AQUAIR S SERIES. of Water to Air Space Heaters INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONSS. Aquair S-10 Aquair S-16 Aquair S-20

Size: px
Start display at page:

Download "AQUAIR S SERIES. of Water to Air Space Heaters INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONSS. Aquair S-10 Aquair S-16 Aquair S-20"

Transcription

1 AQUAIR S SERIES of Water to Air Space Heaters Publication No. ZZ February 2014 INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONSS Aquair S-10 Aquair S-16 Aquair S-20 These instructions are to be left with the User

2 CONTENTS 1 Features 3 2 General Description 3 3 Building Standards & Regulations 4 4 Technical Data 4 5 Preparation & Safety Notes 4 6 Installation Instructions 4 7 Conversion to Side & Upflow Configurations 5 8 Return Air System 5 9 Electrical 6 10 Fan Performance Graph 6 11 Operating Mode 6 12 Commissioning 7 13 Servicing & Maintenance 7 14 Circuit Diagram Notes 9 16 Dimensions Spares List Exploded Diagram 11 In the interest of continuous development Johnson and Starley reserve the right to change specification without prior notice. Johnson and Starley prides itself on it s ability to supply spare parts quickly and efficiently. 2

3 1. FEATURES FIGURE 1. AQUAIR S-10 FEATURES 1 Air Filter 2 Air circulation fan with EC technology 3 PCB control board 4 Hot water return to heat source 5 Hot water flow from heat source Heat Exchanger 7 Air vent position upflow 8 Flow sensor GENERAL DESCRIPTION 2.1 AQUAIR S is a water to air heat exchange unit with a heat output of 10, 16 and 20kW (assuming a hot water supply at 80 C is available). It is supplied as a downflow unit but is also suitable for upflow installations. When used in upflow installations an air vent must be fitted to the heat exchanger. (see section 7) Modairflow control is incorporated. A wire mesh filter is fitted as standard. The unit requires a supply of hot water at a minimum temperature of 60 C. Water connections are left or right handed through knockouts in the sides of the cabinet. 2.2 The air is drawn in through the air filter or air cleaner (if fitted) and the heat exchanger by a centrifugal fan, and is discharged through the opposite end of the unit. A Summer Air Circulation switch (optional) provides the facility to supply unheated air to the air outlets during warm weather. An external timer (not provided) will be required if it is necessary to set the periods of operation. Sales/Spares Replacement Help Line

4 3. BUILDING STANDARDS & REGULATIONS 3.1 TE: Installation shall be in accordance with the following Building Standards (Scotland Consolidation) Building Regulations Building Regulations BS 5720 Mechanical Ventilation and Air Conditioning in Buildings BS 7671 Requirements for Electrical Installations. Wiring Regulations Institute of Electrical Engineers (I.E.E.) Regulations Model and Local Authorities Byelaws Heatlth & Safety Document No The design material specification and installation must only be carried out by competent persons. 4. TECHNICAL DATA ITEM S-10 S-16 S-20 Nominal Rated Output kw Air on Temperature C Air off Temperature C Water Supply Temperature C Water Return Temperature C Water Flow Rate l/s Air Volume m³/h Water Connections bsp ¾ ¾ ¾ Maximum Water Pressure Bar Maximum Power Consumption W 150W 215W 530W Dimensions mm H/W/D 766 x 300 x x 445 x x 481 x 614 Return Air Frame mm 204 x x x 372 Electrical Supply A 230V, 50Hz, fuse rated at 3A Weight kg PREPARATION AND SAFETY TES 5.1 SAFETY INFORMATION Ensure the mains supply voltage, frequency, number of phases and power rating comply with details on the rating label on the unit All wiring must be in accordance with the appropriate standards Ensure safety regulations and practices are adhered to when installing and using this equipment. 5.2 DUCTING INFORMATION It is an advantage to have all the compatible ductwork already installed and ready to connect to the appliance frame Ducting passing through unheated roof voids must be insulated. Ducting runs should be as straight as possible. 4

5 6. INSTALLATION INSTRUCTIONS 6.1 The unit should be positioned to suit duct work and mounted, if necessary, on a plinth or frame strong enough to avoid strain being placed on associated pipe and duct work. 6.2 Clearance of 450mm is required at the front of the casing for servicing and replacement of the heat exchanger. It is recommended that provision be made for complete removal of the unit. 6.3 Sufficient clearance must be provided for the assembly of ducting and pipework. 6.4 Water connections to the unit should be by compression fittings that are suitable for the duty, and isolation valves must be fitted to facilitate the removal of the heat exchanger assembly. IMPORTANT: It is recommended that the water system be drained and flushed prior to the installation of the unit. A strainer should be fitted upstream of the unit. 6.5 If a return air duct is not to be fitted, the top of the unit must be suitably guarded to prevent blockage when installed as a downflow installation 6.6 Once the installion is complete, stick the Aquair decal in position on the front cover top left hand side. 7. CONVERSION TO SIDE & UPFLOW CONFIGURATIONS 7.1 The Aquair standard configuration is a downflow, but can be converted to an upflow. FOR UPFLOW INSTALLATION Unscrew the ten screws on the spigot frame and remove Invert the unit so the filter is at the bottom Screw the frame to the top of the unit to form the duct connection spigot. TE: When using the upflow configuration, an ALTECNIC 502 ROBOCAL Air vent (Part No ) MUST be fitted to the top of the unit. Call Johnson & Starley Ltd for details, Tel: To swivel the cap, break the paint seal by taping the disc and swivel. Remove the cap in the end of the flow pipe and screw in the air vent. FIGURE 2. SPIGOT FRAME FOR SIDE RETURN INSTALLATIONS TE: When using a side return air with either the downflow or upflow you need a blanking plate kit to cover the existing opening. 7.2 Remove the spigot frame and use the blanking plate kit:- Part No.s Aquair 10S = AQ10S-SRA Aquair 16S = AQ16S-SRA Aquair 20S = AQ20S-SRA Tap out the knockouts on you chosen side Fix the template over the knockouts and follow the instructions on the template Fix the spigot frame to the opening and screw into place. 8. RETURN AIR SYSTEM 8.1 The return air system should be constructed of fire-resistant material. It is important that the correct size of return air grilles and ducting is used. Refer to table below for return air duct size, flexible duct size and the return air grille size at maximum output. AQUAIR DUCT EQUIVALENT SIZE FLEXIBLE DUCT SIZE RETURN AIR GRILLE S x 200mm (10 x 8 ) 300mm (12 ) dia 860cm² (137in²) S x 250mm (12 x 10 ) 350mm (14 ) dia 1266cm² (196in²) S x 300mm (16 x 12 ) 406mm (16 ) dia 2118cm² (328in²) 8.2 An adequate and unobstructed return air path is required from areas not served by a directly ducted return and to which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of m²/kW (1in²/250Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms and WC. s. Sales/Spares Replacement Help Line

6 9. ELECTRICAL 9.1 The appliance is supplied with PVC sheathed, 4 core (Black-Brown-Blue-Green/Yellow) 0.75mm 2 csa rated at 6A, connected to a terminal block and exiting through the casing at the top left hand front. The cable is suitable for a 230V 50Hz single phase supply. 9.2 The means of isolating the appliance MUST be via a double pole switch with a contact separation of at least 3mm in both poles, and fused at 3A. If switched live is fitted, a triple pole switch should be used. 10. FAN PERFORMANCE RESISTANCE EXTERNAL TO HEATER AQUAIR 10 AQUAIR 16 AQUAIR m³/h FAN PERFORMANCE FIGURE 3. AQUAIR S FAN PERFORMANCE GRAPH 11. OPERATING MODES 11.1 HIGH TEMPERATURE MODE For high temperature mode the J1 pins has jumper With a thermista-stat connected, the fan will run when a water temperature of 60 C is reached and stops when the water temperature falls to 42 C. The fan speed is controlled by the thermista-stat demand With no thermista-stat connected, the fan will run when a water temperature of 44 C is reached, the fan speed is controlled by the water temperature. The maximum fan speed reached when the water temperature is at 60 C LOW TEMPERATURE MODE For low temperature mode J1 has a jumper across pins With the thermista-stat connected, the fan will run when a water temperature of 33 C is reached and stops when the water temperature falls to 20 C. The fan speed is controlled by the thermistastat demand With no thermista-stat connected, the fan will run when a water temperature of 22 C is reached, the fan speed is controlled by the water temperature. The maximum fan speed reached when the water temperature is at 32 C. 6

7 12. COMMISSIONING 12.1 Ensure the heater is correctly fitted with water and all air vented from the flow and return circuits Switch on electrical supply Setting maximum speed Make a short across thermista-stat connections, if fitted, and adjust the fan speed as required, remove the short Setting minimum fan speed Make a short across the pipe sensor and adjusted the fan speed as required, remove short WITH THERMISTA-STAT FITTED Turn up thermista-stat to call for heat Check for 230V on switch live out With the water at the required temperature ensure fan starts Allow the system to warm up and check temperature rise across unit is 40 C Set water differential to 20 C using lockshield valve or equivalent Turn off thermista-stat and check there is 230V on switch live out Check fan stops when water cools to required temperature WITH THERMISTA-STAT FITTED With the water at the required temperature ensure fan starts Allow the system to warm up and check temperature rise across unit is 40 C Set water differential to 20 C using lockshield valve or equivalent Check fan stops when water cools to required temperature. 13. SERVICING & MAINTENANCE 13.1 ROUTINE MAINTENANCE IMPORTANT: Before carrying out any work on the unit, ALWAYS ENSURE THAT IT IS ISOLATED FROM THE MAINS ELECTRICAL SUPPLY. Remove the filter and unscrew the two retaining screws holding the front cover on the unit, gently pull it forward. Maintenance should be carried out at least once per year Check that the heat exchanger airways are free from obstructions. If necessary, clean with a vacuum cleaner from the air inspection panel, taking care to not damage the airways. CAUTION: THE ELEMENTS OF THE HEAT EXCHANGER ARE VERY FRAGILE Check the condition of the external strainer, cleaning as necessary Check that the air filter is being regularly cleaned in accordance with the User s Instructions PCB REPLACEMENT Ensure that the electrical supply is switched off and isolated PCB REMOVAL Disconnect the wiring at the PCB terminal block Release the 4 clips securing the PCB and withdraw the panel, disconnecting the fan supply lead at the fan tray terminal block Reassembly or replacement is in reverse order FAN REMOVAL Ensure that the electrical supply is switched off and isolated Disconnect the 2 inline connectors on the fan assembly Release the screws securing the fan and withdraw if from the location runners Refitment or replacement is in reverse order HEAT EXCHANGER REMOVAL Ensure that the electrical supply is switched off and isolated Close the isolating valves and drain down the unit Release the clip and remove the heat exchanger and its associated pipework from the unit Refitment or replacement is in reverse order. Ensure that all air locks are expelled, and check for water soundness AIR FILTER REMOVAL The air filter is removed by sliding it out from the front of the unit. Sales/Spares Replacement Help Line

8 14. CIRCUIT DIAGRAM COLOUR CODE bn bl BROWN BLUE PIPE SENSOR bk BLACK g/y r w or y GREEN/YELLOW RED WHITE ORANGE YELLOW LOW VOLTAGE TERMINAL LINK TO TEST DEMAND PIPE SENSOR TEST MAF STAT FAN OPTIONAL JUMPER (SEE INSTRUCTIONS) VOLT FREE DIGITAL STAT MAINS EARTH LINK FOR SUMMER VENT OR TO SET FAN SPEED MAX. REMOVE LINK IF CLOCK OR SWITCHED LIVE IS CONNECTED PCB LINK TO SET FAN SPEED MIN. HIGH VOLTAGE TERMINAL FIGURE 4. AQUAIR S FAN PERFORMANCE GRAPH 14. FAULT FINDING MAF STAT CONNECTED T CALLING FOR HEAT (BOILER T FIRING) WHEN MAF STAT ON MAXIMUM Is there 230 ~ 250VAC across High Voltage terminals 2 & 4? Problem with switched live output going from High Voltage terminal 3 to switch live of boiler Is there 230 ~ 250VAC across High Voltage terminals 1 & 2? Measure DC voltage (5.1V DC Max.) across Low Voltage terminals 3 & 4 Is measured voltage greater than 4.19V? Is there 230 ~ 250VAC across High Voltage terminals 2 & 3? Is there an external clock fitted? Check clock is on & measure output There must be a link between High Voltage terminals 1 & 6 and high voltage termnials 3 & 6. Make sure both links are present Unit mains supply is missing. Check spur e.g. fuse is intact Check connections to high voltage terminals 2 & 3 Measure DC voltage (5.1V DC Max.) across Low Voltage terminals 5 & 6 Is measured voltage greater than 4.7V Check black wire of MAF stat goes to Low Voltage terminal 3 and red wire of MAF stat goes to low voltage terminal 4. Ensure all connections are sound Is 230 ~ 250VAC present? Check for live supply into clock. Repace clock if live is present Open circuit between clock out & High Voltage terminal block 1 Is measured voltage greater than 4.7V Check pipe sensor and connections. If sound, isolate from mains & measure resistance across plug J2 pins 5 & 6 Check harness connections to PCB. If all OK Replace PCB Is measured resistance greater than 11K? Remove MAF stat connections and link Low Voltage terminals TPV & 3. Is there 230 ~ 250VAC across High Voltage terminals 2 & 4? 8

9 FAN T OPERATING WHEN PIPE IS ABOVE 60 C Is the MAF stat connected? Link out low voltage terminals 3 & 4. In If there 230 ~ 250 VAC across High high Voltage voltage terminals 1 & 2? Make sure clock or room stat supplies mains voltage to high voltage terminals 1 & 2. No mains - no fan operation (except for summer vent) Is there and external clock fitted or external mains room stat fitted? There must be a link between High high voltage Voltage terminals 1 & 6 and high voltage terminals 3 & 6. Make sure both links are present Make sure mains is present across High high voltage Voltage terminals 1 & 2 and 23 & 34 Is fan now running? Make sure mains is present across High Voltage terminals 2 & 3 Measure voltage across Low Voltage terminals 5 & 6 Check for mains going into fan plug Is measured voltage greater than 4.7V DC? Measure DC voltage (0 to 10V) within Low Voltage fan connector (blue & yellow) Check pipe and connections. If sound, isolate from mains & measure resistance across plug J2 pins 5 & 6 Is measured resistance greater than 11K? Check sensor is fitted correctly. If it is then replace sensor. Faulty PCB Does the actual pipe temp. match the approx. pipe temp. for the measured voltage in Table A? PCB is not seeing sensor. Confirm by measuring sensor resistance. Replace sensor if resistance is greater then 28K. Is measured voltage greater than 2V? Faulty fan Faulty PCB DC VOLTAGE ACROSS PIPE SENSOR APPROX. PIPE TEMP. C DC VOLTAGE ACROSS PIPE SENSOR APPROX. PIPE TEMP. C DC VOLTAGE ACROSS PIPE SENSOR APPROX. PIPE TEMP. C DC VOLTAGE ACROSS PIPE SENSOR APPROX. PIPE TEMP. C TABLE A Sales/Spares Replacement Help Line

10 DIMENSIONS FIGURE 5. AQUAIR S-10 DIMENSIONS FIGURE 6. AQUAIR S-16 DIMENSIONS FIGURE 7. AQUAIR S-20 DIMENSIONS

11 17. SPARES LIST ITEM DESCRIPTION QTY 10S 16S 20S 1 Air filter 1 AQ AQ AQ Air circulation fan with EC technology 1 AQ AQ AQ PCB control board Mains harness Low voltage harness Temperature flow sensor Heat exchanger 1 AQ AQ AQ Thermista-stat 1 BOS EXPLODED DIAGRAM SPIGOT FRAME 1 2 FRONT COVER SIDE KCK OUTS 4 5 FAN SLIDER 3 FLYING LEAD 7 HOT WATER FLOW FROM HEAT SOURCE HOT WATER RETURN FROM HEAT SOURCE 6 FIGURE 8. AQUAIR S EXPLODED DIAGRAM Sales/Spares Replacement Help Line

12 Johnson & Starley Ltd Rhosili Road, Brackmills, Northampton NN4 7LZ Reception Sales/Spare Service/Warm Air Heating Warm Air Upgrade Johnson & Starley Dravo Division Industrial H&V Sales Anniversary In the interest of continuous developement Johnson & Starley reserve the right to change specifications without prior notice.

WARMCAIR. Condensing Air & Water Heater. High Efficiency Downflow Condensing Air & Water Heater USERS INSTRUCTIONS

WARMCAIR. Condensing Air & Water Heater. High Efficiency Downflow Condensing Air & Water Heater USERS INSTRUCTIONS WARMCAIR Condensing Air & Water Heater Publication No. ZZ 1449-2 September 2016 High Efficiency Downflow Condensing Air & Water Heater USERS INSTRUCTIONS Warmcair C10DW - G.C. No. 43-417-59 Warmcair C16DW

More information

BUILDING REGULATIONS PART L

BUILDING REGULATIONS PART L BUILDING REGULATIONS PART L Publication No. ZZ 1273/1 September 2006 HEATING COMPLIANCE GUIDE (Ref Sections 8 to 11) Johnson & Starley HOT WATER CIRCULATORS INTERLOCK - PUMP OPTIONS INDEPENDENT TIME CONTROL

More information

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No 53 416 06 Publication No. ZZ 180/17 May 2000 These appliances are tested and certified by B G Technology for

More information

Warm Air Central Heating

Warm Air Central Heating Warm Air Central Heating WarmCair Condensing Economaire Hi-Spec www.johnsonandstarley.co.uk As market leaders and innovators, Johnson & Starley have increasingly specialised in domestic heating. We helped

More information

HI-SPEC J25SCA. Warm Air Heater. System E-T Control & Eljan 4/SEA Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS

HI-SPEC J25SCA. Warm Air Heater. System E-T Control & Eljan 4/SEA Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS HI-SPEC J25SCA Warm Air Heater Publication No. ZZ 1325-4 June 2012 System E-T Control & Eljan 4/SEA Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS J25SCA AIR HEATER - G.C. No. 43-416-99

More information

WHHR Midi & Midi Lite

WHHR Midi & Midi Lite WHHR Midi & Midi Lite Residential Whole House Heat Recovery Units with Low Energy EC Motors Optional - Integral LCD Installation, Operating and Maintenance Instructions Image of model with LCD screen Page

More information

Unvented Electric Water Heater 10/15 litre Undersink

Unvented Electric Water Heater 10/15 litre Undersink Unvented Electric Water Heater 10/15 litre Undersink Fitting Instructions and User Guide 1 CONTENTS SECTION PAGE 1.0 INTRODUCTION 2 2.0 TECHNICAL SPECIFICATION 3 3.0 INSTALLATION 4 4.0 COMMISSIONING 9

More information

Alpha CombiMax 350 and 600

Alpha CombiMax 350 and 600 Installation and Servicing Instructions Alpha CombiMax 350 and 600 Unvented Hot Water Store for use with the Alpha 240/280 Range of Gas Fired Combination Boilers For Technical help or for Service call...

More information

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions Commissioning Data: To be completed by the Commissioning Engineer. Refer to User/Homeowner Guide

More information

Gas Condensing Boilers

Gas Condensing Boilers Gas Condensing Boilers www.johnsonandstarley.co.uk QuanTec Ultra Efficient Condensing Gas Boilers Including HR28C with Integral Passive Flue Gas Heat Recovery As market leaders and innovators, Johnson

More information

ECONOMAIRE 32. Warm Air Heater. with Intejan Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS

ECONOMAIRE 32. Warm Air Heater. with Intejan Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS ECONOMAIRE 32 Warm Air Heater Publication No. ZZ 1088-14 January 2016 with Intejan Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS Economaire 32 Air Heater - G.C. No. 42-416-14 Intejan

More information

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit DC Heat Recovery Unit MVHR Wholehouse heat recovery unit Stock Ref. N DC Heat Recovery Unit MVHR 443423 Installation, Maintenance & Users Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

More information

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION SOLARCYL IM/SC INSTALLATION MANUAL This manual gives detailed advice for installation and should be read carefully prior to fitting any unvented

More information

HI-SPEC J25SCA. Warm Air Heater. System E-T Control & Eljan 4/SEA Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS

HI-SPEC J25SCA. Warm Air Heater. System E-T Control & Eljan 4/SEA Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS HI-SPEC J25SCA Warm Air Heater Publication No. ZZ 1325-5 September 2014 System E-T Control & Eljan 4/SEA Water Circulator INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS J25SCA AIR HEATER - G.C. No.

More information

Purge Ventilation Unit. Product Manual. ventilation systems TP625

Purge Ventilation Unit. Product Manual. ventilation systems TP625 EN Purge Ventilation Unit TP625 Product Manual ventilation systems Warnings, Safety Information and Guidance Important Information Important: read these instructions fully before the installation of this

More information

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION 0 RD 0 RI 0000-06 IM/ IM/a INSTALLATION MANUAL This manual gives detailed advice for installation and should be read carefully prior to fitting

More information

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER CARVER - CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER 1:0 SPECIFICATIONS Water capacity Water connections Water supply 9 litres (2 gallons)

More information

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Installation and Maintenance Instructions Retain for future reference 3. To remove the impeller, unscrew the central screw with a 7mm nut runner

More information

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS INSTRUCTIONS FOR: INFRARED IP55 HEATER MODEL:- QZWP45N Thank you for purchasing a Consort Claudgen product. Manufactured to a high standard this product will, if used according to these instructions and

More information

Installation and User Instructions HS10U, HS15U.

Installation and User Instructions HS10U, HS15U. Installation and User Instructions HS10U, HS15U. MULTIPOINT Please read and understand these instructions before starting work. Please leave this leaflet with the user following installation PACK CONTENTS

More information

Bosch Group. 15SBi / 24SBi. WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water

Bosch Group. 15SBi / 24SBi. WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water Bosch Group 15SBi / 24SBi WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water INSTALLATION AND SERVICING INSTRUCTIONS 24SBi This appliance is for use with Natural Gas or

More information

HEATRAE SADIA. Installation and User Instructions for the UTC Undersink Vented Water Heater

HEATRAE SADIA. Installation and User Instructions for the UTC Undersink Vented Water Heater HEATRAE SADIA The quality name in water heating Installation and User Instructions for the UTC Undersink Vented Water Heater UTC 15 Please read and understand these instructions before starting work. Please

More information

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance MRXBOX95B-LOFT Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting Installation and Maintenance The EMC Directive 2004/108/EC The Low Voltage directive 2006/95/EC 1.0 Introduction

More information

HI-SPEC J32 WARM AIR HEATER System E-T & Basic Control

HI-SPEC J32 WARM AIR HEATER System E-T & Basic Control HI-SPEC J32 WARM AIR HEATER System E-T & Basic Control Publication No. ZZ 783-15 September 2010 INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. NUMBERS: Air Heater 42 451 05 These instructions

More information

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for vented systems.

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for vented systems. ECONOPLATE H1-heat only HEAT INTERFACE UNIT Installation, Commissioning and Servicing Instructions for vented systems. Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

"B" SERIES OPEN FLUED WARM AIR HEATERS

B SERIES OPEN FLUED WARM AIR HEATERS INSTALLATION, COMMISSIONING AND SERVICING INSTRUCTIONS "B" SERIES OPEN FLUED WARM AIR HEATERS STORE NEAR HEATER Installer :... Address :... Place :... Telephone :... Date :... Distributed by: J O H N S

More information

Alpha FlowSmart 25 and 50

Alpha FlowSmart 25 and 50 Installation and Servicing Instructions Alpha FlowSmart 25 and 50 Hot Water System incorporating a Flue Gas Heat Recovery Device, Primary Store and an Alpha CD Condensing Combination Boiler For Technical

More information

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for unvented systems.

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for unvented systems. ECONOPLATE H1-heat only HEAT INTERFACE UNIT Installation, Commissioning and Servicing Instructions for unvented systems. Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P

FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P 1 of 13 These instructions should be read by: The specifying engineer. The installation engineer. The user. The service engineer. WARNINGS Failure

More information

FMH Range Hoods. Installation, Operation & Maintenance Instructions

FMH Range Hoods. Installation, Operation & Maintenance Instructions Installation, Operation & Maintenance Instructions Fourneaux de France Ltd Unit 3 Albion Close, Newtown Business Park, Poole Dorset, BH12 3LL Tel 01202-733011 Email info@fdef.co.uk www.fdef.co.uk W1103

More information

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION Ecoline Geo RI HP INSTALLATION MANUAL The Ecoline GEO is an indirect unvented cylinder designed and approved for use with a heat pump. The

More information

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2 INTEGRA PLUS Installation and Wiring Instructions Stock Ref. N INTEGRA PLUS 437666 230V~ 50Hz ABC PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS. IPX2 VENT-AXIA

More information

ECo 2 Wall INSTALLATION GUIDE FOR ENGINEER / INSTALLER

ECo 2 Wall INSTALLATION GUIDE FOR ENGINEER / INSTALLER ECo 2 INSTALLATION GUIDE FOR ENGINEER / INSTALLER Safety IMPORTANT Be sure to have read and understood these instructions before beginning the installation process. PRE-INSTALLATION CHECK LIST The ECO

More information

Alpha CD13R,18R and 24R

Alpha CD13R,18R and 24R Installation and Servicing Instructions Alpha CD3R,8R and 24R Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Regular Boiler Range For Technical help or for Service call...

More information

Aquatap (Boil only) Installation and user manual

Aquatap (Boil only) Installation and user manual Aquatap (Boil only) Installation and user manual CONTENTS SECTION PAGE 1.0 INTRODUCTION 3 2.0 TECHNICAL SPECIFICATION 4 3.0 INSTALLATION - IMPORTANT INSTALLATION POINTS 7 4.0 INSTALLATION - MOUNTING THE

More information

Installation, Operating and Servicing Instructions

Installation, Operating and Servicing Instructions Installation, Operating and Servicing Instructions Wall Mounted Water Boiler WMB3F/B,WMB3F/W Please make a note of your product details for future use: Date Purchased: Model Number: Serial Number: Dealer:

More information

Decentralised Mechanical Extract Ventilation 2 Speed Axial Extract Fan Installation Guide. Fig. 2 Fan components.

Decentralised Mechanical Extract Ventilation 2 Speed Axial Extract Fan Installation Guide. Fig. 2 Fan components. 1.0 Introduction The dmev 2 speed axial extract fan has been designed for continuous ventilation for kitchens or wet rooms and should be installed using 100mm dia. ducting. The unit can be installed in

More information

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 COMPACT PLUS 10 and 15 Litre Unvented Under and Over Sink Water Heater INSTALLATION AND USER GUIDE 1 DIMENSIONS 10L - 250mm 15L - 310mm 100mm 80mm 410mm

More information

AquaFlo II. Issue 3 December Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater

AquaFlo II. Issue 3 December Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater Installation, Maintenance and User Instructions AquaFlo II Issue 3 December 2011 Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater Please leave

More information

Performa System 12e, 18e, 24e & 28e

Performa System 12e, 18e, 24e & 28e Performa System 12e, 18e, 24e & 28e Gas Fired Wall Mounted System Boilers Installation and Servicing Instructions Please leave these instructions with the user Natural Gas Potterton Performa System 12e

More information

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

WHHR125DC Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use "WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor Installation, Operating and Maintenance Instructions domestic and commercial use Page 2 Contents Section Page Number Introduction 3 How

More information

FLAT2000L/R. Low Energy Positive Input Ventilation Unit. Installation and Maintenance. Alternative inlet position. 2.1 Spigot Inserts.

FLAT2000L/R. Low Energy Positive Input Ventilation Unit. Installation and Maintenance. Alternative inlet position. 2.1 Spigot Inserts. FAT2000/R ow Energy Positive Input Ventilation Unit Installation and Maintenance The EMC Directive 204/0/EU The ow Voltage Directive 204/5/EU.0 ITRODUCTIO The uaire Drimaster/Flatmaster range has been

More information

INSTALLATION & TECHNICAL MANUAL

INSTALLATION & TECHNICAL MANUAL The COMET Range of Boilers the ultimate solution for central heating INSTALLATION & TECHNICAL MANUAL If you require any further assistance: Telephone: 01698 820533 Fax: 01698 825697 E-mail: info@electric-heatingcompany.co.uk

More information

Signature, Sovereign, Sentry, Sentinel, Staccato Fan-Assisted Radiator. Installation & User Guide

Signature, Sovereign, Sentry, Sentinel, Staccato Fan-Assisted Radiator. Installation & User Guide Signature, Sovereign, Sentry, Sentinel, Staccato Fan-Assisted Radiator Installation & User Guide Dear Installer, The following items should be included in the carton; Product complete with pre-wired mains

More information

Bosch Group. 15SBi / 24SBi. WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water

Bosch Group. 15SBi / 24SBi. WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water Bosch Group SBi / SBi WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water INSTALLATION AND SERVICING INSTRUCTIONS SBi This appliance is for use with Natural Gas or LPG (Cat

More information

IF IN DOUBT, INSTALLATION SHOULD BE MADE BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH CURRENT WIRING REGULATIONS.

IF IN DOUBT, INSTALLATION SHOULD BE MADE BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH CURRENT WIRING REGULATIONS. INSTALLATION/OPERATING INSTRUCTIONS FOR C100 & C100T Thank you for purchasing a quality Extractor fan from Greenbrook. Please read these instructions fully prior to initial use. Every effort has been made

More information

FLUEBOOST. flueboost 350 gas fire model

FLUEBOOST. flueboost 350 gas fire model 350 FLUEBOOST flueboost 350 gas fire model The flueboost is a box shaped unit with in line spigots for the flue connection, a pressure switch to ensure safe operation and plug-in electrical fittings for

More information

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning Sentinel Kinetic MVHR and Kinetic Plus MVHR Installation & Commissioning Stock Ref. N 438222 Kinetic B 443319 Kinetic BH 438342 Kinetic V 443028 Kinetic Plus B 443029 Kinetic Plus CV/CP PLEASE RETAIN THESE

More information

ELECTRIC COMBINATION BOILER. (European Patent No: Design Right Protected.) TH12-450U MRK 2

ELECTRIC COMBINATION BOILER. (European Patent No: Design Right Protected.) TH12-450U MRK 2 ELECTRIC COMBINATION BOILER (European Patent : 1757678. Design Right Protected.) TH12-450U MRK 2 INCLUDES THERMAL SOLAR & WOOD BURNING STOVE WITH WATER JACKET APPENDIX This product is suitable for connection

More information

SUPREME 140, 155, 170

SUPREME 140, 155, 170 FULL HALF FULL TEMPERATURE READY ON SUPREME 140, 155, 170 Fitting Instructions and User Guide 1 Please read and understand these instructions prior to installing your Supreme water heater. Particular attention

More information

Wall hung combination boilers. This is a CAT II2H3+ appliance USER, INSTALLATION AND SERVICING INSTRUCTIONS SUPPORTED BY

Wall hung combination boilers. This is a CAT II2H3+ appliance USER, INSTALLATION AND SERVICING INSTRUCTIONS SUPPORTED BY Wall hung combination boilers This is a CAT II2H3+ appliance SUPPORTED BY USER, INSTALLATION AND SERVICING INSTRUCTIONS Index Introduction... 3 User instructions...3 Introduction... 4 Controls and lighting...

More information

Installation and Operating Instructions. Budget priced instant boiling water heater for beverages.

Installation and Operating Instructions. Budget priced instant boiling water heater for beverages. Installation and Operating Instructions Zip Econoboil Budget priced instant boiling water heater for beverages. Model No. Description Reg.No. Part No. HS503 Zip Econoboil 3.0 litre White EB003 103592 HS505

More information

Xcell 270 Longlife DC wholehouse heat recovery unit

Xcell 270 Longlife DC wholehouse heat recovery unit Xcell 270 Longlife DC wholehouse heat recovery unit Installation and maintenance instructions Xpelair Xcell 270 Longlife DC wholehouse heat recovery unit Xcell 270, Xcell 270BP Please leave this leaflet

More information

MEGAFLO HE Iss 1

MEGAFLO HE Iss 1 MEGAFLO HE 1 36 00 5843 Iss 1 Contents Contents SECTION PAGE 1 INTRODUCTION... 3 2 GENERAL REQUIREMENTS... 4 3 INSTALLATION - GENERAL... 5 4 INSTALLATION - DIRECT UNITS... 8 5 INSTALLATION - INDIRECT UNITS...

More information

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual. 1 MHG Heating Ltd ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual. Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR Telephone 08456 448802 Fax 08456 448803

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

Speedflow Undersink Unvented Water Heater. Models SF05K, SF10K and SF15K. Instruction Manual

Speedflow Undersink Unvented Water Heater. Models SF05K, SF10K and SF15K. Instruction Manual Speedflow Undersink Unvented Water Heater Models SF05K, SF10K and SF15K Instruction Manual Version 3.0 June 2010 HYCO SPEEDFLOW UNVENTED WATER HEATER MODELS SF05K (5 Litres) SF10K (10 Litres) AND SF15K

More information

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL Instruction Manual. SMARTELEC 2 SmartElec ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL 0 F1 INDEX Section General information ------------------------------------------------------------ 1 Dimensions

More information

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax: TECHNICAL MANUAL CX(E) SPLIT SYSTEMS CONTENTS INDEX PART NUMBERS, OPTIONS, UNIT COMBINATIONS, DIMENSIONS & WEIGHTS 3 PERFORMANCE DATA & AIR FLOW 4 SOUND POWER AND SOUND PRESSURE LEVELS 5 ELECTRICAL DATA

More information

INSTALLATION AND MANINTENANCE INSTRUCTIONS

INSTALLATION AND MANINTENANCE INSTRUCTIONS INSTALLATION AND MANINTENANCE INSTRUCTIONS Appr. Nr. A 9503 T - 0085 AQ 0765 PEGASUS F2 T HIGH EFFICIENCY GAS-FIRED CAST-IRON BOILERS Models 51-68 - 85-102 2 Contents 1. General technical data 2. Dimensional

More information

24i RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

24i RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS 24i RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS GC NUMBERS N.G. 47 311 37 L.P.G. 47 311 38 BOILER OUTPUT To Domestic

More information

INSTALLATION & TECHNICAL MANUAL

INSTALLATION & TECHNICAL MANUAL The FUSION Range of Boilers INSTALLATION & TECHNICAL MANUAL If you require any further assistance: Telephone: 01698 820533 Fax: 01698 825697 E-mail: info@electric-heatingcompany.co.uk Or visit our website

More information

Zip Econoboil. Installation and Operating Instructions. Budget priced instant boiling water for canteens and kitchens.

Zip Econoboil. Installation and Operating Instructions. Budget priced instant boiling water for canteens and kitchens. Installation and Operating Instructions Zip Econoboil Budget priced instant boiling water for canteens and kitchens. 103592 Zip Econoboil 3.0 litre White HS503 105592 Zip Econoboil 5.0 litre White HS505

More information

MRXBOX95-LH1/LH2. Mechanical Ventilation Unit with Heat Recovery for Loft Mounting Installation and Maintenance. Spigot 4.

MRXBOX95-LH1/LH2. Mechanical Ventilation Unit with Heat Recovery for Loft Mounting Installation and Maintenance. Spigot 4. MRXBOX95-LH1/LH2 Mechanical Ventilation Unit with Heat Recovery for Loft Mounting Installation and Maintenance The EMC Directive 2004/108/EC The Low Voltage Directive 2006/95/EC 1.0 Introduction Unit must

More information

The Professional s Choice

The Professional s Choice CPF Series Models: CPF2100, CPF210, CPF310, CPF4100-3, CPF4100-6 & CPF6100 Auto-Fill Catering Water Boiler With Integrated Multi-Filter Installation And User Instructions The Professional s Choice INSTANTA

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1 (Standard Unit) MRXBOXAB-ECO-LP1-OH (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The LP1

More information

Bosch Group. 24CDi OF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

Bosch Group. 24CDi OF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS Bosch Group 24CDi OF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS GC NUMBER 47 311 32 (N.G) GC NUMBER 47 311 33 (L.P.G.)

More information

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5 4 ±0.5 12.0 Servicing 12.2 Annual Servicing Inspection (Cont) Flame Sensing 5 ±1 10 ±1 Position Fig. 45 Spark Ignition 5. Remove the clip securing the gas feed pipe to the air/gas venturi. Disconnect the

More information

PACK CONTENTS WARNING. This water heater must only be installed by qualified persons.

PACK CONTENTS WARNING. This water heater must only be installed by qualified persons. PACK CONTENTS Heater, wall mounting, fixing bracket, fittings, breather pipe assembly & Installation and User Instructions. This water heater must only be installed by qualified persons. Please read and

More information

ZIP AquaFlo II. Models: Direct, Indirect and Solar Compatible. Unvented cylinder water heaters

ZIP AquaFlo II. Models: Direct, Indirect and Solar Compatible. Unvented cylinder water heaters Installation & User Instructions ZIP AquaFlo II Unvented cylinder water heaters Models: Direct, Indirect and Solar Compatible. AquaFlo Installation, Maintenance and User Instructions Page 1 of 28 v 2.04

More information

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning Sentinel Kinetic MVHR and Kinetic Plus MVHR Installation & Commissioning Stock Ref. N 438222 Kinetic B 443319 Kinetic BH 438342 Kinetic V 438342A Kinetic VS 443028 Kinetic Plus B 447938 Kinetic Plus BS

More information

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning Sentinel Kinetic MVHR and Kinetic Plus MVHR Installation & Commissioning Stock Ref. N 438222 Kinetic B 438222A Kinetic BS 443319 Kinetic BH 443319A Kinetic S BH 438342 Kinetic V 438342A Kinetic VS 443028

More information

Installation, Operation and Maintenance Instructions Document Ref:

Installation, Operation and Maintenance Instructions Document Ref: Leopard Fan Coil Units Installation, Operation and Maintenance Instructions Document Ref: Dunham-Bush Ltd, Downley Road, Havant, Hants PO9 2JD 023 9247 7700 info@dunham-bush.co.uk 129-000-001-A UK:www.dunham-bush.co.uk

More information

"Microbox" DC Models MBOX 125/2DC MBOX 125/2DC204

Microbox DC Models MBOX 125/2DC MBOX 125/2DC204 "Microbox" DC Models MBOX 125/2DC MBOX 125/2DC204 Continuous Mechanical Extract Ventilation Unit with Low Energy DC Motor - for domestic and commercial use Installation, Operating and Maintenance Instructions

More information

POWER SHOWERS Models 4500M 5002M 4500T 5002T

POWER SHOWERS Models 4500M 5002M 4500T 5002T II POWER SHOWERS Models 4500M 5002M 4500T 5002T Performance Shower Products CUSTOMER SERVICE HELPLINE: 01883 730339 CONTENTS PLEASE READ THESE INSTRUCTIONS CAREFULLY: This booklet covers all models in

More information

Installation and Servicing Instructions. Alpha CD24C/32C

Installation and Servicing Instructions. Alpha CD24C/32C Installation and Servicing Instructions Alpha CD24C/32C Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers For Technical help or for Service call...

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1SW (Standard Unit) MRXBOXAB-ECO-LP1-OHSW (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The

More information

RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL

RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL HSPBRF HSTIRF HSVTRF RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL INDEX Section General information -----------------------------------------------------------

More information

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual POWERFLOW Series Unvented Electric Storage Water Heaters Installation & Operating Instructions Manual These Instructions must be left with the user after installation. Version 3.0 June 2009 Hyco POWERFLOW

More information

HW3 Handwash Installation and Operating Instructions

HW3 Handwash Installation and Operating Instructions HW3[16]instructions 10/12/15 14:05 Page 1 HW3 Handwash Installation and Operating Instructions IMPORTANT SAFEGUARDS SPECIFICATION: HW3 RATING: 230-240V, 3000W, ~50Hz; DIMENSIONS: 170w x 190h x 80d mm;

More information

Drying Cabinet Installation and Operating Manual

Drying Cabinet Installation and Operating Manual Drying Cabinet Models:- ETS-1900H ETS-1900TR CONTENTS ABOUT THE USER MANUAL Page 2 IDENTIFICATION DATA PLATE Page 2 IMPORTANT SAFETY INSTRUCTIONS Page 3 INSTALLATION INSTRUCTIONS Page 4 OPERATING INSTRUCTIONS

More information

Quartz. Digital. Bath with bath waste filler. Quartz Digital Bath with bath waste filler installation instuctions page 1

Quartz. Digital. Bath with bath waste filler. Quartz Digital Bath with bath waste filler installation instuctions page 1 Quartz Digital Bath with bath waste filler The Waste Electrical and Electronic Equipment (Producer Responsibility) Regulation 2004 This product is outside the scope of the European Waste Electrical and

More information

DSR SERIES DEHUMIDIFIERS ENGLISH GENERAL INFORMATION EXPLODED VIEWS DSR-20 DSR-12 PARTS LISTS ATTENTION!

DSR SERIES DEHUMIDIFIERS ENGLISH GENERAL INFORMATION EXPLODED VIEWS DSR-20 DSR-12 PARTS LISTS ATTENTION! DEHUMIDIFIERS GENERAL INFORMATION EXPLODED VIEWS PARTS LISTS DSR SERIES DSR-20 DSR-12 ENGLISH ATTENTION! There is a time delay on all units fitted with DFC 1 Controller. When starting or re starting the

More information

MEV SPIDER INSTALLATION GUIDE FOR ENGINEER / INSTALLER

MEV SPIDER INSTALLATION GUIDE FOR ENGINEER / INSTALLER MEV SPIDER INSTALLATION GUIDE FOR ENGINEER / INSTALLER Safety IMPORTANT Be sure to have read and understood these instructions before beginning the installation process. PRE-INSTALLATION CHECK LIST Make

More information

Installation & User Instructions:

Installation & User Instructions: Installation & User Instructions: Models: Amathus,Albany,Almyra,Brooklyn,Cestino,Casal,Caleta,Costanza,Casis,Fusion,Harlem, Iowa,Londa,Nebraska,Phantom,Ridgewood,Seraph,Saphir,Soul16,Scala,Tiago Once installed,

More information

Copperad. Copperad Fan Convectors (November 2005 onwards) Installation, Operation and Maintenance Instructions To be retained by the user

Copperad. Copperad Fan Convectors (November 2005 onwards) Installation, Operation and Maintenance Instructions To be retained by the user Copperad Fan Convectors (November 2005 onwards) Installation, Operation and Maintenance Instructions To be retained by the user Copperad QA/IOM/58 Issue 2 1 GENERAL 1.1 GENERAL DESCRIPTION This manual

More information

Installation and Maintenance

Installation and Maintenance 1.0 Introduction MRXBOX-ECO2 (Standard Unit) MRXBOX-ECO2-OH (Opposite hand Unit) MRXBOXAB-ECO2 (Standard Unit) MRXBOXAB-ECO2-OH (Opposite hand Unit) Mechanical Ventilation Units with Heat Recovery for

More information

This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit.

This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit. Installation & Service Instructions Performa System HE This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit. The boiler meets the requirements of Statutory Instrument

More information

HI-LINE LV FAN CONVECTOR MODEL: 7-4.

HI-LINE LV FAN CONVECTOR MODEL: 7-4. HI-LINE LV FAN CONVECTOR MODEL: 7-4. INSTALLATION, OPERATING, MAINTENANCE & AFTER SALES MANUAL Product Serial Number: Please leave this manual with the end user. Part Number: 1370058 heatingthroughinnovation.

More information

Installation, Operation and Maintenance Instructions Document Ref:

Installation, Operation and Maintenance Instructions Document Ref: Panther Fan Coil Units Installation, Operation and Maintenance Instructions Document Ref: Dunham-Bush Ltd, Downley Road, Havant, Hants PO9 2JD 023 9247 7700 info@dunham-bush.co.uk 126-000-001-C UK:www.dunham-bush.co.uk

More information

Zip Econoboil. On wall boiling water. Installation instructions & user manual. Model number: ,

Zip Econoboil. On wall boiling water. Installation instructions & user manual. Model number: , Zip Econoboil On wall boiling water. Model number: 305542, 303542 1 Table of contents Intended Use... 2 Warnings and precautions... 3 Before installation... 5 Technical specification... 6 Installation

More information

INSTALLATION AND SERVICING INSTRUCTIONS

INSTALLATION AND SERVICING INSTRUCTIONS C1 WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS 0 I This appliance is for use with Natural Gas. GC NUMBER 47 311 53 (N.G.)

More information

Installation, Operation & Maintenance Instructions Document Ref:

Installation, Operation & Maintenance Instructions Document Ref: Series AM Fan Convectors Installation, Operation & Maintenance Instructions Document Ref: Dunham-Bush Ltd, Downley Road, Havant, Hants PO9 2JD 023 9247 7700 info@dunham-bush.co.uk 121-000-001-A UK:www.dunham-bush.co.uk

More information

Bosch Group. 24i RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

Bosch Group. 24i RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS Bosch Group 24i RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS GC NUMBERS N.G. 47 311 37 L.P.G. 47 311 38 BOILER OUTPUT

More information

Installation & Operating Instructions

Installation & Operating Instructions Installation & Operating Instructions For 4 / 100mm Centrifugal s Models: K612 & K612T Thank you for purchasing a quality Centrifugal from GreenBrook. Please read these instructions fully prior to initial

More information

PLEASE READ ALL SECTIONS OF THIS GUIDE BEFORE COMMENCING YOUR INSTALLATION AND IN CONJUNCTION WITH YOUR DRAWINGS.

PLEASE READ ALL SECTIONS OF THIS GUIDE BEFORE COMMENCING YOUR INSTALLATION AND IN CONJUNCTION WITH YOUR DRAWINGS. Installation Guide This information is provided as a guide and may differ from project to project. It is assumed that the property is a two storey dwelling. Obviously a bungalow represents a simpler task,

More information

UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2. Version: 2018_07_19_v2.2

UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2. Version: 2018_07_19_v2.2 UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2 Version: 2018_07_19_v2.2 Abstract This is a quick reference guide for selecting the UniQ range of heat batteries for the required application. For designing a

More information

Unvented Direct & Indirect Hot Water Cylinders (400L L)

Unvented Direct & Indirect Hot Water Cylinders (400L L) Unvented Direct & Indirect Hot Water Cylinders (400L - 2500L) Important Please read & understand all these instructions before commencing installation. Please leave this manual with the customer for future

More information

Installation and Servicing Instructions. Alpha 240/280. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers

Installation and Servicing Instructions. Alpha 240/280. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers Installation and Servicing Instructions Alpha 240/280 Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers For Technical help or for Service call... ALPHA HELPLINE Tel: (0322)

More information

Installation & User Instructions: Model: Arizona/Broadway/Corsano/Compton/Compton1000/Corbiere/Empire /Newark/Newark1000/Qube/Tribeca

Installation & User Instructions: Model: Arizona/Broadway/Corsano/Compton/Compton1000/Corbiere/Empire /Newark/Newark1000/Qube/Tribeca Installation & User Instructions: Model: Arizona/Broadway/Corsano/Compton/Compton1000/Corbiere/Empire /Newark/Newark1000/Qube/Tribeca Once installed, the installer should take the appropriate steps To

More information