1 MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996

2 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way without the express written consent of McQuay International. NOTICE Copyright 1994, 1996 McQuay International, Minneapolis MN All rights reserved throughout the world. McQuay International reserves the right to change any information contained herein without prior notice. No guarantees are given as to the accuracy of information provided. ii

3 Contents Revision History 5 Version Overview 7 Introduction to Series-100 Centrifugal Chillers...7 Centrifugal Products included in this Open Protocol Document...8 Series-100 Centrifugal Chiller Input/Output Configuration 9 Analog Inputs...9 Digital Inputs...10 Digital Outputs...10 Control Modes for the Series-100 Centrifugal Chiller 11 Sequence of Operation...11 Description of Modes...13 Start Requested...13 Waiting, Low Oil Sump Temperature...13 Evaporator Pump On...13 Waiting for Load...13 Oil Pump On...13 Condenser Pump On...13 Startup Unloading...14 Motor Control Relay Started...14 Running OK...14 Off: Load Recycle...14 Off: Time Clock...14 Off: Remote Signal...14 Off: Manual Switch...14 Off: Network Signal...14 Begin Routine Shutdown...15 Motor Control Relay Off, Post Lube...15 Begin Rapid Shutdown...15 Off: Fault...15 Hardware 17 MicroTech Controller Hardware Interfacing...17 Communications to a Single Chiller...17 Communications to two Chillers with a LLLB Panel...18 Communications to two or more Chillers...19 Correct Addresses for MicroTech Series-100 Centrifugal Chillers (Control Processor)...19 MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Contents 3 of 62

4 Variables 20 Read Only - Control Processor...20 Read and Write Memory Locations - Control Processor...33 Keypad/Display Controller Addresses...36 Read Only Memory Locations (Display processor)...37 LLLB (Lead Lag Load Balance) Controller 41 Description...41 Read Only Memory Locations for the LLLB Panel...41 Read and Write Memory Locations for the LLLB Panel...42 Series-100 Centrifugal Chiller Simulation Package 45 Required Development Testing Tools...45 Set-up of Hardware for Testing...45 Procedure for setting up the network arrangement...46 Open Protocol Monitor Program 48 Sample Screens...48 Glossary of Terms 59 Index 60 MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Contents 4 of 62

5 Revision History Version 3.2 Version 3.1 Version 3.0 This is a general upgrade and format change of the document. References to "SnyderGeneral Corporation" changed to "McQuay International." Corrections and amplifications (flagged with vertical revision marks; newly added text is underlined). Added Time, Year to the display processor. This was a missing location.. Added Motor Current, Amps to the control processor. This is a new memory location. Added the Watchdog Output to the control processor. This was mislabeled as another output. Added to the Current Fault memory location, fault codes 16 through 29 which were missing. Fault codes 16 to 29 are the codes used when one of the microprocessor sensors have failed. Corrected explanation of the Network Start/Stop memory location. Previous document indicated a value of 1 to 255 would stop the chiller, this has been corrected to read only the value of 255 will stop the chiller. This was a documentation error. Added Entering Evaporator Water Temp - Hi Resolution to the control processor. Added Leaving Evaporator Water Temp - Hi Resolution to the control processor. Added Evaporator Refrigerant Temp. - Hi Resolution to the control processor. Added Compressor Suction Temp - Hi Resolution to the control processor. Added Liquid Line Temp. - Hi Resolution to the control processor. Added Entering Condenser Water Temp. - Hi Resolution to the control processor. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Revision History 5 of 62

6 Added Leaving Condenser Water Temp. Hi Resolution to the control processor. Added Maximum Chilled Water Reset Setpoint to the control processor and added clarifying notes about how chilled water reset works. Added Reset Option memory location to the control processor. Added clarifying notes to the variables Manual Amp Limit and Maximum Amp Limit of the control processor. Added Manual Amp Limit Setpoint to the control processor. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Revision History 6 of 62

7 Overview Introduction to Series-100 Centrifugal Chillers Refrigerants Starting and Stopping the Chiller We manufacture two (2) types of centrifugal chillers - single compressor and dual compressor type units. The single compressor units have one MicroTech control panel. Dual compressor unit always have two MicroTech control panels (one for each compressor) and a factory mounted Lead Lag and Load Balancing Panel (LLLB) for sequencing control and load balancing logic between the two compressors. Both types of chillers can use either R12, R500 or R134a refrigerant. The control panel is factory programmed for the type of refrigerant used. In addition, we provide access to information contained in the MicroTech control panel via a unit mounted keypad/display. The keypad/display is factory programmed to display units in either English Units (i.e. F and Psi) or Metric (i.e. C and KPa). The purpose of the chiller is to produce chilled water. If there is chilled water flow, the controller will monitor the leaving chilled water temperature, compare it to the chilled water setpoint, and then start the compressor(s) and control the inlet vanes on the compressor to maintain setpoint. The chilled water setpoint can be reset from either the entering chilled water temperature, a remote 4-20 ma signal, or via Open Protocol communications. The front panel has a "Start/Stop" rocker switch. If the switch is in the "Stop" position, the chiller will not run. This switch must be in the "Auto" position in order for the chiller to start and run. If the chiller is running and the switch is changed to "Stop", the compressor motor will be turned off immediately. In the meantime, the micro-processor will perform an orderly shutdown by keeping the oil pump on and closing the vanes. The chiller can be turned on or enabled for operation several ways. First, the front panel rocker switch must be in "Auto". The "START MODE" setpoint ( 5th key press of Setup-Options Key) can be set to either "Local" or "Remote". If the keypad/display is in "Local", the chiller will be started and stopped via its internal programmed time schedule. If the keypad/display is in "Remote", the chiller will ignore its internal time schedule and will start and stop in response to the remote start/stop digital input (a contact closure to field terminals 9 & 64). MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Overview 7 of 62

8 Centrifugal Products included in this Open Protocol Document "*" designates a wild card, any character in this location is acceptable McQuay International manufactures MicroTech Series-100 centrifugal chillers for a wide variety of applications from ice chiller systems, to heat recovery, to templifiers (heat pumps), etc. This Open Protocol document specifically addresses standard Series-100 centrifugal chiller applications only. Before applying Open Protocol, confirm that the application has the following software identification (ID), otherwise incompatibilities may result. (Software ID's are imprinted on a label inside the control box or may be obtained by contacting the McQuay International representative). Controller Products Series Software ID Series-100 Centrifugal Chiller Control Processor 100 PC*08* Series-100 Centrifugal Chiller Display Processor 100 PDR08* Lead Lag Load Balance (LLLB) Panel 100 DUA09* In addition, software IDs are stored within the controllers. Software ID's Memory locations are as follows: Series 100 Series 200 $800A-F $0A08-F Note: Above ID's result when the resultant memory location is translated into ASCII, for example, Series-100 Centrifugal Chiller Control Processor code would have $50, $43, *, $30, $35, *. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Overview 8 of 62

9 Series-100 Centrifugal Chiller Input/Output Configuration Analog Inputs Reset Types Input Number Description 0 Leaving Evaporator Water Temperature 1 Entering Evaporator Water Temperature 2 Evaporator Refrigerant Temperature 3 Suction Line Temperature 4 Liquid Line Temperature 5 Entering Condenser Water Temp. 6 Leaving Condenser Water Temp. 7 Discharge Line Temperature 8 Condenser Refrigerant Temperature 9 Oil Feed Temperature 10 Oil Sump Temperature 11 Remote Reset Signal 12 Motor Current 13 Oil Pressure The remote reset signal (Analog #11) can be used to reset either of the following but not both: Chilled H2O Reset Amp Limiting MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2Series-100 Centrifugal Chiller Input/Output Configuration 9 of 62

10 Digital Inputs Digital Outputs Input Number Description 0 Surge Guard 1 Motor Temperature 2 Oil Differential 3 Discharge Pressure Switch 4 Low Refrigerant Pressure Switch 5 Stop/Auto Switch 6 Starter Fault 7 Condenser Water Flow Switch 8 Evaporator Water Flow Switch 9 Starter Transition 10 Remote Start/Stop 11 Vanes Closed Output Number Description 0 Unload Solenoid 1 Load Solenoid 2 Hot Gas Solenoid 3 Motor Control Latch Relay 4 Watchdog 5 Oil Heater 6 Liquid Injection Solenoid 7 Remote Alarm 8 Cooling Tower Stage 1 9 Cooling Tower Stage 2 10 not used 11 Evaporator Pump 12 Condenser Pump 13 Oil Pump 14 MCR Relay 15 LED Front Panel MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2Series-100 Centrifugal Chiller Input/Output Configuration 10 of 62

11 Control Modes for the Series-100 Centrifugal Chiller Sequence of Operation A typical sequence of operation is summarized in the following flow chart from System Startup to Shutdown. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Control Modes for the Series-100 Centrifugal Chiller 11 of 62

12 Off, Load Recycle Time Clock Remote Switch Manual Switch Network Signal Off, Ready to Start Start Requested Waiting, Low Oil Sump Temperature Evaporator Pump On Waiting for Load Oil Pump On Condenser Pump On Startup Unloading MCR On Running Ok Shutdown, Routine or Rapid Waiting, High Current Post Lubrication MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Control Modes for the Series-100 Centrifugal Chiller 12 of 62

13 Description of Modes Start Requested The unit must be in the Off:Ready mode to Start. If the unit is in local, the chiller can get a start request by 1.) Pressing the "Start" key on the keypad/display or 2.) Setting the internal time clock schedule to start the chiller. If the unit is in Remote, the chiller can get a start request from the remote start/stop digital input. In either of the above modes, the chiller can be commanded to stop via communications and the Network Start/Stop memory location. This memory location is the one to use to start and stop the machine via Open Protocol communications. We recommend putting the chiller in remote and installing a jumper across the Remote start/stop field terminals. The chiller will then start and run as long as the Network Start/Stop memory location does not command the chiller to stop. If the chiller has been running and the load is satisfied, the controller will turn off the compressor and go into Off: Load Recycle mode. When the anti-cycle timers are satisfied and the leaving water temp is above the setpoint plus the start-up delta temp, a start will be initiated. Waiting, Low Oil Sump Temperature If a start has been requested, the controller will check the anti-recycle timers to see if is OK to start. If the timers are satisfied, the controller will switch to Waiting, Low Oil Sump Temperature; otherwise, the mode remains at Start Requested until the anti-recycle timers are satisfied. Evaporator Pump On If the oil sump temperature is 50 F above the evaporator (adj.), the controller will turn on the evaporator pump. Flow is confirmed via the digital water flow switch. Waiting for Load If there is chilled water flow, the controller will switch to Waiting for Load. The chilled water leaving temperature has to be several degrees (adj.) over the setpoint in order to start. Oil Pump On If there is a load, the oil pump will be turned on and the vanes will be closed continuously. Condenser Pump On The condenser pump is energized. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Control Modes for the Series-100 Centrifugal Chiller 13 of 62

14 Startup Unloading The controller will check for condenser pump flow. Motor Control Relay Started The controller will check to see that the vanes are closed. If they are, the Motor Control Relay and Motor Control Latching Relay are turned on. Running OK If after 30 seconds there are no faults, the controller will switch to Running OK. There are two types of stop signals - Rapid Shutdown due to a fault and Routine Shutdown. Most of the time the chiller will stop because there is a Routine Shutdown. These are the Routine Shutdowns: Off: Load Recycle Off: Time Clock Off: Remote Signal Off: Manual Switch Off: Network Signal Off: Load Recycle If the leaving chilled water temperature decreases to below the setpoint minus the shut down Delta temp., the chiller will be turned off. In other words, the chiller satisfied the load. Off: Time Clock If the chiller is in Local and the internal time schedule is unoccupied, the chiller will be turned off. Off: Remote Signal If the chiller is in Remote and the Remote Start/Stop switch is opened, the chiller will be turned off. Off: Manual Switch If the rocker switch on the front panel is places in the Stop position, the chiller will be turned off. Off: Network Signal The chiller has been commanded off via network communications from another control panel or system. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Control Modes for the Series-100 Centrifugal Chiller 14 of 62

15 Begin Routine Shutdown If any of the above shutdowns occur, the controller will switch to Begin Routine Shutdown. During this mode, the vanes will be closed, and about one minute later, the Motor Current Relay and condenser pump will be turned off. Motor Control Relay Off, Post Lube At the beginning of this mode, the oil pump is on. 30 seconds later the oil pump is turned off. If the chiller is being shut off due to Load Recycle, the evaporator pump will stay on; otherwise, it will turned off. If the rocker switch is in the "Auto" position, the mode will switch to "Off: Ready to Start". If the rocker switch is in the "Manual" position, the mode will switch to "Off: Manual Switch". Note: A chiller that was shut down due to "Off: Load Recycle" will go through the start up phase until it gets to "Waiting for Load". Begin Rapid Shutdown At other times the chiller is shut down due to a fault. When this happens, a rapid shutdown occurs. If the oil pump wasn't turned on, the unload and post lube shutdown stages will be skipped. This means that the evaporator, condenser, and oil pumps are turned off. In addition, the Motor Control Relay is turned off and the vanes are closed. If the oil pump was on, a more normal shutdown occurs. The vanes will be continuously closed and the Motor Control Relay will already be off. The condenser and evaporator pumps will be turned off and a Post Lube sequence will occur. Off: Fault The chiller will not be allowed to run if there is a fault. The following is a listing of primary faults but does not include sensor failure faults. See Current Fault or Unit Status memory locations for a full listing. Failure of Starter Transition Switch Low Oil Sump Temperature High Oil Feed to Bearings Temperature Low Evaporator Pressure High Compressor Discharge Pressure Switch High Compressor Discharge Line Temperature SurgeGuard Protection Switch High Compressor Suction Temperature High Motor Winding Temperature Switch Starter Fault Switch Low Charge Switch Loss of Evaporator Proof of Flow Switch Loss of Condenser Proof of Flow Switch MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Control Modes for the Series-100 Centrifugal Chiller 15 of 62

16 Low Oil Differential Pressure Switch Low Motor Current Bad Evap Leaving Water Temperature Sensor Vanes Open During Startup MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Control Modes for the Series-100 Centrifugal Chiller 16 of 62

17 Hardware MicroTech Controller Hardware Interfacing The method of Open Protocol interfacing to MicroTech chillers primarily depends upon the number of chiller involved in the integration. Three scenario's are defined below and address the majority of installations. Communications to a Single Chiller One port is configured for RS- 232C, 1200 baud All McQuay MicroTech Series-100 Centrifugal Chillers are shipped from the factory with one communications port factory configured for RS-232C, 1200 baud. The port is located on the Control Processor (Cartridge Style) and is designated port A. This communication port is normally used in conjunction with a optional factory installed modem (See McQuay Installation and Maintenance Bulletin #403, pg. 42 for location of this communications Port A). Since high communication baud rates are usually desirable, it is possible to change the Port A baud rate in the field using a personal computer and the Open Protocol Monitor software program. Thus, the communications interfacing is as follows on the next page. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Hardware 17 of 62

18 ADDRESS Communications to two Chillers with a LLLB Panel In this situation, two MicroTech chillers are connected to a Lead-Lag Load Balance (LLLB) panel. The LLLB panel is used in applications where there are two chillers which need to be Lead Lagged and Load Balanced. The connection point for this application is Port A on the LLLB Model 120 Controller and communications baud is factory configured to 9600 baud. Thus, the communications interfacing is as follows: MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Hardware 18 of 62

19 Communications to two or more Chillers In this situation, two or more MicroTech chillers are installed. If a single communications port is desired for obtaining information from all chillers, a MicroTech OPM panel is required to serve as the communications interface to all chillers. The connection point is Port A on the OPM panel and communications baud is factory configured to 9600 baud. Correct Addresses for MicroTech Series-100 Centrifugal Chillers (Control Processor) Read/Write Request Packet Control Addresses The proper values for Series-100 Centrifugal Chiller addressing is as follows, the address is used as part of the read or write request packet: "ll" "ss" Chiller No Chiller No Chiller No Chiller No Chiller No Chiller No etc. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Hardware 19 of 62

20 Variables Read Only - Control Processor Description Address Range Units Alarm Contact = deenergzd 1 = energized Approach, Condenser Calculated Leaving Evaporator Temperature Setpoint *X+20= F Calculated Network Amp Limit Setpoint Compressor Discharge Temp. Compressor Suction Temp. - Lo Resolution Compressor Suction Temp. - Hi Resolution % of full load amps F F 041C *X+20 = F Condenser Pump 021C 0 = deenergzd 1 = energized Condenser Refrigerant PSIG Pressure Condenser Refrigerant Temp F Condenser Water Flow Switch 050F BIT 6 0 = no flow 1 = flow Cooling Tower Stage = deenergzd 1 = energized Cooling Tower Stage = deenergzd 1 = energized Current Fault 0428 See Below Fault, Last 0834 See Below MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 20 of 62

21 Description Address Range Units Fault See Below Fault See Below Fault See Below Fault See Below Fault See Below Fault 7 083A See Below Fault 8 083B See Below Entering Condenser Water F Temp. - Lo Resolution Entering Condenser Water 041E *X+55 = F Temp. - Hi Resolution Entering Evaporator Water F Temp. - Lo Resolution Entering Evaporator Water 041A *X+20 = F Temp. - Hi Resolution Entering Water Reset = Inactive 1 = Active Evaporator Low Pressure Switch 050E BIT 3 0 = Low press 1 = OK Evaporator Pump 021B 0 = deenergzd 1 = energized Evaporator Refrigerant PSIG Pressure Evaporator Refrigerant F Temp. - Lo Resolution Evaporator Refrigerant 041B *X+20 = F Temp. - Hi Resolution Evaporator Water Flow Switch 050F BIT 5 0 = no flow 1 = flow High Discharge Pressure Switch 050E BIT 4 0 = high press 1 = OK Hot Gas Solenoid = deenergzd 1 = energized Leaving Condenser Water F Temp. - Lo Resolution Leaving Condenser Water 041F *X+55 = F Temp. - Hi Resolution Leaving Evaporator Water F Temp. - Lo Resolution Leaving Evaporator Water Temp. - Hi Resolution *X+20 = F MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 21 of 62

22 Description Address Range Units LED Front Panel 021F 0 = deenergzd 1 = energized Lift Pressure PSIG Liquid Injection Solenoid = deenergzd 1 = energized Liquid Line Refrigerant F Temp. - Lo Resolution Liquid Line Refrigerant 041D *X+55 = F Temp. - Hi Resolution Liquid Subcool Load Solenoid = deenergzd 1 = energized Low Evaporator Pressure Limit 043B 0 = Inactive 1 = Active Manual Amp Limit 043D 0 = Inactive 1 = Active Manual Amp Limit Setpoint % RLA Maximum Amp Limit 043C 0 = Inactive 1 = Active Motor Control Latch Relay = deenergzd 1 = energized Motor Control Relay 021E 0 = deenergzd 1 = energized Motor Current, Amps 0435, 0436 Hi Byte Lo Byte Motor Current 0-65,535 Amps Motor Current, Percent 040C % RLA Motor Temperature Switch 050E 0 = high temp BIT 6 1 = OK Number of Starts 0432, 0433 Hi Byte Lo Byte Oil Delta Pressure 040D PSID Oil Feed Temp F Oil Gage Pressure PSIG Oil Heater = deenergzd 1 = energized Oil Pressure Differential Switch 050E BIT 5 0 = low press 1 = OK Oil Pump 021D 0 = deenergzd 1 = energized Oil Sump Temp. 040A F Read in hex, 0-65,535 starts. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 22 of 62

23 Description Address Range Units Operating Hours 0430, 0431 Hi Byte, Lo Byte Panel Rocker Switch 050E BIT 2 0 = stop 1 = auto Read in hex, 0-65,535 hours. Remote Amp Limit 043E 0 = Inactive 1 = Active Remote Chilled Water Reset = Inactive 1 = Active Remote Reset or Amp Limit Signal, 4-20 ma 040B < 20, mA Remote Start/Stop Switch 050F BIT 3 0 = stop 1 = start Soft Load Limit 043A 0 = Inactive 1 = Active Starter Fault Switch Starter Transition Switch 050F BIT 7 050F BIT 4 0 = fault 1 = OK 0 = fault 1 = OK Superheat Surge Guard Switch 050E BIT 7 0 = surge 1 = OK Unit Status See below Unload Solenoid = deenergzd 1 = energized Vanes Closed Switch 050F BIT 2 0 = open 1 = closed Watchdog Output = deenergzd 1 = energized Alarm Contact 0217 This is used to indicate the presence of an alarm condition. A de-energized state (0) in this location indicates an alarm; an energized state (1) indicates no alarm. Approach (Condenser) 0418 This location contains the Condenser Approach Temperature in F. The approach temperature is calculated by subtracting the Leaving Condenser Water Temperature from the Condenser Refrigerant Temperature. Calculated Leaving Evaporator Temperature Setpoint 0420 This is the calculated leaving evaporator water temperature setpoint which the chiller will be controlled to taking into account any chilled water reset which may be active. To interpret this memory location, multiply by 0.2 and then add 20. The resulting setpoint after reset with a resolution of 0.2 F. See explanation under Maximum Chilled Water Reset Setpoint for more information. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 23 of 62

24 Calculated Network Amp Setpoint 0423 The resulting amp limit setpoint in percent after reset. Compressor Discharge Temperature 0407 This location contains the current Compressor Discharge Temperature in F. Compressor Suction Temperature - Lo Resolution 0403 This location contains the current Compressor Suction Temperature in F. For better resolution of the Compressor Suction Temperature, see the following memory location. Compressor Suction Temperature - Hi Resolution 041C This is the current Compressor Suction Temperature in 0.2 resolution. This location contains a valid value only if the temperature is between 20 F and 71 F. If this location contains a value of 0 or 255, this indicates that the current temperature is out of the 20 to 71 range. If the temperature is out of range for this location, see the above memory location (0403) for an expanded temperature range. Condenser Pump This is the status of the Condenser Pump. A "0" in this location indicates the condenser pump is off. A non zero value indicates the Condenser pump is on. 021C Condenser Refrigerant Pressure 0411 This location contains the current Condenser Refrigerant Pressure in PSIG Condenser Refrigerant Temperature 0408 This location contains the current Condenser Refrigerant Temperature in F. "x" in a bit locations means that bit is not used to determine the status. Condenser Water Flow Switch BIT 6 050F This location contains the status of the Condenser Water Flow Switch. BIT 6 is read to determine the status of the Flow Switch. A "0" in BIT 6 (x0xxxxxx) indicates no flow, and a "1" in BIT 6 (x1xxxxxx) indicates flow. Cooling Tower Stage This location contains the status of the output for Cooling Tower Stage 1. A "0" indicates the output is off. A non zero value indicates the output is on. Cooling Tower Stage This location contains the status of the output for Cooling Tower Stage 2. A "0" indicates the output is off. A non zero value indicates the output is on. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 24 of 62

25 Current Fault 0428 Last Fault 0834 Fault Fault Fault Fault Fault Fault 7 083A Fault 8 083B This section lists all of the faults and their fault codes. This list is also used for Last Fault, Fault 2, Fault 3, Fault 4, Fault 5, Fault 6, Fault 7 and Fault 8. Alarm Value No Fault 0 No Transition 1 Low Oil Sump Temperature 2 High Oil Feed to Bearings Temperature 3 Low Evaporator Pressure 4 High Discharge Pressure 5 High Discharge Temperature 6 Surge 7 High Suction Temperature 8 High Motor Temperature 9 Starter Fault 10 Low Charge 11 No Evaporator Flow 12 No Condenser Flow 13 Low Delta Oil Pressure 14 Low Motor Current 15 Bad Evap Lvg Water Sensor 16 Bad Evap Ent Water Sensor 17 Bad Evaporator Temp Sensor 18 Bad Suction Line Sensor 19 Bad Liquid Line Sensor 20 Bad Ent Cond Water Sensor 21 Bad Lvg Cond Water Sensor 22 Bad Discharge Line Sensor 23 Bad Condenser Temp Sensor 24 Bad Oil Feed Sensor 25 Bad Oil Sump Sensor 26 Bad Remote Reset 27 MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 25 of 62

26 Alarm Value Motor Current 28 Oil Gauge Pressure 29 Vanes Open 30 Entering Condenser Water Temperature - Lo Resolution 0405 This location contains the current Entering Condenser Water Temperature in F. For better resolution of the Entering Condenser Water Temperature, see the following memory location. Entering Condenser Water Temperature - Hi Resolution 041E This is the current Entering Condenser Water Temperature in 0.2 resolution. This location contains a valid value only if the temperature is between 55 F and 106 F. If this location contains a value of 0 or 255, this indicates that the current temperature is out of the 55 to 106 range. If the temperature is out of range for this location, see the above memory location (0405) for an expanded temperature range. Entering Evaporator Water Temperature - Lo Resolution 0401 This location contains the current Entering Evaporator Water Temperature in F. For better resolution of the Entering Evaporator Water Temperature, see the following memory location. Entering Evaporator Water Temperature - Hi Resolution 041A This is the current Entering Evaporator Water Temperature in 0.2 resolution. This location contains a valid value only if the temperature is between 20 F and 71 F. If this location contains a value of 0 or 255, this indicates that the current temperature is out of the 20 to 71 range. If the temperature is out of range for this location, see the above memory location (0401) for an expanded temperature range. Entering Water Reset 0438 This location contains the status of the Entering Water Reset. A "0" indicates that Entering Water Reset is inactive. A "1" indicates that Entering Water Reset is active. Evaporator Low Pressure Switch BIT 3 050E This location contains the status of the Evaporator Low Pressure Switch. BIT 3 is used to indicate low Pressure. A "0" in BIT 3 (xxxx0xxx) indicates low pressure. A"1" (xxxx1xxx). Evaporator Pump This locations contains the status of the Evaporator Pump Output. A "0" in this location indicates the output is off. A non zero value means the pump is on. 021B Evaporator Refrigerant Pressure 0410 This location contains the Evaporator Refrigerant Pressure in PSIG. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 26 of 62

27 Evaporator Refrigerant Temperature - Lo Resolution 0402 This location contain the current Evaporator Refrigerant Temperature in F. For better resolution of the Evaporator Refrigerant Temperature, see the following memory location. Evaporator Refrigerant Temperature - Hi Resolution 041B This is the current Evaporator Refrigerant Temperature in 0.2 resolution. This location contains a valid value only if the temperature is between 20 F and 71 F. If this location contains a value of 0 or 255, this indicates that the current temperature is out of the 20 to 71 range. If the temperature is out of range for this location, see the above memory location (0402) for an expanded temperature range. Evaporator Water Flow Switch BIT 5 050F This location contains the status of the Evaporator Water Flow Switch. A "0" in BIT 5 (xx0xxxxx) indicates no evaporator flow. A "1" (xx1xxxxx) indicates evaporator flow. High Discharge Pressure Switch BIT 4 050E This location contains the status of the High Discharge Pressure Switch. A "0" in BIT 4 (xxx0xxxx) indicates high discharge pressure. A "1" (xxx1xxxx) indicates normal discharge pressure. Hot Gas Solenoid 0212 This location indicates the status of the Hot Gas Solenoid output. A "0" indicates the output is off. A non zero values indicates the output is on. Leaving Condenser Temperature - Lo Resolution 0406 This is the current Leaving Condenser Water Temperature. For better resolution of the Leaving Condenser Temperature, see the following memory location. Leaving Condenser Temperature - Hi Resolution 041F This is the current Leaving Condenser Water Temperature in 0.2 resolution. This location contains a valid value only if the temperature is between 55 F and 106 F. If this location contains a value of 0 or 255, this indicates that the current temperature is out of the 55 to 106 range. If the temperature is out of range for this location, see the above memory location (0406) for an expanded temperature range. Leaving Evaporator Water Temperature - Lo Resolution 0400 This is the current Leaving Evaporator Water Temperature in 1 resolution. For better resolution of the Leaving Evaporator Water Temperature, see the following memory location. Leaving Evaporator Water Temperature - Hi Resolution 0419 This is the current Leaving Evaporator Water Temperature in 0.2 resolution. This location contains a valid value only if the temperature is between 20 F and 71 F. If this location contains a value of 0 or 255, this indicates that the current temperature is out of the 20 to 71 range. If the temperature is out of range for this location, see the above memory location (0400) for an expanded temperature range. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 27 of 62

28 LED Front Panel 021F This location contains the status of the output for the LED on the front panel. A "0" in this location indicates the output is off. A non zero value indicates the output is on. Lift Pressure 0412 This location contains the current Lift Pressure in PSIG. Lift Pressure is calculated by subtracting the Evaporator Pressure from the Condenser Pressure. Liquid Injection Solenoid 0216 This location contains the current status of the Liquid Injection Solenoid output. A "0" in this location indicates the output is off. A non zero value indicates the output is on. Liquid Line Refrigerant Temperature - Lo Resolution 0404 This location contains the current Liquid Line Refrigerant Temperature in F. For better resolution of the Liquid Line Refrigerant Temperature, see the following memory location. Liquid Line Refrigerant Temperature - Hi Resolution 041D This is the current Liquid Line Refrigerant Temperature in 0.2 resolution. This location contains a valid value only if the temperature is between 55 F and 106 F. If this location contains a value of 0 or 255, this indicates that the current temperature is out of the 55 to 106 range. If the temperature is out of range for this location, see the above memory location (0404) for an expanded temperature range. Liquid Subcool 0417 This location contains the current Liquid Subcool Temperature in F. This temperature is calculates by subtracting the Liquid Line Temperature from the Condenser Temperature. Load Solenoid 0211 This location contains the status of the Load Solenoid output. A "0" indicates the output is off. A non zero location indicates the output is on. Low Evaporator Pressure Limit This location contains the status of the Low Evaporator Pressure Limit. A "0" indicates that the limiting is inactive. A"1" indicates that limiting is active. Manual Amp Limit 043B 043D Via the keypad/display on the chiller, the operator may enter a "Manual" amp limit for the chiller (See Manual Amp Limit Setpoint below). If the %RLA of the chiller is exceeding the "Manual" amp limit, then capacity limiting will be enforced. This location contains the status of the Manual Amp Limit. A "0" indicates that limiting is inactive. A"1" indicates that limiting is active. Manual Amp Limit Setpoint 0901 This is the "Manual" amp limit setpoint which the operator has set for the chiller via the keypad/display at the chiller. Note this is a EEPROM memory location and should not be written to. If you desire to change the amp limit in response to an MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 28 of 62

29 algorithm or building demand limit function, use the Network Amp Reset memory location. Maximum Amp Limit 043C If the %RLA of the chiller is exceeding 100%, the chiller capacity will be limited. This location contains the status of "Maximum" Amp Limiting. A "0" indicates that limiting is inactive. A"1" indicates that limiting is active. Motor Control Latch Relay 0213 This location contains the status of the Motor Control Latch output. A "0" indicates the output is off. A non zero value indicates the output is on. Motor Control Relay 021E This location contains the status of the Motor Control Relay (MCR) output. A "0" indicates the MCR output is off. A non zero value indicates the MCR output is on. Motor Current, Amps 0435, 0436 These locations contain the Motor Current in Amps. These locations are read by multiplying the high byte (0435) by 256 and adding the low byte (0436). The result is the Motor Current in Amps (0-65,535). Motor Current, Percent This is the motor amps that the chiller is operating at in percent of Rated Load Amps. Motor Temperature Switch 040C BIT 6 050E This location contains the status of the Motor Temperature Switch. A "0" in BIT 6 (x0xxxxxx) indicates high temperature. A "1" in BIT 6 (x1xxxxxx) indicates normal temperature. Number of Starts 0432, 0433 These locations contain the Number of Starts. These locations are read by multiplying the high byte (0432) by 256 and adding the low byte (0433). The result is the current number of starts. Oil Delta Pressure This location contains the current Oil Delta Pressure in PSID. 040D Oil Feed Temperature 0409 This location contains the current Oil Feed Temperature in F. Oil Gage Pressure 0415 This location contains the current Oil Gage Pressure in PSIG Oil Heater 0215 This location contains the status of the Oil Heater output. A "0" indicates the output is off. A non zero value indicates the output is on. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 29 of 62

30 Oil Pressure Differential Switch BIT 5 050E This location contains the status of the Oil Pressure Differential Switch. A "0" in BIT 5 (xx0xxxxx) indicates low pressure. A "1" in BIT 5 (xx1xxxxx) indicates normal pressure. Oil Pump 021D This location contains the status of the Oil Pump output. A "0" indicates the output is off. A non zero value indicates the output is on. Oil Sump Temperature This location contains the current Oil Sump Temperature in F. 040A Operating Hours 0430, 0431 These locations contain the current Operating Hours. These locations are read by multiplying the high byte (0430) by 256 and adding the low byte (0431). The result is the current number of starts. Panel Rocker Switch BIT 2 050E This location contains the status of the Panel Rocker Switch. A "0" in BIT 2 (xxxxx0xx) indicates that the switch is set to the "Off" position. A "1" in BIT 2 (xxxxx1xx) indicates that the switch is set to the "Auto" position. Remote Amp Limit 043E This locations contains the current status of Remote Amp Limiting. A "0" indicates that Remote Amp Limiting is not active. A "1" indicates that Remote Amp Limiting is active. Remote Chilled Water Reset 0439 This locations contains the current status of Remote Chilled Water Reset. A "0" indicates that Remote Chilled Water Reset is not active. A "1" indicates that Remote Chilled Water Reset is active. Remote Reset or Amp Limit Signal, 4-20 ma This is a reading of the input signal coming in from a remote device. 040B Remote Start/Stop Switch BIT 3 050F This location contains the Status of the Remote Start/Stop Switch. A "0" in BIT 3 (xxxx0xxx) indicates that the Remote Start/Stop Switch is in the "Stop" position. A "1" in BIT 3 (xxxx1xxx) indicates that the Remote Start/Stop Switch is in the "Start" position. Soft Load Limit This locations contains the current status of Soft Load Limit. A "0" indicates that Soft Load Limit is not active. A "1" indicates that Soft Load Limit is active. Starter Fault Switch 043A BIT 7 050F This location contains the status of the Start Fault Switch. A "0" in BIT 7 (0xxxxxxx) indicates that the Starter Fault Switch is in the "Fault" position. A "1" in BIT 7 (1xxxxxxx) indicates that the Starter Fault Switch is in the "OK" position. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 30 of 62

31 Starter Transition Switch BIT 4 050F This location contains the status of the Starter Transition Switch. A "0" in BIT 4 (xxx0xxxx) indicates that the Starter Transition Switch is in the "Fault" position. A "1" in BIT 4 (xxx1xxxx) indicates that the Starter Transition Switch is in the "OK" position. Superheat 0416 This location contains the current Superheat Temperature in F. Superheat is calculated by subtracting the Evaporator Temperature from the Suction Temperature. Surge Guard Switch BIT 7 050E This location contain the status of the Surge Guard Switch. A "0" in BIT 7 (0xxxxxxx) indicates that the Surge Guard Switch is in the "Surge" position. A "1" in BIT 1 (1xxxxxxx) indicates that the Surge Guard Switch is in the "OK" position. Unit Status 0424 This is the current unit status of the chiller. The following is a list of possible modes and their corresponding number. Mode Name Start Requested 1 Waiting Low Oil Sump Temperature 2 Evaporator Pump On 3 Waiting for Load 4 Oil Pump On 5 Condenser Pump On 6 Startup Unloading 7 Motor Control Relay Started 8 Running OK 9 Begin Routine Shutdown 10 Begin Rapid Shutdown 11 Waiting High Current 12 MCR Off Post Lubrication 13 Not Used 16 Off: Fault = No Transition 17 Off: Fault = Low Oil Sump Temperature 18 Off: Fault = High Oil Feed to Bearings 19 Temperature Off: Fault = Low Evaporator Pressure 20 Off: Fault = High Discharge Pressure 21 Off: Fault = High Discharge Temperature 22 Off: Fault = Surge 23 Off: Fault = High Suction Temperature 24 Value MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 31 of 62

32 Mode Name Value Off: Fault = High Motor Temperature 25 Off: Fault = Starter Fault 26 Off: Fault = Low Charge 27 Off: Fault = No Evaporator Flow 28 Off: Fault = No Condenser Flow 29 Off: Fault = Low Delta Oil Pressure 30 Off: Fault = Low Motor Current 31 Off: Fault = Bad Evap Lvg Water Sensor 32 Off: Fault = Bad Evap Ent Water Sensor 33 Off: Fault = Bad Evaporator Temp Sensor 34 Off: Fault = Bad Suction Line Sensor 35 Off: Fault = Bad Liquid Line Sensor 36 Off: Fault = Bad Ent Cond Water Sensor 37 Off: Fault = Bad Lvg Cond Water Sensor 38 Off: Fault = Bad Discharge Line Sensor 39 Off: Fault = Bad Condenser Temp Sensor 40 Off: Fault = Bad Oil Feed Sensor 41 Off: Fault = Bad Oil Sump Sensor 42 Off: Fault = Bad Oil Pres Sensor 45 Off: Vanes Failed Open 46 Off: Load Recycle 48 Off: Time Clock 49 Off: Remote Signal 50 Off: Manual Switch 51 Off: Network Signal 52 Off: Ready to Start 53 Unload Solenoid 0210 This location contains the status of the Unload Solenoid output. A "0" indicates the output is off. A non zero value indicates the output is on. Vanes Closed Switch BIT 2 050F This location contains the status of the Vanes Closed Switch. A "0" in BIT 2 (xxxxx0xx) indicates that the vanes are open. A "1" in BIT 2 (xxxxx1xx) indicates that the vanes are closed. Watchdog Output 0214 This location contains the status of the Watchdog output. A "0" indicates the output is off. A non zero value indicates the output is on. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 32 of 62

33 Read and Write Memory Locations - Control Processor EEPROM can only be written to 10,000 times. The following is a listing of read and write memory locations for the controls processor of a Series-100 centrifugal chiller. Warning, all 09**,08** and 80** memory locations are EEPROM type and may not be written to more than 10,000 times during the life of the chiller. Precautions should be taken to prevent writing to these memory locations repeatedly. Description Address Range Units Clear Current Fault 042A = No Action 1 = Clear Fault Comm Port Baud Rate 8010 $B6 or $BB See below Correct Checksum Leaving Evaporator *X+20= F Temperature Setpoint Maximum Chilled Water *X= F Reset Setpoint Network Amp Reset 0450 <20, Network Chilled Water 044F <20, Reset Network Start/Stop , = Auto 255 = Routine Shutdown Reset Option = No Reset 7 = Amp Reset 8 = Amp & Ent 9 = Ent Reset 10 = ChW Reset 11= Amp & ChW Soft Reset = No Reset 1 = Soft Reset Start Mode = Local Start 5 = Remote Start Startup Differential *X= F Temp. Shutdown Differential Temp *X= F Clear Current Fault 042A If a 1 is written to this memory location, the current fault will be cleared and the controller will be re-initialized. This result is the same as pressing the keypad "Clear Fault" key - the controller will take no action unless the chiller is off. Note: Never write to this memory location without investigating and correcting the cause of the fault. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 33 of 62

34 Port A Baud Rate Comm Port Baud Rate 8010 The Series-100 centrifugal chiller port A is factory configured to 1200 baud and the memory location will contain the Hex value $B6. To change the baud rate to 9600 baud, change the memory location to $BB. Note that the change will take effect only when the controller is reset (i.e. power reset or soft reset). Also, a change to this memory location will affect the microprocessor's operating system checksum so it is required that the Correct Checksum memory location be changed whenever the Comm Port Baud Rate is changed. Correct Checksum 8001 If Port A baud rate is changed from 1200 baud to 9600 baud, at the same time, read this memory location and add $5, then write the result back into the Correct Checksum memory location. Example, 8010 is changed to $BB. Read this memory location and receive $D3 back. Write $D8 ($D3 +$5) to this memory location 1 to 255 = 20 F to 71 F 0.2 F resolution Leaving Evaporator Temperature Setpoint 0900 This is the desired leaving chilled water temperature setpoint before taking into account any chilled water reset which may be active. Since reset always increases the chilled water setpoint, this memory location contains the lowest chilled water setpoint that the chiller will ever control to. Take the desired chilled water setpoint before reset (to the nearest 0.2 F), subtract 20 and then divide by 0.2. Example: 45 F is the desired setpoint before reset, therefore write (45-20)*5 or 125 to this memory location. Maximum Chilled Water Reset Setpoint 0820 This location contains the maximum amount of Chilled Water Reset. This is the amount of reset that will be done when the hardwired remote reset analog signal is at 20mA or the Network Chilled Water Reset memory location is set to maximum. To interpret this memory location, divide by 5. Example: 50 / 5 = 10.0 F. This location works with Leaving Evaporator Temperature Setpoint to create the Calculated Leaving Evaporator Temperature Setpoint. The Calculated Leaving Evaporator Temperature Setpoint is calculated by adding the reset temperature to the Leaving Evaporator Temperature Setpoint. Example: If the Network Chilled Water Reset is at 50 (Valid range is 20 to 100), and the Maximum Chilled Water Reset Setpoint = 10.0 F, and the Leaving Evaporator Temperature Setpoint = 44.0 F, the amount of reset and final control in F will be: = / (100-20) = * 10.0 F = 3.75 F of reset. The value will be rounded up to 3.8 F because the MicroTech controller only works in increments of 0.2 F. 3.8 F F = 47.8 F = Calculated Leaving Evaporator Temperature Setpoint. Note: For chilled water reset to work, the unit control panel must have the chilled water reset option enabled by using the keypad display to change the "Reset Options" (under Setup Options key) set to "ChW" or "AmpChW" (See I&M 403 MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 34 of 62

35 page 5 and 31). Alternately, the Reset Option control variable may be set via communications to "ChW". Network Amp Reset 0450 A value of 20 or less will result in no demand limit. A value written from 20 to 100 will linearly reset the maximum %RLA from 100% to 40% RLA. Thus the following chart summarizes the Network Amp Reset: 100% Remote Amp Limit 40% Network Amp Reset Note: For network amp reset to work, the unit control panel must have the amp reset option enabled by using the keypad display to change the "Reset Options" (under Setup Options key) set to "Amp" or "AmpChW" (See I&M 403 page 5 and 31). Alternately, the Reset Option control variable may be set via communications to "Amp" reset. Network Chilled Water Reset 044F A value of 20 or less will result in no chilled water reset. A value written from 20 to 100 will linearly reset the chilled water control setpoint from no reset to the Maximum Chilled Water Reset Setpoint. See explanation under Maximum Chilled Water Reset Setpoint for more information. Network command to Stop the chiller Network Start/Stop 0451 Writing a value of 0 to this location enables the chiller for automatic operation. Writing a value of 255 to this memory location will result in a routine shutdown of the chiller. The display on the chiller will show "Off: System Control". Since this is a Ram location, in the event the control panel should loose power (as in a building power failure), the Ram location is cleared and the chiller will initiate a start sequence when power is restored. Thus, we suggest that this Ram location be written to repeatedly (perhaps every minute) to assure the chiller starts and stops as desired. When starting and stopping the chiller via this memory location, it is recommended that the chiller Start Mode be set to "Remote" and that a wire jumper be installed between field terminals 9 and 64 in the control box. Reset Option 0822 This memory location controls which of the possible reset options are enabled. The possible values for this memory location are as follows. MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 35 of 62

36 Value Description Explanation 6 NoReset No Resets are Enabled 7 Amp Only Amp Reset is Enabled 8 Amp_Ent Amp Reset is Enabled as well as Entering chilled water reset. (see IM 403). 9 Ent Only Entering chilled water reset is enabled. 10 ChW Only Chilled Water Reset is enabled 11 Amp_ChW Both Amp Reset and Chilled water reset are enabled. Soft Reset 0204 If a non-zero value is written to the controller at any time, the controller is reset and will begin initialization. This is a way to reset the controller via communications. Note: Never soft reset the controller unless the compressor and all auxiliary devices are off. Resetting the controller will immediately turn off (fail safe) all outputs. Start Mode 0824 A value of 4 in this memory location designates "Local" control mode, a value of 5 in this memory location designates "Remote". 5 to 50 = 1 F to 10 F 0.2 F resolution 5 to 50 = 1 F to 10 F 0.2 F resolution Startup Differential Temperature 0826 This is the temperature difference above the Leaving Evaporator Setpoint that will start the unit after a standard "cooling load satisfied" shutdown. Take the desired temperature (to the nearest 0.2 F), and multiply by 5. Example: if 7 F is the desired setpoint, write (7*5) or 35 to this memory location. Shutdown Differential Temperature 0827 This is the temperature difference below the Leaving Evaporator Setpoint that will stop the unit after a standard "cooling load satisfied" shutdown. Take the desired temperature (to the nearest 0.2 F), and multiply by 5. Example: if 4 F is the desired setpoint, write (4*5) or 20 to this memory location. Keypad/Display Controller Addresses There is a separate microprocessor controller board that is used for the Keypad/Display. This microprocessor is a level 2 controller while the chiller controller is a slave (level 3) to the keypad/display. To read memory locations from the display processor, use a different address. The proper addressing for the keypad/display processor is: "ll" "ss" Chiller No Chiller No MicroTech Series 100 Centrif. Chiller Open Protocol Version 3.2 Variables 36 of 62

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

FieldServer Driver - Serial FS McQuay Microtech Open Protocol Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

MicroTech Water-Cooled Screw Chiller Controller

MicroTech Water-Cooled Screw Chiller Controller BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software

More information

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Table 1. Series 200 Centrifugal Chiller. Point Type Range/Units 01

More information

Metasys Integrator McQuay Application

Metasys Integrator McQuay Application Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator McQuay Application Introduction Page * Application Details * Component

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV) Point Map December 1, 2004 Systems Integration McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV) Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-6 Group: Controls Part Number: ED 15121 Date: March 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHAE 135-2004, BACnet

More information

GeneSys Air-Cooled Screw Compressor Chiller

GeneSys Air-Cooled Screw Compressor Chiller Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through

More information

INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER

INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME JOB NO. ADDRESS MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS BRINE FLOW

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

Ice Rink (Single and Dual Configurations) Custom Control Features

Ice Rink (Single and Dual Configurations) Custom Control Features & M&M Refrigeration, Inc. Computer Control System Ice Rink (Single and Dual Configurations) Custom Control Features REVISION DATE DESCRIPTION - 4/20/05 Original release. A 09/21/98 Update Chiller Pump

More information

INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER

INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME ADDRESS JOB NO. MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS BRINE FLOW RATE

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Operating Manual OM WGZ-2 Group: Chiller Part Number: 331374501 Effective: March 2005 Supercedes: OM WGZ-1 Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 120AW, Packaged Water-Cooled Chiller

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER Table of Contents - 2 - INTRODUCTION... 3 OPERATING LIMITS:... 4 CONTROLLER FEATURES... 4 GENERAL DESCRIPTION... 5 CONTROL

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Product Data Catalog Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Variable Speed Total Access Modules MS010W, MS020W, MS030W, MS050W MS010V, MS020V,

More information

Air-Cooled Scroll Compressor Chiller

Air-Cooled Scroll Compressor Chiller Air-Cooled Scroll Compressor Chiller Operation Manual OM AGZC-1 Group: Chiller Part Number: 331376301 Effective: February 2010 Supercedes: April 2009 AGZ 030CH through 190CH, Packaged AGZ 030CB through

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

YST PRE START-UP CHECKLIST

YST PRE START-UP CHECKLIST STEAM TURBINE CENTRIFUGAL LIQUID CHILLERS START-UP CHECKLIST Supersedes 160.67-CL1 (1108) Form 160.67-CL1 (114) YST PRE START-UP CHECKLIST OFFICE LOCATION TECHNICIAN S NAME UNIT MODEL NUMBER YORK CONTRACT

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Heat Pump Water Heater (Generation 4) Troubleshooting (Effective 1 Nov 2016)

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Heat Pump Water Heater (Generation 4) Troubleshooting (Effective 1 Nov 2016) No Power,, Fan or Compressor Nothing happens at all. No compressor motor; no fan; no display. 1. See use and care manuals to turn unit ON and set operating MODE. 2. Check for the presence of power at the

More information

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com FL500 Modbus Communication Operating Manual Order No.: 10193214/00 MSAsafety.com 1000 Cranberry Woods Drive Cranberry Township, PA 16066 A Phone 1-800-MSA-2222 Fax 1-800-967-0398 For your local MSA contacts

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

Operation Manual. MicroTech Remote Monitoring and Sequencing Panel. for Reciprocating and Screw Chillers

Operation Manual. MicroTech Remote Monitoring and Sequencing Panel. for Reciprocating and Screw Chillers Operation Manual Bulletin No. OM 118 June 1995 Part No. 573932Y-01 MicroTech Remote Monitoring and Sequencing Panel for Reciprocating and Screw Chillers [Photo of panel only] For Use With McQuay Models

More information

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal

More information

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R Products That Perform...By People Who Care FORM NO: MS0455A WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R134a HXWC SERIES 205 to 560 Tons 60Hz INTRODUCTION Dunham-Bush's HXWC water cooled

More information

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years. TURBOCOR COMPRESOR CHILLERS General Description Microprocessor controlled, water chiller using HFC 134a refrigerant, two stage centrifugal oil free variable speed compressor's and electronic expansion

More information

Pathfinder Air-Cooled Chillers

Pathfinder Air-Cooled Chillers Operating & Maintenance Manual OMM 1123 Group: Chiller Part Number: OMM 1123 Date: January 2012 Supercedes: December 2011 Rev 00 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes Models

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1)

APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1) Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1) Table 1. European Reciprocating Chiller (CR1). Point Type Description

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Operating and Maintenance Manual OMM 1130 Group: Chiller Part Number: OMM 1130 Effective: March 2012 Supercedes: November 2011 Water-Cooled Scroll Compressor Chillers WGZ030DW to WGZ200DW, Packaged Water-Cooled

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

RSMSD Technical Guide

RSMSD Technical Guide RSMSD Technical Guide www.aaon.com AAON/WattMaster Controls Inc. 8500 NW River Park Drive Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 FAX: (816) 505-1101 E-mail: mail@wattmaster.com

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Operating Manual OM WGZC-2 Group: Chiller Part Number: 331975301 Effective: August 2011 Supercedes: November 2010 Water-Cooled Scroll Compressor Chillers WGZ 030CW To WGZ 200CW, Packaged Water-Cooled Chiller

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Operating Manual OM WGZC Group: Chiller Part Number: 331374501 Effective: January 2008 Supercedes: New Water-Cooled Scroll Compressor Chillers WGZ 030CW to WGZ 200CW, Packaged Water-Cooled Chiller WGZ

More information

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING Tempered Water Logic Control OPERATION l TROUBLE SHOOTING English For MPE Multiple Chiller Units Control Panel TEMPERED WATER SYSTEMS L-2199 Rev. 20080223 Revision: L-2199 20101104 *** IMPORTANT NOTICE

More information

Modbus TCP/IP Option Instruction Manual

Modbus TCP/IP Option Instruction Manual W A L C H E M An Iwaki America Company WebMaster Modbus TCP/IP Option Web Master WIND Modbus TCP/IP Option Instruction Manual s825v008 and higher Five Boynton Road Hopping Brook Park Holliston, MA 01746

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN - 2 - Table of Contents INTRODUCTION... 2 CONTROLLER OPERATING LIMITS:... 3 CONTROLLER FEATURES... 3

More information

Cutting Edge Compressor Technology

Cutting Edge Compressor Technology CHILLER MODULES Cutting Edge Compressor Technology MagLev ; magnetic levitation Oil Free design Quieter than typical background noise Soft start; pulls only 2 amps at 460V Superior part load efficiency

More information

Pathfinder Air-Cooled Chillers

Pathfinder Air-Cooled Chillers Operating & Maintenance Manual OMM 1168 Group: Chiller Part Number: OMM 1168 Date: September 2012 Rev 00 Supercedes: OMM 1123, July 2012 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes

More information

Database for CTS6000 MODBUS

Database for CTS6000 MODBUS Database for CTS6000 MODBUS Valid for: LONcard SW1.7.4B, Variable List V2.02 Version 1.08-4, 01-05-2016 Contents Contents... 2 1. Installation... 3 1.1. Installation and operating instructions... 3 2.

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 1 Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION...

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-537-01 1/9/2018 Verify that you have the most current version of this document

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Manual Magnitude Magnetic Bearing Centrifugal Chillers IOM 1210-1 Group: Chiller Part Number: IOM1210-1 Date: August 2014 Model WMC, C Vintage 125 to 400 Tons (440

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Metasys Integrator Vilter Application

Metasys Integrator Vilter Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 1294 APPLICATION NOTE Metasys Integrator Vilter Application lntroduction Page 3 Application Details *3

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN Table of Contents INTRODUCTION... 2 CONTROLLER OPERATING LIMITS:... 3 CONTROLLER FEATURES... 3 GENERAL

More information

Water-Cooled Screw Compressor Chillers

Water-Cooled Screw Compressor Chillers Operating Manual OM WGS-5 Water-Cooled Screw Compressor Chillers WGS 130AW to WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA to WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700

More information

Magnitude Frictionless Centrifugal Chillers

Magnitude Frictionless Centrifugal Chillers Operation & Maintenance Manual OMM 1034-1 Group: Chiller Part Number: 331499501 Effective: July 2011 Supersedes: June 2011 Magnitude Frictionless Centrifugal Chillers Model WME 0500-700 Software Version:

More information

Magnitude Magnetic Bearing Centrifugal Chillers

Magnitude Magnetic Bearing Centrifugal Chillers Operation & Maintenance Manual OMM 1034-4 Group: Chiller Part Number: 331499501 Effective: November 2012 Supersedes: July 2012 Magnitude Magnetic Bearing Centrifugal Chillers Model WME 0500-700 Software

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic and Seconscrew ranges Manufacturer Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Container Refrigeration

Container Refrigeration Container Refrigeration OPERATION AND SERVICE for 69NT40-561-019 Evergreen Container Refrigeration Units Table 3 6 Controller Alarm Indications (Sheet 1 of 8) AL03 Loss of Superheat Control AL05 Manual

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Air-Cooled Global Chiller

Air-Cooled Global Chiller Product Manual PM 970 Group: Chiller Effective: June 1997 Supersedes: None Air-Cooled Global Chiller Type AGR 055AS through 100AS Reciprocating Compressor with R-22 60 hertz 1997 McQuay International Table

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Manual Magnitude Magnetic Bearing Centrifugal Chillers IOM 1210-1 Group: Chiller Part Number: IOM1210-1 Date: August 2014 Model WMC, C Vintage 125 to 400 Tons (440

More information

Chem-Trak Jr. Instruction Manual

Chem-Trak Jr. Instruction Manual Chem-Trak Jr. Instruction Manual 0900590 Rev: B (02/10) Page 1 of 40 TABLE OF CONTENTS Specifications... 3 System Overview... 4 Operation... 5 Installation... 6 SIB and Interrupt Modules... 8 Wiring Diagram...

More information

Nov 08 PRODUCT SPECIFICATION SHEET

Nov 08 PRODUCT SPECIFICATION SHEET Honeywell UDC1200 and UDC1700 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS 51-52-03-35 Nov 08 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1200 & UDC1700 are microprocessor-based 1/16 DIN and 1/8 DIN

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers Installation, Operation and Maintenance Manual LQ Series Portable Chillers Table of Contents Foreword... 1 Installation... 1 Receiving Inspection... 1 Rigging, Handling, and Locating Equipment... 1 Electrical

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

Wired controller KJR-08B/BE. Run. Fault. TB Tot. Out. Query. Heat. Net-On. Turn-On Mode

Wired controller KJR-08B/BE. Run. Fault. TB Tot. Out. Query. Heat. Net-On. Turn-On Mode R0A (kw-0kw) 0Hz KJR-0B/BE is a human-machine interaction(hmi) used for the communication between chiller operator and main board on the chiller itself. The setting and operation order can be send to the

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

INSTALLATION/OPERATING INSTRUCTIONS BCP-3. Hot Water Reset Control For up to 3 Boilers. How the BCP-3 operates... 1:4 1:3 1:2 1:1.

INSTALLATION/OPERATING INSTRUCTIONS BCP-3. Hot Water Reset Control For up to 3 Boilers. How the BCP-3 operates... 1:4 1:3 1:2 1:1. INSTALLATION/OPERATING INSTRUCTIONS BCP-3 Hot Water Reset Control For up to 3 Boilers The BCP-3 establishes ambient comfort by varying the temperature of the heating system's circulating hot water in response

More information

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS Firmware versions up to V2.0.X INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGCUIT2Protocol-IM-H57880 06/15 1/32 Contents Section I Introduction

More information

RTHE Series R Helical Rotary Liquid Chiller Tons 60Hz

RTHE Series R Helical Rotary Liquid Chiller Tons 60Hz Features Product and Benefits Catalog RTHE Series R Helical Rotary Liquid Chiller 75-255 Tons 60Hz January 2015 RTHE-PRC002-EN Introduction To meet a wide range of applications in the 75~255 ton water-cooled

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

XT-70 Control Panel 3

XT-70 Control Panel 3 Manual XT-003.5 Copyright BTU Ventilation 2013 XT-70 Control Panel 3 3 FORWARD The new XT Series Control Panel from BTU Ventilation is built from the ground up for the 21st century farm manager. Simplicity

More information

McQuay. Screw Chiller Water Cooled. WHS Vintage A. Last Manufactured: Replacement Parts List No New 07/2012

McQuay. Screw Chiller Water Cooled. WHS Vintage A. Last Manufactured: Replacement Parts List No New 07/2012 Replacement s List No. 700024500 New 07/2012 McQuay Screw Chiller Water Cooled WHS 155-200 Vintage A Last Manufactured: 2000 To find your Daikin Applied parts distributor, call 1-800-377-2787 or visit

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

TraceNet ECM Series Control System

TraceNet ECM Series Control System TraceNet ECM Series Control System ECM Operating Guide Thermon Manufacturing Company TraceNet is a registered trademark of Thermon Manufacturing Company. ECM Operating Guide 2014, 2015 Thermon Manufacturing

More information

Contents. FX-1 Operations Manual Micro Air Corporation 124 Route 526 Allentown, NJ 08501

Contents. FX-1 Operations Manual Micro Air Corporation 124 Route 526 Allentown, NJ 08501 Contents FX-1 Operations Manual Micro Air Corporation 124 Route 526 Allentown, NJ 08501 INTRODUCTION... 1 BASIC OPERATION... 2 SYSTEM OVERVIEW... 3 OPERATOR CONTROLS AND DISPLAY PANEL... 4 & 5 DUAL BUTTON

More information

CLEANROOM MONITOR CR3A Network - Installation Instructions

CLEANROOM MONITOR CR3A Network - Installation Instructions CLEANROOM MONITOR CR3A Network - Installation Instructions INTRODUCTION The CR3 Series Cleanroom Monitor, was developed specifically to allow for monitoring of confined spaces with accuracy and reliability.

More information

TWLC - Tempered Water Logic Controller. The Intelligent Control

TWLC - Tempered Water Logic Controller. The Intelligent Control TWLC - Tempered Water Logic Controller The Intelligent Control Chiller Controls Features: Up to six (6) stages: individual board for each stage maximizes redundancy. Menu driven access and programming.

More information

EXD-HP1/2 Stand-alone Superheat/Economizer Controller

EXD-HP1/2 Stand-alone Superheat/Economizer Controller Technical Bulletin EXD-HP1/2 are stand-alone universal superheat and or economizer controllers for heat pumps, heating units, air conditioning and precision cooling such as telecom and shelter applications.

More information

WCOX B Water-Cooled Packaged Chillers with Helical Rotary Compressors

WCOX B Water-Cooled Packaged Chillers with Helical Rotary Compressors WCOX056-07B Water-Cooled Packaged Chillers with Helical Rotary Compressors Installation, Operation, and Maintenance Instructions TABLE OF CONTENTS PAGE. GENERAL INFORMATION...2. Receiving and Inspection...

More information

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a Air-Cooled Variable Speed Drive Screw Chillers Super Efficient Super Quiet Cooling Capacity Range 540-1405 kw R134a World s first low sound Air-Cooled variable speed drive screw chiller The recognition

More information

Q-Logic Digital Controls The Q3 and Qht for Direct Expansion Systems

Q-Logic Digital Controls The Q3 and Qht for Direct Expansion Systems Q-Logic Digital Controls The Q3 and Qht for Direct Expansion Systems OPERATIONS MANUAL Q3 Control Qht Control (with bezel) Dometic Marine Rev. 20110225 L-2516 English 2175 NW 34th Ave Miami, FL 33142 USA

More information