1 TXV Coils EBD, EBA These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system to operate at full capacity. Poorly designed systems will not give satisfactory cooling or economy. They may even shorten the service life of the compressor in the outdoor unit. DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product. DANGER Immediate hazards which will result in severe personal injury or death. WARNING Hazards or unsafe practices which could result in severe personal injury or death. CAUTION Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE Used to highlight suggestions which will result in enhanced installation, reliability, or operation. Safety Labeling and Signal Words Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: WARNING! WARNING The signal word CAUTION is used throughout this manual in the following manner:! CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures on product labels. TABLE OF CONTENTS Installation Condensate Drain Waste Line Connection Refrigerant Line Connections Refrigerant Metering Device Check and Adjust Airflow Start Up Procedure ELECTRICAL SHOCK HAZARD Failure to turn off electric power could result in personal injury or death. Before installing or servicing system, turn off main power to the system. There may be more than one disconnect switch, including accessory heater(s) September 2005

2 INSTALLATION EBA and EBD Coils are designed for Upflow application only (refer to Figures 3 & 4). Using these coils in other configurations may result is excessive water blow off. EBA Loose Coils are shipped with a metal collar plate approximately the same size as the drain pan. The collar plate must be installed between the drain pan and the furnace or air handler cabinet to prevent condensation inside the cabinet. Position the collar plate as shown in Figure 1, with the flanges pointing down, towards the furnace or air handler cabinet. Size the plenum or fabricate spacers to seal against the outside of the collar and prevent air bypass. Figure 1 Collar Plate under drain pan Flanges down EBA Collar Plate EBD Cased Coils are designed to fit furnaces and air handlers of the same width with no modifications. When an EBD Cased Coil is applied to a narrower or wider furnace or air handler, a field fabricated adapter is required. Refer to Figure 2 for examples of field fabricated adapters. PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage. When a narrower coil is installed on a wider gas furnace (upflow, downflow, or horizontal), a field fabricated adapter must create 3 minimum space between furnace and coil to allow airflow to distribute evenly. When a loose coil is installed on any GAS furnace, the drain pan must be at least 2 away from the furnace heat exchanger to avoid drain pan damage. When a loose coil is installed on any OIL furnace, the drain pan must be at least 5 away from the furnace heat exchanger to avoid drain pan damage. PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage A field fabricated auxiliary drain pan, with a separate drain is REQUIRED for all installations over a finished living space or in any area that may be damaged by overflow from a restricted main drain pan. In some localities, local codes require an auxiliary drain pan for ANY horizontal installation. Figure 2 Adapters for Coils Wider or Narrower than Furnace or Air Handler 3 MIN. NARROWER COIL ADAPTER (FIELD SUPPLIED) WIDER COIL WIDER FURNACE ADAPTER (2) (FIELD SUPPLIED) NARROWER FURNACE

3 NOTE: When coil is used in a heat pump application with electric heat, coil must be installed upstream of the electric heater (refer to Figure 3). This prevents electric heat from driving up refrigeration system pressure during heating cycle. NOTE: When coil is installed to a gas or oil furnace, coil must be installed downstream of the furnace heat exchanger (refer to Figure 4). This reduces condensate formation in the furnace heat exchanger during the cooling cycle. Figure 3 Heat Pump Coil Position Relative to Electric Heat Figure 4 Coil Position Relative to Gas or Oil Furnace Heat Exchanger ELECTRIC HEATER A COIL BLOWER AIR FLOW A COIL FURNACE HEAT EXCHANGER AIR FLOW BLOWER NOTE: When coil is installed with a Heat Pump in conjunction with a fossil fuel heating system, a Fossil Fuel Kit must be used. Refer to Product Specification literature for kit part number. CONDENSATE DRAIN Coil is provided with two NPT condensate drain connections. The connection with the larger internal opening is the primary drain, and the connection with the smaller internal opening is the secondary (overflow) drain. Condensate drain lines should be installed in a manner that does not obstruct access to the filter. Use PVC fittings on the plastic condensate pan. Finger tighten plus 1½ turns. Do not over tighten. Use pipe dope. If coil is located in or above a living space where damage may result from condensate overflow, a separate drain must be provided from secondary (overflow) drain connection. Run this drain to a place in compliance with local installation codes where it will be noticed when unit is operational. Condensate flowing from secondary (overflow) drain indicates a plugged primary drain unit requires service or water damage will occur. 1. Connect drain lines to the appropriate drain connections. Drain lines should not be smaller than the drain connections ( ). 2. NOTE: Traps must be used when the coil is installed on the return air side of the system. When coil is installed on the supply side (outlet air) it is not necessary to install traps and better drainage is usually achieved without traps. Install properly sized condensate traps in the drain lines as close to the coil as possible. Install drain lines below the bottom of the drain pan and pitch the NOTE: On furnace installations where the coil is located in an unconditioned space, nuisance sweating may occur in the area around the cabinet to supply duct joint. Wrap the joint between the cabinet and the supply duct with a 6 wide piece of insulation with vapor barrier. drain lines down from the coil at least ¼ inch per foot of run. Horizontal runs over 15 feet long must also have an anti siphon air vent (stand pipe), installed ahead of the horizontal run. An extremely long horizontal run may require an oversized drain line to eliminate air trapping. Refer to Figure 5 for minimum trap dimensions. 3. Route to the outside or to a floor drain. Check local codes before connecting to a waste (sewer) line. 4. Prime all traps, test for leaks, and insulate drain lines where sweating could cause water damage. 5. If a gravity drain cannot be used, install a condensate pump. Install the pump as close to the indoor section as possible. Figure 5 Recommended Condensate Trap UNIT 2 MIN 2 MIN

4 WASTE LINE CONNECTION If the condensate line is to be connected to a waste (sewer) line, an open trap must be installed ahead of the waste line to prevent escape of sewer gases (refer to Figure 6). EXPLOSION HAZARD Failure to provide trap could result in personal injury, death, or property damage. Provide trap with air gap in drain line when connecting to waste (sewer) line. Refer to Figure 6. Figure 6 Condensate Line Trap Condensate Drain to Waste Line Air Gap Above Liquid Level Sewer Line REFRIGERANT LINE CONNECTIONS PERSONAL INJURY HAZARD Failure to relieve pressure in the coil could result in personal injury. Wear eye protection. Coil is factory charged with 15 psi nitrogen. Pierce the centers of both rubber tubing plugs to relieve pressure before removing plugs. NOTE: Factory nitrogen charge may escape past rubber plugs during storage. This does not indicate a leaking coil nor warrant return of the coil. Size and install refrigerant lines according to information provided with outdoor unit. Coil connection tube sizes are shown in Figure 7. Route refrigerant lines to the coil in a manner that will not obstruct service access to the unit or removal of the filter. 1. Remove cabinet door. Remove tubing plate with rubber grommets and slide plate with grommets onto the refrigerant lines (field line set), away from braze joints. 2. Remove rubber plugs from coil stubs using a pulling and twisting motion. Hold coil stubs steady to avoid bending or distorting. 3. Wrap TXV and nearby tubing with a heat sinking material such as a wet cloth. 4. Fit refrigerant lines into coil stubs. Wrap a heat sinking material such as a wet cloth behind braze joints. NOTE: See outdoor unit Installation Instructions regarding requirements for installation of a filter drier in the liquid line close to the indoor coil. 5. Braze using a Sil Fos or Phos copper alloy. 6. After brazing, allow joints to cool. Slide tubing plate with rubber grommets over joints. Position tubing at center of each grommet to ensure an air seal around the tube (refer to Figure 8). Figure 7 Coil Connection Tube Size (inch) Model Size Liquid Suction 18 (1 ton) 24 (2 ton) 30 (2 ton) 36 (3 ton) 42 (4 ton) 48 (4 ton) 60 (5 ton) Figure 8 RUBBER GROMMETS TUBING PLATE Refrigerant Lines

5 Strainer screen is factory installed inside the liquid tube stub (TXV tube). Leave the strainer screen in place during installation (refer to Figure 9). Figure 9 Strainer Screen Strainer Screen PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage. Braze with Sil Fos or Phos copper alloy on copper to copper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV. TXV REFRIGERANT METERING DEVICE EBD and EBA coils have a factory installed hard shut off TXV designed only for use with R 22 refrigerant. Use only with outdoor units designed for R 22. TXV is factory set and not field adjustable. CHECK AND ADJUST AIR FLOW ELECTRICAL SHOCK HAZARD Failure to shut of electric power could result in personal injury or death. Before adjusting blower speed, shut off electric power to the furnace or blower module. It is important that the correct amount of air (CFM) flows through the coil. The installer must determine the required CFM based on the characteristics of the specific system (such as system size, ducting, components, and accessories). In general, 400 CFM per ton is the nominal required value, with a range of CFM per ton. Check Static Pressure Drop and CFM Across Coil The amount of air (CFM) is related to a pressure drop. To determine the CFM, measure the pressure drop using an inclined manometer (sometimes called draft gauge or air flow gauge). 1. The coil should be dry and clean. The air filter must be clean and in place. All registers open. DO NOT run the outdoor unit when checking air flow. 2. Run the blower on cooling speed. PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage. This Coil has a hard shut off TXV metering device. A compressor Hard Start Kit is required in all applications where the matching outdoor unit has a single phase reciprocating compressor. 3. Using the manometer (draft gauge or flow gauge), measure the static pressure drop across the dry coil and compare it to the numbers in Figure Find the corresponding CFM in Figure 10. Adjusting Air Flow If CFM is too low, increase the blower speed and measure the static pressure drop again. Determine CFM from Figure 10. If CFM is too high, reduce the blower speed and measure the static pressure drop again. Determine CFM from Figure 10. NOTE: Change blower speed as shown in the instructions for the furnace or air handler. NOTE: It may not be possible to obtain a gauge reading exactly the same as shown in Figure 10. This is due to variations in duct systems and blower speeds. If the motor is at the highest speed and the CFM is still not high enough, replace the blower and/or motor with a larger size. If the unit has an adjustable belt driven blower, use an ammeter to check the motor current draw. If the current draw is higher than the motor name plate amps, replace the motor with one of greater horsepower

6 Figure 10 Coil Size 18B 1½ tons 24B 2 tons 24F 2 tons 30B 2½ tons 30F 2½ tons 36B 3 tons 36F 3 tons 36J 3 tons CFM and Pressure Drop Static Pressure Drop Across Coil Static Pressure Drop Across Coil CFM CFM (Inches Water Column) Across Coil (Inches Water Column) Across Coil Dry Wet Size Coil Dry Wet J ½ tons L ½ tons F tons J tons L tons J tons L tons START UP PROCEDURE Refer to outdoor unit Installation Instructions for refrigeration system start up instructions and refrigerant charging method details

INSTALLATION INSTRUCTIONS TXV Coils EBU, EBA

INSTALLATION INSTRUCTIONS TXV Coils EBU, EBA TXV s EBU, EBA These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system to operate

More information

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA TXV Coils EDM, EDD, EDA These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system to

More information

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

EL SERIES INSTALLATION INSTRUCTIONS

EL SERIES INSTALLATION INSTRUCTIONS EL SERIES INSTALLATION INSTRUCTIONS Restrictor Orifice Coils These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Installation Instructions

Installation Instructions Evaporator Coil A Coil --- Cased Multipoise NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. Installation NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION... 2 Inspect Equipment... 2 Select

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

Installation Instructions

Installation Instructions CNPHP Cased N Coils Horizontal Heating --- Cooling NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

Installation Instructions

Installation Instructions CNPHP Cased N s Horizontal Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FCP2400D FCP3000D FCP3600D FCP4200D FCP4800D FCP6000D FCP2400C FCX2400C FCP3000C FCP3600C FCX3600C FCP4200C FCP4800C FCX4800C FCP6000C FCX6000C Require AMF001NHA Accessory No

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C7BA Series Split System Indoor Cased Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

Installation Instructions

Installation Instructions Installation Instructions Cased Horizontal Furnace Coil CK3B A96318 Fig. 1 Model CK3B Furnace Coil NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper

More information

C7 Series Split System Uncased Indoor Coils

C7 Series Split System Uncased Indoor Coils Installation Instructions C7 Series Split System Uncased Indoor Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

Installation Instruction

Installation Instruction Installation Instruction Upflow Downflow Heating Cooling CC5A Uncased Coil CD5A Cased Coil SUPPLY RETURN EVAPORATOR COIL DOWNFLOW UPFLOW SUPPLY Fig. 1 Typical Installation of CD5A Cased Coil A96244 NOTE:

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Models FCV3600A FCV4800A FCV6000A Require AMF001NHA Accessory No Heat Kit Contents Use ONL factory listed electric heaters. General Information / Installation... 2 Upflow Installations...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C8DA Series Split System Uncased Indoor Coils - Downturn IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Models EBP EBX EBXX(R -410A) CAUTION Use ONLY factory listed electric heaters. Safety Labeling and Signal Words Danger, Warning and Caution The signal words DANGER, WARNING and

More information

Installation Instructions

Installation Instructions Split System Indoor Coils Installation Instructions! CAUTION: Read the Installation Instructions supplied with furnace/air handler and observe all safety requirements outlined in instructions and/or furnace/air

More information

Fig. 1--Typical Coil Installation

Fig. 1--Typical Coil Installation Installation Instructions For Cased Coils Upflow-Downflow Heating-Cooling CK5A,CK5B CK5P SUPPLY _RETURN EVAPORATOR_ COIL_ -'_41 DOWNFLOW FURNACE UPFLOW FURNACE / / _SUPPLY A_2_ Fig. 1--Typical Coil Installation

More information

Installation Instructions

Installation Instructions Installation Instructions For Cased Coils Upflow-Downflow Heating-Cooling CK5A CK5B SUPPLY RETURN EVAPORATOR COIL DOWNFLOW UPFLOW SUPPLY Fig. 1 Typical Coil Installation NOTE: Read the entire instruction

More information

Installation Instructions

Installation Instructions Installation Instructions For Cased and Uncased Coils Upflow-Downflow Heating-Cooling CK5A, CK5B Cased CJ5A Uncased SUPPLY RETURN EVAPORATOR COIL DOWNFLOW UPFLOW SUPPLY Fig. 1 Typical Coil Installation

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Models MB08B1500A2 MB12F1900A2 MB16J2200A2 MB20N2600A2 Contents 115 Volt General Information / Installation... 2 Installations... 3 Horizontal Installations... 3 Ductwork Connections...

More information

Installation Instructions

Installation Instructions Split System Indoor Coils Installation Instructions CAUTION: Read the Installation Instructions supplied with furnace/air handler and observe all safety requirements outlined in instructions and/or furnace/air

More information

Installation Instructions

Installation Instructions Split System Indoor Coils Installation Instructions CAUTION: Read the Installation Instructions supplied with furnace/air handler and observe all safety requirements outlined in instructions and/or furnace/air

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTUCTIONS Models EBV 2-5 Ton Use ONL factory listed electric heaters. Variable Speed Safety Labeling and Signal ords Danger, arning and Caution The signal words DANGE, ANING and CAU- TION

More information

_"RETURN. s ) EVAPORATOR COIL _ DOWNFLOW FURNACE UPFLOW I R I! / _[_SUPPLY

_RETURN. s ) EVAPORATOR COIL _ DOWNFLOW FURNACE UPFLOW I R I! / _[_SUPPLY Installation Instructions Upflow--Downflow CC5A Uncased Coil HeatingmCooling CD5A, CD5P Cased Coil CC5A CD5A/CD5P U "RETURN s ) EVAPORATOR COIL _ DOWNFLOW FURNACE UPFLOW I R I! / _L [_SUPPLY A_2_ Fig.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Series Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life,

More information

PL Series Premier Indoor Plenum Coils

PL Series Premier Indoor Plenum Coils IM-PLC-0667392-04 April 2016 PL Series Premier Indoor Plenum Coils Installation Instructions GENERAL ADP evaporator coils are designed for use with condensing units or heat pump units. These instructions

More information

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

Cased Aluminum Convertible Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC** 18- AH44D1-4 Cased Aluminum "Convertible" Coils 4TXCB003CC3HC 4TXCB004CC3HC 4TXCC005CC3HC 4TXCC006CC3HC 4TXCC007CC3HC 4TXCC008CC3HC 4TXCD009CC3HC 4TXCD010CC3HC May be "A" or "B" ALL phases of this installation

More information

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Cased Aluminum Coils Dedicated Upflow / Downflow Convertible to horizontal with separately purchased kit 18-AD32D1-3 Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit Upflow models: 4PXCAU24BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA

More information

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC ISO 9001 Certified Quality Management System SAFETY................................................

More information

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214 INSTALLATION MANUAL FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: MC FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: FC PARTIAL-CASED UPFLOW FOR COOLING/HEAT PUMP MODELS: PC ISO

More information

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: ORIFICE METERING DEVICE - G*FD024S14 - G*FD060S24 FACTORY INSTALLED TXV - G*FD024S14T - G*FD060S24T

More information

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA 18- AH39D1-4 Cased Aluminum "Convertible" Coils 2/4TXCA018BC3HCA 2/4TXCA024BC3HCA 2/4TXCB025BC3HCA 2/4TXCB031BC3HCA 4TXCB032BC3HCA 2/4TXCB036BC3HCA ALL phases of this installation must comply with NATIONAL,

More information

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY INSTALLATION MANUAL FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: MC FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: FC PARTIAL-CASED UPFLOW FOR COOLING/HEAT PUMP MODELS: PC ISO

More information

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: ORIFICE METERING DEVICE - G*FD024S14 - G*FD060S24 FACTORY INSTALLED TXV - G*FD024S14T - G*FD060S24T

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR COILS 505,264M (65484504) 05/08 Supersedes 10/07 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE

More information

INSTALLATION INSTRUCTIONS FOR RCQD COILS

INSTALLATION INSTRUCTIONS FOR RCQD COILS INSTALLATION INSTRUCTIONS FOR RCQD COILS efrigerant! RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE

More information

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH AVS Air Handlers Installation Manual for Classic SC, SD, and SDH AVS-NCL-IM (12/15) Copyright 2015 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4 Safety... 5 Equipment Manuals...

More information

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH AVS-ACL-IM (08/15) Copyright 2015 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FOR RCQD COILS WARNING ISO 9001:2008 92-100105-05-03 SUPERSEDES 92-100105-05-02 TABLE OF CONTENTS Model Number Explanation....................... 2 Unit Specifications..............................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FOR CASED/UNCASED COILS FOR GAS AND OIL FURNACES: (-)CFA: featuring R-407C/R-22 Refrigerant (-)CFL: featuring Industry Standard R-410A Refrigerant WARNING! These instructions

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,t_2007 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR 505,264M (65484504) 10/07 Supersedes 09/06 COILS n _putech blications ical Litho U.S.A. RETAIN THESE

More information

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF INSTALLATION MANUAL FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: CF FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CM ISO 9001 Certified Quality Management System GENERAL..............................................

More information

GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT)

GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT) GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT) MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should be retained and

More information

EarthLinked AVN Series Air Handlers Installation Manual

EarthLinked AVN Series Air Handlers Installation Manual EarthLinked AVN Series Air Handlers Installation Manual AVN-410-IM (03/14) Copyright 2014 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4 Safety... 5 Equipment Manuals... 5 Installation...

More information

UPFLOW/DOWNFLOW COILS

UPFLOW/DOWNFLOW COILS UPFLOW/DOWNFLOW COILS INSTALLATION INSTRUCTIONS 1. Important Safety Instructions The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is

More information

Installer s Guide Convertible Air Handlers 1-1/2 5 Ton

Installer s Guide Convertible Air Handlers 1-1/2 5 Ton Convertible Air Handlers 1-1/2 5 Ton 2/4TEC3F18B1000A 2/4TEC3F24B1000A 2/4TEC3F30B1000A 2/4TEC3F36B1000A WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING ALL phases of this installation must

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,1,_2008 Lennox Industries Inc, Dallas, Texas, USA INSTALLATION INSTRUCTIONS CR33 Series Coils EVAPORATOR COILS _ Technical 505,056M LL.L[ Publications 04108 Litho U.S.A. Supersedes 05/05 CR33 Series Coils...

More information

EarthLinked AFN Series Air Handlers Installation Manual

EarthLinked AFN Series Air Handlers Installation Manual EarthLinked AFN Series Air Handlers Installation Manual AFN-410-IM (07/15) Copyright 2015 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4 Safety... 5 Equipment Manuals... 5 Installation...

More information

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195) STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: 535.02-N2Y (795) 535.02-N2Y (1195) HEAT PUMP MODELS F1RP / F1FP018 thru 060 and COOLING MODELS F1RC / F1FC018 thru 036 035-13620

More information

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should

More information

RCTA Horizontal Evaporator Coil Installation Instructions

RCTA Horizontal Evaporator Coil Installation Instructions RCTA Horizontal Evaporator Coil Installation Instructions General: Rheem horizontal evaporator coils are designed for use with condensing units or heat pump units. These instructions are intended as a

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2012 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Merit CBX25UH Series Units THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE Improper installation, adjustment, alteration,

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Multi-Position Cased Coils for Cooling / Heat Pumps FEATURING R-410A OR R-22 REFRIGERANT RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION WARNING These instructions

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

AHG**-0B Series Hydronic Air Handling Units

AHG**-0B Series Hydronic Air Handling Units HEAT CONTROLLER, INC. Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual AHG**-0B Series Hydronic Air Handling Units HEAT CONTROLLER, INC. 1900 Wellworth Ave.,

More information

EVAPORATOR COILS Installation Manual CCG, VCG, MCG M Series Coils

EVAPORATOR COILS Installation Manual CCG, VCG, MCG M Series Coils EVAPORATOR COILS Installation Manual CCG, VCG, MCG M Series Coils www.marsdelivers.com INSTALLATION GUIDE CCG Series - Uncased Upflow/Downflow Coils VCG Series - Cased Upflow/Downflow Coils MCG Series

More information

INSTALLATION & OPERATING INSTRUCTIONS AAC & AEC SERIES CEILING MOUNT AIR HANDLER (ELECTRIC HEAT)

INSTALLATION & OPERATING INSTRUCTIONS AAC & AEC SERIES CEILING MOUNT AIR HANDLER (ELECTRIC HEAT) INSTALLATION & OPERATING INSTRUCTIONS AAC & AEC SERIES CEILING MOUNT AIR HANDLER (ELECTRIC HEAT) MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should be retained

More information

INSTALLER S GUIDE WARNING: TWE-IN-2A 18-GE02D1-3. Convertible 1 ½ - 5 Ton Air Handlers WARNING HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

INSTALLER S GUIDE WARNING: TWE-IN-2A 18-GE02D1-3. Convertible 1 ½ - 5 Ton Air Handlers WARNING HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING INSTALLER S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Model: TWE08P3,0B,FB TWE042P3,0B,FB TWE024P3,0B,FB TWE048P3,0B,FB TWE030P3,0B,FB TWE060P3,0B,FB TWE036P3,0B,FB

More information

INDOOR COILS INDOOR COILS. Airflow Capacities 400 to 2,250 CFM [188.8 to L/s] FORM NO. C REV. 14 Supersedes Form No. C Rev.

INDOOR COILS INDOOR COILS. Airflow Capacities 400 to 2,250 CFM [188.8 to L/s] FORM NO. C REV. 14 Supersedes Form No. C Rev. FORM NO. C11-201 REV. 14 Supersedes Form No. C11-201 Rev. 13 INDOOR COILS INDOOR COILS Airflow Capacities 400 to 2,250 CFM [188.8 to 1061.9 L/s] Rheem Indoor Coils are designed for use with Rheem outdoor

More information

ECTRIC INSTRUCTIONS FURNACE. Models / / EF08B1500A1, EF12F1900A EF16J2200A EF20N2600A. With AMF001NHA Accessory No Heat Kit

ECTRIC INSTRUCTIONS FURNACE. Models / / EF08B1500A1, EF12F1900A EF16J2200A EF20N2600A. With AMF001NHA Accessory No Heat Kit INSTA LATION INSTRUCTIONS Models EF08B500A, EF2F900A EF6J2200A EF20N2600A A2 / / s.// With AMF00NHA Accessory No Heat Kit Use ONLY factor' listed electric heaters. ECTRIC FURNACE Safety Labeling and Signal

More information

INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES GENERAL.............................................. 1 SAFETY................................................ 1 UNIT INSTALLATION.....................................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2011 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation

More information

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2 Service Literature Corp. 0527 L10 Revised May 2011 CB26UH and CBX26UH Series Table of Contents CB26UH CBX26UH Model Number Information................... 2 Specifications / Electrical Data................

More information

INSTALLATION INSTRUCTIONS Apartment Fan Coil

INSTALLATION INSTRUCTIONS Apartment Fan Coil Apartment Fan oil Product Family: FSA2X, FSA4X These instructions must be read and understood completely before attempting installation. DANE, WANIN, AUTION, and NOTE The signal words DANE, WANIN, AUTION,

More information

Evaporator Coil. Installation Instructions GENERAL

Evaporator Coil. Installation Instructions GENERAL IM-HAC-0966540-14 February 2018 Evaporator Coil Installation Instructions TABLE OF CONTENTS PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Condensate Drain... 5 Metering Device...

More information

R-410A. Installer s Guide WARNING: 18-GE04D2-5

R-410A. Installer s Guide WARNING: 18-GE04D2-5 18-GE04D2-5 Convertible Variable Speed Air Handlers 2-1/2 5 Ton for R-410A 4TEE3F31A; 4TEE3F37A; 4TEE3F40A; 4TEE3F49A; 4TEE3F65A WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING ALL phases

More information

INSTALLATION & OPERATING INSTRUCTIONS AAW SERIES VERTICAL WALL MOUNT AIR HANDLER (ELECTRIC HEAT)

INSTALLATION & OPERATING INSTRUCTIONS AAW SERIES VERTICAL WALL MOUNT AIR HANDLER (ELECTRIC HEAT) INSTALLATION & OPERATING INSTRUCTIONS AAW SERIES VERTICAL WALL MOUNT AIR HANDLER (ELECTRIC HEAT) MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should be retained

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE INSTALLATION INSTRUCTIONS ACBX32CM Units WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of

More information

Evaporator Coil. Installation Instructions GENERAL

Evaporator Coil. Installation Instructions GENERAL IM-HAC-0966540-16 August 2018 Evaporator Coil TABLE OF CONTENTS GENERAL PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Condensate Drain... 5 Metering Device... 6 Refrigerant Line

More information

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER ASPEN MANUFACTURING 373 ATASCOCITA RD. HUMBLE, TX 77396 TEL (281) 441-6500 FAX (281) 441-6510 > INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT: "The

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2016 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE WARNING This product contains a chemical known to the State of California to cause cancer,

More information

Installation Instructions

Installation Instructions Installation Instructions Indoor Air Handlers for Systems These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of heating and/or air conditioning

More information

CBX32MV (HFC-410A) SERIES UNITS

CBX32MV (HFC-410A) SERIES UNITS Service Literature Corp. 005-L2 Revised November 5, 202 (HFC-40A) SERIES UNITS (icomfort-enabled) NOTICE A thermostat is not included and must be ordered separately. The Lennox icomfort thermostat must

More information

Upflow/Downflow A-Coil Specifications

Upflow/Downflow A-Coil Specifications June 2013 Upflow/Downflow A-Coil Specifications ADP Model # Width Depth Height Pallet Qty. Coil Weight (lbs) C36A142(*)126 14.25" 21" 16.5" 12 38 1200 386.36 C36A175(*)126 17.50" 21" 16.5" 8 40 1200 386.34

More information

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES ISO 9001 Certified Quality Management System GENERAL.............................................. 1 SAFETY................................................

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2017 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE WARNING This product contains a chemical known to the State of California to cause cancer,

More information

Installation Instructions

Installation Instructions Installation Instructions PAM3 SERIES PACKAGE AIR CONDITIONERS TABLE OF CONTENTS SAFETY LABELING AND SIGNAL WORDS... 2 UNIT DIMENSIONS... 3 SAFE INSTALLATION REQUIREMENTS... 3 LOCATING THE UNIT... 3 CLEARANCES...

More information

GAW SERIES INSTALLATION & OPERATING INSTRUCTIONS VERTICAL WALL MOUNT AIR HANDLER (ELECTRIC HEAT)

GAW SERIES INSTALLATION & OPERATING INSTRUCTIONS VERTICAL WALL MOUNT AIR HANDLER (ELECTRIC HEAT) GAW SERIES INSTALLATION & OPERATING INSTRUCTIONS VERTICAL WALL MOUNT AIR HANDLER (ELECTRIC HEAT) MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should be retained

More information

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT MASSAGE TO INSTALLER: "The United States Environmental Protection Agency ("EPA") has issued various regulations regarding the

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION SINGLE PIECE AIR HANDLERS Supersedes: 535.02-N2V (598) 535.02-N2V (199) HEAT PUMP MODELS F+RP / F+FP018 thru 060 and COOLING MODELS F+RC / F+FC024 thru 036 035-14363 GENERAL This

More information

2TEH3F18A1000A 2TEH3F24A1000A 2TEH3F30A1000A 2TEH3F36A1000A 2TEH3F42A1000A 2TEH3F48A1000A 2TEH3F60A1000A 1½

2TEH3F18A1000A 2TEH3F24A1000A 2TEH3F30A1000A 2TEH3F36A1000A 2TEH3F42A1000A 2TEH3F48A1000A 2TEH3F60A1000A 1½ Cooling/Heat Pump Convertible Air Handlers 2TEH3F18A1000A 2TEH3F24A1000A 2TEH3F30A1000A 2TEH3F36A1000A 2TEH3F42A1000A 2TEH3F48A1000A 2TEH3F60A1000A 1½ 5 Ton Preliminary PUB. NO. 22-1777-04 Features and

More information

INSTALLATION INSTRUCTIONS APARTMENT FAN COIL UNIT FMA4X, FMA4P

INSTALLATION INSTRUCTIONS APARTMENT FAN COIL UNIT FMA4X, FMA4P APATMENT FAN COIL UNIT FMA4X, FMA4P NOTE: ead the entire instruction manual before starting installation. These instructions must be read and understood completely before attempting installation. TA BLE

More information

Inspection Checklist Mechanical Rough in

Inspection Checklist Mechanical Rough in Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and

More information

TECHNICAL SUPPORT MANUAL Fan Coils FVM4X B Series

TECHNICAL SUPPORT MANUAL Fan Coils FVM4X B Series Fan Coils FVM4X B Series DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used

More information

Advance Release September 2009

Advance Release September 2009 Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*

More information

INSTALLATION INSTRUCTIONS AND SPECIFICATIONS: COOLING COIL

INSTALLATION INSTRUCTIONS AND SPECIFICATIONS: COOLING COIL INSTALLATION INSTRUCTIONS AND SPECIFICATIONS: COOLING COIL VERTICAL AND MULTIPOSITION COOLING COIL FOR CHINOOK AND SUPREME Models: CC1.0-10.0-M CC1.5-13.5-V & CC1.5-13.5-M CC2.5-13.5-V & CC2.5-13.5-M CC2.5-15.7-V

More information

R Series Multi-Position Air Handler Electric or No Heat, with available Variable-Speed High Efficiency ECM Motor DISCONTINUED.

R Series Multi-Position Air Handler Electric or No Heat, with available Variable-Speed High Efficiency ECM Motor DISCONTINUED. 0659370-83 December 2010 Installation Instructions R Series Multi-Position Air Handler Electric or No Heat, with available Variable-Speed High Efficiency ECM Motor AIR HANDLER SAFETY 1 INSTALLATION REQUIREMENTS

More information

VERTICAL AHU INSTALLATION MANUAL BULLETIN

VERTICAL AHU INSTALLATION MANUAL BULLETIN VERTICAL AHU INSTALLATION MANUAL BULLETIN 30-015003 TABLE OF CONTENTS MOUNTING 4 LOCATION 5 DUCT CONNECTION 5 AIR FILTRATION 6 PIPING 7 SEQUENCE OF OPERATION 11 CHECKING AIRFLOW 11 CHARGING A COOLING SYSTEM

More information