A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

Size: px
Start display at page:

Download "A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents"

Transcription

1 Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA Gas codes. A. Our boiler controller (flame safety and water level control) comply with UL and c-ul. Q. Burner control devices and control sequence shall comply with the requirements of Factory Mutual. A. Yes. Request on PO. Q. The turndown ratio for the burner shall be at least 4:1 A. No, our turn down ratio is usually 2:1 for EX and depends on model for LX. Refer to A-1 for details. Oil burner: Q. Oil burners shall be: - pressure atomizing forced draft type. A. yes Q. Oil burners shall be complete with -Built-in blower to supply combustion air, complete with motor, silencer and damper A. yes except the silencer(need details of what they need). Silencer is optional. Q. -with stainless steel flame retention diffuser A. Yes Q. - Oil pump complete with integral relief valve A. oil pump has internal recirculation or external return to the tank (depends on model) Q. -Oil filter A. yes, it comes as standard Q. - Pressure gauge A. yes, gauge is standard on the pressure side of the pump. Q. -High voltage ignition transformer A. yes only for EX(H)(W)-100. Other models have gas pilot as ignition means. Q. - Flame observation port A. yes, it comes as standard. Q. - Easy access to nozzles and electrodes A. yes, we can say that. Q. - Fuel and air modulating controls for maximum burner efficiency throughout operating range A. No, our burner is off-low-high step fire control. Q. -Oil atomizer utilizing air blower A. No, our oil atomizer uses the oil pressure itself to spray the oil, and mixes with air supplied by the blower. 1 / 5

2 Q. - electric oil heater to heat fuel oil from - 48 C to 0 C A. No, our burner is designed for #2 fuel oil, which does not need the heater for proper combustion. In cold region or season, the oil supplier usually provides #2 oil arranged for use in cold conditions. Gas burner Q.the burner shall be complete with gas train including -lubricated type manual shut off cock on the gas train A. No, our gas train has ball type manual shut off valve. Q. -automatic gas vent valve A. automatic gas vent is not standard for boilers 200BHP and below. 250 and 300BHP boilers have that, but it is not required by code we comply with. Q. -Main gas safety shutoff valves A. Yes, we have two safety shutoff valves (both UL listed as safety shutoff valve) Q. -high and low gas pressure switches A. Yes, our boiler has both high and low gas pressure switches as standard. Q. -Main manual gas shutoff and leakage test cocks A. Main manual gas shutoff valve is standard, and leakage test cocks are optional as CDS-1 option. Q. -gas pressure regulators A. Standard. Except for LX50-07 which has the gas regulating function integrated in the valve. Q. -Air safety switch A. Air pressure switch is standard Q. -Electronic annunciating combustion safety control with UV sensor. A. Our BL combustion safety control includes display and lamps for status and errors. Q. -Automatic gas valve A. main and pilot gas valves are automatic Q. -Adjustable cam gas metering valves. A. No, we can monitor gas flow using gas orifice differential pressure. Pilot burner Q. -gas pressure regulators A. Standard Q. -Pilot solenoid valve and shutoff cock A. Yes, the pilot gas train has 2 safety shutoff valves and manual shutoff cock. Q. -gas pilot assembly and ignition transformer A. Yes, but except EX(H)(W)100-O. for 100BHP oil burner, the burner is spark direct ignition. 2 / 5

3 Boiler Q. Boiler pressure vessel shall conform to ASME section. A. Our boiler pressure vessel has S stamp = ASME section or H stamp = ASME Section IV. Q. ASHRAE/IESNA 90.1 Compliance: Water-tube boilers shall have minimum efficiency according to Table A. Our boiler efficiency conform to such minimum efficiency requirement. Q. Design, documentation, fabrication and testing shall comply with ASTM, ANSI, CGA, ULC standards and TSSA requirements. A. CGA / CSA = boilers are no longer labeled with these approvals because they are equivalent to UL/c-UL, ULC = boilers will be either labeled UL and c-ul, and not ULC. Q. boiler water tubes shall be made of ASME SA-106-B. A. Now, main models uses SA-178-A, and some still uses SA- 106-B. Q. Boiler should include the following trim: -NEMA 250 type 1 control box A. Our boiler is a packaged boiler including the boiler control panel, and the entire boiler is UL listed. In this case, the NEMA control box is generally not required. Our control box is following the strict rules in the UL codes. Q. -Steam pressure gauge with 6 dial: A. We do have one pressure gauge but 4. And also pressure display on the controller. Q. -Pressure control operator.(modulating) A. Yes, we have BL(or XJ-1) pressure control as well as the backup pressure control switch from Honeywell as standard. However, it is not modulating as itself. Q. -Pressure high limit safety control. A. Yes, we have high limit safety switch as standard. Q. -Water gauge glass A. No, our boiler type is exempt from gauge glass requirement in the ASME code. Q. -Low-Water Cutoff Switch: Manual reset type. External column mounted float type. A. We have the low water cutoff as standard (code requirement) = manual reset, external column mounted, but electrode type (not float type) Q. -Auxiliary low water cutoff A. Yes, we have it as standard = auto reset. Q. -feed pump control A. Yes, we have it as standard included in the BL(or XJ-1). Q. -ASME safety valve(s) A. Yes, we have 1 or 2 (quantity depends on ASME requirement and design) safety valve(s) on the boiler pressure vessel as standard. Q. -Auxiliary contacts for start/stop and alarm indication A. we can supply some dry contacts for monitoring purpose Q. -Alarm Bell: Factory mounted on control panel with silence switch. 3 / 5

4 A. yes Q. -Provide electronic programming relay, feedwater pump and blower motor starter control switches, control circuit transformer and alarm bell. A. all included. Q. -selector switch to permit only low fire. A. not included for BL boilers. Low fire hold only in the test mode. Q. Jacket: Sheet metal, with screw-fastened closures and baked-enamel protective finish. A. Our boiler is installed with painted sheet metal casings. (not baked paint) Q. Mounting base to secure boiler to concrete base A. Yes Q. Two bottom blow valves (one slow and one quick opening, or two slow opening) A. standard boiler includes one quick or slow opening valve. One additional slow opening valve is optional. Economizer Q. Provide an economizer for each of the steam boilers. The economizers shall be gas to liquid heat exchangers, designed to utilize heat in the boiler flue gasses to preheat boiler feedwater. A. Yes. Q. Tube material shall be SA-178-A boiler tube A. economizer water tubes are all SA-106-B boiler tube. Tube size is 1 SCH40. Q. Provide economizer with safety valve. A. on boilers for US market, the economizer is made under ASME section 1 and it is part of the boiler. The safety valve on the main pressure vessel protects the economizer from excessive pressure. On some boilers for Canadian market, the economizer is made under ASME section 8, and considered as a separate pressure vessel. In this case, the economizer is equipped with a pressure relief valve. Q. Provide economizer with automatic soot blower A. Our boiler is intended for fuel gas and #2 oil and the deposit of soot is relatively small. That is why we do not need the soot blower. In case of economizer cleaning, we can open the box and clean the vessels easily for EX models. Q. Provide additional feed water controls as required to ensure proper economizer operation. A. Economizer feed water control is combined with the boiler water control (feed water to the boiler = feed water to the economizer). With BL control, we have one additional control to prevent the water to boil in the economizer. 4 / 5

5 Ancillary Q. Boiler shall use propane as a backup fuel. A. Propane backup fuel is optional only for some LX models. Q. Barometric Damper: Galvanized-steel assembly with flue-gas thermometer having a minimum 90 mm diameter dial. A. Barometric damper is not supplied by our factory. Consult chimney installer when required. Q. Silencer to reduce the noise to 80dB or below A. Air inlet silencer is optional. It can reduce the noise from 85dB to 80dB. Revision Record: Rev. Date Content of change Related docs Revised by 00 May 2009 New content T.F. 01 Apr Amendments to section Boiler K.S. 5 / 5

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired Form No. 8700 Bryan Flexible Water Tube TM Triple-Flex Series Ultra-High Efficiency Condensing Hot Water Boilers 3,000,000 BTUH Natural Gas Fired Minimum 90% Thermal Efficiency at 160 F Return with 20

More information

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC). SECTION 15555 HORIZONTAL FIRE TUBE BOILERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15510 - Piping (HVAC). 2. 15540 - Pumping Equipment (HVAC). 1.02 SUBMITTALS A. Submit properly identified

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

SECTION WATER-TUBE BOILERS

SECTION WATER-TUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections

More information

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project

More information

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures. Issued 2005/06/01 Section 15510 Packaged Boilers Page 1 of 13 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3 Section 01780 Closeout

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 235533 - FUEL-FIRED UNIT HEATERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas fired unit heaters. B. Oil fired unit heaters. C. Tubular infrared heaters. 1.2 RELATED REQUIREMENTS A. Section 230513

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004 Engineering Bulletin Gas Heat for M-Series and T-Series Climate Changer Air Handlers March 2004 CLCH-PRB010-EN Preface Gas heat can be a good heating option for any of the following applications: Climates

More information

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh HEATERS / BOILERS GWB8-E Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 065 July 06 Supersedes September 05 AFUE up to 83.9% Heating Input 50,000 to 99,000 Btuh MODEL NUMBER IDENTIFICATION

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Project Name: Location: Engineer: Contractor: I. GENERAL

Project Name: Location: Engineer: Contractor: I. GENERAL Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL I. PRODUCT Rep: Date: A. Supply and install modulating and condensing boiler(s) as specified

More information

150 BHP, 3 Pass High-Pressure Fire Tube Boiler mounted in a 53 Trailer

150 BHP, 3 Pass High-Pressure Fire Tube Boiler mounted in a 53 Trailer March 1, 2017 150 BHP, 3 Pass High-Pressure Fire Tube Boiler mounted in a 53 Trailer Customer Carey Boiler Works March 1, 2017 Page 2 of 5 Section 10 Boiler... 2 10.1... 2 10.2 Design... 2 10.3 Technical

More information

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E WATER HEATERS / BOILERS -E PRODUCT SPECIFICATIONS Gas-Fired Steam Boiler Bulletin No. 20653 September 202 Supersedes Bulletin No. 20263 AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh MODEL NUMBER

More information

Model CB-LE. Packaged Boiler HP. Operation, Service, and Parts Manual /09. and Model CB Ohio Special HP

Model CB-LE. Packaged Boiler HP. Operation, Service, and Parts Manual /09. and Model CB Ohio Special HP Model CB-LE Packaged Boiler 125-200 HP and Model CB Ohio Special 125-225 HP Operation, Service, and Parts Manual 750-184 04/09 ii CLEAVER-BROOKS Model CB-LE Packaged Boiler 125-200 HP Light Oil, Heavy

More information

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh WATER HEATERS / BOILERS COWB3 Oil-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 0654 March 08 Supersedes September 05 AFUE up to 85.% Heating Input 05,000 to 45,000 Btuh MODEL NUMBER IDENTIFICATION

More information

FUEL-FIRED VERTICAL TUBELESS BOILERS

FUEL-FIRED VERTICAL TUBELESS BOILERS FUEL-FIRED VERTICAL TUBELESS BOILERS 4 60 P orizontal and Vertical Feedwater / Condensate Return Systems and Blow-down Tanks FULTON FUEL-FIRED VERTICAL TUBELESS BOILERS FULTON: AN INDUSTRY LEADER SINCE

More information

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES P R O D U C T S P E C I F I C AT I O N S W A T E R H E A T E R S / B O I L E R S CONSERVATOR Gas-Fired Steam Boiler Bulletin No. 20263 October 200 Supersedes September 2008 AFUE up to 82.7% Heating Input

More information

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh HEATERS / BOILERS GWB8-E PRODUCT SPECIFICATIONS Gas-Fired Hot Water Boiler Bulletin No. 065 September 0 Supersedes Bulletin No. 06 AFUE up to 83.9% Heating Input 50,000 to 99,000 Btuh MODEL NUMBER IDENTIFICATION

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

Hubbell NX500 High Efficiency Gas Condensing Water Heater

Hubbell NX500 High Efficiency Gas Condensing Water Heater Hubbell NX500 High Efficiency Gas Condensing Water Heater Suggested Specification Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep:

More information

FLEXCORE SERIES MASTERSPEC

FLEXCORE SERIES MASTERSPEC FLEXCORE SERIES MASTERSPEC MSFC-2 SECTION 23 52 16 - CONDENSING HIGH EFFICIENCY STAINLESS STEEL FIRETUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

mith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON

mith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON Mills 00A mith Mills 00A Smith CAST IRON OIL, GAS OR COMBITION GAS/OIL COMMERCIAL BOILER/BURNER 00AR STEAM GAUGE OPERATING CONTROL MODULATING CONTROL HI LIMIT PRESSURE CONTROL 0" STEAM DRUM TEST COCK /"

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

Section B1. Flexible Watertube Boilers TABLE OF CONTENTS

Section B1. Flexible Watertube Boilers TABLE OF CONTENTS Section B1 Flexible Watertube Boilers TABLE OF CONTENTS FEATURES AND BENEFITS.................................................. B1-3 PRODUCT OFFERING......................................................

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

Steam Fundamentals. (in heating & processing applications)

Steam Fundamentals. (in heating & processing applications) Steam Fundamentals (in heating & processing applications) Introduction Common Heat Energy conveyers: Thermal Oil Hot water Steam Electrical Electric Heaters Electrodes (High Current) Steam Fundamentals

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

Lattner Boiler Company Model HRT Steam Boilers with Forced Draft Burners

Lattner Boiler Company Model HRT Steam Boilers with Forced Draft Burners Model HRT Steam Boilers with Forced Draft Burners INSTRUCTION MANUAL 2006 to 2007 T: (800) 345-1527 F: (319) 366-0770 E: info@lattner.com www.lattnerboiler.com Index Page 1 Index Section I: General Description

More information

Lattner Boiler Company Scotch Marine Steam & Hot Water Boilers

Lattner Boiler Company Scotch Marine Steam & Hot Water Boilers Lattner Boiler Company Scotch Marine Steam & Hot Water Boilers INSTRUCTION MANUAL December 2005 Lattner Boiler Company 1411 9 th St. SW Cedar Rapids, IA 52404 T: (800) 345-1527 F: (319) 366-0770 E: info@lattner.com

More information

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION FIRE TUBE BOILERS (STEAM)

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION FIRE TUBE BOILERS (STEAM) ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

RBI MASTERSPEC. A. This Section includes gas-fired, non-condensing finned copper water tube water heaters for heating hot water.

RBI MASTERSPEC. A. This Section includes gas-fired, non-condensing finned copper water tube water heaters for heating hot water. MSWFTIII-7 SECTION 22 34 36.29 - SAMPLE SPECIFICATION FOR RBI FUTERA III MODULATING WATER HEATER PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

AFUE 95% Heating Input 50,000 to 200,000 Btuh

AFUE 95% Heating Input 50,000 to 200,000 Btuh PRODUCT SPECIFICATIONS WATER HEATERS / BOILERS GWM-IE Gas-Fired, Modulating, Condensing, Wall Hung Hot Water Boiler Bulletin No. 210650 March 2018 Supersedes December 2015 AFUE 95% Heating Input 50,000

More information

Fuel-Fired Vertical Tubeless Boilers

Fuel-Fired Vertical Tubeless Boilers Fuel-Fired Vertical Tubeless Boilers Fulton Classic (4-60P), The EDGE (6-30P) orizontal and Vertical Feedwater / Condensate Return Systems and Blow-down Separators FULTON FUEL-FIRED VERTICAL TUBELESS BOILERS

More information

LGB COMMERCIAL GAS BOILER. Versatile combustion control systems. Made with Weil-McLain quality COMMERCIAL GAS BOILER APPLICATIONS INCLUDE:

LGB COMMERCIAL GAS BOILER. Versatile combustion control systems. Made with Weil-McLain quality COMMERCIAL GAS BOILER APPLICATIONS INCLUDE: www.weil-mclain.com COMMERCIAL GAS OILER Series Gas Water or Steam MH: 400-,860 Efficiency 85.% Net Load Range: Hot Water 80-, MH / Steam 975-7,40 Sq. Ft. COMMERCIAL GAS OILER APPLICATIONS INCLUDE: Apartment

More information

SERIES 19A. mith PRESSURIZED WET BASE

SERIES 19A. mith PRESSURIZED WET BASE SERIES 19A mith series19a BOILER/BURNER PRESSURIZED WET BASE UNIT series 19A STANDARD EQUIPMENT All s Cast iron wet-base sections tested for 80psi. Insulated metal jacket Cast iron smokehood with integral

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10 Model C Forced Draft Burners Natural Gas or Propane MODEL C10 MODEL C4 GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7 Telephone: (519) 620-0230 Telefax: (519) 620-0232

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GBI 201-5 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

mith Mills Smith Mills 6500A 6500A-4 OIL OR GAS CAST IRON BOILER/BURNER CAST IRON

mith Mills Smith Mills 6500A 6500A-4 OIL OR GAS CAST IRON BOILER/BURNER CAST IRON mith Mills Mills 00A OIL OR GAS CAST IRON BOILER/BURNER Smith CAST IRON 00A- - Gas I=B=R Ratings: Gross Output 7,19 to 1, FRONT VIEW WITH INDUS COMB BURNER SIDE VIEW WITH INDUS COMB BURNER SIDE VIEW -

More information

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: A. Supply and install modulating and condensing boiler(s) as specified herein. Date:

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL SECTION 22 14 00 DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 00 10,

More information

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: Date: A. Supply and install modulating and condensing boiler(s)/water heater(s)

More information

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: Date: A. Supply and install modulating and condensing boiler(s)/water heater(s)

More information

UTICA BOILER. SSV Submittal. Project Name: Project Location: Contractor:

UTICA BOILER. SSV Submittal. Project Name: Project Location: Contractor: UTICA BOILER SSV - 399 Submittal Engineer: Project Name: Project Location: Contractor: APPLICATION: Gas fired hot water heating boiler for indoor installations. Approved for closet or alcove installations.

More information

C1210ES Tankless Water Heater

C1210ES Tankless Water Heater Engineering Submittal Sheet Dimensions and Connections B C D C Combustion air inlet Exhaust outlet Optional combustion air inlet Top view Top view A E Hot water outlet Cold water inlet F H J C I K G Front

More information

SECTION HEATING BOILER FEEDWATER EQUIPMENT

SECTION HEATING BOILER FEEDWATER EQUIPMENT SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American

More information

C1050ES Tankless Water Heater

C1050ES Tankless Water Heater Engineering Submittal Sheet Dimensions and Connections B C D C Combustion air inlet Exhaust outlet Optional combustion air inlet Top view Top view A E F Hot water outlet Cold water inlet Inlet water filter

More information

CSD-1 COMMERCIAL BOILER CONTROLS

CSD-1 COMMERCIAL BOILER CONTROLS SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS CSD- COMMERCIAL BOILER CONTROLS P/N 400043, Rev. A [/03] CSD- COMMERCIAL BOILER CONTROLS! WARNING Fire, explosion, asphyxiation and electrical shock

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

Suggested Specifications Prestige Excellence 110

Suggested Specifications Prestige Excellence 110 Suggested Specifications Prestige Excellence 110 General Requirements A. Furnish and install (qty) completely assembled, modulating, sealed combustion, high efficiency, combination gas-fired boiler(s)

More information

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT CEMLINE Unfired Steam Generators are designed to produce clean steam with steam or high temperature hot water as an energy source for use where there is a need to produce clean steam from boiler steam

More information

SECTION FUEL-FIRED DOMESTIC WATER HEATERS

SECTION FUEL-FIRED DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

User s Information Manual

User s Information Manual User s Information Manual Galaxy GG, GXH & GXHA Series, Sentry Series and Sentinel SE Series Gas Boilers with Intermittent Pilot Ignition Device System (IID) FOR YOUR SAFETY: Before operating this boiler,

More information

Burner Comparisons. Typical Competitor s Burner

Burner Comparisons. Typical Competitor s Burner Burner Comparisons INOV8 s Typical Competitor s Burner Automatic nozzle cleanout Yes No Available BTUs rated as input 100,000 to 1,000,000 76,500 to 500,000 Burner Motor - hp 1/5 1/7 Combustion safety

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS HI DELTA, TYPE WH - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 3500.932A Effective: 04-01-17 Replaces: 10-31-16 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY A.

More information

INVITATION FOR BID. May 17, Purchase Natural Gas Hot Water Boiler MAWSS Purchasing Department

INVITATION FOR BID. May 17, Purchase Natural Gas Hot Water Boiler MAWSS Purchasing Department mawss Buyer II Lisa Russell (251) 694-3162 Office Irussell@mawss.com TO INVITATION FOR BID NUMBER SEPARATE SEALED BIDS FOR BIDS WILL BE RECEIVED AT Prospective Bidders IFB 18-023 INVITATION FOR BID May

More information

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT SECTION 23 09 33 SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT HARSCO INDUSTRIAL, PATTERSON-KELLEY NURO CONTROL CONVERSION KIT Part 1 - GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 / CSA 4.9

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

Type CG Series Forced Draft Gas Burner

Type CG Series Forced Draft Gas Burner Type CG Series Forced Draft Gas Burner Designed and built by Canadians for Canadian Winters By PENDELL BURNERS Office & Plant Address: 155 Regina Road, Unit #3 Woodbridge, Ontario L4L 8L9 Telephone: (416)

More information

Date: Project #: Engineer: Prepared By: Bid Date:

Date: Project #: Engineer: Prepared By: Bid Date: Brute NEOTHERM Date: Project #: Hydronic Boiler Hydronic Boiler Indoor Sizes 285-850 Submittal Data Engineer: Project Name: Prepared By: Location: Bid Date: Contractor: Standard Equipment Electronic PID

More information

Williams & Davis Boilers

Williams & Davis Boilers Williams & Davis Boilers Established 1921 3-Pass Water-Back Scotch Marine Boiler SIZES 15HP THROUGH 1500HP GAS, OIL OR COMBINATION BURNER FIRETUBE HOT WATER & PRESSURE STEAM BOILERS 3000W Standard Features

More information

Bosch Greentherm T9800 SE 199 Gas Tankless Water Heater

Bosch Greentherm T9800 SE 199 Gas Tankless Water Heater Engineering Submittal Sheet Product Overview & Certifications Engineering Specifications The system shall consist of gas tankless water heater model Greentherm T9800 SE 199 as manufactured by Bosch Thermotechnology.

More information

SAMPLE SPECIFICATIONS

SAMPLE SPECIFICATIONS Page 1 of 6 3-03 SAMPLE SPECIFICATIONS The following sample specifications are provided by Superior Boiler Works to assist you in providing your customer with the specific needs for that application. The

More information

EGH Series 5. Control Supplement. EGH-105 to EGH-125 Natural gas CSD-1 control system

EGH Series 5. Control Supplement. EGH-105 to EGH-125 Natural gas CSD-1 control system EGH Series 5 Gas-Fired Boilers Control Supplement EGH-105 to EGH-125 Natural gas CSD-1 control system For propane boilers, install EGH liquefied petreoleum (propane) gas conversion kit in addition to following

More information

KN2/4 SERIES MASTER SPECIFICATION

KN2/4 SERIES MASTER SPECIFICATION KN2/4SP4-2 SECTION 23 52 23 SAMPLE SPECIFICATION FOR HYDROTHERM KN-2 and KN-4 SERIES BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

LOW NOx, HIGH EFFICIENCY, HOT WATER SUPPLY AND HYDRONIC HEATING BOILERS

LOW NOx, HIGH EFFICIENCY, HOT WATER SUPPLY AND HYDRONIC HEATING BOILERS FTIIC-6 LOW NOx, HIGH EFFICIENCY, HOT WATER SUPPLY AND HYDRONIC HEATING BOILERS Futera II Series boilers and water heaters are also available with corrosion-resistant, brushed stainless steel jacket. Ideal

More information

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower VCLEARFIRE High-Efficiency, Commercial Steam Boiler 9.5-60 Horsepower High-Efficiency, Low-Emissions Steam Boiler in a Compact Footprint The Cleaver-Brooks compact, gas-fired ClearFire -V vertical boiler

More information

GAS/LOW NOx SERIES. High or Low Pressure Steam Boiler. The most versatile industrial steam boiler in the world

GAS/LOW NOx SERIES. High or Low Pressure Steam Boiler. The most versatile industrial steam boiler in the world MIURA WX GAS/LOW NOx SERIES High or Low Pressure Steam Boiler NEW XJ1 Micro Computer Boiler Control System The most versatile industrial steam boiler in the world The intelligent boiler that works with

More information

KN-SERIES MASTER SPECIFICATION

KN-SERIES MASTER SPECIFICATION KNSP4-8R KN-6, KN-10, KN-16, KN-20, KN-26, KN-30 SECTION 23 52 16 CONDENSING HIGH EFFICIENCY CAST IRON KN-SERIES BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

Rental Boiler Specifications (Nebraska Boiler)

Rental Boiler Specifications (Nebraska Boiler) Rental Boiler Specifications (Nebraska Boiler) ESI's 72,000 pph trailer-mounted watertube steam boilers are designed and built in accordance with ASME Code. Each boiler is arranged for natural gas or #2

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated HAC INSTALLATION AND OPERATION MANUAL THE POWER TO MANAGE ENERGY 2001 South 21 st Street, Parsons, Kansas 67357 Telephone 620-421-0480, Fax 620-421-0948 Web Site: www.powerflame.com

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

Bryan Water-Pak Indirect Systems 360,000 BTU to 4,500,000 BTU Inputs 199 to 3,533 Gallons Storage Capacity

Bryan Water-Pak Indirect Systems 360,000 BTU to 4,500,000 BTU Inputs 199 to 3,533 Gallons Storage Capacity Form No. 2300-7 (Rev. 2/99) Gas, il or Dual Fuel Fired Bryan Water-Pak Indirect Systems 360,000 BTU to 4,500,000 BTU Inputs 199 to 3,533 Gallons Storage Capacity Originators of the Flexible Water Tube

More information

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS XPAK FT TYPE H - MODELS 088AR-398A SUGGESTED SPECIFICATIONS Catalog No.: 2100.91 Effective: 05/01/15 Replaces: new DIVISION 23 52 33.13 WALL-HUNG STAINLESS STEEL HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

RBI MASTERSPEC. A. This Section includes gas-fired, non-condensing finned copper water tube boilers for heating hot water.

RBI MASTERSPEC. A. This Section includes gas-fired, non-condensing finned copper water tube boilers for heating hot water. MSFTIII-9 SECTION 23 52 33.19 - SAMPLE SPECIFICATION FOR RBI FUTERA III MODULATING BOILER PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

**************************************************************************

************************************************************************** USACE / NAVFAC / AFCEC / NASA UFGS-23 52 43.00 20 (May 2015) Change 1-08/15 ------------------------------- Preparing Activity: NAVFAC Superseding UFGS-23 52 43.00 20 (July 2006) UNIFIED FACILITIES GUIDE

More information

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750-293 www.cleaverbrooks.com Improper installation, adjustment, service, or maintenance can cause equipment damage, personal injury, or death.

More information

User s Information Manual Models: 45, ,000 Btu/hr

User s Information Manual Models: 45, ,000 Btu/hr SBR-USER_100161678_2000017137_Rev C User s Information Manual Models: 45,000-260,000 Btu/hr If the information in this manual is not followed exactly, a fire or explosion may result causing property damage,

More information

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N 238-44219-00 (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! You have just purchased one of the finest water heaters on

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SECTION INCLUDES A. Water heaters. B. Packaged water heating systems. C. Domestic water heat exchangers. D. Water storage tanks. E. Water softeners. F. Reverse osmosis equipment. G.

More information

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler Gas boiler UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM. INSTALLER MUST REVIEW

More information

Figure 10 or Figure 6

Figure 10 or Figure 6 SUPPLEMENT TO INSTRUCTION MANUAL P/N 238-45637-00 and 238-48933-00 (Replaces pg. 32 (238-45637-00) or pg. 28 (238-48933-00) in Wiring Diagram Honeywell A B C VERY HO HO LOW Figure 10 or Figure 6 238-48214-00B

More information

BURNHAM COMMERCIAL 27 February 2008 MPC Multiple Pass Commercial Boiler Suggested Specifications

BURNHAM COMMERCIAL 27 February 2008 MPC Multiple Pass Commercial Boiler Suggested Specifications 2.1 GENERAL A. Reference is made to the clause entitled Buy American Act Balance of Payments Program Construction Materials FAR 52.225-9. Notwithstanding a bidder s right to offer identifiable foreign

More information

DIVISION FIRE-TUBE STAINLESS STEEL HEATING BOILERS

DIVISION FIRE-TUBE STAINLESS STEEL HEATING BOILERS XVERS TYPE H - MODELS 0856-3006 SUGGESTED SPECIFICATIONS Catalog No.: 2000.84A Effective: 06/22/18 Replaces: 3/15/18 DIVISION 23 52 33.13 FIRE-TUBE STAINLESS STEEL HEATING BOILERS - GENERAL 1.1 SUMMARY

More information

MODEL CEW OHIO SPECIAL

MODEL CEW OHIO SPECIAL MODEL CEW OHIO SPECIAL 100-225 HP Steam Wet-back Packaged Burner CONTENTS FEATURES AND BENEFITS...A9-3 Less than 360 Square Feet of Heating Surface:...A9-3 Front and Rear Doors:...A9-3 Natural Gas, No.

More information

FSB Series II Gas-Fired Hot Water Induced Draft Boilers

FSB Series II Gas-Fired Hot Water Induced Draft Boilers FSB Series II Gas-Fired Hot Water Induced Draft Boilers Models FSB- FSB-3 FSB-4 FSB-5 FSB-6 FSB-7 REPAIR PARTS AND OPTIONAL KITS Ordering Instructions Order Parts through your nearest supplier. When ordering

More information

Solution builder. in energy management.

Solution builder. in energy management. Solution builder in energy management Catalog of products 1 COMPANY PROFILE 2 HTHW (High Temperature Hot Water) GENERATOR 3 AQT - WATERTUBE STEAM BOILER 4 AQT - WATERTUBE HOT WATER HEATER 5 AQT HEATER

More information

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation Industrial Space Heating Direct Gas-Fired Heating Greenheat 00% Outdoor Air Greenheat 50/50 Recirculation 80/0 Recirculation March 008 Product Overview Industrial Space Heating Greenheck s space heating

More information

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com Tray ST5 Pressurized and Atmospheric Deaerators Tray Type Deaerator Pressurized.005 cc/liter COUNTER FLOW TRAY design provides guaranteed removal of all dissolved oxygen in excess of.005 cc/liter from

More information

Utica Boilers MAC Submittal

Utica Boilers MAC Submittal Utica Boilers MAC-150 - Submittal Engineer: Project Name: Project Location: Contractor: APPLICATION: Modulating Gas fired Combi boiler for indoor installation. Approved for closet or alcove installations.

More information

Distributed By: M&M Control Service, Inc Building Technologies

Distributed By: M&M Control Service, Inc Building Technologies Building Technologies Combustion Control Systems Count on Siemens. Siemens Building Technologies, the worldwide industry leader in combustion controls, delivers globally approved products specifically

More information