R Series Cooling Manual
|
|
- Beverley Davidson
- 5 years ago
- Views:
Transcription
1 Mini Duct Heating and Air Conditioning Indoor Air Quality Systems R Series Cooling Manual Includes: RPM-E-50 Cooling Module RPM-E-0 Cooling Module RPM-E-00 Cooling Module Manufactured By Energy Saving Products Ltd. ESP 05.05
2 RPM-E Coils Pre-Piped Refrigerant Cooling Module Specifications RPM-E-50 RPM-E-0 RPM-E-00 Part Number Refrigerant Type R-22 R-22 R-22 TX Cooling MBH Fin Material Aluminum Aluminum Aluminum Tubing Material Copper Copper Copper Type of Fins.006 Al.006 Al.006 Al Connection Sizes Liquid Line (Lq) /8 /8 /8 Suction Line (S) /8 /8 /8 Drain Connection /8 /8 /8 TEV with Built in Check Valve & Bypass Yes Yes Yes Site Glass Yes Yes Yes Access Ports Yes Yes Yes Freeze Stat Yes Yes Yes Shipping Weight (lbs) Module Size Length (L) 9 /4 24 /4 2 Width (W) 4 5/8 4 5/8 4 5/8 Height (H) 8 /2 8 /2 8 /2 Matching Fan Coil HE - 50 / 5 / 52 HE - 0 / HE - 00 / 0 Tons ) Smaller condensers may be matched to the fan coil when needed (match TXV to condenser size) 2) Minimum of 8 full outlets per ton of cooling needed MBH = Thousand British Thermal Units per Hour TX = Thermal Expansion TEV = Thermal Expansion Valve Multiple Access Coils: Can be used with a fan coil installed in any position. With our pre-fabricated knock outs, select the desired position and within minutes it is ready for installation. Comes Pre-Piped: The TXV (Thermal Expansion Valve), site glass, access ports and external freeze stat are already installed. The liquid and suction lines have male solder connections at a standard width making connections to the condenser lines quick and easy. Refrigerant modules come with: Heat pump ready Thermal Expansion Valve, with built in check valve Integrated Site glass Integrated access ports Integrated external freeze Two L mounting brackets B H A B Lq S A W Rough Opening Sizes A or B A or B RPM-E 50 /4 L X /4 W /4 L X 9 W RPM-E-0 6 /4 L X /4 W 6 /4 L X 9 W RPM-E /4 L X /4 W 22 /4 L X 9 W Note: Do not use a combination of A/A or B/B L
3 Refrigerant Modules (RPM-E) Fig Mounting Brackets The RPM-E Series cooling module is pre-piped with an adjustable heat pump thermal expansion valve and comes with bleed port, site glass, suction and liquid line service ports, a factory mounted freezed stat, and two L brackets for mounting. The RPM-E comes as a module and must be installed on the return air side of the fancoil The module offers multi-position air flow options for horizontal, highboy, or counterflow configurations (Fig. 0). Fig. 0 - RPM-E Cooling Module A B B Secondary Drain Pan Some building codes call for a secondary drain pan under the entire unit (Fig. 0). Any installation that has the potential of property damage due to condensate must have a secondary drain pan installed. If the unit is installed in a high heat and/or high humidity location, extra insulation around the unit casing may be required. This will prevent excessive condensate from forming on the outer surface of the casing. Fig. 0- Secondary drain pan A When installing, any combination of A and B can be used. For example, for horizontal application you would use A/B, for counterflow you would use B/A or B/A, or for highboy you would use A/B or A/B. Do not use a combination of A/A or B/B. See Pg. for details - Rough Opening Sizes The RPM-E is available with the option of a R-40 heat pump thermal expansion valve and must be factory ordered as such. For other configurations, contact the factory. Mounting the RPM-E Mounting Brackets Two L mounting brackets are shipped loose for attaching the RPM-E to the fancoil, along with two sided foam tape for air seal between units. When mounting the cooling coil to the fan coil (Fig. 02), ensure that no screws puncture the drain pan or coil. See Appendix Pages for the dimensions of the fan coil units and cooling modules. Secondary drain pan P-Trap P - Trap The condensate drain must have a Vented P-trap installed (Fig. 0), and run at a slope of ¼ per foot in the direction of the drain. All RPM-E modules come with a ¾ primary outlet and a ¾ secondary outlet. When installing the P-trap it must be installed on the primary outlet. A vent must be installed between the coil and the P-trap, keeping the vent as close to the coil as possible. R Series Cooling Manual Pg.
4 The RPM-E comes pre-piped with the coil assembly. With the RPM-E, the Liquid and Suction lines are the only brazing that need to be done at the fan coil. For charging and brazing, remove the front access panel of the RPM-E (Fig. 04). With the access panel removed, the coil assembly will be accessible. Wet rag the liquid and suction line (or use a heat dissipating paste) to ensure no overheating occurs to the pre-piped coil assembly. Fig Remove Front Access Panel Evacuating After the piping is installed and all components have been brazed together, a vacuum pump must be used to evacuate the system from both the low and high side to 500 microns. Add pressure to the system to bring the pressure above zero psig. After allowing the refrigerant to absorb moisture, repeat the above procedure. Evacuate the system to 500 microns on the second evacuation, and ensure that the system holds at the vacuum pressure. If not, check for leaks and evacuate again. If the vacuum holds, add refrigerant to raise the pressure to 2 psig. At this point open service valves on precharged condensing units, or add refrigerant to the system. The use of an electronic leak detector is recommended, as it is more sensitive to small leaks under the low pressures. Charging Once the system has been determined clean and ready for charging, refrigerant can be added to the system. The access ports on the condenser must be open at this point. Never leave the system unattended when charging. With the system running, slowly add refrigerant to the system until the site glass is clear of all bubbles. If the site glass is clear of bubbles and the super heat is off, the TX valve will need to be adjusted (See Super Heat for temperature settings). When adjusting the TX valve, never turn it more than a quarter turn at a time. Always allow 5 minutes for the system to settle down before making another TX adjustment. When adjusting the TX valve, a clockwise turn will close the valve, allowing less refrigerant through. With less refrigerant flowing through the coil, less cooling will be done, which will bring up the suction line temperature. Super Heat/Sub-cooling Super heat on Hi-Velocity systems with the RPM-E series should normally be around 6ºF -8ºF. With sub-cooling, double the superheat at 2ºF-6ºF The suction line should be set at approximately 42ºF. Piping the RPM-E Only refrigerant grade pipe and fittings are to be used with Hi-Velocity Systems. Plumbing fittings may contain wax or other contaminants which are detrimental to the proper operation of the system. Insulate the suction line with /8 insulation such as Armaflex. In high heat areas, /2 insulation may be needed. If the lines are run in an area where temperatures could exceed 20 F or runs longer than 50, then the liquid line may need to be insulated as well. Support the pipe every 5 feet, or whatever local code states. Run the pipes in the most direct route possible, taking into account structural integrity and building details. If the evaporator is located above the condenser, slope any horizontal runs toward the condenser. If the condenser is located above the evaporator, a P-trap must be installed at the bottom of the vertical riser. For long vertical risers, additional P-traps must be installed for every twenty feet. For lines running over 50, a suction line accumulator must be installed. Lines running over 00 are not recommended. Pipe Sizing Tables 0 and 02 contain line sizing information for the liquid and uction lines. Table 0 Liquid Line sizes Tons Distance Table 02 Suction Line sizes Tons Distance R Series Cooling Manual Pg. 2 5 The sizes given in the above tables are only for general reference, if the condenser manufacture requires a different size than specified in Table 0 and Table 04, their sizing shall be used whenever a discrepancy occurs. Outdoor Unit Installation Locate the outdoor unit in a suitable location, as close as possible to the fan coil. Maintain the clearances recommended by the manufacturers of the outdoor unit, to ensure proper airflow. The outdoor unit must be installed level, in a properly supported location. A liquid line filter/ drier is recommended to be installed. 2
5 Wiring Outdoor Unit Make all connections to the outdoor unit with rain tight conduit and fittings. Most building codes require a rain tight disconnect switch at the outdoor unit as well (always check local codes). Run the proper size copper wires to the unit, and connect as per the manufacturer s recommendations. Ensure that the unit is setup for a TX system. If not, a hard start kit may be required. Wiring Indoor Unit Refer to HE Installation Manual for interior unit wiring, e.g. thermostat connections, anti-ice control, etc. RPM-E Sizing & Specifications Page contains sizing and specifications for RPM-E Cooling Units. Return Air The return air duct is not supplied with the Hi-Velocity System. It is to be supplied and installed by the contractor. The return air and fresh air make-up ducts are to be installed according to local building code. The first five feet of the return air duct from the air handling units is to be acoustically lined for sound absorption. This only applies on short return air duct work of less than 0 feet. For traditional house return air using a combination of return air metal duct and joist liners, this does not apply. Duct Sizing The return air is to be sized on a 0.5 static pressure as compared to 0.0 static pressure for conventional forced air systems. The maximum length for an individual return air duct is fifty feet. Table 0 Return Air duct sizes Unit Round Duct Square Inches HE-50/5/52 H/BU 2 HE-0/ H/BU 2 HE-00/0 H/BU 4 54 Return Cutout All Hi-Velocity fan coils are shipped with the return air knockouts pre-measured for multiple configurations. Fig. 05 shows the different locations the return air can be installed on Hi-Velocity Systems. Table 04 contains the pre-measured dimensions for the return air knockouts. Fig. 06 shows pre-measured knockout locations (in bold). Fig Return Air Cutout Sizing Supply Side RA-A (Left/Right Side) RA-B Note: This drawing is NOT to scale. Table 04 Return Air Cutout Dimensions Model RA-A RA-B (Horizontal) Fig Return Air Cutout Locations Legend RA - Return air RA-B (Highboy/ Counterflow) HE-50/5 H/BU /4 X /4 /4 X /4 /4 X 9 HE-0/ H/BU 6 /4 X /4 6 /4 X /4 6 /4 X 9 HE-00/0 H/BU 22 /4 X /4 22 /4 X /4 22 /4 X 9 HV-50/5 H/BU 9 /4 X /4 9 /4 X /4 9 /4 X 9 HV-0/ H/BU 4 /4 X /4 4 /4 X /4 4 /4 X 9 HV-00/0 H/BU 20 /4 X /4 20 /4 X /4 20 /4 X 9 When sizing the return air ducts, keep in mind that if they are too small they can create noise, but if they are too large, the fan coil cannot build up proper pressure. Table 0 has recommended return air sizes for round and rectangular ducts. A variance of plus/minus 20% is allowable for sizing return ducts that connect to the Hi-Velocity Systems unit. It is recommended to install a grill that is 0-20% larger than specifications require, this will ensure that there is no air velocity noise at the grill. Where allowed by local codes, a single return air grill may be used. When using flexible duct for return air, use one duct size larger due to the higher friction loss. HE - Horizontal HV - Horizontal HE - Highboy/Counterflow HV - Highboy/Counterflow HE - Highboy/Counterflow (Left Side) HV - Highboy/Counterflow (Right Side) Once the placement of the return has been decided, the return air knockout(s) can be marked and cut (Fig. 06). The pre-measured guide cuts supplied with the fan coil should always be used; this will guarantee maximum airflow across the coil. R Series Cooling Manual Pg.
6 Cooling Start-Up Pipe system with Site Glass and Access Ports at the evaporator. Leak check and evacuate system. Check system operation with power to the outdoor unit off or use the service disconnect. Connect gauges and open outdoor unit service valves. Turn on power to the outdoor unit and start system. Start N Bubbles In Site Glass Remove Charge Until Bubbles Are Visible Y Add Charge Until Site Glass Is Clear Check Suction Line Temperature Temperature at or Over: (And/Or Hunting) 4 F +/- F Temperature at: 42 F +/- F Temperature at or Below: 4 F +/- F Open TX Valve ¼ turn and WAIT FIVE minutes Close TX Valve ¼ turn and WAIT FIVE minutes Confirm Site Glass Is Still Clear System Start-Up Complete Y Line Temperature is Stable Within a +/- 2 F swing N Perform System Trouble Shooting Check Return to Start Rectify Problem 4 R Series Cooling Manual Pg. 4
7 WARRANTY One year limited warranty. The heat exchanger and blower are free from defects in workmanship for one year from date of purchase. Three year limited warranty. The EPC Motor, EPC Controller and EPC Circuit Board are free from defects in workmanship for three years from date of purchase. Two year limited warranty. The electrical strip heater is free from defects in workmanship for two years from date of purchase This warranty applies only to the fan coil unit and does not include connections, attachments, and other products or materials furnished by the installer. This warranty applies only to the first purchaser at retail and excludes any damages caused by changes, relocation to, or installation in a new site. This warranty does not cover any defects caused by failure to follow the installation and operating instructions furnished with the fan coil, local building codes, and good industry standards. Failure to correctly install the fan coil, or material related to the unit, may result in improper system performance and/or damages and will void this warranty. TERMS AND CONDITIONS Any repair performed under warranty must be approved by Energy Saving Products Ltd. for this warranty to be valid. The manufacturer is not liable for any other damages, personal injury, or any other losses of any nature. The liability of the manufacturer is limited to and shall not exceed the cost of replacement parts and shall not include transportation to and from the factory, and field labour. Inoperative parts must be returned with serial number, purchase date, and a detailed description of the entire problem with an ESP RMA Form. This warranty replaces all other warranties expressed or implied. ENERGY SAVING PRODUCTS LTD STREET EDMONTON, ALBERTA, CANADA T5L 0N8 PHONE (80) FAX (80) TOLL FREE
8 Energy Saving Products Ltd., established in 98, manufactures the Hi-Velocity Systems TM product line for residential, commercial and multi-family markets. Our facilities house Administration, Sales, Design, Manufacturing, as well as Research & Development complete with an in-house test lab. Energy Saving Products prides itself on Customer Service and provides design services and contractor support. Comfort from floor to ceiling, Satisfaction from room to room, with TM It s not just a dream, it s reality. HARDI Phone: (80) Fax: (80) Toll Free: velocity.com ESP 05.05
R Series Cooling Modules
R Series Cooling Modules Models RCM/RPM 50 RCM 70 RM 100 RM 140 Manufactured By Energy Saving Products Ltd. Standard ESP 105.03 Refrigerant Modules (RCM/RM) Fig. 02 - Mounting brackets The cooling coil
More informationR Series Cooling Modules
TM Small Duct High Velocity Heating, Cooling and Indoor Air Quality Systems R Series Cooling Modules Models RCM-50 RCM-70 RM-100 Manufactured By Module-RCM/RM-Series-Installation-Manual-120113 Refrigerant
More informationRCM Refrigerant Module
Small Duct High Velocity Heating, Cooling and Home Comfort Systems RCM Refrigerant Module Installation Manual Manufactured By Module-RCM-Refrigerant-Module-Installation-0666 Refrigerant Modules (RCM) Fig.
More informationLV Installation Manual
LV Installation Manual Includes: LV-50 LV-70 LV-120 LV-140 Manufactured By Energy Saving Products Ltd. Module-LV-Series-Installation-Manual-111915 INSTALLATION, OPERATING, AND MAINTENANCE MANUAL LO-V UNIT
More informationLV Installation Manual
LV Installation Manual Includes: LV-50 LV-70 LV-120 LV-140 Manufactured By Energy Saving Products Ltd. ESP 202.02b INSTALLATION, OPERATING, AND MAINTENANCE MANUAL LO-V UNIT INSTALLATION INSTRUCTIONS Lo-V
More informationJH Series Installation
JH Series Installation Space Heating / Fresh Air Make-Up From the Manufacturers of Hi-Velocity Systems TM Includes: JH-15 JH-30 Module-JH-Series-Installation-Manual-010118 Installation JH fan coils by
More informationMini Duct Heating and Air Conditioning Indoor Air Quality Systems. July Featuring: Also Including: Lo-Velocity Systems JH Fancoils
Mini Duct Heating and Air Conditioning Indoor Air Quality Systems July 2008 Parts List Featuring: TM Also Including: Lo-Velocity Systems JH Fancoils Minimum Invoice Amount of $25 Net in Effect ESP 100.02b
More informationParts List * October 2013
Parts List * October 2013 Featuring: Small Duct High Velocity Heating, Cooling and Indoor Air Quality Systems TM HE-Z Series High Velocity Fan Coil LV-Z Series Conventional Replacement JH Series Space
More informationG Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton
G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1
More informationSECTION SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS
1.0 GENERAL SECTION 15740 SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS 1.01 DESCRIPTION Item A. Scope This section specifies four sizes of fan coil units designed for hydronic heating and air conditioning.
More informationMYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1
Page 1 WHY should I install the MYSTICOOL Max Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,
More informationCased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit
18-AD32D1-3 Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit Upflow models: 4PXCAU24BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA
More informationService Step by Step Trouble-Shooting Check-List
WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:
More informationESP. Variable Speed Heat Pump. Installation and Operation. 3 Ton ESP Ton ESP-60
Heating, ooling and Indoor Air Quality Systems ESP Variable Speed Heat Pump 3 Ton ESP-36 5 Ton ESP-60 Installation and Operation www.hi-velocity.com Module-VAR-Variable-Speed-Heat-Pump-060118 Installation
More informationWKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--
8610 Production Avenue San Diego, California 92121 (858) 566-7465 Fax (858) 566-1943 WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- Thank you for choosing a BREEZAIRE cooling unit. We believe
More informationAirPurification System
The AirPurification System Installation and Operation Manual ONE SIZE FITS ALL! ESP 109.01 TABLE OF CONTENTS PARTS LIST........................................ 1 IMPORTANT SAFETY INSTRUCTIONS...................
More informationCondensing Unit Installation and Operating Instructions
Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.
More informationCommercial Applications
Small Duct High Velocity Heating, Cooling and Indoor Air Quality Systems TM Commercial Applications Manufactured by Module-COM-Commercial-Applications-Brochure-042116 The Hi-Velocity System is a Complete
More informationInstructors: Contact information. Don Reynolds Doug McGee Factory Tech Support
Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient
More informationXSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1
Page 1 WHY should I install the XSTREAM Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,
More informationWKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS--
8610 Production Avenue San Diego, California 92121 (858) 566-7465 Fax (858) 566-1943 WWW.BREEZAIRE.COM WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- Thank you for choosing a BREEZAIRE cooling
More informationFeaturing: Small Duct High Velocity Heating, Cooling and Indoor Air Quality Systems
www.hi-velocity.com 2010 Parts List Featuring: Small Duct High Velocity Heating, Cooling and Indoor Air Quality Systems TM Also Including: LV-E Systems JH Fancoils Hi-Velocity Air Purification System PWM
More informationINSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR COILS 505,264M (65484504) 05/08 Supersedes 10/07 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE
More informationMortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS
Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS INTRODUCTION Please note that HUD Manufactured Home Construction and Safety Standard Section 3280.714, paragraph (a) and subparagraph
More information"SWVP - SWHP" COMMERCIAL WATER SOURCE HEAT PUMPS & AIR CONDITIONERS
"SWVP - SWHP" COMMERCIAL WATER SOURCE HEAT PUMPS & AIR CONDITIONERS Belt Driven Self-Contained Packages Vertical and Horizontal Configuration Size 6-8-10 Ton Capacities Spinnaker Industries Inc. SWHP /
More informationOwner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350
Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others
More informationINSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD
TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system
More informationINSTRUCTIONS! DO NOT DISCARD!
INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components dn0521 Page 1 of 12 INSTALLATION INSTRUCTIONS CAUTION
More informationAPPLICATION DATA SHEET
APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat
More informationWineZone Ceiling Mount Ductless Split 15
WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor
More informationOwner s Manual Refrigerated Compressed Air Dryers Model F-100
Owner s Manual Refrigerated Compressed Air Dryers Model F-100 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing
More informationTECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)
DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage
More informationTECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703
TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.
More informationEvaporator Coil. Installation Instructions GENERAL
IM-HAC-0966540-16 August 2018 Evaporator Coil TABLE OF CONTENTS GENERAL PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Condensate Drain... 5 Metering Device... 6 Refrigerant Line
More informationWMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS
WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty
More informationHV to HE Conversion Kit Installation
Small Duct Heating, ooling and Indoor Air Quality Systems www.hi-velocity.com TM HV to HE onversion Kit Installation Manufactured By Module HK - HV to HE onversion Kit Installation 032410 Motor and Blower
More informationINSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH
TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system
More informationVariCool VAV Engineering Guide
Engineering Guide Effective September 2017 Water-Cooled and Chilled Water, Variable Air Volume Contents Product Features... 3 UNIT FEATURES... 3 Product Features... 4 Marvel Plus Microprocessor Control
More informationCondensing Unit Installation and Operating Instructions
Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...
More informationINSTRUCTIONS! DO NOT DISCARD!
INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components d N0417 Page 1 of 10 INSTALLATION INSTRUCTIONS CAUTION
More informationMHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH
MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH 318 MHNCCX NOMENCLATURE BREAKDOWN 4-Pipe Heat/Cool Ceiling Concealed Fan Coil MHNCCW- XX - XX Ceiling Concealed
More informationCS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)
CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System
More informationEvaporator Coil. Installation Instructions GENERAL
IM-HAC-0966540-14 February 2018 Evaporator Coil Installation Instructions TABLE OF CONTENTS PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Condensate Drain... 5 Metering Device...
More informationINSTALLATION INSTRUCTIONS
,t_2007 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR 505,264M (65484504) 10/07 Supersedes 09/06 COILS n _putech blications ical Litho U.S.A. RETAIN THESE
More informationINSTRUCTIONS! DO NOT DISCARD!
INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components dcn0620 Page 1 of 12 INSTALLATION INSTRUCTIONS CAUTION
More informationPL Series Premier Indoor Plenum Coils
IM-PLC-0667392-04 April 2016 PL Series Premier Indoor Plenum Coils Installation Instructions GENERAL ADP evaporator coils are designed for use with condensing units or heat pump units. These instructions
More informationUpflow/Downflow A-Coil Specifications
June 2013 Upflow/Downflow A-Coil Specifications ADP Model # Width Depth Height Pallet Qty. Coil Weight (lbs) C36A142(*)126 14.25" 21" 16.5" 12 38 1200 386.36 C36A175(*)126 17.50" 21" 16.5" 8 40 1200 386.34
More informationTechnical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307
DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application
More informationTECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING
TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be
More informationOwner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532
Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect
More informationInstallation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT
EarthLinked TXV Kit Installation Manual for Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT CONTENTS PAGE Pre-Installation 3 Hydronic Water Module Conversion
More informationINSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER
INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should
More informationDLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS
DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...
More informationTechnical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS
Technical Guide SPLIT-SYSTEM EVAPORATOR BLOWERS 7-1/2 and 10 NOMINAL TONS LA090 & LA120 DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes
More informationInstallation, Operation, and Maintenance Information
Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant
More informationK*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*
TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling
More informationGAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT)
GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT) MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should be retained and
More informationSKYPAK II, 3 Ton Series, gives you a
SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall
More informationCROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25
More informationTECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:
GENERAL SPECIFICATIONS OUTDOOR UNIT: TECHNICAL GUIDE COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM MODELS HB 180 & HB 240 MODELS LB 180 & LB 240 15 & 20 NOMINAL TONS 9.7 EER Two independent refrigerant
More informationINSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA
TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,
More informationTECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36
TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36 Due to continuous product improvement, specifications are
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS FOR AQUECOIL HYDRONIC HEATING UNITS GENERAL INFORMATION The AQUECOIL Hydronic Heating Unit is offered in many different capacities and physical configurations in order to match
More informationInstallation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant
EarthLinked TXV Kit Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Air Handler Conversion 4 System
More informationR-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES
R-410A MODELS: 7.5-20 Ton, 60 Hertz NH-07 thru -20, 2-Pipe NJ-10 thru -20, 4-Pipe General.......................................... 2 Safety Considerations............................... 2 Reference......................................
More informationOwner s Manual Therma-Stor II Heat Recovery System
PO Box 8680 Madison, WI 53708 TS-138C Revised 8/08 Owner s Manual Therma-Stor II Heat Recovery System Installation, Operation & Service Instructions Read and Save These Instructions Table Of Contents 1.
More informationInstallation Instructions
38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes
More informationINSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD
TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system
More informationSPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS
036-21096-001 (0101) SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The
More informationRPI Industries, Inc.
RPI Industries, Inc. AIR SCREEN and SELF-SERVE OPERATION AND SERVICE MANUAL WARRANTY INFORMATION For Models Stratus SCRFC48R-SSI SCRFC60R-SSI SCRFC72R-SSI SCRFC48R-SSII SCRFC72R-SSII SCRFC48R-SSIII SCRFC72R-SSIII
More informationInstallation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant
EarthLinked TXV Kit Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Cased Coil Conversion 4 System Start-Up 17 TXV CCS-410-KIT
More informationFALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)
FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz
More informationENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS RH-24-HAC-P-1L-C-SDE*F Horizontal Single Stage R410a Model Size 24 Reversing (Heating AND Cooling) 208/230-1-60VAC Liquid to Air Geothermal Heat Pumps Maritime Geothermal Ltd.
More informationInstallation Manual BCS2000/3000
Installation Manual BCS2000/3000 Supplies Needed for Installation 1. 3/8 and 5/8 copper tubing. 2. 1/4 copper water supply 3. 1/4 condensate vinyl drain tube/tube clamps 4. Provide 120v 15A circuit for
More informationSPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500
SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing 550.23-N4C-0500 MODEL L*BC240 035-16603 GENERAL This 20 ton evaporator blower is designed with two distinct modules
More informationENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS RH-12-HAC-P-1L-C-SDE*F Horizontal Single Stage R410a Model Size 12 Reversing (Heating AND Cooling) 208/230-1-60VAC Liquid to Air Geothermal Heat Pumps Maritime Geothermal Ltd.
More informationTechnical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)
Technical Guide SUNLINE 2000 SPLIT-SYSTEM EVAPORATOR BLOWER K4EU180 15 NOMINAL TONS (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper
More informationINSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA
TXV Coils EDM, EDD, EDA These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system to
More informationENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical
ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator
More information2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA
18- AH39D1-4 Cased Aluminum "Convertible" Coils 2/4TXCA018BC3HCA 2/4TXCA024BC3HCA 2/4TXCB025BC3HCA 2/4TXCB031BC3HCA 4TXCB032BC3HCA 2/4TXCB036BC3HCA ALL phases of this installation must comply with NATIONAL,
More informationOwner s Manual Refrigerated Compressed Air Dryer Model F-50
Owner s Manual Refrigerated Compressed Air Dryer Model F-50 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all
More informationCHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS
550.23-TG5Y (893) CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L2EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility.
More informationINSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!
4AC 14* ASA1 SERIES R-410a CONDENSING UNITS INSTALLATION GUIDE R-410A ATTENTION, INSTALLER! After installing the system, show the user how to turn off electricity to the unit. Point out control and switch
More informationINSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER
ASPEN MANUFACTURING 373 ATASCOCITA RD. HUMBLE, TX 77396 TEL (281) 441-6500 FAX (281) 441-6510 > INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT: "The
More informationInstallation Instructions
CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...
More informationVERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System
VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System PART 1 SYSTEM DESCRIPTION 1.1 The HVAC system is based on the CGC HYBRID Hydronic Heat Pump System. 1.2 The system will automatically
More informationOperation & Maintenance Manual
Operation & Maintenance Manual VUD, VUF, VDF & HCD Series Unit Ventilator IMPORTANT: Read and save this manual for future reference. This manual is to be left with the equipment owner 2006 TEMSPEC INCORPORATED
More information1.1 This section applies to air handling units for HVAC Systems.
AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling
More informationMANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier
MANUAL 8/12/05 INSTALLATION, OPERATION & MAINTENANCE Commercial High Efficiency Heat Pipe Dehumidifier Model BKP TM 100 Heat Pipe Technology, Inc. 6904 Parke East Blvd. Tampa FL 33610 Tel: (813) 470-4250
More informationH3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog
H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...
More informationRPI Industries, Inc.
IMPORTANT: THE FOLLOWING INFORMATION SHOULD BE RETAINED FOR FUTURE REFERENCE RPI Industries, Inc. building a better case for sales BAKERY and DELI USE AND SERVICE MANUAL WARRANTY INFORMATION SPECIFICATIONS
More informationT-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS
PRODUCT SPECIFICATIONS CONDITIONERS TS T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ Bulletin No. TSA-072-240 (11/2016) 072-090 Models 180-240 Models 120-150 Models EER up to 11.7 6 to 20 Tons Cooling Capacity
More informationINSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS
INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................
More informationInstallation, Start-Up and Service Instructions
38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................
More informationTECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811
Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage
More informationINSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER
INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT MASSAGE TO INSTALLER: "The United States Environmental Protection Agency ("EPA") has issued various regulations regarding the
More informationSporlan Valve Division Parker Hannifan/CIC Group
www.parker.com/cic Sporlan Valve Division Parker Hannifan/CIC Group Matt McGrath, SW Regional Sales Manager Bob Dolan, Sales Engineer - Atlanta www.parker.com/cic Why Discuss TEVs Today? Expansion Valves
More information15 SEER, PACKAGE AIR CONDITIONING UNITS, 2-5 TONS Single Phase, 208/230 V, 60 Hz COOLING
SOUND REFRIGERANT ENVIRONMENTALLY PAN5 Product Specifications 15 SEER, PACKAGE AIR CONDITIONING UNITS, 2-5 TONS Single Phase, 208/230 V, 60 Hz REFRIGERATION CIRCUIT Environmentally sound R--410A refrigerant
More informationMODEL RD-8 Self Contained MODEL RD-2
MODEL RD-8 Self Contained REFRIGERATED SHOWCASE MODEL RD-2 REFRIGERATED SHOWCASE Document Part #: 1150285 Rev: I ECN: 55118 Rev. Date: 5-28-14 The RD-2 and RD-8 refrigerated display showcase units have
More informationCooling/Heat Pump Convertible Air Handlers
Cooling/Heat Pump Convertible Air Handlers 2/4TEH3F18B1000A 2/4TEH3F24B1000A 2/4TEH3F30B1000A 2/4TEH3F36B1000A 2/4TEH3F42C1000A 2/4TEH3F48B1000A 2/4TEH3F60B1000A 1½ 5 Ton PUB. NO. 22-1777-10 Features and
More information