50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

Size: px
Start display at page:

Download "50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS"

Transcription

1 50M56U-843 Universal Single Stage HSI Integrated urnace Control Kit INSTALLATION INSTRUCTIONS INSTALLER MUST READ PAGE 3 CONTAINS WIRING HARNESS AND BLOWER CONNECTION INSTRUCTIONS OR ALL APPLICATIONS AND IMPORTANT OEM REPLACEMENT INSTRUCTION OR: TRANE / AMERICAN STANDARD RHEEM / RUUD BRYANT / CARRIER / DAY & NIGHT / PAYNE AILURE TO READ AND OLLOW ALL INSTRUCTIONS CAREULLY BEORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 50M56U-843 kit is a Universal Single Stage HSI Integrated urnace Control that employs a microprocessor to continually monitor, analyze, and control the proper operation of the gas burner, inducer, and fan. The kit contains: 50M Ignition Control Module 21D64-2 Ignitor Kit Set of Interconnect Harnesses Installation should be done by a qualified heating and air conditioning contractor or licensed electrician. If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or licensed electrician. Do not exceed the specification ratings. All wiring must conform to local and national electrical codes and ordinances. This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction. ollowing installation or replacement, follow manufacturer s recommended installation/service instructions to ensure proper operation.! CAUTION Do not short out terminals on gas valve or primary control. Short or incorrect wiring may damage the thermostat. CONTENTS Description... 1 Precautions... 1 Specifications... 2 Installation... 2 Mounting & Wiring Operation... 6 Troubleshooting... 8! 21D64-2 WARNING 50M PRECAUTIONS ailure to comply with the following warnings could result in personal injury or property damage. IRE HAZARD Do not exceed the specified voltage. Replace existing control with exact model and dash number. Protect the control from direct contact with water (dripping, spraying, rain, etc.). If the control has been in direct contact with water, replace the control. Label all wires before disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Route and secure wiring away from flame. SHOCK HAZARD Disconnect electric power before servicing. Ensure proper earth grounding of appliance. Ensure proper connection of line neutral and line hot wires. EXPLOSION HAZARD Shut off main gas to appliance until installation is complete. PART NO E Replaces D 1414

2 SPECIICATIONS ELECTRICAL RATINGS 77 (25 C)]: Input Voltage: 25 VAC 50/60 Hz Max. Input 25 VAC: 0.45 amp Relay Load Ratings: Valve Relay: VAC 50/60 Hz 0.6 pf Ignitor Relay: VAC 50/60 Hz (resistive) Inducer Relay: 2.2 LA VAC Circulator Relay: 14.5 LA VAC lame Current Requirements: Minimum current to insure flame detection: 1 µa DC* Maximum current for non-detection: 0.1 µa DC* Maximum allowable leakage resistance: 100 M ohms *Measured with a DC microammeter in the flame probe lead OPERATING TEMPERATURE RANGE: -40 to 176 (-40 to 80 C) HUMIDITY RANGE: MOUNTING: Surface mount multipoise Timing Specs: (@ 60 Hz) lame Establishing Time: lame ailure Response Time: maximum 0.8 sec 2.0 sec Gases Approved: Natural, Manufactured, Mixed, Liquified Petroleum, and LP Gas Air Mixtures are all approved for use. INSTALLATION! WARNING IRE HAZARD Do not exceed the specified voltage. Replace existing control with exact model and dash number. Protect the control from direct contact with water (dripping, spraying, rain, etc.). If the control has been in direct contact with water, replace the control. Label all wires before disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Route and secure wiring away from flame. SHOCK HAZARD Disconnect electric power before servicing. Ensure proper earth grounding of appliance. Ensure proper connection of line neutral and line hot wires. EXPLOSION HAZARD Shut off main gas to appliance until installation is complete.! CAUTION Do not short out terminals on gas valve or primary control. Short or incorrect wiring may damage the thermostat. TIMING SPECIICATIONS (All times are in seconds, unless noted otherwise MOUNTING AND WIRING 50M56U-843 Pre-Purge 30 Initial Ignitor Warm-Up (1st 64 attempts) All wiring should be installed by a qualified heating and air conditioning contractor or licensed electrician, according to local and national electrical codes and ordinances. The control must be secured to an area that will experience a minimum of vibration and remain below the maximum ambient temperature rating of 176. The control is approved for minimum ambient temperatures of -40. When mounting the control, any orientation is acceptable. Choose a location that will not damage, obstruct or place stress on the control s terminations, system wiring harness or system components. After finding a suitable location, drill four (4) 1/8 holes for mounting control. To ensure proper mounting hole locations, use the control as a template. When drilling the holes, take care so that the transformer, wiring harness or other system components are not damaged. our (4) #8 sheet metal screws are provided to complete the installation. Refer to the wiring diagram and wiring table when connecting the 50M56U-843 control to other components of the system. UL approved, 105 C rated 18 gauge, stranded, 2/64 thick insulation wire is recommended for all low voltage safety circuit connections. UL approved 105 C rated 16 gauge min., stranded, 4/64 thick insulation wire is recommended for all line voltage connections. After installation or replacement, follow appliance manufacturer s recommended installation or service instructions to ensure proper operation. 17 Maximum Ignitor Warm-Up 19 Ignition Activation Period 2 Trial for Ignition Period 4 Retries 2 Recycles 3 Valve Sequence Period 12 Interpurge 60 Post-Purge 25 Lockout Time 275 Heat Delay-To-an-On 30 Heat Delay-To-an-Off 100/150* Cool Delay-To-an-On 6 Cool Delay-To-an-Off 45 Auto Reset 60 minutes *These times will vary depending on option switch position. See OPERATION section for further information. 2

3 INSTALLATION INSTALLER MUST READ OR PROPER INSTALLATION Wiring harnesses and a Universal 21D64-2 ignitor are included in this package. Refer to the enclosed Cross Reference and Harness Application Chart (Part Number ) for harness selection and ignitor application information. Ignitor installation instructions are in the UNIVERSAL 21D64-2 Ignitor package included with this kit. IMPORTANT: or continuous fan speed operation, one of the unused parked motor taps must be connected to the low heat speed terminal. ailure to do this will result in the blower not energizing in the constant fan mode operation. Refer to figure 1. Installer must read Page (6) Operation and follow option switch setting for proper control operation. In certain applications it may be necessary to remove the control board from the cover to be mounted in the space allowed. Standoffs supplied in the package must be installed before the control board can be mounted. 4 Blower lead extensions are included in the kit if extra length is needed to complete installation. igure 1 Pin 11 (RO In) or continuous fan speed connect one of the unused parked terminals here IMPORTANT OEM REPLACEMENT INSTRUCTIONS TRANE and AMERICAN STANDARD or all TRANE and AMERICAN STANDARD furnaces only: Install jumper (included in this package) into the back of the furnace 12 pin connector harness from pin 5 to pin 11 as shown in igure 2. Make sure jumper snaps into the connector securely. RHEEM / RUUD (1994 and earlier models) If the furnace control being replaced has 2 green lights and NO amber light (furnace date code 3294 or earlier) a lame Sensor Kit, RHEEM Part Number (not available from White-Rodgers) is required. Install the flame sensor and plug the flame sensor lead into pin 7 of the connector on the furnace as detailed in the Rheem lame Sensor Kit instructions. Plug the furnace connector into harness B (included in this package). Plug the other end of harness B into the new module. Attach the orange wire from harness B (3/16 female ) to S on the new module to complete the flame sense circuit. BRYANT / CARRIER / DAY & NIGHT / PAYNE This kit will not replace BRYANT / CARRIER / DAY & NIGHT / PAYNE HK42Z013 modules or CARRIER / BDP modules using an 11 pin (straight) connector. Refer to the enclosed Cross Reference and Harness Application Chart (Instruction sheet Part Number ) included with this kit for the list of modules it replaces. York (P3UR/PCLU) Install Jumper (included in this package) into the back of the furnace 12 pin connector harness from pin 5 to pin 11 as shown in figure 2. Make sure jumper snaps into the connector securely J Pin 5 (RO Out) Jumper (for Trane and American Standard applications and York P3UR/PCLU only) igure Pin Connector (back view) on existing Wire Harness in urnace 3

4 WIRING DIAGRAM HOT (LINE) TYPICAL SYSTEM WIRING DIAGRAM 120 VAC NEUTRAL (LINE) 24 VAC CLASS II TRANSORMER TH 24 VAC TR 50M56 HUMIDIIER COOL LO HEAT HI HEAT LINE XMR EAC HUM PARK PARK IND-N IND IGN IGN-N [4-Pin Connector] INDUCER IGNITOR CIRCULATOR BLOWER ELECTRONIC AIR CLEANER CIR N LINE N XMR N HUM N EAC N Y Y W G W G COMPRESSOR CONTACTOR R R C THERMOSTAT 1 STAGE GAS VALVE or 2 STAGE GAS VALVE LAME SENSOR PROBE S HLO MV LO TH PSO RO OUT TR HLI GND MV COM PSI RO IN MV HI [12-Pin Connector] HIGH LIMIT (N. C.) ROLLOUT (N. C.) AUX. HIGH LIMIT (N. C.) PRESSURE SWITCH (N. O.) or Goodman 50M Application LEGEND 4 IND IGN IND N IGN N 4-Pin Connector HLO PSO HLI PSI MV LO TH RO OUT TR GND MV COM RO IN MV HI 12-Pin Connector Low Voltage (24 VAC) Line Voltage (120 VAC) N. C. = Normally closed switch N. O. = Normally open switch

5 WIRING DIAGRAM 50M56 TERMINAL W G R Y C HLO (Pin 1) MV LO (Pin 2) TH (Pin 3) PSO (Pin 4) RO OUT (Pin 5) TR (Pin 6) HLI (Pin 7) GND (Pin 8) MV COM (Pin 9) PSI (Pin 10) RO IN (Pin 11) MV HI (Pin 12) IND (Pin 1) IGN (Pin 2) IND-N (Pin 3) IGN-N (Pin 4) COOL LO HEAT HI HEAT PARK (2 terminals) LINE XMR EAC (optional) HUM (optional) CIR N LINE N XMR N EAC N (optional) HUM N (optional) S TERMINAL TYPE HLO PSO HLI PSI MV LO TH IND RO OUT TR IGN TYPICAL SYSTEM WIRING TABLE Terminal block with captive screws Maximum recommended flame probe wire length is 36 inches. GND MV COM IND N RO IN MV HI IGN N SYSTEM COMPONENT CONNECTION low voltage thermostat W terminal (or equivalent) low voltage thermostat G terminal (or equivalent) low voltage thermostat R terminal (or equivalent) low voltage thermostat Y terminal (or equivalent) (2nd wire from Y terminal goes to 24 VAC HOT side of compressor contactor coil) 24 VAC COMMON side of compressor contactor coil high limit OUTPUT gas valve first stage 24 VAC transformer (low voltage HIGH side) pressure switch OUTPUT rollout switch OUTPUT 24 VAC transformer (low voltage COMMON side) high limit INPUT MUST BE RELIABLY GROUNDED TO CHASSIS gas valve COMMON pressure switch INPUT rollout switch INPUT gas valve second stage inducer HOT side ignitor HOT side inducer NEUTRAL side ignitor NEUTRAL side circulator blower COOL SPEED terminal circulator blower LO HEAT SPEED terminal circulator blower HI HEAT SPEED terminal unused terminals input voltage (120 VAC) HOT side 24 VAC transformer line voltage HOT side electronic air cleaner HOT side humidifier HOT side circulator blower NEUTRAL terminal input voltage (120 VAC) NEUTRAL side 24 VAC transformer line voltage NEUTRAL side electronic air cleaner NEUTRAL side humidifier NEUTRAL side flame sensor probe 5

6 OPERATION OPTION SWITCHES The option switches on the 50M56U-843 control are used to determine the length of the heat delay-to-fan-off period, the mode of operation, and the 2nd stage delay period. The following illustration shows the options and the selections of the switch positions. The switches are shown in the factory default positions. HEAT MODE When heat is required, the thermostat will send a call for heat to the control. This starts the control s heating sequence. The ignitor and humidifier (optional) are powered. The ignitor is powered after the pre-purge period. Upon initial application of power, the ignitor warm-up time is 17 seconds. The ignitor on-time will then be increased depending on whether or not flame is achieved. The warm-up time is limited to a maximum of 19 seconds. During the first 64 warmup periods following power-up, the warm-up time may not be less than 17 seconds. In the event of a retry, the warm-up time will be increased by one second and locked in at that duration. Once the warm-up time is locked, it remains fixed until another call for heat results in a retry, in which case the warm-up time is again increased by one second and remains locked. In the event of two successive retry attempts, the warm-up time will be unlocked and set to 19 seconds. If flame is then achieved, the warm-up time will begin adapting again with the next call for heat. If, however, this third attempt fails to achieve flame, the control will go into system lockout. After the ignitor warm-up period, MV LO (first stage) and MV HI (second stage) are both energized to the gas valve. lame must be detected within 4 seconds. If flame is detected, the 30-second HEAT delay-to-fan-on period begins. The circulator and electronic air cleaner (optional) will also energize at this time. 1 Stage operation If the Option Switch MODE (SW1-2) is set to the 1 STG position, both MV LO and MV HI will remain energized. 2 Stage operation (Goodman 50M Application only) If the Option Switch MODE is set to 2 STG, MV HI will deenergize after 5 seconds, leaving MV LO energized. If the MODE is in the 2 STG position, 2nd STG DLY (SW1-3) will determine the second stage- on delay as follows: 5 MIN On call for heat, the 5 minute 2nd stage recognition timer begins. After the 5-minute delay, the second stage heat (MV HI) is energized. AUTO On call for heat, the automatic second stage will determine the optimum timing between stages for comfort. Auto will adapt the delay to energize MV HI from instantly to up to 12 minutes. When the thermostat is satisfied, the gas valve is de-energized. After proof of flame loss, the heat delay-to-fan-off period begins and the inducer blower remains energized to purge the system for 25 seconds. When the purge is complete, the inducer blower is de-energized. After the delay-to-fan-off period ends, the circulator fan and electronic air cleaner are de-energized. 6 * * *MODE and 2ND STG DLY for Goodman 50M only If flame is not detected, both valves are de-energized, the ignitor is turned off, and the 50M56U-843 control goes into the retry sequence. The retry sequence provides a 60-second wait following an unsuccessful ignition attempt (flame not detected). After this wait, the ignition sequence is restarted with an additional 1 second of ignitor warm-up time. If flame is established for more than 10 seconds after ignition, the 50M56U-843 controller will clear the ignition attempt (or retry) counter. If flame is lost after 10 seconds, it will re-cycle the ignition sequence. During burner operation, a momentary loss of power of 50 milliseconds or longer will de-energize the main gas valve. When power is restored, the gas valve will remain de-energized and a restart of the ignition sequence will begin immediately. A momentary loss of gas supply, flame blowout, or a shorted or open condition in the flame probe circuit will be sensed within 2.0 seconds. The gas valve will de-energize and the control will restart the ignition sequence. Recycles will begin and the burner will operate normally if the gas supply returns, or the fault condition is corrected. If the control has gone into system lockout, it may be possible to reset the control by a momentary power interruption of one second or longer. Refer to SYSTEM LOCKOUT EATURES. COOL MODE In a typical system, a call for cool is initiated by closing the thermostat contacts. This energizes the 50M56U-843 control and the compressor. The cool delay-to-fan-on period begins. After the delay period ends, the optional electronic air cleaner is energized, and the circulator fan is energized at cool speed. After the thermostat is satisfied, the compressor is deenergized and the cool mode delay-to-fan-off period begins. After the delay-to-fan-off period ends, the circulator fan and electronic air cleaner (optional) are de-energized. MANUAL AN ON MODE If the thermostat fan switch is moved to the ON position, the circulator fan (low heat speed) and optional electronic air cleaner are energized. When the fan switch is returned to the AUTO position, the circulator fan and electronic air cleaner (optional) are de-energized. SYSTEM LOCKOUT AND DIAGNOSTIC EATURES SYSTEM LOCKOUT EATURES When system lockout occurs, the gas valve is de-energized, the circulator blower is energized at heat speed, and, if flame is sensed, the inducer blower is energized. The diagnostic indicator light will flash or glow continuously to indicate system status. (System lockout will never override the precautionary features.) To reset the control after system lockout, do one of the following: 1. Interrupt the call for heat or cool at the thermostat for at least one second but less than 20 seconds (if flame is sensed with the gas valve de-energized, interrupting the call for heat at the thermostat will not reset the control). 2. Interrupt the 24 VAC power at the control for at least one second. You may also need to reset the flame rollout sensor switch. 3. After one hour in lockout, the control will automatically reset itself.

7 OPERATION DIAGNOSTIC EATURES The 50M56U-843 control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate a failure code as shown on page 8. If the failure is internal to the control, the LED will stay off or flash 8 times. In this case, the entire control should be replaced, as the control is not field-repairable. ailure codes will flash the LED in the following flashpause sequences to indicate failure status (each flash will last approximately 0.25 seconds, and each pause will last approximately 2 seconds). AULT RECALL The last five fault codes stored can be displayed on the diagnostic LED. When the control is in standby mode (no call for heat or cool), press the AULT RECALL switch for approximately two seconds or until the diagnostic LED turns off. Release the switch and the LED will remain off for two seconds. Then the fault codes will display beginning with the most recent fault first with a two second pause between codes. After the stored fault codes have all displayed, the LED will remain off for two seconds and then turn on to indicate return to normal status. While displaying the stored fault codes, the control will ignore any new call for heat, cool or fan. AULT CODE RESET The stored fault codes can be erased from memory. When the control is in standby mode (no call for heat or cool), press the AULT RECALL switch for five to ten seconds or until the diagnostic LED begins to rapid flash. When the switch is released, the LED will turn off for two seconds to indicate the codes are erased. After two seconds the LED will turn on to indicate return to normal status. If the switch is held pressed for over ten seconds the rapid flash will stop and the LED will be on to indicate return to normal status. The 50M56U-843 has only one serviceable part an automotive type fuse, which protects the low voltage transformer from damage if the output is short-circuited. If the fuse has opened up, remove whatever caused the short circuit and replace the fuse with only a 3 Amp automotive type fuse. If the fuse does not correct the condition, replace the entire 50M56U-843 control. There are no other user serviceable parts. DEINITION O TERMS Auto Restart After one (1) hour of internal or external lockout, the control will automatically reset itself and go into an auto restart purge for 60 seconds. Cool Delay-To-an-Off The period of time between the loss of a call for cool and the deactivation of the blower motor at Cool speed. Cool Delay-To-an-On The period of time after a thermostat demand for cool before energizing the circulator blower motor at Cool speed. lame ailure Response Time (RT) The period of time between loss of the supervised main burner flame and the action to shut off the gas supply. Heat Delay-To-an-Off The period of time between the loss of a call for heat and the deactivation of the blower motor at Heat speed. Heat Delay-To-an-On The period of time between proof of the supervised main burner flame and the activation of the blower motor at Heat speed. Igniter Warm-up Time The length of time allowed for the igniter to heat up prior to the initiation of gas flow. Ignition Activation Period (IAP) The period of time between energizing the main gas valve and deactivation of the ignition means prior to the end of TI. Inter-purge The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion between the failed trial for ignition and the retry period. Post-purge Time The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion at the end of a furnace burner operating cycle. Post-purge begins at the loss of flame sense. Pre-purge Time The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion at the beginning of a furnace operating cycle prior to initiating ignition. Recycles The additional attempts within the same thermostat cycle for ignition after loss of the supervised ignition source or the supervised main burner flame. Retries The additional attempts within the same thermostat cycle for ignition when the supervised main burner flame is not proven within the first trial for ignition period. Trial for Ignition Period (TI) The period of time between initiation of gas flow and the action to shut off the gas flow in the event of failure to establish proof of the supervised ignition source or the supervised main burner flame. 7

8 Red LED lash Error/Condition Comments/Troubleshooting TROUBLESHOOTING 1 External lockout (exceeded retries) ailure to sense flame is often caused by carbon deposits on the flame sensor, a disconnected or shorted flame sensor lead or a poorly grounded furnace. Carbon deposits can be cleaned with emery cloth. Verify sensor is not contacting the burner and is located in a good position to sense flame. Check sensor lead for shorting and verify furnace is grounded properly. Verify gas supply to valve, gas valve in "On" position and appliance lighting properly. Verify flame reaches flame sensor during ignition attempts and gas pressures are correct. 2 Pressure switch stuck closed Pressure switch stuck closed. Check switch function, verify inducer is turning off. Refer to wiring diagram, terminals PSI / PSO. 3 Pressure switch stuck open Check pressure switch function and tubing. Verify inducer is turning on and pulling sufficient vacuum to engage switch. Refer to wiring diagram, terminals PSI / PSO. 4 Open high temperature limit switch Verify continuity through limit switch circuit. Refer to wiring diagram terminals, HLI / HLO. 5 lame sensed with gas valve de-energized Verify the gas valve is operating and shutting down properly. lame in burner assembly should extinguish promptly at the end of the cycle. Check orifices and gas pressure. 6 Open rollout switch or open fuse Verify continuity through rollout switch circuit. Refer to wiring diagram terminals, RO IN / RO OUT. Verify continuity of fuse which protects the low voltage transformer from damage if the output is short-circuited. If the fuse has opened up, remove whatever caused the short circuit and replace the fuse with only a 3 Amp automotive type fuse. If the fuse does not correct the condition, replace the entire control. 7 Low flame sense current Low flame sense current is often caused by carbon deposits on the flame sensor, a poorly grounded furnace or a mis-aligned flame sense probe. Carbon deposits can be cleaned with emery cloth. Check or improve furnace and module ground. Verify sensor is located in or very near flame as specified by the appliance manufacturer. Refer to wiring diagram S terminal and GND. 8 Ignitor relay fault This flash code does not indicate a broken, disconnected or shorted ignitor. It indicates the ignitor relay contacts on the ignition module are not functioning properly. Replace the ignition module. Rapid lash Reversed polarity Verify the control and furnace are properly grounded. Check and reverse polarity (primary or secondary) if incorrect. Continuous On Normal operation No fault Off Control failure Verify power to the control, replace control if power is at the control and no lit Red LED TECHNICAL SUPPORT: White-Rodgers is a business of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co.

9 50M56U-843 Harness Application Chart Module Model Number Número de Modelo del Módulo Numéro de Modèle du Module 50M56U-843 Cross Reference and Harness Application Data Correspondances et données d applications du harnais 50M56U M56U-843 Referencia cruzada e información sobre la aplicación del arnés urnace Model Modelo de Calefactor Modèle de ournaise Harness Arnés Harnais Ignitor Quemador Allumeur urnace OEM OEM del Horno OEM de our Coleman/Evcon/Luxaire/York N/A *P2URD or PBLU N/A Use existing or / Usar Coleman/Evcon/Luxaire/York Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York *6MG, L8, G9T, GUD, P1CK, Coleman/Evcon/Luxaire/York P1CX, P2DR, P3DH, P3DN, P3HU, P3UR, PACE, PACR, PBLD, PCD, PCLU, PCUH N/A Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York N/A 21D64-2 Lennox N/A Lennox N/A E & Use existing or/ Usar Heil Quaker/ICP/ Thermo Products/Whirlpool AHSC1 N/A A & C 21D64-2 United Technologies A N/A A & C United Technologies A N/A B & D United Technologies B N/A B & D United Technologies C N/A B & D United Technologies D N/A A & C United Technologies D N/A A & C United Technologies N/A Use existing or / Usar Amana/Goodman N/A E & Amana/Goodman N/A E & Amana/Goodman N/A E & Amana/Goodman N/A E & Amana/Goodman N/A E & Amana/Goodman N/A E & Amana/Goodman N/A E & Amana/Goodman N/A E & Amana/Goodman N/A 21D64-2 Amana/Goodman N/A E & Use existing or / Usar Amana/Goodman N/A E & Amana/Goodman N/A 21D64-2 Amana/Goodman S N/A Amana/Goodman 10M93 N/A Lennox 10M9301 N/A Lennox 12L6901 N/A Lennox N/A Use existing or / Usar Lennox N/A International Comfort Products N/A International Comfort Products N/A International Comfort Products PART NO C Replaces/Sp/r B 1104

10 Module Model Number Número de Modelo del Módulo Numéro de Modèle du Module 2 urnace Model Modelo de Calefactor Modèle de ournaise *DGAD, DGAE, DGA, G8, G9S, GG8S, GG9S, GGLS, GM8S, GM9, GM9S, GR8S, GY8S, GY9, GY9S, G8C, L8S, LM8S, LY8S, MG9S, TG8S, TG9S, TGLS, UGAA, UGAB, UGAD, UGAE, UGA *L8S, C8S, L9S, C9S, GY8S, LC8S, LL8S, PS8A, PS8B, PS8C, PS8D, PS8E, PS9A, PS9B, PS9C, PS9D Harness Arnés Harnais Ignitor Quemador Allumeur Use existing or / Usar urnace OEM OEM del Horno OEM de our Coleman/Evcon/Luxaire/York Coleman/Evcon/Luxaire/York *P3MPD, P2DPD, P2MPV, PBKD Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York 32M8801 N/A 21D64-2 Lennox N/A Use existing or / Usar Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York N/A Thermo Products N/A 21D64-2 Thermo Products 41-5 N/A A & C Texas Instruments 50A N/A Use existing or / Usar Heil Quaker/ICP 50A N/A Synder General 50A N/A Heil Quaker/ICP 50A N/A American Standard/Trane 50A N/A Heil Quaker/ICP 50A N/A Heil Quaker/ICP 50A N/A Heil Quaker/ICP 50A N/A American Standard/Trane 50A N/A Amana/Goodman 50A N/A Amana/Goodman 50A N/A E & Amana/Goodman 50A N/A Coleman/Evcon/Luxaire/York 50A N/A Coleman/Evcon/Luxaire/York 50A N/A Armstrong/Heil Quaker 50A N/A Clare Brothers-Canada 50A N/A DMO Industries 50A N/A Coleman/Evcon/Luxaire/York 50A N/A Coleman/Evcon/Luxaire/York 50A N/A Coleman/Evcon/Luxaire/York 50A N/A Coleman/Evcon/Luxaire/York 50A N/A White-Rodgers Standard 50A N/A E & White-Rodgers Standard 50A N/A White-Rodgers Standard 50A N/A E & Amana/Goodman 50A N/A American Standard/Trane 50A N/A American Standard/Trane 50A N/A E & Amana/Goodman 50A N/A American Standard/Trane 50A N/A American Standard/Trane 50A N/A White-Rodgers Standard 50A N/A American Standard/Trane 50A N/A White-Rodgers Standard 50A N/A American Standard/Trane 50A N/A American Standard/Trane 50A N/A American Standard/Trane 50A N/A American Standard/Trane 50A N/A Canadian Market 50A N/A American Standard/Trane 50A N/A Thermo Products/Heil Quaker/ ICP/Whirlpool 50A N/A Coleman/Evcon/Luxaire/York 50A N/A Canadian Market 50A N/A edders 50A N/A White-Rodgers Standard 50A N/A White-Rodgers Standard 50A N/A Amana/Goodman 50A N/A Amana/Goodman 50A N/A Heil Quaker/ICP/Whirlpool/ White-Rodgers Standard

11 Module Model Number Número de Modelo del Módulo Numéro de Modèle du Module urnace Model Modelo de Calefactor Modèle de ournaise Harness Arnés Harnais Ignitor Quemador Allumeur urnace OEM OEM del Horno OEM de our American Standard/Trane 50A A A XE80, XB90 American Standard XE80, XB90 American Standard N/A Use existing or / Usar American Standard/Trane American Standard/Trane 50A N/A American Standard/Trane 50A N/A American Standard/Trane 50A N/A Lennox/White-Rodgers Standard 50A *DGAD, DGAE, DGA, G8, G9S, Coleman/Evcon/Luxaire/York GG8S, GG9S, GGLS, GM8S, GM9, GM9S, GR8S, GY8S, GY9, GY9S, G8C, L8S, LM8S, LY8S, MG9S, MG9S, TG8S, TG9S, TGLS, UGAA, UGAB, UGAD, UGAE, UGA 50A *L8S, C8S, L9S, C9S, GY8S, Coleman/Evcon/Luxaire/York LC8S, LL8S, PS8A, PS8B, PS8C, PS8D, PS8E, PS9A, PS9B, PS9C, PS9D 50A N/A 21D64-2 Lennox 50A N/A Lennox 50A N/A Thermo Products 50A N/A Amana/Goodman 50A N/A Amana/Goodman 50A N/A American Standard/Trane 50A XR80, XR90, reedom 80 Single Stage American Standard/Trane 50A XR80, reedom 80 Single Stage American Standard/Trane 50A N/A White-Rodgers Standard 50A N/A Lennox 50M GDH, GME8, GMH E Use existing or / Usar Amana/Goodman 50M M56U-843 Replacement Kit / Trousse de remplacement 50M56U-843 / Kit de reemplazo 50M56U T GSU, GSM A, C & G Use existing or / Usar Amana/Goodman 50T N/A A, C & G American Standard/Trane/ White-Rodgers Standard 50T GDS8, GHS8, GMS8 E & Amana/Goodman 50T GDS8, GHS8, GMS8 E & Amana/Goodman N/A Coleman/Evcon/Luxaire/York N/A Coleman/Evcon/Luxaire/York 56L84 N/A 21D64-2 Lennox 56L8401 N/A Lennox 613 N/A Texas Instruments xx *R/U GRA B & D Use existing or / Usar xx *R/U GSA B & D xx *R/U GTA B & D Rheem/RUUD** R/U GZC B & D R/U GDG B & D R/U GLH B & D R/U GDJ B & D R/U GLI B & D UGPJ B & D G6 B, H & I Nordyne N/A B, H & I 21D64-2 Nordyne N/A B, H & I Nordyne G4 B, H & I Use existing or / Usar Nordyne N/A B, H & I 21D64-2 Nordyne x *G5RA120-C B, H & I Use existing or / Usar Nordyne N/A B, H & I 21D64-2 Nordyne N/A B, H & I Nordyne N/A B, H & I Nordyne N/A B, H & I Nordyne A G3, G4, G5, G6, M2, M3 B, H & I Use existing or / Usar Nordyne N/A B & D Rheem 3

12 Module Model Number Número de Modelo del Módulo Numéro de Modèle du Module urnace Model Modelo de Calefactor Modèle de ournaise Harness Arnés Harnais Ignitor Quemador Allumeur urnace OEM OEM del Horno OEM de our 69M0801 N/A 21D64-2 Lennox 6DT-1 N/A Texas Instruments 6DT-2 N/A Texas Instruments A N/A B, H & I Nordyne N/A Use existing or / Usar Whirlpool N/A Whirlpool N/A Whirlpool KG6RC B, H & I Nordyne N/A B, H & I 21D64-2 Nordyne G3, G4, G5, G6, M2, M3 B, H & I Use existing or / Usar Nordyne N/A Whirlpool N/A Whirlpool B S N/A E & Amana/Goodman D330927P01 N/A Trane D330930P01 N/A Trane D330934P01 N/A Trane D340035P01 N/A Trane D340774P01 N/A Trane D341213P01 N/A 21D64-2 Trane D341396P01 N/A Trane G951ADB1401 N/A Coleman/Evcon/Lennox/Luxaire/York G951ADB1401C N/A Coleman/Evcon/Lennox/Luxaire/York G951ADB-1401C N/A Coleman/Evcon/Lennox/Luxaire/York G951ADB1402 N/A Coleman/Evcon/Lennox/Luxaire/York G951ADB-1402 N/A Coleman/Evcon/Lennox/Luxaire/York G951ADB-1403 N/A Coleman/Evcon/Lennox/Luxaire/York G951AEB-1403 N/A Use existing or / Usar Coleman/Evcon/Lennox/Luxaire/York HK42Z004, HK42Z007, HK42Z008, HK42Z009, HK42Z011 or HK42Z MAV, 345MAV, 350MAV, 351DAS, 373LAV, 376CAV, 383KAV, 393AAV, 395CAV, 480BAV, 481BAV, 490AAV, 58MCA, 58MSA, 58MXA, 58PAV, 58RAV, 58WAV, 58YAV, 58ZAV, GB1AAV, GB3AAV, PG8DAA, PG8UAA, PG9MAA K & L 21D64-2 Bryant/Carrier/Day & Night/Payne ICM280 N/A A & C ICM P N/A Use existing or / Usar Coleman/Evcon/Luxaire/York X4459 N/A Lennox X N/A Lennox ootnotes: OEM furnace models abbreviated to shorten the length. Reference the control board P/N for proper replacement. Numéros de modèles de chaufferettes d origine abrégés pour des raisons d espace. ournir le numéro de pièce du tableau de commande pour obtenir un remplacement adéquat. *Nordyne/Rheem/York = additional numbers or letters *Les modèles Nordyne / Rheem comportent des chiffres ou des lettres supplémentaires *Los modelos Nordyne / Rheem tienen más números o letras N/A = Not Available N/D = Non disponible N/A = No Disponible **If existing furnace circuit board has 2 green lights and NO amber light (furnace date code 3294 or earlier), an additional lame Sensor Kit (Rheem Part ) may be required. **Si la carte de circuits imprimés existante de la fournaise est pourvue de deux voyants verts et d AUCUN voyant ambré (code de date de fournaise 3294 ou plus ancien), une trousse de détecteur de flamme (pièce no de RHEEM) peut être requise. **Si la placa de circuito del calefactor actual tiene 2 luces verdes y NINGUNA luz ámbar (código de fecha de calefactor 3294 o anterior), es posible que se necesite un kit detector de llama adicional (Rheem número de pieza ). 50M56U-843 will not replace HK42Z013 or control boards with an 11-pin bar connector. Le module 50M56U-843 ne remplace pas le module HK42Z013 ni les cartes de circuits imprimés à connecteur à 11 broches. 50M56U-843 no reemplaza HK42Z013 ni las placas de control con un conector de barra de 11pins. White-Rodgers is a division of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co.

13 INTEGRATED URNACE CONTROLS 50M56U-843 WIRING AND CONIGURATION HOT (LINE) 50M56U-843 TYPICAL WIRING DIAGRAM 120 VAC NEUTRAL (LINE) 24 VAC CLASS II TRANSORMER TH 24 VAC TR 50M56 HUMIDIIER COOL LO HEAT HI HEAT LINE XMR EAC HUM PARK PARK IND-N IND IGN IGN-N INDUCER IGNITOR CIRCULATOR BLOWER ELECTRONIC AIR CLEANER CIR N LINE N XMR N HUM N EAC N Y Y W G W G COMPRESSOR CONTACTOR R R C THERMOSTAT 1 STAGE GAS VALVE LAME SENSOR PROBE S PSI PSO HLI HLO R/O OUT GND R/O IN MV LO MV HI MV COM TR TH HIGH LIMIT (N. C.) ROLLOUT (N. C.) PRESSURE SWITCH (N. O.) AUX. HIGH LIMIT (N. C.) 2 STAGE GAS VALVE TECHNICAL HELP LEGEND Low Voltage (24 VAC) Line Voltage (120 VAC) N. C. = Normally closed switch N. O. = Normally open switch or Goodman 50M Application 209

14 50M56U-843 WIRING AND CONIGURATION INTEGRATED URNACE CONTROLS 50M56U-843 TYPICAL WIRING DIAGRAM W G R Y 50M56 TERMINAL C HLO (1) MV LO (2) TH (3) PSO (4) R/O OUT (5) TR (6) HLI (7) GND (8) MV COM (9) PSI (10) R/O IN (11) MV HI (12) IND (1) IGN (2) IND-N (3) IGN-N (4) TERMINAL TYPE Terminal block with captive screws 12-pin connector & harness 4-pin connector & harness SYSTEM COMPONENT CONNECTION low voltage thermostat W terminal (or equivalent) low voltage thermostat G terminal (or equivalent) low voltage thermostat R terminal (or equivalent) low voltage thermostat Y terminal (or equivalent) (2nd wire from Y terminal goes to 24 VAC HOT side of compressor contactor coil) 24 VAC COMMON side of compressor contactor coil high limit OUTPUT gas valve first stage 24 VAC transformer (low voltage HIGH side) pressure switch OUTPUT rollout switch OUTPUT 24 VAC transformer (low voltage COMMON side) high limit INPUT MUST BE RELIABLY GROUNDED TO CHASSIS gas valve COMMON pressure switch INPUT rollout switch INPUT gas valve second stage inducer HOT side ignitor HOT side inducer NEUTRAL side ignitor NEUTRAL side TECHNICAL HELP COOL circulator blower COOL SPEED terminal LO HEAT circulator blower LO HEAT SPEED terminal HI HEAT circulator blower HI HEAT SPEED terminal PARK (2 terminals) unused terminals LINE input voltage (120 VAC) HOT side XMR 24 VAC transformer line voltage HOT side EAC (optional) electronic air cleaner HOT side HUM (optional) humidifier HOT side CIR N circulator blower NEUTRAL terminal LINE N input voltage (120 VAC) NEUTRAL side XMR N 24 VAC transformer line voltage NEUTRAL side EAC N (optional) electronic air cleaner NEUTRAL side HUM N (optional) humidifier NEUTRAL side S flame sensor probe Maximum recommended flame probe wire length is 36 inches

15 INTEGRATED URNACE CONTROLS 50M56U-843 OPERATION OPTION SWITCHES The option switches on the 50M56U-843 control are used to determine the length of the heat delay-to-fan-off period, the mode of operation, and the 2nd stage delay period. The following illustration shows the options and the selections of the switch positions. The switches are shown in the factory default positions. * * *MODE and 2ND STG DLY for Goodman 50M only HEAT MODE When heat is required, the thermostat will send a call for heat to the control. This starts the controls heating sequence. The ignitor and humidifier (optional) are powered. The ignitor is powered after the pre-purge period. Upon initial application of power, the warm-up time is 17 seconds. The ignitor on-time will then be increased depending on whether or not flame is achieved. The warm-up time is limited to a maximum of 19 seconds. During the first 64 warm-up periods following powerup, the warm-up time may not be less than 17 seconds. In the event of a retry, the warm-up time will be increased by one second and locked in at that duration. Once the warm-up time is locked, it remains fixed until another call for heat results in a retry, in which case the warm-up time is again increased by one second and remains locked. In the event of two successive retry attempts, the warm-up time will be unlocked and set to 19 seconds. If flame is then achieved, the warm-up time will begin adapting again with the next call for heat. If, however, this third attempt fails to achieve flame, the control will go into system lockout. After the ignitor warm-up period, MV LO (first stage) and MV HI (second stage) are both energized to the gas valve. lame must be detected within 4 seconds. If flame is detected, the 30-second HEAT delay-to-fan-on period begins. The circulator and electronic air cleaner (optional) will also energize at this time. 1 Stage operation If the Option Switch MODE (SW1-2) is set to the 1 STG position, both MV LO and MV HI will remain energized. 2 Stage operation (Goodman 50M Application only) If the Option Switch MODE is set to 2 STG, MV HI will de-energize after 5 seconds, leaving MV LO energized. If the MODE is in the 2 STG position, 2nd STG DLY (SW1-3) will determine the second stage- on delay as follows: 5 MIN On call for heat, the 5 minute 2nd stage recognition timer begins. After the 5-minute delay, the second stage heat (MV HI) is energized. AUTO On call for heat, the automatic second stage will determine the optimum timing between stages for comfort. Auto will adapt the delay to energize MV HI from instantly to up to 12 minutes. When the thermostat is satisfied, the gas valve is de-energized. After proof of flame loss, the heat delay-to-fan-off period begins and the inducer blower remains energized to purge the system for 25 seconds. When the purge is complete, the inducer blower is deenergized. After the delay-to-fan-off period ends, the circulator fan and electronic air cleaner are de-energized. If flame is not detected, both valves are de-energized, the ignitor is turned off, and the 50M56U-843 control goes into the retry sequence. The retry sequence provides a 60-second wait following an unsuccessful ignition attempt (flame not detected). After this wait, the ignition sequence is restarted with an additional 1 second of ignitor warm-up time. If flame is established for more than 10 seconds after ignition, the 50M56U-843 controller will clear the ignition attempt (or retry) counter. If flame is lost after 10 seconds, it will restart the ignition sequence. During burner operation, a momentary loss of power of 50 milliseconds or longer will de-energize the main gas valve. When power is restored, the gas valve will remain de-energized and a restart of the ignition sequence will begin immediately. A momentary loss of gas supply, flame blowout, or a shorted or open condition in the flame probe circuit will be sensed within 2.0 seconds. The gas valve will de-energize and the control will restart the ignition sequence. Recycles will begin and the burner will operate normally if the gas supply returns, or the fault condition is corrected. If the control has gone into system lockout, it may be possible to reset the control by a momentary power interruption of one second or longer. Refer to SYSTEM LOCKOUT EATURES. COOL MODE In a typical system, a call for cool is initiated by closing the thermostat contacts. This energizes the 50M56U-843 control and the compressor. The cool delay-to-fan-on period begins. After the delay period ends, the optional electronic air cleaner is energized, and the circulator fan is energized at cool speed. After the thermostat is satisfied, the compressor is de-energized and the cool mode delay-to-fan-off period begins. After the delay-to-fan-off period ends, the circulator fan and electronic air cleaner (optional) are de-energized. MANUAL AN ON MODE If the thermostat fan switch is moved to the ON position, the circulator fan (low heat speed) and optional electronic air cleaner are energized. When the fan switch is returned to the AUTO position, the circulator fan and electronic air cleaner (optional) are de-energized. SYSTEM LOCKOUT AND DIAGNOSTIC EATURES SYSTEM LOCKOUT EATURES When system lockout occurs, the gas valve is de-energized, the circulator blower is energized at heat speed, and, if flame is sensed, the inducer blower is energized. The diagnostic indicator light will flash or glow continuously to indicate system status. (System lockout will never override the precautionary features.) To reset the control after system lockout, do one of the following: 1. Interrupt the call for heat or cool at the thermostat for at least one second but less than 20 seconds (if flame is sensed with the gas valve de-energized, interrupting the call for heat at the thermostat will not reset the control). 2. Interrupt the 24 VAC power at the control for at least one second. You may also need to reset the flame rollout sensor switch. 3. After one hour in lockout, the control will automatically reset itself. TECHNICAL HELP 211

16 50M56U-843 OPERATION INTEGRATED URNACE CONTROLS DIAGNOSTIC EATURES The 50M56U-843 control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate a failure code as shown below. If the failure is internal to the control, the light will stay off. In this case, the entire control should be replaced, as the control is not field-repairable. If the sensed failure is in the system (external to the control), the LED will flash in the following flash-pause sequences to indicate failure status (each flash will last approximately 0.25 seconds, and each pause will last approximately 2 seconds). DIAGNOSTIC INDICATOR LASH CODES LASH 1 System Lockout (Retries Exceeded) 2 Pressure Switch Stuck Closed 3 Pressure Switch Stuck Open 4 Open High Temperature Limit Switch 5 lame Sensed with Gas Valve De-energized 6 Open Rollout Switch 7 Low lame Sense Signal 8 Ignitor Relay ault Rapid lash Reverse Polarity Continuous On Normal Operation Off Control ailure INSTALLER MUST READ OR PROPER INSTALLATION IMPORTANT: or continuous fan speed operation, one of the unused parked motor taps must be connected to the low heat speed terminal. ailure to do this will result in the blower not energizing in the constant fan mode operation. Refer to figure 1. or all Trane and AMERICAN STANDARD applications only: Install jumper (included in this package) in the furnace 12 pin connector harness, pin 5 and pin 11 positions. Make sure jumper snaps into the connector securely. Refer to figure 1. AULT RECALL The last five fault codes stored can be displayed on the diagnostic LED. When the control is in standby mode (no call for heat or cool), press the AULT RECALL switch for approximately two seconds or until the diagnostic LED turns off. Release the switch and the LED will remain off for two seconds. Then the fault codes will display beginning with the most recent fault first with a two second pause between codes. After the stored fault codes have all displayed, the LED will remain off for two seconds and then turn on to indicate return to normal status. While displaying the stored fault codes, the control will ignore any new call for heat, cool or fan. AULT CODE RESET The stored fault codes can be erased from memory. When the control is in standby mode (no call for heat or cool), press the AULT RECALL switch for five to ten seconds or until the diagnostic LED begins to rapid flash. When the switch is released, the LED will turn off for two seconds to indicate the codes are erased. After two seconds the LED will turn on to indicate return to normal status. If the switch is held pressed for over ten seconds the rapid flash will stop and the LED will be on to indicate return to normal status. Pin 11 (R10 In) J Pin 5 (R10 Out) Jumper (for Trane and American Standard Applications only) TECHNICAL HELP DEINITION O TERMS Auto Restart After one (1) hour of internal or external lockout, the control will automatically reset itself and go into an auto restart purge for 60 seconds. Cool Delay-To-an-Off The period of time between the loss of a call for cool and the deactivation of the blower motor at Cool speed. Cool Delay-To-an-On The period of time after a thermostat demand for cool before energizing the circulator blower motor at Cool speed. lame ailure Response Time (RT) The period of time between loss of the supervised main burner flame and the action to shut off the gas supply. Heat Delay-To-an-Off The period of time between the loss of a call for heat and the deactivation of the blower motor at Heat speed. Heat Delay-To-an-On The period of time between proof of the supervised main burner flame and the activation of the blower motor at Heat speed. Igniter Warm-up Time The length of time allowed for the igniter to heat up prior to the initiation of gas flow. Ignition Activation Period (IAP) The period of time between energizing the main gas valve and deactivation of the ignition means prior to the end of TI. Inter-purge The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion between the failed trial for ignition and the retry period. Post-purge Time The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion at the end of a furnace burner operating cycle. Post-purge begins at the loss of flame sense. Pre-purge Time The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion at the beginning of a furnace operating cycle prior to initiating ignition. Recycles The additional attempts within the same thermostat cycle for ignition after loss of the supervised ignition source or the supervised main burner flame. Retries The additional attempts within the same thermostat cycle for ignition when the supervised main burner flame is not proven within the first trial for ignition period. Trial for Ignition Period (TI) The period of time between initiation of gas flow and the action to shut off the gas flow in the event of failure to establish proof of the supervised ignition source or the supervised main burner flame

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION 50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS INSTALLER MUST READ PAGE 3 CONTAINS WIRING HARNESS AND BLOWER CONNECTION INSTRUCTIONS FOR ALL APPLICATIONS

More information

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS 50M56-743 Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD

More information

50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS 50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS INSTALLER MUST READ PAGE 3 CONTAINS WIRING HARNESS AND BLOWER CONNECTION INSTRUCTIONS FOR ALL APPLICATIONS

More information

50A Integrated Furnace Control

50A Integrated Furnace Control 50A56-956 Integrated Furnace Control INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY

More information

50A Integrated Furnace Control

50A Integrated Furnace Control Goodman White-Rodgers 0130F00005 PCBBF110 PCBBF123 50A55-743 0130F00005S PCBBF110S PCBBF123S 50A55-289 B1809926 PCBBF112 50T55-289 B1809926S PCBBF112S 50A55-743 Integrated Furnace Control INSTALLATION

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 50A66-743 Integrated Furnace Control Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 031-01284-000/50A55-241 Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 50A55-286 Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 50A65-843 Universal Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 21M51U-843 Universal Integrated Two-Stage 120Volt Hot Surface Ignition Control Kit INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 50A55-474 & 50A55-571 Integrated Furnace Controls INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE

More information

21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS

21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS 21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE

More information

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS 50T35-743 Integrated Furnace Control INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 50V64-743 Integrated Furnace Control for Furnaces with Variable Fan Speed INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

50M TYPICAL WIRING DIAGRAM 24 VAC CLASS II TRANSFORMER 24 VAC 50M COOL PARK HEAT LO HEAT HI LINE XFMR EAC HUM

50M TYPICAL WIRING DIAGRAM 24 VAC CLASS II TRANSFORMER 24 VAC 50M COOL PARK HEAT LO HEAT HI LINE XFMR EAC HUM 21M51U-843 WIIN AND CONFIUATION INTEATED HOT (LINE) TYPICAL WIIN DIAAM 120 VAC NEUTAL (LINE) 24 VAC CLASS II TANSFOME TH 24 VAC T COOL PAK HEAT LO HEAT HI LINE XFM EAC HUM CICU- LATO BLOWE HUMIDIFIE (OPTIONAL)

More information

A-1106 ACCESSORY KIT INSTALLATION INSTRUCTIONS IGNITION CONTROL P/N S , S , S

A-1106 ACCESSORY KIT INSTALLATION INSTRUCTIONS IGNITION CONTROL P/N S , S , S ACCESSORY KIT INSTALLATI INSTRUCTIS IGNITI CTROL P/N S1-33101972200, S1-37326083000, S1-43101972100 FOR USE WITH THE FOLLOWING FURNACE MODELS: GY9, GF9, GM9, P1UK, PAKU, P2MP, P2MPV, P9MP, P2UR, PBLU,

More information

WARNING CAUTION 50T INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS. Integrated Furnace Control

WARNING CAUTION 50T INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS. Integrated Furnace Control 50T35-743 Integrated Furnace Control INSTALLATION INSTUCTIONS FAILUE TO EAD AND FOLLO ALL INSTUCTIONS CAEFULLY BEFOE INSTALLIN O OPEATIN THIS CONTOL COULD CAUSE PESONAL INJUY AND/O POPETY DAMAE. DESCIPTION

More information

WARNING WARNING TROUBLESHOOTING GUIDE INTEGRATED FURNACE CONTROL MODULE

WARNING WARNING TROUBLESHOOTING GUIDE INTEGRATED FURNACE CONTROL MODULE TROUBLESHOOTING INTEGRATED FURNACE Failure to read and follow all instructions carefully before installing or operating this control, could cause personal injury and/ or property damage. 50A55 INTEGRATED

More information

ADSH8. Two-Stage Convertible. Heating Input: 40, ,000 BTU/h

ADSH8. Two-Stage Convertible. Heating Input: 40, ,000 BTU/h ADSH8 Heating Input: 40,000 100,000 BTU/h Two-Stage Convertible Multi-Speed Gas Furnace 80% AFUE Standard Features Two-stage convertible gas valve automatically adjusts to high or low stage Durable SureStart

More information

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-703 120 VAC Microprocessor-Based Intermittent Pilot Ignition Control F-35-703 July 2016 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

40 Residential Gas Furnace Operation

40 Residential Gas Furnace Operation 40 Residential Gas Furnace Operation Model Evolution/Nomenclature Heating Sequence of Operation Schematics Ignition Systems Service/Troubleshooting American Standard Inc. 999 Preface Air Conditioning and

More information

Emerson Blue Easy Set 1H/1C

Emerson Blue Easy Set 1H/1C Emerson Blue Easy Set 1H/1C Model: 1F86EZ-0251 Non-Programmable Thermostat with 3 Temperature Pre-Sets Home, Sleep and Away Installation Instructions and User Guide Message to Homeowner Congratulations

More information

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION Your new White-Rodgers Digital Thermostat

More information

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS SERIES 35-65 24 VAC Microprocessor-Based Hot Surface Ignition Control F-35-65 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings* 120/240

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA) R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

DM80HE. Two-Stage Convertible Multi-Speed ECM Gas Furnace 80% AFUE. Heating Input: 60, ,000 BTU/h

DM80HE. Two-Stage Convertible Multi-Speed ECM Gas Furnace 80% AFUE. Heating Input: 60, ,000 BTU/h Two-Stage Convertible Multi-Speed ECM Gas Furnace 80% AFUE Heating Input: 60,000 100,000 BTU/h Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 4 Airflow Data... 5 Wiring Diagram...

More information

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS SERIES 35-63J INSTALLATION INSTRUCTIONS FOR REPLACING JOHNSON CONTROLS G77X AND OTHER MODELS WITH FENWAL SERIES 35-63J IP IGNITION CONTROL APPLICATIONS The Fenwal 35-63J series Intermittent Pilot Ignition

More information

Hot Surface Ignition (HSI) System Booklet

Hot Surface Ignition (HSI) System Booklet Hot Surface Ignition (HSI) System Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 E-mail: techsupport@amdry.com 010298MFM/abe

More information

BGH Series Hot Surface Ignition Control

BGH Series Hot Surface Ignition Control Installation Instructions BGH Series Issue Date April 14, 2011 BGH Series Hot Surface Ignition Control Application The BASO Gas Products BGH Series Hot Surface Ignition (HSI) control is microprocessor

More information

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT CONTENTS Installation Instructions for Heating & Air Conditioning 1F79 n-programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-61 24 VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay F-35-61 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge

More information

24 VAC Direct Spark Gas Ignition

24 VAC Direct Spark Gas Ignition Installation Instructions Issue Date March 3, 2017 Quick Reference Guide The Direct Spark Gas Ignition control module is designed for direct burner ignition and supervision. It can be used in new applications

More information

Interrupted Ignition Series Oil Primary Control

Interrupted Ignition Series Oil Primary Control Interrupted Ignition Series Oil Primary Control Application Guide & Installation Instruction for ICM1511*, ICM1512*, ICM151*, ICM1514* For more information on our complete range of American-made products

More information

80% AFUE. Multi-Position, Dual$aver. Heating Input: 70, ,000 BTU/h

80% AFUE. Multi-Position, Dual$aver. Heating Input: 70, ,000 BTU/h Series 80% AFUE Multi-Position, Dual$aver Multi-Speed Gas Furnace Heating Input: 70,000 115,000 BTU/h Standard Features Dual-diameter tubular heat exchanger Two-stage gas valve that allows installer to

More information

OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series

OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com Owner s Manual MGD-B SERIES GAS FURNACE

More information

Quick Reference Guide. Application. Gas Furnaces Boilers Water Heaters Commercial Cooking. Features

Quick Reference Guide. Application. Gas Furnaces Boilers Water Heaters Commercial Cooking. Features Installation Instructions E14QRG Issue Date June 28, 2018 Quick Reference Guide The Direct Spark Gas Ignition control module is designed for direct burner ignition and supervision. It can be used in new

More information

24 VAC Intermittent Pilot Gas Ignition Control

24 VAC Intermittent Pilot Gas Ignition Control C610U Universal 24 VAC Intermittent Pilot Gas Ignition Control Issue Date: 08/24/2016 Quick Reference Guide The C610U Universal Intermittent Pilot Gas Ignition Control module replaces many popular flame

More information

Installation and Operating Instructions

Installation and Operating Instructions Installation and Operating Instructions Furnace Control Tester KGACT0201 Table 1 Kit Contents DESCRIPTION PART NO. QUANTITY Furnace Control Tester KGACT0201 1 Adapter Harness 320742-301 1 Installation

More information

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL Figure 1 Series 9 Intermittent Pilot Ignition Control Application The Series 9 Intermittent Pilot Ignition Control is a microprocessor

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 1F83-51 Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL

More information

1F Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

1F Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS 1F83-261 Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1-316-832-4357

More information

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0204 L2 Revised 11 2006 G60UH(X) G60UH(X) SERIES UNITS G60UH(X) series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! F145-1328/F145-1378 Indoor /Outdoor INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS

More information

Technical Manual MAY 2008 Edition

Technical Manual MAY 2008 Edition SPECIFICATION - GMP SERIES MULTI POSITION INDUCED DRAFT GAS FURNACE EARLY MODELS WITH HOT SURFACE IGNITION AND LATER MODELS WITH DIRECT SPARK IGNITION A.G.A. Approval No. 5113 Technical Manual MAY 2008

More information

TECHNICAL MANUAL. GMH8 39" 80% Gas Furnace 80% AFUE, 2-Stage (Convertible), Multi-Speed, Upflow/Horizontal

TECHNICAL MANUAL. GMH8 39 80% Gas Furnace 80% AFUE, 2-Stage (Convertible), Multi-Speed, Upflow/Horizontal TECHNICAL MANUAL AL GMH8 39" 80% Gas Furnace 80% AFUE, 2-Stage (Convertible), Multi-Speed, Upflow/Horizontal Refer to Service Manual RS660004 for installation, operation, and troubleshooting information.

More information

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS Note: This manual may also be used for 6536-871 series heat pumps if the 6535-3209 Replacement

More information

G60DFV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G60DFV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0211 L3 Revised 09 2006 G60DFV(X) G60DFV(X) SERIES UNITS G60DFV series units are mid efficiency gas furnaces used for downflow applications only, manufactured with Lennox Duralok

More information

59MN7A Series 100 TROUBLESHOOTING GUIDE

59MN7A Series 100 TROUBLESHOOTING GUIDE Variable Speed, Modulating Electronic Condensing Four-Way Multipoise Gas Furnace 59MN7A Series 100 TROUBLESHOOTING GUIDE INDEX PAGE Safety Considerations... 1 Instructions... 1 Example... 2 General...

More information

SV9520H SmartValve System Control Line Voltage Polarity Sense Models

SV9520H SmartValve System Control Line Voltage Polarity Sense Models SV90H SmartValve System Control Line Voltage Polarity Sense Models INSTALLATION INSTRUCTIONS APPLICATION The SV90H SmartValve System Controls combines gas flow control and electronic direct main burner

More information

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 1029 L7 SLP98UHV SLP98UHV SERIES UNITS SLP98UHV series units are high efficiency upflow, horizontal right and left) gas furnaces equipped with variable capacity gas valve, variable

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! HITE-RODERS 1F97-51 7-Day Electronic Digital Thermostat INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLO ALL INSTRUCTIONS CAREFULL BEFORE INSTALLIN OR

More information

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT CONTENTS Installation Instructions for Heating & Air Conditioning 1F72 5/2 Day Programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

IF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning

IF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning CONTENTS Installation Instructions for Heating & Air Conditioning IF79 n- Programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

G60UHV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G60UHV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0124 L11 Revised 11 2006 G60UHV(X) G60UHV(X) SERIES UNITS G60UHV(X) series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 1F82-51 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

1F98EZ-1421, Easy Install

1F98EZ-1421, Easy Install 1F98EZ-1421, -1441 Easy Install For up to 4 Stages and 2 Stages Cool INSTALLATION INSTRUCTIONS APPLICATIONS Configuration Options Single Stage Multi Stage Pump Pump with Dual Fuel FAILURE TO READ AND FOLLOW

More information

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL

More information

GAS UNITS KITS AND ACCESSORIES 505,172M 08/06

GAS UNITS KITS AND ACCESSORIES 505,172M 08/06 2006 Lennox Industries Inc. Dallas, Texas, USA GAS UNITS KITS AND ACCESSORIES 505,172M 08/06 Litho U.S.A. IGNITION CONTROL REPLACEMENT KIT INSTALLATION INSTRUCTIONS FOR IGNITION CONTROL CONVERSION KIT

More information

TECHNICAL MANUAL. AMS8 33-3/8" Gas Furnace Units 80% AFUE, Single Stage, Multi-Speed, Upflow Horizontal

TECHNICAL MANUAL. AMS8 33-3/8 Gas Furnace Units 80% AFUE, Single Stage, Multi-Speed, Upflow Horizontal TECHNICAL MANUAL AL AMS8 33-3/8" Gas Furnace Units 80% AFUE, Single Stage, Multi-Speed, Upflow Horizontal Refer to Service Manual RS6612006 for troubleshooting information. Refer to the appropriate Parts

More information

WHITE-RODGERS COMFORT-SET 90 SERIES

WHITE-RODGERS COMFORT-SET 90 SERIES INSTALLATI DESCRIPTI WHITE-RODGERS COMFORT-SET 90 SERIES MULTI-STAGE/HEAT PUMP INSTALLATI/CFIGURATI This White-Rodgers Automatic Setback Digital Thermostat uses microcomputer technology to provide precise

More information

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

ELECTRONIC FLAME SUPERVISION MULTI-BURNER MULTI-BURNER MODEL: SENS-A-FLAME II Revision: 0 7112 DESCRIPTION Model 7112 Sens-A-Flame II is a second generation solid-state programmable combustion safeguard for supervising multiple burner ovens, furnaces,

More information

Model Universal Oil Primary Control

Model Universal Oil Primary Control Model 70200 Universal Oil Primary Control Installation and Operating Instructions For Use By Qualified Service Technicians Only Universal Replacement for Carlin, Beckett, Honeywell and ICM Controls On-Board

More information

Model 60200FR Gas Primary Control Data Sheet

Model 60200FR Gas Primary Control Data Sheet Programmable, Microprocessor Based Gas Burner Primary Controls On-Board LCD Screen Easy to Understand Icons for Inputs and Outputs Displays micro-amp Flame reading Display operational information Fault

More information

Operator: SaVe these instructions forfuture use

Operator: SaVe these instructions forfuture use Whiter Rodgers 1F86-344 Non-Programmable Electronic Digital Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: SaVe these instructions forfuture use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

GMSS96 / GCSS96 Single-Stage Multi-Speed Gas Furnace

GMSS96 / GCSS96 Single-Stage Multi-Speed Gas Furnace Heating Input: 40,000 120,000 BTU/h / Single-Stage Multi-Speed Gas Furnace up to 96% AFUE Standard Features Heavy-duty aluminized-steel tubular heat exchanger Stainless-steel secondary heat exchanger Single-stage

More information

TECHNICAL MANUAL. GMS8 33-3/8" Gas Furnace Units 80% AFUE, Single Stage, Multi-Speed, Upflow Horizontal

TECHNICAL MANUAL. GMS8 33-3/8 Gas Furnace Units 80% AFUE, Single Stage, Multi-Speed, Upflow Horizontal TECHNICAL MANUAL AL GMS8 33-3/8" Gas Furnace Units 80% AFUE, Single Stage, Multi-Speed, Upflow Horizontal Refer to Service Manual RS6612006 for troubleshooting information. Refer to the appropriate Parts

More information

*9MAC TROUBLESHOOTING GUIDE

*9MAC TROUBLESHOOTING GUIDE Variable Speed, Modulating Electronic Condensing Four-Way Multipoise Gas Furnace *9MAC TROUBLESHOOTING GUIDE INDEX PAGE Safety Considerations... 1 Instructions... 1 Example... 2 General... 2 Sequence of

More information

CSD-1 COMMERCIAL BOILER CONTROLS

CSD-1 COMMERCIAL BOILER CONTROLS SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS CSD- COMMERCIAL BOILER CONTROLS P/N 400043, Rev. A [/03] CSD- COMMERCIAL BOILER CONTROLS! WARNING Fire, explosion, asphyxiation and electrical shock

More information

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System. The Fireye EP260, EP270 (early spark termination), or EP265 (pilot stabilization) programmer modules are used with the FLAME-MONITOR Burner Management Control System (P/N E110). Several operational characteristics

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 1F81-51 Programmable Electronic Digital Multi-stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215) National Comfort Products 539 Dunksferry Road Bensalem, PA 19020 (215) 244-1400 1-800-523-7138 Fax: (215) 639-1674 14299575-10/29/2014 NOTE: These installation and maintenance instructions should be left

More information

Technical Information

Technical Information A I R COMMA ND GAS FURNACE Technical Information 40" 80% Gas Furnaces GUIC EA/EX Refer to Service Manual RS660000 Rev. 2 for installation, operation, and troubleshooting information. All safety information

More information

X341119P10 Gas Furnace Var. Speed Blower Var. Speed Inducer Two Stage Heat Direct Vent Models:

X341119P10 Gas Furnace Var. Speed Blower Var. Speed Inducer Two Stage Heat Direct Vent Models: Service Facts X349P0 Gas Furnace Var. Speed Blower Var. Speed Inducer Two Stage Heat Direct Vent Models: *UY060R9V3W *UY080R9V3W *UY00R9V4W *UY20R9V5W * First letter may be A or T *DY060R9V3W *DY080R9V3W

More information

No. Of Ignition Trials: No. Of Re-Ignition Attempts. Reset by interrupting power for 5.0 Seconds. Diagnostic Output. Re-Ignition Limit Exceeded

No. Of Ignition Trials: No. Of Re-Ignition Attempts. Reset by interrupting power for 5.0 Seconds. Diagnostic Output. Re-Ignition Limit Exceeded DS1-Q INSTALLATION INSTRUCTIONS General Description Model DS1-Q is used to replace and eliminate the factory installed slow responding glow-bar igniter, sensor and associated wiring in commercial laundry

More information

GMSS96 / GCSS96. Single-Stage, Multi-Speed Gas Furnace Up to 96% AFUE. Heating Input: 40, ,000 BTU/h

GMSS96 / GCSS96. Single-Stage, Multi-Speed Gas Furnace Up to 96% AFUE. Heating Input: 40, ,000 BTU/h / Heating Input: 40,000 120,000 BTU/h Single-Stage, Multi-Speed Gas Furnace Up to 96% AFUE Contents Nomenclature...2 Product Specifications...3 Dimensions...5 flow Specifications...7 Wiring Diagram...10

More information

Heat Pump Defrost Board Replacement Kit

Heat Pump Defrost Board Replacement Kit Bard Manufacturing Company, Inc. Bryan, Ohio 43506 8620-223 Heat Pump Defrost Board Replacement Kit KIT FEATURES This kit is made up of the current defrost control board 8201-129 and a new defrost sensor.

More information

PRODUCT SPECIFICATIONS 1 *UH2B080A942VA

PRODUCT SPECIFICATIONS 1 *UH2B080A942VA UH2P-SF-1B Gas Furnace Direct Vent Condensing Two Stage Heat Models: * - First letter may be A or T *UH2B060A936VA *UH2B080A942VA *UH2C100A948VA *UH2D120A960VA *DH2B060A936VA *DH2B080A942VA *DH2C100A948VA

More information

Troubleshooting Guide

Troubleshooting Guide MID -EFFICIENCY VARIABLE -SPEED TWO -STAGE INDUCED -COMBUSTION DELUXE, 4 -WAY MULTIPOISE GAS FURNACE SafetyConsiderations...1 Instructions...1 Example... 2 FurnaceModelNomenclature...2 General......3 SequenceofOperation...3

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and

More information

GMSS92 / GCSS92. Single-Stage, Multi-Speed Gas Furnace Up to 92% AFUE. Heating Input: 40, ,000 BTU/h

GMSS92 / GCSS92. Single-Stage, Multi-Speed Gas Furnace Up to 92% AFUE. Heating Input: 40, ,000 BTU/h / Single-Stage, Multi-Speed Gas Furnace Up to 92% AFUE Heating Input: 40,000 120,000 BTU/h Contents Nomenclature...2 Product Specifications...3 Dimensions...5 Airflow Specifications...7 Wiring Diagram...10

More information

Troubleshooting Guide

Troubleshooting Guide Troubleshooting Guide Deluxe -Stage Gas-Fired Induced-Combustion Furnaces With PSC or ICM Blower Mor INDEX PAGE Instructions... General...-3 Furnace Model Nomenclature... Example...3 Sequence of Operation...3-6

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2004-28 TSG-SOLO-9/04 Table of Contents INTRODUCTION Page 1 SERVICING TIPS AND INSTRUCTIONS Page 3 CONTROL MODULE DISPLAY -

More information

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev.

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev. 95M-200 Gas-Fired Direct Vent Modulating Hot Water Boiler Control Manual And Troubleshooting Guide P/N 24000604, Rev. C [04/09] WARNING! Revise boiler control parameters only if you fully understand the

More information

Commercial Touchscreen Thermostat

Commercial Touchscreen Thermostat 55,13M 1/27 Supersedes 12/25 Commercial Touchscreen Thermostat 25 Lennox Industries, Inc. Dallas, Texas, USA APPLICATION Page 1 INSTALLATION INSTRUCTIONS The Lennox Commercial Touchscreen Thermostat provides

More information

Q4100C Hot Surface Igniter

Q4100C Hot Surface Igniter Q4100C Hot Surface Igniter INSTALLATION INSTRUCTIONS APPLICATION Q4100C Hot Surface Igniters are designed to provide a robust field service replacement igniter in gas fired appliances with 120 VAC silicon

More information

GMSS96 / GCSS96. Single-Stage, Multi-Speed Gas Furnace Up to 96% AFUE. Heating Input: 40, ,000 BTU/h

GMSS96 / GCSS96. Single-Stage, Multi-Speed Gas Furnace Up to 96% AFUE. Heating Input: 40, ,000 BTU/h / Heating Input: 40,000 120,000 BTU/h Single-Stage, Multi-Speed Gas Furnace Up to 96% AFUE Contents Nomenclature...2 Product Specifications...3 Dimensions...5 flow Specifications...7 Wiring Diagram...10

More information

25M01A-100 to 25M01A-199 HSI Single Stage Combination Gas Valve

25M01A-100 to 25M01A-199 HSI Single Stage Combination Gas Valve 25M01A-100 to 25M01A-199 HSI Single Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE

More information

2017 OUTDOOR CONTROL SYSTEM WEATHER BEATER ELECTRONIC CONTROL SYSTEM

2017 OUTDOOR CONTROL SYSTEM WEATHER BEATER ELECTRONIC CONTROL SYSTEM 2017 OUTDOOR CONTROL SYSTEM WEATHER BEATER ELECTRONIC CONTROL SYSTEM GRAND CANYON 3515 East Atlanta Ave. Phoenix, AZ 85040 1-602-344-4217 The Weather Beater Electronic Control System is the ultimate control

More information

Installation Instructions

Installation Instructions Installation Instructions Twinning Kit for HSI Single-and -Stage Upflow Condensing and Non-Condensing Gas Furnaces KGATW050HSI NOTE: Read the entire instruction manual before starting the installation.

More information

*DD2B060A9V3VA *DD2B080A9V3VA *DD2C100A9V5VA *DD2D120A9V5VA

*DD2B060A9V3VA *DD2B080A9V3VA *DD2C100A9V5VA *DD2D120A9V5VA UD2-9V-SF-C Gas Furnace Speed 2 Stage Heat Models: * - First letter may be A or T *UD2B060A9V3VB *UD2B080A9V3VB *UD2C080A9V4VB *UD2C080B9V4VB *UD2B00A9V3VB *UD2C00A9V5VB *UD2C00B9V5VB *UD2DA9V5VB *UD2DB9V5VB

More information

WARNING Important Safety Information

WARNING Important Safety Information 1 Specifications Premier Series Non-Programmable Thermostats MODEL 3000 MODEL 3200 1 2 3 4 5 Specifications Installation Testing Your New Thermostat Programming User Settings Temperature Adjustment WARNING

More information

SV9560/SV9570 SmartValve Water Heater Controls

SV9560/SV9570 SmartValve Water Heater Controls SV9560/SV9570 SmartValve Water Heater Controls INSTALLATION INSTRUCTIONS APPLICATION The SV9560/SV9570; SmartValve Water Heater Control System is a single unit which combines direct ignition sequencing,

More information

I/O ZONE 560/583 AND OPERATION MANUAL

I/O ZONE 560/583 AND OPERATION MANUAL UPM I I/O ZONE 560/583 INSTALLATION AND OPERATION MANUAL 1 UNIT PROTECTION MODULE HARDWARE OPERATION IMPORTANT: This manual is for UPM board part numbers 8733 800 259. See controller label as shown in

More information

GMSS92 / GCSS92. Single-Stage, Multi-Speed Gas Furnace Up to 92% AFUE. Heating Input: 40, ,000 BTU/h

GMSS92 / GCSS92. Single-Stage, Multi-Speed Gas Furnace Up to 92% AFUE. Heating Input: 40, ,000 BTU/h / Heating Input: 40,000 120,000 BTU/h Single-Stage, Multi-Speed Gas Furnace Up to 92% AFUE Contents Nomenclature...2 Product Specifications...3 Dimensions...5 flow Specifications...7 Wiring Diagram...10

More information

TECHNICAL SUPPORT: SERVICE BULLETIN #4 (v ) AB2017 HOT SURFACE IGNITION MODULE OVERVIEW

TECHNICAL SUPPORT: SERVICE BULLETIN #4 (v ) AB2017 HOT SURFACE IGNITION MODULE OVERVIEW TECHNICAL SUPPORT: 1-800-403-3279 SERVICE BULLETIN #4 (v 1.80405) AB2017 HOT SURFACE IGNITION MODULE OVERVIEW WARNING Installation of this ignition control module may only be performed by a qualified and

More information

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION M-4000 JANUARY 29, 200 FIREYE M4RT1 FLAME SAFEGUARD CONTROLS WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government

More information

Upflow/ Horizontal Left/Right, Downflow Single and 2 Stage Non-Condensing Gas Fired Furnace

Upflow/ Horizontal Left/Right, Downflow Single and 2 Stage Non-Condensing Gas Fired Furnace Product Data Upflow/ Horizontal Left/Right, Single and Stage Non-Condensing Gas Fired Furnace Upflow,, Horizontal Right/Left Single Stage S8XA06MPSAA S8XA00MPSAA S8XB00MPSAA S8XB060MPSAA S8XB060MPSAA S8XB080MPSAA

More information

COMMERCIAL GAS WATER HEATERS

COMMERCIAL GAS WATER HEATERS Service Handbook COMMERCIAL GAS WATER HEATERS P.O. Box 1597 Johnson City, TN 37605 MODELS (A)BCG385T500-8N & (A)BCG38T500-8P SERIES 120/121 INSTALLATION CONSIDERATIONS - PRE SERVICE CHECKS - WATER HEATER

More information

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0204 L2 Revised 09 2006 G60UH(X) G60UH(X) SERIES UNITS G60UH(X) series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with

More information