1 BASE BID: SECTION FUEL-FIRED RADIANT HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install a Co-Ray-Vac Low Intensity Vented Infrared Radiant Vacuum Gas Heating System. System must be certified as a system by the American Gas Association under American National Standards for vented infrared heaters. System must be vacuum vented to atmosphere and be under negative pressure at all times during operation to preclude possibility of escape of combustion gases inside building 1.2 SUBMITTALS A. Product Data: Include rated capacities, furnished specialties and accessories. B. Shop Drawings: Detail fabrication including anchorages and attachments to structures and to supported equipment. Include auxiliary motor slides and rails and base weights. 1. Wiring Diagrams: Power, signal, and control wiring. C. Field quality control test reports. D. Operation and Maintenance data 1.3 QUALITY ASSURANCE A. The heating systems supplied shall be design certified by the American Gas Association and this per American National Standard Z Vented Infrared Radiant Heater. B. Each burner shall have a nameplate affixed that bears the seal of the American Gas Association. C. The manufacturer on request of the purchaser shall supply a copy of the current design certification to cover the entire system. D. Clearances to combustible materials shall not exceed those outlined and printed on the burner nameplate and on manufacturer s specification sheet as measured from the surface of the radiant pipe. E. The combustion system shall be capable of being the combustion condensing type in which the products of combustion are exhausted below the dew point of the moisture in the flue gases (140 o F o F). F. Installation of all equipment and materials shall conform to the practices of good workmanship in accordance with applicable requirements. The combustion chambers, pipe work, gas lines and electrical conduit shall be attached to or suspended from the building structure in a manner suitable to meet standards of durability and safety. G. System manufacturer to supply verification from an independent test laboratory showing that the entire system is capable of achieving an annual fuel utilization efficiency (AFUE) of 90% or higher. 1.4 WARRANTY A. Warranty on gas fired radiant systems is to be submitted in writing signed by manufacturer, agreeing to replace/repair, within warranty period, components of gas fired radiant systems furnished by manufacturer, which are defective in either material or workmanship, provided manufacturer s instructions for handling, installing, protecting and maintaining units have been adhered to during warranty period. Replacement is limited to component replacement only and does not include labor for removal and reinstallation. Warranty period - three years from date of substantial completion for all parts Co-Ray-Vac Radiant Heating System Base Bid Specs 1

2 PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Infrared heating system shall be CO-RAY-VAC radiant heating system as manufactured by Roberts-Gordon, Inc., Buffalo, NY, USA. B. Other low intensity radiant systems of equal or greater efficiency and with lower capacity, and with the pattern shown on drawing may be acceptable provided they meet the intent of these specifications and prior approval in writing is obtained from the Engineer at least ten (10) days before the bid date. If such systems are approved, the Contractor assumes responsibility for the design, performance and expense of same. The redesigned system, gas piping, and electric wiring drawings shall be done by a Registered Mechanical Engineer. Shop drawings of the entire new system shall be provided by the Contractor. The Contractor shall state the amount to be credited to the Owner due to this substitution. Where substitutes are used, the Contractor assumes all responsibility for physical dimensions and all other resulting changes. This responsibility extends to cover all extra work as necessitated by other trades as a result of the substitution. The Engineer reserves the right to require the Contractor to remove and replace any material or equipment which does not meet specifications or does not have prior approval as a substitute item. Work shall be completed immediately without cost or inconvenience to the Owner. 2.2 TUBULAR INFRARED HEATERS A. Manufacturers: 1. Roberts-Gordon LLC 2. Approved Alternate Manufacturer B. BURNER UNITS: 1. Each firing unit shall consist of an integral burner control installed in a factory furnished combustion chamber and shall have a maximum gas input rating as indicated on the drawing. Burner assembly shall consist of heavy duty cast iron burner head, pre-wired electronic gas controls with electronic ignition and combustion air filter. 2. Burners shall be designed for firing in tandem without adverse effects from combustion gases from upstream burners. 3. Design firing rate for the burners shall be 40,000 / 60,000 / 80,000 / 100, 000 / 120,000 BTU/HR. 4. The design of the burners supplied shall provide for maintaining a constant proportion of fuel gas to filtered combustion air. These conditions are met for burners in which the pressure of both the fuel gas and the combustion air are both introduced at zero (atmospheric) pressure and the flow of each is established by a vacuum on the downstream side of the flow metering orifices. 5. Outside Air: When specified, the system shall be capable of supplying air from outside to each burner and end vent for the support of combustion in contaminated environments. C. BURNER CONTROL 1. All burners shall be factory wired for 110 volts with transformer for 24 volt DSI operation as supplied with a grounded 18 three wire pigtail located at rear of burner. 2. To assure a high degree of fail-safe operation, the design shall preclude main flow of gas if any or all of the following abnormal conditions occur: (a.) Main valve fails in open position (b.) Vacuum pump motor fails (vacuum proving switch cuts power to burners.) (c.) Power fails (gas valves in burners close in safe position.) 2015 Co-Ray-Vac Radiant Heating System Base Bid Specs 2

3 3. All gas vacuum-firing burner units shall be equipped with a Direct Spark Ignition Module (DSI). The DSI module shall have a 15 second flame response time before lockout occurs. The spark shall shut off when the burner flame is established. 4. All units to be supplied with outside air for combustion and any excess air required by system if inside air contains contaminants. D. RADIANT PIPING - HEAT EXCHANGER 1. Provide Aluminized pipe throughout system. Minimum heat exchanger surface to be 75 sq. ft for each 100,000 BTU/HR input. Connections to be made between pipe sections using stainless steel coupling assemblies. 2. Hanging materials: All system pipe must be supported in accordance with acceptable practices, local codes, seismic requirements, applicable standards and as shown on plans. Pipe shall pitch down at least 1 in 20 toward vacuum pump. E. REFLECTORS: 1. All reflectors shall be deep dish of a highly infrared reflective material such as aluminum. 2. Standard reflector shall be installed on all radiant pipe, manifold pipe, and tail pipe as indicated on system layout furnished. 3. System to have perimeter side extension reflector in certain areas of layout as shown on plan when specified. Side reflector permanently attaches to side of top reflector and is secured to the pipe by three side reflector supports and two Z clips for each 8 ft section of side reflector. F. END VENT ASSEMBLY: 1. Each open end combustion chamber shall have an approved end vent and the reflector in this area shall have an end cap, and be installed according to manufacturer s installation instructions and as shown on plans. G. VACUUM PUMP: 1. The system shall vent all products of combustion outdoors by means of the vacuum pump. 2. Vacuum pump shall be equipped with a maximum of 3/4 HP, 60 Hertz, 120 Volt, 3450 RPM, single phase T.E.F.C. motor. This motor shall have thermal overload protection, ball bearings, and shall be constructed in accordance with electric motor industry standards. 3. The scroll of this pump shall be cast iron with a minimum metal thickness of approximately 3/16 inch. The impeller wheel shall be cast 319 alloy aluminum with a minimum metal thickness of approximately 3/32 inch. 4. There will be a low voltage two-wire circuit from the vacuum proving switch (located at the inlet to the vacuum pump) to the control panel. 5. The connection between the pump inlet and tail pipe is made with an acoustic boot and clamps provided. The discharge connection is made with a 4.5 inch acoustic boot and 4 porcelain coated tail pipe. 6. To further assure a high degree of safety, the system will be under negative pressure at all times during operation to preclude the possibility of the escape of combustion gases inside the building. 7. Vacuum pump motor requires a 1 wire grounded circuit 115 volts, single phase, 60 hertz for a total of 10 full load amps. This motor must have the same rotation to match the direction of the arrow on the fan scroll. If the motor is not rotating in this direction, it must be reversed by interchanging the red wire #8 with the orange wire #5. These are located behind the motor escutcheon plate Co-Ray-Vac Radiant Heating System Base Bid Specs 3

4 8. The vacuum pump shall be acoustically isolated from the system with a flexible connector with a temperature rating of 350 o F minimum. The motor in the vacuum pump shall be secured with rubber mounts for acoustical isolation. 9. Venting materials shall be steel, stainless steel, cast iron, transite pipe or suitable material as required by local codes and as shown on drawings. Venting materials to be supplied by the Mechanical Contractor and not by the manufacturer of the equipment. H. CONTROL PANEL: 1. A pre-wired solid state system control panel shall be provided by the system manufacturer as shown on drawings for each vacuum pump. The control panel shall provide all relays, controls, terminals, lights, etc. to control up to four temperature zones with individual thermostats. Controls shall include a pre-purge sequence of at least 20 seconds prior to initiation of firing and post-purge sequence of at least 20 seconds after shutdown of the last burner. An interlock shall be provided to insure that no burner may be fired without the vacuum pump operating, indicator lights shall appear on outside of panel cover to show Vacuum Pump Operation, Power On and Zone On. 2. Install electrical wiring as indicated. Connect power wiring to burners and vacuum pumps. Connect control wiring between vacuum pumps, control panels and thermostats in accordance with manufacturer s wiring diagrams. Disconnect switches, if required, to be provided and installed under Electrical Section (Division 16000). I. THERMOSTATS: 1. Provide, where indicated, low voltage thermostat connected to control system. Mount thermostat(s) 48 above finished floor, if not otherwise indicated. Supply number of thermostats as shown on drawing. 2.3 SYSTEM CONTROLS A. Pre-wired system control circuits shall be supplied in a control panel with each vacuum pump. The control panel for the control of the burners shall provide relays & terminals to accommodate up to four temperature zones with a thermostat and associated control circuits for the burners for each temperature zone. The control panel shall have indicator lights showing Power On, Vacuum Pump On and 4-Zones in Operation. B. All control circuits must be properly polarized. All burner units located on one radiant pipe line must be on the same zone. All burner units using the same tail pipe also must be on the same zone (except last 10 into pump). C. All combustion chamber and heat exchanger pipes connected to vacuum pump shall be prepurged with air for a period of at least 20 seconds (10 air changes minimum) prior to initiation of firing sequence. D. All combustion chamber and heat exchanger pipes connected to a vacuum pump shall be postpurged with air for a period of at least 20 seconds (10 air changes minimum) after shut down of the last burner firing into the vacuum pump. E. All vacuum pumps shall be provided with vacuum proving switches to prevent opening of gas valves until vacuum in the pipe is proven. F. Pre-purge of the system is obtained from the solid state timer relay located in the furnished panel. The first zone thermostat calling for heat will activate this relay. The pump motor will start and the vacuum proving switch, after sensing a minus pressure of 2 water column, completes the circuit to begin pre-purge. After approximately 45 seconds, the 110 volt control circuits will be activated and burners will light automatically. The burners will remain on until the thermostat is satisfied. At that time, the gas valve and DSI will drop out, but the pump will continue to run to give a post-purge. This post-purge period on the last zone thermostat to be satisfied (internally provided in panel box) Co-Ray-Vac Radiant Heating System Base Bid Specs 4

5 G. The low voltage control system furnished is designed to maintain the set point of the thermostat without additional controls added in the field. Night set-back of this system is not recommended. The system must not be turned off at night or on weekends. (Night set-back of not over 10 degrees may be used on weekends or extended periods of time when the building is not occupied.) Any automatic night set-back devise would have to be installed outside the control panel and on the low voltage circuit only to avoid violating AGA certification. H. The system wiring diagram shall conform to wiring diagrams furnished with installation and service sheets furnished with the units and as on plans. I. All thermostats are low voltage bimetal action with heat anticipator. Low voltage thermostats shall be numbered instead of marked in degrees and shall not have thermometers. Low voltage fittings must follow local codes. PART 3 EXECUTION 3.1 INSTALLATON A. Install radiant heaters as noted in Section 2.2D B. Install and connect gas-fired radiant heaters and associated fuel and vent features and systems according to NFPA 54, applicable local codes and regulations, and manufacturer s written installation instructions. C. Suspended Units: Suspend from substrate using chain hangar kits and building attachments. 3.2 CONNECTIONS A. Gas supply piping must meet local codes and fuel supplier requirements and be sized in accordance with BTU demand, available pressure, and the total equivalent length of pipe required (fittings included). B. Connection from gas supply line to burner unit must be made in accordance with installation details on plans. Special connections are used to allow for expansion and contraction of radiant piping. C. Gas shut-off cock, as supplied with unit, and controls in unit must not be subjected to more than 1/2# or 14 inches water column (W.C.) pressure. If high pressure testing of gas supply line is required, this test must be made with a plug in the 1/2 inch branch line to each burner. Never test the gas line with the 1/2 inch IPS x 3/4 SAB shut-off cock installed or with the burner unit connected. D. Electrical wiring must conform to National Electric Code and local ordinances in accordance with diagrams furnished. 1. Provide outlet box with 3-wire grounded receptacle within 12 inches of each burner or wire as per local code requirements. Units supplied with 24 cord to plug into 3-wire grounded receptacle. However, if another means of disconnect is required by local codes, it will be the responsibility of the electrical or temperature control contractor to provide and wire the same. 3.3 FIELD QUALITY CONTROL A. Provide start-up, test and adjust gas fired radiant heaters in accordance with manufacturer s start-up instructions and utility company s requirements. Check and calibrate controls, adjust burners for maximum efficiency. 3.4 ADJUSTING A. Check and calibrate controls, adjust burners for maximum efficiency 2015 Co-Ray-Vac Radiant Heating System Base Bid Specs 5

6 3.5 DEMONSTRATION A. Provide services of manufacturer s technical representative for one half day to instruct owner s personnel in operation and maintenance of gas fired radiant heaters. Schedule training with Owner, provide at least seven day notice to Contractor and Engineer of training date. END OF SECTION Co-Ray-Vac Radiant Heating System Base Bid Specs 6

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS SL/SLV SIRIUS LINEAR RANGE HIGH EFFICIENCY CONTINUOUS INFRARED SYSTEMS

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS SL/SLV SIRIUS LINEAR RANGE HIGH EFFICIENCY CONTINUOUS INFRARED SYSTEMS GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS SL/SLV SIRIUS LINEAR RANGE HIGH EFFICIENCY CONTINUOUS INFRARED SYSTEMS SECTION 15540 FUEL- FIRED HEATERS (Alternate - SECTION 235523 - GAS-FIRED RADIANT HEATERS)

More information

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS SECTION 15540 FUEL- FIRED HEATERS (Alternate - SECTION 235523 - GAS-FIRED RADIANT HEATERS) This section is based

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS KMI GoGas RANGE HIGH EFFICIENCY, HIGH INTENSITY INFRARED HEATERS

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS KMI GoGas RANGE HIGH EFFICIENCY, HIGH INTENSITY INFRARED HEATERS GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS KMI GoGas RANGE HIGH EFFICIENCY, HIGH INTENSITY INFRARED HEATERS SECTION 15540 - FUEL - FIRED HEATERS (Alternate - SECTION 235523 - GAS-FIRED RADIANT HEATERS)

More information

INFRARED RADIANT HEATERS

INFRARED RADIANT HEATERS IRH-1R INFRARED RADIANT HEATERS High and Low Intensity RSU SERIES Unit is shown rotated at a 45 angle. RSD SERIES HIGH INTENSITY INFRARED HEATERS RSD Series Ceramic Heaters Special Honeycomb Tile Design

More information

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas HVAC Guideline Specifications WHISPER-JET: SET SERIES Two Stage Positive Pressure Gas-Fired Infrared Radiant Tube Type Heater Commercial/Industrial Applications Technical Summary Input Range: 80,000/60,000

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 235533 - FUEL-FIRED UNIT HEATERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas fired unit heaters. B. Oil fired unit heaters. C. Tubular infrared heaters. 1.2 RELATED REQUIREMENTS A. Section 230513

More information

GAS-FIRED PRESSURIZED LOW INTENSITY INFRARED HEATERS SERIES TLP

GAS-FIRED PRESSURIZED LOW INTENSITY INFRARED HEATERS SERIES TLP GAS-FIRED PRESSURIZED LOW INTENSITY INFRARED HEATERS SERIES TLP CATALOG 9-117.1 JUNE, 2003 TABLE OF CONTENTS Modine's TLP Series sets the industry standard for low intensity infrared heating performance

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh

T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh PRODUCT SPECIFICATIONS GAS UNIT HEATERS / DUCT FURNACES TU T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ Bulletin No. 20402 November 207 Supersedes November 206

More information

8+* Bulletin No November 1997

8+* Bulletin No November 1997 ENGINEERING DATA VALUE 80Z UP-FLOW/HORIZONTAL GAS FURNACES *80.0 to 80.5% A.F.U.E. 45,000 to 20,000 Btuh (3.2 to 32.2 kw) Input Heating Capacity -/2 thru 6 Tons (3.5 thru 2. kw) Nominal Add-on Cooling

More information

INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS PROPANE GAS DATE: PROJECT: ARCHITECT/ENGINEER: CONTRACTOR: SUBMITTED BY:

INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS PROPANE GAS DATE: PROJECT: ARCHITECT/ENGINEER: CONTRACTOR: SUBMITTED BY: INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS (CHECK ONE) PROPANE GAS PROJECT: ARCHITECT/ENGINEER: NAME: ADDRESS: NAME: ADDRESS: DATE: CONTRACTOR: SUBMITTED BY: NAME: ADDRESS: EQUIPMENT

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

MERIT SERIES Downflow

MERIT SERIES Downflow PRODUCT SPECIFICATIONS GAS FURNACES ML80DF MERIT SERIES Downflow Bulletin No. 20643 February 208 Supersedes November 207 AFUE - 80% Input - 44,000 to 0,000 Btuh Nominal Add-on Cooling -.5 to 5 Tons MODEL

More information

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0804 L2 Revised 05 05 2008 G71MPP G71MPP SERIES UNITS G71MPP series units are high efficiency multi position (upflow, downflow, horizontal right and left) gas furnaces equipped

More information

Omega II SUBMITTAL DATA. Pre Engineered Packages. Products by: COMBUSTION RESEARCH CORPORATION PROJECT: LOW-INTENSITY INFRARED HEATING SYSTEMS

Omega II SUBMITTAL DATA. Pre Engineered Packages. Products by: COMBUSTION RESEARCH CORPORATION PROJECT: LOW-INTENSITY INFRARED HEATING SYSTEMS LOW-INTENSITY INFRARED HEATING SYSTEMS Omega II Pre Engineered Packages Products by: COMBUSTION SUBMITTAL DATA PROJECT: Specifications for Omega II UNITARY P.E.P. SYSTEMS PART 1 - GENERAL It is the intent

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

SERIES. 10 year limited warranty on Burner Core 5 year limited warranty on All combustion and. 2 year limited warranty on All Burner Controls

SERIES. 10 year limited warranty on Burner Core 5 year limited warranty on All combustion and. 2 year limited warranty on All Burner Controls TM SERIES Available with 40,000 to 200,000 BTU/Hr. inputs and tube lengths from 10 feet to 70 feet. Aircraft Hangars Auto Dealerships Farm Buildings Fire Stations Body Shops Car Washes Sports Facilities

More information

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh WATER HEATERS / BOILERS COWB3 Oil-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 0654 March 08 Supersedes September 05 AFUE up to 85.% Heating Input 05,000 to 45,000 Btuh MODEL NUMBER IDENTIFICATION

More information

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com MODEL HS115-3, HS115-4 & HS115-5 WIRING

More information

AFUE 95% Heating Input 50,000 to 200,000 Btuh

AFUE 95% Heating Input 50,000 to 200,000 Btuh PRODUCT SPECIFICATIONS WATER HEATERS / BOILERS GWM-IE Gas-Fired, Modulating, Condensing, Wall Hung Hot Water Boiler Bulletin No. 210650 March 2018 Supersedes December 2015 AFUE 95% Heating Input 50,000

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

GAS-FIRED HIGH INTENSITY INFRARED HEATERS

GAS-FIRED HIGH INTENSITY INFRARED HEATERS GAS-FIRED HIGH INTENSITY INFRARED HEATERS CATALOG 9-116.1 MARCH, 2003 TABLE OF CONTENTS Modine's MT Series is a gas-fired, high intensity ceramic infrared heater. Ideal for spot heating, the MT series

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

Engineering Submittal Data PPRTH Patio Radiant Tube Heaters.

Engineering Submittal Data PPRTH Patio Radiant Tube Heaters. 12288 Brawn Road 22, Wainfleet, Ontario, Canada L0S 1V0 Phone: 905-899-3473 Fax: 905-899-2262 www.easyradiantworks.com email: erw@vaxxine.com P For either indoor or outdoor installation. Not for use in

More information

Copyright 2011 AIA MasterSpec Full Length 06/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO CALCANA USA LTD.

Copyright 2011 AIA MasterSpec Full Length 06/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO CALCANA USA LTD. Copyright 2011 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA This Product MasterSpec Section is licensed

More information

ELITE SERIES Downflow - High Efficiency Blower Motor

ELITE SERIES Downflow - High Efficiency Blower Motor PRODUCT SPECIFICATIONS GAS FURNACES EL80DFE ELITE SERIES Downflow - High Efficiency Blower Motor Bulletin No. 2066 July 208 Supersedes February 208 AFUE - 80% Input - 44,000 to 0,000 Btuh Nominal Add-on

More information

INFRARED RADIANT TUBE HEATER

INFRARED RADIANT TUBE HEATER INFRARED RADIANT TUBE HEATER LTS 40 250 SERIES PROJECT: ADDRESS: ARCHITECT/ENGINEER: ADDRESS: CONTRACTOR: ADDRESS: SUBMITTED BY: N-NATURAL GAS (CHECK ONE) L-PROPANE GAS EQUIPMENT USED: 5-SINGLE STAGE (CHECK

More information

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project

More information

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS XPAK FT TYPE H - MODELS 088AR-398A SUGGESTED SPECIFICATIONS Catalog No.: 2100.91 Effective: 05/01/15 Replaces: new DIVISION 23 52 33.13 WALL-HUNG STAINLESS STEEL HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY

More information

COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ. Steady-State Efficiency - up to 81% Input - 30,000 to 75,000 Btuh

COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ. Steady-State Efficiency - up to 81% Input - 30,000 to 75,000 Btuh GAS UNIT HEATERS / DUCT FURNACES LF24 COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ PRODUCT SPECIFICATIONS Bulletin 2008 July 206 Supersedes October 20 Steady-State Efficiency - up to 8% Input

More information

LF24. UNIT HEATERS Horizontal - 60 HZ. Thermal Efficiency - up to 80.5% Input - 100,000 to 390,000 Btuh LF A MODEL NUMBER IDENTIFICATION

LF24. UNIT HEATERS Horizontal - 60 HZ. Thermal Efficiency - up to 80.5% Input - 100,000 to 390,000 Btuh LF A MODEL NUMBER IDENTIFICATION E N G I N E E R I N G D ATA G A S U N I T H E A T E R S / D U C T F U R N A C E S LF4 UNIT HEATERS Horizontal - 60 HZ Bulletin. 0000 June 0 Supersedes February 0 Front View Tubular Heat Exchanger Thermal

More information

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications

GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications ENGINEERING DATA Typical Applications G20RE and G20RXE WhisperHeat DOWN-FLO GAS FURNACES *78.0% A.F.U.E. 50,000 to 150,000 Btuh Input Add-On Cooling 2 thru 5 Nominal Tons *Isolated Combustion System rating

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh HEATERS / BOILERS GWB8-E Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 065 July 06 Supersedes September 05 AFUE up to 83.9% Heating Input 50,000 to 99,000 Btuh MODEL NUMBER IDENTIFICATION

More information

1.03 DELIVERY, STORAGE, AND HANDLING Heater will be stored to secure against damage and handled per manufacturer s recommendations.

1.03 DELIVERY, STORAGE, AND HANDLING Heater will be stored to secure against damage and handled per manufacturer s recommendations. HVAC Guideline Specifications supraschwank Packaged Luminous Infrared Radiant Gas Heater Combined Intensity (produces both Low and High Intensity radiant output) Commercial/Industrial Applications Size

More information

PART NO. COMBUSTION AIR TERMINATION CAP

PART NO. COMBUSTION AIR TERMINATION CAP ACCESSORIES FOR SUNSTAR TUBE HEATERS VENT CAP SIDEWALL OR ROOF Unique design prevents back drafts and assists in drawing off and exhausting the products of combustion regardless of wind direction Heavy-gauge

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh HEATERS / BOILERS GWB8-E PRODUCT SPECIFICATIONS Gas-Fired Hot Water Boiler Bulletin No. 065 September 0 Supersedes Bulletin No. 06 AFUE up to 83.9% Heating Input 50,000 to 99,000 Btuh MODEL NUMBER IDENTIFICATION

More information

CORAYVAC Helps Reduce Energy Bills and Improve Comfort

CORAYVAC Helps Reduce Energy Bills and Improve Comfort CORAYVAC Helps Reduce Energy Bills and Improve Comfort CORAYVAC gas-fired, low-intensity, infrared heating systems help provide custom comfort, while facilitating reduced energy consumption up to 50% and

More information

CLEARANCES TO COMBUSTIBLES

CLEARANCES TO COMBUSTIBLES 12288 Brawn Road 22, Wainfleet, Ontario, Canada L0S 1V0 Phone: 905-899-3473 Fax: 905-899-2262 www.easyradiantworks.com email: erw@vaxxine.com Engineering Submittal Data EZB series straight and U shape

More information

INFRARED RADIANT TUBE HEATER

INFRARED RADIANT TUBE HEATER INFRARED RADIANT TUBE HEATER LTU 40 250 SERIES PROJECT: ADDRESS: ARCHITECT/ENGINEER: ADDRESS: CONTRACTOR: ADDRESS: SUBMITTED BY: N-NATURAL GAS (CHECK ONE) L-PROPANE GAS EQUIPMENT USED: 5-SINGLE STAGE (CHECK

More information

Series RE Infrared Heater

Series RE Infrared Heater Series RE Infrared Heater Installation, Operation and Service Instructions WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage,

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

BEACON/MORRIS RBD SERIES INFRARED RADIANT HEATER

BEACON/MORRIS RBD SERIES INFRARED RADIANT HEATER RBDS-1 RBD SERIES CERAMIC HEATERS NATURAL GAS (Check One) PROPANE GAS EQUIPMENT USED: ACCESSORIES: Chain Mounting Kit: Thermostat: Gas Pressure Regulator: Parabolic Extension: Gas Shut-Off Valve: Reverb

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 2000.932C Effective: 04-01-14 Replaces: 07-15-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

STR-Series Indirect-Fired Air Turnover Units

STR-Series Indirect-Fired Air Turnover Units STR-Series Indirect-Fired Air Turnover Units Equipment Specifi cations 1.800.589.3691 www.weather-rite.com GAS/OIL HEATING ONLY INDIRECT-FIRED AIR TURNOVER UNIT GUIDE SPECIFICATIONS PART 1 GENERAL [Gas][Oil][Gas/Oil

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

Suburban RV FURNACES SERVICE MANUAL

Suburban RV FURNACES SERVICE MANUAL Suburban RV FURNACES SERVICE MANUAL DD-17DSI DD-17DSIW NT-12S/SE NT-16S/SE NT-20S/SE NT-24SP NT-30SP NT-34SP NT-40 P-30S/40 SF-20 SF-25 SF-30 SF-35 SF-42 SF-20F SF-25F SF-30F SF-35F SF-42F SH-35 SH-42

More information

GSR21Q GAS FURNACES EXISTING NEG EXISTING NEG ENGINEERING DATA HORIZONTAL POSITION. Typical Applications DOWN-FLO POSITION

GSR21Q GAS FURNACES EXISTING NEG EXISTING NEG ENGINEERING DATA HORIZONTAL POSITION. Typical Applications DOWN-FLO POSITION ENGINEERING DATA GSR21Q PULSE21 SERIES HORIZONTAL/DOWN-FLO GAS FURNACES HORIZONTAL UNIT HEATERS AND DOWN-FLO MOBILE HOME UNITS *91.7% to 95.3% A.F.U.E. 50,000 to 100,000 Btuh Input Add-On Cooling 1-1/2

More information

INFRARED RADIANT TUBE HEATER

INFRARED RADIANT TUBE HEATER INFRARED RADIANT TUBE HEATER NXU 50 200 SERIES NXS 50 200 SERIES PROJECT: ADDRESS: ARCHITECT/ENGINEER: ADDRESS: CONTRACTOR: ADDRESS: SUBMITTED BY: N-NATURAL GAS (CHECK ONE) L-PROPANE GAS EQUIPMENT USED:

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

Greater temperature control

Greater temperature control Brighter glow Easy to clean and hang Increased floor heat features Greater temperature control Ignition options The Ultimate in Reliable, Efficient Radiant Heat Ultra-Ray Broad Comfort Zone Heats an average

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

Typical Mount Height. Combustion Chamber

Typical Mount Height. Combustion Chamber ! WARNING: This heater must be installed and serviced by trained gas installation and service personnel only! Improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 1029 L7 SLP98UHV SLP98UHV SERIES UNITS SLP98UHV series units are high efficiency upflow, horizontal right and left) gas furnaces equipped with variable capacity gas valve, variable

More information

SL280DFV. DAVE LENNOX SIGNATURE COLLECTION Downflow - Two-Stage Heat - Variable Speed Blower

SL280DFV. DAVE LENNOX SIGNATURE COLLECTION Downflow - Two-Stage Heat - Variable Speed Blower P R O D U C T S P E C I F I C AT I O N S G A S F U R N A C E S SL280DFV DAVE LENNOX SIGNATURE COLLECTION Downflow - Two-Stage Heat - Variable Blower Bulletin No. 20576 December 200 Supersedes July 200

More information

PART NO. THROUGH THE ROOF VENT CAP

PART NO. THROUGH THE ROOF VENT CAP ACCESSORIES FOR SUNSTAR TUBE HEATERS SIDEWALL VENT CAP Unique design prevents back drafts and assists in drawing off and exhausting the products of combustion regardless of wind direction Heavy-gauge aluminum

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

DX SERIES TUBE HEATER

DX SERIES TUBE HEATER DX SERIES TUBE HEATER INSTALLATION, OPERATION, MAINTENANCE AND PARTS MANUAL Detroit Radiant Products Company FOR YOUR SAFETY! IF YOU SMELL GAS: 1. Open windows. 2. Do not touch electrical switches. 3.

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

POWER VENTER SYSTEM. Model: PVO-300, PVO-600 POWER VENTER SYSTEM Model: PVO-300, PVO-600 Included is one ETL and cetl listed Power Venter to be used primarily with a single 120VAC controlled oil fired furnace, boiler, or water heater. The PVO may

More information

G61MP. ELITE Series Multi-Position - Two-Stage Heat. AFUE - Up to 95% Input - 44,000 to 132,000 Btuh Nominal Add-on Cooling - 2.

G61MP. ELITE Series Multi-Position - Two-Stage Heat. AFUE - Up to 95% Input - 44,000 to 132,000 Btuh Nominal Add-on Cooling - 2. P R O D U C T S P E C I F I C AT I O N S G A S F U R N A C E S G6MP ELITE Series Multi-Position - Two-Stage Heat Bulletin No. 038 August 009 Supersedes December 008 AFUE - Up to 95% Input - 44,000 to 3,000

More information

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents LGB Gas fired boiler Control Supplement LGB-6 to LGB-23 Series 2 Propane gas Universal Control System Contents I. New installation... 2 II. Existing installation... 4 III. Gas piping... 5 IV. Wiring...

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 2505-4005 SUGGESTED SPECIFICATIONS Catalog No.: 6000.70 Effective: 09-15-16 Replaces: NEW WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes condensing, gas-fired

More information

SUBMITTAL SCHEDULE & DATA

SUBMITTAL SCHEDULE & DATA SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Date: 10/31/2016 Location: Engineer: Submitted by: Jeff Musto Architect: Contractor: Model

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS SECTION 22 36 01 ELECTRIC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY.

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY. KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters Table of Contents FOR YOUR SAFETY Page # Topic If you smell gas: 1 Description of Operation 1 Receiving the

More information

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS XTHERM, TYPE WH - MODELS 1005A- 2005A Catalog No.: 3500.801 Effective: 11-15-14 Replaces: NEW PART 1 - GENERAL 1.1 SUMMARY DIVISION 23 34 36.29 COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

Installation, Operation and Service Instructions RS RANGE RESIDENTIAL INFRARED HEATERS

Installation, Operation and Service Instructions RS RANGE RESIDENTIAL INFRARED HEATERS Installation, Operation and Service Instructions RS RANGE RESIDENTIAL INFRARED HEATERS WARNINGS WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

VICTORY VSPH VICTORYVSPH THE PERFECT CHOICE FOR. Cast-iron sealed combustion, direct vent gas boiler

VICTORY VSPH VICTORYVSPH THE PERFECT CHOICE FOR. Cast-iron sealed combustion, direct vent gas boiler VICTORYVSPH VICTORY VSPH Cast-iron sealed combustion, direct vent gas boiler Cast-iron sealed combustion, direct vent gas boiler THE PERFECT CHOICE FOR NEW RESIDENTIAL CONSTRUCTION, RELIABILITY AND ECONOMY.

More information

Series GR/ET Infrared Heater

Series GR/ET Infrared Heater Series GR/ET Infrared Heater Installation, Operation and Service Instructions WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 1005A-2005A SUGGESTED SPECIFICATIONS Catalog No.: 6000.63B Effective: 3-01-15 Replaces: 9-01-09 WATER-TUBE POOL HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes condensing,

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and

More information

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0204 L2 Revised 11 2006 G60UH(X) G60UH(X) SERIES UNITS G60UH(X) series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

INFRARED RADIANT TUBE HEATER RSTP15C NATURAL GAS RSTP17C

INFRARED RADIANT TUBE HEATER RSTP15C NATURAL GAS RSTP17C PROJECT: INFRARED RADIANT TUBE HEATER RSTP15C NATURAL GAS (CHECK ONE) RSTP17C NAME: ADDRESS: (CHECK ONE) PROPANE GAS DATE: ARCHITECT/ENGINEER: CONTRACTOR: SUBMITTED BY: NAME: ADDRESS: NAME: ADDRESS: EQUIPMENT

More information

Residential Garage Heater Installation, Operation, & Maintenance Instruction Manual (Mount a copy of these instructions adjacent to the heater)

Residential Garage Heater Installation, Operation, & Maintenance Instruction Manual (Mount a copy of these instructions adjacent to the heater) Form RH-IOM-11 210080 Residential Garage Heater Installation, Operation, & Maintenance Instruction Manual (Mount a copy of these instructions adjacent to the heater) MODEL IDENTIFICATION Record the information

More information

PVE SERIES POWER VENTER SYSTEM MANUAL

PVE SERIES POWER VENTER SYSTEM MANUAL PVE SERIES POWER VENTER SYSTEM MANUAL Contents Page I. Typical Venting System Components 2 II. System Operation 3 III. Power Venter Sizing 3,4 IV. Installation Safety Instructions 5,6 V. Installation of

More information

POWER VENTER. Model: PVE Series

POWER VENTER. Model: PVE Series POWER VENTER Model: PVE Series CONTENTS Typical Venting System Components... System Operation... Power Venter Sizing... Installation Safety Instructions... Installation of Power Venter... Connecting Power

More information

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Multi-Function Cooktop

Multi-Function Cooktop INSTALLATION GUIDE Multi-Function Cooktop Contents Wolf Multi-Function Cooktop.................... 3 Multi-Function Cooktop Specifications............ 4 Multi-Function Cooktop Installation...............

More information

Cumberland Heating Systems

Cumberland Heating Systems Cumberland Heating Systems Cumberland "Radiant" Brooder Clean Burning...Fuel Efficient Maintaining proper in-house temperature is critical in climate control. A consistent, stressfree environment promotes

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

Gas-Fired Indoor and Outdoor Duct Furnaces

Gas-Fired Indoor and Outdoor Duct Furnaces July, 2008 Gas-Fired Indoor and Outdoor Duct Furnaces INDOOR GRAVITY VENTED DFG, DBG, DCG INDOOR SEPARATED COMBUSTION DFS, DBS, DCS OUTDOOR GRAVITY AND POWER EXHAUSTED H Series table of contents A complete

More information

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC). SECTION 15555 HORIZONTAL FIRE TUBE BOILERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15510 - Piping (HVAC). 2. 15540 - Pumping Equipment (HVAC). 1.02 SUBMITTALS A. Submit properly identified

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information