1 Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging. Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Refrigerant leaks can affect system performance and the escape of refrigerant into the atmosphere can damage the environment. Refrigerant leaks can be detected using different techniques and different leak detection devices. Electronic leak detectors use a probe that is moved about 1 inch per second over the suspected area to detect leaks. An air filter in the tip of the probe must be replaced periodically. Air mixed with refrigerant is drawn over the detecting element. A leak is indicated by a flashing light, audible signal, or both. Refrigerant leaking under pressure, or air entering a system under vacuum, makes ultrasonic sounds that can be picked up by an ultrasonic leak detector. A leak can be found by injecting a small amount of a fluorescent solution into the refrigeration system. Running the compressor disperses the solution. An ultraviolet light is then scanned over the refrigeration system. A bright yellow-green glow from the fluorescent solution indicates a leak. A leak detecting solution can be applied to areas where leaks are suspected. Bubbles indicates a leak. Small leaks may take several minutes for bubbles to form. Leak testing can be done on a fully operational system, or a system with a partial charge or no charge. An operating system can be checked for leaks by looking for visual indications such as oil leaks and listening for escaping refrigerant. Systems without a charge can be checked for leaks by first pressurizing the system to about 10 psi with refrigerant HCFC-22. Increase the test pressure by backing up the refrigerant pressure with regulated nitrogen. Do not exceed the equipment manufacturer s recommended test pressure (about 125 psig maximum) and use an electronic leak detector to pinpoint the leak. A system with a partial charge may have adequate pressure for leak testing. If not, treat it as a system without charge and follow the procedures for a system without charge. When disassembling a brazed joint to make a repair, first make sure there is no pressure in the system.

2 Flux the joint, apply heat, and take the joint apart. After the joint has cooled, remove the flux residue with a wet cloth and warm water. As part of routine service procedures, refrigerant may be recovered, recycled, or reclaimed to prevent its release into the atmosphere. Recovery is the removal and temporary storage of a unit s refrigerant. Recovery does not clean or filter the refrigerant. When a refrigerant is recycled after recovery, acid, moisture, and other contaminants are removed. Recycling does not restore the refrigerant to the cleanliness level of new refrigerant. Reclamation restores contaminated refrigerant to the cleanliness standards of new refrigerant and is done in a special refrigerant reprocessing facility. The evacuation standards for refrigerant recovery machines vary according to the quantity and type of refrigerant to be recovered. Recovery and recycle units must be certified by the EPA and must be able to recover refrigerant to a specified level. Many different recovery machines are on the market. Select a machine to meet your needs and follow the equipment manufacturer s operating instructions. Most recovery machines can recover liquid or vapor. If the refrigerant is contaminated, install a filterdrier between the unit and recovery machine to prevent contamination of the recovery machine. Some recovery machines have the ability to recycle the refrigerant to remove moisture and acid. Recycling machines cannot process the refrigerant to the cleanliness level of new refrigerant. When recovering or recycling different refrigerants with the same machine, always drain and replace the oil in the recovery machine compressor. Certain refrigerants such as HFC-410A require dedicated recovery machines. Air and moisture contamination of a refrigeration system can lead to compressor failure. Air takes up space needed for condensing and makes the compressor work harder. Under the heat of compression, moisture in the system will react with refrigerant to form harmful acids. Air and moisture can be removed from the system by evacuation. A system evacuation should be done whenever the system has been opened to the atmosphere or if tests show the presence of acid or moisture in the system. Evacuation of a system requires a good vacuum pump and an accurate vacuum indicator. A vacuum pump creates a low pressure. The air and water vapor contained inside the refrigeration system flow into this low pressure.

3 As the vacuum pump lowers pressure in the system, the boiling point of any water in the system is lowered, allowing that water to boil off. For example, at a vacuum of 25,400 microns, water boils at around 80 F. A good vacuum pump is able to produce a vacuum of 500 microns or below. The time it takes to achieve a vacuum depends on the size of the system and the pumping capacity of the vacuum pump. For example, a 6 to12 cfm pump is recommended for systems up to 30 tons. Change the oil in the vacuum pump every 10 hours of operation and always change the oil immediately after pumping down a wet or contaminated system. Always use an electronic vacuum gauge capable of measuring to at least 500 microns or below to achieve a vacuum deep enough to dehydrate the system. The lower the micron reading displayed on the gauge, the closer the vacuum is to a perfect vacuum. A standard gauge manifold or a special high-capacity evacuation gauge manifold can be used for evacuation. The high-capacity gauge manifold is designed to evacuate quicker and easier than the standard set. The condition of the system determines the evacuation method. The deep evacuation method is used in most cases. The triple evacuation method is used on wet or contaminated systems. The deep vacuum method requires that the system be pulled down to a vacuum of 500 microns or below. After 500 microns is achieved, the pump is isolated and the vacuum gauge is observed. If the gauge moves to between 1000 and 2000 microns and stabilizes, the system is leak-free but still contains moisture. If the gauge shows a pressure rise and the pressure continues to rise without leveling off, a leak exists. A wet or contaminated system requires the triple evacuation method in which the system is evacuated to 1000 microns three times. After the first and second evacuations, the system is purged with dry, regulated nitrogen to help absorb moisture. Always use regulated nitrogen to pressurize the system. Never use oxygen or compressed air because an explosion will result. After the final evacuation to 1000 microns, the system is charged. Refrigerant can be charged into the system by weight, by superheat or subcooling, or by using pressure charts.

4 Refrigerant can be dispensed from disposable or refillable cylinders in a liquid or vapor state. Refillable cylinders have valves that dispense liquid or vapor refrigerant. The position of a disposable cylinder --upright or inverted -- determines the state of the refrigerant dispensed. Various refrigerant charging scales are available to charge a system by weight. Many are electronic and offer very good accuracy. Charging cylinders use a calibrated shroud that gives the service technician a visual indication of how much charge has been dispensed. Some recovery/recycle units can be used to charge refrigerant. Follow the manufacturer s instruction for liquid or vapor charging. A sight glass in the liquid line can be used to charge systems with a TXV metering device. With a correct charge, the sight glass should be clear with no bubbles at a 130 F condensing temperature. The desired 130 F condensing temperature can be obtained by blocking the condenser coil. The correct charge for a unit can be found in the manufacturer s service literature or on the equipment nameplate. Split systems may require extra charge if longer than normal line sets or accessories such as liquid line filter-driers are installed. The amount of extra charge required can be found in the manufacturer s literature. Charging by weight is a precise method for charging the entire quantity of refrigerant when the weight is known. Liquid or vapor can be charged that way. Liquid charging by weight is the fastest way to charge an empty system. To prevent compressor damage, liquid is charged into the high side of the system through the high-side service valve with the compressor off. Vapor charging by weight is normally done to top off a system when the complete liquid charge cannot be dispensed. With over 50% of the charge in the system, the compressor can be turned on and the remaining charge dispensed through the low-pressure side of the system. The superheat charging method is used to check or adjust the charge of an operating system that uses a fixed-orifice metering device.

5 The first step is to find the required superheat for the current outdoor air dry-bulb temperature and indoor air wet-bulb and dry-bulb temperatures. This is done using a table supplied by the equipment manufacturer. The required superheat and the measured suction pressure can be used with another table to determine what the correct suction line temperature for a correctly charged system should be. Some manufacturers supply this same information on a slide rule-type superheat charging calculator. The subcooling charging method is used to check or adjust the charge of an operating system with a TXV metering device. The subcooling value for a piece of equipment can be found on the unit nameplate. The method uses the temperature of the subcooled liquid as a means of determining if the correct amount of liquid refrigerant is being fed to the TXV. Actual subcooling is obtained by subtracting the measured liquid line temperature from the saturated liquid line temperature. Some manufacturers supply a slide rule-type subcooling calculator to use when charging with this method. Pressure charts can determine if equipment is charged properly by comparing temperatures and pressures on a chart. If the measured discharge pressure is too high, remove excess refrigerant using a recovery unit to lower the discharge pressure. A zoetrope is a blend of two or more refrigerants in which each component of the blend retains its individual characteristics. As a result, the liquid saturation temperature for a zoetrope is different from the vapor saturation temperature for a given pressure. Each refrigerant in a blend retains its own chemical properties, resulting in different leak rates that alter the properties of the original blend. This is called fractionation. Temperature glide is the range of temperatures in which a zoetrope refrigerant will evaporate and condense for a given pressure. Leaks will alter the original blend by fractionation. This requires the recovery of any remaining refrigerant and a recharge with new refrigerant after the leak is repaired. Zeotrope refrigerants should always be charged in the liquid state to avoid fractionation. If vapor charging into an operating system is necessary, charge with liquid fed through a metering orifice attached to the low-pressure side of the system.

6 Due to the temperature glide, superheat and subcooling must be calculated differently when charging a system that uses a zoetrope.

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING UNIT OBJECTIVES After studying this unit, the reader should be able to Describe how refrigerant is charged into systems in

More information

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system Core 1. Ozone in the stratosphere above the earth consists of: a. Molecules containing 3 oxygen atoms. b. Molecules of 2 oxygen atoms. c. Radioactive particles. d. Pollutants that have risen from ground

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery.

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery. HET- 190 ESL Support page 1 CORE Basic Refrigeration Circuit 1. Liquid refrigerant boils in the evaporator. Heat is absorbed. The heat energy absorbed converts refrigerant liquid into vapor. 2. Refrigerant

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

Residential Piping and Long Line Guideline

Residential Piping and Long Line Guideline AC / HP R-410A Refrigerant Systems Single-Stage, Two-Stage and Variable Speed Models Residential Piping and Long Line Guideline TABLE OF CONTENTS Safety Considerations... 2 Definitions... 2 Introduction...

More information

Refrigerant changeover guidelines

Refrigerant changeover guidelines Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC

More information

MASS. MARITIME ACADEMY

MASS. MARITIME ACADEMY MASS. MARITIME ACADEMY REFRIGERATION LAB OUTLINE Rev.3 Fall 2015 Table of Content Page Lab #1: Introduction to refrigeration system components, tools and procedures 1 Lab #2: Familiarization, operation,

More information

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant EarthLinked TXV Kit Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Cased Coil Conversion 4 System Start-Up 17 TXV CCS-410-KIT

More information

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system Core 1. Ozone in the stratosphere above the earth consists of: a. Molecules containing 3 oxygen atoms. b. Molecules of 2 oxygen atoms. c. Radioactive particles. d. Pollutants that have risen from ground

More information

Often fellow technicians, co-workers and field personnel CHARGE REFRIGERANT DETERMINING PROPER SYSTEM

Often fellow technicians, co-workers and field personnel CHARGE REFRIGERANT DETERMINING PROPER SYSTEM Image courtesy of Mastercool. DETERMINING PROPER SYSTEM REFRIGERANT CHARGE Troubleshooting refrigerant system issues is one of the toughest jobs HVACR technicians will ever face. BY RICH PERROTTA A wireless

More information

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system Core 1. Ozone in the stratosphere above the earth consists of: a. Molecules containing 3 oxygen atoms. b. Molecules of 2 oxygen atoms. c. Radioactive particles. d. Pollutants that have risen from ground

More information

R-407A R-448A R-449A

R-407A R-448A R-449A GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants

More information

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT EarthLinked TXV Kit Installation Manual for Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT CONTENTS PAGE Pre-Installation 3 Hydronic Water Module Conversion

More information

APPLICATION & SERVICE GUIDE

APPLICATION & SERVICE GUIDE APPLICATION & SERVICE GUIDE HFC Refrigerant R410a Used In GeoMax2 Geothermal Heat Pump Systems Although the bulk of this manual is information regarding R410a, R407c will also be discussed for purposes

More information

SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION

SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION UNIT OBJECTIVES After studying this unit, the reader should be able to Describe a standing pressure test. Choose a leak detector

More information

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate Technologies, Inc. does not advocate

More information

Refrigerant Recovery Unit, Model RRU134

Refrigerant Recovery Unit, Model RRU134 Installation, Operation & Maintenance Manual IOMM RRU134 Group: Refrigerant Effective: December 2000 Supersedes: New Refrigerant Recovery Unit, Model RRU134 1999 McQuay International Table of Contents

More information

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved. GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant

More information

10/4/2013. The Changing State of Refrigerants

10/4/2013. The Changing State of Refrigerants 10/4/2013 The Changing State of Refrigerants Refrigerant Chemistry CFC = Chlorofluorocarbon Rapid phase-out Stopped U.S. production in 1996 R-11, R-12, R-113, R-114, R-500, R-502 HCFC = Hydrochlorofluorocarbon

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Copy Right By: Thomas T.S. Wan ) Dec. 28, 2012 All Rights Reserved Case Background: Ammonia is one of the important elements to

More information

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant EarthLinked TXV Kit Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Air Handler Conversion 4 System

More information

Vacuum Gauge. Measures lower-than-atmospheric pressure Digital scales. microns psi in. Hg millibars pascals torr millitorr

Vacuum Gauge. Measures lower-than-atmospheric pressure Digital scales. microns psi in. Hg millibars pascals torr millitorr Vacuum Gauge Measures lower-than-atmospheric pressure Digital scales microns psi in. Hg millibars pascals torr millitorr (Sealed Unit Parts Co., Inc.) Compound Gauge Measures pressure and vacuum Low-side

More information

B. A. T. Basic Appliance Training

B. A. T. Basic Appliance Training B. A. T. Basic Appliance Training BASIC REFRIGERATION presented by Phil Whitehead Program Objective The objective of this program is to give you some of the basic elements that are essential to understanding

More information

Otherwise, you can continue reading the file on the following pages.

Otherwise, you can continue reading the file on the following pages. If you d like to be able to print this file out to study off-line or use on the job, a printable version is available for an administrative fee of $3.97 USD. To download the unlocked file, click here.

More information

HVACR Refrigeration

HVACR Refrigeration Western Technical College 10601101 HVACR Refrigeration Course Outcome Summary Course Information Description Career Cluster Instructional Level Total Credits 4.00 Total Hours 108.00 This course is an introduction

More information

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No HEAT PUMPS Carrier Corporation 2003 GT72-01 Cat. No. 020-018 1. This refresher course covers topics contained in the HEAT PUMPS specialty section of the North American Technician Excellence (NATE) certification

More information

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS English Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Instruction Manual

More information

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system. Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs the unwanted heat, this raises the refrigerant

More information

Ariazone 601HD Refrigerant Recovery&Recycling unit

Ariazone 601HD Refrigerant Recovery&Recycling unit Automotive Air-Conditioning Service Equipment Ariazone 601HD Refrigerant Recovery&Recycling unit OPERATOR MANUAL 1 1. SAFETY FIRST! Important safety information's - Read this user manual carefully before

More information

A/C Refrigerant. Air Conditioning systems use refrigerant to move heat from air inside the car to air outside the car

A/C Refrigerant. Air Conditioning systems use refrigerant to move heat from air inside the car to air outside the car A/C Refrigerant Air Conditioning systems use refrigerant to move heat from air inside the car to air outside the car Refrigerants are HAZARDOUS to you and the environment Motor Vehicle Air Conditioning

More information

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system Core 1. Ozone in the stratosphere above the earth consists of: a. Molecules containing 3 oxygen atoms. b. Molecules of 2 oxygen atoms. c. Radioactive particles. d. Pollutants that have risen from ground

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A. Service Literature Corp. 0521 L9 Revised 09 2007 XC13 SERIES UNITS XC13 The XC13 is a high efficiency residential split system condensing unit, which features a scroll compressor and R 410A refrigerant.

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

ariazone 601HD Refrigerant Recovery & Recycling Unit User's manual

ariazone 601HD Refrigerant Recovery & Recycling Unit User's manual ariazone 601HD Refrigerant Recovery & Recycling Unit User's manual Model: Ariazone 601 HD Serial No: 1 1. SAFETY FIRST! Important safety information's - Read this user manual carefully before operating

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

Best Practices for Mobile A/C Refrigerant System Service

Best Practices for Mobile A/C Refrigerant System Service Best Practices for Mobile A/C Refrigerant System Service Note: Refer to the vehicle manufacturer or aftermarket issued service information, the applicable SAE standards, and tool and equipment instruction

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Event #1 Brazing. In this event you will demonstrate how to:

Event #1 Brazing. In this event you will demonstrate how to: Event #1 Brazing Read and interpret the refrigerant circuit drawing Follow all normal safety procedures Use proper brazing techniques to join tubing, fittings, and components Return all tools, instruments,

More information

National Maritime Center

National Maritime Center National Maritime Center Providing Credentials to Mariners U.S.C.G. Merchant Marine Exam (Sample Examination) Page 1 of 26 Choose the best answer to the following Multiple Choice Questions. 1. If a condenser

More information

Chapter 6. Do s & Don ts in Refrigeration & Air-Conditioning Servicing

Chapter 6. Do s & Don ts in Refrigeration & Air-Conditioning Servicing Do s & Don ts in Refrigeration & Air-Conditioning Servicing Who is Better? OR Common Practices that are damaging to the Refrigeration & Air-conditioning Systems Brazing with Cu electrode for brazing Cu

More information

REFRIGERANT CHANGEOVER

REFRIGERANT CHANGEOVER Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

All About. Servicing. R-410a Refrigerant Systems Electrolux Home Products Inc David Taylor Drive Charlotte, NC 28262

All About. Servicing. R-410a Refrigerant Systems Electrolux Home Products Inc David Taylor Drive Charlotte, NC 28262 All About Servicing R-410a Refrigerant Systems 2010 Electrolux Home Products Inc. 10200 David Taylor Drive Charlotte, NC 28262 August 2010 IMPORTANT The purpose of this service manual is to give the service

More information

Refrigerant Installation Quick Reference Guide

Refrigerant Installation Quick Reference Guide Refrigerant Installation Quick Reference Guide To be used only by experienced and licensed refrigeration technicians Preface: This project objective is to replace existing CFC or HCFC refrigerants with

More information

Installation 50% Service 20% Components 20% Applied Knowledge 10%

Installation 50% Service 20% Components 20% Applied Knowledge 10% LIGHT COMMERCIAL REFRIGERATION INSTALLATION CERTIFICATION Certification Information Scope - Tests a candidate's knowledge of the installation, service, maintenance, and repair of Light Commercial Refrigeration

More information

Negative Superheat? Time to Check Your Tools

Negative Superheat? Time to Check Your Tools Negative Superheat? Time to Check Your Tools I was fresh out of school working as an apprentice at my first real HVAC job and I was listening in on a shop conversation between a few techs. They were talking

More information

SERVICE MANUAL FOR MODEL RM-10

SERVICE MANUAL FOR MODEL RM-10 SERVICE MANUAL FOR MODEL RM-10 REQUIRED TOOLS CORDLESS DRILL COPPER CUTTING TUBE 1/2 OPEN WRENCH SOLDERING IRON SCREWDRIVER SET WITH 9/32 SOCKET VISE GRIP PIERCING VALVE PRECISION FLAT BLADE SLOTTED SCREWDRIVER

More information

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications. TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there

More information

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel: Ocean Breeze Split System General Installation Manual Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida 34997 Tel: 772 220 0038 Warning: The Air Conditioning Unit is a pressurized system; potential

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold LOW VAC INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold REF HIGH SPECIAL FEATURES Low battery indicator Displays 63 refrigerants Displays corresponding saturation, dew or bubble point temperature

More information

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications: TECHNICAL DATA SHEET Features and uses of is a non-azeotropic blend of HFC with zero Ozone Depletion Potential et low Global Warming Potential (GWP), formulated to meet the requirements of the F-Gas Regulation

More information

ENVIRONMENTALLY SAFE R-410A SERVICE TECHNIQUES

ENVIRONMENTALLY SAFE R-410A SERVICE TECHNIQUES ENVIRONMENTALLY SAFE R-410A SERVICE TECHNIQUES R-410A Training Supplement to the Desktop Reference and Training Guide Written by: Robert P. Scaringe Edited by: Michael Amato Eleventh Edition April 2004

More information

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane. 1/1/12 RS-45 (R434A): Q & A 1 Q: What is RS-44? 1.Q: What is RS-45 A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-45 contain? A: RS-45 is

More information

Air Conditioning Operation and Troubleshooting Matt Dunham

Air Conditioning Operation and Troubleshooting Matt Dunham Air Conditioning Operation and Troubleshooting Matt Dunham Major Components (10 Minutes) Compressor heart of the system, causes refrigerant to flow by increasing the pressure of the refrigerant Metering

More information

The Essentials Of Working With R-410A

The Essentials Of Working With R-410A The Essentials Of Working With R-410A By Norm Christopherson Several major manufacturers are producing comfort air conditioning equipment using refrigerant 410A. The trend towards the use of 410A continues

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Refrigeration Systems and Accessories

Refrigeration Systems and Accessories As with the Chapter Review Tests and the Final Exam, the tests your understanding of the materials underlying the learning objectives. After you ve reviewed your answers to the Chapter Review Tests, try

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

Refrigerant Recovery Machine. Model No Operating Manual

Refrigerant Recovery Machine. Model No Operating Manual Refrigerant Recovery Machine Model No. 25700 Operating Manual Safety Precautions WARNING : TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE, CAUTION - Risk of injury. This equipment should only be

More information

DESIGN STANDARDS SECTION 15600

DESIGN STANDARDS SECTION 15600 PART 1 - GENERAL 1.1 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.2 General requirements: A. Reciprocating

More information

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014 Class 1: Basic Refrigera0on Cycle October 7 & 9, 2014 Refrigeration Cycle 4 key components needed in a basic refrigera0on cycle: 1. Compressor 2. Condenser 3. Evaporator 4. Metering Device Compressor Compressor

More information

Additional users operating manual

Additional users operating manual Additional users operating manual For use with A2L Refrigerants e.g. R32, 1234yf, 143a, 1234ze This additional manual is valid for the following Promax Refrigerant Recovery Units: MiniMax-E; RG 5410A-E,

More information

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER! 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS INSTALLATION GUIDE R-410A ATTENTION, INSTALLER! After installing the system, show the user how to turn off electricity to the unit. Point out control and switch

More information

Determining Real Time Performance of Residential AC Systems. Presented at the RESNET Conference San Antonio, TX February 28, 2006

Determining Real Time Performance of Residential AC Systems. Presented at the RESNET Conference San Antonio, TX February 28, 2006 Determining Real Time Performance of Residential AC Systems Presented at the RESNET Conference San Antonio, TX February 28, 2006 Bill Spohn testo, Inc. testo Worldwide 100 90 80 70 60 50 40 30 20 10 0

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL RLV-700 REFRIGERANT RECOVERY / RECYCLING UNIT (PATENTED) NATIONAL REFRIGERATION PRODUCTS 985 Wheeler Way Langhorne, PA 19047 (215) 638-8909 FAX (215) 638-9270 REVISED 03-21-2018

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. SECTION 15650 REFRIGERATION EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. B. Related Section: 1. 11400

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

410AREFRIGERANTTRANSITIONGUIDE

410AREFRIGERANTTRANSITIONGUIDE Contactyourlocal ValueFirstrepresenta ve byvisi ng www.valuefirstonline.com/local 410AREFRIGERANTTRANSITIONGUIDE Replace-Retrofit-Repair (seenextpagefordetails) REPLACE OR REPAIR? OUR HVAC EVALUATION HELPS

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

USING THE P-T CARD AS A SERVICE TOOL

USING THE P-T CARD AS A SERVICE TOOL Service Application Manual SAM Chapter 620-115 Section 2 USING THE P-T CARD AS A SERVICE TOOL Reprinted with permission from Sporlan Division, Parker Hannifin Corporation INTRODUCTION Manufacturers of

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

13ACX. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R 410A.

13ACX. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R 410A. Service Literature Corp. 0612 L2 Revised 06 2007 13ACX SERIES UNITS 13ACX The 13ACX is a high efficiency residential split system condensing unit, which features a scroll compressor and designed for R

More information

NO. F ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER KMD-201AA KMD-201AWA MODEL SERVICE MANUAL

NO. F ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER KMD-201AA KMD-201AWA MODEL SERVICE MANUAL NO. F037-775 ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER MODEL KMD-201AA KMD-201AWA SERVICE MANUAL CONTENTS PAGE I. SPECIFICATIONS ---------------------------------------------------------------------------------------

More information

Vehicle Level Heating and Air Conditioning Description and Operation A/C System - Manual. A/C System - Manual

Vehicle Level Heating and Air Conditioning Description and Operation A/C System - Manual. A/C System - Manual 1 of 5 4/7/2008 8:32 AM Home Account Contact ALLDATA Log Out Help Select Vehicle New TSBs Technician's Reference Component Search: METRO TOYOTA OK 1999 Ford Truck F 450 2WD Super Duty V10-6.8L VIN S Vehicle

More information

Fluid Exchange. Refrigerant Handling Systems Recovery/Recycling Systems Fluid Exchangers Flushers Fluid Exchange Accessories BUYER'S GUIDE

Fluid Exchange. Refrigerant Handling Systems Recovery/Recycling Systems Fluid Exchangers Flushers Fluid Exchange Accessories BUYER'S GUIDE Fluid Exchange Refrigerant Handling Systems Recovery/Recycling Systems Fluid Exchangers Flushers Fluid Exchange Accessories 423 ASCOT 424 Refrigerant Recovery/Recycling Systems Recovery and Recycling Systems

More information

SERVICE MANUAL FOR MODEL RM-49

SERVICE MANUAL FOR MODEL RM-49 SERVICE MANUAL FOR MODEL RM-49 REQUIRED TOOLS CORDLESS DRILL DRIVE CUTTING TUBING OPEN WRENCH OF 1/2 RATCHET WITH SOCKET OF 7/16 SCREWDRIVER SET WITH SOCKET OF 9/32 VISE GRIP PIERCING VALVE WATCHER SLOTTED

More information

SECTION 50 - CAB CLIMATE CONTROL

SECTION 50 - CAB CLIMATE CONTROL AIR CONDITIONING SYSTEM DYNAMIC DESCRIPTION The refrigerant circuit of the air conditioning system contains five major components: Compressor, Condenser, Receiver/Drier, Expansion Valve, and Evaporator.

More information

REFRIGERANT RECOVERY Log Book

REFRIGERANT RECOVERY Log Book REFRIGERANT RECOVERY Log Book R E F R I G E R A N T L O G 1) Policy 2) Troubleshooting 3) Condensers Replaced 4) Compressors Replaced 5) Appliance Disposal 6) Accidental Venting 7) R22 NEW 8) R22 Recover

More information

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge ENSPECO Recovery/ Recycle/ Evacuate/ Recharge RMS 3012 RMS 3034 Approved by UL/SAE to J-1991 R12 Purity Standards Approved by UL/SAE to J-2210 R134 Purity Standards This semi-automatic machine will recover

More information

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions CONTENTS PAGE Pre-Installation 3 Placement & Mechanical Information 4 System Application Options 10 Antifreeze Protection 14 Electrical

More information

13ACX. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R 410A.

13ACX. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R 410A. Service Literature Corp. 0612 L2 Revised 07 2006 13ACX SERIES UNITS 13ACX The 13ACX is a high efficiency residential split system condensing unit, which features a scroll compressor and designed for R

More information

The complete approach to the care and management of A/C & refrigeration systems

The complete approach to the care and management of A/C & refrigeration systems The complete approach to the care and management of A/C & refrigeration systems Testing oil with the Phase III Refrigeration Oil Acid Test Kit Flushing with OEM endorsed R x 11-flush Acid removal with

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL LV8 COMMERCIAL REFRIGERANT RECOVERY UNIT NATIONAL REFRIGERATION PRODUCTS 985 WHEELER WAY LANGHORNE, PA 19047 (215) 638-8909 FAX (215) 638-9270 A01001 7/11/96 NRP-OM-LV8 7/96

More information

Corp L9 Revised HS27 SERIES UNITS SPECIFICATIONS. Model No. HS HS HS HS27-042

Corp L9 Revised HS27 SERIES UNITS SPECIFICATIONS. Model No. HS HS HS HS27-042 Service Literature Corp. 9619 L9 Revised 08 2004 HS27 SERIES UNITS HS27 The HS27 is a 14 SEER high efficiency residential split system condensing unit which features a scroll compressor. It operates much

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS RAWL HIGH EFFICIENCY R-410A COMMERCIAL CONDENSING UNITS NOMINAL SIZES 10, 12., 1 & 20 TONS 10 & 12. TON 1 & 20 TON! Recognize this symbol as an indication of Important Safety

More information

SERVICE MANUAL FOR MODEL RM-26

SERVICE MANUAL FOR MODEL RM-26 SERVICE MANUAL FOR MODEL RM-26 REQUIRED TOOLS CORDLESS DRILL DRIVE CUTTING TUBING OPEN WRENCH OF 1/2 RATCHET WITH SOCKET OF 7/16 SCREWDRIVER SET WITH SOCKET OF 9/32 VISE GRIP PIERCING VALVE WATCHER SLOTTED

More information

ENERGY EFFICIENCY PERFORMANCE SAVINGS SERVICE MANUAL R-290

ENERGY EFFICIENCY PERFORMANCE SAVINGS SERVICE MANUAL R-290 hydrocarbon ENERGY EFFICIENCY PERFORMANCE SAVINGS SERVICE MANUAL R-290 974280 INDEX Why R-290... 1 Best Alternative... 2-3 FAQ... 4-7 Labeling... 8-10 The Difference in R-290 vs. R-134a/R-404A... 11-17

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M 2004 Lennox Industries Inc. Dallas, Texas KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04 Supersedes 503,249M Litho U.S.A. COMPRESSOR REPLACEMENT KIT INSTALLATION INSTRUCTIONS FOR COMPRESSOR

More information