1 Engineering Bulletin Gas Heat for M-Series and T-Series Climate Changer Air Handlers March 2004 CLCH-PRB010-EN

2 Preface Gas heat can be a good heating option for any of the following applications: Climates and applications with large heat loads Applications with high outside air requirements to comply with ASHRAE Standard 62 Buildings without a central boiler plant Remote locations where boiler capacity or water piping expense is prohibitive Areas with relatively inexpensive natural gas or expensive electricity The gas heat offering for the M-Series and T-Series Climate Changer air handlers uses indirect heat exchangers and is designed for recirculating or 100 percent outside air applications. Only top-quality components are used in the cabinet, heat exchanger and burner. Top-quality components means extended equipment life, even in make-up air applications. Trane gas heat modules have considerable option flexibility, which is to be expected in applied air handlers. This flexibility allows customization for a specific application. The M-Series and T-Series Climate Changer air handlers are customized, cataloged air handlers with numerous options. The gas heat option is a predesigned, highly engineered option available in near standard ship cycles American Standard Inc. All rights reserved CLCH-PRB010-EN

3 Contents Features and Benefits... 4 Gas Heat Features... 4 Heat Exchanger Features... 5 Burner and Gas Train Features... 5 Extra Cost Options... 6 Application Considerations...8 Control System Considerations... 9 Constant Volume Units... 9 Variable-Air-Volume... 9 Shipping Considerations Installation Considerations...12 Field Supplied Items Starting the Gas Heat Module Storage Requirements Guide Specifications Heat Exchanger Burner Assembly Combustion Assembly Gas Train Controls Submittal Data Heat Exchanger Burner Assembly Flame Management Gas Train Controls Control Panel...17 Product Options...17 CLCH-PRB010-EN 3

4 Features and Benefits Gas Heat Features Available in unit sizes 6 to 120. Available 200 to 2500 MBh output, 2 to 8 MBh selections per unit size. Gas heat sections are available in the blow-through position, last in airstream, only. Gas heat sections feature double-wall construction. Gas train vestibules are provided with an access door. Gas train components are housed in an internal to unit or external piping cabinet if necessary. Gas train available on left or right side. The preferred location typically is the drive side of the unit. Combustion air inlet. Standard bolt up and roof curb interface. Horizontal (Figure 2) or vertical down (Figure 3) discharge available. Natural gas or propane burners are available. Standard M-Series and T-Series air handler sections are UL listed. Gas heat sections are UL listed, certifying that units have passed both UL Standard 795 and Canadian standard CGA ; the air handler unit as a whole is UL listed. All units are run tested and adjusted before leaving the factory. Figure 1. Gas heat exchanger module Figure 2. Horizontal air discharge Max.Temp See Page 8 Figure 3. Vertical air discharge Air Flow Min. -40 F Min. -40 F Max. Temp See Page 8 Air Flow 4 CLCH-PRB010-EN

5 Features and Benefits Heat Exchanger Features Drum-and-tube heat exchangers are made of 14-gauge, 409 stainless steel on both primary and secondary surfaces. This provides long service life especially in make up air applications during partial load, where the heat exchanger may be condensing. Sight glass is provided in the burner vestibule for viewing the flame condition (except on the 200 MBh heat exchanger where the sight glass is on the opposite side of unit). Heat exchangers are provided with a gasketed cleanout panel. Condensate drains and valves provided on all heat exchangers. Figure 4. Gas Heat Exchanger Burner and Gas Train Features Full-modulation burners: 3:1 turndown ratio (standard offering) available on 200-2,000 MBh output, forced draft burners 10:1 turndown ratio (optional offering) available on 200-2,000 MBh output, forced draft burners 20:1 turndown ratio (optional offering) available on 1,250-2,000 MBh output forced draft burners Power burner with forced draft centrifugal fan and direct drive motor. Induced draft fans mounted and wired (for MBh sizes 1,250, 1,500, 1,750, 2000 and 2,500. Control power transformer provided standard on 1,250 MBh and larger burners. Honeywell electronic flame relay with UV flame sensor, purge cycle and low fire start interlock. Intermittent spark ignition with ignition transformer pre-wired. Safeties provided by burner manufacturer; built into the burner controls. Main and pilot gas pressure regulators. Main regulator is included as a part of the gas solenoid safety shutoff valve. Maximum pressure is 14 inches wc (0.5 psig). Optional high gas pressure regulators are available. Main and redundant solenoid safety shutoff valves. Two manual shutoff cocks. Pilot manual and solenoid shutoff valves. Gas train has unions for ease of service. Combustion airflow switch mounted and wired. Main airflow switch mounted and wired. High temperature cutout. Pre-wired control panel, including system circuit breaker, low fire start relay and numbered terminal strip. Gas train built in accordance with Underwriter s Lab (UL) and Factory Mutual (FM) insurance ratings as standard. Optional Industrial Risk Insurers (IRI) rated gas train is available. CLCH-PRB010-EN 5

6 Features and Benefits Gas pressure requirements: 7 to 14 inches wc (0.25 to 0.5 psig). Note that a minimum of 9 inches wc (0.32 psig) is required for MBh heaters with 10:1 turndown capability. Higher pressures require an optional high gas pressure regulator. Lower pressures may require an oversized gas train. On T-Series Climate Changer air handlers, a stainless steel flue stack is included for field mounting. M-Series Climate Changer air handlers require a field-provided flue stack. High and low gas pressure switches. Gas train controls: 120-volt power or line voltage if control transformer is supplied Dry contact on/off and 0 to 10 Vdc control signal required Terminal blocks for all field control and power wiring terminations Propane configuration is available. Factory Testing All units are run tested and logged before leaving factory. Extra Cost Options MBh: Burners with turndown ratios of 10:1 (required for 100 percent outside air or VAV applications) MBh: Burners with turndown ratio of 20:1 for extra control modulation. High-pressure (greater than 14 inches wc [0.5 psig]) gas regulators. Control power transformer mounted and wired. Reduces line voltage to 120-volt power for gas train. Note the control power transformer is standard on 1,250 MBh and larger burner sizes. Note that if the transformer is not ordered, 120-volt, 60 Hz, singlephase power will need to be supplied to the gas train. Motorized gas valve with proof of closure switches on automatic gas valves (required by some local codes). Gas train built in accordance with Industrial Risk Insurers (IRI). Honeywell digital readout for flame relay: a very effective diagnostic tool. Figure 5. Complete burner and gas train assembly Figure 6. Another view of burner and gas train assembly 6 CLCH-PRB010-EN

7 Features and Benefits Table 1. Gas heat benefits Benefit Description Compete Package Complete central station air handler with chilled water, filtration and gas heating in one package Quality Using industry proven components, Trane offers a superior quality, highly functional heating section that complements the attributes of our M-Series and T-Series Climate Changer air handlers. Industrial quality forced draft burners from industry leaders in combustion technology form the heart of the system. These, combined with heavy-duty heat exchangers of 14-gauge, 409 stainless steel (primary and secondary surfaces), complete a heating system worthy of being called an applied product. Safety Integral to the gas heating section is a state-of-the-art flame management system. Tried and proven flame relays from Honeywell employ an ultraviolet flame scanner typically used on larger output systems Cleanliness Gas trains and piping are inside the burner vestibule, keeping the unit appearance neat and clean. Gas trains are constructed in accordance with UL and FM guidelines. Agency Listings M-Series and T-Series gas heating sections bear the UL label for Commercial and Industrial Gas Heating Equipment (ANSI/UL Standard 749) and ETL Canada label for Industrial Gas Fired Package Units (CGA Standard ). Flexibility Various heat outputs and unit size combinations to allow for closely matching heater size to jobsite requirements. Various control options to tailor the heating system to design requirements. Checkout All units are fully run tested before shipment to ensure proper operation and burner setup reducing start up costs. CLCH-PRB010-EN 7

8 Application Considerations Applying gas heat in air-handling systems is fairly straightforward; however, as with any applied product, there are application guidelines that should be reviewed before making final selections: Apply indirect fired gas heating sections in the blow-thru configuration only with the gas heating section as the last component in the airstream. In this configuration, the gas heat section is under positive static pressure to ensure that combustion products will not enter the airstream. Note: A special end-of-unit shipping split must be ordered with all T-Series units. The discharge air temperature must be controlled to modulate when the airflow is modulated. When reducing airflow, the control system should not allow the temperature rise through the gas heat section to exceed the nominal at full airflow. Standard discharges include both front horizontal and vertical- -- down. Minimum entering air temperature is -40ºF. Maximum discharge air temperature is limited by the downstream components. For example, the maximum temperature for a plenum is 180 degrees F. For any other downstream components, consult the manufacturer's temperature guidelines. Note this does not imply that the gas section can deliver a 180 degree F temperature rise. The maximum temperature rise across the heat exchanger is 101 degrees F. See the selection table for the allowable temperature rise for the specific unit size and burner capacity. Figure 7. Horizontal air discharge Max.Temp See Page 8 Gas heating sections are constructed with a vestibule to house the burner and gas train components. Smaller capacity heating sections are housed entirely within the footprint of the standard casing. Larger capacity sections use an external vestibule. Refer to the quick selects (CLCH-SLB004-EN and CLCH-SLB005-EN) and submittal drawings for details. Air pressure drop through the gas heat section needs to be determined. Heat exchangers and air block-off baffles in the gas heating section have been sized to provide a specific air velocity over the heat exchanger at design CFM. This gives a 0.5 inches wg pressure drop at design airflow. This pressure drop is applicable to all unit sizes. The outlet opening, if less than full size, has a small exit loss. Use CLCH blow-thru fan curves when calculating fan hp and rpm. Most comfort heating applications for full modulating burners require only a 3:1 turndown ratio. Turndown refers to the burner s modulation range. A 3:1 turndown ratio indicates the burner can operate at a capacity as low as 33 percent or one-third Air Flow Min. -40 F of its rated high fire output. Likewise, a 10:1 turndown ratio indicates the burner can operate at a capacity as low as 10 percent or one-tenth of its rated high fire output. 10:1 turndown is typically used for 100 percent makeup air applications. Similarly, a 20:1 turndown ratio indicates the burner can operate at a capacity as low as 5% or one-twentieth. 20:1 is typically used in an industrial process application where much tighter control is required. A condensate drain with shutoff valve is provided on the heat exchanger. For M-Series Climate Changer air handlers, the valve is located in the piping vestibule. For T-Series Climate Changer air handlers, the valve is located on the opposite side of the piping vestibule and accessed through the access door. Provide for a cool-down cycle in the control system. Allow the air handler fan to run for a minimum of 3 minutes after gas heat shut down to cool the heat exchanger to dissipate any residual heat. On high altitude applications, derate the heating capacity (MBh) by 4 percent for every 1,000 feet over 2,000 feet. 8 CLCH-PRB010-EN

9 Application Considerations Exhaust Flue T-Series Climate Changer air handlers are provided with a short exhaust gas flue stack. It is attached to the unit during installation. A field provided exhaust flue stack is not required. M-Series gas heat modules require a field-engineered and field-installed flue stack. Local codes and practices vary throughout the country. The engineer should size the flue based on MBh output, horizontal and vertical run lengths, type of flue material, NFPA 54 Fuel Gas Code, and local codes. The flue should be designed for 800 degrees F (430 degrees C). If horizontal runs over 20 feet or other staticincreasing transitions are necessary, a flue booster fan will be required. Use best practice to ensure adequate draft is ensured for exhausting flue gases. An induced draft fan or exhauster may be required to overcome friction losses from long horizontal runs or flue restrictions. Conversely, a barometric damper may be required if exhausting into a tall chimney which produces excessive draft. The flue should be installed in accordance with NFAPA 54 (ANSI Z223.1) National Fuel Gas Code, NFPA 211 Standard for Chimneys, Fireplaces, Vents and Solid Fuel- Burning Appliances and any other relevant local building codes or regulations. Vent material must have resistance to corrosion and heat equal or greater than 304 stainless steel. Control System Considerations Constant Volume Units Air handler controller requirements for gas heat section operation in constant volume units: One (1) binary output signal is needed for on - off control of the gas burner. A continuous 10 vdc signal to ramp unit to full fire position after start up. This is needed for on - off gas heat control only. One (1) analog output signal for 0-10 vdc to modulate the gas burner with 10 vdc being full fire. An alternate to the 0-10 vdc signal is to use an analog output for 4-20 ma. Note this requires an optional signal converter in the gas heat module. This is needed for modulating gas heat control. Trane supplied air handler controllers have the capability to operate the gas heat section. Note that wiring between the controller and the gas heat section would be done in the field. Consult with the local Trane sales office for design assistance. Minimum Air Flow Requirements - Constant Volume Units Table 2 shows the minimum air flow requirements for a constant volume air handler. The burner firing rate does not have to be reduced if these minimum CFM values are maintained. Table 2. Minimum cfm for constant volume units Unit size Minimum CFM , , , , , , , , ,843 Variable-Air-Volume Air handler controller requirements for gas heat section operation in variable-air-volume units: One (1) binary output signal is needed for on - off control of the gas burner. Two (2) analog inputs for temperature sensors are required. A discharge temperature sensor and a supply air temperature sensor are required to monitor temperature rise across the gas heater. One (1) analog output signal for 0-10 vdc to modulate the gas burner with 10 vdc being full fire. An alternate to the 0-10 vdc signal is to use an analog output for 4-20 ma. Note this requires an optional signal converter in the gas heat module. Trane supplied air handler controllers have the capability to operate the gas heat section. Note that wiring between the controller and the gas heat section would be done in the field. Consult with the local Trane sales office for design assistance. CLCH-PRB010-EN 9

10 Application Considerations Monitor Air Temperature Rise - Variable Air Volume Units On variable air volume systems, as the air handler's air volume decreases in response to zone load, the gas burner firing rate must modulate also so as not to exceed the nameplate temperature rise rating. To do this requires a temperature sensor on the entering and leaving air side of the gas heat section to monitor the temperature rise across the heat exchanger. The temperature rise set point should not exceed the nameplate rating. Minimum Air Flow Requirements - Variable Air Volume Units Variable air volume units have minimum CFM limits for proper operation of the gas heat. Refer to the table below for minimum air handler CFM limits. At these CFM limits, the firing rate of the gas heater must be reduced as described previously. The temperature rise across the heat exchanger must not exceed the nameplate temperature rise rating. Table 3. Minimum cfm for variableair-volume units Unit Size Minimum CFM Note: VAV applications require reduced fire rates. Do not exceed nameplate temperature rise rating. 10 CLCH-PRB010-EN

11 Shipping Considerations The gas heating section ships with the burner and heat exchanger installed. The external piping vestibule, if required, ships attached to the heating section. The exhaust gas flue on T-Series gas heat sections ships inside the burner vestibule and must be field installed. The gas heat section ships separately and must be field installed to the air handler at the jobsite. The heating sections for T-Series Climate Changers can accept roof curb or pier mounting. CLCH-PRB010-EN 11

12 Installation Considerations Field-Supplied Items Controls The gas heat control system requires a binary input signal for on/off control. The control system also requires a 0 to 10 Vdc analog signal for modulation where 10 Vdc is full heat. Avoid using a zone sensor to control leaving air temperature from the gas heat section. This could cause excessive discharge air temperature due to over-firing of the burner. A discharge air sensor is the preferred method of control. For VAV applications when airflow is reduced, the control system should not allow the temperature rise through the gas heat section to exceed the nominal at full airflow. The discharge air temperature must be controlled to modulate when the airflow is modulated. Gas Supply A supply of natural gas must be connected to the gas train. See Table 4 for gas connection sizes. Required gas pressure to the gas train is 7 to 14 inches wc (0.25 to 0.5 psig) for units through 2000 MBh. Note that a minimum of 9 inches wc (0.32 psig) is required for MBh heaters with 10:1 turndown capability. For all size units, do not exceed 14 inches wc (0.5 psig) inlet gas pressure. Gas pressure and volume must be maintained and stable at high fire. Higher inlet gas pressure requires a field-provided high gas pressure regulator. Lower gas pressure will require an oversized gas train contact Lexington Marketing. Note: A propane configuration is also available. Exhaust Flue T-Series Climate Changer air handlers are provided with a short exhaust gas flue stack. It is attached to the unit during installation. A field provided exhaust flue stack is not required. M-Series Climate Changer air handlers require a field provided exhaust flue stack. The flue stack should be selected for a maximum flue gas temperature of 800 degrees F (430 degrees C). Type B flue stacks are not recommended as they are only suitable for a maximum flue temperature of 450 degrees F (230 degrees C). Table 4. Gas connection sizes Gas Output (MBh) ,000 1,250 1,750 2,000, 2,500 Connection Size (inches) 1 1Z\v 1Z\x 2 Table 5. Power supply requirements Gas Output (MBh) 200 1, ,000 with control 1,250 2,500 transformer Amperage (Amps) 11 (single-phase) 11 (three-phase) 20 (three-phase) Use best practice to ensure adequate draft is ensured for exhausting flue gases. An induced draft fan or exhauster may be required to overcome friction losses from long horizontal runs or flue restrictions. Conversely, a barometric damper may be required if exhausting into a tall chimney which produces excessive draft. The flue should be installed in accordance with NFAPA 54 (ANSI Z223.1) National Fuel Gas Code, NFPA 211 Standard for Chimneys, Fireplaces, Vents and Solid Fuel- Burning Appliances and any other relevant local building codes or regulations. Vent material must have resistance to corrosion and heat equal or greater than 304 stainless steel. Wiring All power and control wiring for the gas heat section must be field provided. All power and control wiring for any modules downstream of the gas heat section must be field provided. Power Gas heaters with 200 to 1,000 MBh output require a separate 120V power source to operate the control panel, gas valves, actuators, etc. If the optional control power transformer is ordered, line voltage may be supplied to the control panel. Be sure to order the same voltage as the supply fan. 12 CLCH-PRB010-EN

13 Installation Considerations Gas heaters with 1,250 to 2,500 MBh output require three-phase power for the forced draft exhaust fans. Therefore, these sizes are supplied with a standard control power transformer to power the control panel, gas valves, actuators, etc. Be sure to order the same voltage as the supply fan. A separate 120V is not required. Refer to Table 5for the power supply and amperage requirements. Starting the Gas Heat Module Even though the gas heat section has been run tested in the factory, minor adjustments may be needed at startup. These are usually limited to adjustment of pilot and main burner gas pressure regulators. Detailed start-up procedures are discussed in the Installation and Maintenance manual. Storage Requirements Follow the recommendations in CLCH-SVX03B-EN or CLCH-IM-16A installation and maintenance manuals provided with M-Series and T-Series Climate Changer air handlers. Gas Heat Quick Selects Refer to the M-Series and T-Series Climate Changer gas heat quick selects (CLCH-SLB004-EN and CLCH- SLB005-EN, respectively) to find the combination of unit size and MBh output (or temperature rise) to suit design requirements. Gas heat section piping vestibules, configurations, lengths and weights are also given. CLCH-PRB010-EN 13

14 Guide Specifications General The gas heat section shall be natural gas, indirect fired and shall be completely factory assembled, wired and tested to form an integral part of the unit. It shall bear an ETL or UL label for Commercial and Industrial Gas Heating Equipment (ANSI / UL Standard 795) and for Industrial Gas Fired Packaged Units (CGA Standard ). Heat Exchanger The heat exchanger shall be a twoor four-pass design. The primary surface shall be one or two passes, constructed of welded 409 stainless steel. The secondary heat exchanger shall consist of multiple tubes of 409 stainless steel in a single- or twopass arrangement. Tubes shall be fitted with multi-plane metal turbulators, and both primary and secondary surfaces shall be minimum 14-gauge thickness. Lighter metal gauges will not be acceptable. The heat exchanger shall be fitted with a cleanout plate to facilitate cleaning and inspection of tubes and turbulators as well as a condensate drain connection that is piped to an accessible shutoff valve. Burner Assembly The burner shall be forced draft, industrial type capable of efficient firing over its operating range without producing excessive CO, CO2 or NOX. It shall be fitted with a combustion air damper assembly for control of fuel-air ratio through its modulating range. The burner uses a modulating gas valve design, not a step-controlled gas valve, to provide precise capacity control. Two-speed fan motors will not be acceptable for this application. The burner modulation range (i.e., turndown) shall be as specified on the equipment schedule. The combustion air damper and modulating gas valve shall be linked either internally or through a control linkage that is factory preset. The burner shall have a low fire start interlock and shall be manufactured by Maxon, Power Flame or Eclipse only. Combustion Assembly The combustion blower shall be centrifugal type, direct drive, capable of delivering the proper amount of combustion air to the burner nozzle. The blower motor shall have an internal thermal overload protection, and an air proving switch shall be mounted on the scroll, interlocking burner operation with the gas train controls to prevent burner operation when the combustion air fan is shut down. On unit sizes 1,250 MBh and larger, an induced draft fan shall be employed for positive venting of combustion products. An induced draft (ID) fan shall be centrifugal type, capable of withstanding high temperatures associated with flue gas. The unit shall be equipped with a stainless steel flue stack that rises above the roof level. Gas Train The gas train shall meet FM approval and shall include the following: A modulating gas valve Automatic gas valve with gas pressure regulator Redundant automatic gas valve (above 400 MBh) Main gas shutoff valve with pressure tap and second ball shutoff cock Pilot solenoid Pilot gas pressure regulator Pilot solenoid valve Controls The gas safety controls shall include the following: Electronic flame relay with UV flame sensor High limit control Combustion air flow Primary air flow interlocks The unit shall be programmed to start in low-fire mode, and the flame relay shall be Honeywell Model 7895A or equal and shall be equipped with annunciation lights indicating pilot on, safeties satisfied, combustion airflow and flame failure. The unit shall have a purge cycle that provides a minimum of four air changes of the heat exchanger interior. The purge time shall not exceed four minutes. 14 CLCH-PRB010-EN

15 Guide Specifications The heating system shall have an intermittent spark ignition to establish the pilot flame. The ignition transformer shall be factory wired into the control system. All control components shall be factory pre-wired to numbered terminal strips in the burner control panel. All wiring shall be run in conduit. The control circuit shall have a circuit breaker as a disconnecting device and for overcurrent protection. Field connections shall require only main power (120 Vac or line voltage if supplied with a control power transformer), a heat start contact closure and a modulating 0 to 10 Vdc (4 to 20 Ma optional) signal. Avoid using a zone sensor to control leaving air temperature from the gas heat section. This could cause excessive discharge air temperature due to over-firing of the burner. A discharge air sensor is the preferred method of control. For VAV applications when airflow is reduced, the control system should not allow the temperature rise through the gas heat section to exceed the nominal at full airflow. The discharge air temperature must be controlled to modulate when the airflow is modulated. CLCH-PRB010-EN 15

16 Submittal Data Note: Indirect Fired Gas Heating Section for M-Series and T-Series Climate Changer Air Handlers General The indirect gas heat section consists of the heat exchanger, power burner, gas train, flame management controls and control panel. The section is completely assembled, pre-wired and flame tested before shipment and bears the UL label for Commercial and Industrial Gas Heating Equipment (ANSI/UL Standard 749) and Industrial Gas Fired Package Units (CGA Standard ). The gas heat section features double-wall construction with fiberglass insulation. All burner and control components are housed completely within the section in the burner vestibule. The vestibule wall is double-wall construction on the heat exchanger side, and a combustion air intake louver is provided to allow combustion air into the vestibule. A full-sized hinged vestibule access door is standard. Heat Exchanger The drum-and-tube heat exchanger is constructed of 14-gauge, 409 stainless steel on both the primary and the secondary surfaces. The drum and tubes are fully welded. 200 to 1,000 MBh is a two-pass design and 1,250 to 2,500 MBh is a four-pass design. The heat exchanger is fitted with a cleanout door on the rear flue box to facilitate cleaning and tube inspection. It is also fitted with a condensate drain, which terminates to an accessible shutoff valve. Burner Assembly The burner is a commercial/ industrial forced draft, full modulating type designed to fire natural gas or propane gas. A stainless steel multi-port diffuser and flame retention firing head combine to produce full-range, stable performance. The burner is equipped with an integrally mounted direct drive combustion blower, internal thermal overload protection and a combustion air damper, which controls the fuel-air ratio throughout the modulating range for efficient turndown. The combustion air damper and modulating gas valve are linked either internally or through a factory preset control linkage. The standard turndown is 3:1. Flame Management The heating section uses a Honeywell 7800 series flame relay to provide the flame safeguard programming. The flame relay has annunciation lights, indicating pilot on, safeties satisfied, combustion airflow and flame failure. The flame relay has a pre-purge cycle, providing for a minimum of four air changes in the heat exchanger before ignition. An ultraviolet (UV) flame detector senses the presence of a flame. The flame relay uses a spark-ignited gas pilot system to establish an intermittent pilot. The ignition transformer is mounted on the burner wall and provides a 6000-volt spark. Gas Train The standard gas train meets UL and FM requirements and is designed for 7 to 14 inches wc (0.25 to 0.5 psig) incoming gas pressure. Its components include the following: Main gas safety shutoff valve Redundant safety shutoff valve Gas pressure regulator Manual gas shutoff valve with pressure taps (primary) Manual gas shutoff valve (secondary) Modulating gas valve Gas pressure taps for servicing and adjusting burner Orifice plate High gas pressure safety switch Low gas pressure safety switch Pilot gas pressure regulator Pilot gas solenoid Pilot gas manual shutoff valve Controls Operating and safety controls include the following: Modulating actuator to drive the gas control valve and the combustion air damper Conditioned airflow switch High air temperature limit switch Low fire start relay Combustion air flow switch 16 CLCH-PRB010-EN

17 Submittal Data Control Panel The system control panel is mounted in the burner vestibule. It houses the incoming power terminal block, circuit breaker, low fire start relay and numbered terminal strip. A terminal is available for wiring an external alarm relay. All wiring is run in flex conduit and is numbered for ease of service. Others must provide the temperature control system. Product Options Full-modulation burners: 3:1 turndown ratio (standard offering) available on 200-2,000 MBh output, forced draft burners 10:1 turndown ratio (optional offering) available on 200-2,000 MBh output, forced draft burners 20:1 turndown ratio (optional offering) available on 1,250-2,000 MBh output forced draft burnerscontrol power transformer High gas pressure regulator: required when inlet gas pressure exceeds 14 inches wg (0.5 psig) Digital readout for flame relay: a plug-in module for the flame relay featuring two-line digital English language readout of over 50 parameters Industrial Risk Insurers (IRI) approved gas train CLCH-PRB010-EN 17

18 Trane A business of American Standard Companies For more information, contact your local Trane office or us at comfort@trane.com Literature Order Number CLCH-PRB010-EN Date March 2004 Supersedes CLCH-PRB010-EN (November 2000) Stocking Location Inland Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation Industrial Space Heating Direct Gas-Fired Heating Greenheat 00% Outdoor Air Greenheat 50/50 Recirculation 80/0 Recirculation March 008 Product Overview Industrial Space Heating Greenheck s space heating

More information

TGIF-1. Indirect Fired Heating Systems. Technical Guide for: IF Indoor Installations. IFW Outdoor Installations. Applied Air. Keeps You.

TGIF-1. Indirect Fired Heating Systems. Technical Guide for: IF Indoor Installations. IFW Outdoor Installations. Applied Air. Keeps You. TGIF- Indirect Fired Heating Systems Technical Guide for: IF Indoor Installations IFW Outdoor Installations Applied Air Keeps You Warm Indirect Fired Heating Systems Technical Guide In the business of

More information

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

INDIRECT GAS-FIRED AIR HEATER

INDIRECT GAS-FIRED AIR HEATER INDIRECT GAS-FIRED AIR EATER DG() SERIES INDOOR/OUTDOOR INSTALLATION MANUFACTURED BY TABLE OF CONTENTS Description... Applications... Selection criteria... Installation guidelines... Selection table...7

More information

Equipment Specifications

Equipment Specifications Equipment Specifications GAS/OIL HEATING ONLY INDIRECT-FIRED AIR HANDLER GUIDE SPECIFICATION PART 1 GENERAL [Gas][Oil][Gas/Oil Combo]-Fired Please note: Brackets indicate required choices to be made in

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh

T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh PRODUCT SPECIFICATIONS GAS UNIT HEATERS / DUCT FURNACES TU T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ Bulletin No. 20402 November 207 Supersedes November 206

More information

ELITE SERIES Lo-Boy. AFUE - 83% Heating Input - 101,000 to 151,000 Btuh Nominal Add-on Cooling to 5 Ton. OIL FURNACES El0183b

ELITE SERIES Lo-Boy. AFUE - 83% Heating Input - 101,000 to 151,000 Btuh Nominal Add-on Cooling to 5 Ton. OIL FURNACES El0183b PRODUCT SPECIFICATIONS OIL FURNACES El083b ELITE SERIES Lo-Boy Bulletin No. 20629 February 209 Supersedes July 202 MODEL NUMBER IDENTIFICATION el O 83 bf 0/4 p 60 AFUE - 83% Heating Input - 0,000 to 5,000

More information

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired Form No. 8700 Bryan Flexible Water Tube TM Triple-Flex Series Ultra-High Efficiency Condensing Hot Water Boilers 3,000,000 BTUH Natural Gas Fired Minimum 90% Thermal Efficiency at 160 F Return with 20

More information

Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace

Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace XL 95 TUH2B060A936VA, TUH2B080A92VA, TUH2C100A98VA, TUH2D1A960VA, TDH2B060A936VA, TDH2B080A92VA, TDH2C100A98VA, TDH2D1A960VA

More information

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA

More information

Gas Heat Module/ Section

Gas Heat Module/ Section Installation Operation Maintenance Gas Heat Module/ Section for M-Series and T-Series Climate Changer Air Handlers March 2004 CLCH-SVX04B-EN General Information Use this manual to install, startup, operate,

More information

Installation, Operation and Maintenance

Installation, Operation and Maintenance Installation, Operation and Maintenance Gas Heat Sections for Performance Climate Changer Air Handlers Sizes 6-120 for Indoor and Outdoor Units SAFETY Only qualified personnel should install and service

More information

ECLIPSE INFORMATION GUIDE

ECLIPSE INFORMATION GUIDE ECLIPSE INFORMATION GUIDE JUNIOR INDUSTRIAL BURNERS Models 0 & 6 JIB Info 80 0/9 Easy to install and operate. Rugged construction for long life in industrial environments. Protection against overheating

More information

STR-Series Indirect-Fired Air Turnover Units

STR-Series Indirect-Fired Air Turnover Units STR-Series Indirect-Fired Air Turnover Units Equipment Specifi cations 1.800.589.3691 www.weather-rite.com GAS/OIL HEATING ONLY INDIRECT-FIRED AIR TURNOVER UNIT GUIDE SPECIFICATIONS PART 1 GENERAL [Gas][Oil][Gas/Oil

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000 s AV(W)0500 AV(W) The domestic hot water boiler shall be a Camus ADVANTUS TM model having a recovery capacity of gph (lph) at 100ºF (56ºC) for DHW The domestic hot water boiler shall be design certified

More information

RGE 13 A T - 1 A

RGE 13 A T - 1 A PRODUCT SPECIFICATIONS PACKAGED GAS / ELECTRIC 3GEP / RGE3 Rooftop Units 60HZ Bulletin No. 2063 December 202 Supersedes October 202 MODEL NUMBER IDENTIFICATION -PHASE MODELS SEER - 3.00 (3GEP Shown) AFUE

More information

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000 s AV(W)0500 AV(W) The domestic hot water boiler shall be a Camus ADVANTUS TM model having a recovery capacity of gph (lph) at 100ºF (56ºC) for DHW The domestic hot water boiler shall be design certified

More information

Submittal. Downflow Two Stage Condensing Gas Fired Furnace 100,000 BTUH S9V2C100D4-SUB-1-EN. March 2016 S9V2C100D4PSAA TAG:

Submittal. Downflow Two Stage Condensing Gas Fired Furnace 100,000 BTUH S9V2C100D4-SUB-1-EN. March 2016 S9V2C100D4PSAA TAG: Submittal Downflow Two Stage Condensing Gas Fired Furnace 100,000 BTUH Downflow Only S9V2C100D4PSAA Note: Graphics in this document are for representation only. Actual model may differ in appearance. SAFETY

More information

Product Data. 58EFA Horizontal Gas Furnace. 50, ,000 Btuh Input

Product Data. 58EFA Horizontal Gas Furnace. 50, ,000 Btuh Input Product Data 58EFA Horizontal Gas Furnace 50,000 125,000 Btuh Input GAS SUPPLY MANUAL SHUTOFF VALVE SEDIMENT TRAP UNION Carrier presents the 58EFA, a dedicated horizontal gas furnace that excels in the

More information

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 80,000 BTUH S9V2B080U3-SUB-1-EN. February 2016 S9V2B080U3PSAA TAG:

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 80,000 BTUH S9V2B080U3-SUB-1-EN. February 2016 S9V2B080U3PSAA TAG: Submittal Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 80,000 BTUH Upflow, Convertible to Horizontal Right or Horizontal Left S9V2B080U3PSAA Note: Graphics in this document are

More information

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 80,000 BTUH S9V2B080U4-SUB-1-EN. February 2016 S9V2B080U4PSAA TAG:

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 80,000 BTUH S9V2B080U4-SUB-1-EN. February 2016 S9V2B080U4PSAA TAG: Submittal Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 80,000 BTUH Upflow, Convertible to Horizontal Right or Horizontal Left S9V2B080U4PSAA Note: Graphics in this document are

More information

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 40,000 BTUH S9V2B040U3-SUB-1-EN. February 2016 S9V2B040U3PSAA TAG:

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 40,000 BTUH S9V2B040U3-SUB-1-EN. February 2016 S9V2B040U3PSAA TAG: Submittal Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 40,000 BTUH Upflow, Convertible to Horizontal Right or Horizontal Left S9V2B040U3PSAA Note: Graphics in this document are

More information

Gas-Fired Indoor and Outdoor Duct Furnaces

Gas-Fired Indoor and Outdoor Duct Furnaces July, 2008 Gas-Fired Indoor and Outdoor Duct Furnaces INDOOR GRAVITY VENTED DFG, DBG, DCG INDOOR SEPARATED COMBUSTION DFS, DBS, DCS OUTDOOR GRAVITY AND POWER EXHAUSTED H Series table of contents A complete

More information

INDOOR/ OUTDOOR SPLIT SYSTEM HVAC CATALOG

INDOOR/ OUTDOOR SPLIT SYSTEM HVAC CATALOG INDOOR/ OUTDOOR SPLIT SYSTEM HVAC CATALOG COMMERCIAL/INDUSTRIAL AIR HANDLER AND CONDENSING UNIT AIR HANDLER CAPACITIES 563-7,593 CFM Air 20-400 MBH Heating (Gas/LP) 10-120 kw Heating (Electric) 5-20 Tons

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

DAVE LENNOX SIGNATURE COLLECTION Lo-Boy - Variable Speed Blower

DAVE LENNOX SIGNATURE COLLECTION Lo-Boy - Variable Speed Blower PRODUCT SPECIFICATIONS OIL FURNACES sl085bv DAVE LENNOX SIGNATURE COLLECTION Lo-Boy - Variable Speed Blower Bulletin No. 0677 August 05 Supersedes September 04 AFUE - Up to 87% Heating Input - 79,000 to

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS AutoZone R Model Single Package Rooftop Gas Heating/Electric Cooling Unit Size 07 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION

More information

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat SINGLE PACKAGE ROOFTOP, GAS HEATING/ELECTRIC COOLING UNIT WITH PURON R (R-410A) REFRIGERANT ONE STAGE COOLING CAPACITY CONTROL: SIZES 08-12 TWO STAGE COOLING CAPACITY CONTROL: SIZES 08, 12 & 14 Submittal

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with NOVATIONt Coil Sizes 08, 12, 14 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 235533 - FUEL-FIRED UNIT HEATERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas fired unit heaters. B. Oil fired unit heaters. C. Tubular infrared heaters. 1.2 RELATED REQUIREMENTS A. Section 230513

More information

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating Section 15700 (CSI 23 74 33) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating Note: Optional items and/or items requiring a choice, will be shown between brackets and/or parentheses

More information

Warm. IFR Indirect Fired Gas Heating Systems. Applied Air. Keeps You

Warm. IFR Indirect Fired Gas Heating Systems. Applied Air. Keeps You TGIFR IFR Indirect Fired Gas Heating Systems Technical Guide for: Outdoor Rooftop Mounted Units To 46,000 CFM And 4,000 MBH Output Applied Air Keeps You Warm Indirect Fired Heating Systems Technical Guide

More information

GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications

GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications ENGINEERING DATA Typical Applications G20RE and G20RXE WhisperHeat DOWN-FLO GAS FURNACES *78.0% A.F.U.E. 50,000 to 150,000 Btuh Input Add-On Cooling 2 thru 5 Nominal Tons *Isolated Combustion System rating

More information

8+* Bulletin No November 1997

8+* Bulletin No November 1997 ENGINEERING DATA VALUE 80Z UP-FLOW/HORIZONTAL GAS FURNACES *80.0 to 80.5% A.F.U.E. 45,000 to 20,000 Btuh (3.2 to 32.2 kw) Input Heating Capacity -/2 thru 6 Tons (3.5 thru 2. kw) Nominal Add-on Cooling

More information

ADF/ADFH 300 and 500

ADF/ADFH 300 and 500 MODEL ADF/ADFH DIRECT-FIRED SYSTEMS TECHNICAL DATA Four Sizes - 300, 500, 700, 1200 Horizontal Configuration with Full Curb Cap Base Horizontal or Vertical (down) Discharge Indoor/Outdoor Installation

More information

Downflow/Horizontal Condensing, Gas-Fired Furnace XB 90 PUB. NO

Downflow/Horizontal Condensing, Gas-Fired Furnace XB 90 PUB. NO Downflow/Horizontal Condensing, Gas-Fired Furnace XB 90 TDC1B040A9241A, TDC1B060A9361A TDC1B080A9421A, TDC1C100A9481A TDC1D120A9601A Single-Stage Fan Assisted Combustion System PUB. NO. 22-1670-10 General

More information

Upflow/Horizontal Condensing, Gas-Fired Furnace XB 90 PUB. NO

Upflow/Horizontal Condensing, Gas-Fired Furnace XB 90 PUB. NO Upflow/Horizontal Condensing, Gas-Fired Furnace XB 90 TUC1B00A921A, TUC1B060A9361A TUC1B080A921A, TUC1C100A981A TUC1D100A9601A, TUC1D1A9601A Single-Stage Fan Assisted Combustion System PUB. NO. 22-1669-15

More information

13 GEP A L P - 1 A

13 GEP A L P - 1 A PRODUCT SPECIFICATIONS PACKAGED GAS / ELECTRIC 3GEP MERIT SERIES Residential - R-40A Bulletin No. 20602 December 202 Supersedes October 202 SEER - 3.00 AFUE - 80% 2 to 5 Tons Cooling Capacity - 22,800

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

MODEL ADF/ADFH 300 and 500 INDOOR/OUTDOOR DIRECT-FIRED GAS HEATING/MAKEUP AIR SYSTEM FOR INDUSTRIAL & COMMERCIAL APPLICATIONS

MODEL ADF/ADFH 300 and 500 INDOOR/OUTDOOR DIRECT-FIRED GAS HEATING/MAKEUP AIR SYSTEM FOR INDUSTRIAL & COMMERCIAL APPLICATIONS MODEL ADF/ADFH 300 and 500 FOR INDUSTRIAL & COMMERCIAL APPLICATIONS Model ADF CSA 3.7 ANSI Z83.4 Non-Recirculating Industrial Air Heaters WARNING: GAS-FIRED APPLIANCES ARE NOT DESIGNED FOR USE IN HAZARDOUS

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with Puronr (R---410A) Refrigerant Sizes: 17, 20, 24, 28, 30 Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E WATER HEATERS / BOILERS -E PRODUCT SPECIFICATIONS Gas-Fired Steam Boiler Bulletin No. 20653 September 202 Supersedes Bulletin No. 20263 AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh MODEL NUMBER

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

SUBMITTAL SCHEDULE & DATA

SUBMITTAL SCHEDULE & DATA SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Date: 10/31/2016 Location: Engineer: Submitted by: Jeff Musto Architect: Contractor: Model

More information

POWER VENTER. Model: PVE Series

POWER VENTER. Model: PVE Series POWER VENTER Model: PVE Series CONTENTS Typical Venting System Components... System Operation... Power Venter Sizing... Installation Safety Instructions... Installation of Power Venter... Connecting Power

More information

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS MVB, TYPE WH - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 3500.952C Effective: 06-25-15 Replaces: 12-22-09 DIVISION 23 34 36.29 COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES P R O D U C T S P E C I F I C AT I O N S W A T E R H E A T E R S / B O I L E R S CONSERVATOR Gas-Fired Steam Boiler Bulletin No. 20263 October 200 Supersedes September 2008 AFUE up to 82.7% Heating Input

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL INDIRECT GAS-FIRED DUCT FURNACE

INSTALLATION, OPERATION & MAINTENANCE MANUAL INDIRECT GAS-FIRED DUCT FURNACE INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR COMMERCIAL APPLICATIONS IN-KI INDOOR SERIES RT-NO ROOFTOP SERIES WWW.RENEWAIRE.COM IMPORTANT SAFETY INFORMATION WARNING WARNING Risk of fire or explosion!

More information

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh HEATERS / BOILERS GWB8-E Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 065 July 06 Supersedes September 05 AFUE up to 83.9% Heating Input 50,000 to 99,000 Btuh MODEL NUMBER IDENTIFICATION

More information

Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace

Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace XR 95 TUHB00A92C, TUHB060A936C, TUHB080A92C, TUHC080A960C, TUHC00A98C, TUHD00A960C, TUHDA960C, TDHB00A92C, TDHB065A92C,

More information

48TF GAS HEATING/ ELECTRIC COOLING UNITS

48TF GAS HEATING/ ELECTRIC COOLING UNITS 48TF-4SB 48TF004-014 GAS HEATING/ ELECTRIC COOLING UNITS PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS Copyright 2005 Carrier Corporation Syracuse, New York 13221 Form

More information

KIC Air Curtains. Technical Guide

KIC Air Curtains. Technical Guide TGKIC-3 KIC Air Curtains Technical Guide AIR PERFORMANCE AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. King certifies that the air curtains shown herein are licensed to bear the AMCA seal. The

More information

XV80i. Upflow/Horizontal 80% 2-Stage, Variable Speed Gas-Fired Furnace with Whole House Air Cleaner PUB. NO

XV80i. Upflow/Horizontal 80% 2-Stage, Variable Speed Gas-Fired Furnace with Whole House Air Cleaner PUB. NO Upflow/Horizontal 80% 2-Stage, Variable Speed Gas-Fired Furnace with Whole House Air Cleaner XV80i TUD2B060AFV32A, TUD2B080AFV32A, TUD2C080AFV42A, TUD2B100AFV32A, TUD2D120AFV52A 2009 Trane All Rights Reserved

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS HI DELTA, TYPE WH - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 3500.932A Effective: 04-01-17 Replaces: 10-31-16 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY A.

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ. Steady-State Efficiency - up to 81% Input - 30,000 to 75,000 Btuh

COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ. Steady-State Efficiency - up to 81% Input - 30,000 to 75,000 Btuh GAS UNIT HEATERS / DUCT FURNACES LF24 COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ PRODUCT SPECIFICATIONS Bulletin 2008 July 206 Supersedes October 20 Steady-State Efficiency - up to 8% Input

More information

FEATURES AND BENEFITS

FEATURES AND BENEFITS FEATURES AND BENEFITS Product Features and Benefits Full Product Line Offering Feature All models are 80% thermally efficient Blower performance up to 3.0 W.C. DX or chilled water section with factory

More information

Field Start-Up Sheet Direct Fired Gas Equipment

Field Start-Up Sheet Direct Fired Gas Equipment Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 2000.932C Effective: 04-01-14 Replaces: 07-15-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

Direct Gas-Fired Make-Up Air Models DG and DGX

Direct Gas-Fired Make-Up Air Models DG and DGX Direct Gas-Fired Make-Up Air Models DG and DGX Commercial, Industrial and Kitchen Applications 800-48,000 cfm 4 in. wg External Static Pressure Direct Gas-Fired Heating Optional Cooling - Packaged DX (2.5

More information

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh HEATERS / BOILERS GWB8-E PRODUCT SPECIFICATIONS Gas-Fired Hot Water Boiler Bulletin No. 065 September 0 Supersedes Bulletin No. 06 AFUE up to 83.9% Heating Input 50,000 to 99,000 Btuh MODEL NUMBER IDENTIFICATION

More information

SECTION WATER-TUBE BOILERS

SECTION WATER-TUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections

More information

48TM GAS HEATING/ELECTRIC COOLING UNITS

48TM GAS HEATING/ELECTRIC COOLING UNITS 48TM-4SB 48TM004-014 GAS HEATING/ELECTRIC COOLING UNITS PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS Copyright 2005 Carrier Corporation Syracuse, New York 13221 Form

More information

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units TECHNICAL SPECIFICATIONS R7DA Series 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units 5.4 ISMRE Commercial System 81% Steady State Efficiency Standard Features Fits Pre-Existing Curbs High-Efficiency Low

More information

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10 Model C Forced Draft Burners Natural Gas or Propane MODEL C10 MODEL C4 GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7 Telephone: (519) 620-0230 Telefax: (519) 620-0232

More information

AFUE 95% Heating Input 50,000 to 200,000 Btuh

AFUE 95% Heating Input 50,000 to 200,000 Btuh PRODUCT SPECIFICATIONS WATER HEATERS / BOILERS GWM-IE Gas-Fired, Modulating, Condensing, Wall Hung Hot Water Boiler Bulletin No. 210650 March 2018 Supersedes December 2015 AFUE 95% Heating Input 50,000

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 6000.611 Effective: 10-31-16 Replaces: NEW FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 1005A-2005A SUGGESTED SPECIFICATIONS Catalog No.: 6000.63B Effective: 3-01-15 Replaces: 9-01-09 WATER-TUBE POOL HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes condensing,

More information

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

POWER VENTER SYSTEM. Model: PVO-300, PVO-600 POWER VENTER SYSTEM Model: PVO-300, PVO-600 Included is one ETL and cetl listed Power Venter to be used primarily with a single 120VAC controlled oil fired furnace, boiler, or water heater. The PVO may

More information

PVE SERIES POWER VENTER SYSTEM MANUAL

PVE SERIES POWER VENTER SYSTEM MANUAL PVE SERIES POWER VENTER SYSTEM MANUAL Contents Page I. Typical Venting System Components 2 II. System Operation 3 III. Power Venter Sizing 3,4 IV. Installation Safety Instructions 5,6 V. Installation of

More information

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki model CH- Gas Fired,

More information

Downflow/Horizontal Right Induced Draft Gas Furnace

Downflow/Horizontal Right Induced Draft Gas Furnace Downflow/Horizontal Right Induced Draft Gas Furnace American Standard 80 ADE1A060A9361A, ADE1B060A9361A ADE1B080A951A, ADE1B100A951A ADE1C100A9601A, ADE1D120A9601A Single-Stage Fan Assisted Combustion

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

BURNERS/ FLARES. VAREC BIOGAS 244W Series WASTE GAS BURNER & IGNITION SYSTEM

BURNERS/ FLARES. VAREC BIOGAS 244W Series WASTE GAS BURNER & IGNITION SYSTEM BURNERS/ FLARES VAREC BIOGAS 4W Series WASTE GAS BURNER & IGNITION SYSTEM The Varec Biogas 4W Series Waste Gas Burner is a highly reliable flare and ignition system ideal for use in burning excess biogas.

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS HI DELTA, TYPE H - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 2000.953 Effective: 10-31-16 Replaces: NEW DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS - GENERAL 1.1 SUMMARY A. Section includes

More information

FORM NO. G REV. 2 Supersedes Form No. G Rev. 1 GAS FURNACES

FORM NO. G REV. 2 Supersedes Form No. G Rev. 1 GAS FURNACES FORM NO. G11-489 REV. 2 Supersedes Form No. G11-489 Rev. 1 GAS FURNACES RGPR- SERIES ECM Equipped Models with Input Rates from 50,000 to 125,000 BTU/HR 115 Volts, 60 Hz, Single Phase [15 to 37 kw] (U.S.

More information

G34M Bulletin #69/ August 2003

G34M Bulletin #69/ August 2003 ENGINEERING DATA G34M MULTI POSITION GAS FURNACE 12.4 to 31.0 kw Output 52.7 to 131.9 Mj Input 3.5 to 17.6 kw Nominal Add-on Cooling GAS FURNACES 50 Hz G34M Bulletin #69/490045 August 2003 Typical Applications

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 2505-4005 SUGGESTED SPECIFICATIONS Catalog No.: 6000.70 Effective: 09-15-16 Replaces: NEW WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes condensing, gas-fired

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 502C-902C SUGGESTED SPECIFICATIONS Catalog No.: 6000.601A Effective: 07-12-18 Replaces: 10-31-16 FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY.

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY. KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters Table of Contents FOR YOUR SAFETY Page # Topic If you smell gas: 1 Description of Operation 1 Receiving the

More information

Upflow/Horizontal Left, Downflow/Horizontal Right Two Stage Condensing Gas-Fired Furnace

Upflow/Horizontal Left, Downflow/Horizontal Right Two Stage Condensing Gas-Fired Furnace Upflow/Horizontal Left, Downflow/Horizontal Right Two Stage Condensing Gas-Fired Furnace XL 90 TUX060, 080, 100, 120R TDX060, 080, 100, 120R Direct Vent with Variable Speed Inducer PUB. NO. 22-1705-02-1202

More information

UNIT HEATER CATALOG. Form RZ-NA-C-UH (Version F)

UNIT HEATER CATALOG. Form RZ-NA-C-UH (Version F) UNIT HEATER CATALOG Form RZ-NA-C-UH (Version F) BACKGROUND Reznor was founded in 1888 to manufacture the Reznor reflector heater, which used a luminous flame gas burner developed by George Reznor. This

More information

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS XTHERM, TYPE WH - MODELS 1005A- 2005A Catalog No.: 3500.801 Effective: 11-15-14 Replaces: NEW PART 1 - GENERAL 1.1 SUMMARY DIVISION 23 34 36.29 COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

GAS FURNACES. Communicating Furnace Thermostat. FORM NO. G Supersedes Form No. G RHC-TST550CMMS MID HIGH

GAS FURNACES. Communicating Furnace Thermostat. FORM NO. G Supersedes Form No. G RHC-TST550CMMS MID HIGH FORM NO. G11-508 Supersedes Form No. G11-508 GAS FURNACES RGLE- SERIES ECM Equipped Models with Input Rates from 75,000 to 125,000 BTU/HR 115 Volts, 60 Hz, Single-Phase [22 to 37 kw] (U.S. & Canadian Models)

More information