THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

Size: px
Start display at page:

Download "THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS"

Transcription

1 THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS Panu Mustakallio 1, Arsen Melikov 2, Marcin Duszyk 2, Risto Kosonen 1 1 Oy Halton Group Ltd., Helsinki, Finland. 2 International Centre for Indoor Environment and Energy, DTU Civil Engineering, Technical University of Denmark, Lyngby, Denmark. Abstract The objective of this study was to identify the importance of heat load distribution on the cooling power of radiant panels. A full-scale test room was equipped with two top insulated ceiling radiant panels installed near the long walls. Radial multi-nozzle supply air diffuser was installed in the middle of the ceiling so that the supply air jet was flushing the radiant panels. The test room was constructed according EN-standards for accurate measurement of cooling power of the radiant unit. The cooling power of the panels was studied in two situations: 1) without supply air to compare two standardized testing methods for chilled beams in the case of radiant panels when the are conducted through test room walls or when using uniformly distributed heated dummies in the test room, and 2) with supply air in the similar cases as earlier and also in the case when the internal heat loads are located only in one end of the test room. The air temperatures and black ball temperatures were measured in the test room, and supply air jet pattern was visualized with smoke. Two standardized testing methods for the chilled beams gave nearly the same cooling output for the radiant panels. The most significant effect of on the performance of the radiant panels occurs when are located unevenly and their convection flow turns or weakens the supply air jet flushing the radiant panels. This should be taken into account in the design when supply air is used to enhance the operation of the radiant panel. Keywords: radiant panel, cooling power, heat load 1 Introduction The cooling power of radiant panels is affected by the arrangement of in the room because the operation of the panels is based on free convection and radiation. It is important to account for this effect during the design of radiant panel systems because often their cooling output is the limiting factor for the use in practice. The objective of this study was to identify the importance of heat load distribution on the cooling power of radiant panels. The radiant cooling panels are tested normally according EN (2004) standard in test room under uniform distribution of internal heat sources. In this study the cooling power of radiant panels determined by two methods namely with presence of uniform heat load distribution in test room and when the heat load is conducted through the walls of test room. Both methods are used in the standardized testing of active and passive chilled beams. The situation when are located unevenly and located on one end of the room was studied as well. It is similar to the conditions in rooms in the external zone of building where heat loads are located unevenly near warm window façade. 1

2 2 Methods A full-scale test room 4.7 m (L), 3.0 m (W) and 2.5 m/ 2.8 m (false ceiling H/ H) was equipped with two top insulated ceiling radiant panels with dimensions 3 m x 0.6 m. The panels were installed near to the long walls of the room. The multi-nozzle supply air diffuser was installed in the middle of the ceiling so that the supply air jet was flushing the radiant panels. Test was performed first without supply air, and then with 25 l/s (1.8 l/s/m 2 floor) and 16 ⁰C supply air. The test room was constructed according EN-15116/EN standards to allow for accurate measurement of the cooling power of the chilled beams and following also guidelines in chilled ceiling testing standard EN (2004). The water flow rate was measured with electromagnetic flowmeter and air flow rate with orifice plate flowmeter. Temperatures were 4.7m Radiation panel 3m x 0.6m Room height 2.5m / 2.8m (false ceiling / total height Radiation panel 3m x 0.6m 3.0m Heated dummy (cylinder) Case 1 Case 1B Case 2 Case 2B Case 2C Figure 1. Location of the radiation panels, air distribution unit and heat sources in the ceiling Figure 2. A) Overall view of the setup with heated dummies positioned symmetrically; B) heated dummies positioned unevenly, i.e. only in one side of the test room, C) supply air jet smoke visualizations in case 1 and case 2C. 2

3 measured with PT-100 temperature sensors. The measurement systems are designed for maintaining very stabile conditions and are calibrated regularly for maintaining the measurement tolerances required by the EN standard. The accuracy requirement for water flow rate is 1% (+/- 0.5%) and for water temperature 0.05 ⁰C. The test cases are listed in Table 1 and are shown in the Fig. 1. Photos of the actual room and smoke visualizations are shown in the Fig. 2. In the first case, case 1, water temperature for the radiant panels was 15/17 ⁰C and the room air temperature was adjusted to 26 ⁰C by compensating heat load conducted through the walls of test room. In the second case, case 1B, the compensated were located symmetrically inside the test room. Isothermal ambient temperature was used by adjusting the external temperature to the same as average room temperature at 1.3 m height. Supply water temperature and mass flow rate were kept same as in the case 1. The cases 2, 2B and 2C were done similar way as cases 1 and 1B, but with supply air. In the last case, the effect of uneven heat load arrangement was measured. The case 1B is done mostly according to the chilled ceiling testing standard EN (2004). The test room fulfils the accuracy criteria and standardized heated dummies are used. There are only some minor exceptions, e.g. the heated dummies are located correctly, but there should be 10 instead of 8 of them, and at least 70% of ceiling should be covered with radiant panels, now only 26% as in the present study. Room air temperature (T) was measured at four locations and vertical temperature difference at one location. Black ball temperatures (Tbb) were measured at two locations. Supply air flow pattern was visualized with smoke. The measurement locations and heights are shown in the Fig. 3. Cooling power of the radiant panels was calculated from water temperature difference and mass flow rate. Conductances were calculated by dividing the cooling power with the difference of mean water temperature and average room air temperature at 1.3 m height (from four locations measured). Exponent based on radiant panel s manufacturer data was used for the temperature difference. Case parameters and measured cooling powers are shown in the Table 1. Cooling power of 16ºC supply air is approx. 22 W/m 2 floor and of radiant panels 26 W/m 2 floor. This supply air temperature level is often required during summer design day due to the drying of the supply air in the air handling unit Temperature measurements in the test chamber (T=Air temperature, Tbb=Black ball temperature) 1. T1 at 1.3m height Tbb1 at 1.1m height T5 at 0.1m height T6 at 1.8m height T7 at 2.3m height 2. T2, Tbb2 3. T3 4. T4 Figure 3. Locations of the temperature measurement Table 1: Experimental conditions during the tests and measured cooling power CASE ROOM T. SUPPLY AIR WATER IN PANELS TOTAL COOLING [degc] [l/s] [degc] [W] [W/m2_fl.] [kg/s] IN [degc] OUT [degc] [W] [W/m2_fl.] [W] [W/m2_fl.] 1 No supply air, wall B. No supply air, symmetric dummy Multi-nozzle air supply, wall B. Multi-nozzle air supply, symm C. Multi-nozzle air supply, uneven

4 3 Results The measured horizontal and vertical temperature distribution in the studied cases are shown in Fig. 4 and Fig. 5 respectively. The results in Fig. 4 show that the difference between black ball temperature and air temperature was less than 0.5 ºC. The difference between the operative temperature calculated from the black ball temperature following the recommendations in standard ISO 7726, and the air temperature was approx. 20% lower. The largest difference of air temperature in horizontal and vertical direction was measured in the case 2C where the convection flow of the heated dummies centralized to one side of the test room causes higher temperature readings locally. Otherwise the vertical and horizontal temperature difference is less than 0.5 ºC in all cases. Fig. 6 compares the results on the cooling power of the radiant panels determined for the studied cases. The cooling power of the radiant panels was decreased by 7% when the heat load was simulated by heated dummies (case 1B) compared to the case when the heat load was conducted through the walls (case 1). In the case 2 with supply air, the cooling power was increased 10% when comparing to the case 1 without supply air, but this disappeared when comparing the case 2B, with dummy heat loads and supply air, to the case 1. Still when comparing the case 2B with the case 1B (in both cases dummies were used as heat source) there is 5% increase because of the supply air flushing the radiant panels. In the case 2C with uneven heat load distribution (dummies located on one side of the room) the increase in cooling power of the radiant panels disappears. This is caused by the colliding local convection flow from dummies with the ventilation flow that can be seen in the smoke visualization shown in Fig Room temp. (1-4) at 1.3m height / Black ball temp. (bb1-bb2) at 1.1m height Temperature [ºC] T1 Tbb1 T2 Tbb2 T3 T No supply air, wall 1B. No supply air, symmetric dummy 2. Multi-nozzle air supply, wall 2B. Multi-nozzle air supply, symm. 2C. Multi-nozzle air supply, uneven Studied case Figure 4. Room air temperatures and black ball temperatures in the occupied zone 4

5 Height [m] Temperature [ºC] Vertical room temperature in studied cases 1. No supply air, wall 1B. No supply air, symmetric dummy 2. Multi-nozzle air supply, wall heat loads 2B. Multi-nozzle air supply, symm. 2C. Multi-nozzle air supply, uneven Figure 5. Vertical temperature stratification measured in the studied cases Radiation panel cooling conductances with relative increase on top -6.7 % +9.6 % +5.1 % -1.8 % to case 1 to case 1 to case 1B to case 1B 30.0 Conductance [W/K] No supply air, wall 1B. No supply air, symmetric dummy 2. Multi-nozzle air supply, wall 2B. Multi-nozzle air supply, symm. 2C. Multi-nozzle air supply, uneven Studied cases Figure 6. Radiation panel conductances in cooling mode in the studied cases. Comparison of the cases 1B and 2 to the case 1, and of the cases 2B and 2C to the case 1B is shown. 5

6 4 Discussion When comparing the cooling power of the radiant panels in the cases without supply air, the case 1B with dummy used as heat load gives a bit smaller cooling power. Although the difference is not large, the result is not consistent to the assumption that internal, more local should increase the power of the radiant panels. This same effect can be seen more clearly in the cases 2 and 2B when air supply was used. The room temperature in the case 1B was higher than in the other cases for this reason and due to too high dummy heat load comparing to the cooling capacity of the radiant panels. The cooling capacity used to define the dummy heat load was based on the manufacturer s product data that was not detailed enough for this kind of installation at that time when the measurements were performed. The relative effect of that was the biggest in the case without the cooling power of the supply air. Still when the conductances are calculated, the performance of the radiant panel can be compared in different cases. The ratio of radiant and convective heat transfer of radiant panels in cooling conditions is approx. 50/50 according to Babiak et al. (2007). The or supply air jet can effect the convective heat transfer but the radiant part stays nearly the same. When comparing the cases with wall and with dummy, there is most probably somehow non-optimal flow field near the radiant panels in the case with dummy, and it has small effect on the operation of the radiant panels. This should be further studied with CFDsimulations, which could give detailed information on the difference in the flow field between these cases. Radiant panels were located near the long side wall in order to obtain longer distance from the supply air diffuser. This would allow increase of the supply air temperature (which was 16 ºC and close to the water temperature 15/17 ºC cooling the panels) and thus to increase the convective heat transfer between the air and the radiant panel. In the case 2C where heated dummies were located only on one side of the room the generated thermal plums interact with the ventilation flow resulting in its discharge towards opposite end of the room. For that reason the supplied ventilation air does not flush the radiant panel as efficiently as in the case with symmetrical. The effect of the heat load arrangement on the cooling power of the radiant panels is biggest when the thermal plums generated by the heat sources effect significantly the distribution of the supply air jet used to enhance the cooling output of the radiant panel. This can be seen when comparing the cooling power of the cases 2 and 2C. 5 Conclusions The heat load arrangement in room affects the performance of radiant cooling panels. It can be concluded that two standardized methods for testing the performance of chilled beams, namely heat load simulation by dummies and by heat load conducted through walls, give nearly the same cooling output for the radiant panels. The most explicit guideline for the design of the radiant panels when considering the effect of the heat load arrangement is to ensure that the supply air jet flushing the panels is as less as possible influenced by the convective flows generated by the heat load in the room. 6 Acknowledgement The study is supported by Technology Agency of Finland (TEKES). The authors wish to thank Mr. Risto Paavilainen for his participation in the measurement work, and Itula Oy for providing the radiant panels and for all other co-operation. 6

7 7 References European standard EN 14240:2004 Ventilation for Buildings. Chilled ceilings. Testing and rating, European committee for standardization CEN, January 2004, Brussels, Belgium European standard EN 14518:2005 Ventilation for Buildings. Chilled beams. Testing and rating of passive chilled beams, European committee for standardization CEN, June 2005, Brussels, Belgium European standard EN 15116:2008 Ventilation in Buildings. Chilled beams. Testing and rating of active chilled beams, European committee for standardization CEN, April 2008, Brussels, Belgium International standard ISO 7726:1998 Ergonomics of the thermal environment- Instruments for measuring physical quantities, International Organization of Standardization ISO, November 2008, Geneve, Switzerland, p , Babiak, J., Olesen, B.W., Petras, D. (2007) Low temperature heating and high temperature cooling, Rehva guidebook no 7, Finland, ISBN , p

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Thermal Comfort with Convective and Radiant Cooling Systems

Thermal Comfort with Convective and Radiant Cooling Systems Proceedings of 9 th Windsor Conference: Making Comfort Relevant Cumberland Lodge, Windsor, UK, 7-10 April 2016. Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Thermal Comfort with

More information

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail. Powered by TCPDF (www.tcpdf.org) This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail. Mustakallio, Panu; Kosonen, Risto;

More information

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Risto Kosonen 1, Arsen Melikov 2, Boryana Yordanova 2 and Lyuben Bozkhov 2 1 Halton Oy 2 International

More information

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June Thermal comfort with radiant and convective cooling systems Risto Kosonen Halton Oy and Aalto University risto.kosonen@halton.com Panu Mustakallio Halton Oy The difference in thermal conditions between

More information

Performance of Chilled Beam with Radial Swirl Jet and Diffuse Ceiling Air Supply in Heating Mode

Performance of Chilled Beam with Radial Swirl Jet and Diffuse Ceiling Air Supply in Heating Mode Downloaded from orbit.dtu.dk on: May 12, 2018 Performance of Chilled Beam with Radial Swirl Jet and Diffuse Ceiling Air Supply in Heating Mode Bertheussen, Bård ; Mustakallio, Panu ; Melikov, Arsen Krikor;

More information

Comparison of radiant and convective cooling of office room: effect of workstation layout

Comparison of radiant and convective cooling of office room: effect of workstation layout Downloaded from orbit.dtu.dk on: Apr 27, 2018 Comparison of radiant and convective cooling of office room: effect of workstation layout Bolashikov, Zhecho Dimitrov; Melikov, Arsen Krikor; Rezgals, Lauris;

More information

American Society of Heating, Refrigerating and Air-Conditioning Engineers

American Society of Heating, Refrigerating and Air-Conditioning Engineers Flow Pattern and Thermal Comfort in Office Environment with Active Chilled Beams Journal: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Manuscript ID: Draft Publication:

More information

Human response to thermal environment in rooms with chilled beams

Human response to thermal environment in rooms with chilled beams Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment

More information

The impact of thermal loads on indoor air flow

The impact of thermal loads on indoor air flow The impact of thermal loads on indoor air flow Risto Kosonen 1, Maija Virta 1 and Arsen Melikov 2 1 Halton Oy 2 International Center for Indoor Environment and Energy, Department of mechanical Engineering,

More information

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Downloaded from orbit.dtu.dk on: Mar 02, 2018 Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Wu, Xiaozhou; Fang, Lei; Olesen, Bjarne

More information

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN , Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

Air and operative temperature measurements in a plus-energy house under different heating strategies

Air and operative temperature measurements in a plus-energy house under different heating strategies Downloaded from orbit.dtu.dk on: Oct 03, 2018 Air and operative temperature measurements in a plus-energy house under different heating strategies Kazanci, Ongun Berk; Olesen, Bjarne W. Published in: Proceedings

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0188 ISBN: 978-83-7947-232-1 Dispersion of pollutants released at floor level under three types of heating systems: A CFD study. Laura

More information

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Arsen K. Melikov 1,*, Marcin Duszyk 1, Barbora Krejciríková 1,2, Tomonori Sakoi 3, Jan

More information

Don t Turn Active Beams Into Expensive Diffusers

Don t Turn Active Beams Into Expensive Diffusers This article was published in ASHRAE Journal, April 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING G. COURRET, P. W. EGOLF, O. SARI Haute école spécialisée de Suisse occidentale, Institut de Génie Thermique, Rte de Cheseaux 1, CH

More information

AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE

AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE R Kosonen 1,*, H Koskela 2 and P Saarinen 2 1 Halton Oy, Haltonintie 1-3, 474 Kausala, Finland 2 Finnish Institute of

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

nzeb office building

nzeb office building nzeb office building Ympäristötalo in Helsinki, Finland City of Helsinki has taken the exemplary role of the public sector seriously. The latest proof is the Environment Centre building Ympäristötalo completed

More information

State of the Art of HVAC Technology in Europe and America

State of the Art of HVAC Technology in Europe and America Downloaded from orbit.dtu.dk on: Oct 27, 2018 State of the Art of HVAC Technology in Europe and America Olesen, Bjarne W.; Kazanci, Ongun Berk Published in: Proceedings of the World Engineering Conference

More information

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater MIRCEA NICOARĂ mircea.nicoara@mec.upt.ro AUREL RĂDUłĂ aurel.raduta@mec.upt.ro LAURENłIU ROLAND CUCURUZ roland.cucuruz@mec.upt.ro COSMIN

More information

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS Stefano Schiavon, Ph.D., P.E. Center for the Built Environment, University of California at Berkeley, Member ASHRAE

More information

Performance Rating of Active Chilled Beams

Performance Rating of Active Chilled Beams AHRI Standard 1241 (SI) 2016 Standard for Performance Rating of Active Chilled Beams IMPORTANT SAFETY RECOMMENDATIONS AHRI does not set safety standards and does not certify or guarantee the safety of

More information

IEA EBC Annex 59 - Possibilities, limitations and capacities of indoor terminal units

IEA EBC Annex 59 - Possibilities, limitations and capacities of indoor terminal units Downloaded from orbit.dtu.dk on: Jan 06, 2019 IEA EBC Annex 59 - Possibilities, limitations and capacities of indoor terminal units Kazanci, Ongun Berk; Olesen, Bjarne W. Published in: Energy Procedia

More information

Simulation of Full-scale Smoke Control in Atrium

Simulation of Full-scale Smoke Control in Atrium Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 608 613 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Simulation of Full-scale Smoke Control in

More information

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office Downloaded from orbit.dtu.dk on: Aug 24, 2018 Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office Zukowska-Tejsen, Daria; Wolsing, Marie; Grysbæk, Malene; Hviid, Christian Anker

More information

Experimental study of space cooling using ceiling panels equipped with capillary mats

Experimental study of space cooling using ceiling panels equipped with capillary mats Experimental study of space cooling using ceiling panels equipped with capillary mats Tiberiu Catalina and Joseph Virgone University of Lyon, France Corresponding email: tiberiu.catalina@insa-lyon.fr SUMMARY

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

Fire Risks of Loviisa NPP During Shutdown States

Fire Risks of Loviisa NPP During Shutdown States Fire Risks of Loviisa NPP During Shutdown States Sami Sirén a*, Ilkka Paavola a, Kalle Jänkälä a a Fortum Power And Heat Oy, Espoo, Finland Abstract: Fire PRA for all 15 shutdown states of Loviisa NPP

More information

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca

More information

Halton Rex 600 Basic R6B - Active chilled beam

Halton Rex 600 Basic R6B - Active chilled beam Halton Rex 600 Basic R6B - Active chilled beam Halton Rex 600 Basic chilled beam is: A base version to the combined cooling, heating, and supply air unit for flush installation within a suspended ceiling.

More information

CBH - Active Chilled Beam. Halton CBH. Active Chilled Beam

CBH - Active Chilled Beam. Halton CBH. Active Chilled Beam Halton CBH Active Chilled Beam Combined cooling, heating and supply air unit for exposed wall installation Well suited for hotel guest rooms with high requirements for thermal comfort and room acoustics

More information

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products Bakalis S.*, Giannakourou M.C. and Taoukis P. School of Chemical Engineering, National Technical

More information

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling The cooling capacity of the Thermo Active Building System combined with acoustic ceiling Peter Weitzmann, Technical consultant, BuildDesk A/S; peter.weitzmann@builddesk.dk Emanuele Pittarello, MSc, International

More information

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply. Halton CSW Swirl comfort unit for ceiling installation The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply. A combined cooling, heating, and supply-air unit for flush

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

Research on fire protection methods and a case study "Futurum"

Research on fire protection methods and a case study Futurum Available online at www.sciencedirect.com Procedia Engineering 40 (2012 ) 339 344 Steel Structures and Bridges 2012 Research on fire protection methods and a case study "Futurum" J. Outinen a *, J. Samec

More information

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering Analysis of the influence of open door size on fire smoke diffusion law in protective engineering Abstract Zheli Xing a, Jinfeng Mao b, Chaofeng Li c and Jin Zhou d PLA University of Science and Technology,

More information

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam Halton CBC Active Chilled Beam Combined cooling, heating, and supply air unit for flush installation within a suspended ceiling Well suited for spaces with high cooling loads and low humidity load Ideal

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016 Downloaded from vbn.aau.dk on: januar 28, 2019 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's

More information

UL268 7 th challenge with single infrared smoke detector

UL268 7 th challenge with single infrared smoke detector UL268 7 th challenge with single infrared smoke detector Hans Aebersold Siemens Schweiz AG, Building Technologies Division, Switzerland Abstract Coming up UL217 8th and UL268 7th edition with added new

More information

Typologies of Hybrid Ventilation in Schools

Typologies of Hybrid Ventilation in Schools Typologies of Hybrid Ventilation in Schools Peter van den Engel Delft Technological University, the Netherlands Corresponding email: p.vd.engel@deerns.nl SUMMARY This article is the result of a study on

More information

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps Søren Østergaard Jensen February 2017 1 Preface The present document

More information

Cooling load calculations of radiant and all-air systems for commercial buildings

Cooling load calculations of radiant and all-air systems for commercial buildings Downloaded from orbit.dtu.dk on: Aug 17, 2018 Cooling load calculations of radiant and all-air s for commercial buildings Bourdakis, Eleftherios; Bauman, Fred; Schiavon, Stefano; Raftery, Paul; Olesen,

More information

A study of Transient Performance of A Cascade Heat Pump System

A study of Transient Performance of A Cascade Heat Pump System Available online at www.sciencedirect.com ScienceDirect Energy Procedia 79 (2015 ) 131 136 2015 International Conference on Alternative Energy in Developing Countries and Emerging Economies A study of

More information

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom Improvement of Temperatures Stratification caused by Air-conditioner by means of Ceiling Fan in Classroom Natsuka Wakamatsu 1, Yoshihisa Momoi 1, Toshio Yamanaka 1, Kazunobu Sagara 1, Hisashi Kotani 1

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Corn drying experiments by pilot dryer

Corn drying experiments by pilot dryer Agronomy Research Biosystem Engineering Special Issue 1, 91-97, 2011 Corn drying experiments by pilot dryer L. Kocsis, M. Herdovics, J. Deákvári and L. Fenyvesi Hungarian Institute of Agricultural Engineering,

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER A. Bolher 1, E. Fleury 1, J.R. Millet 1, D. Marchio 2 and P. Stabat 2. 1 Centre Scientifique et Technique du bâtiment, 84, avenue

More information

EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM

EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM Hui-Pei Chang 1, San-Ping Ho 2*, Chao-Shi Chen 3,Tsung-Ming Wu 4,Chin-Feng Chen 5 and Cheng-Wei Wu 6 1 Department

More information

QUALITY ASSURANCE AND SAFETY AT A TID RADIATION TEST LABORATORY

QUALITY ASSURANCE AND SAFETY AT A TID RADIATION TEST LABORATORY QUALITY ASSURANCE AND SAFETY AT A TID RADIATION TEST LABORATORY Seville, 31.03.2016 Pedro Martin, RadLab Radiation Facility Supervisor TÜV NORD GROUP QUALITY ASSURANCE AND SAFETY «Anything that can go

More information

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1

More information

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Siddharth Jain, Yogesh Deshpande, Atul Bokane, Arun Kumar Santharam, and Deepak Babar, Halliburton Abbreviations: Computational

More information

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? Corresponding author: Jasmin Geppert University of Bonn Household and Appliance Technology Section Nussallee 5 D-53115 Bonn E-Mail: haushaltstechnik@uni-bonn.de

More information

FLOW CONDITIONS IN A MECHANICALLY VENTILATED ROOM WITH A CONVECTIVE HEAT SOURCE

FLOW CONDITIONS IN A MECHANICALLY VENTILATED ROOM WITH A CONVECTIVE HEAT SOURCE EFFECTIVE VENTILATION 9th AIVC Conference, Gent, Be1 gium 12-15 September, 1988 Poster 19 FLOW CONDITIONS IN A MECHANICALLY VENTILATED ROOM WITH A CONVECTIVE HEAT SOURCE PER HEISELBERG, PETER V. NIELSEN

More information

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti

More information

Experimental Verification of Cooling Load Calculations for Spaces with Non-Uniform Temperature Radiant Surfaces

Experimental Verification of Cooling Load Calculations for Spaces with Non-Uniform Temperature Radiant Surfaces Experimental Verification of Cooling Load Calculations for Spaces with Non-Uniform Temperature Radiant Surfaces ASHRAE 1729-TRP Project Prepared by Dr. Atila Novoselac Principle Investigator Dr. Stephen

More information

Center for the Built Environment October 2013

Center for the Built Environment October 2013 Thermal Comfort in the Context of Radiant Systems Center for the Built Environment University of California Berkeley Center for the Built Environment October 2013 Overview of talk A brief summary of research

More information

ISO AIR FILTERS FOR GENERAL VENTILATION: DETERMINING FRACTIONAL EFFICIENCY

ISO AIR FILTERS FOR GENERAL VENTILATION: DETERMINING FRACTIONAL EFFICIENCY ISO 16890-2 AIR FILTERS FOR GENERAL VENTILATION: DETERMINING FRACTIONAL EFFICIENCY APPLICATION NOTE AFT-005 (US) Contents Introduction to ISO 16890... 1 How ISO 16890 Compares to EN 779 and ASHRAE 52.2...

More information

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation Cooling and heating systems Static cooling ceiling system SKS-/3 DS 10 E 01.010 Static cooling ceiling system SKS-/3 Main features Preliminary remarks / Applications 3 Main dimensions and materials 3 Construction

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0320 ISBN: 978-83-7947-232-1 The Analysis of the Air Velocity Distribution above the Trench Heater with Natural Convection Mariusz

More information

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys Enabling Wellbeing M.A.R.V.E.L. revolutionises energy footprint in galleys The M.A.R.V.E.L.* is the first truly intelligent,

More information

Available online Journal of Scientific and Engineering Research, 2017, 4(10): Research Article

Available online   Journal of Scientific and Engineering Research, 2017, 4(10): Research Article Available online www.jsaer.com, 2017, 4(10):305-311 Research Article ISSN: 2394-2630 CODEN(USA): JSERBR Low Cost Humidity/Temperature Calibration System Yasser A. Abdelaziz 1 Central Laboratories Department,

More information

Hot-air heating of family houses with accumulation of energy in the floor

Hot-air heating of family houses with accumulation of energy in the floor Agronomy Research 11 (2), 329 334, 2013 Hot-air heating of family houses with accumulation of energy in the floor P. Kic Czech University of Life Sciences Prague, Faculty of Engineering, Kamycka 129, 16521,

More information

Energy and Exergy Performances of Air-Based vs. Water-Based Heating and Cooling Systems: A Case Study of a Single-Family House

Energy and Exergy Performances of Air-Based vs. Water-Based Heating and Cooling Systems: A Case Study of a Single-Family House Downloaded from orbit.dtu.dk on: Apr 11, 2018 Energy and Exergy Performances of Air-Based vs. Water-Based Heating and Cooling Systems: A Case Study of a Single-Family House Kazanci, Ongun Berk; Shukuya,

More information

State-Of-The-Art Developments to Save Energy in Coating Drying. Bob Bates, P.Eng Metso Paper

State-Of-The-Art Developments to Save Energy in Coating Drying. Bob Bates, P.Eng Metso Paper State-Of-The-Art Developments to Save Energy in Coating Drying Bob Bates, P.Eng Metso Paper Overview Two (2) case studies are presented to illustrate two (2) new developments in coating drying, with a

More information

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

Available online at  ScienceDirect. Procedia Engineering 135 (2016 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 135 (2016 ) 439 444 Study of Grid Ceiling on Parametric Optimization Design of Automatic Sprinkler System Xiang-yu Qu a,*, Hai-yan

More information

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array International Journal of Modern Studies in Mechanical Engineering (IJMSME) Volume 4, Issue 1, 2018, PP 11-16 ISSN 2454-9711 (Online) DOI: http://dx.doi.org/10.20431/2454-9711.0401002 www.arcjournals.org

More information

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection DS 4094 E 05.2007/1 Technical Selection Main features 2 Preliminary remarks 3 Construction design 3 Main dimensions and materials 3 Design data 3 Layout example 5 Design specifications 8 Installation instructions

More information

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System International Journal of Engineering Research and Technology. ISSN 0974-3154 Volume 9, Number 1 (2016), pp. 89-94 International Research Publication House http://www.irphouse.com Experimental Studies on

More information

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection Julio Toko, Martin Fromme, Bernd Horbach and Wieland Hill LIOS Technology GmbH, Cologne, Germany

More information

Heat transfer enhancement in an air process heater using semi-circular hollow baffles

Heat transfer enhancement in an air process heater using semi-circular hollow baffles Available online at www.sciencedirect.com Procedia Engineering 56 ( 2013 ) 357 362 5 th BSME International Conference on Thermal Engineering Heat transfer enhancement in an air process heater using semi-circular

More information

Purdue e-pubs. Purdue University

Purdue e-pubs. Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 206 Experimental Investigation of the Refrigerant Flow Distribution Characteristic

More information

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation BTBa CEILING UNIT FLUSHLINE BTBa FLUSHLINE BTBa is a complete climate system offering immense flexibility. Ideal for large areas with

More information

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Peter Stahl Wagner Schweiz AG, Wallisellen, Switzerland Abstract Fire detection system and firefighting solutions are getting a

More information

Design, Development & Testing of Double Pipe Heat Exchanger With Heat Transfer Enhancement Liners

Design, Development & Testing of Double Pipe Heat Exchanger With Heat Transfer Enhancement Liners Volume 2, Issue 1, January 2017 ISSN (online): 2456-0006 International Journal of Science Technology Management and Research Available online at: Design, Development & Testing of Double Pipe Heat Exchanger

More information

Effect of Inclination Angle on Temperature Characteristics of Water in- Glass Evacuated Tubes

Effect of Inclination Angle on Temperature Characteristics of Water in- Glass Evacuated Tubes International Conference on Ideas, Impact and Innovation in Mechanical Engineering (ICIIIME 217) ISSN: 2321-8169 Effect of Inclination Angle on Temperature Characteristics of Water in- Glass Evacuated

More information

C o o l i n g a n d h e a t i n g s y s t e m s

C o o l i n g a n d h e a t i n g s y s t e m s 2 C o o l i n g a n d h e a t i n g s y s t e m s Cooling ceiling system description Preliminary remarks Cooling ceilings Cooling ceilings are room cooling systems for placement in the ceiling zone. Their

More information

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Heat Transfer Basics Human Body Heat Exchange Radiant Cooling Basics Radiant Cooling Suitability? Radiant

More information

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile Available online at www.pelagiaresearchlibrary.com Advances in Applied Science Research, 2013, 4(5):232-237 ISSN: 0976-8610 CODEN (USA): AASRFC Performance analysis of ejector refrigeration system with

More information

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing

More information

K.F. Fong *, C.K. Lee, T.T. Chow

K.F. Fong *, C.K. Lee, T.T. Chow Investigation on radiative load ratio of chilled beams on performances of solar hybrid adsorption refrigeration system for radiant cooling in subtropical city K.F. Fong *, C.K. Lee, T.T. Chow Building

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY Proceedings of BS5: 4th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 5. AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN

More information

Connect North and South Korean Separated Families Higher Comfort Lower Energy

Connect North and South Korean Separated Families Higher Comfort Lower Energy Transsolar Academy 2016-2017 Final Project Summary Connect North and South Korean Separated Families Higher Comfort Lower Energy SUIN KIM 1, ELMIRA REISI 2 1 Transsolar Academy, Transsolar Energietechnik

More information

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature International Journal Of Computational Engineering Research (ijceronlinecom) Vol 3 Issue 3 Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

More information

Mathematical Simulation of Longan Fruit Drying

Mathematical Simulation of Longan Fruit Drying Mathematical Simulation of Longan Fruit Drying Aree Achariyaviriya, Somchart Soponronnarit and Jirawan Tiansuwan ABSTRACT The objectives of this study were to develop a mathematical model and to simulate

More information

Department of MCE, Islamic University of Technology 2. Abstract

Department of MCE, Islamic University of Technology 2. Abstract Paper ID: TE-85 Study of power consumption characteristics of LPG and R134a in a vapor compression refrigeration system Md. Abu Shaid Sujon 1, Rakibul Hossain Ahmed 2, Dr. A.K.M. Sadrul Islam 3, Sk. Suzauddin

More information

SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS

SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS Klaus Ellehauge SolEnergi Center Danmark, Danish Technological Institute, Energy, Teknologiparken, DK-8 Aarhus C, Tel.: +45 722 137, Fax:

More information

Numerical analysis of thermal comfort in Near-Zero Energy Buildings (NZEB) with light radiant ceilings and diffuse ventilation.

Numerical analysis of thermal comfort in Near-Zero Energy Buildings (NZEB) with light radiant ceilings and diffuse ventilation. Numerical analysis of thermal comfort in Near-Zero Energy Buildings (NZEB) with light radiant ceilings and diffuse ventilation. Marie Rugholm Krusaa *1,2, Christian Anker Hviid 1,2, Jakub Kolarik 1 1 Technical

More information

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Proceedings of the International Conference in Dubrovnik, 15-16 October 2015 FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Johan Anderson a, Lars Boström a, Robert Jansson

More information

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER WULANDANI, D., K. ABDULLAH, E. HARTULISTIYOSO Department of Agricultural Engineering, Faculty of Agricultural

More information

lindab ventilation Lindab Comfort Waterborne indoor climate solutions Product overview

lindab ventilation Lindab Comfort Waterborne indoor climate solutions Product overview lindab ventilation Lindab Comfort Product overview Products within the Lindab Waterborne solutions, e.g. chilled beams, facade systems, radiant heating and cooling panels, uses water to regulate the room

More information

Units for suspended ceilings

Units for suspended ceilings X X testregistrierung Units for suspended ceilings Type, hinged induced air grille, water connections Active chilled beam with two-way air discharge and horizontal heat exchanger, suitable for grid ceilings

More information