UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

Size: px
Start display at page:

Download "UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units..."

Transcription

1 Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators Rooftop Units...18 Telecommunications Hut/POP Applications...20 Heat Pumps...23 Pump Lead/Lag...24 Questions Common to All Applications Controllers Configured to Function as Point Multiplexers Procedure Overview Detailed Procedures Creating a Fan Coil Application Creating a Unit Ventilator Application...34 Creating a Rooftop Unit Application...45 Creating a Telecommunications Hut/POP Application...57 Creating a Heat Pump Application...58 Creating a Pump Lead/Lag Application Completing the Common Section of UNT Application Question/Answer Paths Configuring a Controller as a Point Multiplexer Module Point Assignments and Parameters Fan Coil Units Unit Ventilators Johnson Controls, Inc. Code No. LIT Software Release 8.03

2 2 Rooftop Units...87 Telecommunications Hut/POP...91 Heat Pumps...96 Pump Lead/Lag Parameters...100

3 3 Using Introduction Unitary (UNT) controller applications are specifically designed for digital control of packaged air handling units, rooftop units, unit ventilators, fan coils, heat pumps, and other terminal units including Air Handling Units (AHUs) serving a single zone or room. These applications may be used with standalone controllers, controllers connected to the N30/N31 Supervisory Controller, controllers connected to Metasys Companion /Facilitator controllers, or controllers integrated with the Metasys Network through a Network Control Module (NCM). This document provides an overview of UNT applications and includes procedures for the creation of applications. This document describes how to: create a fan coil application create a unit ventilator application create a rooftop unit application create a Telecommunications Hut/POP (Point of Presence) application create a heat pump application create a pump lead/lag application complete the common section of UNT application question/answer paths configure a controller as a point multiplexer module

4 4 Key Concepts UNT Controller Applications Getting Started UNT controller applications are specifically designed for digital control of packaged air handling units, rooftop units, Telecommunications Hut/POPs, unit ventilators, fan coils, heat pumps, and other terminal units serving a single zone or room. These applications may be used with standalone controllers, controllers connected to Companion/Facilitator controllers or controllers integrated with the Metasys Network through a Network Control Module (NCM). When connected to the Metasys N2 Network, the controller provides all point and control information to the rest of the network. The devices communicate through the N2 Bus. For a smaller facility, the controller can stand alone in conjunction with a Zone Terminal. In all configurations, the UNT applications can configure a wide variety of single zone and room Heating, Ventilating, and Air Conditioning (HVAC) equipment. The UNT applications support up to 16 sideloops that are separate from the main control logic. See Appendix A: Sideloop Applications (LIT ) for more information. The UNT controller can control many different single zone or room applications and control strategies (Figure 1). The types of zone applications that can be controlled include: unit vent fan coil packaged rooftops Telecommunications Hut/POP heat pump generic Input/Output (I/O) The first five applications are explained in this application note. Use the table of contents to locate the specific application you are using. Note: Do not use UNT1100 Series controllers for floating or three wire actuator applications, because these actuators could compromise the service life of the UNT1100 output relays.

5 5 See the HVAC PRO User s Guide for information on HVAC PRO software. See the Unitary Controller (UNT) Technical Bulletin (LIT ) for UNT wiring and installation information. File Open New Select Existing File Central Plant Applications OEM Applications Rooftop Applications Terminal Unit Applications Generic I/O Pump Lead/Lag Control Packaged Rooftop Unit Vent Fan Coil Heat Pump Point Multiplexer CNUNTFLW Figure 1: UNT Application Configuration Paths The UNT can be pre-configured with control strategies for specific Original Equipment Manufacturer (OEM) applications. HVAC PRO software contains the configuration files to commission specific OEM applications. HVAC PRO software, which is a part of the M-Tool software package, also allows you to configure all hardware points as inputs or outputs to the N2 Network. Modes of Operation Table 1 illustrates the source of control commands for each mode of operation. Table 1: Command Source for Modes of Operation Mode of Operation N2 ZT BI Built-in HVAC PRO Software Commissioning* Occ/Unocc X X X X Standby X X X Shutdown X X X X Temp Occ/Occ Extend X X Boost X Power Fail Restart X Warmup X X X Vent X X Purge X X * Online commissioning via the Zone Bus or N2 network connection. When you exit Commissioning mode, parameters that are not saved to the controller are released immediately. Overrides to inputs, outputs, and commandable parameters are also released when commissioning is exited. Refer to Exiting Commission Mode for ASC Devices in the Commissioning a Controller chapter of the HVAC PRO User s Guide for further information.

6 6 Control Sequence Figure 2 shows the relationship of the heating (htg), economizer, and mechanical cooling (clg) output commands vs. changes in zone temperature. Increasing Output Commands 100% 0% Heating Prop Band Heating Setpoints - Occupied - Standby - Unoccupied Econ Prop Band Cooling Deadband or Alternate Cooling Deadband Cooling Setpoints - Occupied - Standby - Unoccupied Cooling Prop Band Increasing Zone Temperature GRPHUV Figure 2: Heating and Cooling Setpoints All unitary controllers use the same default zone setpoints for the Occupied, Unoccupied, and Standby modes of operation. See the default I/O point and parameter tables for each application to determine default values used to set up the base sequence of operation. Note: Standby mode only initiates when the controller is already in Unoccupied mode. Closed Loop Control The controller provides separate heating and cooling setpoints with associated proportional bands. Integration is available for heating and cooling, including economizer and mechanical cooling functions. Default Parameter The cooling deadband allows you to sequence mechanical cooling with an economizer output or overlap the two outputs. Set the cooling deadband equal to the economizer prop band to provide a sequence of free cooling and mechanical cooling without overlap. IMPORTANT: When using integration and increasing the economizer proportional band to tune the damper control, make sure that the cooling deadband is equal to the economizer proportional band.

7 7 The alternate cooling deadband allows you to decide if the mechanical cooling output should start at the cooling setpoint when free cooling is not available. By default, all zone integration timers are zero and no integration is added into the zone control process. If integration is desired, add the adjustment during commissioning only after the control process is under stable proportional control. For room control, a value of 400, equivalent to 10 minutes, is a good place to start for an integration time. A larger integration value has less effect on the control loops. If using integration, the proportional band may need to be increased for stable control. IMPORTANT: For applications that use on-off or staged outputs for heating and/or cooling, use of integration may make the loop difficult to tune. This is due to interaction with the minimum on and off timers and maximum cycles per hour. In these cases, extremely long integration times are appropriate, on the order of 600 to 1000 (15 to 25 minutes), for zone control.

8 8 Damper Logic Modes The Warmup, Vent, and Purge modes (Table 2) are available in any configuration that incorporates an outside air damper. Table 2: Damper Logic Modes Mode Warmup The Warmup mode is pre-configured in the controller, so the user is not prompted through the Question and Answer session for this feature. A Warmup cycle is initiated by an N2 or Zone Terminal command only when the controller is in Unoccupied mode. Once set to Warmup mode, systems configured with outside air dampers hold the dampers fully closed and sequence heating/cooling. The fan cycles based on the call for heating or cooling. Outside air damper operation is enabled when the system is commanded to Occupied mode. Occupied mode does not automatically initiate a disable command to Warmup, although it does disable the Warmup operation. Vent Vent mode is only initiated or ended via an N2 command. During Vent mode, systems configured with a proportional or Zone Bus output to the outside air damper hold the dampers in the fully open position until Vent mode is ended. The mechanical heating and cooling outputs operate as required. Purge Purge mode is only initiated or ended via an N2 command. During Purge mode, systems configured with a proportional or Zone Bus output to the outside air damper hold the dampers in the fully open position until Purge mode is ended. The mechanical heating and cooling outputs are shut off. Note: If you command Vent and Purge modes at the same time, the Vent mode takes priority. Vent and Purge modes do not automatically start the fan. To run the fan in Vent or Purge modes, you must first command the controller to Occupied mode. Fan Coil Units Applications A fan coil unit is a simple method of controlling an individual space. Typically used in entryways and other similar perimeter zones, fan coils consist of a fan, a heating and/or cooling coil, and a filter (Figure 3). In some cases, the unit may come with a manually adjustable outside air damper. If the unit requires an automatic outside air damper, use either the Unit Ventilator or Rooftop application.

9 9 Wall Zone Sensor Conditioned Air Fan Controller Heating and/or Cooling Coil Air Filter Return Air FANCOIL Figure 3: Typical Fan Coil Unit A controller with a wall-mounted or return air mounted sensor controls fan coil heating and cooling in sequence to achieve setpoint. Water-based fan coil systems may be arranged in a 2-, 3-, or 4-pipe configuration. These configurations require different numbers of valves and different control sequences. If the fan coil has separate heating and cooling coils, separate valves are used. When a common coil is used for heating and cooling, the supply and return piping systems affects the control method. Two Pipe Heating and Cooling Systems When a common coil provides both heating and cooling with a single valve, controller action must switch when chilled water, not hot water, is present (Figure 4). Hot or Chilled Water Supply Common Heating and Cooling Coil Hot or Chilled Water Return pipes Figure 4: Two Pipe Heating and Cooling Three Pipe Heating and Cooling Systems IMPORTANT: This application was a common piping practice in the past and is only found in retrofits. When a common coil provides both heating and cooling, two valves are required: a chilled water supply valve and a hot water supply valve (Figure 5). These valves are then modulated in sequence to control the temperature.

10 10 Hot Water Supply Chilled Water Supply Common Heating and Cooling Coil Hot and Chilled Water Return Pipes1 Figure 5: Three Pipe Heating and Cooling Four Pipe Heating and Cooling Systems IMPORTANT: This application is not common. You cannot configure an application of this type using HVAC PRO software. When a common coil provides both heating and cooling, three valves are required: a chilled water supply valve, a hot water supply valve, and a switching return valve (Figure 6). The heating and cooling valves are then modulated in sequence to control the temperature. The return valve is switched while both valves are closed. Hot Water Supply Chilled Water Supply Common Heating and Cooling Coil Hot Water Return Chilled Water Return Pipes2 Figure 6: Four Pipe Heating and Cooling Control System Fault Tolerance If the zone sensor becomes unreliable, the position of the valves is user definable from 0-100%.

11 11 Unit Ventilators Applications Unit ventilators heat, ventilate, and cool a space by introducing outside air in quantities up to 100%. They also provide the option to cool and dehumidify with a cooling coil (either chilled water or DX). Hot water, steam, or electric resistance provide heating. Valves, face and bypass dampers, or control switches/relays are used to control these sources of heat. The basic components of a unit ventilator are encased in a housing and include: a fan a motor a heating element dampers a filter outlet grilles (or diffusers) Unit ventilators are used primarily in schools, meeting rooms, offices, and other areas where the density of occupancy requires controlled ventilation. These ventilators provide sufficient heating capacity to rapidly warm up a room in the morning and to ventilate and heat as required during occupancy. In most cases, unit ventilators use additional outside air to dissipate uncontrolled heat. Figure 7, Figure 8, and Figure 9 show component placement in various American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) cycles.

12 12 Glass Conditioned Air Wall Discharge Low Limit Zone Sensor Fan Bird Screen Coil Valve Actuator Outside Air Intake Louver Air Filter Recirculated Air Intake Outside Air Damper Damper Actuator Recirculated Air Damper UNITVENT Figure 7: Component Placement for ASHRAE Cycles I and II

13 13 Glass Conditioned Air Wall Zone Sensor Fan Outside Air Intake Louver Bird Screen Coil Valve Actuator Air Filter Return Air/Mixed Air Control Recirculated Air Intake Outside Air Damper Damper Actuator Recirculated Air Damper UNITVEN2 Figure 8: Component Placement for ASHRAE Cycle III

14 14 Glass Conditioned Air Wall Discharge Low Limit Fan Bird Screen Coil Valve Actuator Zone Sensor Outside Air Intake Louver Air Filter Recirculated Air Intake Outside Air Damper Damper Actuator Recirculated Air Damper UNITVEN3 Figure 9: Component Placement for Cycle W ASHRAE Control Cycles Unit ventilators are generally controlled by one of the standard ASHRAE Control Cycles (I, II, III, or W). Variations in the amount of outside air delivered to the room determine which cycle to use. All unit manufacturers use standard ASHRAE Control Cycle designations. ASHRAE cycles I, II, III, and W allow the user to wire a fan status input to the controller. This application provides the actual status of the fan, because the controller may not have total control over the fan s operations. To prevent frozen coils, use the status of the fan to modify the control algorithm.

15 15 Cycle I ASHRAE Cycle I (Figure 10) supplies 100% outside air at all times. As the room temperature rises into the normal operating range of the zone thermostat, the outside air damper is fully opened and the return air damper is closed. The heating valve is controlled by the zone thermostat to maintain setpoint. The discharge air thermostat can override the zone thermostat action on the heating valve to open the valve to maintain a minimum discharge air temperature into the space. Open ½ Closed Room Setpoint Heating Normal Ventilation Room Temperature Outside Air (OA) Damper Valve or Face Damper Cycle1 Figure 10: ASHRAE Cycle I Cycle II A fixed minimum amount of outside air, normally 15 to 50%, is admitted during the heating and ventilating period (Figure 11). The percentage is gradually increased to 100%, if required, during the ventilating period. The heating valve and outside air dampers are operated in sequence as required to maintain space temperature. The discharge air sensor can override the zone thermostat action on the heating valve to open the valve. As the discharge temperature continues to drop, the heating goes to 100% and the Outside damper closes to prevent discharge air from dropping below a minimum temperature.

16 16 Open Room Setpoint 1/2 Minimum Closed Heating Normal Ventilation Room Temperature OA Damper Valve or Face Damper cycle2 Figure 11: ASHRAE Cycle II Cycle III In this ASHRAE cycle (Figure 12), the discharge sensor of Cycles I and II becomes a mixed air sensor by placing it in the unit ventilator airstream entering the heating source. During the heating, ventilating, and cooling stages, Cycle III supplies a variable amount of outside air as required to maintain a fixed temperature (typically 55 F) entering the heating coil. As the zone temperature rises into the normal range of the zone thermostat, ventilation dampers control the air temperature entering the heating coil at the mixed air setpoint. Space temperature is controlled by positioning the heating valve, as required. Without low limit interference, the room sensor directly controls the heating element. Open Room Setpoint OA at 50 degrees 1/2 Mix Air Control Range OA at 0 degrees Closed Heating Normal Ventilation Room Temperature OA Damper Valve or Face Damper cycle3a Figure 12: ASHRAE Cycle III

17 17 Cycle W In addition to the standard ASHRAE cycles of control, a fourth cycle, Cycle W (Figure 13), has been created. Cycle W is the same as ASHRAE Cycle II with one exception: the discharge air low limit sensor controls only the outside and recirculated air dampers. The room sensor directly controls the heating element. Open Room Setpoint 1/2 Minimum Closed Heating Required Normal Cooling Required Room Temperature OA Damper Valve or Face Damper cyclew Figure 13: Cycle W Control System Fault Tolerance The following points are useful for control system fault tolerance: If the outside air sensor is unreliable, the damper goes to 0%, cooling lockout status is off, and economizer status is off. If the zone sensor is unreliable, heating and cooling outputs are user definable. The fan goes on or stays on. If the discharge sensor is unreliable, the damper goes to minimum position if occupied and 0% if unoccupied. If warmer/cooler remote setpoint adjustments become unreliable, the controller uses the software setpoints. If heating/cooling remote setpoint adjustments become unreliable, the controller uses the software setpoints.

18 18 Rooftop Units Applications An Outside rooftop unitary equipment system cools or heats an entire zone. The complete system consists of unitary equipment, a ducted air distribution system, and a temperature control system. The equipment is generally mounted on the roof but can also be mounted on grade. When a single unit application is required, the rooftop unit and associated ductwork constitute a central station all air system. Each temperature control zone may have its own unit. Determine the control zones by using cooling and heating loads for the space served, occupancy considerations, allowable roof loads, flexibility requirements, appearance, duct-size limitations, or equipment size availability. These units also serve core areas of buildings with perimeter spaces being served by packaged terminal air conditioners (fan coil, unit ventilator, and heat pump). The rooftop unit provides standalone control of all heating, cooling, and economizer functions. The unit can heat and cool at all times with automatic changeover, regardless of the mode of operation of other spaces in the building. Night setback (unoccupied) and standby operations conserve energy when the space is unoccupied for short and long time periods. You can add an optional airflow switch to immediately shut down all heating/cooling equipment upon loss of fan airflow. Lighting integration and diagnostics for staged outputs to indicate malfunction are also provided. To save cooling energy, this application can obtain free cooling from outside air rather than starting the mechanical equipment. If required, you can readjust the cooling setpoint based on the zone humidity to save on cooling energy. (According to ASHRAE comfort zone standards, if the zone humidity is low during cooling, the zone temperature can be higher while establishing the same comfort level.)

19 19 Upgrade Information Staged heating/cooling diagnostics are supported only by controllers with A0n or later firmware. If you upgrade the controllers, the upgrade uses all existing controller parameters unless there is a newly assigned function. When doing an upgrade, the cooling lockout for staged cooling is now automatic. HVAC PRO software assigns an outside air sensor to an unused Analog Input (AI). If all AIs are used, it overwrites user-defined analog input at AI5 with an outside air sensor. This default cooling lockout value is 15.0 C (60.0 F). If you upgrade a rooftop unit that has a proportional damper, the discharge low limit proportional band has changed from a default of 1.5 C (3.0 F) to a default of C (-30.0 F). If this point has been overridden by a network device, check the override to make sure it accounts for the new value. Control System Fault Tolerance The following points are useful for control system fault tolerance: If an outside air sensor becomes unreliable, the damper goes to 0%, heating and cooling lockout status is off, and economizer status is off. If the zone sensor is unreliable, heating and cooling outputs are user selectable. The fan goes on or stays on. If a discharge sensor becomes unreliable, the damper goes to minimum position if occupied and 0% if not occupied. In the case of the zone setpoint adjusted from the zone humidity selection, if the zone humidity sensor is unreliable, the controller uses the default setpoints. In the case of the outside air enthalpy or enthalpy comparison economizer switchover selections, if the outside air or zone humidity sensor becomes unreliable, the controller uses the dry bulb temperature default for economizer switchover. If warmer/cooler remote setpoint adjustments become unreliable, the controller uses the default setpoints. If heating/cooling remote setpoint adjustments become unreliable, the controller uses the default setpoints.

20 20 Telecommunications Hut/POP Applications A Telecommunications Hut/POP (Point of Presence) unitary system controls the HVAC equipment for the zone in a telecommunications/data communications equipment hut. The huts feature redundant heating/cooling units. There are two types of Telecommunications Hut/POP applications, the Compressor Lead/Lag application and the Compressor Stage Swapping application. Compressor Lead/Lag Application The Compressor Lead/Lag application has two equal-sized units that share equal time as the lead system. The two units in combination are treated as two stages of heating or cooling, but the first stage unit is rotated based on runtime. The runtime is a configurable parameter adjustable from 0 to 1000 hours. A pushbutton connected to Binary Input (BI) 4 permits a manual changeover of the lead unit. Any changeover resets the runtime counter to zero. As the zone temperature drops below the heating setpoint, the first heat stage energizes based on the percent heating command selected during the configuration. If the zone temperature continues to drop, the second stage energizes. When the zone temperature rises, stages turn off in the reverse order (last on, first off). Each stage has a minimum on time and stage delay that must be met before the next stage energizes or turns off. As the zone temperature rises above the zone cooling setpoint and the economizer status is Off, the outside air damper is at its minimum position setting. The first stage of cooling energizes based on the percent compressor command selected during the configuration. If zone temperature continues to increase, the second stage energizes after the configurable interstage delay. The cooling stages turn off in reverse order (last on, first off). Compressor Stage Swapping Application The Compressor Stage Swapping application has two unequal-sized (one small and one large) DX compressors to control the cooling. The compressors function in three stages of cooling: the small compressor alone, the large compressor alone, and both compressors together.

21 21 As the zone temperature rises above the zone cooling setpoint and the economizer status is Off, the dampers modulate to the minimum position and the first stage energizes when the compressor command reaches 33%. When the compressor command reaches 66%, the first stage de-energizes and the second stage energizes. The first stage re-energizes when the compressor command reaches 100% and then both stages are in operation. Each stage has a minimum on time and cooling stage delay that must be met before the next stage energizes. Free Cooling To save cooling energy, the economizer allows free cooling from outside air rather than starting the mechanical equipment. The economizer status On means that free cooling is available and the dampers will modulate from 0% to 100% as the zone temperature increases. If the economizer status is On and the cooling lockout status is Off, the dampers modulate to full open. If the zone temperature continues to rise, the first cooling stage energizes and the dampers modulate closed to lengthen the on time (false loading), prevent short cycling, and facilitate the pump down cycle of the refrigeration equipment. If you change the defaults and allow free cooling and mechanical cooling simultaneously, air entering the compressor at less than 65 F can cause it to shut down, requiring a manual reset. With a proportional economizer, the system assigns a discharge air sensor to maintain the low limit logic for the economizer cycle. A reverse acting Proportional plus Integral (PI) algorithm backs off the economizer command and positions the damper to maintain the low limit setpoint. The Discharge Air Low Limit (DALL) control can override the minimum position setting if the discharge temperature continues to drop below the setpoint (e.g., freezing conditions in the outside air). If you require a minimum damper position, regardless of the DALL (e.g., if you are not in danger of freezing mechanical equipment), use the damper offset parameter that prevents the damper from going below this value during Occupied or Standby modes. The DALL setpoint automatically increases (up to 3.0 C [5.0 F]) depending on the difference between the zone temperature and the Outside Air Temperature (OAT). For example, if the outside air temperature is 20 F colder than the zone temperature, the DALL does not reset. However, if the outside air is 100 F colder than the zone, the DALL setpoint increases 3.0 C (5.0 F). If an outside air sensor is not connected or is unreliable, the DALL setpoint does not reset.

22 22 If the zone or discharge air sensor is unreliable, the damper is commanded to minimum position during Occupied and Standby modes and to 0% during Unoccupied mode. If the Outside air temperature is above the Economizer Switchover parameter, the economizer status is Off. If either the outside air or zone sensors become unreliable, economizer status is Off. Airflow Interlock An airflow switch is incorporated in the application. Airflow must be proven to operate the heating, cooling, and damper outputs. If airflow is lost for longer than the Fan Alarm Delay parameter; the heating, cooling, and damper commands go to 0%. If integration is used, the integrated value is zeroed and the fan status comes back on, the controller commands the outputs with a proportional-only command and then starts to add integration again. A fan alarm indication is given if the Fan Alarm Delay parameter expires and the fan command and airflow switch are in different states. Heating and Cooling Lockout When the outside air temperature exceeds the lockout setpoint, heating lockout status is On, indicating heat is unavailable. If the outside air temperature is below the cooling setpoint, cooling lockout status is On, indicating cooling is unavailable. Heating and cooling failsoft commands operate if the zone sensor becomes unreliable. Table 3 shows the status of the failsoft and the temperature conditions where it occurs. During cooling failsoft, you can specify the compressor output command between 0% and 100%. Table 3: Zone Sensor Unreliable Failsoft Lockout Status Outside Air Temperature (OAT) vs. Lockout temperature Lockout status Condition OAT > Heating Lockout On Heating Failsoft OAT < Heating Lockout* Off Heating Failsoft OAT > Cooling Lockout* Off Cooling Failsoft OAT < Cooling Lockout On Cooling Failsoft * Indicates a two-degree (C and F) differential, heating 2 and cooling +2.

23 23 Heat Pumps Applications Unitary heat pump equipment consists of factory-matched air conditioning systems that are shipped as complete, preassembled units and include internal wiring, controls, and piping. The heat pump acts as a heat engine in reverse. This means it requires work input to remove heat from a low temperature source and deliver it to a higher temperature sink. The heat pump achieves this by using refrigerant circulated within a compact closed-circuit coil to absorb and transfer heat from one area to another. The difference between a heat pump and a common air conditioner is the heat pump s ability to reverse the roles of the evaporator and condenser coils. The process begins with the evaporator coil absorbing heat from the air around it. The compressor then pumps refrigerant to the condenser where the heat is rejected to the surrounding air. During the cooling season, the unit reverses the evaporator and condenser coils, thus absorbing heat from inside the building and discharging it outside. The heat pump uses a single source of energy to fulfill a dual function of heating and cooling, so a single piece of equipment achieves year-round comfort. A reversing valve or valves, located in the refrigerant circuit, accomplishes the system changeover from Cooling to Heating mode. The heat pump application includes an economizer option to take advantage of outside air as a source of free cooling. The two basic types of unitary heat pumps in general use are the air to air and water to air heat pump. The air to air heat pump uses an air to refrigerant heat exchanger that extracts heat from outside air when heating indoor air, and rejects heat to outside air when cooling indoor air. Motor-driven or manually operated dampers can reciprocate the air circuit to obtain either heated or cooled air for the conditioned space. The water to air heat pump relies on water as the heat source and sink and uses air to transmit heat to or from the conditioned space. Typically, the water supply is a recirculating closed loop, but it could also be a well, lake, or stream. A refrigerant-to-water heat exchanger is used as a refrigerant heat source when heating indoor air and as a refrigerant heat sink when cooling indoor air. In both applications, specify whether mechanical cooling is prevented from operating based on the outside air temperature.

24 24 Pump Lead/Lag The use of electric-resistive elements as a supplemental heat source is optional. This is typical if heating needs exceed the capacity obtainable from equipment selected for the cooling load. The heaters only energize after all heat pump compressors are fully loaded. A user-defined delay takes effect following the transition to Standby or Occupied modes to prevent the supplemental heat from operating immediately after startup. This allows the heat pump compressors time to respond to a call for heat. An optional outside air sensor prevents heater elements from energizing during mild weather conditions when they are not needed. You can define a flow switch to prevent the heat pump from operating unless airflow is proven. In addition, immediate shutdown of compressors and supplemental heat results if loss of airflow occurs during normal operation. Control System Fault Tolerance Heating and cooling failsoft commands can operate the heat pump compressor if the zone sensor becomes unreliable. The command to the supplemental heat goes to 0% if the zone temperature sensor becomes unreliable. All other failsoft conditions are described in the sequence of operation. Applications A hot water or chilled water circulating system ordinarily uses two circulating pumps. They are used as the lead or main operating pump and the standby or backup pump. When the lead pump is enabled, it operates continuously. The status of the pumps can be monitored in two ways: a common flow switch for both or a separate flow switch for each pump. If the lead pump fails, it triggers an alarm and the lag pump starts. You have the option to turn off the output to the lead pump when the lead pump fails. The lead pump resumes operation when the alarm reset is triggered.

25 25 Questions Common to All Applications A common set of questions appears in each of the UNT application question/answer paths. A brief description of the results follows the question. The remainder of this topic provides related information on several of the questions in the common portion of the question/answer paths. Occupied Mode During Occupied mode, the controller sequences the heating/economizer/cooling outputs based on the occupied setpoints. During Unoccupied mode, the controller sequences the heating/economizer/cooling outputs based on the unoccupied setpoints. Standby Mode The Standby mode is an unoccupied strategy and does not have any effect when the controller is in the Occupied mode. When Standby is on, the controller sequences the heating/economizer/cooling based on the standby setpoints. Shutdown Mode All configurations have a Shutdown command as an option. When shutdown is enabled, the fan and cooling devices are commanded off, and the heating is commanded to the shutdown position specified by the user. At the same time, the integration timers are set to zero so no controller windup occurs while the system is off. The user-adjustable shutdown position for heating is available with HVAC PRO software Release 7.00 and later on Unit Vent applications only. All other UNT Configurations All configurations have a Shutdown command as an option. When shutdown is enabled, all fans, heating, and cooling devices are commanded to off (0% command). At the same time, the integration timers are set to zero so no controller windup occurs while the system is off. When the Shutdown command is issued to a normally open valve, the controller either sends 10 VDC (for an analog output) or energizes the triac providing 24 VAC (for binary outputs [BOs]) to drive the valve to its 0% flow position. When the Shutdown command is issued to a normally closed valve, the controller either sends 0 VDC (for analog output [AO]) or de-energizes the triac providing 0 VDC (for binary outputs) to drive the valve to its 0% flow position.

26 26 If your application requires the normally open valve to fail open on shutdown, there are two ways you can accomplish this: Add a relay to remove the 10 VDC or 24 VAC signal when shutdown is enabled. If you have a supervisory system, you can write logic to command the output to On (100% command). This causes the controller to send either 0 VDC (for an analog output) or de-energize the triac (for binary outputs), which drives the valve to its 100% flow position. All configurations have a Shutdown command as an option. When shutdown is enabled, all outputs to fans, heating, and cooling are turned off and integration timers are set to 0, so no windup occurs when the system is put back into control. Temporary Occupied Mode Temporary Occupied mode allows you to set the controller to Occupied mode for a user-defined time period and then return to Unoccupied mode. During Temporary Occupied mode, the controller maintains occupied temperature setpoints. For UNT applications, you may need to monitor the status of the temporary occupancy status data point to turn on the central system or maintain records for tenant billing. When you enable the Temporary Occupied mode, a time-out setpoint called occupied override time and a temporary occupancy status point are added to the parameter table. Once you start Temporary Occupied mode, it remains in effect until the override time runs out; it cannot be canceled. Boost Mode If you have not configured Temporary Occupied mode in your application, you may enable Boost mode. Boost mode allows an occupant to quickly change the controller s operating mode to full heating or cooling within an area. A popular application for Boost mode is a conference room where the number of people entering the room changes quickly, causing major load variations in the space. The controller must be in Occupied mode for Boost mode to work. While in Boost mode, the controller provides either 100% heating if the zone temperature is below the zone heating setpoint, or 100% cooling if the zone temperature is above the zone cooling setpoint, for a user defined period. If the temperature is in the deadband, pushing Boost has no effect. Boost mode is discontinued if the temperature moves into the deadband area (between heating and cooling setpoints).

27 27 When you enable Boost mode, time-out setpoints called Boost Override Time and Binary Data (BD) Status Point are added to the parameter table. To use the Boost mode, go to the parameters list box and specify the length of time that you want Boost mode to be active (in minutes) in the Boost Override Time field. The timer starts when you release the zone sensor momentary button and cannot be canceled. Diagnostics Unit Vent, Rooftop, Heat Pump, and Fan Coil UNT applications include the capability for diagnostics. The answer to the question asking the user to add diagnostics to the application defaults to Yes. Controllers Configured to Function as Point Multiplexers You can configure a controller to function as a point multiplexer module. This allows you to use all inputs and outputs for independent monitoring and control through the Metasys, N30/N31, or Companion/Facilitator systems. Note: The logic added when these questions are answered applies only to any sideloops that are defined later. It does not affect user-defined points that are not part of a sideloop. The remainder of this topic provides related information on the questions in the question/answer path. Occupied Mode During Occupied mode, the controller sequences the heating/economizer/cooling outputs based on the occupied setpoints. During Unoccupied mode, the controller sequences the heating/economizer/cooling outputs based on the unoccupied setpoints. Shutdown Mode All configurations have a shutdown command as an option. When shutdown is enabled, all outputs to fans, heating, and cooling are turned off and integration timers are set to 0, so no windup occurs when the system is put back in control.

28 28 Power Fail Restart Logic This mode allows you to disable all BOs of the controller that are in sideloops whenever the device first powers up; however, this does not apply to Binary Outputs associated with sideloops defined as Condition Single BOs or BOs mapped to a supervisory controller. You may stage the restart timers per floor or per area. This is useful when multiple controllers are used in a building, and you want to stagger the times when each controller energizes its outputs. A restart status variable indicates On for the duration of the delay. Point Multiplexer Input/Output Points The hardware inputs and outputs are all set to unused unless defined for occupied or shutdown mode during the Question and Answer session. To rename a point, follow the normal hardware definition steps to match the input or output type definition to the hardware being monitored or controlled. You can define any sideloops needed in the controller.

29 29 Procedure Overview Table 4: Using To Do This Create a Fan Coil Application Create a Unit Ventilator Application Create a Rooftop Unit Application Create a Telecommunications Hut Application Create a Heat Pump Application Create a Pump Lead/Lag Application Complete the Common Section of UNT Application Question/Answer Paths Configure a Controller as a Point Multiplexer Module Follow These Steps: On the File menu, click New. Select Application Group > Terminal Unit Applications. Select Application > Fan Coil. Answer the questions as they are presented. On the File menu, click New. Select Application Group > Terminal Unit Applications. Select Application > Unit Vent. Answer the questions as they are presented. On the File menu, click New. Select Application Group > Rooftop Applications. Select Application > Packaged Rooftop. Answer the questions as they are presented. On the File menu, click New. Select Application Type > Telecommunications Hut/POP Application. Select Compressor Lead/Lag Application or Compressor Stage Swapping Application. On the File menu, click New. Select Application Group > Terminal Unit Applications. Select Application > Heat Pump. Answer the questions as they are presented. On the File menu, click New. Select Application Group > Central Plant Applications. Select Application > Pump Lead/Lag Control. Answer the questions as they are presented. Answer the questions as they are presented. On the File menu, click New. Select Application Group > Generic I/O. Select Application > Point Multiplexer. Answer the questions as they are presented.

30 30 Detailed Procedures Creating a Fan Coil Application To create a fan coil application: 1. On the File menu, click New. 2. Select Application Group > Terminal Unit Applications. 3. Select Application > Fan Coil. 4. Answer the questions as they are presented (Figure 14) using the information in the remainder of this procedure as a guide. Note: Once you have answered the specific fan coil questions, the question/answer path automatically goes to the questions common to all applications. See the Completing the Common Section of UNT Application Question/Answer Paths procedure for a description of that path. Select Heating Type: Two Pipe Common Htg/Clg Coil (Incr) Two Pipe Common Htg/Clg Coil (Prop) None Proportional Normally Open Valve Normally Closed Valve/Single Stage Select Cooling Type: Incremental None Proportional Normally Open Valve Normally Closed Valve/Single Stage Incremental Fan Cycled during Occupied and Standby Modes? No Yes To Questions Common To All Applications Fancqa Figure 14: Fan Coil Question/Answer Path

31 31 Table 5: Select Heating Type Select Heating Type Choose from the options in Table 5. Option Two Pipe The controller determines the current mode using a binary input. When the binary input Common Htg/Clg indicates that the fan coil is in Heating (Htg) mode (on = heating mode), the controller Coil (incr) modulates a floating/three-wire valve to control the zone temperature at the heating setpoint. When the binary input indicates the fan coil is in Cooling (Clg) mode (off = cooling mode), the controller modulates a valve to control the zone temperature at the cooling setpoint. The controller uses two binary outputs to position the control valve. The specified stroke time determines the timing of these binary outputs. To determine the required valve position, the controller uses the zone temperature and energizes the appropriate output for a percent of full stroke. As the required position drops below the current position, the controller energizes the appropriate output to close the valve. As the required position increases, the controller energizes the other output to open the valve. When the change from the current position to the calculated new position is within the controller s deadband, neither output is energized, leaving the valve in its current position. The controller uses overdrive logic to ensure the position of the valve. When the output reaches 99%, it is driven for 1.5 times the stroke time, causing the valve to reach its 100% position. If the controller determines that the valve remains at the 100% position for 20 minutes, it again drives the output for 1.5 times the stroke time to ensure the device is in the proper position. This can occur again after another 20 minutes elapse and the valve remains at the 100% position. When the output reaches 1%, it is driven for 1.5 times the stroke time, causing the valve to reach its 0% position. If the controller determines that the valve remains at the 0% position for 20 minutes, it again drives the output for 1.5 times the stroke time to ensure the device is in the proper position. This can occur once more after another 20 minutes elapse and the valve remains at the 0% position. If your actuator does not have equal stroke times in the open and close directions, see the end of Table 59 for the equation to determine the proper stroke time for the actuator. The controller provides separate heating and cooling setpoints with associated proportional bands for each mode. Integration is available for each mode. Two Pipe The controller determines the current mode using a binary input. When the binary input Common Htg/Clg indicates that the fan coil is in Heating mode (on = Heating mode), the controller Coil (prop) modulates a valve to control the zone temperature at the heating setpoint. When the binary input indicates the fan coil is in Cooling mode (off = Cooling mode), the controller modulates a valve to control the zone temperature at the cooling setpoint. None There is no point/parameter assignment or logic sequence for this selection Proportional The controller modulates a valve from 0-100% as the zone temperature goes through the heating proportional band. Normally Open The controller provides a binary output to control a normally open heating valve. When Valve the zone temperature drops below the heating setpoint through the proportional band, the controller de-energizes the binary output. The binary output energizes when the zone temperature rises above the heating setpoint (see Figure 15). The binary output is subject to minimum on, minimum off, and cycles-per-hour settings. Normally Closed The controller provides a binary output to control the normally closed heating valve or Valve/Single normally off electric heat. When the zone temperature drops below the heating setpoint Stage through the proportional band, the controller energizes the binary output. The binary output is de-energized when the zone temperature rises above the heating setpoint. The binary output is subject to minimum on, minimum off, and cycles-per-hour settings. Continued on next page...

32 32 Option (Cont.) Incremental The controller uses two binary outputs to position the control valve. The specified stroke time determines the timing of these binary outputs. To determine the required valve position, the controller uses the zone temperature and energizes the appropriate output for a percent of full stroke. As the zone temperature drops below the heating setpoint through the heating proportional band, the required position changes from 0 to 100%. As the required position drops below the current position, the controller energizes the appropriate output to close the valve. As the required position increases, the controller energizes the other output to open the valve. When the change from the current position to the calculated new position is within the controller s deadband, neither output is energized, leaving the valve in its current position. The controller uses overdrive logic to ensure the position of the valve. When the output reaches 99%, it is driven for 1.5 times the stroke time, causing the valve to reach its 100% position. If the controller determines that the valve remains at the 100% position for 20 minutes, it again drives the output for 1.5 times the stroke time to ensure the device is in the proper position. This can occur again after another 20 minutes elapse and the valve remains at the 0% position. If your actuator does not have equal stroke times in the open and close directions, see the end of Table 59 for the equation to determine the proper stroke time for the actuator. Zone Temperature Heating Setpoint Heating = Off Heating Proportional Band Heating = On untcmd2 Figure 15: Heating Control Diagram for Normally Open and Normally Closed Valves

33 33 Table 6: Select Cooling Type Select Cooling Type Choose from the options in Table 6. Option None Proportional Normally Open Valve Normally Closed Valve/Single Stage Incremental There is no point/parameter assignment or logic sequence for this selection The controller modulates a valve from 0-100% as the zone temperature goes through the cooling proportional band. If heating is also selected, the cooling setpoint is above the heating setpoint to prevent simultaneous operation of heating and cooling. The controller provides a binary output to control a normally open cooling valve. When the zone temperature rises above the cooling setpoint through the proportional band, the controller de-energizes the binary output. The binary output energizes when the zone temperature drops below the cooling setpoint. The binary output is subject to minimum on, minimum off, and cycles-per-hour settings. The controller provides a binary output to control the normally closed cooling valve or normally off cooling stage. When the zone temperature rises above the cooling setpoint through the proportional band, the controller energizes the binary output. The binary output de-energizes when the zone temperature drops below the cooling setpoint. The binary output is subject to minimum on, minimum off, and cycles-per-hour settings. The controller uses two binary outputs to position the control valve. The timing of these outputs is based on an operator-specified stroke time. The controller uses the zone temperature to determine the required position of the valve. Then the controller causes the appropriate output to energize for a percent of full stroke to achieve the required valve position. As the zone temperature rises above the cooling setpoint, the controller energizes the appropriate output to open the valve. As the zone temperature decreases, the controller energizes the other output to close the valve. When the temperature is within the deadband of the controller, neither output energizes, leaving the valve in its current position. The controller uses overdrive logic to ensure the position of the valve. When the output reaches 99%, it is driven for 1.5 times the stroke time, causing the valve to reach its 100% position. If the controller determines that the valve remains at the 100% position for 20 minutes, it again drives the output for 1.5 times the stroke time to ensure the device is in the proper position. This can occur once more after another 20 minutes elapse and the valve remains at the 0% position. If your actuator does not have equal stroke times in the open and close directions, see the end of Table 59 for the equation to determine the proper stroke time for the actuator. Zone Temperature Cooling = On Cooling Setpoint Cooling Proportional Band Cooling = Off untcmd Figure 16: Cooling Control Diagram for Normally Open and Normally Closed Valve

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

TEC210x-2 Series Networked Thermostats

TEC210x-2 Series Networked Thermostats Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

TEC2100 Series Networked Thermostats

TEC2100 Series Networked Thermostats Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...

More information

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application 2050 Application Note 140-1136 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware Outputs...

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

ZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 Application Note 140-1042 Building Technologies Table of Contents Overview... 4 Hardware

More information

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

BACnet Points List for Single Compressor Water to Water PROSSWWE-01 The network variables will be listed by point type instance convention. 2:1 would mean point type 2, point instance 1. All volatile (Output) type points will revert to the uncommanded values after a power

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

iworx Air Side Application Wiring Guide

iworx Air Side Application Wiring Guide iworx Side Application Wiring uide Pages ASM2 Sequence of peration & ypical Wiring 1 ALM2 Sequence of peration & ypical Wiring 2 U2 Sequence of peration, Flow iagram & ypical Wiring 3 - U3 Sequence of

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application 2273 Application Note 140-1045 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT8600 Rooftop Unit Heat Pump and Indoor Air Quality Controllers 3 VT86X0U5X00B

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

TEC Networked Multi-Stage Economizer Thermostat

TEC Networked Multi-Stage Economizer Thermostat Installation Instructions Issue Date January 19, 2005 TEC2104-2 Networked Multi-Stage Economizer Thermostat Application The TEC2104-2 thermostat is an N2 networked thermostat that provides control of single-

More information

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Product Bulletin T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4, T601DFH-4+PIR, T602DFH-4+PIR,

More information

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide SE8600 Series Room Controllers 2 TABLE OF CONTENTS Overview 2 SE8600 Rooftop Unit and Indoor Air Quality Controllers 3 SE8600UxBxx 2 Heating

More information

Johnson Controls Fan Coil Units and Direct Digital Controls

Johnson Controls Fan Coil Units and Direct Digital Controls Product Bulletin Issue Date August 12, 2005 Johnson Controls Fan Coil Units and Direct Digital Controls This offering includes Johnson Controls fan coil units with a factory-installed Johnson Controls

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT86X0U5X00B 2 heating / 2 Cooling for Rooftop unit and Indoor air quality 3

More information

Metasys Integrator McQuay Application

Metasys Integrator McQuay Application Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator McQuay Application Introduction Page * Application Details * Component

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH, SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS Options AG3 Unit-Mounted Ductstat Options AG15, AG16 A = Ductstat Temperature Module P/N 115848 B = Stage Adder Module, P/N 115849 (quantity varies

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual: 200-393O Supersedes: 200-393N Date: 2-26-6 Page of 8 CONTENTS Shipping

More information

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1 Model TRO24T4XYZ1 Description The TRO24T4XYZ1 is a combination controller and thermostat. The VAV Thermostat Controller is designed for simple and accurate control of any variable air volume box in a number

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,

More information

AdaptAire. Digital Control System. User Manual

AdaptAire. Digital Control System. User Manual AdaptAire Digital Control System User Manual Rev. 10-22-07 1 Table of Contents OVERVIEW... 6 NETWORKING... 7 ADAPTAIRE DEFAULT SETTINGS... 7 UNIT OPERATING MODES... 8 MDT Controls:... 8 UNIT OFF MODE...8

More information

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

Advanced Installation and Configuration Instructions

Advanced Installation and Configuration Instructions TP-WEM01-A Performance Series AC/HP Wi- Fi Thermostat Carrier Côr Thermostat Advanced Installation and Configuration Instructions Table of contents How to Use This Document... 3 Wiring Diagrams... 4 Installations

More information

T600MEP-2 Programmable Economizer Thermostat

T600MEP-2 Programmable Economizer Thermostat Installation Instructions Issue Date January 19, 2005 T600MEP-2 Programmable Economizer Thermostat Application The T600MEP-2 is a programmable thermostat for control of single- or two-stage unitary rooftop

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

CommStat 4 Controller

CommStat 4 Controller CommStat 4 Controller CommStat 4 Telecom HVAC Controller The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners, heat pumps and air conditioners with

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide HomeWorks QS Palladiom Thermostat Configuration Guide Table of Contents Description...4 Step : Identify the HVAC Equipment and Confirm Device Installation...5 Identify the HVAC Equipment...5 Confirm Device

More information

American University Design Standards

American University Design Standards 25 95 00 CONTROL SEQUENCES FOR HVAC PART 1. GENERAL 1.01 SECTION INCLUDES A. Description of Work B. Control Sequences General Requirements C. System Specific Control Sequences 1.02 RELATED DOCUMENTS A.

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

Pioneer Gold Controller Technical Guide

Pioneer Gold Controller Technical Guide Pioneer Gold Controller Technical Guide Pioneer Gold Controller Code: Version 1.03 Electric Heat Expansion Module Code: Version 1.0 Used with AAON WSHP WV Series Vertical and WH Series Horizontal This

More information

CONTENTS. Installation Guide. VT7200 Series

CONTENTS. Installation Guide. VT7200 Series VT7200 Series Installation Guide For mercial HVAC Applications November 2015 CONTENTS Installation 2 Location 2 Installation 2 Configurable BI/UI inputs overview 4 Network ready 6 Terminal, Identification

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

TEC Networked Multi-Stage Thermostat

TEC Networked Multi-Stage Thermostat Installation Instructions Issue Date September 2, 2003 TEC2103-1 Networked Multi-Stage Thermostat Application The TEC2103-1 is an N2 networked thermostat that provides control of multi-stage Heating, Ventilating,

More information

Installer Guide. WARNING Important Safety Information. 1 Specifications

Installer Guide. WARNING Important Safety Information. 1 Specifications 1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Heat Pump or 2 Heat / 2 Cool Conventional Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front

More information

COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems

COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals control sequences Table 47: QST / EST Analog Electronic Control Strategies Control Package Number QST EST FS-A-5000 FSE-A-5000 FS-A-5001 FSE-A-5001 FS-A-5002 FSE-A-5002 FS-A-5003 FSE-A-5003 FS-A-5004 FSE-A-5004

More information

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs TEC2620 Series Non-Programmable Fan Coil Network Thermostat ler and Remote I/O Relay Packs TEC2620H-0, TEC2620C-0, TEC2620H-0+PIR, TEC2620C-0+PIR, TEC2621H-0, TEC2621C-0, TEC2621H-0+PIR, TEC2621C-0+PIR

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

ROOM THERMOSTATS KNX BASIC DOCUMENTATION

ROOM THERMOSTATS KNX BASIC DOCUMENTATION ROOM THERMOSTATS KNX BASIC DOCUMENTATION Contents 2 2 2 2 ABOUT THIS DOCUMENT Document use / request to the reader Target audience, prerequisites Glossary 59 59 60 62 63 HANDLING Mounting and installation

More information

Commercial Touchscreen Thermostat

Commercial Touchscreen Thermostat 55,13M 1/27 Supersedes 12/25 Commercial Touchscreen Thermostat 25 Lennox Industries, Inc. Dallas, Texas, USA APPLICATION Page 1 INSTALLATION INSTRUCTIONS The Lennox Commercial Touchscreen Thermostat provides

More information

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

Siemens Thermostats. RDY2000BN Thermostat

Siemens Thermostats. RDY2000BN Thermostat Siemens Thermostats RDY2000BN Thermostat Answers for infrastructure and cities. Introducing the RDY2000BN BACnet Commercial Thermostat Bring more buildings and zones under control Reduce energy costs BACnet

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs Lesson 1 - Basic Heat Pump Theory (Part 1) Describe the basic operation of a heat pump. Explain the function of various heat pump controls. Interpret the wiring diagrams and performance data provided by

More information

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT-1201736 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST

INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST DC3002 and DC3003 SOLID STATE LEAD/LAG CONTROLLER with DC FAN CONTROL Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just

More information

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Product Bulletin T606MSN-4, T606MSN-4+PIR, T606MSP-4, T606MSP-4+PIR The T606MSN-4 and T606MSN-4+PIR Series Non-programmable

More information

MicroTech Water-Cooled Screw Chiller Controller

MicroTech Water-Cooled Screw Chiller Controller BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software

More information

- Data Brochure Boiler Control 274

- Data Brochure Boiler Control 274 - Data Brochure Boiler Control 274 274_D 03/17 The Boiler Control 274 operates up to four on/off boilers to provide outdoor reset operation, domestic hot water and setpoint operation with priority. When

More information