step 2, "Min Cool Setpnt". In other words, the value that is set as the maximum cannot be less than the minimum value. 6. " cool setpnt" 22ºC 10ºC to 40ºC [71.6ºF] [50ºF to 104ºF] Set the cooling setpoint that will be used in the Operation mode. This cooling setpoint value is restricted by the heating setpoint values defined at Step 7, "HEAT setpnt". The cooling 7. " HEAT setpnt MIN " 10ºC 0ºC to 40ºC [50ºF] [32ºF to 104ºF] In the Operation mode, you cannot decrease the setpoint to less than the value set as the minimum heating setpoint. The minimum value is restricted by the maximum value set at Step 6, "HEAT setpnt". In other words, the value that is set as the minimum cannot be greater than the maximum value. 8. " HEAT setpnt MAX " 40ºC 40ºC to 125ºC [104ºF] [104ºF to 257ºF] In the Operation mode, you cannot increase the setpoint to more than the value set as the maximum heating setpoint. The maximum value is restricted by the minimum heating value set at Step 5 "HEAT setpnt" and Step 7 "HEAT setpnt". In other words, the value that is set as the maximum cannot be less than the minimum value. 9. " HEAT setpnt" 20ºC 0ºC to 125ºC [68ºF] [32ºF to 257ºF] Set the cooling setpoint that will be used in the Operation mode. This cooling setpoint value is restricted by the heating setpoint values defined at Step 4, "cool setpnt". The heating 10. Temp Mode Auto (Automatic), CooL (Cooling Only),, HEAt (Heating Only), Select the control mode that you want to authorize to the user. To authorize all the available modes, select Auto (Automatic Mode). The cooling and heating symbols are also displayed. The selection made at this step determines the options available on the Operation mode. Page 6

7 Humidity Setpoints and User Control ARO Series Universal Room Controller The humidity and dehumidification configuration setpoints require a functioning humidity sensor installed. These setpoints appear only on the models with the humidity sensor. For more information on supported models, see 'Error! Reference source not found.on page " Humdty Offset" Offset: 40% ±5% 10% to 90% RH 0.1% RH The display shows the relative humidity percentage read by the humidity sensor. Adjust the offset by comparing it with a known value humidistat. If the sensor is not connected or short-circuited, unit displays the sensor's limits. 12. "Dehum setpnt Min " 10.0% RH 0 to 80.0% RH 0.1% RH In the Operation mode, you cannot decrease the setpoint to less than the value set as the minimum dehumidify setpoint. The dehumidification 13. "Dehum setpnt Max " 80.0% RH 10.0 to 100.0% RH 0.1% RH In the Operation mode, you cannot increase the setpoint to more than the value set as the maximum dehumidification setpoint. The maximum value is restricted by the minimum value set at Step 12, "Dehum setpnt". In other words, the value that is set as the maximum cannot be less than the minimum value. The dehumidification 14. "Dehum setpnt" 60.0% RH 0 to 100.0% RH 0.1% RH Select the desired dehumidification setpoint of the zone in occupied operation mode. The setpoint value is restricted by the minimum at Step 10, "Dehum setpnt" and maximum at Step 11, "Dehum setpnt" values. The dehumidification symbol is also displayed. 15. "Hum setpnt Min " 10.0% RH 0.0 to 100.0% RH 0.1% RH In the Operation mode, you cannot decrease the setpoint to less than the value set as the minimum humidity setpoint. The minimum value is restricted by the maximum value set at Step 14, "Hum setpnt". In other words, the value that is set as the minimum cannot be greater than the maximum value. The humidity 16. "Hum setpnt Max " 80.0% RH 0.0 to 100.0% RH 0.1% RH In the Operation mode, you cannot increase the setpoint to more than the value set as the maximum humidity setpoint. The maximum value is restricted by the minimum value set at Step 13, "Hum setpnt". In other words, the value that is set as the maximum cannot be less than the minimum value. The humidity Page 7

8 17. "Hum setpnt" 40.0% RH 0.0 to 100.0% RH 0.1% RH Set the desired humidity setpoint. The setpoint value is restricted by the minimum at Step 13, "Hum setpnt" and at Step 14, "Hum setpnt" values. The humidity 18. "Humdty Mode", hun, Auto, and dhun Select the humidity mode that you want to authorize to the user. To authorize all the available modes, select Auto (Automatic Mode). The selection made at this step determines the options available on the Operation mode. The controller can be set in Humidification or Dehumidification mode or both. When both are used, the controller will request a humidity demand until the humidity setpoint is reached. If the humidity level increases to the dehumidify setpoint (should be higher than humidity setpoint), the controller will request a dehumidify demand, which usually activates air conditioning. The humidity CO2 Setpoints and Modes The CO2 configuration setpoints require a functioning humidity sensor installed. These setpoints appear only on the models with the CO2 sensor. For more information on supported models, see 'Error! Reference source not found.on page "CO2 Offset" Offset: 600 ppm ± 250 ppm 1.0 ppm Compare the displayed CO2 level reading with a known value from a CO2 sensing device. To offset or calibrate the sensor, use the arrow buttons to set the desired CO2 level reading. This is useful for controllers installed in areas where the CO2 level is slightly different than the prescribed value. The alarm icon appears in case of a sensor malfunction. 20. "CO2 Setpnt Min " ppm 0 to ppm 1.0 ppm In the Operation mode, you cannot decrease the setpoint to less than the value set as the minimum CO2 setpoint. The minimum value is restricted by the maximum value set at Step 19, "CO2 Setpnt". In other words, the value that is set as the minimum cannot be greater than the maximum value. The CO2 21. "CO2 Setpnt Max " 1500 ppm 0 to 2000 ppm 1.0 ppm In the Operation mode, you cannot increase the setpoint to more than the value set as the maximum CO2 setpoint. The maximum value is restricted by the minimum value set at Step 18, "CO2 Setpnt". In other words, the value that is set as the maximum cannot be less than the minimum value. The CO2 22. "CO2 Setpnt" ppm 400 to ppm 1.0 ppm Set the desired limit of the CO 2 concentration. The setpoint value is restricted by the maximum range at Step 19, "CO2 Setpnt". The CO2 Page 8

9 23. "CO2 Mode" ON ON and Select the desired CO2 sensor operation mode from the options: ON or to enable or disable the CO2 mode. When the CO2 mode is disabled and even if the CO2 is assigned to an analog or binary output, the CO2 value will not be calculated. The CO2 VOC Setpoints and Modes The VOC configuration setpoints require a functioning humidity sensor installed. These setpoints appear only on the models with the VOC sensor. For more information on supported models, see 'Error! Reference source not found.on page "VOC Offset" to ppb 1.0 ppb Compare the displayed VOC level reading with a known value from a VOC sensing device. To offset or calibrate the VOC sensor, use the arrow buttons to set the accurate VOC level reading. This is useful for controllers installed in areas where the VOC concentration is slightly different than the prescribed value. The alarm icon appears in case of a sensor malfunction. 25. "VOC Setpnt Min " 0 ppb 0 to 1000 ppb 1.0 ppb In the Operation mode, you cannot decrease the VOC setpoint to less than the value set as the minimum user point. The minimum value is restricted by the maximum value set at Step 24, VOC Setpnt. In other words, the value that is set as the minimum cannot be greater than the maximum value. The VOC 26. "VOC Setpnt Max " 1000 ppb 0 to 1000 ppb 1.0 ppb In the Operation mode, you cannot increase the setpoint to more than the value set as the maximum VOC setpoint. The maximum value is restricted by the minimum value set at Step 23, "VOC Setpnt". In other words, the value that is set as the maximum cannot be less than the minimum value. The VOC 27. "VOC Setpnt" 800 ppb 0 to 1000 ppb 1.0 ppb Set the desired limit of the VOC concentration. The setpoint value is restricted by the maximum value defined at Step 24, VOC Setpnt. The VOC 28. "VOC mode" and ON Select the desired VOC sensor operation mode from the options: ON or to enable or disable the VOC mode. When the VOC mode is disabled, and even if the VOC is assigned to an analog or binary output, the VOC value will not be calculated. The VOC Page 9

10 Analog Output 1 (AO1) 29. "AO1 Min Volt" 0 Volt 0 to 10 Volts 0.1 Volt Select the desired minimum voltage ( zero value) for the AO1 ramp. The minimum value is restricted by the maximum value at Step 28, "AO1 Max Volt". In other words, the minimum value should be less than the maximum value. 30. "AO1 Max Volt" 0 Volt 0 to 10 Volts 0.1 Volt Select the desired maximum voltage ( span value) for the AO1 ramp. The maximum value is restricted by the minimum value at Step 27, "AO1 Min Volt". In other words, the maximum value should not be less than the minimum value. 31. "AO1 Mode" HIGH HIGH and AvrG Select the desired AO1 mode from High or Average. This mode determines how the controller calculates the AO1 ramp output value (0-10Vdc unless the min/max values were changed). The controller compares all the assigned input values and uses either the highest value or the average of all values depending on the selected mode (High or AvrG). Assign one or more of the following input values to AO1 (steps 33 to 39): Fan Cool Heat Dehumidification Humidification CO2 VOC If the Fan Mode setting in the Operation mode is set to, the Analog Output will remain at a minimum voltage (default: 0Vdv). 32. "AO1 DIRREV" dir (Direct) dir (Direct), rev (Reverse) Set the desired direction of the analog signal to Direct (for example, 0 to 10Vdc) or Reverse (for example, 10 to 0Vdc). 33. "AO1 Fan" ON ON and Select the desired analog output fan mode from ON or. If the AO1 Mode is set to AvrG, the Fan value will not be calculated. The Fan 34. "AO1 Cool" ON and Select the desired analog output cooling to ON or. The Cooling Page 10

11 35. "AO1 Heat" ON and Select the desired analog output heating control from ON or. The heating 36. "AO1 DEHUM" ON and Select ON to enable or to disable the dehumidification mode that will be used in the operation mode. The dehumidification 37. "AO1 HUM" ON and Select ON to enable or to disable the analog output humidification mode that will be used in the operation mode. The humidity 38. "AO1 CO2" ON and Select ON or to enable or disable the analog output CO2 sensor. The CO2 functioning CO2 sensor installed. AO1 CO2 requires a 39. "AO1 VOC" ON and Select ON or to enable or disable the analog output VOC sensor. The Filtration function VOC requires a functioning VOC sensor installed. AO1 Analog Output 2 (AO2) All Analog Output 2 options are available only when the application profile 0 is selected. App Profile 0 describes the manual configuration that is used by advanced users. 40. "AO2 Min Volt" 0 Volt 0 to 10.0 Volts 0.1 Volt Select the desired minimum voltage ( zero value) for the AO2 ramp. The minimum value is restricted by the maximum value at Step Error! Reference source not found., Error! Reference source not found.. In other words, the minimum value should be less than the maximum value. 41. "AO2 MAX Volt" 100 Volts 0 to 100 Volts 0.1 Volt Select the desired maximum voltage ( span value) for the analog output 2. The maximum value is restricted by the minimum value at Step Error! Reference source not found., Error! Reference source not found.. In other words, the maximum value should not be less than the minimum value. Page 11

12 42. "AO2 MODE" HIGH HIGH and AvrG Select the AO2 control mode from Average to High. This mode determines how the controller calculates the AO2 ramp output value (0-10Vdc unless the min/max values were changed). The controller compares all the assigned input values and uses either the highest value or the average of all values depending on the selected mode (High or AvrG). Assign one or more of the following input values to AO1 (steps 44 to 50): Fan Cool Heat Dehumidification Humidification CO2 VOC If the Fan Mode setting in the Operation mode is set to, the Analog Output will remain at a minimum voltage (default: 0Vdv). 43. "AO2 DIRREV" dir (Direct) dir (Direct), rev (Reverse) Set the desired direction of the analog signal to Direct (for example, 0 to 10Vdc) or Reverse (for example, 10 to 0Vdc). 44. "AO2 fan" and ON Select the desired analog output fan mode from ON or. If the AO1 Mode is set to AvrG, the Fan value will not be calculated. The Fan 45. "AO2 COOL" and ON Select the desired analog output cooling to ON or. The Cooling 46. "AO2 HEAT" and ON Select the desired analog output heating control from ON or. The heating 47. "AO2 dehum" and ON Select ON to enable or to disable the dehumidification mode that will be used in the operation mode. The dehumidification Page 12

13 48. "AO2 HUM" and ON Select ON to enable or to disable the analog output humidification mode that will be used in the operation mode. The humidity 49. "AO2 CO2" and ON Select ON or to enable or disable the analog output CO2 sensor. The CO2 functioning CO2 sensor installed. AO2 CO2 requires a 50. "AO2 VOC" and ON Select ON or to enable or disable the analog output VOC sensor. The VOC functioning VOC sensor installed. AO2 VOC requires a Binary Output (BO1) 51. "BO1 MODE" HIGH HIGH and AvrG Select the desired BO1 mode from High or Average. This mode determines how the controller calculates the BO1 ramp output value. The controller compares all the assigned input values and uses either the highest value or the average of all values depending on the selected mode (High or AvrG). Assign one or more of the following input values to BO1 (steps 58 or 64): Fan Cool Heat Dehumidification Humidification CO2 VOC If the Fan Mode setting in the Operation mode is set to, the Binary Output will remain at a minimum voltage (default: 0Vdv). 52. "BO1 DIRREV" NO NO (Normally Open) and NC (Normally Close) Set the desired direction for the binary output1 from the options; NO (NO to NC) or NC (NC to NO). Page 13

14 53. "BO1 TPM HYST" HYST HYST and TPM Select the desired binary output 1 hysteresis from the options; HYST and TPM (Time Proportional Modulation). The hysteresis range is 0% (low) to High (20%). 54. "BO1 TPM CPH" 4 3, 4, and 8 CPH (cycle per hour) Set the desired binary output 1 TPM cycles per hour from the options: 3, 4, or "BO1 anti cycle sec" 0 sec 0 to 300 sec 1 sec Set the desired binary output 1 anti-cycle delay in seconds before activating or reactivating the cooling contact to protect the compressor. 56. "BO1 hyst low percnt" 20% 0 to 100% 1% Select the desired binary output 1 hysteresis low percentage. The hysteresis range is 0% (low) to High (30%). The minimum hysteresis value is restricted by the maximum high hysteresis value set at Step 55, Error! Reference source not found.. In other words, the minimum value should be less than the maximum value. 57. "BO1 hyst high percnt" Increment 80% 20 to 100% 1% Select the desired binary output 1 hysteresis high percentage. The maximum hysteresis value is restricted by the minimum high hysteresis value set at Step 54, Error! Reference source not found.. In other words, the maximum value should not be less than the minimum value. 58. "BO1 fan" ON and Select the desired operation mode of the fan for binary output 1 from the options; ON or. The Fan displayed. symbol is also 59. "BO1 cool" ON and Select the desired cooling mode for binary output 1 from the options: ON or. The Cooling 60. "BO1 heat" ON and Select the desired heating mode for binary output 1 from the options: ON or. The Heating Page 14

15 61. "BO1 dehum" ON and Select the desired dehumidification mode for binary output 1 from the options ON or to enable or disable the dehumidification. The BO1 dehumidification option requires a functioning humidity sensor. The dehumidification also displayed. symbol is 62. "BO1 hum" ON and Select the desired humidification mode for binary output 1 from the options ON or to enable or disable the humidification. The humidity The BO1 humidification option requires a functioning humidity sensor. 63. "BO1 co2" ON and Select the desired CO2 control mode for binary output 1 from ON or to control the CO2 level. The BO1 CO2 option requires a functioning CO2 sensor. The CO2 64. "BO1 voc" ON and Select the desired CO2 control mode for binary output 1 from ON or to control the CO2 level. The BO1 VOC option requires a functioning CO2 sensor. The VOC Binary Output 2 (BO2) 65. "BO2 mode" All Binary Output 2 objects are available only when the application profile 0 is selected. App Profile 0 describes the manual configuration that is used by advanced users. HIGH HIGH and AvrG Select the desired BO2 mode from High or Average. This mode determines how the controller calculates the BO2 ramp output value. The controller compares all the assigned input values and uses either the highest value or the average of all values depending on the selected mode (High or AvrG). Assign one or more of the following input values to BO2 (steps 72 to 78): Fan Cool Heat Dehumidification Humidification CO2 VOC If the Fan Mode setting in the Operation mode is set to, the Binary Output will remain at a minimum voltage (default: 0Vdv). Page 15

16 66. "BO2 DIRREV" NC NO and NC Set the desired direction for the binary output1 from the options; NO (NO to NC) or NC (NC to NO). 67. "BO2 TPM HYST" HYST HYST and TPM Select the desired binary output 2 hysteresis from the options; HYST and TPM (Time Proportional Modulation). The hysteresis range is 0% (low) to High (20%). 68. "BO2 TPM CPH" 4 3, 4, and 8 Set the desired binary output 2 TPM cycles per hour from the options: 3, 4, or "BO2 anti cycle sec" 0 sec 0 to 300 sec 1sec Set the desired binary output 2 anti-cycle delay in seconds before activating or reactivating the cooling contact to protect the compressor. 70. "BO2 hyst low percnt" Increment 20% 0 to 80% 1% Select the desired binary output 2 hysteresis low percentage. The hysteresis range is 0% (low) to High (30%). The minimum hysteresis value is restricted by the maximum high hysteresis value set at Step 69, Error! Reference source not found.. In other words, the minimum value should be less than the maximum value. 71. "BO2 hyst high percnt" Increment 80% 80 to 100% 1% Select the desired binary output 2 hysteresis high percentage. The maximum hysteresis value is restricted by the minimum high hysteresis value set at Step 68, Error! Reference source not found.. In other words, the maximum value should not be less than the minimum value. 72. "BO2 fan" ON and Select the desired operation mode of the fan for binary output 2 from the options; ON or. The Fan displayed. symbol is also Page 16

17 73. "BO2 cool" ON and Select the desired cooling mode for binary output 2 from the options: ON or. The Cooling 74. "BO2 heat" ON and Select the desired heating mode for binary output 2 from the options: ON or. The Heating "BO2 dehum". 75. "BO2 Dehum" ON and Select the desired dehumidification mode for binary output 2 from the options ON or to enable or disable the dehumidification. The BO2 dehumidification option requires a functioning humidity sensor. The dehumidification also displayed. symbol is 76. "BO2 hum" ON and Select the desired humidification mode for binary output 2 from the options ON or to enable or disable the humidification. The humidity The BO2 humidification option requires a functioning humidity sensor. 77. "BO2 co2" ON and Select the desired CO2 control mode for binary output 2 from ON or to control the CO2 level. The BO2 CO2 option requires a functioning CO2 sensor. The CO2 78. "BO2 voc" ON and Select the desired CO2 control mode for binary output 2 from ON or to control the CO2 level. The BO2 VOC option requires a functioning CO2 sensor. The VOC Analog and Binary Inputs (AI1 and BI1) 79. "AI1 mode" All Analog Input 1 and Binary Input 1 options are available only when the application profile 0 is selected. App Profile 0 describes the manual configuration that is used by advanced users., OAt, OCC, nsb, dft, FLS, and FLP Select the desired Analog Input 1 options from the following: - If selected, the controller does not use the input. OAT - If selected, the controller uses an outside air temperature sensor. OCC - If selected, the controller activates the occupancy status. Page 17

18 nsb - If selected, the controller activates the night set back status. dft - If selected, the controller activates an alarm to indicate that the filter is dirty. FLS - If selected, the controller activates an alarm to indicate that the airflow is absent. FLP - If selected, the controller activates an alarm to indicate that the airflow is absent. The controller shuts off all outputs. 80. "BI1 mode", OCC, nsb, dft, FLS, and FLP Select the desired Binary Input 1 options from the following: - If selected, the controller does not use the input. OCC - If selected, the controller activates the occupancy status. nsb - If selected, the controller activates the night set back status. dft - If selected, the controller activates an alarm to indicate that the filter is dirty. FLS - If selected, the controller activates an alarm to indicate that the airflow is absent. FLP - If selected, the controller activates an alarm to indicate that the airflow is absent. The controller shuts off all outputs. 81. "EXTRN TEMP SET" 0 0 C C to C [32ºF] [-50ºF to 50ºF] Adjust the calibration of the external sensor by comparison with a known thermometer. The display shows the temperature read by the external temperature sensor. Use the and keys to adjust the temperature read. 82. "AO1 OAT HI TEMP" 50 0 C 40 0 C to C C [122ºF] [104ºF to 257ºF] Set the desired heating outside air high-temperature limit for the analog input 1. This setpoint appears when 'OAT' is selected in the step 77, "AI1 mode". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc). 83. "AO1 OAT low TEMP" C C to C C [-104ºF] [-104ºF to 257ºF] Set the desired heating outside air low-temperature limit for the analog input 1. If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc). 84. "AO2 OAT HI TEMP" 50 0 C 40 0 C to C C [122ºF] [104ºF to 257ºF] Set the desired heating outside air high-temperature limit for the analog input 2. This setpoint appears when 'OAT' is selected in the Step 77, "AI1 mode". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc). Page 18

19 85. "AO2 OAT low TEMP" C C to C C [-104ºF] [-104ºF to 257ºF] ARO Series Universal Room Controller Set the desired heating outside air low-temperature limit for the analog input 1. The minimum value is restricted by the value set at Step 82, "AO2 OAT HI TEMP". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc). 86. "BO1 OAT HI TEMP" 50 0 C 40 0 C to C C [122ºF] [104ºF to 257ºF] Set the desired heating outside air high-temperature limit for the binary output 1. This setpoint appears when 'OAT' is selected in the Step 77, "AI1 mode". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc). 87. "BO1 OAT low TEMP" C C to C C [-104ºF] [-104ºF to 257ºF] Set the desired heating outside air low-temperature limit for the binary output 1. The minimum value is restricted by the value set at Step 86, "BO1 OAT HI TEMP". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc). 88. "BO2 OAT HI TEMP" 50 0 C 40 0 C to C C [122ºF] [104ºF to 257ºF] Set the desired heating outside air high-temperature limit for the binary output 2. This setpoint appears when 'OAT' is selected in the Step 77, "AI1 mode". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc). 89. "BO2 OAT low TEMP" C C to C C [-104ºF] [-104ºF to 257ºF] Set the desired heating outside air low-temperature limit for the binary output 2. This setpoint appears when 'OAT' is selected in the Step 77, "AI1 mode". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc). 90. unocc cool setpnt min 10ºC 0ºC to 10ºC [50ºF] [32ºF to 50ºF] Set the minimum cooling setpoint when the zone is in unoccupied mode. This setpoint appears when 'Occupancy' is selected in the Step 77, "AI1 mode" and Step 78, "BI1 mode". The minimum value is restricted by the maximum value set at Step 89, " unocc cool setpnt". In other words, the value that is set as the minimum cannot be greater than the maximum value. 91. unocc cool setpnt max 40ºC 10ºC to 125ºC [104ºF] [50ºF to 257ºF] Set the maximum cooling setpoint when the zone is in unoccupied mode. This setpoint appears when 'Occupancy' is selected in the Step 77, "AI1 mode" and Step 78, "BI1 mode". The maximum value is restricted by the minimum value set at Step 88, unocc cool setpnt. In other words, the value that is set as the maximum cannot be less than the minimum value. Page 19

20 92. unocc cool setpnt 32ºC 0ºC to 32ºC [89.6ºF] [32ºF to 89.6ºF] In the Operation mode, you cannot increase the unoccupied heat setpoint to more than the value set as the unoccupied cooling setpoint. This setpoint appears when 'Occupancy' is selected in the Step 77, "AI1 mode" and Step 78, "BI1 mode". The cooling symbol is displayed. 93. "UNOCC HEAT setpnt Min 10ºC 0ºC to 40ºC [50ºF] [32ºF to 122ºF] Set the minimum heating setpoint when in unoccupied mode. This setpoint appears when 'Occupancy' is selected in the Step 77, "AI1 mode" and Step 78, "BI1 mode". The minimum value is restricted by the maximum value set at Step 92, "UNOCC HEAT setpnt". In other words, the value that is set as the minimum cannot be greater than the maximum value. 94. "UNOCC HEAT setpnt MAX " 40ºC 0ºC to 125ºC [104ºF] [32ºF to 257ºF] Set the maximum heating setpoint when in unoccupied mode. This setpoint appears when 'Occupancy' is selected in the Step 77, "AI1 mode" and Step 78, "BI1 mode". The maximum value is restricted by the minimum value set at Step 91, UNOCC HEAT setpnt. In other words, the value that is set as the maximum cannot be less than the minimum value. 95. "UNOCC HEAT setpnt" 18ºC 0ºC to 125ºC [64.4ºF] [32ºF to 257ºF] In the Operation mode, you cannot increase the unoccupied heat setpoint to more than the value set as the maximum unoccupied heating setpoint. This setpoint appears when 'Occupancy' is selected in the Step 77, "AI1 mode" and Step 78, "BI1 mode". The heating symbol is displayed. PI (Proportional-Integral) Band 96. "cool p band" 5ºC 2ºC to 50ºC [41ºF] [35.6ºF to 122ºF] Select the desired proportional band value of the cooling ramp. The cooling 97. "heat p band" 5ºC 2ºC to 50ºC [41ºF] [35.6ºF to 122ºF] Select the desired proportional band value of the heating ramp. The heating BO2 OAT HI TEMP 98. "humdty p band" 5ºC 2ºC to 50ºC [41ºF] [35.6ºF to 122ºF] Select the desired proportional band value of the humidity ramp. The humidity Page 20

21 99. "co2 p band" 500 ppm 0 to 2000 ppm 1 ppm Select the desired proportional band value of the CO2 ramp. The CO "voc p band" 500 ppb 10 to 1000 ppb 1 ppb Select the desired proportional band value of the VOC ramp. The VOC 101. "cool i time sec" 60 Seconds 1 to 120 Seconds 1 Second Set the desired value for cooling integral factor compensation. The cooling 102. "heat i time sec" 60 Seconds 1 to 120 Seconds 1 Second Set the desired value for heating integral factor compensation. The heating 103. "humdty i time sec" 60 Seconds 1 to 120 Seconds 1 Second Set the desired value for humidity integral factor compensation. The humidity symbol is displayed symbol is also displayed 104. "co2 i time sec" 60 Seconds 1 to 120 Seconds 1 Second Set the desired value for CO2 integral factor compensation. The CO "voc i time sec" 60 Seconds 1 to 120 Seconds 1 Second Set the desired value for VOC integral factor compensation. The VOC Network Settings 106. "select netwrk proto" bac bac and mod Select the desired network communication protocol from the options: BACnet or Modbus. Page 21

22 BACnet 107. "bacnet baud rate" Auto Auto, 9.6k, 19.2k, 38.4k, 57.6K, and 76.8k Set the desired MS/TP baud rate setting from the options: 9600, 19200, 38400, or that will be used in the Operation mode. The default option is Auto, and when selected, the controller automatically configures its baud rate by detecting the network speed upon connection to the network. If you enabled Auto Baud Rate Detection at Step 106, "BACnet Auto Bauds Rate" the controller displays the automatically detected baud rate "bacnet auto bauds rate" Auto Auto, 9.6k, 19.2k, 38.4k, 57.6K, and 76.8k The default option is Auto, and when selected, the controller automatically configures its baud rate by detecting the network speed upon connection to the network "mstp mac addrss" 0 1 to Select the desired MSTP MAC Address. Each device on the network must have a unique MAC address "mstp max master" to Select the desired MSTP MAX address for the master device "adjust device inst " No No, Yes To change the device instance, select Yes and continue to the next step. If you select No, the device instance will be modified automatically according to the MAC address "015325" Current Value 0 to Use the arrow keys to change the value and press the device instance. button to move to the next digit. Ensure that you provide a unique Modbus 113. "modbus baud rate" No default (information display only) 9.6k, 19.2k, 38.4k, 57.6k Select the desired Modbus baud rate. If you enabled Modbus Auto Baud Rate Detection, the controller displays the automatically detected baud rate. Page 22

23 114. "modbus port config" NP2S NP2S, "OP1S", "EP1S" Select the desired parity and number of stop bits for the modbus communication. Select from the following options: 0= No parity, 2 Stop bits 1= Even parity, 1 stop bit 2= Odd parity, 1 stop bit 115. "modbus addrss" 1 1 to 246 Select the desired Modbus address from the range: 1 to 246]. Each device on the network must have a unique Modbus address "local unit" MET 0 C MET 0 C and ImP 0 F Select the unit type that will be displayed on the controller in the Operation mode. The default unit is Metric "auto scroll" ON ON and Select the desired status of the auto-scroll of sensor readings in the Operation mode. Page 23

24 Operation Mode ARO Series Universal Room Controller The Mode Selector Jumper (JP3) must be set to the "RUN" mode (Operation Mode). For more information, see Wiring. Press to change setpoint Press to change setpoint Press to change setpoint Press to change setpoint Auto scroll or press F % Auto scroll or press Auto scroll or press Press Press Press to change temp mode: Auto Heat Cool Off Press to change RH mode: Auto HUM DEHUM Press to change CO2 mode: ON Press to adjust The displayed setpoint. Press to change system mode: ON Press to change fan mode: Auto ON Power Up Upon power up, the LCD illuminates, and all segments appear for 2 seconds. The controller then displays its current version for 2 seconds. LCD Backlight Pressing any key illuminates the LCD for 4 seconds. Night Set Back (NSB) Mode This function is only available if you have set input to nsb (Night Set Back contact). If the contact is triggered, the controller enters NSB Mode (the symbol appears) and uses the NSB setpoints defined at Steps, "NSB Heating Setpnt", "NSB Cooling Setpnt" and "NSB Fan Mode". Press any key to override NSB for the delay defined at Step, NSB Override Delay Minutes. The symbol flashes to indicate that the NSB mode is overridden (during this time the standard setpoints are used). No Occupancy Mode This function is only available if you have set input to OCC (occupancy contact). If the contact is triggered and the minimum occupancy time defined at Step 103, "OCC Minimum Time In Minutes" has elapsed, the controller enters Occupancy Mode (the symbol appears) and uses the OCC setpoints defined at Steps 107, "No OCC Heating Setpnt", 108 "No OCC Cooling Setpnt" and 105, "No OCC Fan Mode". Press the star * button to override no occupancy. Each time you press the star * button, 15 minutes are added to the override up to a maximum defined by Step 104, "No OCC Override Delay Minutes". Press the star * button until 0 is displayed to disable the override. The icon will flash and the remaining override time will be displayed in minutes. Page 24

25 Appendix - Application Profiles This appendix provides additional information about the application profiles (App Profiles) used in the ARO Series Universal Room Controller. APP PROFILE 1 Outside Air Application (Temperature only) Exhaust Fan Outside ECM T INT When selecting the option "1" from the application profiles menu, the ARO automatically configures the following options: AO1 AO2 BO1 BO2 AI BI System Modes Demand Source Fan Demand Source Fan Configuration Occupancy Main System On Control Mode Highest Control Mode Highest Temperature Auto Direction Direct Direction Direct Humidity Off Min. Value 0% TPM/Hysteresis Hysteresis CO2 Off Max. Value 100% Hysteresis Low 0% VOC Off Hysteresis High 20% JP3 A B C PGM RUN JP1 A B C A B C JP2 TB : COM 2: 24Vac 4: BO1 (-) Common (+) 24Vac XFO N (-) Common (+) 24 Vac Signal Auxiliary Contact / End switch Line Voltage L On/Off Supply Damper : BI1 11: AI (-) Common (+) 24 Vac Signal Auxiliary Contact / End switch On/Off Supply Damper Normally Opened 15 JP5 A B C EOL (-) Common (+) 24 Vac Signal Modulating Fan (ECM Motor) Page 25

26 APP PROFILE 2: Conference Room (Temp, RH, and CO 2 ) When selecting the option "2" from the application profiles menu, the ARO automatically configures the following options: AO1 AO2 BO1 BO2 AI BI System Modes Demand Source Fan Demand Source Fan Configuration Occupancy Main System On Control Mode Average Control Mode Average Temperature Auto Direction Direct Direction Direct Humidity Auto Min. Value 0% TPM/Hysteresis Hysteresis CO2 On Max. Value 100% Hysteresis Low 0% VOC Off Hysteresis High 20% Page 26

27 Notes ARO Series Universal Room Controller

28 Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult Lebeau blvd, Montreal, Qc, H4N 1R6, Canada Toll free in North America: Tel.: (514) Fax: (514) Customer service fax: (514) Monday to Friday: 8:00am to 5:00pm (Eastern time)

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color.

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color. TDU Series LCD Thermostat Models Model # Temp RH CO2 Color TDU10-100 TDU10-101 TDU10-102 TDU10-103 grey LCD white enclosure TDU10 Series Model # Temp RH CO2 Color TDU40-100 TDU40-101 TDU40-102 TDU40-103

More information

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication Description The TFHB24F3XYZ1 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications.

More information

Networkable Fan Coil Controller Specification and Installation Instructions

Networkable Fan Coil Controller Specification and Installation Instructions Controller Models EFCB10T-OE1 (24Vac / 0 relays) EFCB12T-OE1 (240Vac / 0 relays) EFCB10TU4-OE1 (24Vac / 4 relays) EFCB12TU2-OE1 (240Vac / 2 relays) EFCB12TU4-OE1 (240Vac / 4 relays) TFL Series Thermostat

More information

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1 Model TRO24T4XYZ1 Description The TRO24T4XYZ1 is a combination controller and thermostat. The VAV Thermostat Controller is designed for simple and accurate control of any variable air volume box in a number

More information

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422 ºF / º C Rooftop Thermostat Controller Model TRT2422 Description The TRT2422 is a combination controller and thermostat with a built-in scheduler, which is designed for simple and accurate control of single

More information

Humidity Controller Specification and Installation Instructions. Model HRO20

Humidity Controller Specification and Installation Instructions. Model HRO20 Model Description The Humidity Controller is an advanced application to control relative humidity for general purpose applications. They are specially designed to control humidifiers and dehumidification

More information

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor Model TFH24FXYZ2 Stand-alone with Internal Humidity Sensor Description The TFH24FXYZ2 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications. No additional

More information

± 3% or better at 40%RH and 23ºC [73ºF] 0.8 mm 2 [18 AWG] minimum

± 3% or better at 40%RH and 23ºC [73ºF] 0.8 mm 2 [18 AWG] minimum Room Humidistat Features: Attractive modern look with large LD and backlight Icons driven information and 1 line of text External humidity sensor input Humidification and dehumidification indicator Multi

More information

Fan Coil Thermostat. Specification & Installation Instructions TFC54F3Y1. Technical Data

Fan Coil Thermostat. Specification & Installation Instructions TFC54F3Y1. Technical Data Fan Coil Thermostat Features: Selectable pipe or 4 pipe system Selectable control mode Selectable fan speed contact Selectable Fahrenheit or Celsius scale Manual Night Set Back override (programmable)

More information

Networkable VAV Controller Specification and Installation Instructions. Controller Model EVCB14NIT4X (4 TRIACS / independent / external motor)

Networkable VAV Controller Specification and Installation Instructions. Controller Model EVCB14NIT4X (4 TRIACS / independent / external motor) Controller Model EVCB14NIT4X (4 TRIACS / independent / external motor) For use with external floating or modulating actuators TRL Series Thermostat TRL24 (Thermostat 2x4) TRLH24 (Thermostat 2x4 with Humidity)

More information

Humidity Controller Specification and Installation Instructions. Model HROB20

Humidity Controller Specification and Installation Instructions. Model HROB20 Model Description The Humidity Controller is a combination controller and humidistat with support for networked communications via the BACnet MS/TP protocol. The Humidity Controller is an advanced application

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Networkable VAV Controller Specification and Installation Instructions

Networkable VAV Controller Specification and Installation Instructions Networkable VAV ontroller ontroller Models EVB14NIT0S EVB14NIT2S EVB14NIT4S EVB14NDT4S EVB14NIT0SF EVB14NIT4SF (0 TRIAS / pressure independent) (2 TRIAS / pressure independent) (4 TRIAS / pressure independent)

More information

Direct Steam Injection Humidifier

Direct Steam Injection Humidifier SKD-J (Jacketed) Series For the following configurations: Jacketed Single Tube Mini Rack Multi-Tube READ AND SAVE THESE INSTRUCTIONS SKD-J Humidifier Manual-180704-ESL Foreword and Safety Instructions

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS SKD-M Series Direct Steam Injection Humidifier For the following configuration: Multi-Steam SD (Standard) Multi-Steam HD (with X-Stream Technology) READ AND SAVE THESE INSTRUCTIONS SKD-M Humidifier Manual-180704-ESL

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

Pressurized Condensate Return System (PCR)

Pressurized Condensate Return System (PCR) (PCR) For use with SKD Direct Steam Injection Humidifiers READ AND SAVE THESE INSTRUCTIONS PCR Manual-180411-R2-ESL Neptronic Company Overview Foreword and Safety Instructions Founded in 1976, we re a

More information

Multi-Steam HDR* SKD-R Series Direct Steam Injection Humidifier with Integrated Re-Evaporator. Installation Instructions and User Manual

Multi-Steam HDR* SKD-R Series Direct Steam Injection Humidifier with Integrated Re-Evaporator. Installation Instructions and User Manual * SKD-R Series Direct Steam Injection Humidifier with Integrated Re-Evaporator For the following configuration: Multi-Steam with Integrated Re-Evaporator Includes integrated Re-Evaporator and X-Stream

More information

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs TEC2620 Series Non-Programmable Fan Coil Network Thermostat ler and Remote I/O Relay Packs TEC2620H-0, TEC2620C-0, TEC2620H-0+PIR, TEC2620C-0+PIR, TEC2621H-0, TEC2621C-0, TEC2621H-0+PIR, TEC2621C-0+PIR

More information

CLEANROOM MONITOR CR3A Network - Installation Instructions

CLEANROOM MONITOR CR3A Network - Installation Instructions CLEANROOM MONITOR CR3A Network - Installation Instructions INTRODUCTION The CR3 Series Cleanroom Monitor, was developed specifically to allow for monitoring of confined spaces with accuracy and reliability.

More information

T600MEP-2 Programmable Economizer Thermostat

T600MEP-2 Programmable Economizer Thermostat Installation Instructions Issue Date January 19, 2005 T600MEP-2 Programmable Economizer Thermostat Application The T600MEP-2 is a programmable thermostat for control of single- or two-stage unitary rooftop

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide SE8600 Series Room Controllers 2 TABLE OF CONTENTS Overview 2 SE8600 Rooftop Unit and Indoor Air Quality Controllers 3 SE8600UxBxx 2 Heating

More information

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings ETNC-FC-BAC-PIR- Rev. Index Operating instructions....- Turning the thermostat and OFF Selecting temperature scale Adjusting the Set point temperature (for set point and set points configurations) Selecting

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1234-1 BACnet Thermostat Group: Applied Air Systems Part Number: IM 1234 Date: December 2014 Use with Daikin MicroTech Integrated Systems or as standalone Table of

More information

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Product Bulletin T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4, T601DFH-4+PIR, T602DFH-4+PIR,

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT86X0U5X00B 2 heating / 2 Cooling for Rooftop unit and Indoor air quality 3

More information

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.

More information

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors Product sheet SN1.402 Type CDR-AL CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors CDR-AL sensors are designed to detect carbon dioxide concentration and temperature in the room spaces. The units

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

TEC210x-2 Series Networked Thermostats

TEC210x-2 Series Networked Thermostats Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

TEC2100 Series Networked Thermostats

TEC2100 Series Networked Thermostats Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT8600 Rooftop Unit Heat Pump and Indoor Air Quality Controllers 3 VT86X0U5X00B

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

VH7200 Humidistat Series For Humidification & Dehumidification Control For Commercial HVAC Applications (Issue Date January 22, R7)

VH7200 Humidistat Series For Humidification & Dehumidification Control For Commercial HVAC Applications (Issue Date January 22, R7) VH7200 Humidistat Series For Humidification & Dehumidification Control For Commercial HVAC Applications (Issue Date January 22, 2013 028-0208 R7) 1 Product overview The VH7200 humidity controller family

More information

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE OWNER S MANUAL COMMERCIAL THERMOSTAT P/N P374-2800 I 2 : 0 0 Su AUTO Pm 74 COOL 7 2 HEAT T O T A L I N E HEAT COOL 7-DAY HEAT PUMP PROGRAMMABLE DIGITAL THERMOSTAT 3 Configurable Outputs Control up to 2

More information

User s Manual

User s Manual 997-060180-4e User s Manual 8403-060 Menu Driven Display 1120-445 I. CONTROLLER OPERATION ADJUSTING TEMPERATURE (Temporary Override when in Programmable mode) 1. Before you can adjust the temperature,

More information

INSTALLATION & USER MANUAL

INSTALLATION & USER MANUAL INSTALLATION & USER MANUAL HC Digital Automatic Humidistat (Y3760) CONTROLS 506808-01 3/2016 Supersedes 6/2011 picture goes here THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE NOTICE

More information

Smart thermostat with Humidification/De-humidification control

Smart thermostat with Humidification/De-humidification control x Smart thermostat with Humidification/De-humidification control Enter/Confirm Scroll Right = Increase Left = Decrease Back/Cancel TABLE OF CONTENTS Everyday Use 1. Adjusting Temperature...3 2. Adjusting

More information

HEAT COOL. Meets Commercial California Title 24

HEAT COOL. Meets Commercial California Title 24 Digital Thermostat commercial THERMOSTAT T2900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers & Deadbands

More information

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

HEAT HEAT HEAT COOL COOL

HEAT HEAT HEAT COOL COOL OWNER S MANUAL AUTO 74 COOL 7 2 HEAT T O T A L I N E HEAT COOL COMMERCIAL THERMOSTAT P/N P374-2700 HEAT PUMP NON-PROGRAMMABLE DIGITAL THERMOSTAT 3 Configurable Outputs Control up to 2 Heat & 2 Cool Stages

More information

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings Touch Screen Thermostat MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series MTS/SUPER/CO2, MTS24/SUPER/CO2 Series Owner s manual and technician settings Rev. 2.4 Index 1. Owner s Manual... 3 1.1 Quick Guide. 4 1.2

More information

TB7300 Series Communicating Fan Coil Thermostats 24 VAC/FOR COMMERCIAL AND LODGING HVAC APPLICATIONS

TB7300 Series Communicating Fan Coil Thermostats 24 VAC/FOR COMMERCIAL AND LODGING HVAC APPLICATIONS TB7300 Series Communicating Fan Coil Thermostats /FOR MERCIAL AND LODGING HVAC APPLICATIONS APPLICATION INSTALLATION INSTRUCTIONS The TB7300 PI thermostat family is specifically designed for fan coil control.

More information

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE Emerson Blue Wireless Comfort Interface - Homeowner User Guide Message to Homeowners Congratulations on choosing the Emerson Blue

More information

TER Active Room Temperature Sensor (Controller),

TER Active Room Temperature Sensor (Controller), Product sheet SN1.415 Type TER TER Active Room Temperature Sensors (Controllers) The TER active sensors are designed to detect temperature in the room spaces. The TER sensors have linear 0..10V signals

More information

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page Code. LIT-1900896 Issued February 17, 2017 TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page Description The TEC3000 Series Thermostat

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat residential THERMOSTAT T1 800 7-DAY PROGRAMMABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat commercial SCHOOL THERMOSTAT T2900SCH MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Energy Saving Operation Morning Warm-up Period Programmable Override Unoccupied until button press

More information

INSTALLATION MANUAL. This manual covers TopTech models: TT-S-755H. Need Help? Thermostat Applications Guide. Power Type. Table of Contents.

INSTALLATION MANUAL. This manual covers TopTech models: TT-S-755H. Need Help? Thermostat Applications Guide. Power Type. Table of Contents. INSTALLATION MANUAL This manual covers TopTech models: TT-S-755H Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a fieldselectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

Instruction Guide: Thermostat Operation

Instruction Guide: Thermostat Operation Instruction Guide: Elite Communicating Thermostats TPCM32U03*/TPCM32U04* (*GSR, GSM, TRN, AST) INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT Thermostat Operation NOTE: These communicating thermostats

More information

RC-2000 Thermostat Installation Instructions

RC-2000 Thermostat Installation Instructions RC-2000 Thermostat Installation Instructions DESCRIPTION The RC-2000 is a precision digital thermostat designed for 24 VAC heating and cooling systems. The RC-2000 will support the following systems: Single

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8800 Universal Communicating Thermostat Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 2 Thermostat mounting...

More information

TEC Networked Multi-Stage Thermostat

TEC Networked Multi-Stage Thermostat Installation Instructions Issue Date September 2, 2003 TEC2103-1 Networked Multi-Stage Thermostat Application The TEC2103-1 is an N2 networked thermostat that provides control of multi-stage Heating, Ventilating,

More information

TB7200 Series Communicating Zone Thermostats

TB7200 Series Communicating Zone Thermostats TB7200 Series Communicating Zone Thermostats TB7200 Series Thermostat INSTALLATION INSTRUCTIONS APPLICATION The TB7200 Series PI thermostat family is specifically designed for zoning applications. The

More information

INSTALLATION MANUAL. Need Help? This manual covers the following models: T725. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T725. Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers the following models: T725 Thermostat Applications Guide Des cription Gas or Oil Heat Electric Furnace Heat Pump ( Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical Service Literature Corp. 0808 L6 06/08 IMC BACnet Module General The IMC BACnet Module (BP1) allows communication between the Lennox IMC M1 8 controller and a BACnet MS/TP network. This module is mounted

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

CONTENTS. Installation Guide. VT7200 Series

CONTENTS. Installation Guide. VT7200 Series VT7200 Series Installation Guide For mercial HVAC Applications November 2015 CONTENTS Installation 2 Location 2 Installation 2 Configurable BI/UI inputs overview 4 Network ready 6 Terminal, Identification

More information

TEC Networked Multi-Stage Economizer Thermostat

TEC Networked Multi-Stage Economizer Thermostat Installation Instructions Issue Date January 19, 2005 TEC2104-2 Networked Multi-Stage Economizer Thermostat Application The TEC2104-2 thermostat is an N2 networked thermostat that provides control of single-

More information

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers the following models: T755 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat Installation and operation instructions The ONX908PIT-V1-S1-F1 modulating digital thermostats are designed to provide Proportional-Integral (PI) modulating

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

CLEVER CONTROL Version: V3

CLEVER CONTROL Version: V3 CLEVER CONTROL Version: V3 INSTALLATION AND FUNCTIONING MANUAL USER AND BASIC VERSION Please, read these instructions carefully before attempting installation SECURITY ADVISE SIMBOLS Attention, Danger,

More information

BAC-4000 Series AppStat

BAC-4000 Series AppStat BAC-4000 Series AppStat Description The KMC AppStat combines the power of a space mounted equipment controller with the convenience of built-in temperature, humidity and motion sensors. The controllers

More information

Installation Instructions

Installation Instructions TP --- PRH --- A, TP --- NRH --- A PerformancetSeries Edger Thermidistatt Control Installation Instructions Programmable Control A07049 A07048 Non---Programmable Control NOTE: Read the entire instruction

More information

Bacnet Room Setpoint & Temp Display. Descriptions. Specifications

Bacnet Room Setpoint & Temp Display. Descriptions. Specifications Descriptions Bacnet Room Setpoint & Temp Display is designed for environment monitoring and controlling in industrial, commercial and other buildings. These transmitters can be used to monitor air temperature

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

Series Digital Controller Instruction Sheet

Series Digital Controller Instruction Sheet 216/3/11 Series Digital Controller Instruction Sheet Thank you very much for purchasing DELTA DTC Series Temperature Controller. Please read this instruction sheet before using your DTC series to ensure

More information

INSTALLATION MANUAL. Need Help? This manual covers TopTech models: TT-N-721 and T721. Power Type. Thermostat Applications Guide.

INSTALLATION MANUAL. Need Help? This manual covers TopTech models: TT-N-721 and T721. Power Type. Thermostat Applications Guide. INSTALLATION MANUAL This manual covers TopTech models: TT-N-721 and T721 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump ( Aux. or Emergency Heat) Heat Pump (with Aux.

More information

VT7600 Series Programmable & Non-Programmable Thermostats With Humidification & Dehumidification Strategy For Commercial HVAC Applications

VT7600 Series Programmable & Non-Programmable Thermostats With Humidification & Dehumidification Strategy For Commercial HVAC Applications VT7600 Series Programmable & Non-Programmable Thermostats With Humidification & Dehumidification Strategy For Commercial HVAC Applications (Issue Date June 12, 2008 028-0171 R5 Product overview The VT76x7

More information

Series Temperature Controller Instruction Sheet

Series Temperature Controller Instruction Sheet Series Temperature Controller Instruction Sheet Thank you very much for purchasing DELTA A Series. Please read this instruction sheet before using your A series to ensure proper operation and please keep

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Manual for the integration in BMS/GTC

Manual for the integration in BMS/GTC Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat residential THERMOSTAT T1 900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP with HUMIDITY CONTROL Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd &

More information

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers TopTech models: TT-N-851 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

Models Available. Features and benefits. Through the network or smart local occupancy sensing. Advanced occupancy functions

Models Available. Features and benefits. Through the network or smart local occupancy sensing. Advanced occupancy functions PIR Ready VT76X7 Series Programmable & Non-Programmable Thermostats With Humidification & Dehumidification Strategy For Commercial HVAC Applications September 1, 2010 Product overview The VT76x7 PI thermostat

More information

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B 2 CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B CAUTION CAUTION - ONLY TRAINED, QUALIFIED PERSONNEL SHOULD INSTALL AND/OR SERVICE CLIMATEMASTER EQUIPMENT. SERIOUS

More information

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help? INSTALLATION MANUAL This manual covers the following models: T955W Master Thermostat Base Module Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency

More information

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Product Bulletin T606MSN-4, T606MSN-4+PIR, T606MSP-4, T606MSP-4+PIR The T606MSN-4 and T606MSN-4+PIR Series Non-programmable

More information

ATC32U03 igate Communicating, Programmable Thermostat

ATC32U03 igate Communicating, Programmable Thermostat ATC32U03 igate Communicating, Programmable Thermostat User Manual 97B0055N02 Rev.: 11/3/17 Table of Contents Section Title Page Menu Navigation Shortcuts 3 1.0 Operating Mode Selection 3 2.0 Temperature

More information

Installer Guide. WARNING Important Safety Information. 1 Specifications

Installer Guide. WARNING Important Safety Information. 1 Specifications 1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Conventional and Heat Pump Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE READ ALL

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

ETN-24-SUPER-PROG (US Program - Celsius)

ETN-24-SUPER-PROG (US Program - Celsius) Meitavtec Ltd (Contel group) Tel: 972 (3) 962 6462 Fax: 972 (3) 962 6620 www.meitavtec.com support@meitavtec.com ETN24SUPERPROG (US Program Celsius) Owner s Manual Installation and Operating Instructions

More information

T-32-TS Touchscreen Thermostat. Installation Manual

T-32-TS Touchscreen Thermostat. Installation Manual T-32-TS Touchscreen Thermostat Installation Manual TABLE OF CONTENTS Introduction...4 Getting Started...5 Installing the Thermostat...6, 8 Disassembly...6 Thermostat Location...6 Mounting the Subbase...6,

More information