The Effects of Hydrophilicity on Water Drainage and Condensate Retention on Air-Conditioning Evaporators

Size: px
Start display at page:

Download "The Effects of Hydrophilicity on Water Drainage and Condensate Retention on Air-Conditioning Evaporators"

Transcription

1 Purdue University Purdue e-pubs International Refrigeration and ir Conditioning Conference School of Mechanical Engineering 26 The Effects of Hydrophilicity on Water Drainage and Condensate Retention on ir-conditioning Evaporators Liping Liu University of Illinois at Urbana-Champaign nthony M. Jacobi University of Illinois at Urbana-Champaign Follow this and additional works at: Liu, Liping and Jacobi, nthony M., "The Effects of Hydrophilicity on Water Drainage and Condensate Retention on ir- Conditioning Evaporators" (26). International Refrigeration and ir Conditioning Conference. Paper This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at Herrick/Events/orderlit.html

2 R9, Page 1 THE EFFECTS OF HYDROPHILICITY ON WTER DRINGE ND CONDENSTE RETENTION ON IR-CONDITIONING EVPORTORS Liping LIU*, nthony M. JCOBI Department of Mechanical and Industrial Engineering, University of Illinois at Urbana Champaign, 126 W. Green St. MC-244, Urbana, IL 6181 US Phone: (217) , Fax: (217) , lliu9@uiuc.edu *Corresponding uthor BSTRCT n experimental study is conducted to investigate condensate drainage and retention and the attendant thermalhydraulic effect associated with changes in surface hydrophilicity on air-conditioning evaporators. Three heat exchangers that have controlled wettability covering a range of contact angles and a baseline untreated aluminum heat exchanger are tested. Results from dynamic dip-testing as well as wind-tunnel experiments under fully wet conditions are presented. The data show that for the heat exchangers used in this study the Colburn j factor is not strongly influenced by condensate retention, but the friction factor is significantly reduced by the enhancement of surface hydrophilicity. Heat exchangers with improved wettability hold slightly more water than the baseline in a dynamic dip-test, but retain remarkably less than the untreated coil in a wet wind-tunnel experiment. Steady-state mass retention in wind-tunnel tests decreases with increasing air flow rate, and the retention is more sensitive to the air-side Reynolds number for heat exchangers with higher contact angles. 1. INTRODUCTION The evaporator in air-conditioning systems normally operates with the air-handling surface colder than the dewpoint temperature of the conditioned air. Therefore, moisture condenses and accumulates on the surface of the heat exchanger. Condensate retained on the air-side heat transfer surface has a profound impact on the performance of the heat exchanger and on the air quality. Very recently, material processing advances have produced fins with enhanced wettability, which effectively reduce the contact angle of water condensate and improve the condensate drainage. Methods of coating the aluminum fins have been well documented by Hong and Webb (2), and Kim et al. (22) proposed a new method of plasma treating. The effect of a hydrophilic coating on air-side performance of compact heat exchangers has been examined by Wang et al. (22), and Min et al. (2) provide a long-term performance assessment of heat exchangers for commercial coatings. lthough some studies have been performed with the air-side performance under wet conditions, there is limited information about the condensate characteristics and drainage behavior associated with surface hydrophilicity. It is uncommon to find data reported along with condensate retention data, much less a characterization of surface wettability. The objective of this study is therefore focused on investigating the condensate drainage and retention associated with changes in surface wettability. The thermal-hydraulic effect will also be examined, in order to build a complete picture of the relationships between wettability retention and performance. 2. TEST METHODS Four fin-and-tube heat exchangers with the same geometry (6.6 mm diameter tubes, a staggered tube layout, slit fins, and 1.1 mm fin pitch) as given in Figure 1 were used in this study. s shown in Table 1, the wettability of three of the heat exchangers was controlled through a plasma coating process, and the fourth one represents an untreated International Refrigeration and ir Conditioning Conference at Purdue, July 17-2, 26

3 R9, Page 2 aluminum surface. It has been observed by others that the contact angles measured on the uncoated aluminum fins gradually decrease with increasing numbers of wet/dry cycles, but the wettability of the plasma coated aluminum appears to be robust (Kim et al., 22). 29 mm 6.73 mm 313 mm 25 mm Figure 1. Schematic of heat exchanger geometry Table 1: Hydrophilicity description of the tested heat exchangers Specimen dvancing contact angle θ (º) Receding contact angle θ R (º) Surface treatment Plasma coating Plasma coating Plasma coating Un-coated 2.1 Dynamic dip testing Dynamic dip tests were conducted with the apparatus shown in Figure 2. The apparatus consists of a large water reservoir, a smaller submerged air reservoir to control the submersion of coils by displacement of water using compressed air, and a structure to suspend and weigh the heat exchanger. To start an experiment, the balance was turned on and zeroed after the test coil was suspended over the reservoir. The displacement tank was filled with water, and the water level is made to rise and submerge the test specimen using the compressed air supply. Once the specimen was submerged, the air supply was closed and air vent was suddenly opened to allow water lever to drop quickly and at that moment data recording starts. This apparatus and relevant operating procedure are described in more detail by Zhong and Jacobi (23). s water drains from the specimen, the amount of water retained on the heat exchanger surface is recorded by a computer-based data acquisition system with a minimum recording interval of.1 second. It should be noted that only 1 out of 2 data points are shown in the plots of this paper. The balance has a reported uncertainty of less than.1 grams and the difference of results from repeated runs is approximately 1%. 2.2 Wind-tunnel testing closed-loop wind tunnel as shown in Figure 3 was used to test heat exchangers under wet-surface conditions. The air-side temperature was regulated by controlling the power applied to heaters that can deliver up to 8 kw. Humidification was provided by a boiler, capable of providing more than 12 kg/hr of steam, regulated using dewpoint chilled-mirror sensors and a PID controller. ir-side temperatures were measured using a grid of precision thermocouples at the inlet and exit of the heat exchanger. Volumetric airflow rates up to about 2 m 3 /min were provided using a variable speed drive. The air flow was carefully conditioned upstream of the test heat exchanger to ensure that a uniform approach flow with a low free-stream turbulence is provided. water-glycol mixture supplied by a gear pump was used to cool the evaporator during the experiments. The temperature of the coolant was regulated using a chiller system and monitored using immersion RTD s at the inlet and exit of the heat exchanger. International Refrigeration and ir Conditioning Conference at Purdue, July 17-2, 26

4 R9, Page 3 Coriolis-effect flowmeter was used to measure the mass flow rate of the coolant flow, and test conditions were set to simulate the nearly constant-temperature refrigerant side typical to application. During an experiment, the data acquisition system would sample instruments throughout the tests and log data to a text file for subsequent analysis. Figure 2. Schematic diagram of dip-test apparatus Tests were conducted with a coolant inlet temperature of 4.4ºC, and an air inlet temperature of 23.9ºC. The upstream dewpoint temperature was set to be 18.3ºC. These conditions ensured that the coolant temperature remained lower than the air-side dewpoint temperature throughout an experiment, which is known as the fully wet condition. Data reduction and interpretation follow the methods detailed by the RI Standard for condensing heat exchangers. Correlations for air-side Colburn j factors are provided for specific geometry as a function of the Reynolds number. Likewise, a conventional treatment provides the Fanning friction factor as a function of the Reynolds number. The j factors and friction factors are related to the basic thermal-hydraulic and geometrical data through the following equations: where nd where j = StPr 2 PHX ρ a min 2 ρup min ρ a f = (1 ) σ G tot ρdown tot ρup min σ = front min 2/3 Nu h St = = Re Pr GC Cpaµ a Pr = k ma G = & a ρup + ρ ρa = 2 down pa (1) (2) (3) (4) (5) (6) (7) International Refrigeration and ir Conditioning Conference at Purdue, July 17-2, 26

5 R9, Page 4 Figure 3. Schematic diagram of the wind tunnel; () return duct; (B) thermal mixing chamber; (C) Screens and honeycomb flow conditioning; (D) 9:1 flow contraction; (E) test heat exchanger; (F) measurement locations; (G) resistance heaters; (H) steam injection tube; (I) axial blower Figure 4: The installation of the heat exchanger in the wind tunnel; () wind tunnel; (B) strap; (C) balance; (D) coolant supply; (E) heat exchanger; (F) drainage hole 2.3 Real-time retention measurement Real-time retention measurements were conducted separately from the heat transfer tests. In this way the test section could be modified to obtain the highest data fidelity when recording the retention data, or the best insulation when doing the thermal-hydraulic performance tests. s shown in Figure 4, the heat exchanger was hung in the wind tunnel with a strap. The same balance as used in dynamic dip-testing was placed under the test section to measure the condensate retained on the specimen during the experiment. To reduce the measurement uncertainty, a non-absorbing strap with passage for water to go through was used. Inlet and outlet coolant tubes were kept horizontal and as loose as possible, in order to minimize interference with the specimen weight measuring. Two thin wires were tied between the heat exchanger and the wind-tunnel, providing only horizontal forces against the pushing action of the incoming air. Experimental data showed that the measurements obtained in the circulating system gave results lower than the real object mass with an acceptable accuracy. The error was under 5% for moderate face velocities, reaching approximately 1% at an air face velocity of about 3 m/s. Balance calibration was conducted before each test by recording readings for calibration weights. linear correlation was then acquired and used to calibrate the recorded data in subsequent testing. 3. RESULTS ND DISCUSSION The results from dynamic dip testing are shown in Figure 5, which gives the mass retention in decreasing magnitude to be specimen 1 (θ =3 ) > 2 (θ =5 ) > 3 (θ =11 ) > 4 (uncoated). These results may be explained by recalling that hydrophilic surfaces have an affinity for water and therefore should retain more water. lthough specimen 3 has a large advancing contact angle of 11, it differs from conventional water-repellent surface by having a zero receding contact angle it has a very large contact angle hysteresis. During a dynamic dip test, the heat exchanger is flooded with water, which is completely different from the case of having droplet distributions and combined drywet areas as in a wind-tunnel test. Without the existence of droplets, the contact angle hysteresis is not playing an important role. In the dip test, the retention differences between the three plasma treated heat exchangers are quite small (less than 5%) with an average value of approximately 65 g/m 2 after 5 minutes, while the uncoated heat exchanger holds approximately 57 g/m 2 under the same conditions. This is in accordance with expectation. With the same geometry International Refrigeration and ir Conditioning Conference at Purdue, July 17-2, 26

6 R9, Page 5 and identical test conditions, and the advancing contact angle does not have a significant effect, the only thing that matters is the receding contact angle. 11 Mass per rea (g/m 2 ) θ =3 o θ =5 o Α θ =11 o Time (min) Figure 5. Dynamic dip testing results j θ =3 o θ =5 o θ =11 o Re dh Figure 6. Colburn j factors under fully wet test conditions Shown in Figure 6 and 7 are the wind-tunnel test results under fully wet conditions. The data show that for the heat exchangers used in this study, the Colburn j factor is not strongly influenced by condensate retention, but the friction factor is significantly reduced by the enhancement of surface hydrophilicity. This is because the condensation occurring on specimen 1 and specimen 2 is basically filmwise, and that occurring on specimen 3 and specimen 4 are more likely dropwise. Therefore, droplets can stand up on the surfaces of specimen 3 and specimen 4, bridge between adjacent fins, and block the air flow causing pronounced pressure drops. The reason why the f factors for specimen 1 (θ =3 ) are slightly higher than specimen 2 (θ =5 ) is not clear. International Refrigeration and ir Conditioning Conference at Purdue, July 17-2, 26

7 R9, Page f.15.1 θ =3 o θ =5 o.5 θ =11 o Re dh Figure 7. Fanning f factors under fully wet test conditions 12 1 Mass per rea (g/m 2 ) θ =3 o θ =5 o 2 θ =11 o Time (min) Figure 8. Real-time retention measurement results One set of real-time retention measurement results for a fixed fan power is given in Figure 8. Under the same fully wet test conditions as specified before, specimen 1 (θ =3 ) and specimen 2 (θ =5 ) exhibit similar drainage performance and specimen 3 (θ =11 ) and specimen 4 (uncoated) retain much more condensate. This result is counter to the dynamic dip-test results, which may be due to the distinct condensation and drainage mechanisms in these two experimental systems. For hydrophilic specimens (specimen 1 and specimen 2), the water on the surface is likely to take the form of a film, whether it was deposited by dipping or condensation. Therefore, the amount of water should be roughly equal for International Refrigeration and ir Conditioning Conference at Purdue, July 17-2, 26

8 R9, Page 7 these two cases. Considering the existence of shear due to the air flow in addition to gravity drainage, the steady state retention in the wind-tunnel (shown to be 51g/m 2 in Figure 8) should be slightly less than that in a dynamic dip test (65g/m 2 ). For hydrophobic coils, this behavior is different. The heat exchanger is flooded with water in the dynamic dip test, and when the air vent is suddenly opened, the water level drops quickly and a large amount of water leaves the heat exchanger in a very short time. This flow of water sweeps the surface, reducing the retention much less than the steady-state retention of droplets and bridges in a wind-tunnel test Mass per rea (g/m 2 ) θ =3 o θ =5 o 2 θ =11 o Re dh Figure 9. Steady-state mass retention data s shown in Figure 9, the steady-state mass retention in a wind-tunnel test decreases with increasing air side Reynolds number for all of the heat exchangers. The specimens with higher contact angles retain more water than the hydrophilic ones, and their retention is more sensitive to the change of air side Reynolds number, which is also true for f factors as revealed in Figure 7. One possible explanation is that with the increased air shear, the droplet number density as well as its distribution will be significantly affected for dropwise condensation, while the thin stable water film on hydrophilic heat exchangers is largely unaffected. 4. CONCLUSIONS This study reports the effect of surface hydrophilicity on the air-side performance and the retention and drainage behavior of slit fin-and-tube heat exchangers. Experiments were performed for plasma coated heat exchangers and uncoated aluminum heat exchanger. The major findings of this study are summarized as follows: Heat exchangers with improved wettability hold slightly more water in a dynamic dip test. The advancing contact angle does not serve an important role in affecting the mass retention. Hydrophilic coatings reduce the wet pressure drop significantly without decreasing the wet sensible heat transfer coefficient for a heat exchanger. Heat exchangers with improved wettability retain much less water than hydrophobic ones in a wet windtunnel test. Steady-state mass retention in a wind-tunnel test decreases with increasing air flow rate, and the value is more sensitive to the change of air side Reynolds number for heat exchangers with higher contact angles. International Refrigeration and ir Conditioning Conference at Purdue, July 17-2, 26

9 R9, Page 8 NOMENCLTURE front frontal area (m 2 ) Subscripts min minimum flow area (m 2 ) advancing tot total surface area (m 2 ) R receding C p specific heat (J/kg-K) a air f friction factors ( ) up upstream G mass flux at min. flow area (kg-m 2 /s) down downstream h heat transfer coefficient (W-m 2 /K) HX heat exchanger j Colburn j factor ( ) dh hydraulic diameter k conductivity (W-m/K) m& mass flow rate (kg/s) Nu Nusselt number ( ) Pr Prantdl number ( ) Re Reynolds number ( ) St Stanton number ( ) θ dynamic contact angle (º) σ area ratio ( ) ρ density (kg/m 3 ) P pressure drop (Pa) REFERENCES Hong, K., Webb, R. L., 2, Wetting Coatings for Dehumidifying Heat Exchangers, HVC&R Research, vol. 6, no. 3: p Hong, K., Webb, R. L., 1999, Performance of Dehumidifying Heat Exchangers With and Without Wetting Coating, J. Heat Transfer, vol. 121: p Min, J., Webb, R. L., Bemisderfer, C. H., 2, Long-Term Hydraulic Performance of Dehumidifying Heat- Exchangers With and Without Hydrophilic Coatings, HVC&R Research, vol. 6, no. 3: p Kim, G., Lee, H., Webb, R. L., 22, Plasma Hydrophilic Surface Treatments for Dehumidifying Heat Exchangers, Experimental Thermal and Fluid Science, vol. 27: p Wang, C. C., Lee, W. S., Sheu, W. J., Chang, Y. J., 22, Comparison of the irside Performance of the Fin-and- Tube Exchangers in Wet Conditions; With and Without Hydrophilic Coating, pplied Thermal Engineering, vol. 22: p Shin, J., Ha, S., 22, The Effect of Hydrophilicity on Condensation Over Various Types of Fin-and-Tube Heat Exchangers, Int. J. Refrig., vol. 25: p Wang, C. C., Chang, C. T., 1998, Heat and Mass Transfer for Plate Fin-and-Tube Heat Exchangers, With and Without Hydrophilic Coating, Int. J. Heat Mass Transfer, vol. 41: p Zhong, Y., Jacobi,. M., 23, Dynamic Dip-Testing to ssess the Condensate-Drainage Behavior of Dehumidifying Heat Exchangers, 2 nd Int. Conference on Heat Transfer, Fluid Mechanics and Thermodynamics: p CKNOWLEDGEMENT We are grateful for assistance from LG Electronics Company in providing the heat exchanger samples, and for financial support from the ir Conditioning and Refrigeration Center (CRC) at the University of Illinois. International Refrigeration and ir Conditioning Conference at Purdue, July 17-2, 26

Off-Cycle Condensate Drainage Behavior of Compact Heat Exchangers: Assessment and Enhancement

Off-Cycle Condensate Drainage Behavior of Compact Heat Exchangers: Assessment and Enhancement Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Off-Cycle Condensate Drainage Behavior of Compact Heat Exchangers: Assessment

More information

Assessing the Condensate-Drainage Behavior of Dehumidifying Heat Exchangers

Assessing the Condensate-Drainage Behavior of Dehumidifying Heat Exchangers Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 4 Assessing the Condensate-Drainage Behavior of Dehumidifying Heat Exchangers

More information

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance

More information

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 Performance Comparisons Of A Unitary Split System Using Microchannel and

More information

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 Effects of Frost Formation on the External Heat Transfer Coefficient of

More information

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Research On Gas Injection High Temperature Heat Pump With

More information

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area Sahil

More information

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2012 Energy Transfer Based Test Method Development and Evaluation of Horizontal Air

More information

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for

More information

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Evaluation and Design Optimization of Refrigerated Display

More information

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Effect of Height Difference on The Performance of Two-phase Thermosyphon

More information

Air-Cooled Heat Exchanger Performance for R410A

Air-Cooled Heat Exchanger Performance for R410A Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1996 Air-Cooled Heat Exchanger Performance for R41A T. Ebisu Daikin Industries

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

Purdue e-pubs. Purdue University

Purdue e-pubs. Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 206 Experimental Investigation of the Refrigerant Flow Distribution Characteristic

More information

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Experimental Research and CFD Simulation on Microchannel Evaporator Header

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel Flow Heat Exchangers Under Wet Conditions

Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel Flow Heat Exchangers Under Wet Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel

More information

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2006 Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

More information

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE HEFAT2012 9 th International nference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE Kim K.,

More information

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Architectural Engineering -- Faculty Publications Architectural Engineering and Construction, Durham School of 2018 Evaluation

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Purdue e-pubs. Purdue University. Ian H. Bell Purdue University. Eckhard A. Groll Purdue University

Purdue e-pubs. Purdue University. Ian H. Bell Purdue University. Eckhard A. Groll Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Experimental Comparison of the Impact of Air- Side Particulate Fouling

More information

In the name of God. Jami Institute of Jami - Mehdi Rasti

In the name of God. Jami Institute of Jami - Mehdi Rasti In the name of God 1 Heat Transfer Jami Institute of Technology Heat Exchangers part 2 Mehdi Rasti 2 The Counter-Flow Heat Exchanger In contrast to the parallel-flow exchanger, this configuration provides

More information

Performance of CO2 Cycles with a Two-Stage Compressor

Performance of CO2 Cycles with a Two-Stage Compressor Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 Performance of CO2 Cycles with a Two-Stage Yun Hong Hwang University of

More information

Experimental Study on the Performance of Twisted Capillary Tube

Experimental Study on the Performance of Twisted Capillary Tube Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Experimental Study on the Performance of wisted Capillary ube Amr O. Elsayed

More information

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 199 Development of a Transient Simulation Model of a Freezer Part II: Comparison

More information

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle

More information

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement

More information

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences - Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems

More information

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Effect of the Use Pattern on Performance of Heat Pump Water Heater Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Effect of the Use Pattern on Performance of Heat Pump Water Heater

More information

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR Santhosh Kumar Student(M.Tech), Mechanical Dept Gokul group of institutions Visakhapatnam, India M Karteek Naidu ASST PROFF, Mechanical

More information

Gandhinagar Institute of Technology Mechanical Engineering (Thermal Engineering) Semester II. Design of Heat Exchange Equipments [ ]

Gandhinagar Institute of Technology Mechanical Engineering (Thermal Engineering) Semester II. Design of Heat Exchange Equipments [ ] Experiment 1 Study of fundamentals of Fluid Flow and Heat Transfer associated with Heat Exchangers Review questions (1) Significance of dimensionless numbers. (2) Define overall heat transfer coefficient.

More information

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM - 1 - EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM Shun YOSHIOKA, Hyunyoung KIM, Kazushige KASAI, Daikin Industries,

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

Simultaneous Heat and Mass Transfer in a Wetted Heat Exchanger, Part I: Experiments

Simultaneous Heat and Mass Transfer in a Wetted Heat Exchanger, Part I: Experiments Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Simultaneous Heat and Mass Transfer in a Wetted Heat Exchanger, Part I:

More information

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 22 An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning

More information

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible

More information

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Performance Characteristics and Optimization of a Dual-Loop Cycle for a

More information

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2 Modern Applied Science; Vol. 9, No. 13; 2015 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education The Design of a Shell-Tube Heat Exchanger as Evaporator an Absorption

More information

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Mini Vapour Cycle System For High Density Electronic Cooling Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Mini Vapour Cycle System For High Density Electronic Cooling Applications

More information

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING M. POIRIER, D. GIGUÈRE, Z. AIDOUN, M. OUZZANE Natural Resources Canada, CANMET Energy Technology Centre-Varennes 1615, Lionel

More information

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Numerical Simulation of a New Cooling System for Commercial Aircrafts Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Numerical Simulation of a New Cooling System for Commercial Aircrafts Karin

More information

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack #1 Digvijay A. Shelar, #2 N.S. Gohel, #3 R. S. Jha #1 Mechanical Engineering Department,

More information

Global Journal of Engineering Science and Research Management

Global Journal of Engineering Science and Research Management EXPERIMENTAL AND THEORETICAL STUDY OF MINIATURE VAPOR COMPRESSION CYCLE USING MICROCHANNEL CONDENSER Issam M. Ali Aljubury*, Ahmed Q. Mohammed, Marwa S. Neama * Mechanical Eng. Dept. College of Engineering,

More information

ABSTRACT. Professor Reinhard Radermacher, Department of Mechanical Engineering

ABSTRACT. Professor Reinhard Radermacher, Department of Mechanical Engineering ABSTRACT Title of Document EXPERIMENTAL STUDY OF HYBRID COOLED HEAT EXCHANGER Han-Chuan Tsao, Master of Science, 2011 Directed By Professor Reinhard Radermacher, Department of Mechanical Engineering A

More information

Refrigerant Mass and Oil Migration During Start-up Transient

Refrigerant Mass and Oil Migration During Start-up Transient Refrigerant Mass and Oil Migration During Start-up Transient Steffen Peuker, Predrag Hrnjak* Department of Mechanical and Industrial Engineering University of Illinois at Urbana-Champaign 1206 West Green

More information

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES The experimental system established in the present study to investigate the transient flow boiling heat transfer and associated bubble characteristics of

More information

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca

More information

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps

More information

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Experimental

More information

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 The Development Of High Efficiency Air Conditioner With Two Compressors

More information

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube

More information

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators

More information

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Evaluation of a Plug-In Refrigeration System Running Under

More information

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor

More information

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2008 The Innovative Green Technology for Refrigerators Development of Innovative Linear

More information

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers University of Nebraska - Lincoln From the SelectedWorks of David Yuill Summer July 9, 2018 Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

More information

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 216 Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration

More information

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube

More information

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Design and Research of the Digital VRV Multi- Connected Units With Three

More information

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering Real Time Upright Freezer Evaporator Performance Under Frosted Conditions T.

More information

2. HEAT EXCHANGERS MESA

2. HEAT EXCHANGERS MESA 1. INTRODUCTION Multiport minichannel and microchannel aluminium tubes are becoming more popular as components in heat exchangers. These heat exchangers are used in various industrial applications and

More information

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System A D Parekh, and P R Tailor Abstract Because of damaging effect of CFC refrigerants on stratospheric

More information

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent

More information

Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems

Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems OBJECTIVES Warning: though the experiment has educational objectives (to learn about boiling heat transfer, etc.), these should not

More information

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way 1 CHAPTER I INTRODUCTION In the modern life, electronic equipments have made their way in to practically every part, which is from electronic gadgets to high power computers. Electronic components have

More information

Study of R161 Refrigerant for Residential Airconditioning

Study of R161 Refrigerant for Residential Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen

More information

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2004 Development and Performance Measurements of a Small Compressor for Transcritical CO2

More information

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Comparison of Performance of a Residential Air- Conditioning System Using

More information

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Design Optimization of Variable Geometry Microchannel Heat Exchangers Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Design Optimization of Variable Geometry Microchannel Heat Exchangers Long

More information

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Improving Heating Performance of a MPS Heat Pump System With Consideration

More information

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2010 Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear

More information

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Experimental Study of Two-phase Seperators for Vapor Compression Systems

More information

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Control Method Of Circulating Refrigerant Amount For Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Control Method Of Circulating Refrigerant Amount For Heat Pump System Jin

More information

ENSC 388: Engineering Thermodynamics and Heat Transfer

ENSC 388: Engineering Thermodynamics and Heat Transfer ENSC 388: Engineering Thermodynamics and Heat Transfer Experiment 3: Free and Forced Convection Objective Determination of heat transfer coefficient for free and forced convection for different geometries.

More information

Compression of Fins pipe and simple Heat pipe Using CFD

Compression of Fins pipe and simple Heat pipe Using CFD Compression of Fins pipe and simple Heat pipe Using CFD 1. Prof.Bhoodev Mudgal 2. Prof. Gaurav Bhadoriya (e-mail-devmudgal.mudgal@gmail.com) ABSTRACT The aim of this paper is to identify the advantages

More information

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Performance Analysis of a Miniature-Scale Vapor Compression System for

More information

Open-Cell Metal Foams for Use in Dehumidifying Heat Exchangers

Open-Cell Metal Foams for Use in Dehumidifying Heat Exchangers Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Open-Cell Metal Foams for Use in Dehumidifying Heat Exchangers Xiaohong

More information

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 004 Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow

More information

Efficiency of Non-Azeotropic Refrigerant Cycle

Efficiency of Non-Azeotropic Refrigerant Cycle Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 Efficiency of Non-Azeotropic Refrigerant Cycle X. Liu Carrier Corporation

More information

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015 The Design of a Heat Exchanger Shell - Tube as Evaporator an Absorption Chiller Cycle to Reduce the Temperature of the Air Entering Diesel Engine Heavy Loads 75% And 50% of the Engine Part Seyyede Sepideh

More information

Performance Measurement of R32 Vapor Injection Heat Pump System

Performance Measurement of R32 Vapor Injection Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Performance Measurement of Vapor Injection Heat Pump System Yunho Hwang

More information

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition Purdue University Purdue e-pubs nternational Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2 Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

More information

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5 IJAET International Journal of Application of Engineering and Technology ISSN: 2395-3594 Vol-1 No.-2 CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys

More information

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface Journal of Mechanical Science and Technology 23 (2009) 528~535 Journal of Mechanical Science and Technology www.springerlink.com/content/738-494x DOI 0.007/s2206-009-0426-0 A study on performance improvement

More information

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study of Fouling Performance of Air Conditioning System with

More information

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12 EXPERIMENTAL ANALYSIS OF THE EFFECT OF FIN GEOMETRY ON HEAT TRANSFER RATE THROUGH THE REFRIGERATOR CONDENSER ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

More information

System Modeling of Gas Engine Driven Heat Pump

System Modeling of Gas Engine Driven Heat Pump Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 System Modeling of Gas Engine Driven Heat Pump Isaac Mahderekal shenb@ornl.gov

More information

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Conceptual Design of a Better Heat Pump Compressor for Northern Climates Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1976 Conceptual Design of a Better Heat Pump Compressor for Northern Climates D. Squarer

More information

Investigations Of Chinese Cabbage Cold Storage Chamber Operation

Investigations Of Chinese Cabbage Cold Storage Chamber Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Investigations Of Chinese Cabbage Cold Storage Chamber Operation Miroslawa

More information

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2018 Experimental Investigation Of A New Low- Approach Evaporator With Reduced

More information

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University

More information

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Experimental Investigation of a New High Temperature Heat Pump Using Water

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning

More information

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule

More information

Investigation of Evaporator Performance with and without Liquid Overfeeding

Investigation of Evaporator Performance with and without Liquid Overfeeding Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Investigation of Evaporator Performance with and without Liquid Overfeeding

More information

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 22 Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement

More information

Effect of magnetic field on the performance of new refrigerant mixtures

Effect of magnetic field on the performance of new refrigerant mixtures INTERNATIONAL JOURNAL OF ENERGY RESEARCH Int. J. Energy Res. 2003; 27: 203 214 (DOI: 10.1002/er.868) Effect of magnetic field on the performance of new refrigerant mixtures Samuel M. Sami n,y and Shawn

More information

Manufacturing & Testing of Air-to-Refrigerant Heat Exchangers Based on 0.8mm Diameter Tubes

Manufacturing & Testing of Air-to-Refrigerant Heat Exchangers Based on 0.8mm Diameter Tubes Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 216 Manufacturing & Testing of Air-to-Refrigerant Heat Exchangers Based on.8mm

More information