1 CHILLER CWS AQUACONTROL Modelli CWS BASIC INSTALLATION MANUAL USAGE AND SCHEMATICS A /10/2012 COMPANY WITH QUALITY SYSTEM CERTIFIED BY DNV =ISO 9001/ /2008 = ISO VECO S.p.A. via Cantore 6, Giussano (MB)(MI)ITALY Italy ViaCantore,6/ Giussano Phone Fax info@veco.net Web:

2 1 ELECTRICAL CONNECTIONS 1.1 POWER SUPPLY All the electrical connection must be carried out by technicians and must follow the security guidelines of the country where the system is installed. System must be grounded through a properly dimensioned cable. System power supply cable must be correctly dimensioned to maximum power allowed by the system components. The same must be done for the pumps' power supply cable. System power supply bust be handled by an automatic switch. Before any maintenance, power supply must be switched off completely from the system. 1.2 ELECTRICAL CONNECTION OF THE SYSTEM COMPONENTS Electrical connections inside the system electrical box must be carried out as in schema C312 (electrical schematics is in the attachment CWS AQUACONTROL POWERBOARD CONNECTIONS ). 2 SEA WATER CIRCUIT 2.1 SEA WATER PUMP Sea water pump is necessary to allow sea water circulation in the correct quantity through the heat exchanger. Therefore sea water pump has to be silent, able to work continuously and built with water resistant material. 2.2 SEA WATER PUMP POSITION A Pump must be installed orizontally, with the water exit on the top. Pump must be installed minimum 0,50 meters under the sea level. C Sea water tap, the filter and the pump must be connected without siphons; the hose must always go up; from the sea water tap to the pump. 0,5 m D The hose from the sea water tap to the pump must the the shortest possible. The sea water circuit will not work well if the hose is longer then 1 meter. B Sea water intake has to be oriented towards the prow. PROW E In order for the pump to run correctly, the hose exiting the pump has to be vertical for at least 25 cm (10 inc.). STERN

3 2.3 PUMP INSTALLATION The sea water pump has to be fixed with screws using the existing holes in the base of the pump or the special fixing base available for small pump models. For bigger pumps, we suggest to mount them on silentblock. 2.4 SEA WATER CIRCUIT The sea water circuit must always have a positive slope from the sea water intake to the heat exchanger. After the heat exchanger, there is no specific requirement for the circuit slope. The sea water out must be installed to avoid noises for the boat itself and for the boats around.

4 3- FAN COILS' FRESH WATER CIRCUIT 3.1 FRESH WATER CIRCUIT CONNECTIONS Follow the installation diagrams. It's important to follow the instruction about the direction and position of all the system components. To allow an easy maintenance, make sure all the components are accessible. For all components strictly follow the indication about water flow direction. Leave access to the air outlet valve on the fresh water circuit. Follow the nominal diameter of the collector and leave the collector accessible, with the air outlet valve on the top. If installed, check that every control valve is completely open. Follow the schematics for the expansion tank. The connection door has to be on the top to allow drainage. Follow the schematics for the fresh water pump. Fresh water circuit has to be the shortest and the simplest as possible; each single top point in the circuit has to have an air outlet valve. Avoid siphons and avoid slopes in the fresh water circuit because they may create problems while emptying the fresh water circuit from air. For each fancoil, follow the water flow direction indicator. Each fan coil has an air outlet valve that must be accessible during installation and also during maintenance. 3.2 FLOW METER (OPTIONAL) Flow meter has to be installed on the fresh water circuit. It has to be accessible for maintenance and for calibration. The flow meter switch is an additional safety equipment that will stop the system whenever the fresh water flow stops or if it is not enough. The flow meter switch has to be electrically connected to the electrical box of the fan coil as specified in the electrical schematics. 3.3 PRESSURE IN THE FRESH WATER CIRCUIT The pressure gauge kit installed on the fresh water circuit has 2 point of access to the circuit (H-H1). Each point has a manual valve and an automatic one-way valve that block the water in the circuit to go into the pressurize sanitary water circuit in case of any error. Use one of the 2 valves and the pressure gauge in order to pressurize the circuit with fresh water at 1,5 Bar; this valve must be permanently connected to the water sanitary circuit in the boat. Check that the fresh water circuit pressure remains the same over the time, which means that it has no leaks. If the leak check is successful, remove some water from the circuit to leave some space and add anti-freezing liquid to the circuit. 3.4 ANTIFREEZE LIQUID Following two methods are suggested in order to add to the circuit antifreeze liquid. a) Calculate the circuit capacity and fill it with a mix of water (80%) and antifreeze (20%), using the second valve by gravity or with a pressure pump. Connect the fresh water circuit to the water sanitary circuit and pressurize it until 1,5 Bar; then start removing the air from the circuit. If there is a lot of air that has to be removed from the circuit, it will be necessary to add more liquid to it; remember to add 80% water and 20% antifreeze. b) Completely empty the circuit after the leak check. Prepare the necessary quantity of liquid (80% water and 20% antifreeze) and fill up the circuit using a pressure pump. After the circuit is full, remove all the air in it and then fill it up again with the same liquid.

5 3.5 AIR REMOVAL FROM THE FRESH WATER CIRCUIT When the circuit is under pressure and already contains the antifreeze, follow these instructions to remove air from the circuit. The air must be completely removed from all the access points of the circuit (collectors, fan coils and all the other system components) starting from the lowest point and maintaining the pressure at 1,5 Bar. This must be done without using the pump. Continue to remove air from each single access point of the fresh water circuit until no air exits anymore, always maintaining the pressure at 1,5 Bar. Switch off the chiller completely (compressor) and check that the sea water intake is open. Start the system (compressor) in COOL mode. Both the pumps (sea and fresh water) will start. Leave the fresh water pump working for 30 seconds, then shut down the system completely again and start with the previous procedure to remove air from each access point to the fresh water circuit, always maintaining the pressure at 1,5 Bar. Air removal is complete when no more air exits from the access points and the fresh water pump works with no problem and with no noise. We strongly advise to install in the fresh water circuit a deaerator, right after the pump water exit. The deaerator will reduce almost to zero the need of removing air from the circuit. Deaerator is available in different measures depending on the size of the fresh water circuit. 3.6 FAN COILS FRESH WATER CIRCUIT

6 3.6 FAN COILS FRESH WATER CIRCUIT

7 4- SYSTEM STARTUP 4.1 FRESH WATER CIRCUIT Important: the fresh water flow must be calibrated with respect to the fan coil and system capacity. Verify that the flow is greater or equal to the capacity specified in the chiller. Compressor, therefore the chiller unit, cannot work without the fresh water circuit. If the flow in the fresh water circuit is not sufficient, the evaporator of the chiller unit can freeze and can even bring the system to break. Following guidelines can avoid damage to the system due to insufficient water flow. A) ANTIFREEZE LIQUID fresh water circuit needs to be filled with water (80%) and antifreeze (20%). Antifreeze will low the water freezing point, making the water not freezing. Even if the water freeze, the mix of water and antifreeze will be more soft and it is harder for this kind of ice to damage the system. Antifreeze also reduces the corrosion inside the fresh water circuit. Always check that the pressure gauge is showing 1,5 Bar in the fresh water circuit. B) FLOW METER SWITCH (Optional) The flow meter stops the system when the fresh water flow is under the safety threshold. As described in chapter 3.2, the flow meter switch is installed on the outgoing collector of the circuit. Make sure that the flow meter is correctly connected to the control box. To test it, simulate e low flow situation pressing the lever inside the protection of the switch. Attention: the flow meter switch is connected to the main electrical box and all the checks and connection have to be done by professional personnel taking all the safety precaution required. 4.2 START UP Power up the main control box Set the MODE switch on COOL or HEAT Check that the sea water intake is completely open Check that the pumps water flow is enough (both sea and fresh) When the compressor is running, fresh water temperature will start cooling down (if COOL mode) or heating up (if HEAT mode); when the temperature will reach the set value (+12 C in COOL mode, +40 in HEAT mode) the thermostat will shut down the compressor. The time that the fresh water takes to reach the set point depends from different things: the number and the capacity of the fan coils, the speed of the fan coils, the ambient temperature, therefore it is not possible to specify in how much time the temperature will reach the set point. 4.4 FAN COIL Check that the fresh water reaches each single fan coil. Measure the ingoing and the outgoing water temperature; the difference has to be between 5 and 10 C. If the difference is more, it probably means that there is still air in the circuit and that the flow in the fan coil is too slow. In case of very long fresh water circuits, it is suggested to regulate the fan coil water flow calibrating valves, closing the ones more close to the collector, in order for the water to reach the most far away fan coils. Check that the thermostat sensor is correctly positioned where the air enters in the fan coil. If the temperature control is on FAN ONLY, the thermostat stops the fan when the air temperature reaches the set point. IMPORTANT: The temperature sensor has to be positioned where the air enters in the fan coil, not on the fan coil itself. If the fan coil control is on WATER VALVE, the thermostat closes the water valve connected to the fan coil while the fan continues to work. In this case the sensor has to be on the fan coil, fixed to the apposite platelet.

8 5- OPERATING INSTRUCTION 5.1 CHILLER START UP Rotate the switch MODE on the electrical box of the chiller on HEAT, to run in heat mode, or COOL, to run in cool mode. The system will start and the compressor will start operating. 5.2 CHILLER SHUT DOWN Rotate the switch MODE on OFF. 5.3 PUMP Both the sea water pump and the fresh water pump start when the switch is moved on COOL or HEAT. IMPORTANT: Both pumps will run even if the thermostat stops the compressor. 5.4 FAN COIL CONTROL Each cabin's temperature is monitored by a thermostat that controls the fan's speed. The thermostat is connected to the display in each single room. Display can be mechanical (Fig.1) or digital (Fig.2). Please refer to the mechanical panel or to the digital display instruction for more information. Fig.1 Mechanical panel. Fig.2 Digital display Vega MKII. 6 - MAINTENANCE 6.1 CHECKS BEFORE RUNNING THE SYSTEM Before turning the system on, check that the pressure in the fresh water circuit is between 1,5 and 2 Bar (21-28 PSI). Use a pressure gauge. If the fresh water circuit pressure goes below the safety threshold, the circuit needs to be repaired, fixing every leak. Continuously adding water to the circuit is not a solution since the antifreeze quantity will go below 20%. The liquid in the circuit must be checks at least every to years, more frequently if there are leaks. Liquid inside the fresh water circuit must be 80% water and 20% antifreeze (Glicole for example) Check frequently also the sea water circuit: Check the sea water filter and clean it frequently Measure and check the water flow coming out from the sea water drain Always have a spare gasket (packing gland) for the sea water pump and one for the fresh water pump. Clean and substitute the air filters for every fan coil. A dirty air filter reduces dramatically the air flow, reducing the fan coil efficiency. At the beginning of the summer season, check that every fan coil drain is clean and that it drains correctly. Consider that when humidity and temperature are high the condense can reach 1 litre/hour for each fan coil. When the system was stopped for a long period, before starting it, it is suggested to manually check the pumps, removing the back cover cap and manually rotating the cooling fan inside the pump. IMPORTANT: Be sure to correctly fix the back cover cap correctly before running the pump at the end of the maintenance.

9 7 TROUBLESHOOTING 7.1 CENTRAL UNIT - CHILLER AQUACONTROL The central chiller unit problems can be caused by: Insufficient sea water flow in the sea water circuit. This can be checked by looking at the sea water drain. Running the system with an insufficient sea water flow can damage the central unit. In case of any doubts, check the sea water circuit and pumps while the all system is shut off. Low power supply. Insufficient voltage to the system can damage the electrical parts and the compressor itself. 7.2 FAN COILS If the fan of the fancoil is not working, check that the control panel of the fan coil is set to the correct mode ( COOL in the summer and HEAT in the winter) and that the thermostat is at the minimum temperature in the summer and in the maximum temperature in the winter. Check the power supply. Check if the voltage is correct after setting the fan coil to the maximum speed. Voltage must be 230V. If voltage is correct, the fan engine may be broken and it has to be replaced. In order to get the correct spare part from the Veco Customer Service, provide us with all possible details of the fan coil and on the engine. Please note that the fan coil engine needs a specific condenser that is installed in the control box. 7.3 TROUBLESHOOTING FRESH WATER CIRCUIT DOES NOT COOL (in cool mode) SEA WATER PUMP AND FRESH WATER PUMP If pumps do not run, check power supply. COMPRESSOR IT IS WORKING BUT IT DOES NOT COOL The gas charge may not be enough. Check and recharge the gas circuit after repairing the leak. IT IS NOT WORKING Check the switch MODE, if it's OFF switch it on COOL IF THE SET POINT THERMOSTAT > +12 C Set the Set Point to + 12 C. If the compressor still does not work: IF THE RELAY IS OPEN Compressor relay is broken, substitute the compressor relay. IF THE RELAY IS CLOSED COMPRESSOR POWER SUPPLY IS WORKING Check and eventually substitute the compressor. COMPRESSOR POWER SUPPLY IS WORKING Check the compressor electronics. 7.4 TROUBLESHOOTING FRESH WATER CIRCUIT DOES NOT HEAT (in heat mode) SEA WATER PUMP AND FRESH WATER PUMP If pumps do not run, check power supply. COMPRESSOR IT IS WORKING BUT IT DOES NOT COOL The gas charge may not be enough. Check and recharge the gas circuit after repairing the leak. IT IS NOT WORKING Check the switch MODE, if it's OFF switch it on HEAT IF THE SET POINT THERMOSTAT < +40 C Set the Set Point to + 40 C. If the compressor still does not work: IF THE RELAY IS OPEN Compressor relay is broken, substitute the compressor relay. IF THE RELAY IS CLOSED COMPRESSOR POWER SUPPLY IS WORKING Check and eventually substitute the compressor. COMPRESSOR POWER SUPPLY IS WORKING Check the compressor electronics.

10 8 TECHNICAL DATA 8.1 CONDENSERS Condenser table for each fan coil. Codici ELECTRICAL BOXES FOR FANCOILS FAN CODE Condensers' codes. Codici CONDENSER CODE

11 C312 - CWS AQUACONTROL POWERBOARD CONNECTIONS COMPRESSOR MAINS SUPPLY 230/1/50-60 Ø = 3 x 2,5 mmq C Reverse Cycle Valve (RCV) (Up to 10 mt) Sea Water Pump Fresh Water Pump S R CM FUSE 250V 6,3A Compressor Neon Led RCV Neon Led Sea Pump Neon Led Fresh Pump Neon Led Flat Cable IMPORTANT NOTE: Local control shows/ sets temperatures, parameters, setpoints, alarms but can t switch on/off the system. To switch on/off CWS system need to use mecanical panel or touch screen Local Display LD1 BLINKING: Serial Communication Working LD2 OFF: No devices to communicate with or communication problems AQUACONTROL BASIC POWERBOARD Cod. M74330 ON S SW1 LD3 ON: LPS OPEN (Low Pressure Alarm) LD3 OFF: DEVICE OK LD2 ON: HPS OPEN (High pressure Alarm) LD2 OFF: DEVICE OK LD4: NOT USED WHITE (COM) BLUE (COOL) PWM SIGNAL (NOT USED) RS 485 Modbus ORANGE (HEAT) GND DELAY * DIP SWITCH LEGEND 1 ON / 2 OFF = Reverse Cycle 1 OFF / 2 ON = Cool Only Switches 3-4 are not used INVALID SETTING display:off* To see setted configuration press Arrow down 5 time (till CON is shown on display) then press S to enter and see system configuration. CANL (-) CANH (+) TOUCH SCREEN Mec. RC Panel COOL Return Fresh Water Temp Anti Freeze Temp (Aft) Supply Sea Fresh Water Water Temp (St) Temp (SEA) (OPTIONAL) (OPTIONAL) OFF HEAT PC SUPERVISOR Mec. CO Panel COOL OFF Cod.M79290 C312 WHITE (COM) HPS FS (High Pressure Switch) LPS (Flow Switch) (Low Pressure Switch) BLUE (COOL) Cod.M78610CO

CWS AIR-CONDITIONERS

CWS AIR-CONDITIONERS CWS AIR-CONDITIONERS MODUL & MODUL XL INSTALLATION, OPERATION AND MAINTENANCE MANUAL MODUL_GB_2007.doc page 1 of 28 10/04/07 CWS air-conditioners 1 - Installation CONTENTS 1 Installation 2 Commissioning

More information

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table) 1 2 Warning: - Do not place your hand or any other objects into the air outlet and fan. It could damage the heat pump and cause injuries; - In case of any abnormality with the heat pump, cut off the power

More information

Rev B, 9/2/2009. Kodiak Chiller Overview

Rev B, 9/2/2009. Kodiak Chiller Overview 930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part

More information

CONTROL PANEL INSTRUCTIONS RSQ-4

CONTROL PANEL INSTRUCTIONS RSQ-4 CONTROL PANEL INSTRUCTIONS RSQ-4 FOR SIRAC AIR TO WATER HEAT PUMP (SINGLE COMPRESSOR, AIR TO WATER) 1) System Configuration This system is composed of mainboard and wire control panel. 146mm Φ4 4 Mainboard

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7

More information

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA. OWNER S MANUAL Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750 Proudly Made in the USA support@aquacomfort.com 888-475-7443 Manufacturing High Quality, High Efficiency Heat

More information

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS Note: This manual may also be used for 6536-871 series heat pumps if the 6535-3209 Replacement

More information

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA OWNER S MANUAL Models: AC110, AC125, AC150 made from 2003 through 2010 Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support/ (888) 475-7443 Manufacturing High Quality,

More information

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS HP727S Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS 1. General Description 2. Specifications 3. Installation Instructions 4. Electrical Wiring 5. Instrument Wiring

More information

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO 06-10616. File name: URS-1 Service Manual up to 06-10616 Last revised: Jan. 30th 2009 TROUBLESHOOTING AND SERVICE GUIDE: The following is intended as

More information

Vega MK 3. Instruction and Operation Manual. Annapolis MD USA

Vega MK 3. Instruction and Operation Manual. Annapolis MD USA Vega MK 3 Instruction and Operation Manual Annapolis MD USA www.veco-na.com MK3 is a control system with innovative features for Climma independent units: a) Large digital display b) Simple settings by

More information

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA OWNER S MANUAL Vintage Classic HEAT COOL models Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support 888-475-7443 Manufacturing High Quality, High Efficiency Heat Pump

More information

Owner s Manual PRINTED IN CANADA 05/2009

Owner s Manual PRINTED IN CANADA 05/2009 Owner s Manual PRINTED IN CANADA 05/2009 Table of contents Introduction 2 General Safety Instructions 4 Installation Instructions Location 6 Water piping 7 Electrical 7 Bonding 8 Bonding and plumbing

More information

Q&A 2016 Practical Guide

Q&A 2016 Practical Guide Q&A 2016 Practical Guide A guide made to help you! Do not hesitate to consult this Q&A before sending a service call request to Waterco Canada Inc. Service: 450.748.6002 / 1.888.796.6002 Fax: 450.748.4365

More information

REMOTE CONTROL FOR CHILLER MYCHILLER

REMOTE CONTROL FOR CHILLER MYCHILLER REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS Page 1 of 10 THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS Purpose of Manual The purpose of this manual is to provide operating, servicing and repair instructions for the Summit standard models ThermaPhase

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

RCS Residential Control Systems Inc.

RCS Residential Control Systems Inc. RCS Residential Control Systems Inc. Model TZ16 Z-Wave Communicating Thermostat with Rev P HVAC Control Unit INSTALLATION AND OPERATION MANUAL DCN: 141-00882 Rev 02 5/18/06 This manual applies to the following

More information

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1-316-832-4357

More information

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start Mokon Troubleshooting Guide Model 311 Process pump will not start Process pump shuts down during operation Pump seal leak Tank overflows or will not fill on systems with autofill option (water makeup valve)

More information

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB R407C EASY_R Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans 5,2 41,5 kw T_ESY_R_0508_GB EASY_R R407C INDEX WORKING LIMITS... 3 SERIES IDENTIFICATION... 4 MODEL

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL DATE OF PURCHASE: MODEL: SERIAL NO.: Record above information from nameplate. Retain this information for future reference.

More information

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort User manual CLIMATIC 2/4 - Controller Providing indoor climate comfort MUL35E-56 9-26 INDEX CONTENTS PAGE INDEX 1 GENERAL DESCRIPTION 2 THE KEYPAD, Climatic 2 3 THE KEYPAD, Climatic 4 4 THE KEYPAD REMOTE

More information

SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL

SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL MODEL AT105 AT115 AT130 with Titanium Heat Exchanger 2213 Andrea Lane Ft. Myers FL 33912 888-297-3826 941-482-0606 www.aquathermheatpumps.com DIGITAL

More information

BasicTroubleshooting Information and Guidelines

BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines Information and Guidelines May 2017 BasicTroubleshooting PRIOR TO CONTACTING CLIMATEMASTER TECHNICAL SUPPORT,

More information

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions. User Manual for model FLOWMAX-90 Condensing water heater 85,000 BTU WARNING If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal

More information

Owners Manual Refrigerated Air Dryer MHT SERIES

Owners Manual Refrigerated Air Dryer MHT SERIES Owners Manual Refrigerated Air Dryer MHT SERIES IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS IN- FORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILAR WITH THE PROPER INSTALLATION

More information

Rif Cod i220-0

Rif Cod i220-0 15 52 50 6 13 53 51 2 9 8 3 20 19 18 5 1 7 14 10 4 17 Rif Cod 1 0010060 2 0060287 3 0060310 4 0080003 5 0080004 6 0080051 7 0080053 8 0080410 9 0080413 10 0080430 11 0080432 12 0080434 13 0080435 14 0080436

More information

Dough Retarder Prover. Service Manual

Dough Retarder Prover. Service Manual Service Manual Revision 3 June 2000 Dough Retarder Prover - Service Manual RBC MKII Controller Revision 6 Page 2 CONTENTS Page(s) 1. INTRODUCTION 3 2. RBC MK 2 CONTROLLER OPERATION 5-9 Process Cycle Overview

More information

CONTENTS. 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling

CONTENTS. 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling CONTENTS 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling 6. Installation 6.1 Plates 6.2 Dimensions 6.3 Location 6.4 Free room 6.5 Installation

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

Note: before using the system read this manual carefully, store it and, in case, transfer it to a new user. prima

Note: before using the system read this manual carefully, store it and, in case, transfer it to a new user. prima page 1 Note: before using the system read this manual carefully, store it and, in case, transfer it to a new user. prima No-idle auxiliary battery operated air con PICCOLO SPLITTER Model PS3000 MY2012

More information

CHILLER. Model CH3000. Operator s & Installation Manual

CHILLER. Model CH3000. Operator s & Installation Manual CHILLER Model CH3000 Operator s & Installation Manual Release Date: February 14, 2011 Publication Number: 620054173OPR Revision Date: May 08, 2014 Revision: B Visit the Cornelius web site at www.cornelius.com

More information

Operating Functions Temperature Parameters

Operating Functions Temperature Parameters Operating Functions Temperature Parameters Room set temperature (T set) Room ambient temperature (T amb) Fundamental Functions After powered on, no matter when the compressor is started, the time interval

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

DIGITAL MODULATING BOILERS

DIGITAL MODULATING BOILERS DIGITAL MODULATING BOILERS FOR HEATING AND SANITARY HOT WATER CMX15 CMX18 CM15 CM18 INSTALLATI INSTRUCTIS AND USER GUIDE Please read these instructions before installing or using this appliance for the

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Packaged Chiller Models CC 6601, 6501, 6401, 6301, 6201, 6101 For Service, please contact Pfannenberg Service Company: U.S.A. Pfannenberg Inc. 68 Ward Road.

More information

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A 11 - A 12 - A 13 - A 14 (R410A)

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A 11 - A 12 - A 13 - A 14 (R410A) Code 007806 0 Edit. 0/04 INSTRUCTION AND MAINTENANCE MANUAL DRYERS A - A - A - A 4 (R40A) READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. Cod. 007806 0 - Edition 0/04 - CONTENTS

More information

User Manual Ichill 200 L/D (Firmware version 1.7)

User Manual Ichill 200 L/D (Firmware version 1.7) User Manual Ichill 2 L/D (Firmware version 1.7) Pag. 1 of 142 INDEX 1. GENERAL FEATURES...8 1.1 Main Function... 8 2. ICHILL 2L/D TABLE OF THE FEATURES...1 3. USER INTERFACE...11 4. REMOTE KEYBOARD...15

More information

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS RAE 1352 F.K + MV AIR R-407C FC Series RAE... F.K Cooling capacity from 77 to 289 kw - 2 circuits The air cooled chillers of RAE... F.K series, are designed for outdoor installation and are particularly

More information

40KMC KMQ

40KMC KMQ 40KMC------301 40KMQ------301 OWNER S MANUAL Split system Global cassette indoor unit IR Remote Control Room Controller Zone Manager The unit can be used with infrared Remote Control, with the Carrier

More information

SERVICE MANUAL REFRIGERATION

SERVICE MANUAL REFRIGERATION SERVICE MANUAL REFRIGERATION ELECTROLUX HOME PRODUCTS S.p.A. Publication no. Spares Operations Italy 599 37 75-07 Corso Lino Zanussi, 30 060824 I - 33080 PORCIA / PN (ITALY) ITZ/SERVICE/AA Fax +39 0434

More information

Operation manual. Rooftop Packaged Unit

Operation manual. Rooftop Packaged Unit Operation manual Rooftop Packaged Unit odels: UATYQ20ABAY1 UATYQ25ABAY1 UATYQ30ABAY1 UATYQ45ABAY1 UATYQ50ABAY1 UATYQ55ABAY1 UATYQ65ABAY1 UATYQ75ABAY1 UATYQ90ABAY1 UATYQ110ABAY1 UATYQ115ABAY1 UATYQ20AFC2Y1

More information

Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061

Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061 Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061 Imported by: Zwembad BVBA Industrieweg 9 3190 Boortmeerbeek België www.harmopool.eu 0 Table of content Introduction... 2 Safety instructions...

More information

OPERATION STARTUP TRUE

OPERATION STARTUP TRUE OPERATION STARTUP A. Temperature controls are factory-set to give refrigerators an approximate temperature of 35 F (1.6 C) and freezers an approximate temperature of -10 F (-23.3 C). Allow unit to function

More information

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A10

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A10 Code 00773 04 Edit. 03/0 INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A0 READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. Cod. 00773 04 - Edition

More information

MANUAL FOR AIR COOLED INDUSTRIAL CHILLERS MODEL: UCS-10A

MANUAL FOR AIR COOLED INDUSTRIAL CHILLERS MODEL: UCS-10A MANUAL FOR AIR COOLED INDUSTRIAL CHILLERS MODEL: UCS-10A Universal Chilling Systems, LLC. 2 Unit Manual Contents 1. Specification 2. Transportation 3. Unit Installation 4. Electrical Installation 5. Commissioning

More information

USER MANUAL SILENT16 PORTABLE AIR CONDITIONER

USER MANUAL SILENT16 PORTABLE AIR CONDITIONER USER MANUAL SILENT16 PORTABLE AIR CONDITIONER Thank you for choosing electriq Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. Visit our

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

SILENT 12 PORTABLE AIR CONDITIONER USER MANUAL

SILENT 12 PORTABLE AIR CONDITIONER USER MANUAL SILENT 12 PORTABLE AIR CONDITIONER USER MANUAL Thank you for choosing ElectriQ Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. Visit our

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

OWNER S Manual PRINTED IN CANADA 10/2009

OWNER S Manual PRINTED IN CANADA 10/2009 OWNER S Manual PRINTED IN CANADA 10/2009 Table of contents Introduction 2 General Safety Instructions 4 Installation Instructions Location 6 Water piping 7 Electrical 7 Bonding 8 Bonding and plumbing

More information

Refrigeration. User Instructions & Service History

Refrigeration. User Instructions & Service History Refrigeration User Instructions & Service History Eberspächer (UK) Ltd. Headlands Business Park Salisbury Road, Ringwood Hampshire, BH24 3PB Tel: +44 (0) 1425 480151 Fax: +44 (0) 1425 480152 Website: www.eberspacher.com

More information

Diplomat Inverter/Diplomat Duo Inverter

Diplomat Inverter/Diplomat Duo Inverter www.thermia.com The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC) Copyright Thermia Värmepumpar Table of

More information

CLIM9000CE PORTABLE AIR CONDITIONER USER MANUAL

CLIM9000CE PORTABLE AIR CONDITIONER USER MANUAL CLIM9000CE PORTABLE AIR CONDITIONER USER MANUAL Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. SAFETY INSTRUCTIONS Important! Carefully

More information

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS TC SERIES OPTIONS TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15,, 5 AIR COOLED PACKAGED WATER CHILLERS CONTENTS EQUIPMENT AND COMPONENT DETAILS PERFORMANCE AND TECHNICAL DATA SCHEMATIC FLOW & SYSTEM

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

PACKAGED TERMINAL AIR CONDITIONER

PACKAGED TERMINAL AIR CONDITIONER Your Source for Home Comfort PACKAGED TERMINAL AIR CONDITIONER USER MANUAL FOR MODELS: 1PTC07A-3.5, 1PTC09A-3.5, 1PTC12A-3.5, 1PTC12A-5.0, 1PTC15A-3.5, 1PTC15A-5.0 Before using your air conditioner, please

More information

AQUA LOGIC S MULTI-TEMP Water-Cooled Marine Duty Series chiller

AQUA LOGIC S MULTI-TEMP Water-Cooled Marine Duty Series chiller AQUA LOGIC S MULTI-TEMP Water-Cooled Marine Duty Series chiller INSTALLATION & OPERATING INSTRUCTIONS Effective 8-19-15 Thank you for purchasing an Aqua logic chiller. It has been designed and built to

More information

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB Summary 1 CONNECTIONS... 8 1.1 TEMPERATURE PROBES...8 1.2 PRESSURE PROBES...9 1.3 LOW VOLTAGE DIGITAL INPUTS...10 1.4 LIVE DIGITAL INPUTS...11 1.5 RELAY OUTPUTS...12 2 VOLTAGE/FREQUENCY INPUT...13 3 POWER

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Owner s Manual for Swimming Pool Heat Pump

Owner s Manual for Swimming Pool Heat Pump Owner s Manual for Swimming Pool Heat Pump FC Series nirvanahp.com CONTENTS How it works 1 Installation 2 3 Settings 4 5 6 7 Start-up 8 Winterizing 9 Maintenance 10 Troubleshooting 11 12 13 Warranty 14

More information

HP50HA ABG Heat Pump

HP50HA ABG Heat Pump HP50HA ABG Heat Pump Troubleshooting Guide Residential TSG-ABGHPa Copyright 2017 Hayward Industries Inc. Safety Precautions Warning! High Voltage Electrocution Hazard Hazardous voltage can shock, burn,

More information

Planning guide. Atec.

Planning guide. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS COMFORT CONTROL CENTER 2 THERMOSTAT OPERATING INSTRUCTIONS PROGRAMMABLE THERMOSTAT MODEL 3314080.000 BLACK 3314080.015 WHITE USA SERVICE OFFICE Dometic Corporation 1120 North Main Street Elkhart, IN 46514

More information

Swedish design and manufacture since 1967

Swedish design and manufacture since 1967 Swedish design and manufacture since 167 PVP MA20-14 rev.2 Manual User manual Copyright 2017 Pahlén AB, Box 728, SE-14 27 Upplands Väsby, Sweden Tel. +46 8 54 110 50, Fax +46 8 50 868 80, e-mail: info@pahlen.se,

More information

Table 1. Serie of Digital Room Thermostats.

Table 1. Serie of Digital Room Thermostats. Digital Room Thermostats INSTALLATION MANUAL APPLICATION DR is a serie of Digital Room Thermostats, provides a single stage, temperature control. Table 1 shows all the available models. All models can

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

CHILLER MODEL: CH1500, 2000 AND 3000

CHILLER MODEL: CH1500, 2000 AND 3000 CHILLER MODEL: CH1500, 2000 AND 3000 Operator s & Installation Manual Release Date: February 12, 2010 Publication Number: 621055837OPR Revision Date: March 25, 2014 Revision: E Visit the Cornelius web

More information

Ecoboiler T20 & T30 SERVICE MANUAL. Marco Beverage Systems Ltd. 63d Heather Road, Sandyford Industrial Estate, Dublin 18, Republic of Ireland

Ecoboiler T20 & T30 SERVICE MANUAL. Marco Beverage Systems Ltd. 63d Heather Road, Sandyford Industrial Estate, Dublin 18, Republic of Ireland Ecoboiler T20 & T30 SERVICE MANUAL Marco Beverage Systems Ltd. 63d Heather Road, Sandyford Industrial Estate, Dublin 18, Republic of Ireland Ireland Tel: (01) 295 2674 Ireland Fax: (01) 295 3715 UK Tel:

More information

User & Installer Manual SMT-400 "Enterprise" Wi-Fi Thermostat

User & Installer Manual SMT-400 Enterprise Wi-Fi Thermostat User & Installer Manual SMT-400 "Enterprise" Wi-Fi Thermostat Ver 1.01 May 2018 Great care has been taken in the preparation of this manual. Smart Temp Australia P/L takes no responsibility for errors

More information

USER AND MAINTENANCE MANUAL

USER AND MAINTENANCE MANUAL FDNF96 DEHUMIDIFIER USER AND MAINTENANCE MANUAL INFORMATION FOR USERS For the purpose and effect of Directives 2002/95/CE, 2002/96/CE and 2003/108/CE, relative to the reduction of the use of hazardous

More information

User Manual for model RK 18 RK 25 RK 34 CE 0694 RK 18_25_34 - RAD - ING - MAN.UT A - DIGITECH 2 - REGNO UNITO - EXTRAHEAT - CBD

User Manual for model RK 18 RK 25 RK 34 CE 0694 RK 18_25_34 - RAD - ING - MAN.UT A - DIGITECH 2 - REGNO UNITO - EXTRAHEAT - CBD User Manual for model RK 18 RK 25 RK 34 Premix condensing boiler User instruction CE 0694 RK 18_25_34 - RAD - ING - MAN.UT - 1104A - DIGITECH 2 - REGNO UNITO - EXTRAHEAT - CBD Technical specification by

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 201 C K RAE 482 C K AIR R-407C Series RAE... C K from 19 to 83 kw - 1 and 2 circuits The air cooled chillers of RAE... C K series, with centrifugal fans, are designed for indoor installation and are

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW TECHNICAL INSTRUCTIONS PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER to KW PHRT PHRT PHRT PHRT For terminal units and boiler overhaul applications Heating Cooling PHRT.00 kw -. kw PHRT.0 kw /.0 kw

More information

AQUARIUS 45 MARINE SERVICE MANUAL

AQUARIUS 45 MARINE SERVICE MANUAL AQUARIUS 45 MARINE SERVICE MANUAL CONTENTS: PAGE 1. INTRODUCTION 3 2. SAFETY INSTRUCTIONS 4 3. BASIC INSTRUCTIONS 5 3.1. Installation Details 5 3.2. Operating the Boiler for the First Time 6 3.3. Troubleshooting

More information

TWLC - Tempered Water Logic Controller. The Intelligent Control

TWLC - Tempered Water Logic Controller. The Intelligent Control TWLC - Tempered Water Logic Controller The Intelligent Control Chiller Controls Features: Up to six (6) stages: individual board for each stage maximizes redundancy. Menu driven access and programming.

More information

Installation and Operating Instructions

Installation and Operating Instructions The Leader of RF and Sonic Level For Assistance Call 1-800-527-6297 Outside North America 1-215-674-1234 Installation and Operating Instructions Series 504-1200 Ultrasonic VeriGAP Switch using 404-1200

More information

EnviroZone-4 & EnviroZone-2 Quick-Start Guide

EnviroZone-4 & EnviroZone-2 Quick-Start Guide EnviroZone-4 & EnviroZone-2 Quick-Start Guide This guide is intended to give the installer a brief set of instructions about how to set up the FHP EnviroZone System. For more detailed information about

More information

Service Manual. Modular Crescent Cuber Models KM-901MAJ, MWJ, MRJ/3 KM-1100MAJ, MWJ, MRJ KM-1340MAJ, MWJ, MRJ/3 KM-1601MRJ/3. hoshizakiamerica.

Service Manual. Modular Crescent Cuber Models KM-901MAJ, MWJ, MRJ/3 KM-1100MAJ, MWJ, MRJ KM-1340MAJ, MWJ, MRJ/3 KM-1601MRJ/3. hoshizakiamerica. Service Manual Modular Crescent Cuber Models KM-901MAJ, MWJ, MRJ/3 KM-1100MAJ, MWJ, MRJ KM-1340MAJ, MWJ, MRJ/3 KM-1601MRJ/3 hoshizakiamerica.com Number: 73213 Issued: 1-30-2018 Revision: 3-13-2018 WARNING

More information

The guarantee on this appliance is valid for 12 months from the first day of installation.

The guarantee on this appliance is valid for 12 months from the first day of installation. Users Manual Dear Customer, Thank you for choosing an ARISTON boiler. We guarantee that your boiler is a reliable and technically sound product. This Users Manual provides detailed instructions and recommendations

More information

INSTRUCTION AND MAINTENANCE MANUAL

INSTRUCTION AND MAINTENANCE MANUAL Code 007758 0 Edit. 0/009 INSTRUCTION AND MAINTENANCE MANUAL DRYERS A A A A READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. Cod. 007758 0 - Edition 0/009 - CONTENTS PART A:

More information

Chiller units and air-water heat pumps RANGE OPERATING LIMITS

Chiller units and air-water heat pumps RANGE OPERATING LIMITS Chiller units and air-water heat pumps Cooling capacity: Heating capacity: 6, to 6,6 kw 8, to 69,4 kw ENVIRONMENTALLY FRIENDLY HFC R407C PROTECTION DE L'ENVIRONNEMENT Silent and compact design Air-conditioning

More information

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL Technicold Marine Systems www.technicold.com Technicold by Northern Lights 1419 W. Newport Center Drive Deerfield Beach, FL 33442 Tel:

More information

SWIMMING POOL HEAT PUMP UNIT ECO - series. Installation & Instruction manual

SWIMMING POOL HEAT PUMP UNIT ECO - series. Installation & Instruction manual SWIMMING POOL HEAT PUMP UNIT ECO - series Installation & Instruction manual Rev. 1.00 28.11.2007 Contents SWIMMING POOL HEAT PUMP UNIT 1 CONTENTS 2 1. PREFACE 3 2. SPECIFICATIONS 4 2.1 Performance data

More information

Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series

Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series Section 1: Temperature Control Your Haskris will have one of three different types of controller. Use table 1-1 to identify the relevant controller. The controller may appear different than examples. Contact

More information

Chiller Organizer 2/3

Chiller Organizer 2/3 Chiller Organizer 2/3 OPERATOR S MANUAL Introduction The Chiller Organizer 2/3, is a further evolution of the basic model Chiller Organizer, and it is a microprocessor-based device, which translates with

More information

SERVICE MANUAL FOR 6795B,C,D SERIES PACKAGED AIR CONDITIONERS

SERVICE MANUAL FOR 6795B,C,D SERIES PACKAGED AIR CONDITIONERS SERVICE MANUAL FOR 6795B,C,D SERIES PACKAGED AIR CONDITIONERS TABLE OF CONTENTS 1. Warnings.................................................................. 2 2. Unit Dimensions And Specifications............................................

More information

E U R O V E N T CERTIFIED PERFORMANCE

E U R O V E N T CERTIFIED PERFORMANCE Compact Horizontal Air-Air Heat Pump Model RTH 07L to 30L Ref.: Y-R70171 0707 Technical information E U R O V E N T CERTIFIED PERFORMANCE I S O 9 0 0 1 ER-0028/1991 Johnson Controls Manufacturing España,

More information

UNIT CONTROLLER 8 (UC8) Troubleshooting guide

UNIT CONTROLLER 8 (UC8) Troubleshooting guide UNIT CONTROLLER 8 (UC8) Troubleshooting guide Date: 27 July 2015 Issue: 2 Page 1 of 18 Contents 1. Cautions... 3 2. Recommended service tool set... 3 3. Recommended set of spare parts... 3 4. Items to

More information

SERVICE MANUAL. Ecoboiler Model range: T20 ( ) T30 ( )

SERVICE MANUAL. Ecoboiler Model range: T20 ( ) T30 ( ) SERVICE MANUAL Ecoboiler Model range: T20 (1000662) T30 (1000663) Marco Beverage Systems Ltd. 63d Heather Road, Sandyford Industrial Estate, Dublin 18, Republic of Ireland Ireland Tel: (01) 295 2674 Ireland

More information

Thermo 230 / 231 / 300 / 301 / Troubleshooting

Thermo 230 / 231 / 300 / 301 / Troubleshooting Thermo 230 / 231 / 300 / 301 / 350 5 Troubleshooting 5 Troubleshooting 5.1 General This section describes troubleshooting procedures for the heaters Thermo 230, 231, 300, 301 and 350. CAUTION Troubleshooting

More information