1 38MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 30, 36 and 48 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 GENERAL... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 PIPING REQUIREMENTS... 4 WIRING... 5 DIMENSIONS... 6 CLEARANCES INSTALLATION GUIDE INSTALLATION TIPS OUTDOOR UNIT INSTALLATION ELECTRICAL DATA CONNECTION DIAGRAMS SYSTEM VACUUM AND CHARGE NOTES: Read the entire instruction manual before starting the installation. Image for illustration purposes only. Actual model may be slightly different. START UP OUTDOOR UNIT DIAGNOSTIC GUIDES... 17

2 SAFETY CONSIDERATIONS Installing, starting up, and servicing air conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment. Untrained personnel can perform basic maintenance functions such as coil cleaning. All other operations should be performed by trained service personnel. When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Keep a quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA Recognize safety information. This is the safety alert symbol!!. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.! CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start up. GENERAL These instructions cover the installation, start up and servicing of the multi zone outdoor unit connected to up to five indoor fan coil units. For approved combinations, refer to the product data document. 2

3 PARTS LIST Table 1 Parts List PART NO. PART NAME QTY. 1 Outdoor unit 1 - Literature package including installation instructions and warranty 1 - Grommet to secure the outdoor unit (helps with vibration prevention during unit operation) 4 - Drain Joint 1 - Drain Hose 1 - Conversion Joints (see Table 4) - Outdoor 1 Fig. 1 - Parts List A NOTES: If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe before it enters the wall to the indoor unit. This ensures that rain drips from the connection pipe before it enters the wall. Piping and the interconnecting wiring are field supplied. The illustration above is only a sketch. Different models may be differ slightly. The following units are covered in these installation instructions. Table 2 Unit Sizes SYSTEM TONS kbtuh VOLTAGE - PHASE OUTDOOR MODEL / MGRQ18B / MGRQ24C / MGRQ30D / MGRQ36D / MGRQ48E--3 3

4 SYSTEM REQUIREMENTS Allow sufficient space for airflow and service of the unit. See Fig. 2 for the required minimum distances between the unit, walls or ceilings. PIPING REQUIREMENTS IMPORTANT: Both refrigerant lines must be insulated separately. The minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m). The following lengths are allowed. Table 3 lists the pipe sizes for the outdoor unit. For the indoor unit pipe sizes refer to the indoor unit installation instructions. Table 3 Piping and Refrigerant SYSTEM SIZE 18K 24K 30K 36K 48K Min. Piping Length per each indoor unit ft (m) 10 (3) 10 (3) 10 (3) 10 (3) 10 (3) Standard Piping Length per each indoor unit ft (m) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) Max. outdoor-indoor height difference (OU higher than IU) ft (m) 49 (15) 49 (15) 49 (15) 65 (20) 65 (20) Max. outdoor-indoor height difference (IU higher than OU) ft (m) 49 (15) 49 (15) 49 (15) 65 (20) 65 (20) Max. height different between indoor units ft (m) 32 (10) 32 (10) 32 (10) 32 (10) 32 (10) Max. Length per each indoor unit ft (m) 82 (25) 98 (30) 115 (35) 115 (35) 115 (35) Piping Max. Piping Length with no additional refrigerant charge per System ft (m) 49 (15) 74 (22.5) 98 (30) 123 (37.5) 123 (37.5) (Standard Piping length x No. of Zones) Total Maximum Piping Length per system ft (m) 131 (40) 197 (60) 263 (80) 328 (100) 328 (100) Refrigerant Additional refrigerant charge (between Standard Max piping length) Suction Pipe Size Liquid Pipe Size Oz/ft (g/m) in (mm) in (mm) 0.16 (15) 0.16 (15) 0.16 (15) 0.16 (15) 0.16 (15) 3/8*2 (9.5*2) 1/4 *2 (6.3*2) 3/8*3 (9.5*3) 1/4 *3 (6.3*3) 1/2*1+3/8*3 (12.7*1+9.5*3) 1/4 *4 (6.3*4) 1/2 *2+3/8*2 (12.7*2+9.5*2) 1/4 *4 (6.3*4) 1/2 *2+3/8*3 (12.7*2+9.5*3) 1/4 *5 (6.3*5) Refrigerant Type R410A R410A R410A R410A R410A Charge Amount Lbs (kg) 4.41 (2.0) 6.17 (2.8) 6.61 (3.0) (4.6) (4.6) NOTES: The refrigerant charge included is adequate for the outdoor unit s maximum number of zones multiplied by the standard piping length per zone. For piping runs greater than the Maximum Piping Length with no additional refrigerant charge per System, see Additional Refrigerant Charge (see Table 5). Refrigerant Piping: Line sets to be sized based on the connection size of the indoor unit. Each pipe should be insulated individually. Conversion Joints: The outdoor unit includes a package of conversion joints to facilitate installation of the various fan coil sizes. These joints are to be connected to the outdoor unit as needed to match the line set size. Table 4 Conversion Joints No. of Zones Size Adaptor Qty. 2 zone 18 3/8 --1/2 2 3 zone 24 3/8 --1/2 3 3/8 --1/2 3 4 zone 30 1/2 --3/8 1 1/4 --3/8 1 1/2 --5/8 1 4 zone 5 zone Table 5 Additional Refrigerant Charge Additional Charge Required Unit Size No. of Zones Charge oz. (kg.) After ft. (m) /2 --3/8 2 1/4 --3/8 2 1/2 --5/8 2 3/8 --1/2 3 Additional Charge oz./ft. (g/m) Total Maximum Piping Length ft. (m.) (2.0) 49 (15) 0.16 (15) 131 (40) (2.8) 74 (22.5) 0.16 (15) 197 (60) (3.0) 98 (30) 0.16 (15) 263 (80) (4.6) 123 (37.5) 0.16 (15) 328 (100) (4.6) 123 (37.5) 0.16 (15) 328 (100) Additional Refrigerant Calculation Sum Total Liquid Pipe ft. (m) - Additional Charge Required After ft. (m.) x Additional Charge oz./ft. (g/m) 0.16 (15) NOTES: If the calculation results in a negative number no additional refrigerant is required. Electronic expansion valves in the outdoor unit are used as metering devices. 4

5 WIRING All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. Per the caution note, only stranded copper conductors with a 600 volt insulation rating wire must be used. Recommended Connection Method for Power and Communication Wiring: The main power is supplied to the outdoor unit. The field supplied 14/3 stranded wire with ground with a 600 volt insulation rating, power/communication wiring from the outdoor unit to indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are line voltage AC power, one is communication wiring (S) and the other is a ground wire. Wiring between indoor and outdoor unit is polarity sensitive. The use of BX wire is NOT recommended. If installed in a high Electromagnetic field (EMF) area and communication issues exists, a 14/2 stranded shielded wire can be used to replace L2 and (S) between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only.! CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Wires should be sized based on NEC and local codes. Use copper conductors only with a 600 volt insulation rating wire.! CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Be sure to comply with local codes while running wire from the indoor unit to the outdoor unit. Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected. No wire should touch the refrigerant tubing, compressor or any moving parts. Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner. Connecting cable with conduit shall be routed through the hole in the conduit panel. 5

6 DIMENSIONS Table 6 Dimensions UNIT SIZE Height in (mm) 27.6 (703) (810) (810) (1333) (1333) Width in (mm) (845) (946) (946) (1045) (1045) Depth in (mm) (335) (386) (386) (380) (380) Weight-Net lbs (kg) (48) (68) (71) (101.5) (101.5) NOTES: Master valves are not available on the size 18 unit. Fig. 2 - Outdoor Dimensions Size 18 6

7 DIMENSIONS (CONTINUED) Gas Line Liquid Line Fig. 3 - Outdoor Dimensions Size 24 Gas Line Liquid Line Fig. 4 - Outdoor Dimensions Size 30 7

8 DIMENSIONS Gas Line Liquid Line Fig. 5 - Outdoor Dimensions Size 36 8

9 DIMENSIONS Gas Line Liquid Line Fig. 6 - Outdoor Dimensions Size 48 9

10 CLEARANCES A Air-inlet E D B C Air-outlet Fig. 7 - Clearances Outdoor Table 7 Clearances Outdoor Values MINIMUM VALUE UNIT in. (mm) A 24 (609) B 24 (609) C 24 (609) D 4 (101) E 6 (152) NOTES: Outdoor Unit must be mounted at least 2in (50mm) above the maximum anticipated snow depth. 9.8in (25cm) or more for proper airflow 24in (61cm) or more is recommended for service 118in (300cm) or more 19in (48cm) or more on a multiple parallel unit arrangement 4in (10cm) or more on a single parallel unit arrangement 9.8in (25cm) or more for proper airflow 24in (61cm) or more is recommended for service 59in (150cm) or more on a multiple parallel unit arrangement 24in (61cm) or more on a single parallel unit arrangement 24in (60cm) or more Fig. 8 - Clearances for multiple units 10

11 INSTALLATION GUIDE Up to five fan coil units can be connected to one outdoor unit. Refer to the product data for approved combinations. INSTALLATION TIPS Ideal installation locations include: Outdoor Unit A location which is convenient to installation and not exposed to strong winds. A location which can bear the weight of the outdoor unit and where the outdoor unit can be mounted in a level position. A location with appropriate clearances as outlined in Fig. 7. Do not install the indoor or outdoor units in a location with special environmental conditions. For those applications, contact your Ductless representative. OUTDOOR UNIT INSTALLATION 1. Use a rigid base to support unit in a level position. 2. Locate the outdoor unit and connect piping and wiring.! CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Excessive torque can break flare nut depending on installation conditions. NOTES: Install the outdoor unit on a rigid base to reduce noise levels and vibration. Determine the optimal air outlet direction to prevent discharged air from being blocked. If the installation site is exposed to strong winds such as a coastal areas, ensure the fan s proper operation by installing the unit lengthwise along the wall or use dust or shield plates. If the unit needs to be suspended, the installation bracket should comply with the suspension requirements in the installation bracket diagram. The installation wall should be solid brick, concrete or the same intensity construction, or take steps to reinforce and dampen the support. The connection between the bracket and the wall as well as the bracket and the air conditioner should be firm, stable and reliable. Ensure there is no obstacle which may block the radiating air. Strong wind Avoid sags in the suction line to prevent the formation of oil traps. Insulate each tube with minimum 3/8 in. (10 mm) wall thermal pipe insulation. Inserting the tubing into the insulation before making the connections saves time and improves installation quality. 1. The unit is equipped with multiple pairs of service valves. Each pair is clearly marked (color and letter) to identify the indoor unit circuits. In the outdoor unit wiring area, each indoor unit interconnecting terminal block is marked (letter) the same as the corresponding pair of service valves. The indoor units must be piped and wired in matched sets (A to A; B to B, etc.). 2. It is not required to use all of the available fan coil connections if the application does not require them at the current time. The system can be expanded at any time. 3. Conversion joints are supplied with the outdoor unit. They are required for certain fan coil combinations. These joints are to be connected to the outdoor unit as needed to match the line set size. 4. Remove the service connection, if provided with the unit. 90 Oblique Roughness Burr Fig Cut the Pipe 5. Remove all the burrs from the cut cross section of the pipe avoiding any burrs inside the tubes. 6. Remove the flare nuts attached to the indoor and outdoor units. 7. Install the correct size flare nut onto the tubing and make a flare connection. Refer to Table 8 for the flare nut spaces. Table 8 Flare Nut Spacing OUTER DIAM. (mm) A (mm) Max. Min. Ø1/4 (6.35) 0.05 (1.3) 0.03(0.7) Ø3/8 (9.52) 0.06 (1.6) 0.04(1.0) Ø1/2 (12.7) 0.07 (1.8) 0.04(1.0) Ø5/8 (15.88) 0.09 (2.2) 0.08(2.0) Bar "A" Bar Copper pipe Clamp handle Handle Yoke Cone Red arrow mark Fig Flare Nut Spacing 8. Apply a small amount of refrigerant oil to the flare connection on the tubing. 9. Align the center of the pipes and/or the service valve. A07350 Fig. 9 - Wind Installation MAKE REFRIGERANT PIPING CONNECTIONS (OUTDOOR UNIT) IMPORTANT: Use refrigeration grade tubing ONLY. No other type of tubing may be used. Use of other tubing types will void the manufacturer s warranty. Piping Guide: Do not open service valves or remove protective caps from tubing ends until all the connections are made. Bend the tubing with bending tools to avoid kinks and flat spots. Keep the tubing free of dirt, sand, moisture, and other contaminants to avoid damaging the refrigerant system. unit tubing Flare nut Piping Fig Align Pipe Center 10. Connect both the liquid and gas piping to the indoor unit. 11. Tighten the flare nut using a torque wrench as specified in Table Complete the installation. Table 9 Tightening Torque PIPE DIAMETER TIGHTENING TORQUE INCH (mm) Ft-lb N-m Ø1/4 (6.35) 10 to to 17.6 Ø3/8 (9.52) 24 to to 42.0 Ø1/2 (12.7) 37 to to 62.3 Ø5/8 (15.88) 50 to to

12 INSTALL ALL POWER AND INTERCONNECTING WIRING TO OUTDOOR UNIT 1. Mount the outdoor power disconnect. 2. Run power wiring from the main box to the disconnect per NEC and local codes. 3. Remove the field wiring cover (if available) from the unit by loosening the screws. 4. Remove the caps on the conduit panel. 5. Connect the conduit to the conduit panel (see Fig. 13). 6. Properly connect both the power supply and control lines to the terminal block per the connection diagram. 7. the unit in accordance with NEC and local electrical codes. 8. Use the lock nuts to secure the conduit. 9. Reinstall the field wiring cover.! CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Be sure to comply with local codes while running wire from indoor unit to outdoor unit. Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure all wiring is tightly connected. No wire should be allowed to touch the refrigerant tubing, compressor or any moving parts. Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner. Connecting cable with conduit shall be routed through hole in the conduit panel. Outdoor unit Terminal Block Over 1.57" (40mm) G Conduit panel Conduit DRAIN CONNECTIONS Install drains must meet local sanitation codes. Install the outdoor unit drain joint Fit the seal into the drain joint, then insert the drain joint into the base pan hole of the outdoor unit. Rotate 90 to securely assemble them. Connect the drain joint with an extension drain hose to avoid condensate from draining off the outdoor unit during the heating mode. Seal Drain joint Base pan Base pan hole Seal Drain joint Fig Drain Joint Images are for illustration purposes only.! CAUTION In cold climates, ensure the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit. NOTES: Basepan built in with multiple holes for proper draining during defrost. For applications where it is required to seal these holes, and re direct the condensate drain, rubber plugs are available through RCD. Table 10 Rubber Plugs Outdoor Unit Model Number Basepan Base Rubber Plugs RCD Part Number Quantity per unit 38MGRQ18B A MGRQ24C--3 38MGRQ30D A MGRQ36D--3 38MGRQ48E A Fig Field Wiring A07455 ELECTRICAL DATA Table 11 Multi zone Outdoor Unit UNIT SIZE SYSTEM VOLTAGE OPERATING VOLTAGE COMPRESSOR OUTDOOR FAN VOLT / PHASE / HZ MAX / MIN* RLA FLA HP W MCA MOCP /1/ / x x *Permissible limits of the voltage range at which the unit will operate satisfactorily. LEGEND FLA - Full Load Amps MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection RLA - Rated Load Amps 12

13 CONNECTION DIAGRAMS Unit A Unit A Power Supply L1 L2 S Unit B Unit B Power Supply L1 L2 S FIELD POWER SUPPLY L2 L1(A) L2(A) S(A) L1(B) L2(B)S(B) Main Power to Power to Power Supply Unit A Unit A Unit B Unit B Fig Connection Diagram Size 18K 2 Zone Unit A Unit A Power Supply L1 L2 S Unit B Unit B Power Supply L1 L2 S Unit C Unit C Power Supply L1 L2 S FIELD POWER SUPPLY L2 L1(A) L2(A) S(A) L1(B) L2(B) S(B) L1(C) L2(C) S(C) Main Power to Power Supply Unit A Unit A Power to Power to Unit B Unit B Unit C Unit C Fig Connection Diagram Size 24K 3 Zone Unit A Unit A Power Supply L1 L2 S Unit B Unit B Power Supply L1 L2 S Unit C Unit C Power Supply L1 L2 S Unit D Unit D Power Supply L1 L2 S FIELD POWER SUPPLY L2 L1(A) L2(A) S(A) L1(B) L2(B) S(B) L1(C) L2(C) S(C) L1(D) L2(D)S(D) Main Power to Power Supply Unit A Unit A Power to Power to Power to Unit B Unit B Unit C Unit C Unit D Unit D Fig Connection Diagram Size 30K 4 Zone 13

14 CONNECTION DIAGRAMS (CONTINUED) Unit A Unit A Power Supply L1 L2 S Unit B Unit B Power Supply L1 L2 S Unit C Unit C Power Supply L1 L2 S Unit D Unit D Power Supply L1 L2 S FIELD POWER SUPPLY L2 L1(A) L2(A) S(A) L1(B) L2(B) S(B) L1(C) L2(C) S(C) L1(D) L2(D)S(D) Main Power Supply Power to Power to Power to Power to Unit A Unit A Unit B Unit B Unit C Unit C Unit D Unit D Fig Connection Diagram Size 36K 4 Zone Unit A Unit A Power Supply L1 L2 S Unit B Unit B Power Supply L1 L2 S Unit C Unit C Power Supply L1 L2 S Unit D Unit D Power Supply L1 L2 S Unit E Unit E Power Supply L1 L2 S FIELD POWER SUPPLY L2 L1(A) L2(A) S(A) L1(B) L2(B) S(B) L1(C) L2(C) S(C) L1(D) L2(D)S(D) L1(E) L2(E)S(E) Main Power Supply Power to Power to Power to Power to Power to Unit A Unit A Unit B Unit B Unit C Unit C Unit D Unit D Unit E Unit E Fig Connection Diagram Size 48K 5 Zone 14

15 SYSTEM VACUUM AND CHARGE! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Never use the system compressor as a vacuum pump. Refrigerant pipes and indoor unit coils should be evacuated using the recommended 500 microns deep vacuum method. The alternate triple evacuation method may be used if the following procedure is followed. Always break a vacuum with dry nitrogen. NOTES: All units (except the 18,000 BTU model) have a Master Suction and Liquid Line Service Valve. Using Vacuum Pump 1. Completely tighten the flare nuts of the liquid and gas pipes on the indoor and outdoor side (for all fan coils) (see Fig 20). Outdoor Unit Refrigerant Gas Side Unit 10. Reference Table 5 when additional charge is needed. 11. Disconnect the charge hoses and manifold gauge. 12. Using a hexagonal wrench, fully open all the gas and liquid service valves for the size 18 and all the Master Gas and Liquid service valves for sizes (see Fig. 21). Master Gas Port Master Service Valves Individual Service Valves Liquid Side Service Valve Fig Service Valves 2. For size 18, DO NOT open the Gas or Liquid service valves until the evacuation is complete. For sizes 24 48, fully open all the connected Individual Service Valves (with the line set attached). DO NOT open the Master Service Valves until the evacuation is complete (see Fig 22). 3. For size 18, connect the manifold gauge (low side hose) to the Individual Service Valve (5/16 port, use the adapter to fit a 1/4in hose) to evacuate each of the circuits. For sizes 24 48, connect the manifold gauge (low side hose) to the Master service valve (5/16 port, use the adapter to fit a 1/4in. hose) to evacuate all circuits at the same time (see Fig. 24). 4. Connect the charge hose to the vacuum pump (see Fig. 23). 5. Open (fully) the low pressure valve of the manifold gauge (see Fig. 23 for 18. Fig.24 for sizes 24 48). 6. Start the vacuum pump. 7. Evacuate using either the deep vacuum or the triple evacuation method (see Fig. 25 and 26). 8. After the evacuation is complete, fully close the low pressure valve of the manifold gauge and stop the vacuum pump operation. 9. Insert a hexagonal wrench into each Gas Side Service Valve for size 18 or into the Master Gas Side Service Valve for sizes and open the valve by turning the wrench 1/4 counterclockwise. Listen for gas to exit the system (see Fig. 21). Fig Service Valves Sizes NOTES: The Master valve utilizes a 5/16 port. Manifold Gauge Compound gauge Pressure gauge 500 microns Low pressure valve Low pressure hose Gas Line and Port Gas Service valve pressure valve Charge hose Fig Manifold Gauge Vacuum pump Liquid Line Open valves to all connected ports for evacuation Flare nut Fig Manifold Sizes Valve body Valve stem Cap Fig Service Valve Diagram 15

16 Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gauge capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water (see Fig. 25). MICRONS LEAK IN SYSTEM MINUTES Fig Deep Vacuum Graph VACUUM TIGHT TOO WET TIGHT DRY SYSTEM A95424 Triple Evacuation Method The triple evacuation is the recommended method of dehydration. Refer to Fig. 26 and proceed as follows: 1. Pump the system down to 1500 microns and allow the pump to continue operating for an additional 15 minutes. 2. Close the service valves and shut off the vacuum pump. 3. Connect a dry nitrogen cylinder and regulator to the system and break vacuum until the system reaches 2 psig. 4. Close the service valve and allow the system to stand for 1 hr. During this time, the dry nitrogen can diffuse throughout the system absorbing moisture. 5. Pump the system down to 1000 microns. 6. Break the vacuum with dry nitrogen (2 psig). 7. Pump the system down to 500 microns. 8. Perform the hold test for 30 minutes. START UP! CAUTION DO NOT apply power to the outdoor unit if the Master Service Valves are not fully open. Compressor damage will occur. TEST OPERATION Perform a test operation after completing a gas leak and electrical safety check. Review the indoor unit installation instructions and owner s manual for additional start up information. SYSTEM CHECKS 1. Conceal the tubing where possible. 2. Ensure the drain tube slopes downward along its entire length. 3. Ensure all tubing and connections are properly insulated. 4. Fasten the tubes to the outside wall, when possible. 5. Seal the hole through which the cables and tubing pass. OUTDOOR UNIT 1. Are there unusual noises or vibrations during operation? Explain the Following Items to the Customer (with the aid of the Owner s Manual): 2. Explain care and maintenance. 3. Present the installation instructions to the customer. EVACUATE TO 1500 MICRONS BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG EVACUATE TO 1000 MICRONS BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG EVACUATE TO 500 MICRONS MINIMUM (HOLD FOR 30 MINUTES) CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM) RELEASE CHARGE INTO SYSTEM BY OPENING VALVES COMPLETELY Fig Triple Evacuation Method Final Tubing Check IMPORTANT: Ensure the factory tubing on both the indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on the feeder tubes are secure and tight. 16

17 OUTDOOR UNIT DIAGNOSTIC GUIDES For ease of service, the systems are equipped with a diagnostic code display LED on both the indoor and outdoor units. The outdoor diagnostic is displayed on the outdoor unit microprocessor board. There may be a few error codes displayed on the indoor unit that might relate to the outdoor unit s problems. If possible, always check the diagnostic codes displayed on the indoor unit first. In standby, the LED displays. In the compressor operation, the LED displays the running frequency. In the defrosting mode, the LED displays df or alternative displays between the running frequency and df (each appears for 0.5s). During the compressor pre heating cycle, the LED displays PH or alternative displays between the running frequency and PH (each appears for 0.5s). During the oil return process, the LED displays RO or alternative displays between the running frequency and RO (each appears for 0.5s). In the low ambient cooling mode, the LED displays LC or alternative displays between the running frequency and LC (each appears for 0.5s). In the forced cooling mode, the LED displays FC or alternative displays between the running frequency and FC (each appears for 0.5s). When PFC module protection occurs three times within 15 minutes, the LED displays E6 or alternative displays between the running frequency and E6 (each appears for 0.5s). In protection or malfunction, the LED displays an error code or a protection code. The diagnostic codes displayed on the outdoor units are listed on Table 12. OUTDOOR UNIT DISPLAY Table 12 Outdoor Unit Error Display LED STATUS INDOOR UNIT DISPLAY E0 Outdoor EEPROM malfunction F4 E2 Communication malfunction between indoor and outdoor units E1 E3 Communication malfunction between IPM board and outdoor main board E4 Open or short circuit of outdoor temperature sensor (T3 T4 T5 T2B) F2/F1/F3/F6 E5 protection P1 E6 PFC module protection E8 Outdoor fan speed has been out of control (Only for DC fan motor models) F5 E9 Wrong wiring connection of 24K indoor unit F1 No A unit coil outlet temp. sensor or connector of sensor is defective F2 No B unit coil outlet temp. sensor or connector of sensor is defective F3 No C unit coil outlet temp. sensor or connector of sensor is defective F4 No D unit coil outlet temp. sensor or connector of sensor is defective F5 No E unit coil outlet temp. sensor or connector of sensor is defective F6 No F unit coil outlet temp. sensor or connector of sensor is defective P0 Temperature protection of compressor top P2 P1 pressure protection P2 P2 Low pressure protection P2 P3 Current protection of compressor F0 P4 Temperature protection of compressor discharge P5 temperature protection of condenser P6 IPM module protection P0 17

18 Copyright 2017 CAC/BDP W. Morris St. Indianapolis, IN Edition Date: 08/17 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 18 Catalog No: IM-38MGR-02 Replaces: 38MGR-01SI

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... DLCMRA INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 GENERAL... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

Installation Instructions

Installation Instructions 38MGQ Multi-Zone Ductless System Sizes 18, 27, 36 and 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS DLCSRA INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only.

More information

Installation Instructions

Installation Instructions 38MPRA Outdoor Unit Single Zone Ductless System Sizes 09 to 12 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Installation Instructions

Installation Instructions 8GXM / 0GXM Multi---Split High---Wall Duct Free Split System 8GXM --- Size 18k, k, and 0k 0GXM --- Size 9k, 1k, and 18k Installation Instructions NOTE: Read the entire instruction manual before starting

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

Installation Instructions

Installation Instructions 40MAQ / 38MAQ 619PB / 538PR High---Wall Ductless Split System Sizes 09 to 30 Installation Instructions TABLE OF CONTENTS PAGE PARTS LIST... 2 SAFETY CONSIDERATIONS... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS...

More information

Installation Instruction

Installation Instruction 40GRQ / 619FB / 38GRQ / 538FR High- Wall Ductless Split System Sizes 09-18 Installation Instruction NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY

More information

Installation Instruction

Installation Instruction DLFCAB / DLCCAR / DLFCHB / DLCCHR DLFDAB / DLCDAR / DLFDHB / DLCDHR High- Wall Ductless Split System Sizes 09-36 Installation Instruction NOTE: Read the entire instruction manual before starting the installation.

More information

Installation Instructions

Installation Instructions 40MBD Ducted Style Ductless System Sizes 09 to 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless System Sizes 09 to 36 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only. Actual models

More information

Installation Instructions

Installation Instructions 40MHH High Wall Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes only. Actual

More information

Installation Instructions

Installation Instructions 40MBCQ Cassette Ductless System Sizes 09 to 8 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS INDOOR... 5 CLEARANCES INDOOR...

More information

INSTALLATION INSTRUCTIONS R 410A

INSTALLATION INSTRUCTIONS R 410A R 410A Ductless Split System Air Conditioner and Heat Pump MODELS: DLC4(A/H) Outdoor, DLF4(A/H) SIZES: 9K, 12K, 18K, 24K, 30K, and 36K NOTE: Read the entire instruction manual before starting the installation.

More information

HEAT PUMP INSTALLATION MANUAL

HEAT PUMP INSTALLATION MANUAL DUCTLESS INVERTER HEAT PUMP INSTALLATION MANUAL Models: TERRA09HP230V1A TERRA12HP230V1A TERRA18HP230V1B TERRA24HP230V1B Thank you for choosing a Gree Terra Ductless Heat Pump for your customer. Please

More information

Product Data INDUSTRY LEADING FEATURES / BENEFITS

Product Data INDUSTRY LEADING FEATURES / BENEFITS 8MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 0, 6 and 48 Fig. 1 18K Fig. 2 24K and 0K Product Data INDUSTRY LEADING FEATURES / BENEFITS A competitively priced and creative solution to design

More information

Installation Instructions

Installation Instructions Evaporator Coil A Coil --- Cased Multipoise NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. Installation NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION... 2 Inspect Equipment... 2 Select

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

Installation Instructions

Installation Instructions CNPHP Cased N s Horizontal Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION...

More information

Installation Instructions

Installation Instructions CNPHP Cased N Coils Horizontal Heating --- Cooling NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INVERTER SPLIT - TYPE

INVERTER SPLIT - TYPE INVERTER SPLIT - TYPE ISSUE No 2 DATE 04/09/08 P/No 2020323A2868 CONTENTS SAFETY PRECAUTIONS Warning 2 Operating temperature 2 BEFORE INSTALLATION Tools needed for installation 3 Items required for installing

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INSTALLATION INSTRUCTIONS TABLE OF CONTENTS

INSTALLATION INSTRUCTIONS TABLE OF CONTENTS KSAIF KSAIF0501AAA & KSAIF0601AAA Wi-Fi Interface Kit for Ductless Systems INSTALLATION INSTRUCTIONS NOTE: Read and become familiar with these instructions before beginning installation. TABLE OF CONTENTS

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

Installation Instructions

Installation Instructions Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A, Z Chassis Installation Instructions NOTE: Read the entire instruction manual before starting

More information

Installation Instructions Read and become familiar with these instructions before beginning installation.

Installation Instructions Read and become familiar with these instructions before beginning installation. KSAIC020230 (208-230V) 24V Interface Kit for Ductless Outdoor Single Zone matched with Air Handler Installation Instructions Read and become familiar with these instructions before beginning installation.

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Installation Instructions

Installation Instructions 50ES---A, 50EZ---A, 50VL---A, 50VG---A, 50VR---A, 50VT---A, 604D--- ---A, 607C--- ---A, 607E,--- ---A, 704D--- ---A, 707C--- ---A, 707E--- ---A PA3G --- --- A, PH3G --- --- A SMALL PACKAGED PRODUCTS Electric

More information

SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual

SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual Presents SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual 9k,12k 18k 24k, 30k, 36k ECR International, Inc. 2201 Dwyer Avenue, Utica NY 13501 Phone: 800.325.5479

More information

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

Installation Instructions

Installation Instructions 50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions

More information

Installation Instructions

Installation Instructions Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A Manufactured Home Installation Instructions NOTE: The Dual Point Kit can only be installed on

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

Owner s Information Manual

Owner s Information Manual 50EZ---A and 50VT ---A Comfort and Performance 13 and 14 SEER Single Packaged Heat Pump System With PuronR (R ---410A) Refrigerant Single and Three Phase 2---5 Nominal Tons (Sizes 24---60) Owner s Information

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump COMFORT...BUILT TO LAST 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump INSTALLATION MANUAL INDOOR UNIT: 1PAMSH09-SZW-14.5 1PAMSH09-SZW-15 1PAMSH12-SZW-15 1PAMSH18-SZW-15

More information

Installation Instructions

Installation Instructions 50ES--A, 50EZ--A, 50VG--A, B, 50VL--A, B, 50VR--A, 50VT--A, B 604D-- --A, 607C-- --A, B, 607E-- --A, 704D-- --A, 707C-- --A, B, 707E-- --A PA3G -- -- A, PH3G -- -- A, PA4G, PH4G PAD3, PHD3, PAD4, PHD4,

More information

Installation Instructions

Installation Instructions HUMBBSFP1016 HUMCCSFP1016 Small Fan Powered Humidifier and Humidistat Installation Instructions! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.

More information

Residential Piping and Long Line Guideline

Residential Piping and Long Line Guideline AC / HP R-410A Refrigerant Systems Single-Stage, Two-Stage and Variable Speed Models Residential Piping and Long Line Guideline TABLE OF CONTENTS Safety Considerations... 2 Definitions... 2 Introduction...

More information

Installation Instructions

Installation Instructions Installation Instructions Cased Horizontal Furnace Coil CK3B A96318 Fig. 1 Model CK3B Furnace Coil NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper

More information

Installation Instruction

Installation Instruction Installation Instruction Upflow Downflow Heating Cooling CC5A Uncased Coil CD5A Cased Coil SUPPLY RETURN EVAPORATOR COIL DOWNFLOW UPFLOW SUPPLY Fig. 1 Typical Installation of CD5A Cased Coil A96244 NOTE:

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL

HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL Models: RIO09HP115V1A RIO12HP115V1A RIO09HP230V1B RIO12HP230V1B RIO18HP230V1B RIO24HP230V1A Thank you for choosing a Rio Heat Pump

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

KSACN0101AAA Wired Remote Controller (with Timer Function) For Ductless Systems. Owner's Manual

KSACN0101AAA Wired Remote Controller (with Timer Function) For Ductless Systems. Owner's Manual KSACN0101AAA Wired Remote Controller (with Timer Function) For Ductless Systems Owner's Manual TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 3 WIRED CONTROLLER FEATURES AND FUNCTIONS... 5 WIRED CONTROLLER

More information

Fig. 1 - Unit PHD4 and WPH4

Fig. 1 - Unit PHD4 and WPH4 OWNER S MANUAL 14 SEER Single -Package Heat Pump System with R -410A Refrigerant Single Phase and Three Phase 2 to 5 Nominal Tons PHD4 Series F and WPH4 Series B Fig. 1 - Unit PHD4 and WPH4 A09034 NOTE

More information

MULTI HEAT PUMP INSTALLATION MANUAL DUCTLESS INVERTER. Models: MULTI18HP230V1AO MULTI24HP230V1AO MULTI30HP230V1AO MULTI36HP230V1AO MULTI42HP230V1AO

MULTI HEAT PUMP INSTALLATION MANUAL DUCTLESS INVERTER. Models: MULTI18HP230V1AO MULTI24HP230V1AO MULTI30HP230V1AO MULTI36HP230V1AO MULTI42HP230V1AO MULTI DUCTLESS INVERTER HEAT PUMP INSTALLATION MANUAL Models: MULTI18HP230V1AO MULTI24HP230V1AO MULTI30HP230V1AO MULTI36HP230V1AO MULTI42HP230V1AO Thank you for choosing a Gree Multi Ductless Heat Pump

More information

HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL

HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL Models: VIR09HP115V1B VIR12HP115V1B VIR09HP230V1B VIR12HP230V1B VIR18HP230V1B VIR24HP230V1B VIR30HP230V1B VIR36HP230V1B Thank you

More information

Installation Instructions

Installation Instructions 53DS --- 900 --- --- --- 092 Duct---Free Systems Accessory Power Ventilation Kit for In --- Ceiling Cassette Fan Coil Units Size 018 --- 036 Installation Instructions NOTE: Read and become familiar with

More information

WALL MOUNT DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL

WALL MOUNT DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL WALL MOUNT DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL Models: SAP09HP230V1AO SAP12HP230V1AO SAP18HP230V1AO SAP24HP230V1AO SAP09HP230V1AH SAP12HP230V1AH SAP18HP230V1AH SAP24HP230V1AH

More information

CAUTION ! WARNING SAFETY CONSIDERATIONS INTRODUCTION. 38MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 30, 36 and 48

CAUTION ! WARNING SAFETY CONSIDERATIONS INTRODUCTION. 38MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 30, 36 and 48 38MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 30, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 MODEL/SERIAL NUMBER NOMENCLATURES... 2 SPECIFICATIONS OUTDOOR...

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

ROOM AIR CONDITIONER INSTALLATION MANUAL

ROOM AIR CONDITIONER INSTALLATION MANUAL ROOM AIR CONDITIONER INSTALLATION MANUAL (Inverter Split Type) Please read this installation manual completely before installing the product When the power cord is damaged, replacement work shall be performed

More information

Product Data INDUSTRY LEADING FEATURES / BENEFITS. 38MA*R Outdoor Unit Single Zone Ductless System Sizes 09 to 36

Product Data INDUSTRY LEADING FEATURES / BENEFITS. 38MA*R Outdoor Unit Single Zone Ductless System Sizes 09 to 36 38MA*R Outdoor Unit ingle Zone Ductless ystem izes 09 to 36 Product Data INDUTRY LEADING FEATURE / BENEFIT A PERFECT BALANCE BETWEEN BUDGET LIMIT, ENERGY AVING AND COMFORT. The 38MA*R series ductless systems

More information

Installation Instructions

Installation Instructions EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 Installation Instructions NOTE: Read the entire instruction manual before starting

More information

Packaged Heat Pumps. Owner s Guide to Operating and Maintaining Your Heat Pump

Packaged Heat Pumps. Owner s Guide to Operating and Maintaining Your Heat Pump Packaged Heat Pumps Owner s Guide to Operating and Maintaining Your Heat Pump NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the spaces

More information

Product Data INDUSTRY LEADING FEATURES / BENEFITS. 38MBQ Outdoor Unit Single Zone Ductless System Sizes 36 to 48

Product Data INDUSTRY LEADING FEATURES / BENEFITS. 38MBQ Outdoor Unit Single Zone Ductless System Sizes 36 to 48 38MBQ Outdoor Unit Single Zone Ductless System Sizes 36 to 48 Product Data INDUSTRY LEADING FEATURES / BENEFITS A PERFECT BALANCE BETWEEN BUDGET LIMITS, ENERGY SAVINGS AND COMFORT. The 38MBQ series ductless

More information

Choosing the installation site. Installation. 07 Choosing the installation site

Choosing the installation site. Installation. 07 Choosing the installation site Installation Installation warnings: 1. Carefully read the installation manual before beginning. 2. Follow each step as shown. 3. Observe all local, state, and national electrical codes and by qualified,

More information

Installation Manual. KS Series KS09 KS12 KS18 KS24 KS28. J3387_Kaden_Installer_Manual_ indd 1

Installation Manual. KS Series KS09 KS12 KS18 KS24 KS28. J3387_Kaden_Installer_Manual_ indd 1 Wall Mounted AIR CONDITIONER Installation Manual KS Series KS09 KS12 KS18 KS24 KS28 J3387_Kaden_Installer_Manual_050917.indd 1 5/09/2017 9:07 AM J3387_Kaden_Installer_Manual_050917.indd 2 5/09/2017 9:07

More information

Installation. All about the. of your. Split Type Room Air Conditioner. Refer to Page 2 for table of contents.

Installation. All about the. of your. Split Type Room Air Conditioner. Refer to Page 2 for table of contents. All about the Installation of your Split Type Room Air Conditioner Refer to Page 2 for table of contents. www.frigidaire.com USA 1-866-942-1567 www.frigidaire.ca Canada 1-866-942-1567 2020323B2335 (June

More information

Owner s Information Manual

Owner s Information Manual 48ES---A and 48VL---A Comfort and Performance 13 and 14 SEER Single Packaged Air Conditioner and Gas Furnace System With Puron (R---410A) Refrigerant Single and Three Phase 2---5 Nominal Tons (Sizes 24---60)

More information

Installation Instructions

Installation Instructions Performance Series Heat Pumps with PURONr Refrigerant 1 --- 1/2 to 5 Nominal Tons Installation Instructions Fig. 1 --- A07532 NOTE: Read the entire instruction manual before starting the installation.

More information

Installation Instructions Read and become familiar with these instructions before beginning installation.

Installation Instructions Read and become familiar with these instructions before beginning installation. KSAIC005 (5V) KSAIC00230 (208-230V) 24V Interface Kit for Ductless Systems Installation Instructions Read and become familiar with these instructions before beginning installation. SAFETY CSIDERATIS Read

More information

Installation Instructions

Installation Instructions Electric Heaters 5 --- 20 kw Installation Instructions SMALL PACKAGED PRODUCTS 2to5Tons Accessory Electric Heaters (Single---Point Connection) NOTE: Read the entire instruction manual before starting the

More information

Horizontal/Side Discharge Condensing Units

Horizontal/Side Discharge Condensing Units INSTALLATION, OPERATION & MAINTENANCE MANUAL Horizontal/Side Discharge Condensing Units Models CMA12SD-0 CMA18SD-1 CMA24SD-1 CMA30SD-1 CMA36SD-1 CMA48SD-1 517.787.2100 www.marsdelivers.com Horizontal/Side

More information

DUCTLESS MINI-SPLIT INSTALLATION MANUAL COMFORT...BUILT TO LAST

DUCTLESS MINI-SPLIT INSTALLATION MANUAL COMFORT...BUILT TO LAST COMFORT...BUILT TO LAST SINGLE ZONE DUCTLESS MINI-SPLIT INSTALLATION MANUAL 2PAMS SERIES Before using your air conditioner please read this manual carefully and keep it for future reference, along with

More information

Installation Instructions

Installation Instructions ---751,---754,---755,---756 Condensing Heat Exchanger Kit Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation,

More information

Installation Instruction

Installation Instruction 40QAC / 38HDR 40QAQ / 38QRR Ceiling---Suspended Duct Free Split System Sizes 018 to 060 Installation Instruction 40QAC, QAQ Unit 38HDR, QRR Unit the environmentally sound refrigerant NOTE: Read the entire

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

Installation Manual. WAS / WYS Series. For 9,000-36,000 BTU/hr Systems. Inverter+ and Inverter++ Models

Installation Manual. WAS / WYS Series. For 9,000-36,000 BTU/hr Systems. Inverter+ and Inverter++ Models DUCTLESS MINI SPLIT SYSTEM AIR CONDITIONER / HEAT PUMP WAS / WYS Series WAS: Cooling Only Version WYS: Cooling and Heating Version Inverter+ and Inverter++ Models For 9,000-36,000 BTU/hr Systems Installation

More information

Installation Instructions

Installation Instructions 25HHA4 Performance Series Heat Pump with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-25HHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

Inverter Air Conditioner Installation Manual GIN 090/GIN 091 GIN 120/GIN 121 GIN 180/GIN 181 GIN 240/GIN 241

Inverter Air Conditioner Installation Manual GIN 090/GIN 091 GIN 120/GIN 121 GIN 180/GIN 181 GIN 240/GIN 241 Inverter Air Conditioner Installation Manual GIN 090/GIN 091 GIN 120/GIN 121 GIN 180/GIN 181 GIN 240/GIN 241 Please read this user manual first! Dear Customer, Thank you for preferring a Beko product.

More information

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can

More information

Installation Instructions

Installation Instructions Installation Instructions For Cased Coils Upflow-Downflow Heating-Cooling CK5A CK5B SUPPLY RETURN EVAPORATOR COIL DOWNFLOW UPFLOW SUPPLY Fig. 1 Typical Coil Installation NOTE: Read the entire instruction

More information

Service Manual CAUTION ! WARNING SAFETY CONSIDERATIONS INTRODUCTION. 38MA*R Outdoor Unit Single Zone Ductless System Sizes 09 to 36

Service Manual CAUTION ! WARNING SAFETY CONSIDERATIONS INTRODUCTION. 38MA*R Outdoor Unit Single Zone Ductless System Sizes 09 to 36 38MA*R Outdoor Unit Single Zone Ductless System Sizes 09 to 36 Service Manual TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 MODEL / SERIAL NUMBER NOMENCLATURES... 2 SPECIFICATIONS...

More information

Fig. 1 - Unit PGD4, PGS4, WPG4

Fig. 1 - Unit PGD4, PGS4, WPG4 OWNER S MANUAL 14 SEER Single -Package Air Conditioner and Gas Furnace System with R -410A Refrigerant Single Phase 2 to 5 Nominal Tons Three Phase 3 to 5 Nominal Tons PGD4andPGS4SeriesE,WPG4SeriesB Fig.

More information

Installation and Operation Manual. SVH Series. Inverter Single Zone Ductless Mini-Split SVH09SA-0 SVH09SA-1 SVH12SA-0 SVH12SA-1 SVH18SA-1 SVH24SA-1

Installation and Operation Manual. SVH Series. Inverter Single Zone Ductless Mini-Split SVH09SA-0 SVH09SA-1 SVH12SA-0 SVH12SA-1 SVH18SA-1 SVH24SA-1 Installation and Operation Manual SVH Series Inverter Single Zone Ductless Mini-Split SVH09SA-0 SVH09SA-1 SVH12SA-0 SVH12SA-1 SVH18SA-1 SVH24SA-1 www.marsdelivers.com Table of Contents Installation Manual

More information

Installation manual AIR CONDITIONER (SPLIT TYPE) Outdoor Unit RAV-SP300AT2-UL RAV-SP360AT2-UL RAV-SP420AT2-UL. For OUTDOOR USE only.

Installation manual AIR CONDITIONER (SPLIT TYPE) Outdoor Unit RAV-SP300AT2-UL RAV-SP360AT2-UL RAV-SP420AT2-UL. For OUTDOOR USE only. AIR CONDITIONER (SPLIT TYPE) Installation manual Outdoor Unit Model name: RAV-SP300AT2-UL RAV-SP360AT2-UL RAV-SP420AT2-UL For OUTDOOR USE only Not accessible to the general public Vente interdite au grand

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the

More information

DVC/DVH Series. Inverter Single Zone Ductless Mini-Split A-DVC/DVH 09SF A-DVC/DVH 12SF A-DVC/DVH 18SF A-DVC/DVH 24SF

DVC/DVH Series. Inverter Single Zone Ductless Mini-Split A-DVC/DVH 09SF A-DVC/DVH 12SF A-DVC/DVH 18SF A-DVC/DVH 24SF Installation Manual DVC/DVH Series Inverter Single Zone Ductless Mini-Split A-DVC/DVH 09SF A-DVC/DVH 12SF A-DVC/DVH 18SF A-DVC/DVH 24SF B-DVC/DVH 09SF B-DVC/DVH 12SF B-DVC/DVH 18SF B-DVC/DVH 24SF www.marsdelivers.com

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C7BA Series Split System Indoor Cased Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

Installation Instruction

Installation Instruction KGADC0101BVC INTERNAL VENT KIT Installation Instruction NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

Service Manual CAUTION ! WARNING INTRODUCTION. 619PB High Wall Ductless System Sizes 09 to 36

Service Manual CAUTION ! WARNING INTRODUCTION. 619PB High Wall Ductless System Sizes 09 to 36 619PB High Wall Ductless System Sizes 09 to 36 Service Manual TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 MODEL/SERIAL NUMBER NOMENCLATURES... 2 SPECIFICATIONS... 3 COMPATIBILITY...

More information

Product Data INDUSTRY LEADING FEATURES / BENEFITS

Product Data INDUSTRY LEADING FEATURES / BENEFITS 8MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 0, 6 and 48 Fig. 1 18K Fig. 2 24K and 0K Product Data INDUSTRY LEADING FEATURES / BENEFITS A competitively priced and creative solution to design

More information

SPLIT-TYPE ROOM AIR CONDITIONER

SPLIT-TYPE ROOM AIR CONDITIONER Before using your air conditioner, please read this manual carefully and keep it for future reference SPLIT-TYPE ROOM AIR CONDITIONER Please read this installation manual completely before installing the

More information

Installation Manual SPLIT-TYPE ROOM AIR CONDITIONER

Installation Manual SPLIT-TYPE ROOM AIR CONDITIONER SPLIT-TYPE ROOM AIR CONDITIONER Installation Manual IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.

More information

Installation Instructions

Installation Instructions CRHEATER270A00 - ELECTRIC HEATER ACCESSORY SINGLE PACKAGE ROOFTOP UNITS 15 to 27.5 TONS Installation Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS... 1 GENERAL... 1 MODEL/CAPACITY TABLES... 2-11

More information

Installation Instructions

Installation Instructions Electric Heater Kit For use with GC Geothermal Heat Pumps KWCEH0101B05 KWCEH0101B10 KWCEH0101B15 KWCEH0101B20 Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

Installation Instructions

Installation Instructions Installation Instructions EHMA SERIES ELECTRIC HEATERS FOR PAM3 SERIES PACKAGE AIR CONDITIONERS PHM3 SERIES PACKAGE HEAT PUMPS TABLE OF CONTENTS SAFE INSTALLATION REQUIREMENTS... 2 GENERAL INFORMATION...

More information