Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Size: px
Start display at page:

Download "Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison"

Transcription

1 Emerging Technologies: VFDs for Condensers Douglas T. Reindl Director, IRC University of Wisconsin-Madison University of Wisconsin-Madison 1

2 We ve looked at VFDs on Evaporators and compressors, what is the potential for application on condensers? 2

3 Head Pressure Control Our heat rejection system controls head pressure Evaporative condenser fan controls on/ (single speed fans) two-speed fans variable speed fans 3

4 Floating Head Pressure Control Consequences of lowering head pressure increased evaporative condenser energy use decreased compressor energy use reduced high stage compression (on average) Does the decrease in compressor energy use outweigh the increase in condenser fan energy use??? 4

5 Optimum Head Pressure Axial Fan T Compressor+Condenser oa,wb =78 F Power (kw) Compressor T cond,opt = 87.1 F Condenser Saturated Condensing Temperature (F) 5

6 Optimum Head Pressure 300 Centrifugal Fan T oa,wb =78 F 250 Power (kw) Compressor+Condenser Compressor Condenser T cond,opt = 89.9 F Saturated Condensing Temperature (F) 6

7 Optimum Head Pressure Depends on: Condenser fan type (axial vs. centrifugal) Fan control strategy Condenser sizing strategy 95 F saturated condensing (historic) 90 F saturated condensing (recommended) 85 F saturated condensing (possible not practical) 7

8 Case Study: Cold Storage Warehouse Size 34 F 39,000 (ft²) 0 F 52,000 (ft²) 600,000 (lbs/day, food) Type ammonia, single-stage compression, liquid overfeed evaporators Operating Costs 9,000 ($/month) 4 Compressors Available Instrumentation Temp, Pressure, Mass Flow! Defrost Strategies Head Pressure Control The refrigeration system examined as part of this case study is a cold storage warehouse facility located near Milwaukee, WI. The facility contains four types of refrigerated spaces low temperature freezer (0 F), cooler (34 F), docks (45 F), and ripening rooms (45-64 F). From a thermal mass perspective, the warehouse construction type can be considered lightweight for all spaces. There is mostly insulation and very little mass in the walls and roofs. The freezer and cooler with its loading dock are separate buildings located adjacent to each other. The banana and tomato ripening rooms are located in a heated space adjacent to the cooler. The refrigerant used throughout this system is ammonia (R-717). Evaporators in the freezer are top fed, pumped liquid overfeed. Cooler, and cooler dock evaporators are all bottom feed pumped liquid overfeed where as the evaporators in the banana and tomato ripening rooms are direct expansion controlled by thermal expansion valves and back pressure regulators. (NOTE: This case study was conducted by Manske, K. A. in partial fulfillment of the requirements for a MS degree in Mechanical Engineering under the direction of Professor s Reindl, D. T., and Klein, S.A. during Portions of the thesis prepared by Mankse titled Performance Optimization of Industrial Refrigeration Systems, 1999 have been excerpted for this section. A complete copy of the Manske thesis is available for download at: 8

9 Case Study: Cold Storage Warehouse Q reject HPR Condenser F D X Evap Q spac e Design Loads BPR Fruit Ripening = 90 tons Cooler = 107 tons Freezer = 106 tons PLO Evap Q spac e PLO Evap Q spac e 23 F -10 F Yearly Average Loads Fruit Ripening = 43 tons Cooler = 58 tons Freezer = 71 tons There are three main vessels in the system as shown above. The first is the high pressure receiver where liquid refrigerant draining from the condenser is stored. Liquid refrigerant from the high pressure receiver is then throttled to either the intermediate pressure receiver or to the direct expansion evaporators in the banana and tomato ripening rooms. The temperature of the refrigerant in the banana/tomato room evaporators is regulated at a desired level by use of a back-pressure regulator. The back-pressure regulator then throttles the refrigerant gas to the intermediate pressure receiver which is at a lower temperature/pressure. Liquid in the intermediate pressure receiver is then either pumped to the cooler and cooler dock evaporators or throttled again to the low pressure receiver. Liquid refrigerant from the low pressure receiver is pumped to freezer evaporators with a mechanical liquid recirculating pump. Liquid levels in the intermediate and low pressure receivers are maintained at a near constant level by a pilot operated, modulating expansion valve controlled by a float switch located on the receiver tank. A single-screw (Vilter model# VSS 451 connected to the low temperature vessel) and reciprocating compressor (Vilter model# VMC 4412 connected to the high temperature vessel) operate in parallel, each compressing to a common discharge header and a single evaporative condenser. The suction line from the low pressure receiver leads to the screw compressor. The suction line from the intermediate pressure receiver leads to the reciprocating compressor. Additional compressors, in parallel piping arrangements to the primary compressors, can be brought on-line if the load exceeds the capacity of the primary compressors. 9

10 Control Options Single speed fan with on/ control most common head pressure control method set cut-in (e.g. 150 psig) & cut-out pressures (e.g. 140 psig) simple control method but results in higher energy consumption vs. two-speed or VFD higher maintenance (fan motors & belts) liquid management problems w/multiple condensers 10

11 Control Options Cont. 2-Speed fan control set high speed cut-in (e.g. 160 psig) low-speed cut-in pressure (e.g. 150 psig), and low-speed cut-out pressure (e.g. 140 psig) relatively simple control method but results in higher capital cost compared to single speed fan option lower energy consumption vs. single-speed but slightly higher energy consumption compared to variable speed yields less system transients compared to single speed sequencing speed controls requires attention 11

12 Control Options Cont. Variable speed fan (VFD) set a target head pressure modulate fan speed to maintain head pressure a very simple principle & method to implement highest capital cost alternative lowest energy consumption control alternative modulate all condensers the same in systems with multiple evaporative condensers results in smoother system operation with minimal transients 12

13 Condenser Fan Control Map Strategy Mode 1 Mode 2 Mode 3 Mode 4 Mode Small Motor half-speed half-speed on on Large Motor half-speed half-speed on Small Motor Small Motor Small Motor Small Motor on on variable speed on on on on Large Motor Large Motor Large Motor Large Motor on variable speed on on half-speed on on The above map provides five different strategies that could be used for an evaporative condenser that is equipped with twin motors, two-speed fans, or variable speed fans. The modes are indicative of changes in head pressure (either increasing as one moves from left to right or decreasing as one moves from right to left). For example, strategy 3 would work as follows. In mode 1 all fans are. As the head pressure rises, the system responds by energizing a small fan motor in attempts to maintain system head pressure. If the head pressure continues to rise and the setpoint is not satisfied, mode three is initiated by the start of the larger fan motor to half-speed. As the head pressure rises further, mode 4 dictates that the larger fan motor is tripped to run at high speed. The exact opposite sequence occurs as the head pressure falls. 13

14 Condenser Fan Control Options The above figure illustrates the required fan energy (expressed as a percentage of full-load fan power) as a function of the evaporative condenser capacity for the five strategies listed previously. The least efficient option is the on/ control (strategy 1) while the most efficient option is the variable speed drive option. The two-speed fan option yields nearly all of the part-load power and capacity benefits of the variable speed option but with much less costly equipment. Notice that at zero fan power for all options, the capacity of the evaporative condenser is not zero. This is due to the fact that natural convection will occur drawing air through the condenser coils and rejecting heat yielding about 10% of the condenser s heat rejection capacity while the fans are idle. This assumes that the condenser coils are running wet i.e. water continues to flow over the condenser coils. 14

15 Condenser Fan Controls May Source: Manske, K., 2000 Of course we do not want to just minimize the power of the evaporative condenser at the expense of the system; consequently, we must look at the impacts or trades associated with spending more energy on evaporative condenser fans vs. the reduction in compressor power that accrues due to the lower head pressure. The case study system had an oversized evaporative condenser. As a result, it was possible to drive head pressures extremely low in the system. So low in fact that the incremental expenditure of fan energy was not compensated for by an incremental reduction in compressor energy demand. The above plot shows the comparison between heat rejection system control strategies. The point furthest to the left on the curves in the figure represents the system balance point head pressure at which the condenser is operating at 100 percent capacity (for a given outdoor air wet bulb and system load during a peak hour on a average day in May). Any further decrease in condensing pressure would prevent the condenser from rejecting the required amount of energy from the system. The figure shows that VFD fan control could save the system nearly 8% in combined compressor and condenser energy requirements if the head pressure were raised to 125 psia. VFD fan control looses its advantages at low head pressures because the fans must run at near full speed most of the time anyway. At high head pressures the fans in on/ control don t stay on long because of the high rate of heat transfer that occurs. However, at high head pressure an on/ control strategy would cycle the fans on and frequently which would cause excessive wear on the motors and fan belts. The figure also shows that there is a different optimum head pressure for each type of condenser fan control. It is also interesting to note that half-speed fan motors have energy requirements that are only approximately one percent above the VFD motors at elevated head pressures. Since this system has a minimum allowed head pressure of 130 psia, VFD and half-speed motors may have very similar energy requirements for most of the year. 15

16 Optimum Head Pressure Control Source: Manske, K., 2000 This plot illustrates the preferred control head pressure control strategy for two different evaporative condenser sizes. With an evaporative condenser sized for 95 F saturated condensing temperature on a design day, the optimum head pressure is the lowest head pressure achievable by running the evap condenser fans full out. If the condenser is oversized (i.e. an oversized evap condenser is defined as one that yields a saturated condensing temperature of 85 F on the design day), there is an optimum head pressure (i.e. a head pressure greater than the minimum achievable that will minimize the combined power of the compressor and condenser). In this case, the optimum head pressure is likely a function of the outside air wetbulb temperature. The dark set of lines is for the condenser that is currently installed in the system. The current condenser is large enough to allow the system to balance out with a saturated condensing temperature of 85 F on the design day. The compressor/condenser power with a smaller condenser is given by the lighter colored line. The point furthest to the left on each line represents the pressure at which the evaporative condenser has reached 100 percent capacity. Given that the load is constant, it would be physically impossible to achieve a lower head pressure without adding additional condensing capacity. Note, the above case assumes that the refrigeration load is progressively decreasing during the winter months; however, refrigeration load has little influence on the optimum head pressure. Because of the presence of high temperature direct-expansion coils in the case study system, the head pressure is not allowed to go below 130 psia. Therefore, the system cannot possibly be operated at its ideal head pressure except for the months of June through September. It must be operated above its optimum head pressure resulting in a slight excess of compressor power. 16

17 Optimum Head Pressure Optimum Head Pressure [psia] Curve Fit (Variable Evaporator Load) Calculated Condenser Heat Rejection (Variable Evaporator Load) Calculated Condenser Heat Rejection (Constant Evaporator Load) Calculated Ideal Head Pressure (Variable Evaporator Load) Calculated Ideal Head Pressure (Constant Evaporator Load) minimum head pressure as required by dx txv 3.4x x x x x x x x x x x Outside Air Wet Bulb Temperature [ F] Total System Heat Rejection [Btu/hr] Source: Manske, K., 2000 When performing the calculations to identify the optimum condensing pressure for the year, we discovered that the optimum condensing pressure had a near linear relationship with the outside air wet bulb temperature. The above curve illustrates the relationship between optimum head pressure and outside air wetbulb temperature (lower curve) over a range of evaporator load conditions (corresponding variability in heat rejection is shown by the points above). In the case of this system, a very simple linear relationship was developed that allows a supervisory reset on the system head pressure given the prevailing outside air wet bulb temperature according to the following: P head,opt = * T wb where P head,opt is the head pressure corresponding to minimum system power in psia and T wb is the outside air wet bulb temperature in F. This relationship assumes that the condensers have variable speed drives. Keep in mind that the above relationship needs to have a lower bound as dictated by the characteristics of each given system. 17

18 Optimizing Head Pressure 1. Measure the outdoor air wet bulb temperature 2. Note the current condensing pressure and system electrical demand 3. Reset the condensing pressure down 5 psig & allow system to equilibrate 4. Note the new system electrical demand 5. Continue steps 3 and 4 until the lower condensing pressure limit setpoint is reached 6. Plot the system electrical demand vs. the condensing pressure and note the condensing pressure corresponding to point of minimum system electrical demand 7. Plot that single optimum condensing pressure point on a optimum condensing pressure vs. outdoor air wet bulb temperature curve 8. Repeat the procedure from 1-7 to more fully develop a curve analogous to the figure given on the previous page. Procedure for Determining Optimum Relation Between Condensing Pressure and Outdoor Wetbulb The trajectory of optimum condensing pressures for corresponding outside air wet bulb temperatures as shown on the previous page is specific to the existing ammonia system. Each system will have its own unique trajectory. However, the following procedure can be used to empirically develop the trajectory of optimum condensing pressures. Note, this procedure needs to be executed during -design periods of the year (during relatively lower outside air wet bulb conditions). The procedure also requires the ability to continuously monitor the outdoor air wet bulb temperature, condensing pressure, and the engine room total electrical demand. We also recommend that other system state variables (such as suction pressures, superheat if applicable, etc.) be monitored to ensure reliable system operation during the procedure. 1. Measure the outdoor air wet bulb temperature 2. Note the current condensing pressure and system electrical demand 3. Reset the condensing pressure down 5 psig (35 kpa) and allow the system to equilibrate 4. Note the new system electrical demand 5. Continue steps 3 and 4 until the lower limit in condensing pressure setpoint is reached 6. Plot the system electrical demand vs. the condensing pressure and note the condensing pressure that corresponds to the point of minimum system electrical demand 7. Plot that single optimum condensing pressure point on a optimum condensing pressure vs. outdoor air wet bulb temperature curve 8. Repeat the procedure from 1-7 to more fully develop a curve analogous to the figure given on the previous page. Once the optimum condensing pressure trajectory curve is developed, it can be programmed i t t PLC i t ll t i ld ti t f th h t 18

19 Economic Benefits of Drive Annual savings for warehouse 13 kw (peak) reduction 97,140 kwh reduction (~5%) $3,856 per year in electrical operating costs (~5%) Drive cost = $6,900 Simple payback of 1.8 yrs 19

20 Final Thoughts VFDs on condensers can provide economic and operating cost benefits on the high-side Take advantage of lowering head pressure Consider barriers to lowering head pressure 20

21 Floating Head Pressure Control Head pressure limits dictated by: hot gas defrost requirements setting of defrost relief valves sizing of hot gas main condensate management in hot gas main DX evaporators most thermostatic expansion valves need at least 75 psig differential pressure to function properly liquid injection oil cooling check manufacturer s requirements for TXV pressure differential As with most things, there are limits to lowering system head pressure. We do not want to create problems by trying to improve the efficiency of our systems. The above items are some of the more common factors constraining or limiting our ability to lower system head pressure. Keep in mind that these items may not necessarily be unmovable barriers; however, changes in components or system arrangements may be required to overcome their limiting effects on the system. Hot Gas Defrost: Many industrial refrigeration systems utilize hot gaseous refrigerant to defrost evaporators. In cases where defrost relief valves are installed, a sufficient pressure differential (e.g. 75 psig) across the valve must be created to open the valve. Sizing of the hot gas main may also impose constraints. If a hot gas main is undersized, hot gas (at a sufficient rate) will not be delivered to the evaporator without a high differential pressure. For larger size hot gas mains, a much lower differential pressure will allow adequate flow of hot gas to defrosting evaporator(s). Finally, if condensate is not properly managed in hot gas mains, hydraulic shock can cause catastrophic failures of hot gas piping on a call for defrost. Also, the condensate effectively decreases the pipe size causing similar symptoms as an undersized line with regard to head pressure requirements. All of these deficiencies can be overcome in the long run; however, they do create real barriers to lowering head pressure in the short run. DX Evaporators: In systems that utilize direct-expansion evaporators, a minimum differential pressure is required across the thermostatic expansion valves (TXV). The minimum pressure differential is dependent on the specific valve selection but is routinely on the order of 75 psig. When we drop the pressure differential across the TXV below the minimum, we lose controllability of the valve (control engineers call this control authority ). What results is an inability to properly modulate refrigerant to the evaporator. Since our evaporator pressure i.e. downstream of the TXV the pressure is fixed (to satisfy our temperature requirements for meeting load), the head 21

22 Floating Head Pressure Control Head pressure limits dictated by: evaporative condenser selection oversized evaporative condensers results in an optimum head pressure that depends on outdoor air wet bulb temperature evaporative condenser fan controls VFD fans are preferred but 2-speed fans yield considerable benefits thermosiphon oil coolers Evaporative Condenser Selection: If an evaporative condenser is too small, the system head pressure will rise until its heat rejection capacity is sufficient to reject the needed heat from the system. Fan Controls: Although fan controls themselves do not necessarily limit head pressure, there are methods of fan controls that lead to more stable and efficient system operation. Two speed condenser fans or variable frequency drive (VFD) fans have better capacity modulating capability and result in more stable head pressures leading to more stable system operation. In addition to their stability, two-speed and VFD controlled fans will result in improved energy due to their better part-load performance as compared to single speed fans. Thermosiphon Oil Cooling (TSOC): TSOC improves compressor efficiency by using a thermosiphon effect coupled with the system s evaporative condenser to reject heat from the compressor s oil. 22

23 Floating Head Pressure Control Head pressure limits dictated by: hand expansion valve settings significantly lowering head pressure will likely require seasonal HEV adjustments this constraint can be overcome by the use of motorized valves or pulse width valves oil separator sizing gas driven systems (transfer systems & gas pumpers) controlled-pressure receiver setpoints heat recovery engineering and operations (knowledge & willingness) 23

Energy efficient food processing: focus on refrigeration. Refrigeration Systems Review

Energy efficient food processing: focus on refrigeration. Refrigeration Systems Review Energy efficient food processing: focus on refrigeration Refrigeration Systems Review Todd Jekel, P.E., Ph.D. Assistant Director, IRC University of Wisconsin Madison University of Wisconsin-Madison Introduction

More information

Performance Optimization of Industrial Refrigeration Systems. By Kyle A. Manske

Performance Optimization of Industrial Refrigeration Systems. By Kyle A. Manske Performance Optimization of Industrial Refrigeration Systems By Kyle A. Manske A thesis submitted in partial fulfillment of the requirements for the degree of Master of Science (MECHANICAL ENGINEERING)

More information

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Load Sharing Strategies in Multiple Compressor Refrigeration Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2 Load Sharing Strategies in Multiple Compressor Refrigeration Systems K. A.

More information

Midwest Industrial Initiative Webinar: Industrial Refrigeration

Midwest Industrial Initiative Webinar: Industrial Refrigeration Midwest Industrial Initiative Webinar: Industrial Refrigeration Opportunities for Energy Efficiency and Cost Savings Thursday, June 6, 2013 www.kw-engineering.com Bryan Hackett, PE kw Engineering What

More information

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power energy center Paper Report Summary 210-1 174-2 Fixed and Floating Head Pressure Comparison for Madison Ice Arena Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power July 1998 April,

More information

DISCLOSURE THIS GUIDEBOOK WAS PREPARED BY THE IRC. NEITHER THE IRC, NOR ANY PERSON ACTING ON BEHALF OF THEM:

DISCLOSURE THIS GUIDEBOOK WAS PREPARED BY THE IRC. NEITHER THE IRC, NOR ANY PERSON ACTING ON BEHALF OF THEM: DISCLOSURE DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES THIS GUIDEBOOK WAS PREPARED BY THE IRC. NEITHER THE IRC, NOR ANY PERSON ACTING ON BEHALF OF THEM: (A) MAKES ANY WARRANTY OR REPRESENTATION

More information

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs Abstract Fan and coil evaporators as used in the industrial refrigeration industry can be certified for performance per ANSI/AHRI Standard 420-2008, Performance Rating of Forced-Circulation Free-Delivery

More information

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City) BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION Business Name Site physical address (Street, Suburb, City) Nature of site / business operation Electricity Supplier Power factor

More information

Intermediate Refrigeration Systems for Operators

Intermediate Refrigeration Systems for Operators Intermediate Refrigeration Systems for Operators A web-based course conducted by the www.irc.wisc.edu Intermediate Refrigeration Systems for Operators This class is designed to build upon and extend the

More information

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

Low Charge ADX Ammonia. Presented by: Bruce Nelson, President, Colmac Coil Manufacturing Rick Watters, Vice President, AMS Mechanical Systems

Low Charge ADX Ammonia. Presented by: Bruce Nelson, President, Colmac Coil Manufacturing Rick Watters, Vice President, AMS Mechanical Systems Low Charge ADX Ammonia Presented by: Bruce Nelson, President, Colmac Coil Manufacturing Rick Watters, Vice President, AMS Mechanical Systems Background Why use ammonia? It s a natural refrigerant ODP =

More information

Automation and Energy Efficiency of Industrial Refrigeration Systems

Automation and Energy Efficiency of Industrial Refrigeration Systems Automation and Energy Efficiency of Industrial Refrigeration Systems E360 Forum Chicago, IL October 5, 2017 Mike Micak Director of Sales Logix Controls Introduction Management thinker Peter Drucker was

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

IRC Staff. Director Doug Reindl 608/ or 608/

IRC Staff. Director Doug Reindl 608/ or 608/ The Cold Front IN THIIS ISSUE Liquid Injection vs. 1-6 Thermosiphon Oil Cooling of Screw Compressors Upcoming Ammonia Classes 2 Noteworthy 2 Join the IRC in 2004 6 2004 R&T Forum Advanced 7 Notice IRC

More information

Technical Information

Technical Information Date of last update: 02-08 Ref: Application Engineering Europe COPELAND SCROLL COMPRESSORS USING VAPOUR INJECTION FOR REFRIGERATION CONTENTS 1 Introduction...1 2 Principle of Operation...1 3 Capacity Effect...2

More information

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

terminal units only provide sensible cooling, a separate dehumidification system is usually needed. providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

THERMOSTATIC EXPANSION VALVES Part 1

THERMOSTATIC EXPANSION VALVES Part 1 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 THERMOSTATIC EXPANSION VALVES Part 1 Revised by Loren Shuck, CMS INTRODUCTION The thermostatic expansion valve (frequently

More information

ENERGY EFFICIENCY PROJECTS. NO-COST AND LOW-COST UPGRADES FOR YOUR FACILITY In partnership with: Refrigerating Engineers & Technicians Association

ENERGY EFFICIENCY PROJECTS. NO-COST AND LOW-COST UPGRADES FOR YOUR FACILITY In partnership with: Refrigerating Engineers & Technicians Association ENERGY EFFICIENCY PROJECTS NO-COST AND LOW-COST UPGRADES FOR YOUR FACILITY In partnership with: Refrigerating Engineers & Technicians Association INTRODUCTION Save Money, Improve Operations Today s refrigeration

More information

Energy Performance of Low Charge NH3 Systems in Practice. Stefan S. Jensen

Energy Performance of Low Charge NH3 Systems in Practice. Stefan S. Jensen Energy Performance of Low Charge NH3 Systems in Practice Stefan S. Jensen Introduction Central type, dual compression stage, ammonia vapour compression systems. Main Design Features: Reciprocating Compressors

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012 SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

5. ASSESSMENT RECOMMENDATIONS

5. ASSESSMENT RECOMMENDATIONS 5. ASSESSMENT RECOMMENDATIONS AR No. 1 Reduce Discharge Pressure Recommended Action Reduce the minimum condensing temperatures on your warehouse refrigeration systems from 110 F to 60 F. In order to reduce

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

Partial Load Performance Of Refrigeration System

Partial Load Performance Of Refrigeration System Chapter 11 Partial Load Performance Of Refrigeration System Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Hot Gas Bypass & Liquid Injection: When the compressor is under surge condition,

More information

Trim Pump Impellers. Fredrick/Weinman Engineered Products 2-1/2 KH, 2-1/2 x 3 x 12

Trim Pump Impellers. Fredrick/Weinman Engineered Products 2-1/2 KH, 2-1/2 x 3 x 12 Head, ft. w.c. Trim Pump Impellers TRIM THE PUMP IMPELLER SO THE FLOW PRODUCED MATCHES THE DESIGN REQUIREMENT WITH THE DISCHARGE SERVICE VALVE WIDE OPEN. IN MOST CASES, THIS WILL REDUCED THE PUMP ENERGY

More information

50Low- and. No-Cost Tips for Saving Energy INDUSTRIAL REFRIGERATION ENERGY EFFICIENCY

50Low- and. No-Cost Tips for Saving Energy INDUSTRIAL REFRIGERATION ENERGY EFFICIENCY 50Low- and No-Cost Tips for Saving Energy INDUSTRIAL REFRIGERATION ENERGY EFFICIENCY LOW- AND NO-COST SOLUTIONS THAT INCREASE ENERGY EFFICIENCY If you pay the power bill at an industrial cold storage or

More information

energydesignresources

energydesignresources energydesignresources design brief Energy building Efficiency design Practices in Industrial Refrigeration Summary Energy costs are a significant expense for facilities that operate industrial refrigeration

More information

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration Understanding Head Pressure Control Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration WE WILL LOOK AT: 1. Why We Need Head Pressure Control? 2. How Do We Control Head Pressure - Methods?

More information

Technical Information

Technical Information Date of last update: May-12 Ref: : Application Engineering Europe ENHANCED VAPOUR INJECTION (EVI) FOR ZH*KVE SCROLL COMPRESSORS 1 Introduction... 2 2 Principle of operation... 2 3 Capacity effect... 3

More information

On Balance: Heat Rejection Control a Packaged Solution

On Balance: Heat Rejection Control a Packaged Solution On Balance: Heat Rejection Control a Packaged Solution Echelon Americas Channel Partner Conference March 11, 2005 Presented by Doug Scott VaCom Technologies La Verne, California Opportunity An integrated

More information

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off Application Guide AG 31-003-1 Chiller Plant Design 51.5F Return Water To Chiller Two 400 Ton Chillers Each At 300 Tons (Balanced Load) 51.5F 480 gpm Flow Through Decoupler 44F 54F Building Load 600 Tons

More information

LOW RECIRCULATION RATE EVAPORATORS

LOW RECIRCULATION RATE EVAPORATORS WHITE PAPER LOW RECIRCULATION RATE EVAPORATORS Written by: Jeff Welch President Welch Engineering Corporation Abstract Fin coil evaporators with enhanced internal tube surfaces allow for optimum performance

More information

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative A U.S. Environmental Protection Agency survey released in 2007 concluded that IT data centers consumed 61 billion kw of electricity at a total cost of $4.5 billion in 2006. As energy costs continue to

More information

Presented By: John Dolan, P.E.

Presented By: John Dolan, P.E. Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com

More information

Sustainable Techniques in Refrigerated Space

Sustainable Techniques in Refrigerated Space Sustainable Techniques in Refrigerated Space Sustainability and high performance of refrigerated space used for the preservation of perishable product capitalizes on conservation techniques which reduce

More information

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Session 2633 Development of a Psychrometric Test Chamber Michael J. Swedish Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Acknowledgments The design of the Psychrometric

More information

Method to test HVAC equipment at part load conditions

Method to test HVAC equipment at part load conditions IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking

More information

CO 2 EVAPORATOR DESIGN

CO 2 EVAPORATOR DESIGN By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. CO 2 EVAPORATOR DESIGN Introduction The process of selecting air cooling evaporators to operate in a CO 2 refrigeration system is very

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment

More information

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 216 Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration

More information

WHAT IS AN ENERGY BALANCE AND WHY SHOULD I CARE?

WHAT IS AN ENERGY BALANCE AND WHY SHOULD I CARE? WHAT IS AN ENERGY BALANCE AND WHY SHOULD I CARE? Presented at RETA 2017 Conference September 26 September 29, 2017 Hershey, Pennsylvania Juan Parra / Andrew Fiala Project Professional / Sr. Project Professional

More information

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application 1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights

More information

Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International

Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint Daryl Showalter ChillerApplications Manager McQuay International Equipment Using Different Kinds Of Equipment Or Different Performance

More information

Application of Air Source Variable Refrigerant Flow in Cold Climates

Application of Air Source Variable Refrigerant Flow in Cold Climates PREPARED BY Seventhwave with the assistance of Daikin North America, LLC Masters Building Solutions Application of Air Source Variable Refrigerant Flow in Cold Climates A White Paper March 2015 275-1

More information

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson

More information

KE2 EvaporatorEfficiency Theory of Operation

KE2 EvaporatorEfficiency Theory of Operation Theory T.1.1 June 011 TM thermsolutions ENTER BACK KE Therm Solutions, Advanced Energy Saving Technology for Commercial Refrigeration and AC Systems Page Table of Contents Basic Refrigeration System Evaporator

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James

More information

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup Pack Calculation Pro Users guide Version 4.10 Morten Juel Skovrup 1 Contents 2 Introduction... 5 3 Example... 7 3.1 Setup systems... 7 3.1.1 Selecting compressors... 9 3.1.2 Suction side... 12 3.1.3 Discharge

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

Industrial Refrigeration Defrost Solutions TM Package. Brochure R-222

Industrial Refrigeration Defrost Solutions TM Package. Brochure R-222 aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding Industrial Refrigeration Defrost Solutions TM Package Brochure R- R-

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

CO2 TRANSCRITICAL BOOSTER SYSTEMS

CO2 TRANSCRITICAL BOOSTER SYSTEMS CO2 TRANSCRITICAL BOOSTER SYSTEMS William Katz Sr. Technical Writer Hillphoenix 2016 Gees Mill Road Conyers, GA 30013 Tel: 678-613-9364 Email: william.katz@hillphoenix.com Refrigeration systems for supermarkets

More information

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office

More information

Measure Guidelines. for EnergySmart Grocer (ESG)

Measure Guidelines. for EnergySmart Grocer (ESG) Measure Guidelines for EnergySmart Grocer (ESG) Measure Guidelines for EnergySmart Grocer (ESG) Table of Contents Page Cases 1. Low Open Case to New Reach-in..................................1 2. Medium

More information

Heat Transfer Products. Product Line Update

Heat Transfer Products. Product Line Update Heat Transfer Products Product Line Update EP2 Portable Chiller Variable-Speed Compressor Option What s different with variable-speed option? Fixed-Speed Compressor Units Variable-Speed Compressor Units

More information

REFRIGERATION EQUIPMENT SCOPE - QUESTIONNAIRE

REFRIGERATION EQUIPMENT SCOPE - QUESTIONNAIRE REFRIGERATION EQUIPMENT SCOPE - QUESTIONNAIRE Please provide the following information to receive a no-cost estimate of how much money our control system could save your facility and to assist us in preparing

More information

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System

More information

7 THERMAL APPLICATIONS

7 THERMAL APPLICATIONS THERMAL APPLICATIONS:COOLING SYSTEMS 7 THERMAL APPLICATIONS 7.1. COOLING SYSTEMS For process cooling it is always best from the standpoint of energy conservation to use the least expensive form of energy

More information

The electrical wattage needed by the circulator is:

The electrical wattage needed by the circulator is: The electrical wattage needed by the circulator is: w e = 0.4344 f P n w/w A current-generation wet-rotor circulator has a maximum wire-towater efficiency in the range of 25 percent. If we put the data

More information

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

Chapter 4 Compressors Overview & System Annual Power Consumption

Chapter 4 Compressors Overview & System Annual Power Consumption Chapter 4 Compressors Overview & System Annual Power Consumption Copy Right By: Thomas T.S. Wan 温 Sept. 3, 2008 All rights reserved (Cor. 07-08-12) Compressor is the heart of the refrigeration system.

More information

Refrigerant valves. Valves for precise control and optimum energy efficiency in refrigeration systems. Answers for infrastructure.

Refrigerant valves. Valves for precise control and optimum energy efficiency in refrigeration systems. Answers for infrastructure. Refrigerant valves Valves for precise control and optimum energy efficiency in refrigeration systems Answers for infrastructure. MVL661.. MVS661..N and matching ASR valve insert The new generation MVL661..

More information

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Chiller Plant Design. Julian R. de Bullet President debullet Consulting Chiller Plant Design Julian R. de Bullet President debullet Consulting 703-483-0179 julian@debullet.com This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer ASHRAE

More information

ENERGY EVALUATION OF A

ENERGY EVALUATION OF A ENERGY EVALUATION OF A FROZEN FOODS PLANT Final Report - March 2000 Prepared by University of Wisconsin HVAC&R Center Funded by SOUTHWESTERN ELECTRIC POWER COMPANY DISCLAIMER OF WARRANTIES AND LIMITATION

More information

Small Applications with Ammonia

Small Applications with Ammonia eurammon Symposium 2017 Small Applications with Ammonia Daniel McDougall Star Refrigeration Ltd. Schaffhausen, 22 nd /23 rd June, 2017 Traditional Ammonia Refrigeration Technology Compressor Plantroom

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Psychrometry One of the Fundamental Series D C B A C B D A July 2012 TRG-TRC001-EN Psychrometry One of the Fundamental Series A publication of Trane Preface Psychrometry A Trane

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

Best Practices for Condensing Boilers

Best Practices for Condensing Boilers ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cleaverbrooks.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For

More information

REFRIGERATION EQUIPMENT SCOPE - QUESTIONNAIRE

REFRIGERATION EQUIPMENT SCOPE - QUESTIONNAIRE REFRIGERATION EQUIPMENT SCOPE - QUESTIONNAIRE Please provide the following information to receive a no-cost estimate of how much money our control system could save your facility and to assist us in preparing

More information

RDT Refrigeration Book

RDT Refrigeration Book RDT Refrigeration Book Indoor / Outdoor Air-Cooled Systems Indoor Air-Cooled Systems 1. Shorter line runs. 2. Systems located off roof or dock space. 3. Weather covers are not required (saves cost). 4.

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

JCseries EVAPORATIVE CONDENSER. engineering data

JCseries EVAPORATIVE CONDENSER. engineering data JCseries EVAPORATIVE CONDENSER engineering data Recold JC Series Evaporative Condenser Contents 2 Construction... 3 Schematic... 4 Engineering Data... 5 Selection Procedure... 6-9 Multi-Circuited Selection

More information

ENERGY EFFICIENCY PROJECTS. NO-COST AND LOW-COST UPGRADES FOR YOUR FACILITY In partnership with: Refrigerating Engineers & Technicians Association

ENERGY EFFICIENCY PROJECTS. NO-COST AND LOW-COST UPGRADES FOR YOUR FACILITY In partnership with: Refrigerating Engineers & Technicians Association ENERGY EFFICIENCY PROJECTS NO-COST AND LOW-COST UPGRADES FOR YOUR FACILITY In partnership with: Refrigerating Engineers & Technicians Association INTRODUCTION Save Money, Improve Operations Today s refrigeration

More information

General information on refrigerant controllers

General information on refrigerant controllers General information on refrigerant controllers Condensing pressure controller The condensing or condenser pressure controller is a back pressure controller and its task is to maintain the condensing pressure

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

Refrigeration Systems

Refrigeration Systems Refrigeration Systems COP COP = coefficient of performance Air conditioners, refrigerators: COP=QL/Wnet Heat pumps: COP=QH/Wnet Energy balance: Wnet+QL=QH From Cengel, Thermodynamics: An Engineering Approach,

More information

R07. Answer any FIVE Questions All Questions carry equal marks *****

R07. Answer any FIVE Questions All Questions carry equal marks ***** Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

Dehumidifying with Dedicated Outdoor Air

Dehumidifying with Dedicated Outdoor Air Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,

More information

Performance of an Improved Household Refrigerator/Freezer

Performance of an Improved Household Refrigerator/Freezer Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin B40-THERM-PDI-14 1069132 ThermoSaver TM Hot Gas Defrost System For use on select

More information

Phillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants

Phillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants Phillips REFRIGERATION MECHANICAL PUMP RECIRCULATORS BULLETIN MPR-03E Engineering Data VALVES VESSELS SYSTEMS CONTROLS HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

Carwin COMPRESSOR SELECTION PROGRAM

Carwin COMPRESSOR SELECTION PROGRAM Carwin COMPRESSOR SELECTION PROGRAM IMPORTANT! READ CAREFULLY BEFORE USING By using this disk covering a software program entitled CARLYLE SELECTION PROGRAM WINDOWS (Software), you indicate your acceptance

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Air-Cooling Evaporators

Air-Cooling Evaporators Air-Cooling Evaporators Types of construction Circuit Configurations Methods of Refrigerant Feed Methods of Air Circulation Methods of Defrost Type of Construction Bare tube Finned Tube Plate-surface Bare

More information

Air Cooled Packaged Systems AIRAH Back to Basics

Air Cooled Packaged Systems AIRAH Back to Basics Air Cooled Packaged Systems AIRAH Back to Basics What s changed? New Refrigerants R410a MEPS EER / AEER / SEER Manufacturing Technologies Research, Development and Testing New technologies, controls, reliability

More information

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job. June 01 / BULLETIN - 3-Way Valves The right solenoid valve for any job. Page 2 / Bulletin - Advantages Sporlan 3-Way Valves 3-Way Pilot eliminates costly high- to low-side leaks. "B" reduces total installed

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It Single Screw Ammonia Heat Pumps Harness Your Heat... Don t Reject It Harness Your Heat Don't Reject It Industrial processes consume considerable energy from two primary sources in the production of their

More information

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A900-22007), 120/208/240/1/60, R404A, LT/MT APPS Introduction The superheat controller is designed

More information

Parilla Thermal Storage Project Case Study. May Page 1 of 11

Parilla Thermal Storage Project Case Study. May Page 1 of 11 Parilla Thermal Storage Project Case Study May 2014 Page 1 of 11 BACKGROUND Parilla Premium Potatoes is a large refrigerated storage facility (Figure 1) located in South Australia; the facility consists

More information