CODE PANEL QUESTIONS

Size: px
Start display at page:

Download "CODE PANEL QUESTIONS"

Transcription

1 NORTH CAROLINA ELECTRICAL INSTITUTE 89 th ANNUAL MEETING APRIL 3-4, 2018 HILTON NORTH RALEIGH RALEIGH, NORTH CAROLINA CODE PANEL QUESTIONS Opinions of the Code Panelist are NOT interpretations issued by the NC Department of Insurance / Office of State Fire Marshal NC Department of Insurance Office of State Fire Marshal NC State Board of Examiners of Electrical Contractors NC Ellis Cannady Chapter of the International Association of Electrical Inspectors

2 Al Paris ---> NCBEEC 1. Is it the responsibility of the electrical contractor to bond CSST gas piping? Bryan Holland ---> NEMA 2. Table covers burial depth underground. How much concrete must cover a raceway to be considered under a building per Table 300.5? What coverage would I need to install a piece of RMC in a slab above grade? Chad Kennedy ---> Schneider 3. Given a feeder load of six 5 HP 3 phase motors, I understand to get the minimum overcurrent protective device that we take the largest motors calculated overcurrent protective device and add the ampacity of the other 5 motors. I also understand that we cannot use the next larger breaker size. For conductor size it would be 125% of the largest motor and then add the ampacity of the other motors. What happens to this calculation if we add a small lighting load? Are we now obligated to still have the overcurrent protective device as high as the original calculation, thus being forced to have a conductor size that match that ampacity? Dave Mercier ---> Southwire 4. Section (C)(2) states that I can splice in a conduit body. If I need to splice the equipment grounding conductor s does apply (it states box not conduit body) and thereby requiring an equipment grounding conductor to be connected to the conduit body? If so, can I just tap the conduit body and add a lug? Don Hursey ---> NC Educator 5. NC has decided to abandon the amendment to 210.8(A)(7) that excluded the kitchen sink. But not there is a new amendment to section (B)(2); can you explain the logic behind this?

3 Jeff Fecteau ---> UL 6. Can a Classified circuit breaker be installed in a panelboard when the breaker is listed to be installed in the panelboard but the manufacturer of the panelboard prohibits the use of these breakers? Jeff Sargent ---> NFPA 7. If I run a separate circuit in order to add a shower light, the branch circuit does not require AFCI protection. However, would I need AFCI protection if I tapped into an existing branch circuit from a circuit in a bedroom that is currently not AFCI protected? Mike Holt ---> National Educator 8. According with (B)(2), perimeter bonding is required to be attached to the pool reinforcing steel or copper conductor grid at a minimum of four (4) points uniformly spaced around the perimeter of the pool. Does this requirement apply to vinyl shell pools? Keith Lofland ---> IAEI 9. Now that we measure form the wall and not the connection edge, can an outlet be installed on the end of the peninsula, and not on the wall space and meet the intent of the code?

4 Al Paris ---> NCBEEC 10. I have an electrical business with a Limited License. I would like to bid a project that is $49, labor only. The material will be furnished by the building contractor in the amount of $ The inspector said if I bid this project he would not issue me a permit. Why? Bryan Holland ---> NEMA 11. Does section 514.9(A) prohibit a RMC coupling from being used inside the gas pump dispenser? Assume there is no information about the RMC coupling being exposionproof. Chad Kennedy ---> Schneider 12. Can I add a new circuit to a federal pacific panel? Dave Mercier ---> Southwire 13. Given a parallel feeder where there are 10 conduits and the equipment grounding conductor has been upsized to the point where it is larger than the feeder conductor then would the feeder conductors need to be upsized to the size of the equipment grounding conductor? If not, why not? I know the equipment grounding conductor was upsized in order to ensure the breaker trips in case of a ground fault so why wouldn t the ungrounded conductors need to be sized accordingly for a phase to phase short? Don Hursey ---> NC Educator 14. If a panel was compliantly installed over a stairway years ago can I replace the panel and leave it in the same location? If not, can I add a new circuit to that panel?

5 Jeff Fecteau ---> UL 15. There is a ¼ hole in the bottom of every 200 meter base that I have installed and some manufacturers state that is for the grounding electrode conductor. Some people say that a Kenny Clamp: must be used based on the 2011 changes to 250.8(A). Of course, the clamp manufacturer says these are required to bond the box where it enters a metal enclosure. They also cite (E) Jeff Sargent ---> NFPA 16. If 350 KCMIL AL mc cable (parallel) is used on the secondary side of a transformer to a 500a main breaker panel, how can the grounding conductor in the cable assembly be properly sized per table or ? Can the correct size grounding conductor be tie wrapped on the outside of the cables? Bonding is done in the transformer. Mike Holt ---> National Educator 17. Can I use the feeder equipment grounding conductor, of the wire-type, be used for both the feeder equipment grounding conductor and the remote building grounding electrode conductor as permitted with Exception? Keith Lofland ---> IAEI 18. How many receptacles are required to serve a 10 foot by 20 foot kitchen island that contains a sink with 7 feet of countertop behind the sink? Al Paris ---> NCBEEC 19. I am a certified well pump contractor and I hold a Special Water Pump (SP-WP) electrical contracting license. It is my understanding if I hold a well pump contractors certification I no longer need my electrical contracting license. Is this true?

6 Bryan Holland ---> NEMA 20. A panel is mounted on sloped roof rafters in an attic. Assume we have the height and clearance. Is the panel location compliant? Temperature is not an issue as this is a sealed attic. Chad Kennedy ---> Schneider 21. I have an installation where the contractor increased his wire size to accommodate voltage drop. He also increased his ground wire size proportionately. However, in his junction boxes, he sized the bonding jumper for the box to the overcurrent device size. Does the bond jumper need to be increased proportionately with the ungrounded conductors? Dave Mercier ---> Southwire 22. In the image below would the wires from the heater floor (heat tape) on the right need to be sleeved a bit further by getting the conduit out into the floor a bit or flush with the outside of the wall?

7 Don Hursey ---> NC Educator 23. I am replacing a heat pump that was originally installed under the 2008 NEC with #12 AWG romex. Under the 2008 NEC, the 60 C column stated that #12 AWG romex has an allowable ampacity of 25 amps; however, the NEC all reduce the #12 AWG romex to 20 amps. The new unit requires a minimum circuit ampacity of 22.7 amps. Am I now required to replace the entire circuit? Jeff Fecteau ---> UL 24. Is it compliant to use a plaster ring on a 4 square box with a receptacle and handy box cover if the box is surface mounted? I realize the pic below needs caulking but would it be compliant if it was caulked? Jeff Sargent ---> NFPA 25. There is a tap of service conductors ahead of main disconnect for a PV system (230.82(6)). There are three sets of conductors in parallel. Can you tap just one of the three sets of service conductors for a PV system? The tap will be done using piercing taps. The piercing taps are adequate and rated for the PV load. Mike Holt ---> National Educator 26. I have an outdoor hot tub sitting on grade where the top rim of the tub is at least 28 in. above all perimeter surfaces within 30 in. If nonconductive steps are provided for entry and exit from the tub, is equipotential bonding of perimeter surfaces in accordance with (B)(2) required? Keith Lofland ---> IAEI 27. A fluorescent lighting circuit is rated at 208 volts and the fixture has an internal disconnect for the ballast. Can I use a single pole switch to control the lights as long as I have a double pole breaker in the panel?

8 Al Paris ---> NCBEEC 28. Do I need an electrical contracting license to install any load control devices by an electrical power supplier? Bryan Holland ---> NEMA 29. If you run a size #10 wire in and out of a 20 amp receptacle circuit, to avoid voltage drop on a long run, and connected the device with #12 pigtails, then would you count the device as 2 wires based on #12 or #10 conductors. The code states based on the largest conductor connected to the device but is that the intent? Chad Kennedy ---> Schneider 30. I was turned down for having a panel in a detached garage, using five 15-amp breakers as my disconnect means. It seems to be allowed per A. Why am I turned down? Dave Mercier ---> Southwire 31. Is an air handler that contains refrigerant coils, and heat strips required to comply with Article 422 (appliances), 424 (fixed electric space-heating equipment), 430 (motors), and/or 440 (AC and refrigerating equipment)? All four sections have different rules concerning ampacity sizing, overcurrent protection, and disconnecting means. Don Hursey ---> NC Educator 32. I want to replace my existing meter base with a meter panel combo. The existing main panel that will become a subpanel is located in the center of the home making the service entrance cable hard to replace without opening the walls, floors, and/or ceilings. I was told that NC has amendments in place that give this situation options; can you explain?

9 Jeff Fecteau ---> UL 33. If a motor is rated 230V is it compliant to wire it to a 208V system? What about a 240V system? If 208V is allowed then what column would I use in to calculate conductor size? The 208V or 230V column? Does 110.3(B) come into play on this? Jeff Sargent ---> NFPA 34. Would a receptacle inside a low voltage panel in the laundry room need to be GFCI protected? Mike Holt ---> National Educator 35. An outside hot tub sitting on grade has one side of the tub flush with a deck. Is equipotential bonding of perimeter surfaces in accordance with (B)(2) required? Keith Lofland ---> IAEI 36. Suppose this cabinet is 8 wide at the front end, with 2 wall on both sides. Does the receptacle in the middle qualify for the required wall space outlet or must I have a receptacle on each 2 wall space since a cabinet isn t considered wall space. This is not a workspace area as mentioned in (A)(2). Would a receptacle be required above the cabinet? Same scenario only the cabinet is not recessed in a cove as shown below? Al Paris ---> NCBEEC 37. The first license examination I took was the Limited. Since that time I went back and took the Unlimited and passed but have never activated the Unlimited. What would I have to do if I wanted to upgrade my license to Unlimited?

10 Bryan Holland ---> NEMA 38. For years I have been arguing that it was non-compliant in many cases to have 2 garage doors and the receptacles in the garage on the same 20 amp circuit because of section (A)(2). Now after reading on non-coincidental loads I am thinking it may be allowed. Can you clarify? Chad Kennedy ---> Schneider 39. Can the light in the automatic garage door opener server as the lighting outlet required by (A)(1)(a)? Dave Mercier ---> Southwire 40. Does the NEC require a disconnect within sight of the interior unit of a listed mini split HVAC equipment that has a branch circuit supplied only to the exterior unit? Don Hursey ---> NC Educator 41. Can I sleeve romex outside in a 6 foot whip of liquid tight that runs from my exterior disconnect or panel box to the heat pump? Jeff Fecteau ---> UL 42. Is it permissible to apply the demand factors of Table for refrigerators, freezers, booster heaters and other kitchen type equipment located in breakrooms, hospital labs and other areas outside of the kitchen?

11 Jeff Sargent ---> NFPA 43. Can unit equipment emergency lights be supplied from a lighting circuit that is part of a multiwire branch circuit? The exception to (F)(2)(3) has the inspector convinced that I must pull a separate and individual branch circuit. Mike Holt ---> National Educator 44. Can the primary branch circuit equipment grounding conductor, of the wire-type, be used for both the primary equipment grounding conductor and the secondary grounding electrode conductor as permitted with Exception? Keith Lofland ---> IAEI 45. If a motor is rated 208 v and there is a delta 3 phase with a high leg that is around 208V then can one use line to neutral (208V) connection for the motor? Al Paris ---> NCBEEC 46. As a qualifier of a firm do I have to visit each site that the firm s employees have installed electrical work? Bryan Holland ---> NEMA 47. Do receptacles near aquariums in a pet or bait and tackle store require GFCI protection?

12 Chad Kennedy ---> Schneider 48. I have a disconnect at an LED driver that is behind a parapet wall out of sight from the sign it illuminates. Does the NEC require another disconnect for the LED driver circuits, where those conductors enter the sign? Dave Mercier ---> Southwire 49. Is AFCI protection require for a receptacle in an alcove of a hallway? Don Hursey ---> NC Educator 50. If the original permit did not include the replacement of the feeder- it was accidentally cut during construction- then should the electrician fail on the original permit? Or would he need another permit for the feeder? The trench was inspected with no new permit required, however the job failed based on the missing electrodes. Jeff Fecteau ---> UL 51. Can 2 equipment grounding conductors be installed in PVC to satisfy ? Jeff Sargent ---> NFPA 52. Does a hotel room with a refrigerator, cabinets and countertops, sink, coffee maker, toaster oven and microwave meet the definition for dwelling unit and therefore need two small appliance circuits?

13 Mike Holt ---> National Educator 53. Section allows multiple underground sets of service conductors, 1/0 AWG and larger, to be run to the same location and connected at their supply end but not connected at their load end to supply a building. Would this be permitted for multiple feeders run to a building? If not, why not? Keith Lofland ---> IAEI 54. Section requires all conductors of the circuit to be run in the same cable, however there is an exception in 300.3(B)(3) for non-metallic cables if you follow the rules in (B). It appears to me that I can run 2 runs of 10/2 nm to wire a 120/240v electric dryer provided they pass thru the same hole where the cables pass thru metal as in a panel. Is this correct? Of course, one conductor of a 10/2 cable would not be used. Al Paris ---> NCBEEC 55. Do contractors that install Cat 5 Cabling, Telephone and TV require an electrical license? Bryan Holland ---> NEMA 56. Does the NEC prohibit a cord and plug sump pump for an air handler in a lay-in ceiling? Chad Kennedy ---> Schneider 57. Does the NEC prohibit abandoned NM Cable in a wall?

14 Dave Mercier ---> Southwire 58. The NEC requires a laundry circuit for the receptacle required in a laundry area. If the single family dwelling does not have a laundry area, then does the code require a dedicated circuit anywhere I chose? Don Hursey ---> NC Educator 59. I need to replace an existing pool equipment panel that has a branch circuit to the pool pump Do I have to provide GFCI protection to the pool pump just for replacing the panel? What if I just need to replace the breaker for the pool pump? Jeff Fecteau ---> UL 60. Must a raceway comply with and qualify as an equipment grounding conductor when used as a wiring method for a luminaire that meets Exception No. 2 to (3) in section ? Jeff Sargent ---> NFPA 61. The NEC requires metal piping to be bonded. The NFPA requires that a fire sprinkler pipe not be used as a grounding electrode conductor. Then must the fire sprinkler pipe be bonded, and if so where? Mike Holt ---> National Educator 62. My customer wants to install a bathroom receptacle on a wall inside a cabinet that sets on top of the countertop. The receptacle is within 3 feet of the sink, but only accessible by opening the cabinet door. Would this be allowed as the required receptacle?

15 Keith Lofland ---> IAEI 63. I have 4 mobile home service pedestals within 5 feet of each other. Does the NEC allow all 4 services to share the same 2 ground rods driven? Al Paris ---> NCBEEC 64. My business is listed with the board as a part-time business. I work alone but on some projects it is difficult to work by myself. Is it ok to pay this person and give him a 1099 tax form at the end of the year? Bryan Holland ---> NEMA 65. Can NM Cable be used in straw bale construction? What if I sleeve it in PVC? Chad Kennedy ---> Schneider 66. Section requires the engineering reports be independent. What exactly does independent mean? Can the engineer who seals the design also be a subcontractor for the project s installation? Dave Mercier ---> Southwire 67. Can all the receptacles in a laundry area, including the washing machine, be on one circuit? Are they required to be on the same circuit?

16 Don Hursey ---> NC Educator 68. I have a meter panel combo outside of a home without any branch circuits. The original feeder to the inside subpanel that is protected by the main breaker was sized in accordance with (B)(7) because it is a main power feeder. I want to add a branch circuit for an irrigation system to the meter panel combo. Am I required to resize the feeder to the subpanel in accordance with (B)(16)? Jeff Fecteau ---> UL 69. Does the NEC allow the access to a junction box through a light fixture? Jeff Sargent ---> NFPA 70. Does the NEC require ground rods for pole lights? Mike Holt ---> National Educator 71. Can a 100 amp breaker protect the conductors feeding a panelboard with a 200 amp main breaker? Keith Lofland ---> IAEI 72. Does the NEC prohibit the gas line, plumbing piping, and electrical raceways or cables be buried in the same ditch? Al Paris ---> NCBEEC 73. My license is a SP-SFD license. I tried to get a permit from the local authority before I starting wiring a construction trailer for temporary use at a job site for a store building; this is just a construction trailer. Why is he not issuing me a permit for this project?

17 Bryan Holland ---> NEMA 74. Is dying concrete red to show it is a duct bank required by a Code or any other standard? Chad Kennedy ---> Schneider 75. I have a listed Power Outlet I use as a t-pole that has never been altered from its original listed design since its purchase. The duplex GFCI receptacles are not listed as weather-resistant but are in good working order. Am I now required to alter the original listing and replace the receptacles to comply with 590.4(D)(2) and 406.9(B)(1)? Dave Mercier ---> Southwire 76. Can a panelboard with circuit breakers be located in a commercial bathroom? Don Hursey ---> NC Educator 77. If a 4 wire feeder to an exterior building (shed) is replaced from the house to a junction box on the side of the shed, is the electrician responsible to add grounding electrodes to bring the shed up to code? Jeff Fecteau ---> UL 78. Can the intersystem bonding termination device be used to bond the gas line?

18 Jeff Sargent ---> NFPA 79. Does the NEC prohibit me from wiring my cabin with 24 volts? Mike Holt ---> National Educator 80. Are the platforms that surround and support a bathtub part of the bathtub or bathtub area when considering 406.9(C) and (D)? Keith Lofland ---> IAEI 81. Is the area under an open mobile home considered a dry, damp, or wet location? Does installing underpinning change the status? Al Paris ---> NCBEEC 82. My business is doing well in this area and I would like to expand my services into another city, where I would like to operate a second location. What are the Boards requirements for this new location? Bryan Holland ---> NEMA 83. Can a pull chain light fixture be installed in an attic for complying with (A)(3) if the chain is reachable from the entryway?

19 Chad Kennedy ---> Schneider 84. The utility power company brings the high-leg of the delta transformer in on the far right lug of the meter. Am I required to relocate the high-leg on the B phase? If so, at what point do I make this alteration? Should I alter anything in the meter? Dave Mercier ---> Southwire 85. If a lighting fixture requires 90 C rated wire within 6 inches of the ballast, can 75 C rated wire be wrapped in electrical tape to raise the temperature rating? If so, how many wraps? Don Hursey ---> NC Educator 86. Does moving an existing house down the street constitute upgrading the electrical to the current code? Jeff Fecteau ---> UL 87. If I have a motor that only has the UL mark and not an additional US mark in the 4 o clock position, is the motor certified to use in North Carolina? If the motor has the UL mark and an additional C in the 8 o clock position but not an additional US mark in the 4 o clock position, is the motor certified to use in North Carolina? Jeff Sargent ---> NFPA 88. Does the NEC consider an office that provided laser hair removal or injectable weight treatment a health care facility?

20 Mike Holt ---> National Educator 89. Does the NEC permit the feeder conductors from the service disconnect to pass through the meter socket enclosure for easy access to the interior wall of a building? Keith Lofland ---> IAEI 90. There is a switch located in the patient care vicinity that receives its power supply from hospital grade MC Cable. The lights the switch serves are 10 foot in the ceiling and exempt from the (B)(3). Can I supply power to the lights with regular MC Cable from the load side of the switch? Al Paris ---> NCBEEC 91. I have moved to a new address. My renewal date is in a few months. Do I still need to notify the Board of the new address? Bryan Holland ---> NEMA 92. Is a 15 amp circuit allowed to supply a switched receptacle in a dining room? What about only the top of a duplex and then allow the bottom to be non-switched? Chad Kennedy ---> Schneider 93. Section (A)(4) appears to allow the use of a AFCI receptacle within 50 feet of a typical non-afci breaker. Can you explain why the inspector says that part (d) has not been met?

21 Dave Mercier ---> Southwire 94. Section requires NM Cable be supported every 4 ½ feet and 12 inches from every box. Are those measurements the distance of wire or distance from point to point and from the box itself? Does this mean any NM Cable that gets within 12 inches from a box must be strapped? Don Hursey ---> NC Educator 95. NC has decided to amend Article 555 to exempt this Article from regulating residential applications. Does Article 682 apply to the wiring method for a residential dock? Jeff Fecteau ---> UL 96. The handicap pool lift is one example of a machine as a whole that is not typically listed by a qualified testing laboratory. However, the electrical system within the lift is listed. Do you consider equipment of this nature as complying with 110.3(C)? Jeff Sargent ---> NFPA 97. Is it compliant to fasten nm cable to the bottom of the engineered beams as shown in the photo below (between the strapping)? Assume the strapping is 1 x4 boards.

22 Mike Holt ---> National Educator 98. Can a pool heat pump be used to bond the pool water of a vinyl pool where none of the bonded parts identified in (B) are in direct connection with the pool water? Keith Lofland ---> IAEI 99. Does (A)(1) require the ground rods to be driven below the frost line? Al Paris ---> NCBEEC 100. I have a SP-PH license. When replacing an A/C unit in most cases units are more energy efficient and breaker needs to be changes to a lesser amperage than the existing unit. May I replace a circuit breaker when I rewire the appliance? Remember to Scan-Out in order to receive your Continuing Education Credit. Thank you for attending. We hope to see you next year at the 90 th Annual NC Electrical Institute April 9 th and 10 th 2019.

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004 Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004 1. A 2 PVC conduit was installed in the ground prior to setting a factory manufactured home on the foundation. The required service

More information

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

2011 and 2014 National Electrical Code Changes Residential Only

2011 and 2014 National Electrical Code Changes Residential Only 2011 and 2014 National Electrical Code Changes Residential Only Sponsored By: and.net Instructor: Fritz Gunther, Chief Electrical Inspector 585-436-4460 www.nyeia.com NEW YORK ELECTRICAL INSPECTION AGENCY

More information

Spring Test 6 due 04/26/2013

Spring Test 6 due 04/26/2013 Spring Test 6 due 04/26/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. The article that covers TV wiring installations in residences

More information

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016)

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016) Cheboygan County Department of Building Safety 870 South Main Street P.O. Box 70 Cheboygan, Michigan 49721 TX: (231) 627-8813 FX: (231) 627-8454 www.cheboygancounty.net Service Entrance ONE- AND TWO-FAMILY

More information

2009 ELECTRICAL CODE REQUIREMENTS

2009 ELECTRICAL CODE REQUIREMENTS 2009 ELECTRICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Inspection Request Line (231) 533-3510 Electrical requirements

More information

Program, Code Panel Questions, & Survey/Comments

Program, Code Panel Questions, & Survey/Comments NORTH CAROLINA ELECTRICAL INSTITUTE 90 th ANNUAL MEETING APRIL 9 th 10 th, 2019 HILTON NORTH RALEIGH RALEIGH, NORTH CAROLINA Program, Code Panel Questions, & Survey/Comments Opinions of the Code Panelist

More information

Instructor: L. Keith Lofland

Instructor: L. Keith Lofland One and Two Family Dwelling Electrical Systems 2014 NEC AFCIs, GFCIs, and Other Dwelling Unit Requirements Training Presentation by: International Association of Electrical Inspectors Instructor: L. Keith

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Residential Wiring (2014 NEC) (Homestudy)

Residential Wiring (2014 NEC) (Homestudy) Residential Wiring (2014 NEC) (Homestudy) Oregon Electrical License This course will cover the requirements in the 2014 NEC for installing electrical systems in dwelling units. Code sections for residential

More information

Residential Wiring (2017 NEC) (Homestudy)

Residential Wiring (2017 NEC) (Homestudy) Residential Wiring (2017 NEC) (Homestudy) Idaho Electrical License This course will cover the requirements in the 2017 NEC for installing electrical systems in dwelling units. Code sections for residential

More information

District 1. 1 Tony Tadysak Craig Mulder

District 1. 1 Tony Tadysak Craig Mulder STATE OF WISCONSIN Department of Safety and Professional Services 1400 E Washington Ave. Madison WI 53703 Web: dsps.wi.gov Governor Scott Walker Secretary Dave Ross Electrical Program Web: Electrical Program

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

2010 Residential Ques. & Ans.

2010 Residential Ques. & Ans. 1.I am replacing several existing receptacles in an older apartment building because they no longer hold the plug securely. Do I need to install tamper resistant receptacles? Ans. No 406.11, 210.52, Comm.

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is low voltage cable allowed to be run through drilled

More information

ll. Consistency Questions

ll. Consistency Questions Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and buildings economically viable to serve the needs of our community. We strive

More information

NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012

NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012 NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012 1. Can we install 120 Volt conductors in the same space with 277 Volt conductors? If the answer is yes, are there

More information

SW District 1. 1 Tony Tadysak Craig Mulder

SW District 1. 1 Tony Tadysak Craig Mulder STATE OF WISCONSIN Department of Safety and Professional Services 1400 E Washington Ave. Madison WI 53703 Web: dsps.wi.gov Governor Scott Walker Secretary Dave Ross Electrical Program Web: Electrical Program

More information

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 The City of Portsmouth adopts the State Building Code, which adopts by reference The National Electrical Code, 2017(NEC), as Chapter 15, Part IV, of the

More information

Residential Wiring According to the 2011 NEC

Residential Wiring According to the 2011 NEC Residential Wiring According to the 2011 NEC Utah Electrical License This course will cover the requirements in the 2011 NEC for installing electrical systems in dwelling units. Code sections for residential

More information

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod Journeyman and Master Common Exam 2 1 The grounding terminal of a grounding-type receptacle installed in a metal box shall be? A. Connected to the equipment ground B. Bonded to the box C. Connected to

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

NEC CODE QUESTIONS. Western Section IAEI 103 rd Annual Meeting September 17-19, 2007

NEC CODE QUESTIONS. Western Section IAEI 103 rd Annual Meeting September 17-19, 2007 NEC CODE QUESTIONS Western Section IAEI 103 rd Annual Meeting September 17-19, 2007 1. Can a fire pump controller be fed from a UPS? Or is a separate service and separate transfer switch required? 2. Section

More information

Residential Wiring According to 2011 NEC (Homestudy)

Residential Wiring According to 2011 NEC (Homestudy) Residential Wiring According to 2011 NEC (Homestudy) Utah Electrical License This course will cover the requirements in the 2011 NEC for installing electrical systems in dwelling units. Code sections for

More information

IEC and NCCER Mapping for Year 1

IEC and NCCER Mapping for Year 1 Craft: 26102-14 Safety IEC and NCCER Mapping for Year 1 Perform a visual inspection on various types of ladders 102.4 STATE GENERAL SAFETY CONSIDERATIONS IN ELECTRICAL INSTALLATIONS (LADDER SAFETY, SLECTION

More information

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xiii How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 1. Is a standard wire-nut approved for a wet location as in an outside j-box? Is there a listed

More information

Graded Project. National Electrical Code

Graded Project. National Electrical Code Graded Project National Electrical Code National Electrical Code INTRODUCTION This next portion of your program is a project-based assignment designed for you to demonstrate your understanding of the

More information

RESIDENTIAL OVER. 4. Would it be permissible to hard- wire the dishwasher in question 3? If so, under what conditions?

RESIDENTIAL OVER. 4. Would it be permissible to hard- wire the dishwasher in question 3? If so, under what conditions? WELCOME TO THE EASTERN SECTION CODE BREAKFAST CODE BREAKFAST QUESTIONS FOR THE EASTERN SECTION ANNUAL MEETING 93 rd ANNUAL EASTERN SECTION MEETING, KING OF PRUSSIA, PA RESIDENTIAL ALL QUESTIONS BASED ON

More information

SDEC 2017 Questions, Group 1

SDEC 2017 Questions, Group 1 SDEC 2017 Questions, Group 1 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing? Answer: NEC 410.36(B)

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016 IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS June 17th, 2016 RE: City Council Adopts 2014 National Electrical Code with Pool Alarm Requirements On April 25th, 2016 the

More information

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA American Electrical Institute 2014 PART 2 83 CONTINUING EDUCATION FOR OREGON ELECTRICIANS AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 www.aeitraining.com 84 PART 3 American Electrical

More information

2009 WESTERN SECTION CODE PANEL QUESTIONS

2009 WESTERN SECTION CODE PANEL QUESTIONS 2009 WESTERN SECTION CODE PANEL QUESTIONS 1. The local inspector red-tagged the temporary wiring for a new store of type III construction because he said Romex wasn t allowed to be run in the open according

More information

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations... Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

Overview of Significant 2017 NEC Changes

Overview of Significant 2017 NEC Changes Overview of Significant 2017 NEC Changes National Fire Protection Association. All rights reserved. Five New NEC Articles Article 426 Fixed Resistance and Electrode Industrial Heating Equipment Article

More information

NEC Study Guide CORRECT: C NEC (A)(1)

NEC Study Guide CORRECT: C NEC (A)(1) 1 According to the NEC, the maximum distance from the point of entrance to the building that the water pipe may be used as a grounding electrode interconnect is: A. 3' B. 4' C. 5' D. 6' CORRECT: C NEC

More information

Revisions for the 2011 National Electrical Code - Part 1

Revisions for the 2011 National Electrical Code - Part 1 PDHonline Course E355 (3 PDH) Revisions for the 2011 National Electrical Code - Part 1 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &

More information

A HOMEOWNERS HANDBOOK

A HOMEOWNERS HANDBOOK ELECTRICAL A HOMEOWNERS HANDBOOK By Everett H. Rawlings Electricity in the home plays a critical role in our lives. From activating our alarm clock in the morning to all aspects of our lives for the rest

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

2017 NEC Presented by: Russ LeBlanc

2017 NEC Presented by: Russ LeBlanc 2017 NEC Presented by: Russ LeBlanc 1. 90.2(A)-installation and removal 2. 90.3-code layout 3. 100-readily accessible 4. 100-field evaluation body (FEB) 5. 100-field labeled 6. 100-receptacle 7. 100-structure

More information

TABLE 1-E (2017) Effective July 1, 2017

TABLE 1-E (2017) Effective July 1, 2017 TABLE 1-E (2017) Effective July 1, 2017 Oregon Amendments to the 2017edition of the National Fire Protection Association (NFPA) 70, National Electrical Code (NEC) for the 2017 Oregon Electrical Specialty

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

TOM BURNS, PLANNING DIRECTOR

TOM BURNS, PLANNING DIRECTOR ~~ 0 173 COUNTY OF SANTA CRUZ August 4,2005 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR Agenda:

More information

The Association of Electrical and Medical Imaging Equipment Manufacturers Arc Fault Circuit Interrupter

The Association of Electrical and Medical Imaging Equipment Manufacturers Arc Fault Circuit Interrupter Arc Fault Circuit Interrupter SUCCESS STORIES AFCIs avert potential disaster in South Carolina I would like to take the time and thank you for the Arc Fault breaker, your product saved our lives and our

More information

INSTALLATION AND OPERATING INSTRUCTIONS. For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK

INSTALLATION AND OPERATING INSTRUCTIONS. For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK INSTALLATION AND OPERATING INSTRUCTIONS For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK Congratulations on your purchase of the Reliance Controls Generator Power Transfer

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

Inspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013

Inspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013 Inspection Report Prepared for: Tonia Mann Property Address: 402 Leslie Court McDonough, GA 30253 Date: March 07, 2013 Inspector: Charles Mann Edifice Inspections, Inc. (770) 594-2222 www.edificeinspections.com

More information

TECHNICAL ARTICLE. Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009

TECHNICAL ARTICLE. Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009 TECHNICAL ARTICLE Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009 Many inspectors were contractors in some prior life. The progression from contractor to inspecting

More information

Axiom Property Inspections

Axiom Property Inspections Cover Page Axiom Property Inspections Property Inspection Report 868 Wally Avenue, Henderson NV, 89178 Inspection prepared for: John Doe Agent: David Lawson - Axiom Inspection Date: 8/12/2010 Time: 2:30

More information

Troy's Home Inspection Services LLC

Troy's Home Inspection Services LLC Cover Page Property Inspection Report 33706 Inspection prepared for: Cord King & Patricia King Real Estate Agent: Jane Freel - RE/MA Date of Inspection: 3/4/2017 Time: 8:30 Age of Home: 2008 Size: 3279

More information

This Report Was Prepared For: Property Address Inspected:

This Report Was Prepared For: Property Address Inspected: This Report Was Prepared For: Jane Do (to protect the identity and privacy of our clients) Property Address Inspected: 321 Sample Dr Example Report, FL 32828 Date: August 11, 2115 File # H50855255 The

More information

INDEX. Page 2 to 7 Electrical Specifications. Page 8 Electrical Schemes: Basement Plan. Page 9 Electrical Schemes: First Floor Plan

INDEX. Page 2 to 7 Electrical Specifications. Page 8 Electrical Schemes: Basement Plan. Page 9 Electrical Schemes: First Floor Plan 30 Greenway, NW Suite 11 Glen Burnie, Maryland 21061 tel 410.528.8899 fax 410.558.6312 www.gbalternatives.com INDEX Page 2 to 7 Electrical Specifications Page 8 Electrical Schemes: Basement Plan Page 9

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

PROPERTY REINSPECTION REPORT

PROPERTY REINSPECTION REPORT PROPERTY REINSPECTION REPORT Prepared For: Andrew Xia Address: 1078 Great Meadow Dr. Allen, TX 75013 By: Robert Taylor, TREC license # 3619 Date: 10/27/2014 The Three Page Visual Contract Agreement previously

More information

Page 1 of General

Page 1 of General Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors

More information

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST Plan Check No. Plan Check Expiration Date Job Address: Square Footage Use Zone Fire Zone Occ. Group Type of Construction No. of Stories Applicant Phone

More information

Units 2, 3, 4, 5, 6, 8, 9, 10, Electrical Wiring Residential Unit 2 (Unit 5 Fourth Edition)

Units 2, 3, 4, 5, 6, 8, 9, 10, Electrical Wiring Residential Unit 2 (Unit 5 Fourth Edition) Units 2, 3, 4, 5, 6, 8, 9, 10, 11-22 Electrical Wiring Residential Unit 2 (Unit 5 Fourth Edition) 1. What is an outlet? Point on a wiring system where current is taken to supply utilization equipment 2.

More information

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Suppression Systems; and Chapter 34-National Electric

More information

Inspection Report. Mr. Happy Homeowner. Property Address: Focal Point Home Inspection Ltd.

Inspection Report. Mr. Happy Homeowner. Property Address: Focal Point Home Inspection Ltd. Page 1 of 19 Inspection Report Mr. Happy Property Address: Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Page 2 of 19 Table of Contents Cover Page Table of Contents

More information

FAIRA TRANSPARENCY REPORTS th Ave NE B-3, Kenmore, WA March 28 th, 2017

FAIRA TRANSPARENCY REPORTS th Ave NE B-3, Kenmore, WA March 28 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 17817 80th Ave NE B-3, Kenmore,

More information

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc Inspection Report 1 Inspection Way Orlando, FL 32825 Prepared for: Wanda Figueroa Prepared by: Page 1 of 25 Needs Service Summary This summary is not the entire report. The complete report may include

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

WIRING AND PROTECTION

WIRING AND PROTECTION 5997ch02.qxd_mg_cc 4/6/05 12:42 PM Page 5 2 WIRING AND PROTECTION (Excerpts from Chapter 2) 210.1 Scope ARTICLE 210 BRANCH CIRCUITS I. General Provisions Article 210 applies to all branch circuits except

More information

2014 National Electrical Code & NFPA 70E/Arc Flash

2014 National Electrical Code & NFPA 70E/Arc Flash Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

Electrical Program. Electrical Laws & Rules. Electrical RCW WAC B. Permits Inspections Access Description Directions Comments.

Electrical Program. Electrical Laws & Rules. Electrical RCW WAC B. Permits Inspections Access Description Directions Comments. Electrical Laws & Rules Licensing Electrical Work Scope Administrator Duties Certification Supervision RCW 19.28 WAC 296-46B Permits Inspections Access Description Directions Comments Electrical Program

More information

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults? RECEPTACLEFAQs AFCI 1 What is an arc fault? UL provides a definition for an arc fault in UL 1699 (Standard for Safety Arc Fault Circuit Interrupters). It is an unintentional arcing condition in a circuit.

More information

FAIRA TRANSPARENCY REPORTS NE 117th Pl, #F8, Kirkland, WA 98034

FAIRA TRANSPARENCY REPORTS NE 117th Pl, #F8, Kirkland, WA 98034 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 12527 NE 117th Pl, #F8, Kirkland, WA 98034 Thank you for your interest in this Faira Certified

More information

National Electrical Code Forum. Your Questions Answered

National Electrical Code Forum. Your Questions Answered National Electrical Code Forum Your Questions Answered Meet Your Distinguished Experts Moderator: Lloyd Osborn- Cheyenne, Wyoming Tom Lichtenstein Republican Organizer-Chicago, IL Tim McClintock NFPA Regional

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL

More information

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on HOME PROPERTY SCAN INSPECTIONS The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on January 11, 2010 and

More information

Revisions for the 2011 National Electrical Code - Part 4

Revisions for the 2011 National Electrical Code - Part 4 PDHonline Course E358 (3 PDH) Revisions for the 2011 National Electrical Code - Part 4 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

Electrical Essentials corrected calculation slides only

Electrical Essentials corrected calculation slides only Electrical Essentials corrected calculation slides only IAEI Southern Nevada Chapter/Educode 2015 Electrical Theory 1 Feeders and OCP 5 NEC Structure 2 Service and Grounding 6 Print Reading 3 Fault Current

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE

SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE ELECTRICAL CODE COMMITTEE SEPTEMBER 12, 2012 PREFACE This document was developed by the Southern Nevada Building Officials Electrical

More information

SAN JOAQUIN COUNTY ELECTRICAL PLAN CHECK CORRECTION SHEET (209) FAX (209)

SAN JOAQUIN COUNTY ELECTRICAL PLAN CHECK CORRECTION SHEET (209) FAX (209) SAN JOAQUIN COUNTY ELECTRICAL PLAN CHECK CORRECTION SHEET (209) 468-2098 FAX (209) 468-9907 PERMIT NO: DATE: PROJECT: APPLICANT: OWNER: PHONE #: PHONE # JOBSITE ADDRESS: CHECKED BY: KERMIT L. DARROW, AIA-E

More information

ELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES

ELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES ELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES Review Guide for: Hospitals Nursing Facilities Clinics Office of Statewide Health Planning and Development Facilities Development Division www.oshpd.ca.gov

More information

GE Industrial Solutions. Residential Electronic Circuit Interrupters

GE Industrial Solutions. Residential Electronic Circuit Interrupters GE Industrial Solutions Residential Electronic Circuit Interrupters Dual Function Circuit Interrupter (DFCI) Provides ground fault and arc fault circuit protection in one unit The 2014 National Electric

More information

Inspector Gadget Homes

Inspector Gadget Homes Cover Page Inspector Gadget Homes Property Inspection Report 34105 Inspection prepared for: Mike Cranley Date of Inspection: 3/20/2017 Time: 5:30pm Age of Home: 25 yrs old Size: 3,039 sq ft Weather: Sunny

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

Subpanels. Bring Big Amps to Distant Spaces. A subpanel is a secondary breaker box BY CLIFFORD A. POPEJOY

Subpanels. Bring Big Amps to Distant Spaces. A subpanel is a secondary breaker box BY CLIFFORD A. POPEJOY Subpanels A subpanel is a secondary breaker box Instead of originating at the main service panel, electrical circuits can begin at a nearby subpanel that is powered from the main panel through one heavy-gauge

More information

Sundance Spas SPA EQUIPMENT SYSTEM. Installation Instructions. P/N Rev. A

Sundance Spas SPA EQUIPMENT SYSTEM. Installation Instructions. P/N Rev. A Sundance Spas SPA EQUIPMENT SYSTEM Installation Instructions P/N 6530-456 Rev. A Contents Important Notices 1 Important Safety Instructions 2 Where to Place the Equipment System 3 Connecting Pipes Between

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

BUILDER S PRE-INSPECTION CHECKLIST

BUILDER S PRE-INSPECTION CHECKLIST Warrenton Fire Protection District 606 Fairgrounds Rd. Warrenton, MO 63383 Ph: 636-456-8935 Fax: 636-456-7764 www.warrenton-fire.org BUILDER S PRE-INSPECTION CHECKLIST This checklist is designed as a general

More information

Mechanical Systems Submittal Guide

Mechanical Systems Submittal Guide 5200 Dover Center Road 440-777-8000 North Olmsted, OH 44070 North-Olmsted.com Mechanical Systems Submittal Guide Residential Code of Ohio (RCO) n applicant is free to submit any mechanical systems description

More information

I. STRUCTURAL SYSTEMS

I. STRUCTURAL SYSTEMS I. STRUCTURAL SYSTEMS A. Foundations Type of Foundation(s): Pier & Beam - Crawlspace Opinion: All exposed areas of the foundation were examined visually. Examination of the foundation was limited to photographs

More information

HVAC Equipment Access Equipment Location

HVAC Equipment Access Equipment Location City of Lancaster- Building Department 121 East Chestnut Street, Suite 102, Lancaster, Ohio 43130-3825 (740) 687-6649, Fax (740) 681-5030 Web site: www.ci.lancaster.oh.us/dept/building HVAC Heating, Ventilating,

More information

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General ARTICLE 760 Fire Alarm Systems Introduction to Article 760 Fire Alarm Systems Article 760 covers the installation of wiring and equipment for fire alarm systems, including all circuits controlled and powered

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA 27966 Thackeray Avenue/ Mail address Hayward, Calif. 94544 2011 150TH AVENUE SAN LEANDRO, CALIFORNIA 21:12 August 07, 2015 Page 1 of 11 Table of Contents Definitions 2 General Information 2 Lots and Grounds

More information

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices. SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance

More information