ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

Size: px
Start display at page:

Download "ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data."

Transcription

1 ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. The RVA63 controller can be utilized to control the following system configurations via LPB communication. Equipment Required System Configuration Single Boiler. Two timed heating zones with independent pumps. Common flow temperature. Fixed temp / weather compensation. HWS Control. Single Boiler. Two timed heating zones with independent pumps. Independent flow temperatures. Fixed temp / weather compensation. HWS Control. Single Boiler. (Multiples of) Two timed heating zones with independent pumps. (Via multiple RVA63s) Independent flow temperatures. Fixed temp / weather compensation. HWS Control. OCI420 Com Clip One per boiler Outside sensor (QAC31/Q AC32 / *620 Ω to RVA63/47 or QAC34 to boiler) Mixing Valve/s supplie d by others one per zone Flow sensor/s (QAD21/ QAD26) One per zone Room Unit/s QAA70/ QAA50/ QAA10 directly to RVA63 Yes Yes No No Yes For pump control Yes Yes Up to 2 Up to 2 Up to 2 For valve and pump control Yes Yes Up to the number of zones Up to the number of zones Up to the number of zones As above) RVA47 Cascade manager To control up to 12 boilers No No No HWS Sensor or Volt fee enable. (QAZ21 direct to RVA63) Yes Yes Yes Multiple Boilers. Two timed heating zones with independent pumps. Common flow temperature. Fixed temp / weather compensation. HWS Control. Multiple Boilers. Two timed heating zones with independent pumps. Independent flow temperatures. Fixed temp / weather compensation. HWS Control. Multiple Boiler. (Multiples of) Two timed heating zones with independent pumps. (Via multiple RVA63s) Independent flow temperatures. Fixed temp / weather compensation. HWS Control. Yes Yes No No Yes For pump control Yes Yes Up to 2 Up to 2 Up to 2 For valve and pump control Yes Yes Up to the number of zones Up to the number of zones Up to the number of zones (As Above) Yes Yes Yes Yes Yes Yes The system configuration and sensor requirement information detailed above is not an exhaustive list, as many control options are available utilizing the Siemens Albatross control system in conjunction with the ProCon range. (*620 Ohms Substitute resister part # RES-620) Where the system configuration calls for the inclusion of a RVA47 controller, reference must be made to the specific quick reference guide for accurate parramatization. 1

2 To ensure that the ProCon can communicate with the RVA63/47 controllers the following hardware must be connected to each LMU64 controllers mounted in the rear of each ProCon boiler. 1x OCI420 Communication Clip. Clipped into the right hand space on the front of the LMU64 controller. 1x OCI420 Wiring loom to be connected to the exposed PCB at the base of the OCI420 Clip X40 and to the exposed PCB at the base of the LMU64 controller X40. Wiring Configuration and Type The interconnecting cascade wiring from the RVA 63 to RVA47 (if required) to the ProCon boilers must be connected as follows: In a parallel configuration using screened cable. (The screening must be earthed) When utilising the RVA47 as a cascade manager in conjunction with the RVA63 the following pump wiring changes must be undertaken. The pump supply wiring must be altered as follows. The boiler pump must be connected to the K1 terminals, and not the K2 terminals. RVA63 LPB Connections. MB Pink DB Purple RVA47 LPB Connections. MB Pink DB Purple LMU64 / OCI420 Clip ProCon Boiler Connections. X41 Connection Plug on front of OCI420. #1 left hand terminal. DB Purple #2 Right hand terminal. MB Pink 2

3 Communication Operation Indications The RED LED on the OCI420 flashes to indicate the detected operational status of the ProCon boiler dictated by the LPB communication from the RVA47. LED FLASH STATUS LED ON Constantly LED OFF Constantly LED ON 93% OFF 7% LED ON 5% OFF 95% LED ON 5% OFF 20% ON 5% OFF70% INTERPRETATION OPTIONS OCI420 not configured to operate with LMU64 OCI420 Configured. LPB Short Circuit / No Power. OCI420 and LUM64 Not Compatible / LPB Address inadmissible. Boiler being controlled via LPB and required to be not operating. Boiler being controlled via LPB and required to be operating. Boiler and RVA63 Parameter Configuration A number of parameters within each boiler must be altered to ensure correct operation of the system cascade communications. Press and Hold the UP and DOWN PROG buttons on the facial of the boiler until H90 appears on the display. Press the UP PROG button until the following parameters are displayed. Alter the parameters as detailed using the PLUS and MINUS button. Following the alteration of the final parameter press the INFO button to confirm the final alteration. All previous alterations will be stored into the memory by pressing the UP PROG button to pass to the next parameter for alteration. LMU64 ProCon Controller Parameter Alterations. PARAMETER EXISTING REQUIRED (Single Boiler Installation.) REQUIRED (Multiple Boiler Installations Via RVA47) System Dependant Do Not Alter from Standard Setting for Normal Operation 604 Bit Fist boiler in cascade = 2 Second boiler in cascade = 3 Third boiler in cascade = 4 80 To the maximum number of boilers allowable in cascade boiler # 12 = 13 3

4 RVA63 Controller Parameter Alterations. PARAMETER EXISTING REQUIRED (Single Boiler Installation.) REQUIRED (Multiple Boiler Installations Via RVA47) * For the first RVA63 then for subsequent RVA63s. 1* For the first RVA63 then for subsequent RVA63s * (Heat consumer not heat generator) 1* (Heat consumer not heat generator) * If LPB communication difficulties are experienced using these settings please adjust 140 to the last consecutive unused addresses up to 14 and 141 to 0. (Heat Generator) RVA 63 Fault Indication If the sensors or ProCons connected to the RVA63 controller fail or are removed from circuit, an error message will be displayed on the left of the LCD screen. Error Message Notation Er. Once an error message is present the cause of the error can be traced by accessing function [50]. To access function [50], Open the flap of the controller and press the DOWN PROG button twice. [50] Should appear in the left-hand side of the LCD display. The figure shown in the center of the screen is the fault identification number. The display can hold a number of faults but will only display 2 at any one time. The second error can be accessed by pressing the + or buttons. Once a fault has been rectified the error number will disappear or be replaced with another fault number if further attention is required. ProCon Fault Indication. The following codes will be displayed on both the Boiler control panel and all RVA controllers. Boiler Control Panel: If the Boiler LMU64 Controller or RVA63 Unit detects an operational fault a relevant code is flashed alternately with the Time of Day display. If the fault prevents the boiler from operating the appears at the lower left corners of the display. By pressing the INFO button on the display a full screen display will indicate the fault code. By opening the opening the side-hinged cover / flap on the RVA63 unit and pressing the PROG button twice Line # 50 will indicate the fault code and give a brief description of the fault. Faults can only be rest at the boiler by pressing the RESET button. Prior to pressing the RESET button a note should be made of the fault code for future reference. 4

5 Fault Code Description E-0 No Error Detected E-10 Outside Air Sensor Fault / Not Detected E-20 Flow Water Sensor Fault / Not Detected E-26 System Flow Sensor Faulty / Not Detected E-28 Flue Gas Sensor Fault / Not Detected E-40 Return Water Sensor Fault / Not Detected E-46 System Return Water Sensor Fault / Not Detected E-50 HWS Sensor Short Circuit 1 E-52 HWS Sensor Short Circuit 2 (Not Used) E-58 HWS Volt Free Switch Fault / Not Detected E-60 Faulty Room Sensor E-61 Faulty Room Sensor E-62 Incorrect Room Unit Connected E-77 Air Pressure Sensor Not Detected (Not Used) E-78 Water Pressure Sensor Defective (Not Used) E-81 LPB Short Circuit (Boiler Cascade Wiring) E-82 LPB Address Conflict (Boiler Cascade Settings) E-86 Short Circuit on PPS Connection (Not Used in ProCon Configuration) E-91 EEPROM E-92 Hardware Malfunction E-100 Conflict Between Time of Day Master Control (Boiler / QAA73 / RVA47) E-110 Boiler Water Temperature Overheat. Internal Fuse failure. X3:03 wiring error. E-111 Boiler Temperature Too High (Auto Resetting) E-113 Flue Gas Temperature overheat (Not Used) E-117 High System Water Pressure Sensor (Not Used) E-118 Low System Water Pressure Sensor (Not Used) E-119 System Water Pressure Switch Activated (Below 0.8 bar) E-124 Boiler Temperature Too High (Auto Resetting) E-128 No Flame Detected After Final Ignition Attempt (version D LMUs) E-129 Flame Extinguished During Operation (Version D LMUs) E-130 Flue Temperature Too High (Auto Resetting) E-131 Fault With Burner E-132 External Safety Interlock Activated (Open Circuit) E-133 No Flame Detected After Final Ignition Attempt E-134 Flame Extinguished During Operation E-135 Air Supply Error (Not Used) E-140 LPB Segment / Address Not Recognized (Boiler Cascade Settings) E-142 LPB Missing Partner (Boiler Cascade Settings) E-145 Wrong Device Connected to PPS Circuit (Not Used in ProCon Configuration) E-146 Unrecognized Plant Configuration E-147 Burner Modules Not Connected (PPS Circuit Not Used in ProCon Configuration ) E-148 LPB Interface Not Configured (Boiler Cascade Settings) E-150 General Boiler Fault E-151 Boiler LMU64 Controller Malfunction E-152 Boiler LMU64 Controller Parameter Programming Error E-153 Boiler Control Interlocked E-154 Boiler Operating Outside of Predefined Parameters. (System Hydraulic Error.) E-160 Fan Not Reaching Set Point E-161 Combustion Fan Speed Too High E-162 Air Pressure Switch Fault (Not Used) E-164 Flow Switch / Pressure Switch Open (Not Used) E-166 Air Pressure Switch Fault (Not Used) E-180 Boiler Operating in Chimney Mode 100% Output E-181 Boiler Operating in Commissioning Mode E-183 Boiler Controller / QAA73 Room Unit in Parameter Setting Mode 5

6 Complete RVA63 Boiler and Multi zone Controller End User Parameter Setting. To enter the End User Parameter Program, the door must be opened and one of the UP or DOWN Prog buttons must be depressed. A number between 1 & 50. Will appear in a bracket on the left of the display window. These can be paged through by using the UP or DOWN buttons. To alter or input the required data in the selected program line # use the + or - buttons. To leave the End User Parameter Setting Menu press the AUTO button. The defaults indicated below are for standard systems. If additional control features are required alteration will have to be made. Please refer to the RVA63 manual for additional details. #, -, --- Indicates where an input can be made if required. -- Indicates where an input can not be made and a sensed / attenuated figure is displayed. OFF will be displayed if the +/- buttons are used. [Prog #] Description of Prog # Range Inputs Standard Time of Day. 1 Time of day 0-23:59 Hr/Min 00:00 2 Weekday 1 7 Day 1 3 Date Day / Month Date Year 0000 Year 2005 Time Switch Program Heating Zone 1 5 Every day the same. 1-7 Day - Every day different. 1 7 Day 6 1 st On time :00 Hr/Min 06: st Off time :00 Hr/Min 22: nd On time 00-24:00 Hr/Min - 6

7 9 2 nd Off time 00-24:00 Hr/Min rd On time 00-24:00 Hr/Min rd Off time 00-24:00 Hr/Min - Time Switch Program Heating Zone 2 5 Every day the same. 1-7 Day - Every day different. 1 7 Day 6 1 st On time :00 Hr/Min 06: st Off time :00 Hr/Min 22: nd On time 00-24:00 Hr/Min nd Off time 00-24:00 Hr/Min rd On time 00-24:00 Hr/Min rd Off time 00-24:00 Hr/Min - Time Switch Program HWS 19 Every day the same. 1-7 Day - Every day different. 1 7 Day 20 1 st On time :00 Hr/Min 06: st Off time :00 Hr/Min 22: nd On time 00-24:00 Hr/Min nd Off time 00-24:00 Hr/Min rd On time 00-24:00 Hr/Min rd Off time 00-24:00 Hr/Min - Hot Water Service 26 Required HWS temperature C 55 Heating Circuit 27 Night set back temperature C Frost Protection temp 4-15 C 10 7

8 29 Summer/Winter switching 8-30 C Slope of heating curve -/ If a 0-10 volt signal is the required heat generation control method for the RVA63 / 47 / boiler installation this setting must be adjusted to -- on all RVA63s /47s present in the boiler cascade installation. This will result in the Auto, On/Off and Frost lights becoming inactive. Alteration to parameter #170 and #172 will also be required. Actual Values 33 Actual Room temperature 0-50 C Actual outside temperature C -- (Pressing the +&- buttons simultaneously until the display stops flashing will reset the averaged value.) Maintenance 35 Burner Hours run Stage 1 or LMU enabled Burner Hours run Stage Number of burner starts Stage Number of burner starts Stage Time switch factory presets reset. 0/1-0 Press +&- together for 3 seconds Holidays 40 Holiday Period (up to 8 preprogrammed holiday periods can be stored) 41 Start date for holiday period. Month/Day --:-- Holiday period setting factory reset. Press +&- together for 3 seconds 42 End date for holiday period. Month/Day --:-- Holiday period setting factory reset. Press +&- together for 3 seconds Service Indications 49 Module Error Code 1..4/ (Not always displayed) 50 Indication of faults

9 Heating Engineer Parameter Setting. To enter the Heating Engineer Parameter Program, the door must be opened and the UP & DOWN Prog buttons must be depressed for at least 3 seconds until # 51 appears in the window. A # between 51 & 173. will appear in a bracket on the left of the display window. These can be paged through by using the UP or DOWN buttons. To alter or input the required data in the selected program line # use the + or - buttons. To leave the Heating Engineer Parameter Setting Menu press the AUTO button. [Prog #] Description of Prog # Range Standard Service Values 51 Output Test 0 Automatic control All outputs Off 2 Burner stage 1 on (K4) 3 Burner stages 1 & 2 On (K4 & K5) 4 HWS pump/valve on (Q3 / Y3) 5 Heating Circulating pump 1 On (Q2) 6 Mixing Valve 1 Open (Y1) 7 Mixing Valve 1 Close (Y2) 8 Heating Circulating pump 2 On (Q6) 9 Mixing Valve 2 Open (Y5) 10 Mixing Valve 2 Close (Y6) 52 Input Test 0 Boiler Sensor (B2) HWS 1 Sensor (B3) 2 Display of input of H2 (H2/B31) 3 Flow sensor Heating zone 1 (B1) 4 Flow sensor Heating zone 2 (B12) 5 Outside air sensor (B9) 6 Room sensor heating zone 1 (RG1,A6) 7 Room sensor heating zone 2 (RG2,A7) 8 Flue gas sensor (B8) 9 Display of input of H1 (H1) 53 Plant Type # refer to drawings at rear of manual (System Specific) Actual Values 55 Actual value of Zone flow temperatures

10 56 Actual value of Boiler flow temperature Actual value of common flow temperature Actual value of HWS 1 temperature Actual value of HWS 2 temperature Maximum value flue gas temperature Press +&- together for 3 seconds to reset setting 65 Attenuated outside air temperature Comp outside air temperature --/ Outside air temperature source 00.01/ RVA63 Dictated Set Points 68 Display of boiler temperature set point Affected by external inputs 69 Display of common flow temperature set points Affected by external inputs Display of HWS temperature set point 0.0/ Nominal Room temperature set point 0.0/ Display of Set point of room temperature 0.0/ Display of flow temperature set point Underfloor heating control 77 Floor curing data. Day Temperature set point Heat Generation Equipment 80 Type of heat source Via LPB or PPS 1. Single Stage burner 2. 2 stage burner 10

11 81 Minimum limitation of boiler flow temperature Bathroom circuit heating supply pump overrun Inactive 1. Active Space Heating 100 Displacement of heating curve Gain factor for room temperature influence Active 1. Inactive 102 Room temperature pump switching differential Higher = Less stable temperature ---/ Lower = More stable temperature Inactive. 103 Operating / Control mode of Room unit Parallel action. Room unit 1 on Heating Zone 1 Room unit 2 on Heating Zone 2 1. Crossed action Room unit 1 on Heating Zone 2 Room unit 2 on Heating Zone 1 2. Serial action Room unit 1 on Heating Zones 1 & Room unit values Parallel action. Room unit 1 on Heating Zone 1 Room unit 2 on Heating Zone 2 1. Crossed action Room unit 1 on Heating Zone 2 Room unit 2 on Heating Zone 1 2. Serial action Room unit 1 on Heating Zones 1 & Minimum limitation of flow temperature Maximum limitation of system flow temperature. 109 Optimum Start Maximum Forward Shift 00-06:00 00:00 00:00 Inactive 11

12 110 Optimum Stop Maximum Forward Shift 00-06:00 00:00 00:00 Inactive 113 Type of build construction 0/1 1 0 Heavy 1 Light 114 Adaptation of heating curve. 0/1 0 0 Inactive 1 Active 115 Gain of locking signal % 100 Effect of HWS priority on mixing valves 116 Floor curing activation setting Off 1. Functional Heating 2. Floor curing 3. Functional and floor curing HWS 120 Reduced HWS temperature set point HWS time control hours per day. 1. As heating times with 1 hour shift. 2. As HWS time settings. 123 HWS control system Controlled via local circuit 1. Controlled via all segment 2. Controlled via all in LPB system 124 HWS charging cycles per 24 hour period One per day with 2.5 hour forward shift. 1. Several per day with 1 hour forward shift. 125 HWS sensor type Sensor. 1. Thermostat switch. 126 Flow temperature boost in HWS mode

13 127 HWS Priority / Shifting Absolute priority. 1. Shifting priority heating reduced to increase recovery on HWS. 2. No priority HWS and Heating operate. 3. Shifting / Absolute Pump circuit switched off, mixing circuit decreased to increase recovery of HWS. 128 HWS Charging option Charging pump 1. Diverter valve LPB Communication Setting 140 LPB control device address Standalone single RVA Master RVA63 cascade manager with sensors attached Slave RVA63 / 47s operating from master RVA63.(House Number.) (Each subsequent RVA47 should be given consecutive numbers.) 141 LPB control segment address Heat generator. (Street Name.) 1.14 Heat consumer. 142 LPB Bus power supply Off. 1. On. 143 Operation of LPB power supply. On / Off Change over via LPB connections All controller in same segment. 1. All controllers in LPB system. 146 Auto Summer / Winter change over function Local control only. 1. Entire control via LPB. 147 Central Standby switching Deactivated. 1. Activated. 148 Clock mode Autonomous Clock Individual controller can have different times. 1. System time, time will match system can not be adjusted. 2. System time with adjustment. 3. System Clock, master. There can be only one master on system. 13

14 150 Automatic Seasonal Time Adjustment. Date.Month Spring, time adjustment Date and Month of the last Sunday in the month of March 151 Automatic Seasonal Time Adjustment. Date.Month Autumn, time adjustment Date and Month of the last Sunday in the month of October 156 Display of PPS to Room unit for zone Input H1 170 Operation of H1 terminals Changeover of operation all Heating and HWS systems 1. Changeover of operation all heating only. (HWS released) 2. Minimum flow temperature maintained (Set at 171.) 3. Heat generation stooped when switch is made. (Frost Active) Volt control to vary flow temperature. (Curve set at 172) (Terminal # volt. Terminal #2. Ground.) 5. Changeover of operation of heating zone Changeover of operation of heating zone 2. If a 0-10 volt signal is the required heat generation control method for the RVA47 / boiler installation this setting must be adjusted to 4. Alterations must also be made to parameter #17. The setting must be adjusted from 32 to on all RVA63 / 47s present in the boiler cascade installation. This will result in the Auto, On/Off and Frost lights becoming inactive. Possible alterations to parameter #172 may also be required. 171 Minimum temperature set point for H Maximum temperature set point for H (For 0-10 Volt control) 173 Operating action of H1 and H2 contacts The contact is Normally Closed. 1. The contact is Normally Open. The RVA47 will operate according to its internal time switches and presets. If a remote BMS is controlling the RVA47 via a Volt Free switch across H1 0 should be inserted. This will allow the boilers operate when the Volt Free switch is made and stopped (Blocked.) when the switch is opened. If you are controlling the lead (master) RVA/Boiler via a volt free switch across H1, all slave modules should be left with 1 as the input. This will allow the AUTO light and the OFF light to indicate their operational mode dictated by the lead (master) RVA/Boiler. 14

15 174 Operating function of H2/B31 terminal HWS Sensor #2 1. Minimum flow set point 2. Heat Generation lock 3. Changeover of operation of heating zone 1 4. Changeover of operation of heating zone 2 OEM Parameter Setting. To enter the OEM Parameter Program, the door must be opened and the UP & DOWN Prog buttons must be depressed for at least 10 seconds until appears in the window. The display must be changed to by inputting a password. The password for the RVA 63 is DOWN, DOWN, PLUS, MINUS, PLUS. A # between 1 & 92. will appear in a bracket on the left of the display window. These can be paged through by using the UP or DOWN buttons. To alter or input the required data in the selected program line # use the + or - buttons. To leave the OEM Parameter Setting Menu press the AUTO button. [Prog #] Description of Prog # Range. Standard Setting Heat Source OEM 1 Minimum limitation of boiler flow temperature (Manual operation.) 2 Maximum module temperature (Manual operation.) 3 Switching differential of boiler temperature Minimum run time of boiler. 5 Release limit (Integral) of burner stage Reset limit (integral) of burner stage Pump overrun timer following burner off

16 9 Operating mode of boiler To maintain min temperature 0. Continuous. Burner operates to maintain minimum flow temperature regardless of control signal (#81) 1. Automatic. Burner operates to maintain minimum flow temperature outside of automatic controlled on modes. (#81) 2. Automatic. Burner operate only when required dependant upon automatic controlled on modes. 10 Condensation reduced startup Heat load not restricted during start up to promote condensing. 1. Heat load restricted during start up to reduce condensing. 12 Boiler pump control Mixed temperature operation. 1. Parallel to burner operation Space Heating OEM 30 Flow temperature set point boost mixing valves Room influence gain factor Constant for quick setback and optimum start Boost of room temperature set point (Room sensor dependant) Increase. Heat up time reduced. Decreased. Heat up time increased. 34 Frost protection program Frost protection program switched. Off 1. Frost protection program switched. On 35 Control Mode of actuators Zone 1 and position (Y1 / Y5) (see # 36) 1. 3 position (Y1,Y2 / Y5,Y6) 36 Switching differential of 2 position valves

17 37 Over temperature protection for pump heating circuits 0. Inactive 1. Active. 38 Heat gains Increase. If gains are high. Decrease If gains are low. 39 Curve Adaptation 1 sensitivity Outside air range between C 40 Curve Adaptation 2 sensitivity Outside air range below 4 0 C 41 Proportional band for heating zone mixing Valves 42 Integral action time for heating zone mixing Valves 43 Actuator running time for heating zone mixing Valves HWS OEM 50 Maximum HWS set point HWS switching differential.(sensor Only) Legionella function Inactive 1. Active 53 Set point of Legionella function Discharge protection during HWS heating No 1. Continuously 2. Partly 17

18 Configuration of Plant OEM 90 Continuous Display Option Weekday / Time of day 1. Actual flow temperature 91 Software Version RVA47 controller operating hours ,

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. The RVA 46 Zone Controller can only be used in conjunction with a RVA47 controlled boiler installation. The RVA46 controller

More information

ProCon Boiler Controller Commissioning Quick Reference Guide

ProCon Boiler Controller Commissioning Quick Reference Guide ProCon Boiler Controller Commissioning Quick Reference Guide This sheet is intended as a quick reference guide and should be read in conjunction with the operating and maintenance manual for the boiler

More information

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

District heating controller for two heating circuits and d.h.w. according to Siemens specifications: 4 319 2984 0 G2384en en Installation Instructions District heating controller for two heating circuits and d.h.w. RVD240 Installation Place of installation In a dry room, e.g. in the heat exchanger room

More information

G a

G a G2474 74 319 0081 0 a en Installation Instructions Heating controllers RVP3... Installation Place of installation In a dry room, e.g. in the boiler room Mounting choices: Control cabinet (in the front,

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning G2524en Heating controller Installation Instructions RVL471 1 Installation 1.1 Place of installation In a dry room, e.g. the boiler room Mounting choices: In a control panel (on the inner wall or on a

More information

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation Edition 1.0 Controller series A CE1P2546en 15.03.2011 Building Technologies Siemens Switzerland Ltd Industry

More information

Installation and Operating Manual for the ProCon HT 150 & 225 Floor Standing Condensing Boiler Range.

Installation and Operating Manual for the ProCon HT 150 & 225 Floor Standing Condensing Boiler Range. Installation and Operating Manual for the ProCon HT 150 & 225 Floor Standing Condensing Boiler Range. MHG Heating Ltd, Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR 0845 6448802

More information

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation RVA47.320 Cascade Controller for modulating gas-fired Boilers Basic Documentation Edition 2.0 Controller series B CE1P2379E 27.09.1999 Siemens Building Technologies Landis & Staefa Division 2/188 Landis

More information

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

RVL471 Heating and Domestic Hot Water Controller Basic Documentation RVL471 Heating and Domestic Hot Water Controller Basic Documentation Edition: 2.2 Controller series: C CE1P2524E 23.10.2002 Siemens Building Technologies HVAC Products 2/118 HVAC Products 23.10.2002 Contents

More information

Appliance and Controller Electrical Installation Guide.

Appliance and Controller Electrical Installation Guide. Appliance and Controller Electrical Installation Guide. MHG Heating Ltd Unit 4 Epsom Downs Metro Centre Waterfield Tadworth Surrey KT20 5LR Telephone 0845 6448802 Fax 0845 6448803 Email Info@mhgheating.co.uk

More information

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation Edition 2.0 Controller series A CE1P2545en 2018-07-27 Building

More information

Heating and D.h.w. Controller RVL482 Basic Documentation

Heating and D.h.w. Controller RVL482 Basic Documentation Heating and D.h.w. Controller RVL482 Basic Documentation Edition: 1.0 Controller series: A CE1P2542en 20.05.2008 Building Technologies Siemens Switzerland Ltd Building Technologies Group International

More information

Contents. 1 General Appliance Type Single Units Cascade Manager Units Cascade Slave Units...

Contents. 1 General Appliance Type Single Units Cascade Manager Units Cascade Slave Units... 1 Contents 1 General... 3 1.1 Appliance Type... 3 1.1.1 Single Units... 3 1.1.2 Cascade Manager Units... 4 1.1.3 Cascade Slave Units... 4 2 Installation... 5 2.1 Installation Regulations and Requirements...

More information

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000 M SERIES M116 / M45 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS Type : B23 Country BE CH ES FR GB IE IT LU NL PT Category I2E(R)B I2H I2H I2Esi I2H

More information

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division RVA66.540 Heating Circuit or Primary Controller Basic Documentation Edition 1.3 Controller series B CE1P2378E 19.04.2001 Siemens Building Technologies Landis & Staefa Division 2/150 Contents 1 Summary...

More information

Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range.

Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range. Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range. 1 Section Page # 1.0 Appliance Type 3 1.1 ProCon H 3 1.2 ProCon S 3 1.3 ProCon HS 3 1.4 ProCon

More information

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division QAA73.110 Room Unit for Boiler Control with OpenTherm Interface Basic Documentation Edition 1.0 Device series A CE1P2284en 07.05.2001 Siemens Building Technologies Landis & Staefa Division 2/64 Landis

More information

RVL481. Heating Controller. including d.h.w. heating

RVL481. Heating Controller. including d.h.w. heating 2 541 Heating Controller including d.h.w. heating RVL481 Multifunctional and communicating heating controller for use in residential and non-residential buildings. Suited for heating circuit control with

More information

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating 2 477 Heating Controller for 2 heating circuits, dhw and boiler, communicating RVP330 Multi-functional heating controller for use in residential and non-residential buildings Suitable for weather-compensated

More information

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating 2 526 Heating Controller including dhw heating Series C RVL472 Multifunctional heating controller for use in residential and non-residential buildings Suited for: Heating zone control with or without room

More information

RVL470. Heating Controller. Use. Functions. Series B

RVL470. Heating Controller. Use. Functions. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products Albatros2 Boiler controllers User manual Edition 2.0 Controller series B CE1U2354en 11. May 2007 RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Building Technologies HVAC Products 2/156 HVAC Products

More information

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail) 74 319 0400 0 G2484 en Installation Instructions Solar Energy Manager RVP502 Installation Place of installation In a dry room, e.g. in the boiler room Installation choices: - Control panel (in the panel

More information

RVL47. Heating Controller. Installations Instructions. Installation

RVL47. Heating Controller. Installations Instructions. Installation Heating Controller Installations Instructions Installation Place of installation - In a dry room, e.g. the boiler room - Mounting choices: - In a control panel (on the inner wall or on a DIN mounting rail)

More information

Type summary Albatros 2

Type summary Albatros 2 OEM Type summary lbatros 2 The lbatros 2 family is a comprehensive range of controls. It offers solutions for basic to complex heating plant. Uniform and integral operating philosophy with clear-text display

More information

RVL480. Heating Controller

RVL480. Heating Controller 2 540 Heating Controller RVL480 Multifunctional and communicating heating controller for use in residential and non-residential buildings. Suited for heating circuit control, boiler temperature control

More information

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation Edition 2.0 Controller series A, C CE1P2510en 2018-04-30 Building echnologies Published by: Siemens Switzerland Ltd. Building

More information

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

1 DOCUMENT REVISION CONTROL ELEMENTS... 9 CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11

More information

Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled**

Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled** Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled** MHG Heating Ltd, Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey,

More information

RVP310. Heating Controller. Building Technologies HVAC Products

RVP310. Heating Controller. Building Technologies HVAC Products 2 475 Heating Controller RVP310 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products lt o V.5 1 2 0 N O Albatros2 Boiler controllers User Manual Edition 2.1 Controller series B CE1U2357en 6. July 2006 RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Building Technologies

More information

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products 2 478 Heating Controller for 2 heating circuits, d.h.w. and boiler RVP331 Multi-functional heating controller for use in residential and non-residential buildings Suitable for weather-compensated flow

More information

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products Albatros 2 Zone controller User Manual RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Edition 3.0 @@@@ CE1U2353en 02.06.2009 Building Technologies HVAC Products 2/135 HVAC Products 02.06.2009 Contents

More information

Quickheat 30 weather compensated boiler control

Quickheat 30 weather compensated boiler control Quickheat 0 weather compensated boiler control A compact and sophisticated heating controller The compact KM controller is designed for the control of fan assisted boilers with modulating burners. The

More information

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products Albatros2 Boiler controller User Manual Edition 3.0 Controller series B CE1U2354en 23. August 2007 RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Building Technologies HVAC Products 2/180 HVAC

More information

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax: MC200 Users Instructions BSI Registered Firm HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: 01460 53535 Fax: 01460 52341 FM 414 Ind. & Comm. Air Heaters; Air Moving Equipment; Flues & Chimneys;

More information

Room Unit for Boiler Control QAA User manual. Building Technologies. With OpenTherm Interface

Room Unit for Boiler Control QAA User manual. Building Technologies. With OpenTherm Interface s Room Unit for Boiler Control With OpenTherm Interface User manual QAA73.210 Edition 1.0 Device series A CE1U2283en 16.08.2010 Building Technologies Siemens Switzerland Ltd Industry Sector Building Technologies

More information

PRELIMINARY EDITION

PRELIMINARY EDITION 3 131 PRELIMINARY EDITION 14.01.2003 Synco 700 Heating Controllers Heating controller for medium-size and large buildings. The is used as a heating circuit or primary controller. The controller is supplied

More information

RVL479. Heating Controller. for use with a partner unit

RVL479. Heating Controller. for use with a partner unit 2 543 Heating Controller for use with a partner unit RVL479 Communicating heating controller for use in residential and non-residential buildings. For exclusive use on the bus together with heating controllers

More information

Electronic Pellet Burner Controller NPBC-V3-1

Electronic Pellet Burner Controller NPBC-V3-1 Electronic Pellet Burner Controller NPBC-V3- SOFTWARE VERSION 3.2/3. page of 3 CHANGES IN THE TECHNICAL AND USER GUIDE OR IN THE SOFTWARE VERSION Technical and User Guide's version Changes Page 2.8. The

More information

INSTRUCTION FOR THE USER THC V E OIL BLU

INSTRUCTION FOR THE USER THC V E OIL BLU INSTRUCTION FOR THE THC V E OIL BLU CONTENTS General safety information 4 Precautions 4 Control panel 5 Mode selection 8 User levels 10 Start-up 12 Temporary shutdown 15 Preparing for extended periods

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Albatros2 Boiler Controllers User Manual RVS13.. RVS53.. Siemens Schweiz AG HVAC Products. Edition 1.0 Controller series A CE1P2383en

Albatros2 Boiler Controllers User Manual RVS13.. RVS53.. Siemens Schweiz AG HVAC Products. Edition 1.0 Controller series A CE1P2383en Albatros2 Boiler Controllers User Manual Edition 1.0 Controller series A CE1P2383en 01.05.12005 RVS13.. RVS53.. Siemens Schweiz AG HVAC Products 2/89 HVAC Products 6. June 2005 Contents 1 Summary...7 1.1

More information

Operating Instructions

Operating Instructions Operating Instructions Control panel Logamatic 4323 For the user Please read carefully before use 6 720 618 563-11/2008 US/CA Contents 1 Introduction................................................ 4 2

More information

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502* User's Guide VI.7B.D5.02 2005.10 P20 *VI7BD502* *087R8014* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8014* *VI7BD502* Boiler controller P20 VI.7B.D5.02

More information

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS... User Manual Contents 1 DOCUMENT REVISION... 4 2 SOFTWARE VERSION... 4 3 BASIC DESCRIPTION... 4 4 BASIC OVERVIEW OF HYDRAULIC DIAGRAMS... 5 4.1 BOILER NOT CONTROLLED BY THE CONTROLLER:... 5 4.2 BOILER CONTROLLED

More information

Control Application. Supplement - ACVMax

Control Application. Supplement - ACVMax prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

- Data Brochure Steam Control 279

- Data Brochure Steam Control 279 - Data Brochure Steam Control 279 D 279 12/07 The tekmar Steam Control 279 can operate a single on-off steam boiler or an on-off steam valve using outdoor reset. The control determines the on time of the

More information

Service Manual Models: 1.0, 1.3, and 1.5

Service Manual Models: 1.0, 1.3, and 1.5 AWX2-SER_100160837_2000000360_Rev F Service Manual Models: 1.0, 1.3, and 1.5 LOW LEAD CONTENT WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,

More information

INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT

INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT Instruction manual of the control equipment Program version: 2014-01-17 Benekov 04.00 C L I M A T I X 2-1 - CONTENTS 1. Introduction... 3 1.1. TERMINOLOGY AND ABBREVIATIONS... 3 1.2. NUMBER OF HEATING

More information

Hamworthy. Wessex Modumax. High Efficiency, Fully Modulating Boilers Condensing & Non Condensing, Pre-mix, Gas Fired. Outputs 100kW to 750kW

Hamworthy. Wessex Modumax. High Efficiency, Fully Modulating Boilers Condensing & Non Condensing, Pre-mix, Gas Fired. Outputs 100kW to 750kW Hamworthy Wessex Modumax High Efficiency, Fully Modulating Boilers Condensing & Non Condensing, Pre-mix, Gas Fired Outputs 100kW to 750kW Wessex ModuMax High Efficiency, Condensing Compact space saving

More information

prestige Control Application Supplement - ACVMax

prestige Control Application Supplement - ACVMax 2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory

More information

District heating controller

District heating controller 2 513 District heating controller for 1 heating circuit and d.h.w., communicating RVD250 Multifunctional heating controller for district heat transfer stations and plants with LPB and M-bus communication.

More information

Condensing Boiler RS100 Controller Training Program

Condensing Boiler RS100 Controller Training Program Condensing Boiler RS100 Controller Training Program Training Program #501102A 062311 www.rinnai.us 2009 Rinnai America Corporation Features and Benefits The RS100 connects directly to the boiler and acts

More information

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO Great Britain en Installation, user and service manual Control panel HMI Gas 310/610 ECO PRO Dear Customer, Thank you very much for buying this appliance. Please read through the manual carefully before

More information

Installation and Operating Manual for the ProCon 47, 75 & 77 Wall Mounted Condensing Boiler Range

Installation and Operating Manual for the ProCon 47, 75 & 77 Wall Mounted Condensing Boiler Range Installation and Operating Manual for the ProCon 47, 75 & 77 Wall Mounted Condensing Boiler Range 1 Section Page # 1.0 Appliance Type 3 2.0 Installation Regulations and Requirements 4 2.1 Appliance Warranties

More information

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482 Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482 Content Overview, display, and symbols... 4 Info button... 7 Operating modes... 8 Switching the heating ON... 9 D.h.w. heating...

More information

District heating controller

District heating controller 2 515 District heating controller for 2 heating circuits and d.h.w., communicating RVD260 Multifunctional heating controller for district heat transfer stations and plants with LPB and M-bus communication.

More information

Use. Functions. Key function. Other functions

Use. Functions. Key function. Other functions 2 466 Heating Control System RVP102/SET Heating control system for use in smaller plants. Control of boiler temperature through direct burner control, pump control, weather-compensated setpoint (with or

More information

Operating Instructions

Operating Instructions Operating Instructions Heating Controller Landis & Staefa RVL469 Overview... 2, 3 Symbols used... 4 Info button... 5 Operating modes... 6 Switching the heating on... 7 Room temperature is not correct...

More information

OJ Waterline control system

OJ Waterline control system OJ Waterline control system THERMOSTATS FOR COMFORT HEATING AND SNOW MELTING Product presentation Mk3 It s all about Room Temperature Control! The essential main goals are: Comfort Flexibility Reliability

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

Service Manual Models:

Service Manual Models: KBXII-SER_100161490_2000013413_Rev L Service Manual Models: 400-801 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual

More information

Electronic Pellet Burner Controller NPBC-V3M

Electronic Pellet Burner Controller NPBC-V3M Electronic Pellet Burner Controller NPBC-V3M SOFTWARE VERSION 3.3a/3.2 page of 27 CHANGES IN THE USER MANUAL OR IN THE CONTROLLER'S SOFTWARE Version of the user manual Changes Page 2.2. The software version

More information

Boiler controller Lambdatronic S 3200

Boiler controller Lambdatronic S 3200 Operating Instructions Boiler controller Lambdatronic S 3200 Version 50.04 - Build 05.04 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information

Boiler controller S-Tronic Plus

Boiler controller S-Tronic Plus Operating Instructions Boiler controller S-Tronic Plus Version 50.0 - Build 05.0 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information

Control Products & Systems OEM

Control Products & Systems OEM LMS The modular management system for condensing boilers Control Products & Systems OEM www.siemens.com/buildingtechnologies-oem LMS advanced electronics and proven software At times of dwindling resources,

More information

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O HMC300 Control unit EMS plus 6 720 808 471-00.1O Operating Instructions 6 720 813 192 (2014/10) Contents Contents Key to symbols and safety instructions................3 1.1 Key to symbols...........................

More information

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date:

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date: Trinity Tft/Lx Model #s: Tft60-399/Lx150-800 Version Date: 2013-07-26 NEW FEATURES Second Central Heat Input Internal Lead-Lag Control System Sensor Modulation Sensor Alternatives Warm Weather Shutdown

More information

Settings and Maintenance of the CombinAir

Settings and Maintenance of the CombinAir Atmos CombinAir Settings and Maintenance of the CombinAir Issue 13.8.10 Operation and commissioning: The control unit on the front of the CombinAir is used to adjust the settings during commissioning.

More information

prestige Control Application Supplement WARNING

prestige Control Application Supplement WARNING prestige Control Application Supplement WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this

More information

Mixer module VR 61. Operating and Installation Manual. Mixer module for VRC 430 / VRC 430f

Mixer module VR 61. Operating and Installation Manual. Mixer module for VRC 430 / VRC 430f For the heating engineer/for the owner Operating and Installation Manual Mixer module VR 61 Mixer module for VRC 430 / VRC 430f VR 61 GB Contents Contents 1 Notes on the documentation 3 1.1 Storage of

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information

Service Manual Models:

Service Manual Models: KBXII-SER Rev A Models: 400-801 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Knight XL Installation

More information

ADI LT CONDENSING LOW TEMPERATURE BOILER

ADI LT CONDENSING LOW TEMPERATURE BOILER ADI LT CONDENSING LOW TEMPERATURE BOILER TECHNICAL MANUAL OF INSTALLATION, USE AND MAINTENANCE V. 07/2017 INDEX 1. INTRODUCTION 4 2. REGULATIONS 5 3. EEC APPROVALS AND CERTIFICATIONS 5 4. BOILER GENERAL

More information

Weather compensated flow temperature control of heating and boiler systems

Weather compensated flow temperature control of heating and boiler systems Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance DH-SMT/DK VI.KT.G3.02 Danfoss 06/2008 How

More information

Sirius FS Working towards a cleaner future. Floor Standing Condensing Gas Boilers. Installation, Operation & Maintenance Manual

Sirius FS Working towards a cleaner future. Floor Standing Condensing Gas Boilers. Installation, Operation & Maintenance Manual To be kept by the user October 2010 Sirius FS 50-70 Floor Standing Condensing Gas Boilers Installation, Operation & Maintenance Manual Working towards a cleaner future heating specialists Dear Customer,

More information

Odyssey. issue 01c. system manual

Odyssey. issue 01c. system manual dyssey issue 01c system manual SYSTEM MANUAL Table of Contents Technical Specification 1 Summary of Features 2 General Description 3 Control ptions 4 Description of Main Features 5 Control Schemes 6 Installation

More information

Hamworthy. Purewell VariHeat

Hamworthy. Purewell VariHeat up to Seasonal efficiency (gross) Hamworthy Purewell VariHeat High Efficiency, Fully Modulating Boilers Condensing & Non Condensing Cast Iron, Pre-mix, Modular Gas Fired Single Boiler Outputs 65kW to 180kW

More information

ADI CD CONDENSING BOILER

ADI CD CONDENSING BOILER ADI CD CONDENSING BOILER º TECHNICAL MANUAL OF INSTALLATION, USE AND MAINTENANCE V. 07/2017 1 INDEX 1. INTRODUCTION 4 2. REGULATIONS 5 3. EEC APPROVALS AND CERTIFICATIONS 5 4. BOILER GENERAL VIEW: DESCRIPTION

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

DOMESTIC HOT WATER Follow operational sequence

DOMESTIC HOT WATER Follow operational sequence DOMESTIC HOT WATER Follow operational sequence Turn Winter/Summer selector to Summer position. The display is switch on. Go to section A Error 110 flashing Error 131 flashing Turn the selector to reset

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502* User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled

More information

User Instructions For TopTronic RS-30

User Instructions For TopTronic RS-30 User Instructions F TopTronic RS-30 430294ENG-Jun02 Hoval Ltd Nthgate Newark Nottinghamshire NG24 1JN Phone 01636 672711 Fax 01636 673532 2 Index 430294ENG-Jun02 Introduction Introduction... 3 Controls...

More information

Room Units and Sensors for Use in Heating Plants. Siemens Building Technologies HVAC Products SIGMAGYR. Type summary

Room Units and Sensors for Use in Heating Plants. Siemens Building Technologies HVAC Products SIGMAGYR. Type summary 2 401 SIGMAGYR Room Units and Sensors for Use in Heating Plants Type summary Sensors and room units with PPS interface: QAA24, QAA64, QAA10, QAW50..., QAW70, QAW59x, QAC22, QAC32, QAD22, QAD26, QAE22,

More information

DAY/TIME Button: Selects hour, minute and day setting.

DAY/TIME Button: Selects hour, minute and day setting. CONTENTS MODEL 5400 USER MANUAL READ ALL INSTRUCTIONS BEFORE PROCEEDING For more information on energy savings, go to www.energystar.gov Premier Series Universal Auto Changeover Thermostat Up to 3 Heat

More information

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating

More information

COnDEnSInG BOIlERS TAU UNIT OIL USER parameters manual

COnDEnSInG BOIlERS TAU UNIT OIL USER parameters manual CONDENSING BOILERS TAU UNIT OIL USER parameters manual 1 CONTENTS List of end user level parameters 3 Setting functioning parameters 6 -- Time programs 6 -- Heating circuits 6 -- Room temperature 7 --

More information

Albatros 2 CHP Controller User Manual OEM. RVC32.4x0. Building Technologies HVAC Products

Albatros 2 CHP Controller User Manual OEM. RVC32.4x0. Building Technologies HVAC Products Albatros 2 CHP Controller User Manual OEM RVC32.4x0 Edition 0.12 Controller series Z CE1UsManCHP1OEMen 12. September 2008 Building Technologies HVAC Products 2/77 HVAC Products 12. September 2008 Contents

More information

Service Manual Models: Series 100 & 101

Service Manual Models: Series 100 & 101 100305279_2000558130 Rev A Service Manual Models: 55-285 Series 100 & 101 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this

More information

ECL Comfort 110, application 130

ECL Comfort 110, application 130 Operating Guide ECL Comfort 110, application 130 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Operating instructions

Operating instructions Operating instructions Control unit Logamatic 4211 For users Read carefully before use 7 747 016 927-03/2008 GB/IE Contents 1 Introduction................................................ 4 2 What you should

More information

Service Manual Models:

Service Manual Models: FBII-SER Rev B Service Manual Models: 751-2001 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Crest Installation

More information

Boiler controller SPS 4000

Boiler controller SPS 4000 Operating instructions Boiler controller SPS 4000 Version 1.0 Translation of the original German operating instructions for the operator Read and follow the instructions and safety information! Technical

More information

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL The SF-10 Temperature Control () is an efficient boiler operator with a digital LCD display with backlight, a boiler pump output, and an alarm. The

More information

Modulating clock thermostat

Modulating clock thermostat EN Digital timer thermosatat Modulating clock thermostat Installation and Service Manual 123189-AB Contents 1 Preface...4 1.1 General...4 2 Location of the installation...5 2.1 Position of the regulator...5

More information

Service Manual Models:

Service Manual Models: 100267829_2000508773_Rev B Service Manual Models: 55-285 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the

More information

User Manual for model

User Manual for model User Manual for model RKA 24 /20 Wall mounted storage combi boiler premix condensing boiler CE 0694 Technical specification RADIANT BRUCIATORI S.p.A. Montelabbate RKA 24.20 - RAD - ING - MAN.UT - 1309.1

More information