PACKAGED LIQUID CHILLERS

Size: px
Start display at page:

Download "PACKAGED LIQUID CHILLERS"

Transcription

1 C-Series PACKAGED LIQUID CHILLERS Service Manual INSTALLATION AND OPERATING INSTRUCTIONS Chiller Solutions LLC 1 Service Manual

2 Section 1.0 Receiving & Inspection...4 Section 2.0 Installation Basic Description Operational Clearance Service Access Clearance Additional Placement Considerations Outdoor Installation Indoor Installation (if ducting exhaust air is required) Mounting Plumbing Piping the Chiller Material Location Field Piping Design and Layout Insulation Power Supply to Chiller Electrical Connection Main Power Connection Grounding Voltage/ Phase/ Hertz Phasing Rotation Control Wiring Options Pumping System Pump Design Understanding the Properties of Anti-freeze Integrated Pumping Variable Speed System Pump (optional) AB Series Bypass Pump (optional) Chiller Liquid Charge...18 Section 3.0 Operation and Control of Edwards Packaged Chillers...19 Typical Electrical Component Layout (Standard) Water Temperature Control (Operating Control) High Pressure Control (Compressor Discharge Pressure) Pressure Control Adjustment Pressure Control Diagram Oil Pressure Safety Control (Compressor Lubrication) Freeze-Up Protection Control Fan Motor Pressure Staging Control Outdoor Units Only Compressor ON/OFF Switch System Circulator ON/OFF Switch By-pass Circulator ON/OFF Switch Motor Circuit Protection Gauge Panel...29 Section 4.0 Start-Up Procedure Initial Start-up and Start-up After Prolonged Shut down...31 Chiller Solutions LLC 2 Service Manual

3 Section 5.0 Functional Operation of the Refrigeration System Solenoid Valve Liquid Line Filter Drier Refrigerant Sight Glass and Moisture Indicator Thermostatic Expansion Valve (TXV) Superheat Adjustment Servicing Operational Function of the System...35 Air Cooled Chiller Refrigerant and Cooling Cycle Coolant System Pressure Relief Valve Automatic Air Eliminator / Tank Fill Pipe and Dip Tube Storage Tank Sight Glass Design and Application of the Edwards Packaged Chiller Pumping Application Operating Temperature Ranges...38 Appendix A - Temperature Control Settings...39 Chiller Indoor Installation...39 Chiller - Outdoor Installation...41 Appendix B Refrigeration Gas Conversion Charts...42 Appendix C - Troubleshooting Guide...43 Appendix D - Refrigeration Piping Assembly Standards...46 System Cleanliness...46 Pressure Testing of Piping...46 Evacuation and Dehydration...47 Brazing Techniques...47 Protective atmosphere...47 Flux...47 Clean Joints...48 Appendix E - Factory Functional Test Record...49 Appendix F Warranty...50 Chiller Solutions LLC 3 Service Manual

4 Section 1.0 Receiving & Inspection Visually inspect for any damage that might have occurred during shipping or transit. Note that your rights of damage claim are limited once the bill of lading has been signed. All freight leaving Chiller Solutions is FOB Pompton Plains, NJ (Please see the Chiller Solutions standard terms and condition of sale along with the Chiller Solutions Acknowledgement of shipping risk of loss forms for more details.) The purchaser above has submitted an order for original equipment products (hereinafter, products ) manufactured by Chiller Solutions LLC (hereinafter Seller ) of 101 Alexander Ave., Unit 3, Pompton Plains, NJ Notwithstanding any other agreed on Terms and Conditions of Sale/Purchase by and between the Purchaser and the seller, Purchaser shall make no claims against the Seller for loss upon shipment as a result of the products transportation, handling, storage, which is f.o.b. point of origin- generally, Pompton Plains, New Jersey, United States of America. Form CSL-16 Note: Damage occurring in transit may include concealed damage. All damages due to travel related abuse are not covered under the Chiller Solutions Standard Warranty. See Standard Warranty for details. Please check the following: 1. Visually inspect the unit and container for any signs of damage or abuse. 2. Remove all packaging from the unit and inspect for damage. 3. Open the electrical access door on the front of the unit and inspect for damage. 4. Open the compressor access door on the rear of the unit and inspect for damage. 5. Inspect the refrigerant pressure gauges (if provided) for pressure between 75 and 125 PSI on all gauges. (If gauges are not provided, a certified technician should check to ensure system pressure(s) are within the above limits.) Chiller Solutions LLC 4 Service Manual

5 Section 2.0 Installation 2.1 Basic Description The A series chillers are one of the most space efficient air cooled chillers available in the market. For a successful installation of the packaged chiller, attention must be given to the clearance allowed around the chiller. The chiller requires coolant fluid to remove heat, electrical power to drive the motors and controls, and air to reject heat. Appropriate clearance around the unit will allow the chiller to draw air through the condenser coils where the heat of absorption and other mechanical heat is rejected. After the heat is added to the air the fan system discharges the air away from the condenser coils. 2.2 Operational Clearance Operationally, the air condensers must be provided an unrestricted source of clean air. Outdoor installations require locating the system away from potential restrictions so that air can move unobstructed through the condensers. Ensure that at least 36 of space is allowed from each of the condenser coils to the nearest possible obstruction. Ensure that the discharge of the condenser fan system is unimpeded and that no obstructions can deflect airflow back toward the air cooled condenser coils. (See Section 2.4.2) WARNING! Restricting airflow to the inlet(s) or from the outlet(s) of the condenser section will restrict the ability to reject heat. This will lead to higher discharge pressures, higher power consumption, diminished chilling capacity, and premature failure of system components. Chiller Solutions LLC 5 Service Manual

6 2.3 Service Access Clearance Another important consideration for the placement of the A-series chiller is the ability to service the components. The A-series is designed to make access to each of the components simple with the removal of one of the access panels. Care must be taken not to obstruct access to these panels when piping or electrically connecting the system. Take special care not to restrict access to the front of the system to allow appropriate access to the operating and safety controls, and compressor area for servicing. Provide enough room on all sides of the unit for servicing and removal of the largest component, should replacement be necessary. Each access panel should have at least 36 of clearance to allow proper service/maintenance of the chiller. Consult local codes for additional clearance limitations. It is also necessary to review the operating environment of the chiller for anything that could affect the performance or longevity of the chiller. Items may include exhaust vents, additional cooling items, corrosive air environments, etc. Recommended distance of at least 36 from nearest object Chiller Solutions LLC 6 Service Manual

7 2.4 Additional Placement Considerations The environment the chiller is placed in will directly affect the performance of the system. Thoroughly understand the products limited warranty! Outdoor Installation In many metropolitan areas, fumes from vehicle exhaust may create an acidic condition in the air, which will prematurely corrode the components of the system. In some marine environments, salt will also prematurely corrode the components of the system. Some industrial buildings have exhaust vents which can increase the temperature of the air in an area causing a higher temperature air to enter the condenser. Debris from lawn maintenance or a naturally dusty environment can cause blockage in the air coils. While every environment can not be mentioned, care must be taken to ensure that the proper options are selected for a given installation, and that a suitable maintenance program is implemented Indoor Installation (if ducting exhaust air is required) Most of Edwards air cooled condensers are furnished with prop-type fans designed for open-air discharge, without ducts. Air requirements are 600 CFM per ton at nominal rating of unit. If ducts are to be connected for condenser air discharge, care should be exercised when designing ducts to ensure that the pressure drop does not exceed 0.1". Venting of the chiller should be planned and constructed so that no air restrictions occur because of duct size or type of installation. Ducts should be smooth on the inside, as rough places tend to collect debris which will decrease capacity and eventually clog the duct and prevent the chiller from exhausting condenser air. Elbows, if used, must be smooth on the inside. All joints must be made so that the exhausted end of one section is inside the next one down stream. Whenever an elbow is used, turning vanes should be utilized to control air stream. If duct work is not implemented at site location or deemed unnecessary, be sure that there are no obstructions, such as a roof or ceiling, above the path of the discharged air. If an obstruction is present, the hot air will not dissipate adequately and may return to the condenser coils and decrease the efficiency of the system. Chiller Solutions LLC 7 Service Manual

8 2.5 Mounting The chiller should be installed on a concrete pad or floor or reinforced floor capable of supporting the operating weight of the entire unit. (Refer to manufacturer s data for unit operating weight.) Consult local codes for additional structural requirements or limitations. Where seismic or vibration isolation is desired, use only isolation devices capable of supporting each corner of the machine according to the corner weight. Minimum distances should be maintained around the unit to allow for adequate air flow. Each chiller skid is designed to support the entire weight of the chiller through the base frame. Adequate support for the base frame is to be provided while moving and mounting the chiller. Moving or mounting a packaged chiller is hazardous and should only be attempted by experienced rigging professionals. CAUTION! Be sure to jack up the chiller evenly on all sides to avoid tipping the chiller over. Do not tilt the chiller more than 20 from its own vertical axis while installing. Do not leave chiller standing in an elevated position. Where casters are optionally provided, ensure that the casters are locked and sufficiently blocked prior to operation. Also ensure that these chillers are installed on a level surface. 2.6 Plumbing On air-cooled models, the only plumbing required is that of connecting the water inlet and outlet from the chiller to the equipment intended to use the chilled liquid solution. These connections should be made prior to the addition of liquid to the chiller. If subject to freezing conditions, use an anti-freeze solution Piping the Chiller Piping to and from the chiller should conform to standard industry practices which fall in line with all pertinent codes. Some considerations about piping the system are material, size, layout, and serviceability. When piping, take care to avoid obstructing the access panel below the piping and the air coil above the piping. Some anti-freeze solutions may not be suitable for use with certain joint compounds or piping products. Consult the manufacturer s information for confirmation prior to piping Material Many options such as PVC, steel, copper, stainless steel, etc. may be used to pipe the system. Examine the area of installation to determine the best solution. The material should be selected to operate in the environment, with the selected anti-freeze, at the chilled fluid temperatures, using joining techniques approved by the manufacture of said material. Material should also conform to all pertinent codes. Chiller Solutions LLC 8 Service Manual

9 2.6.3 Location The location of the chiller should partly be determined by the distance and complexity of the piping system. Distance and turns in piping increase the pressure drop of the system directly increasing the amount of energy required for pumping. Minimizing these factors will improve the efficiency of the chiller system. Location should also conform to all pertinent codes Field Piping Design and Layout A well designed piping system will provide a more reliable and efficient chiller system. Ensure design of piping meets all pertinent codes. Use material that is not affected negatively with the heat transfer fluid to be used. Size the piping large enough to ensure an appropriate velocity through the pipe. Cut down on pressure drop by using as few turns between the chiller and the process as practical. Support the piping according to all applicable codes or standard industry practices. Use air eliminators at the highest areas of the piping system. Use ball or butterfly valves near the inlet and outlet of the chiller to allow isolation from the rest of the system. Provide vibration dampening devices where necessary. Install a serviceable 60 to 80 mesh screen strainer in the return line of the chiller to prevent clogging of the evaporator. Provide a convenient fill valve for the system and an appropriately sized expansion tank. Note: When connecting the supply and return lines from the equipment to the chiller inlet and outlet, be sure to use a suitable flexible connector. Do not connect metal to metal to avoid any possibility of sound transmission from running equipment and other connecting equipment. POTABLE WATER MAXIMUM PRESSURE If liquids other than water (such as glycol, oils, etc.) are used in a chiller system, do not connect permanently to potable water supply If system is to be filled from city water supply, feed through a 25 PSI pressure reducing valve into the return line. Once system is filled, remove pressure reducing valve and feed line. The chiller storage tank is designed for a maximum pressure indicated on the relief valve. Chiller Solutions LLC 9 Service Manual

10 2.6.5 Insulation Insulating the piping is important to prevent condensation from forming on the pipes as well as absorbing heat from the surrounding area. The insulation should meet local codes, and conform to standard industry practice. The insulation should provide reliable thermal resistance and a vapor barrier. The thickness and type of insulation to be used depends on the temperature of the coolant fluid in the system along with the installation environment. 2.7 Power Supply to Chiller A circuit breaker or disconnect switch should be installed, in sight of the chiller, in the power supply lines. On units ordered with disconnect assembly factory mounted, no further devices are needed. The power lines should be connected to the main power tie in lugs as per the schematic diagram supplied with each unit. Factory Installed Disconnect Assembly The machine should be properly grounded and the wire supplying current to the chiller should be heavy enough to handle the chiller load without voltage drop in the line under full load. All wiring should be installed in accordance with local and national electrical codes. Main Electrical Connection (Section 2.7.2) Electrical Connection The A-series packaged chiller is engineered for single point electrical connection. All copper conductors should be used when connecting the electrical to the chiller. Electrical connection to the chiller should meet current National Electric Code along with local codes. The A-series chiller meets or exceeds NEC but may not conform to local codes. Consult local codes for details. Chiller Solutions LLC 10 Service Manual

11 2.7.2 Main Power Connection From the exterior of the chiller, electrical service connection holes have been provided into the main electrical panel. A chase nipple should be used from the exterior panel to the interior electrical box for adequate protection. The main power should connect directly to the top of the panel mounted disconnect marked L1 through L3. Failure to provide the correct electrical conductors and wiring could result in component failure and fire. WARNING! Failure to follow the prescribed Main Power Connection instructions could result in injury or death Grounding An appropriately sized ground must be secured to the Main Ground Lug provided adjacent to the panel mounted disconnect. Ensure that each electrical connection has torque sufficient to resist vibration related loosening. Grounding the chiller should meet current National Electric code along with local codes. See Illustration 4A for details Main Ground Lug Optional Voltage Phase Monitor Panel Mounted Disconnect (Factory Installed) WARNING!! Failure to follow the prescribed Grounding instructions may result in erratic operation of the motors and controls of the system or the premature failure of components. Unsafe operation of the system could result in injury or death Voltage/ Phase/ Hertz The A-series chiller is offered in multiple main power configurations. Ensure that name plate voltage/ phase/ hertz match the electrical service being provided to the system. WARNING! Failure to provide the correct main power configuration to the system may result in severe damage to the system. Chiller Solutions LLC 11 Service Manual

12 2.7.5 Phasing Rotation The A-series chiller typically utilizes a 3 phase system. Incorrect phasing will result in the motors of the system operating in reverse. Chillers utilizing the scroll style compressors are direction sensitive. Running these scrolls in reverse may result in permanent damage to the compressor. Ensure that prior to operating the chiller that other motors in the system are operating in the correct direction prior to starting the compressor. Please also review Section 4 and follow the start up check list. Incorrect phasing can typically be remedied by switching two of the main power legs on the line side of the main power disconnect. WARNING! Phasing the system should only be attempted by a qualified electrician as severe injury or death could result. WARNING! Operating the system in reverse rotation will result in the failure of the components of the system. Chiller Solutions LLC 12 Service Manual

13 2.7.6 Control Wiring Options The standard A-series is configured to allow simple remote operation of the chiller. The control terminal strip provides contacts to operate the chiller run, the pump run, and an alarm contact. Simply provide a normally open relay or switch to these contacts and close the contacts to operate. Consult the wiring diagram for the model of chiller purchased to verify the terminal numbers. These terminals have a factory jumper installed that would be removed if these remote starting options are implemented. You may also optionally purchase switches and/or a remote operating panel in several different configurations from Chiller Solutions. (Consult factory for options and accessories list) Pump Run Contacts - must always be closed and operating prior to the compressor. A system pump interlock in the compressor control circuit prevents the compressor from operating until the system pump starter is activated and operating. The Chiller Run contacts, when remotely connected, should close within a few minutes of starting the system pump or could be started simultaneously. Chiller Run Contacts - must be closed for the compressor to begin cooling. Alarm Contacts - will close with suction or discharge pressure safety control lockout. These dry contacts can be connected to many different controls to provide the operator information that the safety lockout has occurred. The contacts are rated for 240 volts at 10 amps. Flow Switch Contacts - are provided for simple attachment of a coolant flow switch as an option for factory installation or for field attachment. If opened (no flow), these contacts will disable the compressor circuit from operating. Chiller Solutions LLC 13 Service Manual

14 2.8 Pumping Pump design is commonly disregarded in overall system design. Most chillers will provide a pump that will accomplish the task of moving the volume of fluid at a given pressure. However, pump efficiency and design can add significantly to the operating and maintenance cost of the chiller system. An inefficient pumping system costs the operating process twice. First, an inefficient pump will require a larger horsepower motor to operate at the flow and pressure thus directly increasing the amount of power consumption. Second, an inefficient pump will add heat to the process that must be removed by the refrigeration process of the chiller. This is parasitic energy that has no benefit to the chiller operation System Pump Design Prior to purchasing the chiller, determine the total system flow and pressure drop to ensure that the correct pump is selected at the factory. Commonly, a process may require a higher or lower flow than the chiller is rated for. Once the flow and total dynamic head (TDH) is determined, simply select the appropriate pump for the application. If a specific pump is required that is not listed in the pump selection section, consult the factory for selection assistance Understanding the Properties of Anti-freeze Another consideration in pumping design is fluid viscosity and specific gravity. The addition of antifreeze to the system typically causes the fluid to become more viscous, or thicker, directly increasing pump energy requirements. When more anti-freeze is added than is required, the increase in viscosity results in parasitic energy consumption (mentioned previously). Additionally, antifreeze also adversely affects the specific heat of the fluid, or thermal conductivity. This impedance to heat transfer will degrade system efficiency thus increasing runtime and energy usage. Ensure that the appropriate amount of anti-freeze mixture is used to ensure optimal performance of the chiller system. Every 5% of concentration of glycol in the chilled system loop, the capacity of the system drops 1%. Refer to the chart for concentration according to the lowest ambient temperature conditions For example, a system with 60 40ºF: % Concentration of Pressure Drop Glycol (PSI) Pump HP Loss of Capacity % % % Chiller Solutions LLC 14 Service Manual

15 Gallons of Permanent Anti-freeze Required to Lower the Freezing Point of Water in the Storage Tank Only C-SERIES CHILLER MODEL NO. STORAGE TANK CAPACITY IN GALLONS TEMPERATURE +20 F +10 F 0 F -10 F -20 F -30 F -40 F PERCENTAGE ANTI-FREEZE BY VOLUME 17% 26% 35% 41% 45% 51% 53% Chiller Solutions LLC 15 Service Manual

16 2.8.3 Integrated Pumping The system pump is the primary pump for the chiller to move the coolant fluid to the process from the chiller. The standard configuration for the A-series is for the system pump to return the process coolant fluid back through the evaporator into the storage tank with the suction of the system pump connected to the bottom of the tank. This standard configuration requires that the system pump operate any time the refrigeration system operates. The A-series comes with a bypass circuit sized to allow enough coolant fluid flow to return to the evaporator for the safe operation of the refrigeration system. In applications where 2-way valves can effectively shut off all coolant fluid flow to or from the system, the chiller internal bypass valve must remain open or another method of bypass must be installed into the process piping. WARNING!! Compressor operation without rated coolant fluid flow through the evaporator could result in a freezing condition in the evaporator which could cause a freeze rupture. Closing the By-pass valve on a system that has no other means of by-pass could result in the loss of flow to the evaporator. Ensure that the compressor suction safety cutout device is appropriately calibrated to the chiller operating conditions along with the freeze point of the coolant. (See table # 6b for settings) WARNING!! Operating the system pump without a means of bypass in the system and the internal chiller bypass valve closed will result in pump failure Variable Speed System Pump (optional) Optional variable speed controls can be added to allow the system pump to maintain a pressure differential across the process with the use of a variable frequency drive and pressure transducer. This increases the efficiency of the system pumping part of the system by using only as much horsepower as is required to maintain a given pressure. As the AB-series chiller operates to maintain the tank temperature, the system pump can be independently controlled. Consult the factory for pricing and details. Chiller Solutions LLC 16 Service Manual

17 2.8.5 AB Series Bypass Pump (optional) In some applications a bypass pump is desired to maintain the chiller tank temperature, thus allowing the system pump to operate only with a call from the process or operator. This option changes the model name of the chiller to an AB-series. Maintaining the tank temperature provides a measure of thermal storage so that when the process calls coolant at set-point temperature is readily available. The bypass pump uses far less energy than the system pump due to the relatively small amount of pressure drop of the bypass circuit. Additionally, when the system pump is operating full time, the additional heat from pumping must also be chilled thus creating additional parasitic energy usage. Chiller Run with Bypass Pump In the system/bypass AB-series arrangement the C1 and C2 Chiller Run terminals, when closed, operate the bypass pump, which is interlocked with the compressor temperature control circuit. The chiller is sent with a Jumper between the chiller run terminals (C1 & C2), should exterior control be required, remove the jumper and field provide an isolation relay or switch (contact closure) to signal the chiller to operate. System Pump Run with Bypass Pump In the system/bypass AB-series arrangement the P1 and P2 System Pump Run terminals when closed operate the system pump independent of chiller operation. For the system pump to operate a field provided isolation relay or switch (contact closure) must be provided to the System Pump Run terminals (P1 & P2). Chiller Solutions LLC 17 Service Manual

18 2.8.6 Chiller Liquid Charge A fill pipe is located at the top of the storage tank of the water chiller and is so tagged (See Section 5.6 for illustration). By removing the cap from this line and inserting a funnel, the liquid to be chilled may be added to the storage tank and interconnecting lines. To allow for venting while filling the storage tank, make sure this funnel does not seal off the top of the fill pipe. Be sure to replace the cap and air vent after filling. On large installations, it may be desirable to pump the chiller liquid solution into the tank(s) and inter-connecting lines. Care should be taken in selecting the pump for this process. The storage tank(s) is designed for a maximum pressure indicated on the relief valve installed on the storage tank. A sight glass is located on each storage tank for a visual check on chiller liquid level. The storage tank is so designed to allow a 2" air cushion at the top of each tank for expansion of the chiller liquid when warm. POTABLE WATER If an anti-freeze solution is used in the chiller, do not permanently connect to potable water supply. AMBIENT FREEZING Chillers located outdoors should be protected for ambient freeze-up by anti-freeze solution to the lowest outside temperature likely to occur in the area where the chiller is to be installed. Chillers installed indoors should be protected by antifreeze solution to approximately 25 F below the lowest water temperature control setting to be used. Before starting chiller be sure controls are set in accordance with the control setting. Chiller Solutions LLC 18 Service Manual

19 Section 3.0 Operation and Control of Edwards Packaged Chillers The chiller is controlled automatically by the water temperature control located on the control panel (Section 3.1). Models 1 through 12 ton (Standard) The water temperature control senses the return chilled liquid to the chiller and cycles the compressor as the cooling load requires. It makes and breaks the electrical circuit to the compressor contactor upon reaching the cut-out setting on the control. The compressor will remain shut down until the return liquid to the chiller reaches the cut-in setting. This energizes the electrical circuit to the compressor and it will continue to operate until the cut-out temperature setting is again reached. Models 16 ton and larger (Standard) On these units the temperature control works in conjunction with the liquid line solenoid valve. When return chilled liquid reaches the cut-out setting, the temperature control breaks the electrical circuits to the liquid line solenoid valve allowing it to close. Once closed, the compressor goes into refrigerant pump down, pumping the refrigerant from the low side (evaporator) to the high side (condenser and receiver). As the refrigerant is pumped out of the low side, the suction pressure lowers until it reaches the cut-out point on the suction pressure control. The compressor will remain shut down until the return liquid to the chiller reaches the cut-in setting on the coolant temperature control. This will energize the electrical circuit to the solenoid valve and it will open allowing the suction pressure to rise. When the pressure reaches the cut-in point on the suction pressure control, it energizes the electrical control circuit to the compressor. Chiller Solutions LLC 19 Service Manual

20 Typical Electrical Component Layout (Standard) Section 3.1 Section 3.11 Section 3.5 Section 3.10 Section 3.2 Chiller Solutions LLC 20 Service Manual

21 3.1 Water Temperature Control (Operating Control) On single compressor units (1 though 60 ton) the standard temperature control is a single stage available in two temperature ranges: 20 F to 80 F and -30 F to 50 F. The control that corresponds best to the specified temperature range on chiller ordered will be used. Both controls are identical other than the difference in range. Each have an adjustable cut-in cut-out differential of between 4 and 14. This adjustment is found on the inside of the control. By removing the front cover, the adjustment slide on the right side can be moved up to increase, or down to decrease, differential. Additional control options are also available, please consult factory for pricing and specifications. On dual compressor models (60 through 120 ton units) a two stage temperature control is utilized with the same temperature ranges that are available in the single stage. The differential on the control is fixed at 3.5 F. The differential between the two stages is adjustable from 2 F to 7 F. Additional control options are also available, please consult factory for pricing and specifications. On units with three or more compressors, a multi-stage proportioning temperature controller is used. This unit incorporates a sensor, signal center, staging control, and potentiometer to provide accurate staging of the compressors under varying load conditions. OPTION: On units incorporating the 2 stage temperature control there is an option of a lead-lag compressor relay assembly. This will enable the operator to change the lead compressor which operates the first stage of the temperature control by a selector switch. The sensing bulb of the water temperature control is located in the return chilled liquid line of the chiller and is controlling the temperature of the chilled liquid. The front dial should be set at 5 F above the maximum temperature desired. The differential on the inside of the control should be set at the lowest temperature desired. This would be the setting on the front dial minus the differential. CAUTION! Before setting this control below 42 F, be sure to check the freezing point of the chilled solution with a hydrometer. The chilled solution should contain enough anti-freeze to protect it at 25 F below the minimum setting on the temperature control. Chiller Solutions LLC 21 Service Manual

22 3.2 High Pressure Control (Compressor Discharge Pressure) The pressure control senses the compressor discharge pressure. This control is required to be set no higher than 400 psi, and comes from the factory set at 375 psi. The high pressure control is tested for operation during factory testing. Once the control has tripped, the compressor will not start until the manual reset switch has been pressed. Be sure to check the troubleshooting guide for possible reasons for this safety control trip prior to reset of the device. Once the cause of the trip has been identified and remedied, reset of the switch will allow the compressor circuit to complete and the compressor to start. (Consult the electrical diagram for more information on impact of the high pressure control on the compressor circuit.) Models 1 though 12 ton (Standard) The control on this unit is a manual reset on both low and high pressure cut-out. The reset button is located on the front cover of the control and must be depressed to bring the unit back into operation after trip-out. The low pressure cut-out is to prevent freezing of the chilled solution on low suction. If the control trips on low pressure, check the settings on this control and the settings on the water temperature control. They should be in accordance with the charts in Appendix A. Frequent shutdowns on low suction usually indicate that the machine is low on refrigerant gas. The high pressure cut-out is set at the factory at 375 PSI. Models 16 tons and larger (Standard) The controls on these units are automatically reset by operation of the temperature control. Cut-in and cut-out points should be in accordance with the charts in Appendix A. Short cycling on low pressure control usually indicates that the control settings are incorrect or unit is low on refrigerant gas. The high pressure control is factory set at 375 PSI. Chiller Solutions LLC 22 Service Manual

23 3.2.1 Pressure Control Adjustment The following guidelines and diagrams illustrate the procedures for adjusting these controls. All-Range Controls (Low Side Only) The low side of All-Range pressure controls has a scaleplate that displays the CUT IN and CUT OUT setpoints. (See visible scale on left side of control.) Turning the range screw adjusts the CUT IN and CUT OUT setpoints up or down simultaneously, while maintaining a constant pressure differential. Turning the differential screw adjusts the CUT OUT setpoint only on the left side of the scale, and changes the pressure differential. High Side Dual Pressure Controls The high side of the dual pressure control has a scaleplate that displays only the CUT OUT setpoint. (See the visible scale on right side of control.) Turning the range screw adjusts the CUT OUT setpoint. The differential is fixed at approximately 65 psi. For controls with the high side (or combination low side and high side) Manual Reset Lockout option, see Manual Reset Operation. CAUTION! DO NOT ADJUST POINTERS BEYOND THE HIGHEST OR LOWEST INDICATOR MARKS ON THE CONTROL S PRESSURE SCALE. ADJUSTING POINTERS BEYOND INDICATOR MARKS MAY DAMAGE SCREW THREADS AND CAUSE INACCURATE CONTROL OPERATION. CAUTION! CAUTION! USE THE PRESSURE CONTROL SETTINGS RECOMMENDED BY THE MANUFACTURER. DO NOT EXCEED THE PRESSURE RATINGS OF THE CONTROLLED EQUIPMENT OR ANY OF ITS COMPONENTS WHEN CHECKING PRESSURE CONTROL OPERATION OR OPERATING THE CONTROLLED EQUIPMENT AFTER INSTALLING AND ADJUSTING PRESSURE CONTROL AND BEFORE LEAVING INSTALLATION, CYCLE THE CONTROLLED EQUIPMENT SEVERAL TIMES (AT LEAST THREE) AT NORMAL OPERATING CONDITIONS. USE PRESSURE GAUGES TO VERIFY PROPER CONTROL SETTINGS AND EQUIPMENT OPERATION Chiller Solutions LLC 23 Service Manual

24 To manually adjust the pressure controller, follow the steps below. 1. Set low side CUT IN by adjusting low side range screw. Turn screw clockwise to raise CUT IN setpoint. 2. Adjust the differential screw. Turning the differential screw changes the CUT OUT setpoint. Turn screw clockwise to raise CUT OUT setpoint. 3. Set high side CUT OUT setpoint by adjusting high side range screw. Turn screw clockwise to raise the CUT OUT setpoint. (High side differential setting is fixed.) Manual Reset Operation Pressure controls with the Manual Reset option lock out when they reach the CUT OUT pressure setpoint and must be manually reset by the user to restart the chiller system. The manual reset mechanism is trip-free and cannot be overridden by blocking or tying the reset button down. On equipment with locked out controls, first determine and remedy the cause of the lockout before proceeding. When lockout is caused by the control s low side CUT OUT, allow the sensed pressure to rise to the CUT IN setpoint. When lockout is caused by the control s high side CUT OUT, allow the sensed pressure to drop at least 70 psig below the CUT OUT setpoint. After the sensed pressure has reached the desired pressure (as described above), press and release the Reset button on the front of the control to restore operation of the chiller. Chiller Solutions LLC 24 Service Manual

25 3.2.2 Pressure Control Diagram Differential Screw (Low Side Only) Low Side Range Screw Manual Reset Button (Combination Low Side and High Side Manual Reset) High Side Range Screw Low Side CUT OUT or DIFFERENTIAL pointer Low Side Bellows High Side Bellows High Side CUT OUT Pointer Low Side CUT IN pointer Chiller Solutions LLC 25 Service Manual

26 3.3 Oil Pressure Safety Control (Compressor Lubrication) Models 30 ton and up (Standard) The two probes of this control are placed between the compressor lubrication oil pump and the compressor crankcase pressure and are sensing the pressure differential between these two points. This control is factory preset at 9 PSI differential and no field adjustment should be made. Should the compressor shut down on the oil pressure control, check the level of oil in the compressor oil sight glass located on the side of the compressor; oil should be approximately half way on the sight glass. IMPORTANT! 3.4 Freeze-Up Protection Control Never reset this control more than once. If compressor goes off on oil pressure control again, a refrigeration service organization should check out and correct this problem. At no time should this control be jumped out or set below the 9 PSI differential. If control is reset more than once, permanent damage may be cause to the compressor bearings due to lack of lubrication. Models 16 ton and up (Standard) This control prevents the freezing of the chilled liquid on low pressure. It incorporates a time delay network to allow momentary low pressure surge and low pressure build up during compressor start-up. This control must be manually reset by depressing the reset button located on the front cover. This control should be set in accordance with the control setting charts in Appendix A. 3.5 Fan Motor Pressure Staging Control Outdoor Units Only Models 3 and 5 ton The pressure transducer and a permanent split capacitor motor provide infinite speed variation of the condenser fan. The pressure connection of this control is made directly into the high pressure side of the chiller. The transducer sensing the high pressure variation, coupled with the builtin printed circuit, modulates the phase conduction angle of the bipolar AC sine wave power supply to the fan motor. Models 7 ton and up (Standard) These units use a multiple fan motor arrangement to provide increased or decreased air flow through the condenser under varying ambient conditions. Each fan controller has a pressure control with a cut-out for operation of the fan motors. These controls are preset Chiller Solutions LLC 26 Service Manual

27 at the factory at cut-in and cut-out points and are both automatically reset by the increase and decrease in condensing pressure. 3.6 Compressor ON/OFF Switch If present, this switch is used to make and break the electrical circuit to the compressor controller. It should be kept in the on position at all times of normal operation. On chillers 16 tons and larger, this switch should be used as an emergency shut down only. 3.7 System Circulator ON/OFF Switch If present, this switch operates the main system circulator. Control Circuit Voltage 115 Volts. 3.8 By-pass Circulator ON/OFF Switch If present, this switch operates the by-pass circulator controller. The by-pass pump should be kept in the on position at all times Positively do not run the compressor with the by-pass pump switch in the off position or freeze-up of the evaporator might occur. CAUTION! Chiller Solutions LLC 27 Service Manual

28 3.10 Motor Circuit Protection Motor protectors are supplied for each pump, compressor, and fan and are so labeled in ascending numerical order (See wiring diagram for motor protector assignments). Each motor protector is factory set for maximum operating conditions where condensing temperatures may reach as high as 140ºF and exercise additional amp draw on the component. To manually set protection level, insert a small flat-head screwdriver into the slot located on the dial left of the STOP indicator. Lineup indicator arrow to desired amp protection: counterclockwise to increase and clockwise to decrease. Care should be exercised when setting the dial outside factory recommendation. Note: Dial setting is full load motor current. Trip current is 125% of dial setting. Typical Protection Device Note Location of Dial WARNING! The opening of the branch-circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of fire or electric shock, the component of the controller should be examined and replaced if damaged. If burnout of the current element of an overload relay occurs, the complete device must be replaced. Chiller Solutions LLC 28 Service Manual

29 3.11 Gauge Panel When performing preventative maintenance, or servicing the chiller, the supply of accurate data is essential to troubleshoot and repair any known issues. The upper portion of this stainless steel panel includes one liquid filled pressure gauge for the suction line and one for the discharge. These gauges provide simple read-out of the operating refrigerant pressures. The 6 point temperature display is mounted to the front of the electrical enclosure. This electronic display utilizes a selector knob to display 1 of six temperatures. The temperatures sensed are: Fluid Inlet Temperature Fluid Outlet Temperature Suction Line Temperature Liquid Line Temperature Compressor Discharge Temperature Condenser Air Outlet Temperature The pressure-temperature (PT) chart is used by a technician to ensure proper system operation. PT charts are most often used for three purposes: to set a coil pressure so that the refrigerant produces the desired temperature, to check the amount of superheat above the saturated vapor condition at the outlet of the evaporator and to check the amount of sub-cooling below the saturated liquid condition at the end of the condenser. Chiller Solutions LLC 29 Service Manual

30 Section 4.0 Start-Up Procedure CAUTION! DO NOT TURN DISCONNECT SWITCH TO THE ON POSITION UNTIL THE FOLLOWING STEPS HAVE BEEN COMPLIED WITH. UNDERSTAND THE FOLLOWING STEPS BEFORE PROCEEDING WITH UNIT POWER-ON. 1. Ensure that system is completely filled with chiller liquid (water; water/glycol; etc.) 2. Close all gate valves going to the process to be cooled. 3. Turn all compressor and circulator on-off switches to the off position, if applicable. 4. AIR COOLED MODELS ONLY - Check fan blade clearance in venturi to ensure that proper clearance has been maintained and blades are clear. 5. Set all temperature and pressure controls in accordance with the control settings in Appendix A. 6. Open all gate valves on unit that pertain to the recirculation piping. 7. ALL SINGLE PUMP UNITS - Open the by-pass valve located above the circulator in the by-pass line. 8. Place the main power disconnect switch to the on position. 9. Turn the by-pass pump to the on position and check rotation. Rotation should be in accordance with the direction arrow shown on pump housing. If rotation is incorrect, shut off main power disconnect and interchange two of the three phase wires supplying power to the unit. 10. Unit is now ready for start-up. a. Turn disconnect switch to on position. b. Unit should be left in this position for 24 hours to allow time for compressor crankcase heater to boil off any refrigerant liquid that might be in crankcase. c. Turn by-pass pump to the on position. d. On model 16 tons and higher, turn manual pump-down switch to on position, if applicable. e. Turn compressor on-off switch to the on position and compressor will start if applicable. Note: Condenser fans will start modulating once head pressure exceeds 200 PSI. The pressure transducer located on the compressor discharge line provides a 4-20mA signal to a VFD which modulates fan RPM to maintain discharge pressure. Chiller Solutions LLC 30 Service Manual

31 4.1 Initial Start-up and Start-up After Prolonged Shut down If water temperature in storage tank and lines are high (above 75 F) upon start-up, the compressor may shut off on the high pressure control. This is normal; if it occurs, wait until suction and discharge pressures (as read on pressure gauges) read approximately within 5 PSI of each other, then reset the discharge control. This operation may have to be repeated until the water temperature in the tank reaches a lower temperature. Chiller Solutions LLC 31 Service Manual

32 5.0 Functional Operation of the Refrigeration System The Edwards Packaged Chiller has the major components found in all refrigeration systems: evaporator, compressor and condenser. In addition to these major components, the system also has a thermal expansion valve, suction tube, liquid suction interchanger, filter drier, suction line filter, vibration eliminators, receiver, low and high side charging valves. 5.1 Solenoid Valve The solenoid valve is an on/off type valve which operates when the energized solenoid coil uncovers a port inside the valve allowing it to open. The valve also is equipped with a manual stem allowing the valve to be closed using a refrigeration service wrench. This valve is designed to protect the system from liquid migrating in off cycle times. The solenoid is opened simultaneously with compressor operation. 5.2 Liquid Line Filter Drier The liquid line filter drier is a hermetically sealed type filter drier designed to assist in screening and dehydrating the liquid refrigerant returning from the condenser. The filter drier is installed prior to the solenoid valve, sight glass and expansion valve thus providing additional protection. 5.3 Refrigerant Sight Glass and Moisture Indicator The sight glass is designed with a moisture indicator to provide a view inside the liquid line. The moisture indicator changes color based on the amount of moisture in the system. 5.4 Thermostatic Expansion Valve (TXV) The expansion valve operates to control the amount of refrigerant that enters the evaporator. The valve is designed in three primary components: the body, the cage, and the power-head. The cage is designed to operate in a range of capacities and can be exchanged with other cage sizes within the design of the expansion valve assembly. The power-head is designed to monitor the suction line temperature and pressure providing control of the amount of superheat directly after the evaporator. Chiller Solutions LLC 32 Service Manual

33 5.4.1 Superheat Adjustment The superheat can be adjusted using a standard flat screwdriver to adjust the spring tension of the cage. This is located under the 9/16 hex bolt on the valve below the dome of the power-head. WARNING! ONLY A CERTIFIED REFRIGERATION TECHNICIAN SHOULD ATTEMPT TO ADJUST THE SUPERHEAT; VALVES ARE FACTORY-SET TO A SPECIFIC SUPERHEAT. IF ADJUSTMENT IS NEEDED REFER TO INSTRUCTIONS BELOW FOR PROPER PROCEDURE. IMPROPER ADJUSTMENT MAY RESULT IN VALVE MALFUNCTION AND/OR SYSTEM DAMAGE. Expansion valves are factory-set for a static superheat. However, the superheat can be adjusted if needed. To properly adjust Alco Thermo Valves to other superheat settings: 1. Remove seal cap on side of valve 2. Turn the adjusting stem in a clockwise direction to increase the super heat, and counter clockwise to decrease superheat (approximately 1/2ºF per turn for R22 applications). Allow adequate time between adjustments for system to stabilize before checking superheat. 3. When the desired superheat is achieved, reinstall the seal cap. Note the location of the 9/16 hex bolt to be removed to access the screw that will adjust spring tension Chiller Solutions LLC 33 Service Manual

34 5.4.2 Servicing Before opening any system, make sure the pressure in the system is brought to and remains at atmospheric pressure. Failure to comply may result in system damage and or personal injury. To inspect, clean, or replace parts of the Emerson Thermo valve: 1. Disconnect equalizer line. 2. Remove the cap screws. 3. Carefully lift off the power assembly. 4. Remove cage assembly and gaskets. 5. Lightly oil gasket with refrigeration oil. (Note: Good service practice replacing all gaskets whenever a valve is opened.) 6. Assemble in the same order as disassembled. 7. When putting the power assembly on, make sure the cage assembly lugs line up with the slots inside the power assembly. (See figure below) 8. Tighten cap screws evenly and torque to 300 inch pounds. 9. Check for leaks. Chiller Solutions LLC 34 Service Manual

35 5.5 Operational Function of the System The high pressure & temperature refrigerant vapor is pumped from the compressor discharge side to the condenser where removal of heat and condensation of the refrigerant from a vapor to a liquid occurs. The high temperature & pressure liquid then passes into the filter drier, this removes any moisture from the liquid refrigerant. After passing through the liquid drier, the liquid passes through the liquid line sight glass and into the thermal expansion valve. The thermal expansion valve senses the temperature in the suction line leaving the evaporator by a remote sensing bulb. The TXV meters the amount of refrigerant fed to the evaporator and in conjunction with the compressor, maintains a proper pressure differential between the high side and the low side of the system. Upon leaving the expansion valve, the liquid refrigerant is subjected to a much lower pressure and the refrigerant immediately begins to vaporize. As refrigerant passes through the evaporator it completely vaporizes, drawing heat from the surrounding evaporator surface and water passing through the evaporator coil. The low pressure & temperature vapor is then drawn back through the suction line. At the same time, the temperature of the water passing through the evaporator coils is lowered as a result of the heat being drawn from it. Chiller Solutions LLC 35 Service Manual

36 Air Cooled Chiller Refrigerant and Cooling Cycle Chiller Solutions LLC 36 Service Manual

37 5.6 Coolant System The three major components of the coolant system are the system circulator, by-pass circulator* and combination storage tank and evaporator. The coolant is pumped from the storage tank to the equipment to be cooled and returned by means of the system circulator. The returning coolant is then boosted by the operation of the by-pass circulator and fed into the evaporator coil inside the storage tank. Here heat is removed from the coolant by the refrigerant surrounding the evaporator coolant passages. After leaving the coils at the desired temperature the coolant is discharged into the storage tank where it is ready to be used to complete the coolant cycle. This system also incorporates a by-pass line with a swing check valve, which allows water to by-pass directly to the by-pass circulator when the system pump is pumping against a dead head or system pump flow is greatly reduced. This ensures that a proper flow is maintained through the evaporator and the refrigeration cycle is kept at top efficiency. The coolant system also incorporates several minor components: an automatic air eliminator, tank fill pipe and dip tube, a storage tank sight glass and a storage tank pressure relief valve. Chiller Solutions LLC 37 Service Manual

PACKAGED AIR-COOLED LIQUID CHILLERS. Model CF-07-A-1ZB3 Serial # INSTALLATION AND OPERATING INSTRUCTIONS

PACKAGED AIR-COOLED LIQUID CHILLERS. Model CF-07-A-1ZB3 Serial # INSTALLATION AND OPERATING INSTRUCTIONS C-Series PACKAGED AIR-COOLED LIQUID CHILLERS Model CF-07-A-1ZB3 Serial # 097771 INSTALLATION AND OPERATING INSTRUCTIONS Chiller Solutions LLC 1 Instruction Manual Receiving & Inspection...4 System Description...5

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Surna 25-Ton Chiller Operating & Maintenance Manual

Surna 25-Ton Chiller Operating & Maintenance Manual www.surna.com 303.993.5271 Surna 25-Ton Chiller Operating & Maintenance Manual Models: 300F3-3. 300F4-3, 300FW-3 Revised: July 2015 Table of Contents Warranty Information 4 Limited Warranty 4 Limitation

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

CHILLER. Model CH3000. Operator s & Installation Manual

CHILLER. Model CH3000. Operator s & Installation Manual CHILLER Model CH3000 Operator s & Installation Manual Release Date: February 14, 2011 Publication Number: 620054173OPR Revision Date: May 08, 2014 Revision: B Visit the Cornelius web site at www.cornelius.com

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATION AND OPERATING INSTRUCTIONS HIGH-EFFICIENCY CONDENSING UNITS RAWD- 6 1 2 & 7 1 2 TON RAWE - 6 1 2 & 7 1 2 TON! RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!! WARNING

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

EQ Series Portable Chillers

EQ Series Portable Chillers EQ Series Portable Chillers Installation, Operation and Maintenance Manual Copyright Thermal Care Inc. 2010 Table of Contents Foreword... 1 Installation... 1 Receiving Inspection... 1 Rigging, Handling,

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity & efficiency in accordance with

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s) Electrical Problems Fuse(s) blow or circuit breaker trips Does the unit use circuit breakers or fuses? Fuse(s) Circuit breakers Are the fuses dual element time delay? Is the circuit breaker HACR rated?

More information

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 10 SEER Standard Efficiency Split System These units have been designed and tested for capacity and efficiency in accordance with

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions ! Condensate Return Systems General Installation, Operation, & Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. SAFETY INSTRUCTIONS This safety alert symbol will be used in this

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

EP1 Series Portable Chillers

EP1 Series Portable Chillers USER GUIDE UGH036-0613 www.conairgroup.com EP1 Series Portable Chillers Air-Cooled Models EP1A-01, EP1A-02, EP1A-03 Water-Cooled Models EP1W-02, EP1W-03 Remote Condenser Model EP1R-03 Thank you for purchasing

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

CHILLER. Operator s & Installation Manual

CHILLER. Operator s & Installation Manual CHILLER MODELS: CH1001-A Operator s & Installation Manual Release Date: August 9, 2002 Publication Number: 620914301 Revision Date: May 6, 2010 Revision: E Visit the IMI Cornelius web site at www.cornelius.com

More information

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers Installation, Operation and Maintenance Manual LQ Series Portable Chillers Table of Contents Foreword... 1 Installation... 1 Receiving Inspection... 1 Rigging, Handling, and Locating Equipment... 1 Electrical

More information

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N PROAIR Air Conditioner CR23 Model INSTRUCTION MANUAL Rev. D P/N 89112522 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TPA Series HEAT PUMPS 7.5 TO 10 TONS 506148 01 12/08 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act of 1990 bans the intentional

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

Trouble Shooting Guide PWA, 3-phase (D10571)

Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage Loose wire

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 2-Stage R-410A Split System These units have been designed and tested for capacity & efficiency in accordance with A.H.R.I. Standards.

More information

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( )

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( ) (N,P)R SPLIT SYSTEM HEAT PUMP For Use With R --- 22 Refrigerant 1---1/2 TO 5 TONS (018 --- 060) Product Data *Units factory---shipped with no refrigerant. Dry nitrogen charge only. FEATURES AND BENEFITS

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

CHILLER MODEL: CH1500, 2000 AND 3000

CHILLER MODEL: CH1500, 2000 AND 3000 CHILLER MODEL: CH1500, 2000 AND 3000 Operator s & Installation Manual Release Date: February 12, 2010 Publication Number: 621055837OPR Revision Date: March 25, 2014 Revision: E Visit the Cornelius web

More information

BasicTroubleshooting Information and Guidelines

BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines Information and Guidelines May 2017 BasicTroubleshooting PRIOR TO CONTACTING CLIMATEMASTER TECHNICAL SUPPORT,

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE I.O.M. #123 updated 03/28/2016 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE Covering models From 5 to 40 tons With M1 Instruments & Scroll Compressors Model: Serial Number : 525 East Stop 18 Road

More information

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill of lading

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES 11-AC11D2-5 INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: Condensing Units 2A7A5024-048, 2A7A4018-060, 2A7A2018-060 & 2A7A1018-060 IMPORTANT

More information

AIR COOLED PACKAGED CHILLER

AIR COOLED PACKAGED CHILLER AIR COOLED PACKAGED CHILLER UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 1 Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION...

More information

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

LC Series - Light Commercial Pump Station Installation and Operation Manual

LC Series - Light Commercial Pump Station Installation and Operation Manual LC Series - Light Commercial Pump Station Installation and Operation Manual Please keep this manual with the pump station Content Rain Bird LC Series Overview... Safety Instruction... Operation... 3 Pump

More information

AIR COOLED CONDENSING UNITS IMPORTANT DESIGN FEATURES

AIR COOLED CONDENSING UNITS IMPORTANT DESIGN FEATURES AIR COOLED CONDENSING UNITS The Model RCD air cooled condensing unit is a product of years of experience in the design, manufacture and application of heat transfer equipment. Thoroughly proven by thousands

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

Installation, Operation and Maintenance Manual. LQ Series. Portable Chillers 7 to 40 Tons

Installation, Operation and Maintenance Manual. LQ Series. Portable Chillers 7 to 40 Tons Installation, Operation and Maintenance Manual LQ Series Portable Chillers 7 to 40 Tons Copyright Thermal Care Inc. 2011 Page intentionally blank Table of Contents Foreword... 1 Installation... 1 Receiving

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Direct Drive Fluid Coolers

Direct Drive Fluid Coolers H-IM-68 March 2000 Part No. 25001301 Replaces H-IM-44 Direct Drive Fluid Coolers Installation and Maintenance Data Table of Contents Inspection System Warranty Installation...2 Rigging Instructions...3

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

30GT FLOTRONIC AIR-COOLED CHILLERS

30GT FLOTRONIC AIR-COOLED CHILLERS 30GT-41SB 30GT040-110 FLOTRONIC AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GT-41SB Supersedes 30GT-21SB, 30GT-22SB, 30GT-23SB, Printed

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT: GENERAL SPECIFICATIONS OUTDOOR UNIT: TECHNICAL GUIDE COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM MODELS HB 180 & HB 240 MODELS LB 180 & LB 240 15 & 20 NOMINAL TONS 9.7 EER Two independent refrigerant

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TPA Series 7.5 AND 10 TON HEAT PUMPS 7.5 TO 10 TONS 506148 01 10/2011 Supersedes 06/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean

More information

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning

More information

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions CONTENTS PAGE Pre-Installation 3 Placement & Mechanical Information 4 System Application Options 10 Antifreeze Protection 14 Electrical

More information

INSTALLATION AND OPERATING INSTRUCTIONS (2 Through 10-ton Air Cooled Single Stage Chillers)

INSTALLATION AND OPERATING INSTRUCTIONS (2 Through 10-ton Air Cooled Single Stage Chillers) INSTALLATION AND OPERATING INSTRUCTIONS (2 Through 10-ton Air Cooled Single Stage Chillers) PORTABLE WATER CHILLERS COLD SHOT CHILLERS MARRONE & CO., INC. 14020 INTERDRIVE WEST HOUSTON, TEXAS 77032 TEL:

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

This manual should be maintained in legible condition and kept adjacent to the heat pump or in a safe place for future use.

This manual should be maintained in legible condition and kept adjacent to the heat pump or in a safe place for future use. Perfectemp Swimming Pool Heat Pump CE OWNER S MANUAL Models PT4, PT6, and PT8 R C LISTE D 9900276 US This manual should be maintained in legible condition and kept adjacent to the heat pump or in a safe

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

Trouble Shooting Guide FAA, 3-phase (D3631)

Trouble Shooting Guide FAA, 3-phase (D3631) Trouble Shooting Guide FAA, 3-phase (D3631) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS Page 1 of 10 THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS Purpose of Manual The purpose of this manual is to provide operating, servicing and repair instructions for the Summit standard models ThermaPhase

More information

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER! 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS INSTALLATION GUIDE R-410A ATTENTION, INSTALLER! After installing the system, show the user how to turn off electricity to the unit. Point out control and switch

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE Master Rack Compressor Sequencer 7/21/2017 1 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PARALLEL RACK NOMENCLATURE...

More information

Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series

Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series Section 1: Temperature Control Your Haskris will have one of three different types of controller. Use table 1-1 to identify the relevant controller. The controller may appear different than examples. Contact

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

I.O.M. #116 7/10 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE. Covers Models from 25 to 100 tons.

I.O.M. #116 7/10 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE. Covers Models from 25 to 100 tons. I.O.M. #6 7/0 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE Covers Models from 25 to 00 tons. 525 East Stop 8 Road Greenwood, IN 4642 37-887-0729 fa: 37-88-277 Service Department fa: 37-885-8683

More information

TEMPERATURE & PRESSURE CONTROLS

TEMPERATURE & PRESSURE CONTROLS TEMPERATURE & PRESSURE CONTROLS RANCO LUBE OIL PROTECTION CONTROLS These lube oil protection controls guard pressure-lubricated refrigeration compressors against major damage due to loss of oil pressure.

More information

Owners Manual UA75 TO UA1200 SERIES Refrigerated Air Dryer

Owners Manual UA75 TO UA1200 SERIES Refrigerated Air Dryer 1 Owners Manual UA75 TO UA1200 SERIES Refrigerated Air Dryer DESCRIPTION PAGE INTRODUCTION 2 INSTALLATION 3 INSTALLATION GUIDE 4 DRYER CONTROLS 5 DRYER CONTROLS AND SAFTEY SHUTDOWNS 6 START UP 6 INITIAL

More information

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION INSTRUCTIONS...4

More information