Mechanical System Description

Size: px
Start display at page:

Download "Mechanical System Description"

Transcription

1 1. Building Description: Mechanical System Description The building is a Type-1B construction, 9-levels, non-high rise building with 67 affordable family housing units. The first level of the structure includes retail, bathrooms, utility and trash rooms, entry lobby, yard, and offices. The Second level contains 8 dwelling units and the typical residential level contains 9 residential units. The first floor yard and a 9 th floor terrace/community garden will provide common open space with hard-scaped and landscaped areas. The project is located at the corner of Sixth Street and Howard Street and it replaces an existing building at the same location. The project will subscribe to the Multifamily GreenPoint rating system for demonstrating the building energy and water efficiency and other aspects of the Green Building design. The project will also comply with the SF Green Building Ordinance requirements including the Full Building Commissioning. 2. Mechanical System Description: A. Residential Units Heating and Ventilation System. 1. Space Heating: A central hot water heating plant shall be located in the Mechanical Penthouse on Low roof and shall consist of (2) high-efficiency condensing gas boilers, (2) circulation pumps, with automatic lead-lag operation, and VFD for variable flow control. A simple Building Automation System (BAS) will be provided to start-stop and control the boilers, pumps, hot water supply temperature reset based on outside air stat and hot water distribution piping to all heating terminals. b. Residential Units: Each bedroom and living room shall be provided with hot water baseboard convectors or flat steel tube radiators (Runtal or equal) with remote wall thermostats. c. Bathrooms: Provide mechanical ventilation with ceiling mounted exhaust grille connected to the scavenger exhaust fans located on roof. The exhaust duct will be connected to the common exhaust duct riser with 22-inch subduct. d. Kitchen: Recirculation type Kitchen range hood will be provided for each kitchen. Additionally, a kitchen general exhaust grille will be provided and ducted to the common exhaust riser with scavenger exhaust fan on roof. The exhaust duct will be connected to the common exhaust duct riser with 22-inch subduct. e. Ventilations: Due to the project site being located at a heavy traffic area, and to comply with the City Department of Public Health mandate Article 38, up to 3 rd floor the dwelling units will be positively supplied with fresh neutral temperature air from the roof and is exhaust through the common Bath and Kitchen exhaust system. For units with multiple rooms, either the supply air will be distributed. For dwelling unit on fourth floor and above Z-ducts will be provided to provide ventilation air to the units. The combination of positive supply and/or Z-ducts and the 24x7 common exhaust fans on roof, provides ventilation for each unit. B. Residential Common Areas: 1. Corridors: Provide mechanical ventilation with 100% tempered (gas heating) outside air and 100% exhaust / relief. Corridor exhaust system shall be sized to provide minimum ventilation per the T-24 Standards. Supply and exhaust fans shall be located on roof, with duct risers down shaft to serve Levels 1 thru 9. Fire Smoke Dampers shall be provided at all corridor supply and exhaust air outlets. Supply fan shall run continuously, 24 hours a day. Ajmani & Pamidi Inc. Page-1 May 20, 2013

2 2. Trash/Janitor Rooms: Provide mechanical ventilation exhaust with ceiling exhaust fans, discharge into exhaust shafts via branch ducts. The shaft penetrations shall be protected with FSD. 3. Central Laundry Rooms: The central laundry rooms are located on 3 rd and 9 th floors facing the Howard Street. Each room is provided with Hi & Low lovers to provide combustion air to the dryers and general ventilation to the room. The dryers are exhausted sideways to the street. The dryer exhaust vents shall be provided per 2010 CMC with smooth interiors. Where the exhaust duct length exceeds the code maximum, a booster exhaust fans will be provided and interlocked with the operation of the dryer. 4. Exhaust shafts: Shall be constructed of galvanized sheet metal ductwork, up to rooftop scavenger exhaust fans. The exhaust fans shall run continuously, 24 hours a day. C. Office & Multipurpose Room HVAC System: 1. Space Conditioning: Each of the office spaces and the 1 st and 2 nd floors and the multipurpose rooms on floors 4, 6 & 7 will be provide with a central split heat pump system which can serve multiple indoor fan coil units with wall or ceilingmounted cassettes. The air cooled outdoor heat pump unit shall be located on roof. D. Main Multi-Purpose (Community) Room HVAC: 1. The main Multipurpose room is located on the 1 st floor and in the Northwest corner. The room is provided with split system heat pump units. Outside air louvers are provided on the interior yard side and the on the Howard Street sides to draw fresh air and mix with the return air and conditioned and supplied to the space. Excess air is relieved to outdoors through relief louvers and barometric dampers. The indoor fan coils will be ceiling hung within the room in soffited areas. E. First Floor common areas and equipment room Ventilation: 1. Outside Air Supply and Exhaust: Provide mechanical air handling unit with hot water heating coil, ceiling hung, with tempered 100% outside air for supply and in-line exhaust fan for excess air, odor and miscellaneous exhaust air removal. G. First Floor Retail Kitchen Ventilation System: 1. Type-I Grease Hoods: Provide mechanical ventilation with welded metal ductwork with cleanouts and duct riser up to mechanical penthouse roof. Grease exhaust fans shall be located on roof. Provide one system for Retail A. 2. Type II Vapor Hoods: Provide mechanical ventilation with welded stainless steel ductwork and risers up to mechanical penthouse roof. Exhaust fans shall be located on roof. Provide one system for Retail A & B. 3. Make-Up Air System: Provide space on the roof for hood make-up air unit on the roof. H. Life Safety System: 1. Fire smoke dampers shall be provided at all corridor supply and exhaust air outlets. Interlock dampers with Life Safety Control System.\ Ajmani & Pamidi Inc. Page-2 May 20, 2013

3 2. Duct smoke detectors shall be provided at all Air Handling Units in First Floor and the HV-1 unit on Roof, for automatic shutdown. I. Retail Tenant Space Provisions: 1. There are two retail spaces located on the 1 st floor facing the 6 th street. The retail space at the corner of Howard and 6 th Street is dedicated for a restaurant tenant. Outside air and general exhaust will be provided through the exterior wall louvers on 6 th street side. Additional Type-I kitchen hood make-up air will be brought-in from the rooftop make-up air unit. The ductwork and the shaft will be provided for future connection by the tenant provided rooftop make-up air unit. Similarly, exhaust duct risers in dedicated shafts will be provided for Type-I and Type-II hoods from the tenant space to the roof. Space will be ear-marked for the future tenant exhaust fans and make-up air unit. 2. The non-restaurant tenants will be provided exterior wall louvers for outside air and general exhaust on the 6 th street side. The retail tenant will provide necessary heat pump units within his space and the condensing units on roof to provided heating, cooling and ventilation for the respective space. the tenant will be provided with duct risers for type-ii hood exhaust. J. PG&E Gas Meter Room Ventilation: The PG&E gas meter room will be ventilated in accordance with the PG&E Rule J-16 with explosion-proof supply fans and gas detection system. Plumbing System Description A. Residential Units Plumbing System: 1. Domestic Cold Water: a. One (1) house meter shall be provided. Water meter shall be located under sidewalk, with backflow preventer at incoming service located inside building. Water pressure booster pump shall be provided to provide adequate water pressure to fixtures on Floors 3 thru 9 and with hydro-pneumatic tank and expansion tanks located in the penthouse Boiler Room at low Roof. b. Dedicated water meters will be also provided one each for the retail tenant space. The meters will be located under the side walk. Water pipes will be extended to each of the retail spaces, valved and capped for future use. 2. Domestic Hot Water: a. A central hot water heating plant shall be provided to service the dwelling units and the common areas and located in penthouse Boiler Room on low roof and shall consist of (2) gas fired hi-efficiency condensing water heaters, a storage tank and (2) re-circulating pumps (one is standby). The system shall be a re-circulated system. Provision will be made for integration of Solar Hot Water System. b. Each of the three retail tenants will generate their own hot water based on their demand. 3. Natural Gas System: a. One house meter shall be provided to provide gas supply for the water heaters, hydronic boilers and the HV unit on the roof. Gas meter room shall be located adjacent to exterior wall facing 6 th street, with distribution piping to Ajmani & Pamidi Inc. Page-3 May 20, 2013

4 all gas appliances and mechanical equipment on roof and laundry dryers. b. Each of the two retail spaces will be provided with dedicated gas meters and located in the common PG&E gas meter room. Gas piping will be extended from the meter room to the respective tenant spaces, valved and capped for future use by the tenant. 4. Potable Water Booster Pump: A packaged skid mounted booster pump for the domestic water supply. The pump will be located in the 1 st floor pump room to boost the available City water supply pressure to serve the building. A hydropneumatic tank will be provided at the water heater room to maintain constant pressure in the system under low load condition without bringing on the booster pumps. 5. Reclaimed Water Booster Pump: A packaged skid mounted RW booster pump will be provided in the booster pump room at the 1 st floor level to boost the available City water supply pressure to serve the building. A hudropneumatic tank will be provided at the water heater room to maintain constant pressure in the system under low load condition without bringing on the booster pumps. 6. Backflow Preventers: City approved type Reduced Pressure Backflow Preventers (RPBP) will provided for each of the building potable water supply mains, the Reclaimed water supply main, the Irrigation water supply main and each of the restaurant tenant domestic water supply mains. All RPBPs will be located within the 1 st floor pump room. 7. Solar Thermal System: A Solar Thermal (ST) system will be installed on the roof consisting of solar panels, (1) 1,500 gallon solar thermal storage tank, heat exchanger, circulation pumps, closed loop solar panel loop utilizing food-grade ethylene glycol and the open loop domestic hot water loop. The ST system provider will be responsible for providing the system to achieve a solar fraction capacity of 0.3 to 0.7 based on the availability of the roof space for the panels. The ST system will be used to preheat the domestic cold water supply to the water heaters. The solar thermal system components will be located on the low roof near the Domestic water heater equipment room. The plumbing contractor will be specified to provide all the interconnection piping between the potable hot water system and the ST system. All piping will be labeled to identify the system and direction of flow. 8. Building Reclaimed Water (RW) System: As mandated by the City of San Francisco SF-PUC Ordinance, all the water closets, urinals, trap primers, ornamental fountains, mechanical system make-up water will be plumbed separately to utilize the Reclaimed Water (RW) to flush or supply to these fixtures. A rain water harvesting system consisting of 5,000 gallon underground storage cistern, filtration system and pumping system will be provided to reduce the run-off per the City ordinance. The reclaimed water from this system will be used to supply the flushing requirements for the dwelling unit & common area water closets. As the available water pressure will be low, a booster pumping system will be specified. The RW backflow preventer and the booster pump will be located in the domestic water pump room. The entire RW piping system will be specified to use the purple piping system per the California Plumbing Code to clearly distinguish it from the potable water system. Similar to the potable water system, the RW piping and fittings will be Type-L copper but wrapped with purple color tape and labeled to distinguish it from the potable water piping system. Domestic water supply will be connected to the RW system to replenish the system during non-rainy season. 9. Landscape Irrigation Water Supply: One water meter shall be located under sidewalk with backflow preventer located inside building with distribution piping to all planter areas and valve stations. Planter irrigation distribution piping shall be Ajmani & Pamidi Inc. Page-4 May 20, 2013

5 capped for future extension by landscape contractor. 10. Sanitary & Storm Drain: Complete gravity drainage and venting for all fixtures. Storm water drainage shall be directed through a Retention Holding System. 11. The Interior yard landscape drainage shall discharge through sand interceptor. B. Retail Tenant Spaces: 1. Domestic Cold Water: One meter per space shall be provided. Water meter shall be located under sidewalk, with backflow preventer at incoming service located inside building. Water system shall be served with street water pressure for Floors 1 and Domestic Hot Water: A central hot water heating plant shall be located in the Boiler Room and shall consist of (2) gas fired hi-efficiency condensing water heaters, a storage tank and (2) re-circulating pumps (one is standby). The system shall be a recirculated system. 3. Domestic Hot Water for Dishwasher: An integral electric heater shall be provided by dishwasher supplier with dishwasher to boost water temperature to 180 deg.f. 4. Natural Gas System: One meter per space shall be provided in the house gas meter room with distribution piping to all kitchen / dining facility gas appliances and equipment. 5. Sanitary Drainage: Each of the retail tenant spaces will be provided with a 4 sanitary waste and a 3 vent stub outs within the respective tenant spaces for future connection to the toilet rooms added by the respective tenants. Per the City FOG ordinance, the future restaurant tenants will be required to provide point-of-use grease extraction devices (GEDs) to collect and recycle grease waste from each restaurant tenant space. C. Plumbing Fixtures: All fixtures shall be low-flow fixtures with water saving flow restrictors. 1. Water Closets: 1.28 gpf 2. Urinals: None in the project 3. Showers: 1.5 gpm 4. Kitchen Sink: 2 gpm 5. Unit Bathroom Lavatory: 1.5 gpm 6. Public Restroom Lavatory: 0.5 gpm Fire Protection System Description A B General: The fire protection system will be provided for the full coverage of the building in accordance with requirements of California Fire Code, NFPA 13, 24, City & County of San Francisco fire department requirements. Fire Sprinkler Classification: A. Light Hazard The major portion of the main building including the office and public areas. The maximum spacing per head shall not exceed 225 sq. ft. The flow density shall be 0.1gpm/sq. ft. over 1,500 sq. ft. area of sprinkler operation or as per NFPA 13. B. Ordinary Hazard Mechanical rooms, Electrical rooms, and Equipment rooms and similar areas. The maximum spacing per head shall not exceed 130 sq. ft. The flow Ajmani & Pamidi Inc. Page-5 May 20, 2013

6 density for Group-I shall be 0.16gpm/sq. ft. (0.19gpm/sq. ft. for Group-II) over 1,500 sq. ft. area of sprinkler operation or as per NFPA 13. C D E F Fire protection water supply will be from the city. The building fire water line will be extended 5-0 beyond the building exterior wall for connection to the site fire main under civil/site work. At the point of connection between the building supported piping and the street utility piping, settlement joints will be provided to allow for ground settlement under the Civil scope of work. Fire Pump: A fire pump, a jockey pump and associated control system will be provided for the building and located in a dedicated room adjacent to the booster pump room at the basement level. The double check detector valve assembly (DCDVA) will be located within the fire pump room. The room will be equipped with appropriate floor drains to handle the discharge from the relief valves and test valves. Fire Department Pumper Connections: Fire Department Connections (FDC) will be provided and located as required by the local Fire department. A minimum of two (2) FDCs are anticipated for the project and located atleast 50 feet from a hydrant. FDCs shall be provided with polished chrome finish. These locations will be discussed with the local Fire Department and reflected on the architectural drawings. Sprinkler Drain and Test Risers: 2" sch. 40 galvanized drain risers will be located at each of the combination stand pipe in the stairwell for the sprinkler control valve flow test. The discharge from the drain riser shall be terminated indirectly into the building sanitary sewer system per the City of SF Plumbing requirements. The drain riser will be appropriately labeled per NFPA. - END - Ajmani & Pamidi Inc. Page-6 May 20, 2013

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December

More information

2016 Plumbing Supplemental Plan Review List

2016 Plumbing Supplemental Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE SCHEDULE OF S Penalty Fees. The fee for construction work performed before securing permit(s), where required, may be charged a fee of TWO TIMES THE COST OF THE PERMIT (S). Building Fee Schedule Residential

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#58619/Page 1/November 1, 2017 PLUMBING Executive Summary: Presently, the Plumbing Systems serving the building are cold water, hot water, sanitary, waste and vent system, storm drain piping, and natural

More information

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply:

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply: Planning/Building Department 115 Ramsdell Street Fircrest WA 98466 (253) 564-8902 COMMERCIAL PERMIT APPLICATION AND CHECKLIST Depending on the scope of your project, the following submittal requirements

More information

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition

More information

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS City of Redwood City Community Development Department Building and Inspection Department 1017 Middlefield Road Redwood City, CA 94063 Phone (650) 780-7350 2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.

More information

Sanitary Drainage Systems

Sanitary Drainage Systems 11.1 MATERIALS See Section 3.1. Sanitary Drainage Systems 11.2 BUILDING SEWERS AND BUILDING DRAINS 11.2.1 Sewer or Drain in Filled Ground Chapter 11 Building sewers or building drains that are installed

More information

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Ventilation for New Low-Rise Residential Buildings July 20, 2015 Ventilation for New Low-Rise Residential Buildings July 20, 2015 BSC Standard 01 2015 Building Science Corporation 3 Lan Drive, Suite 102 Westford, MA 01886 www.buildingscience.com Contents 1. PURPOSE...3

More information

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE 1. BUILDING FEES: 1 AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE ESTABLISHMENT OF FEES PURSUANT TO N.J.A.C.

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Charles M. LeMaistre PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and

More information

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division These Notes are intended to assist in issuing simple remodel permits. It provides information on the most common requirements relating to the construction or remodeling of kitchens, bathrooms and bedrooms.

More information

Bill de Blasio, MAYOR. build safe live safe. Rick D. Chandler P.E., COMMISSIONER

Bill de Blasio, MAYOR. build safe live safe. Rick D. Chandler P.E., COMMISSIONER E LAA limited alteration application - FILING GUIDE information you need to know Bill de Blasio, MAYOR build safe live safe Rick D. Chandler P.E., COMMISSIONER FIXTURES COMMENTS efile Backflow Preventer

More information

SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL)

SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) Basketball Courts 15 25 Built Improvements Playgrounds, Site Furniture, etc. 20 20 Catch Basin 40 40 Cold Water Lines 40 40 Compactors DHW Supply

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and Element Z for technical

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

CHAPTER 10 TRAPS AND INTERCEPTORS

CHAPTER 10 TRAPS AND INTERCEPTORS CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved

More information

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY ARCHITECTURE ROLLING HILLS ELEMENTARY SCHOOL Rolling Hills Elementary was built in 1999 and is the newest addition to the Mukwonago Area School District. The building contains approximately 64,900 gross

More information

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW... SECTION 230001 TABLE OF CONTENTS SECTION 230001 PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS... 1 1.00 FILED SUB BID... 1 1.01 PROJECT OVERVIEW... 2 1.02 DESIGN CRITERIA... 4 1.03 CODE ISSUES...

More information

STACKS AND STACK VENTS

STACKS AND STACK VENTS CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 199 ANNEX (@ ST. TERESA'S) - QUEENS, 50-15 44TH STREET, New York, 11377 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-18 11:39 AM 2018-05-14 12:27 PM Asset Data

More information

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

Gulfport, Mississippi 21 May 2007

Gulfport, Mississippi 21 May 2007 G PLUMBING GENERAL REQUIREMENTS The D-BC shall design the plumbing system to comply with this criteria and the Plumbing Code. Piping shall be shown on the same plan as the fixtures being served. Pipe size

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 29 - STATEN ISLAND, 1581 VICTORY BLVD, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-10 11:28 AM 2018-01-17 11:37 AM Asset Data Are there fuel tanks?

More information

PENNSYLVANIA. Downloaded

PENNSYLVANIA. Downloaded Housekeeping/Laundry/Maintenance 205.26. Laundry. PENNSYLVANIA Downloaded 01.15.11 (a) A laundry room shall be provided in a facility where commercial laundry service is not used for the washing of soiled

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 841- QUEENS, 48-25 37TH STREET, New York, 11104 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-02 12:54 PM 2018-05-14 12:28 PM Asset Data Are there fuel tanks? Total

More information

Appendix B. Facilities Assessment Report

Appendix B. Facilities Assessment Report Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates

More information

APPENDIX L ALTERNATE PLUMBING SYSTEMS

APPENDIX L ALTERNATE PLUMBING SYSTEMS ALTERNATE PLUMBING SYSTEMS L 1.0 General. L 1.1 Applicability. The intent of this appendix is to provide clarification of procedures for the design and approval of engineered plumbing systems, alternate

More information

Agustin Lara Elementary Academy

Agustin Lara Elementary Academy Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,

More information

PLUMBING REQUIREMENTS

PLUMBING REQUIREMENTS PLUMBING REQUIREMENTS This handout is a compilation of the standard requirements based on the State Plumbing Code and City Ordinance for projects of this type. This information sheet does not contain all

More information

$ Each additional variance per petition. $ All Other Zoning Districts: One variance per petition

$ Each additional variance per petition. $ All Other Zoning Districts: One variance per petition 2015 SCHEDULE COMMUNITY DEVELOPMENT DEPT. ENGINEERING PLAN REVIEW Single Family New Construction All Other Plan Reviews Minimum Engineering Fee Planned Unit Development - PUD: Step #1: Step #2: See Site

More information

CONNECTICUT. Downloaded

CONNECTICUT. Downloaded Housekeeping/Laundry/Maintenance J. Laundry. CONNECTICUT Downloaded 01.15.11 (1) This service, if provided, shall be used exclusively for laundry and shall be remote from resident and food service areas,

More information

NYC Department of Education

NYC Department of Education Asset: LIBERTY HS - MANHATTAN, 250 WEST 18 STREET, New York, 10011 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-29 11:32 AM 2018-02-01 10:16 AM Asset Data Are there fuel tanks?

More information

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc. FAARM-Underground Facility Conceptual Design Review Mechanical Systems Prepared by: Dunham Associates, Inc. April 17, 2012 Dunham Project Number: 0412145-000-00 Dunham Associates Inc. Page 1 of 8 Mechanical

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 86 ANNEX - BRONX, 124 EAMES PLACE, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-05 1:03 PM 2018-04-27 1:35 PM Asset Data Are there fuel tanks? Total

More information

PLUMBING INSTALLATIONS

PLUMBING INSTALLATIONS PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT PLUMBING INSTALLATIONS A homeowner guide to plumbing requirements for single-family dwellings November 2017 contents Permit Requirements... 3 Inspection Requirements...

More information

NYC Department of Education

NYC Department of Education Asset: AUTOMOTIVE TRADES VOC HS - K, 50 BEDFORD AVENUE, New York, 11222 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-01 8:09 AM 2018-05-10 2:18 PM Asset Data Are there fuel

More information

CMHC HOME MAINTENANCE CHECKLIST

CMHC HOME MAINTENANCE CHECKLIST Make sure air vents indoors and outdoors (intake, exhaust and forced air) are not blocked by snow or debris. Check and clean range hood filters on a monthly basis. Test ground fault circuit interrupter(s)

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Chapter 9 Indirect Waste Piping and Special Wastes 9.1 INDIRECT WASTES 9.1.1 General Drains from fixtures, fixture compartments, equipment, appliances, appurtenances, and other devices requiring protection

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 ADMINISTRATION............... 1 R101 Title, Scope and Purpose.................... 1 R102 Applicability.............................. 1 R103

More information

Josefa Ortiz De Dominguez Elementary School

Josefa Ortiz De Dominguez Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS EXISTING MECHANICAL CONDITIONS SUMMARY The items listed below are based on our site visit on Nov 10, 2016. Our review is based on current conditions and anticipated future use of these building. In the

More information

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A vent stack handling 25 dfu s with a developed length of 35 feet shall be inches minimum

More information

Level I Chapter 1 Worksheet

Level I Chapter 1 Worksheet Chapter 1 Worksheet 1. For applicability requirements of the Plumbing Code, refer to: a. Building Code b. Administration and Enforcement Code c. Plumbing Code d. Residential Code 2. The provisions of the

More information

Cook - Wissahickon Elementary School

Cook - Wissahickon Elementary School Cook - Wissahickon Elementary School 201 E. Salaignac St., Philadelphia, PA 19128 HVAC Replacement Project Scope Determination Report May 10, 2018 Prepared by: G.P. Lamina, Jr., P.E., MBA School District

More information

SMC FEE TYPE CURRENT FEE DESCRIPTION/DETAIL

SMC FEE TYPE CURRENT FEE DESCRIPTION/DETAIL CITY OF SNOHOMISH - FEE SCHEDULE - ADOPTED PER RESOLUTION 1385 SMC FEE TYPE CURRENT FEE DESCRIPTION/DETAIL Appeals of Orders, Decisions or Determinations of the Building/Fire Official $500 Building Permit

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 188 - MANHATTAN, 442 EAST HOUSTON STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-08 8:52 AM 2018-06-13 5:06 PM Asset Data Are there fuel tanks?

More information

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. ICP Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A 1 inch diameter faucet, where the inside edge of the spout opening is 2.5 inches away

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

AIRPORT PLUMBING DESIGN STANDARDS REV. 3 3/18/2016

AIRPORT PLUMBING DESIGN STANDARDS REV. 3 3/18/2016 1.1 GOALS The goal of this section is to provide guidance in the design of Plumbing and Fire Protection systems to LAWA standards. The LAWA Plumbing Design Standards are a compilation of general design

More information

1 Exam Prep Plumber s Handbook Tabs and Highlights

1 Exam Prep Plumber s Handbook Tabs and Highlights 1 Exam Prep Plumber s Handbook Tabs and Highlights These 1 Exam Prep Tabs are based on the Plumber s Handbook Revised 2006. Each Tabs sheet has five rows of tabs. Start with the first tab at the first

More information

CHAPTER VI BUILDING PLUMBING

CHAPTER VI BUILDING PLUMBING CHAPTER VI BUILDING PLUMBING 6.1. INTRODUCTION The chapter covers questions related to water demand, distribution and drainage. The basic principles for planning and installing common plumbing systems

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 78 - QUEENS, 48-09 CENTER BLVD., New York, 11109 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-02 11:40 AM 2018-04-19 9:04 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: J.H.S. 216 - QUEENS, 64-20 175 STREET, New York, 11365 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-06 8:51 AM 2017-11-22 10:04 AM Asset Data Are there fuel tanks? Total

More information

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION Quality Products & Value Packages Residential Solutions FIRE PROTECTION COMFORTSUSTAINABILITYCONTROL PRESSURE REGULATORS TRENCH DRAINSHVAC SYSTEMS SAFETY ANTI-SCALE SYSTEMS HEATING & COOLING CONTROLS PLUMBING

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Chapter 5 Traps, Cleanouts and Backwater Valves 5.1 SEPARATE TRAPS FOR EACH FIXTURE a. Plumbing fixtures shall be separately trapped by a water seal trap placed as close as possible to the fixture outlet.

More information

2015 MPC, MMC and IFGC Significant Changes

2015 MPC, MMC and IFGC Significant Changes 2015 MPC, MMC and IFGC Significant Changes Based on the 2015 Michigan Plumbing Code, (MPC), the 2015 Michigan Mechanical Code (MMC) and the 2015 International Fuel GaS Code (IFGC) Purpose This program

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 128 - MANHATTAN, 560 WEST 169 STREET, New York, 10032 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:50 AM 2018-06-14 1:16 PM Asset Data Are there fuel tanks?

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

NYC Department of Education

NYC Department of Education Asset: UNIVERSITY NEIGHBORHOOD - M, 200 MONROE STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-05 11:56 AM 2018-03-02 7:14 PM Asset Data Are there fuel

More information

CHAPTER 10 TRAPS AND INTERCEPTORS TABLE 10-1 HORIZONTAL LENGTHS OF TRAP ARMS (EXCEPT FOR WATER CLOSETS AND SIMILAR FIXTURES) 1, 2

CHAPTER 10 TRAPS AND INTERCEPTORS TABLE 10-1 HORIZONTAL LENGTHS OF TRAP ARMS (EXCEPT FOR WATER CLOSETS AND SIMILAR FIXTURES) 1, 2 CHAPTER 10 TRAPS AND INTERCEPTORS < 1001.0 Traps Required. Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.1, shall be separately trapped by an approved type

More information

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,

More information

Edward Jenner Elementary Academy of the Arts

Edward Jenner Elementary Academy of the Arts Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

DOMESTIC WATER PACKAGED BOOSTER PUMPS

DOMESTIC WATER PACKAGED BOOSTER PUMPS DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 150 foot

More information

NYC Department of Education

NYC Department of Education Asset: J. K. ONASSIS HS FOR INT CAREERS-M, 120 WEST 46 STREET, New York, 10036 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-11 11:37 AM 2017-12-26 12:18 PM Asset Data Are there

More information

Notable Changes in the Mechanical Codes

Notable Changes in the Mechanical Codes Notable Changes in the Mechanical Codes July 2004 The following are some of the changes between the 1997 Uniform Mechanical Code and the 2003 International Mechanical Code(M) and the 2003 International

More information

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL SECTION 15100 PART 1 GENERAL THIS IS A DESIGN GUIDE NOT A SPECIFICATION Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL HVAC SYSTEMS APPLICATIONS 1.1 SCOPE: The intent of this

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:42 AM 2017-12-13 12:31 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 194 - MANHATTAN, 244 WEST 144 STREET, New York, 10030 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-12 10:48 AM 2018-01-29 10:54 AM Asset Data Are there fuel tanks?

More information

Calmeca Academy of Fine Arts and Dual Language

Calmeca Academy of Fine Arts and Dual Language Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

AIRPORT PLUMBING DESIGN STANDARDS REV. 2 11/02/2015

AIRPORT PLUMBING DESIGN STANDARDS REV. 2 11/02/2015 1.1 GOALS The goal of this section is to provide guidance in the design of Plumbing and Fire Protection systems to LAWA standards. The LAWA Plumbing Design Standards are a compilation of general design

More information

Lincoln Public Schools

Lincoln Public Schools Lincoln Public Schools School Building Committee Meeting February 13, 2019 Today s Agenda 1. Review Updated Site Plan 2. Review and Approve OPR 3. Review MEP Systems 4. Review Progress Energy Model Review

More information

CHAPTER 10 TRAPS AND INTERCEPTORS The vent pipe opening from a soil or waste No more than one (1) approved slip joint

CHAPTER 10 TRAPS AND INTERCEPTORS The vent pipe opening from a soil or waste No more than one (1) approved slip joint CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved

More information

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety

More information

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R CHAPTER 31 VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R This page left intentionally blank. 426R 2003 INTERNATIONAL RESIDENTIAL CODE For SI: PIPE SIZE (inches) TABLE P3107.3 COMMON VENT SIZES

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 104 - BROOKLYN, 9115 5TH AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-21 8:55 AM 2018-02-21 1:09 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 160 - BROOKLYN, 5105 FORT HAMILTON PARKWAY, New York, 11219 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-03 8:01 AM 2018-05-18 1:45 PM Asset Data Are there fuel

More information

Read Only Copy Not For Distribution. Chapter 10. Water Supply and Distribution 10.1 QUALITY OF WATER SUPPLY 10.2 RESERVED 10.

Read Only Copy Not For Distribution. Chapter 10. Water Supply and Distribution 10.1 QUALITY OF WATER SUPPLY 10.2 RESERVED 10. Water Supply and Distribution 10.1 QUALITY OF WATER SUPPLY a. Only potable water shall be supplied to plumbing fixtures used for drinking, bathing, culinary use or the processing of food, medical or pharmaceutical

More information

NYC Department of Education

NYC Department of Education Asset: A. PHILLIP RANDOLPH HS - MANHATTAN, 443 WEST 135 STREET, New York, 10031 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-02 8:11 AM 2018-06-14 1:21 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 4 - MANHATTAN, 500 WEST 160TH STREET, New York, 10032 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-08 8:29 AM 2017-12-08 3:44 PM Asset Data Are there fuel tanks?

More information

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device DIVISION 23800 APPENDIX A ASHTABULA CAMPUS: 1. Air Handling Equipment And Appurtenances 2. Exhaust Fans 3. Fume Hood Exhaust Fans 4. Fume Hood monitoring devices and annual certification of face velocity

More information

SECTION PLUMBING

SECTION PLUMBING SECTION 22 10 00 PLUMBING PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish all labor, material and equipment necessary for the complete installation of the sanitary sewer system (including soil and vent piping),

More information

Existing Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1

Existing Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1 L21366/101 090 00.00/Page 1 HVAC EXECUTIVE SUMMARY The North Middlesex Regional High School has received average maintenance of the HVAC systems over its occupied years. Even with adequate maintenance,

More information

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401 Henry L. Chauvin, Architect, LLC 9429 Highway 941 Gonzales, Louisiana 70737 (225) 612-0707 Fax: (224) 612-4565 Email: henry.chauvin@outlook.com Additions & Alterations to Ascension Parish Library Galvez

More information

NYC Department of Education

NYC Department of Education Mechanical Inspection Asset: P.S. 1 - MANHATTAN, 8 HENRY STREET, New York, 10038 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-09-28 8:39 AM 2017-10-12 5:28 PM Asset Data Are there

More information

Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN

Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN 55021 www.faribault.org (507) 333-0359 Property Address: Number of Units Building Type Name

More information

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by

More information

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. The minimum air gap for a fixture with an effective open of 1/2", located away from a

More information

Home Maintenance Schedule

Home Maintenance Schedule Home Maintenance Schedule Regular Maintenance is the Key Inspecting your home on a regular basis and following good maintenance practices are the best way to protect your investment in your home. Whether

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 69 - STATEN ISLAND, 144 KEATING PLACE, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-19 8:39 AM 2018-01-23 4:33 PM Asset Data Are there fuel tanks?

More information

While most maintenance is seasonal, there are some things you should do on a frequent basis year-round:

While most maintenance is seasonal, there are some things you should do on a frequent basis year-round: Inspecting your home on a regular basis and following good maintenance practices are the best way to protect your investment in your home. Whether you take care of a few tasks at a time or several all

More information

B E ROUTE DUCT BEHIND BOOKSHELF. GRILLE MOUNTED ON TOP OF BENCH. BOOK CASE WALL 12x8 8x5 I 8"Ø 7"Ø 125 CFM I D M FLOOR SIDE WALL VENT 6x5 160 CFM 6"Ø 6"Ø 8x10 J C G 1 Section M-1 NOT TO SCALE Project No

More information