Installation, Operation and Maintenance Manual. MX Series. Rotary Screw Modular Chillers 50 to 125 Tons. Copyright 2009 Thermal Care

Size: px
Start display at page:

Download "Installation, Operation and Maintenance Manual. MX Series. Rotary Screw Modular Chillers 50 to 125 Tons. Copyright 2009 Thermal Care"

Transcription

1 Installation, Operation and Maintenance Manual MX Series Rotary Screw Modular Chillers 50 to 125 Tons Copyright 2009 Thermal Care

2 Table of Contents Foreword... 1 Safety Guidelines... 1 General Information... 2 Table 1 Water Cooled Chiller General Data (60 Hz)... 2 Table 2 Remote Air Cooled Condenser Chiller General Data (60 Hz)... 3 Figure 1 Model Number Description... 4 Capacity Data... 5 MXW Chiller Ratings... 5 Table 3 Water Cooled Chiller Performance Data (60 Hz)... 5 MXR Chiller Ratings... 7 Table 4 Remote Air Cooled Chiller Performance Data (60 Hz)... 7 Installation... 9 Receiving Inspection... 9 Rigging, Handling, and Locating Equipment... 9 Foundation... 9 Electrical Power... 9 Table 5 Chiller Electrical Data (60 Hz) Table 6 Remote Air-Cooled Condenser Electrical Data (60 Hz) Condenser Water Line Figure 2 MXW Series Condenser Water Pressure Drop Table 7 Water Cooled Condenser Water Flow Rate Requirements Chilled Water Line Figure 3 MXW/MXR Series Evaporator Water Pressure Drop Table 8 - Chilled Water Flow Rate Requirements Interconnecting Refrigerant Piping Water Pressure Gauges Remote Process Sensor System Fluid Freeze Protection System Refrigerant and Oil Charge MXW Chillers MXR Chillers Operating Principles Coolant Circuit Refrigerant Circuit Oil Circuit Components Chilled Water In Temperature Sensor Chilled Water Out Temperature Sensor Compressor Compressor Electronic Motor Module Compressor Internal Relief Valve Compressor Service Valve Condenser Remote Air-Cooled Condenser Water-Cooled Condenser Water In Temperature Sensor Condenser Water Out Temperature Sensor Condenser Water Regulating Valve Coolant Flow Switch Crankcase Heater... 18

3 Discharge Check Valve Discharge Pressure Sensor Discharge Temperature Sensor Electronic Expansion Valve (EEV) Evaporator High Refrigerant Pressure Switch Human Machine Interface (HMI) Liquid Line Check Valve Liquid Injection Solenoid Valve Liquid Line Solenoid Valve Loader / Unloader Solenoid Valve Oil Filter Oil Level Switch Oil Separator Oil Service Valve Oil Sight Glass Oil Temperature Sensor Pressure Relief Valve Process Supply Temperature Sensor Receiver Refrigerant Filter/Drier Refrigerant Service Valve Refrigerant Sight Glass Suction Pressure Sensor Suction Temperature Sensor Water Service Valves (Optional) Y Strainer Operator Interface HMI Screens and Setup Overview Chiller Chiller Statistics Security System Options Chiller Options Mode Chiller Setup Menu Tuning MXR Models Tuning MXW Models Chiller Operation Runtime Hours Alarm List I/O View Graphics Service Info Clock Calendar Setup HMI Screen Navigation Control System Parameters Table 9 Parameter List Alarm Banner Summary Chiller Compressor Fault Chiller Compressor High Pressure Fault Chiller Compressor Low Pressure Fault Chiller Crankcase Oil Level Low Fault... 46

4 Chiller Compressor Run Contactor Fault Chiller Compressor Run Contactor Overload Chiller Compressor Start Contactor Fault Chiller Compressor Start Contactor Overload Chiller E-Stop Pressed or MCR Off Chiller Flow Switch Fault Chiller Freezestat Fault Chiller Glycol Warning Chiller High Superheat Alarm Chiller Leaving Water High Temperature Alarm Chiller Low Superheat Fault Chiller Open Pressure Transducer Fault Chiller Refrigerant High Pressure Fault Chiller Refrigerant Low Pressure Fault Chiller TC Module Slot 1 Ch.(X) Alarm Condenser Fan VFD Alarm Maximum Differential Pressure Minimum Differential Pressure PLC Battery Low Power Phase Fault Remote Temperature Sensor Fault Control Sequence Startup and Running Sequence Shutdown Sequence Table 10 System Compressor Staging Initial Startup Table 11 - Recommended Glycol Solutions Preventive Maintenance Once a Week Once a Month Once a Year Maintenance Installing and Replacing Processor Battery Replacing a Fuse on the Power Supply Cleaning the Operator Interface Checking Compressor Oil Level Warranty Information PLC Troubleshooting Table 12 - Processor Status LEDs General Troubleshooting Preventive Maintenance Checklist... 60

5 Foreword The intent of this manual is to serve as a guide for placing your central chiller in service and operating and maintaining it properly. Improper installation can lead to poor equipment performance or severe equipment damage. Failure to follow the installation instructions may result in damage not covered by your warranty. It is extremely important that a qualified refrigeration installation contractor perform all installation line sizing and piping. Please supply these instructions to your authorized refrigeration contractor. This manual is for our standard product line with supplements as required to accommodate any special items provided for a specific application. The written information contained in this manual, as well as various drawings, are intended to be general in nature. The drawings included in this manual are typical only and may not represent the actual unit purchased. Actual drawings are included with the equipment for troubleshooting and servicing of the unit. Additional copies of drawings are available upon request. We strive to maintain an accurate record of all equipment during the course of its useful life. Every effort was made to standardize the design features of these chillers, the various options may make it necessary to rearrange some of the components; therefore, some of the general drawings in this manual may differ from your specific unit. Due to the ever-changing nature of applicable codes, ordinances, and other local laws pertaining to the use and operation of this equipment we do not reference them in this manual. There is no substitute for common sense and good operating practices when placing any mechanical equipment into operation. We encourage all personnel to familiarize themselves with this manual's contents. Failure to do so may unnecessarily prolong equipment down time. The chilling equipment uses chemical refrigerants for heat transfer purposes. This chemical is sealed and tested in a pressurized system containing ASME coded vessels; however, a system failure will release it. Refrigerant gas can cause toxic fumes if exposed to fire. Place these units in a well-ventilated area, especially if open flames are present. Failure to follow these instructions could result in a hazardous condition. The standard refrigerant used in these units is a hydro fluorocarbon (HFC) trade named R-134A. We strongly recommend our customers implement a refrigerant management program including a survey of all equipment to document the type and quantity of refrigerant in each machine. We recommend all refrigeration service technicians be licensed and certified by an EPA approved organization. Follow good piping practices and the information in this manual to insure a successful installation and operation of this equipment. We are not responsible for liabilities created by substandard piping methods and installation practices external to the chiller. We trust your equipment will have a long and useful life. If you should have any questions, please contact our Customer Service Department specifying the serial number and model number of the unit as indicated on the nameplate. Safety Guidelines Observe all safety precautions during installation, startup, and service of this equipment due to the presence of high voltage and refrigerant charge. Only qualified personnel should install, startup, and service this equipment. When working on this equipment, observe precautions in literature, and on tags, stickers, and labels located on the equipment. Wear work gloves and safety glasses. WARNING: This equipment contains hazardous voltages that can cause severe injury or death. Disconnect and lock out incoming power before installing or servicing the equipment. WARNING: This equipment contains refrigerant under pressure. Accidental release of refrigerant under pressure can cause personal injury and or property damage. Exercise care while working on or around this equipment. WARNING: Vent all refrigerant relief valves in accordance to ANSI/ASHRAE Standard 15, Safety Code for Mechanical Refrigeration. This equipment should be located within a well-ventilated area. Inhalation of refrigerant can be hazardous to your health and the accumulation of refrigerant within an enclosed space can displace oxygen and cause suffocation. 1

6 General Information Table 1 Water Cooled Chiller General Data (60 Hz) Model MXW50 MXW75 MXW100 MXW125 Compressor Quantity Nominal Capacity (ton) Number of Capacity Steps Continuously Variable Capacity Adjustment Minimum Unloaded Capacity (ton) Condenser Fluid Volume (gal) Maximum Refrigerant Pressure (psig) Refrigerant Pressure Relief Valve Setting (psig) Refrigerant Pressure Relief Valve (in) 5 / 8 SAE Flare 5 / 8 SAE Flare 3 / 4 FPT 3 / 4 FPT Refrigerant Pressure Relief Valve Flow Capacity (lbs. of air/min) Maximum Fluid Pressure (psig) Fluid Inlet Flange Connection (in) Fluid Outlet Flange Connection (in) Evaporator Fluid Volume (gal) Maximum Refrigerant Pressure (psig) Maximum Fluid Pressure (psig) Fluid Inlet Flange Connection (in) Fluid Outlet Flange Connection (in) Fluid Drain NPT Connection (in) 1 / 2 1 / 2 1 / 2 1 / 2 General Information Refrigerant Type R134a R134a R134a R134a Refrigerant Charge (lb) Oil Charge (oz) Shipping Weight (lb) 2,965 3,915 4,315 5,020 Operating Weight (lb) 3,145 4,095 4,575 5,330 2

7 Table 2 Remote Air Cooled Condenser Chiller General Data (60 Hz) Model MXR50 MXR75 MXR100 MXR125 Compressor Quantity Nominal Capacity (ton) Number of Capacity Steps Continuously Variable Capacity Adjustment Minimum Unloaded Capacity (ton) Condenser Maximum Refrigerant Pressure (psig) Refrigerant Pressure Relief Valve Setting (psig) Refrigerant Pressure Relief Valve SAE Flare (in) 5 / 5 8 / 5 8 / 5 8 / 8 Refrigerant Pressure Relief Valve Capacity (lbs. of air/min) Liquid Line Connection (in) 1 3 / / / / 8 Discharge Line Connection (in) 2 1 / / / / 8 Evaporator Fluid Volume (gal) Maximum Refrigerant Pressure (psig) Maximum Fluid Pressure (psig) Fluid Inlet Flange Connection (in) Fluid Outlet Flange Connection (in) Fluid Drain NPT Connection (in) 1 / 2 1 / 2 1 / 2 1 / 2 General Information Refrigerant Type R134a R134a R134a R134a Refrigerant Charge (lb) Varies based on system refrigerant piping see Installation Guidelines Oil Charge (oz) Shipping Weight Chiller (lb) 2,495 3,340 3,485 3,700 Operating Weight Chiller (lb) 2,620 3,510 3,710 3,980 Shipping Weight Remote Condenser (lb) 1,600 2,810 2,885 4,050 Operating Weight Remote Condenser (lb) Varies base on system refrigerant charge and operating conditions 3

8 Figure 1 Model Number Description Unit Model MX W 075 A M 4 S S Digit Number 1,2 3 4,5, Digits 1,2 Chiller Type Digit 14 Panel Type MX = Modular Rotary Screw Compressor 1 = NEMA-4/12 (Standard Non Flange) 2 = NEMA-12 (Flange Disconnnect) Digit 3 Condenser Type 3 = NEMA-4 (Flange Disconnect) R = Remote Air-Cooled Condenser W = Integral Water-Cooled Condenser Digit 15 Disconnect Type 0 = No Disconnect Digits 4,5,6 Nominal Compressor Cooling Capacity 1 = Rotary Non-Fused 050 = 50 ton 2 = Flange Non-Fused 075 = 75 ton 100 = 100 ton Digit 16 Water Service Valves 125 = 125 ton 0 = Without Water Service Valves 1 = With Water Service Valves Digit 7 Development Sequence A = First Development Series Digit 17 Alarm Horn 0 = No Alarm Horn Digit 8 Controller Type 1 = Alarm Horn M = Master Controller S = Slave controller Digit 18 Stack Light E = Engineered 0 = No Stacklight 1 = Stack Light Digit 9 Main Power Input 2 = Engineered 3 = 230/3/60 4 = 460/3/60 Digit 19 Sound Blanket 5 = 575/3/60 0 = No Sound Blanket E = Engineered 1 = With Sound Blanket Digit 10 Digit 11 Digit 12 Design Efficiency H = High Efficiency S = Standard Efficiency Operating Range S = Standard Temperature Range (20 F to 80 F) E = Engineered Refrigerant Type 1 = R134a 2 = R404a 3 = R507 4 = R407c 4

9 Capacity Data MXW Chiller Ratings All performance data is based on: 1. Coolant temperature rise of 10 F (5.6 C) 2. Cooler fouling factor of ft 2 hr F/Btu ( m 3 kw) 3. Condenser fouling factor of ft 2 hr F/Btu ( m 3 kw) 4. Subcooling of 10 F (5.6 C) 5. Refrigerant R-134A Table 3 Water Cooled Chiller Performance Data (60 Hz) LCWT 1 ( F) Model Cap 2 Input kw 3 Condenser Entering Water Temperature ( F) Cooler Flow Rate (gpm) Cond 4 Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) Cond 4 Flow Rate (gpm) MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW Notes: 1. LCWT = Leaving Coolant Temperature 2. Cap = Capacity in tons of refrigeration 3. kw = Compressor motor input power at rated voltage 4. Cond = Condenser 5. = Requires antifreeze protection of system fluid. See Application Consideration section for more details. Capacities, energy use, and flows based upon ethylene glycol solutions as follows based on Leaving Coolant Temperature: 15% for 35 F, 20% for 30 F, 25% for 25 F, and 30% for 20 F. Cap 2 Input kw 3 Cooler Flow Rate (gpm) Cond 4 Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) Cond 4 Flow Rate (gpm) 5

10 MXW Chiller Ratings All performance data is based on: 1. Coolant temperature rise of 10 F (5.6 C) 2. Cooler fouling factor of ft 2 hr F/Btu ( m 3 kw) 3. Condenser fouling factor of ft 2 hr F/Btu ( m 3 kw) 4. Subcooling of 10 F (5.6 C) 5. Refrigerant R-134AAll performance data is based on: Table 3 Water Cooled Chiller Performance Data (60 Hz) - Continued LCWT 1 ( F) Model Cap 2 Input kw 3 Condenser Entering Water Temperature ( F) Cooler Flow Rate (gpm) Cond 4 Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW MXW Notes: 1. LCWT = Leaving Coolant Temperature 2. Cap = Capacity in tons of refrigeration 3. kw = Compressor motor input power at rated voltage 4. Cond = Condenser Cond 4 Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) Cond 4 Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) Cond 4 Flow Rate (gpm) 6

11 MXR Chiller Ratings All performance data is based on: 1. Coolant temperature rise of 10 F (5.6 C) 2. Cooler fouling factor of ft 2 hr F/Btu ( m 3 kw) 3. Subcooling of 10 F (5.6 C) 4. Refrigerant R-134A Table 4 Remote Air Cooled Chiller Performance Data (60 Hz) LCWT 1 ( F) Model Cap 2 Condenser Entering Air Temperature ( F) Input kw 3 Cooler Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR Notes: 1. LCWT = Leaving Coolant Temperature 2. Cap = Capacity in tons of refrigeration 3. kw = Compressor motor input power at rated voltage 4. = Requires antifreeze protection of system fluid. See Application Consideration section for more details. Capacities, energy use, and flows based upon ethylene glycol solutions as follows based on Leaving Coolant Temperature: 15% for 35 F, 20% for 30 F, 25% for 25 F, and 30% for 20 F. Cap 2 Input kw 3 Cooler Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) 7

12 MXR Chiller Ratings All performance data is based on: 1. Coolant temperature rise of 10 F (5.6 C) 2. Cooler fouling factor of ft 2 hr F/Btu ( m 3 kw) 3. Subcooling of 10 F (5.6 C) 4. Refrigerant R-134A Table 4 Remote Air Cooled Chiller Performance Data (60 Hz) Continued LCWT 1 ( F) Model Cap 2 Condenser Entering Air Temperature ( F) Input kw 3 Cooler Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR MXR Notes: 1. LCWT = Leaving Coolant Temperature 2. Cap = Capacity in tons of refrigeration 3. kw = Compressor motor input power at rated voltage Cap 2 Input kw 3 Cooler Flow Rate (gpm) Cap 2 Input kw 3 Cooler Flow Rate (gpm) 8

13 Installation Receiving Inspection Each chiller is skid mounted and plastic wrapped prior to shipment. If the chiller has a remote air-cooled condenser, the condenser will ship skid mounted and will contain a holding charge of nitrogen. Before accepting delivery, check the overall equipment condition for any visible damage and document any evident on the delivery receipt. Shipping damage is the responsibility of the carrier. In order to expedite payment for damages, it is important to follow proper procedures and record keeping. Photographs of damaged equipment are excellent documentation for your records. Inspect for hidden damage after removing the packing. Refrigerant lines can be susceptible to damage in transit. Check for broken lines, oil leaks, damaged controls, or any other major component torn loose from its mounting point. Our Customer Service Department will provide assistance in preparation and filing of your claims, including arranging for an estimate and quotation on repairs; however, filing the claim is the responsibility of the receiving party. Rigging, Handling, and Locating Equipment The units have a structural steel frame. Use proper rigging methods to prevent damage to components. Avoid impact loading caused by sudden jerking when lifting or lowering the chiller. Use pads on any abrasive surface contact areas. The frame supporting the unit is for positioning the unit with a crane or a forklift. Please refer to the drawings provided with the chiller for chiller rigging details. If the chiller has a remote air-cooled condenser, please refer to the Remote Condenser Installation Guidelines manual for further instructions on locating and rigging the remote condenser. This separate document has been prepared to assist refrigeration contractors with the installation and piping design for our remote condensers. As standard, these chillers are for indoor use. Standard units are for indoor use and should not be installed or even stored in an outdoor location; however, some custom units are for outdoor installations. The unit can be stored in environments between -22 F (-30 C) and 122 F (50 C) and is designed for operation in environments between 30 F (-1 C) and 110 F (43 C). CAUTION: To prevent damage to the equipment caused by freezing, do not store or operate the unit in an ambient which may cause freezing without adequate freeze protection Serviceability was a primary concern when designing your central chiller. Do not compromise this feature by locating the chiller in an inaccessible area. Please allow a minimum of 3 feet around the perimeter of the chiller for required clearance around the chiller. If it is necessary to store the chiller in an unheated area when not in use, drain all water from the unit or add an adequate amount of antifreeze to prevent freeze-up of the unit. Foundation Provide a rigid mounting surface for the chiller of adequate strength to support the operating weight of the chiller. It is imperative to include the entire operating weight, including the completed piping and full operating weight of the refrigerant and water, in total operating weight support requirements. The chiller once mounted should be level within a 1/4 over the length and width of the unit. Electrical Power All wiring must comply with local codes and the National Electric Code. Minimum Circuit Ampacities (MCA) and other unit electrical data are on the unit nameplate are in Table 5 Chiller Electrical Data (60 Hz) and Table 6 Remote Air-Cooled Condenser Electrical Data (60 Hz). A specific electrical schematic is shipped with the unit. Measure each leg of the main power supply voltage at the main power source. Voltage must be within the voltage utilization range given in Table 5 Chiller Electrical Data (60 Hz). If the measured voltage on any leg is not within the specified range, notify the supplier and correct before operating the unit. Voltage imbalance must not exceed two percent. Excessive voltage imbalance between the phases of a three-phase system can cause motors to overheat and eventually fail. 9

14 Voltage imbalance is determined using the following calculations: %Imbalance = (Vavg Vx) x 100 / Vavg Vavg = (V1 + V2 + V3) / 3 Vx = phase with greatest difference from Vavg For example, if the three measured voltages were 442, 460, and 454 volts, the average would be: ( ) / 3 = 452 The percentage of imbalance is then: ( ) x 100 / 452 = 2.2 % This exceeds the maximum allowable of 2%. The unit includes a terminal block for main power connection to the main power source. The main power source should be connected to the terminal block through an appropriate disconnect switch. A separate lug for grounding the unit is in the main control panel. Check the electrical phase sequence at installation and prior to Startup. Operation of the compressor with incorrect electrical phase sequencing will result in mechanical damage to the compressors. Check the phasing with a phase sequence meter prior to applying power. The proper sequence should read ABC on the meter. If the meter reads CBA, open the main power disconnect and switch two line leads on the line power terminal blocks (or the unit mounted disconnect). All components are wired and phased correctly at the factory. Do not interchange any load leads that are from the unit contactors or the motor terminals. WARNING: It is imperative that L1-L2-L3 are connected in the A-B-C phase sequence to prevent equipment damage due to reverse rotation. CAUTION: The unit requires the main power to remain connected during off-hours to energize the compressor s crankcase heater. Disconnect main power only when servicing the chiller. The crankcase heater should remain on when the compressor is off to ensure liquid refrigerant does not accumulate in the compressor crankcase. WARNING: The control panel and safeties such that connecting the appropriate power source to the main terminal block energizes the entire electric circuitry of the chiller. A control transformer and power supply has been factory wired to step down the incoming power to the 115VAC and 24VDC control power. Electric power at the main disconnect should be shut off before opening access panels for repair or maintenance. Ground the unit properly in compliance with local and national codes. 10

15 Table 5 Chiller Electrical Data (60 Hz) Voltage Utilization Number of Compressor Data Unit Data Rated Number of Model Power Voltage Min Max Conductors Connections RLA 1 LRA 2 MCA 3 MOCP 4 MXW50 460/3/ /3/ MXW75 460/3/ /3/ MXW /3/ /3/ MXW /3/ /3/ MXR50 460/3/ /3/ MXR75 460/3/ /3/ MXR /3/ /3/ MXR /3/ /3/ Notes: 1. RLA is Rated Load Amps 2. LRA is Locked Rotary Amps 3. MCA is Minimum Circuit Ampacity (for wire sizing) 4. MOCP is Maximum Overcurrent Protection Table 6 Remote Air-Cooled Condenser Electrical Data (60 Hz) Model Rated Voltage Utilization Number of Power Number of Fan Data Unit Data Voltage 4 Connections Conductors Min Max Qty RLA 1 Each MCA 2 MOCP 3 LAVF /3/ LEVF /3/ LAVF /3/ LAVF /3/ Notes: 1. RLA is Rated Load Amps 2. MCA is Minimum Circuit Ampacity (for wire sizing) 3. MOCP is Maximum Overcurrent Protection /3/60 remote condensers require special selection and pricing. Consult factory for details. Condenser Water Line (MXW Models Only) The performance of a condenser is dependent on maintaining the proper flow and temperature of water through the heat exchanger. Insufficient water flow or high condenser water supply temperature will result in the reduction of cooling capacity of the chiller. Extreme conditions will eventually result in the chiller shutting down due to high refrigerant pressure. If condenser fouling by contaminants in the condenser water stream occurs, performance is negatively affected. In order to reduce maintenance costs and chiller downtime, a water treatment program is highly recommended for the condenser cooling water. If condenser plugging occurs, contact our Customer Service Department for assistance in the proper procedure for cleaning out the condenser. Caution: The use of untreated or improperly treated water in a chiller can result in scaling, erosion, algae, or slime buildup. This can lead to poor system performance or premature failure. The standard cooling capacity assumes 85 F (29 C) condenser cooling water supply. Under normal operating conditions, there will be approximately 10 F (6 C) rise through the condenser resulting in 95 F (35 C) exiting water temperature from the condenser. To ensure proper water flow through the condenser, the condenser water pump must be able to supply the pressure drop given in Figure 2 MXW Series Condenser Water Pressure Drop when providing the required condenser water flow. 11

16 Pressure Drop (PSI) Figure 2 MXW Series Condenser Water Pressure Drop MXW100 MXW MXW Water Flow Rate (GPM) Nominal condenser water flow rates based on 50 F leaving chiller water temperature and 85 F entering condenser cooling water are given in Table 7 Water Cooled Condenser Water Flow Rate Requirements. For conditions other than nominal, reference the condenser water flows listed in Table 3 Water Cooled Chiller Performance Data (60 Hz). Do not exceed the minimum and maximum limits in Table 7 Water Cooled Condenser Water Flow Rate Requirements. Flow rates greater than the maximum will cause excessive tube erosion and lead to premature tube failure. Flow rates less than the minimum will result in excessive tube fouling and reduced heat transfer. Table 7 Water Cooled Condenser Water Flow Rate Requirements Chiller Model Minimum Flow Nominal Flow Maximum Flow gpm (lpm) psid (kpa) gpm (lpm) psid (kpa) gpm (lpm) psid (kpa) MXW50 22 (83) 0.1 (0.7) 155 (587) 5.2 (35.9) 221 (837) 10.6 (73.1) MXW75 29 (110) 0.1 (0.7) 216 (818) 4.8 (33.1) 295 (1117) 9.0 (62.1) MXW (121) 0.1 (0.7) 293 (1109) 10.6 (73.1) 403 (1526) 20.0 (137.9) MXW (163) 0.2 (1.4) 367 (1389) 12.0 (82.7) 487 (1844) 21.1 (145.5) The pressure drop given in Figure 2 MXW Series Condenser Water Pressure Drop, is the minimum pressure drop required in order that the condenser water-regulating valve operates below a 60 open position. Above 60 open position, the valve flow characteristics are non-linear and can result in poor controllability. The condenser water-regulating valve controls the condenser water flow in order to maintain the discharge pressure set point. The chiller loading, condenser water inlet temperature, and discharge pressure set point determine the actual flow. The chiller starts and operates with a condenser water supply temperature range from 55 F (12.8 C) to 105 F (40.6 C). However, for the most efficient and stable chiller operation, it is recommended to maintain the condenser water supply temperature range from 65 F (18.3 C) to 85 F (29.4 C). To prevent damage to the condenser or regulating valve, the condenser water pressure should not exceed 150 PSIG (1035 kpa). The water-regulating valve will modulate the flow rate of condenser water through the condenser in order to maintain the discharge pressure set point. If the discharge pressure is above the set point, the water-regulating valve will open to increase the water flow attempting to provide more cooling. The condenser water flow can exceed nominal flow rates during these conditions and reduce the available water flow through other processes if sharing the same pump. Warning: If the condenser water pump is feeding other sources in addition to the chiller, it is highly recommended to install a circuit setter in line with the chiller in order to limit the maximum flow through the chiller. 12

17 Pressure Drop (PSI) Chilled Water Line To prevent unwanted condensation, insulate all chilled water piping. If water condenses on the piping, the state change of the water from gas to liquid will result in a substantial heat load that becomes an additional burden for the chiller. Standard central chillers provide 50 F (10 C) coolant to the process. Under normal operating conditions there will be a 10 F (6 C) rise through the process resulting in 60 F (16 C) return coolant temperature to the chiller. The importance of properly sized piping between the chiller and process cannot be overemphasized. See the ASHRAE Handbook or other suitable design guide for proper pipe sizing. In general, run full size piping out to the process and then reduce the pipe size to match the connections on the process equipment. Poorly designed piping is one of the most common causes of unsatisfactory chiller performance. Avoid unnecessarily long lengths of hoses or quick disconnect fittings that offer high resistance to water flow. When manifolds are required for water distribution, install them as close to the use point as possible. Provide flow-balancing valves at each chilled water use point to assure adequate water distribution in the entire system. Figure 3 MXW/MXR Series Evaporator Water Pressure Drop provides the pressure drop through the evaporator and chilled water piping associated with the chiller. Use this information for assistance when sizing a chilled water pump. Nominal chilled water flow rates are provided in Table 8 - Chilled Water Flow Rate Requirements, and are based on a 10 F (18 C) range across the evaporator at 50 F (10 C) LWT and 85 F (29.4 C) entering condenser water or 95 F (35 C) ambient air for remote air cooled chillers. For other leaving chilled water temperatures, refer to Table 3 Water Cooled Chiller Performance Data (60 Hz) and Table 4 Remote Air Cooled Chiller Performance Data (60 Hz). Figure 3 MXW/MXR Series Evaporator Water Pressure Drop MXW/MXR100 MXW/MXR MXW/MXR50 MXW/MXR Water Flow Rate (GPM) 13

18 Table 8 - Chilled Water Flow Rate Requirements Minimum Flow Nominal Flow* Maximum Flow Chiller Model gpm (lpm) psid (kpa) gpm (lpm) psid (kpa) gpm (lpm) psid (kpa) MXW50 62 (235) 1.9 (13.1) 127 (481) 8.1 (55.8) 250 (946) 31.4 (216.5) MXW75 88 (333) 1.9 (13.1) 179 (678) 7.9 (54.5) 350 (1325) 30.0 (206.8) MXW (447) 2.5 (17.2) 242 (916) 10.5 (72.4) 470 (1779) 39.7 (273.7) MXW (560) 2.6 (17.9) 302 (1143) 11.0 (75.8) 592 (2241) 42.2 (291.0) MXR50 56 (212) 1.6 (11.0) 114 (432) 6.5 (44.8) 224 (848) 25.2 (173.7) MXR75 78 (295) 1.5 (10.3) 162 (613) 6.4 (44.1) 312 (1181) 23.8 (164.1) MXR (397) 2.0 (13.8) 220 (833) 8.7 (60.0) 420 (1590) 31.7 (218.6) MXR (503) 2.1 (14.5) 276 (1045) 9.2 (63.4) 532 (2014) 34.1 (235.1) * Nominal flow required to meet capacity at standard conditions of 60 F (15 C) EWT and 50 F (10 C) LWT The minimum flow rates are required to prevent fouling and to ensure the chiller stays within normal refrigerant operating conditions. If the process flow requirement is lower than the minimum flow limitation shown in Table 8 - Chilled Water Flow Rate Requirements, multiple smaller chillers may be used. Another alternative is to use a primary pumping loop designed for lower flow at a higher temperature rise through the process and a secondary pumping loop designed for a higher flow and lower temperature drop through the chiller. If a secondary pumping loop is used, maintain the mixed temperature of coolant entering the evaporator at a minimum of at least 5 F (2.8 C) above the set point of the chiller. The maximum flow limitation shown in Table 8 - Chilled Water Flow Rate Requirements, is the theoretical limits of the chiller based upon a 5 F (2.8 C) drop across the cooler; however, these flows result in impractical pressure drops through the cooler and are therefore not likely for a system design. If the process flow requirement is higher than the maximum flow limitation shown in Table 8 - Chilled Water Flow Rate Requirements, a bypass around the chiller may be used. Another alternative is to use a primary pumping loop designed for higher flow and lower temperature rise through the process and a secondary pumping loop designed for lower flow and higher temperature drop through the chiller. If a secondary pumping loop is used, maintain the mixed temperature of coolant entering the cooler at a minimum of at least 5 F (2.8 C) above the set point of the chiller. The use of varying cooler flows is sometimes necessary; however, it is highly recommended to use a dedicated evaporator circulation pump to provide increased system stability. The controls of the chiller are very adaptable and are capable of adjusting to variations in the flow of water through the system and will load and unload compressor(s) as needed to maintain tight control of the leaving water temperature of the system. If the cooler flow is varied, the minimum fluid loop volume must be in excess of 3 gallons of coolant per ton of cooling (3.2 L per kw) and the flow rate must change at a rate of no greater than 10% per minute in order to maintain an acceptable level of temperature control. This is a practical amount of water which typically buffers fluctuations in the process enough that the chiller will generally see fairly gradual rates of change in the inlet water temperature and will be able to accurately load or unload the compressor(s) which in turn will allow for very consistent and stable supply temperatures to the process. Use a system volume of 6 to 10 gallons of coolant per ton (6.4 to 10.8 L per kw) if the flow rate changes more rapidly than 10% per minute. If the chiller sees a net rates of change greater than 10% per minute it may result in temporary supply temperature fluctuations greater than 1 F (0.56 C). Interconnecting Refrigerant Piping (MXR Models Only) The chiller unit has a full charge of oil, excluding the additional charge for field piping, and a refrigerant holding charge. The chiller is for use only with the air-cooled condenser provided with the unit. The following section covers the required piping between the chiller and the provided air-cooled condenser. Caps are located on the discharge and liquid lines. These line sizes do not necessarily reflect the actual line sizes required for the piping between the chiller and the air-cooled condenser. The installing contractor need only provide the interconnecting piping between the chiller and the air-cooled condenser. Refrigerant piping size and piping design has a significant effect on system performance and reliability. For specific pipe sizing and configuration, refer to the MXR Series Chiller Remote Air Cooled Condenser Installation Guidelines Manual. All piping should conform to the applicable local and state codes. Use refrigerant grade copper tubing only and isolate the refrigeration lines from building structures to prevent transfer of vibration. Do not use a saw to remove end caps. This might allow copper chips to contaminate the system. Use a tube cutter or heat to remove the caps. When sweating copper joints it is important to flow dry nitrogen through the system. This prevents scale formation. Do not use soft solders. For 14

19 copper-to-copper joints use a phos-copper solder with 6% to 8% silver content. Use a high silver content brazing rod for copper-to-brass or copper-to-steel joints. Only use oxy-acetylene brazing. Water Pressure Gauges It is highly recommended to install pressure gauges or taps (field supplied) in the inlet and outlet of both the condenser and evaporator chilled water piping. The ability to read the pressure drop across the chiller is important and will aid in preventive maintenance and in troubleshooting the chiller performance. Remote Process Sensor When using multiple chiller modules together to form a single system, a remote process-supply temperature sensor is field installed in the common chilled water supply piping. This sensor should be installed downstream of all individual chilled water supply streams. This sensor will be the control sensor for the chilled water set point and will determine the loading/unloading of all compressors. Select the Remote Temp Sensor in the system options screen within the HMI. It is possible to use a remote process sensor with a single chiller if the chilled water control point is not local to the chiller. Mount the sensor in a ½ NPT coupling in minimum pipe size of 3. The probe sheath is ½ OD x 3 in length and is equipped with a ½ NPT fitting for direct mounting in a coupling. The sensor is equipped with a NEMA 4 sensor head. Wiring must be field provided from the sensor head to the chiller electrical enclosure and landed at the designated terminal blocks within the enclosure. Please see the electrical schematic provided for further detail. System Fluid Freeze Protection For applications where system fluid will be exposed to ambient conditions of 32 F (0 C) or colder and/or the set point of the system will be below 40 F (4.4 C), antifreeze must be added to the system fluid to protect the chiller and system piping from potential damage. The amount of antifreeze will vary depending on the actual desired operating conditions and should be enough to provide freeze protection to temperatures 15 F (8.3 C) colder than the coldest temperature anticipated. Use only antifreeze solutions designed for heat exchanger duty. Do not use automotive antifreeze due to the potential for fouling that can occur once its relatively short-lived inhibitors break down. System Refrigerant and Oil Charge MXW Chillers Water-cooled MXW chillers receive a full refrigerant and oil charge and run test at the factory prior to shipping. No additional refrigerant charge is required during startup unless shipping damage occurred and a refrigerant leak resulted. MXR Chillers The approximate amount of the refrigerant charge required by the system can be determined by referring to the MXR Series Chiller Remote Air-Cooled Condenser Installation Guidelines Manual. To verify the actual system charge, run the system and check the liquid line sight glass to verify proper superheat and subcooling. The chiller is factory charged with the amount of oil required by the chiller only and not the total system. The amount of additional oil required is dependent upon the amount of field-installed piping. Please see the MXR Series Chiller Remote Air Cooled Condenser Installation Guidelines Manual for the additional oil that is required. Check the oil level after the chiller has run for 15 minutes. View the oil level within the compressor sight glass while the compressor is running. If oil is required, add it through the compressor oil service valve. Solest 170 is the only approved oil for this system. 15

20 Operating Principles Coolant Circuit The coolant pump, external to the chiller, circulates coolant through the process piping and then back to the chiller. Upon entering the chiller, the coolant will pass through a y-strainer, which filters the process fluid before entering the evaporator. Heat transferred from the coolant to the refrigerant occurs in the evaporator. Varying the amount of heat transferred in the evaporator determines the loading of the compressor, which maintains the temperature set point of the coolant delivered to the process. A Process Return thermocouple senses the temperature of the coolant as it enters the evaporator. After leaving the evaporator, the coolant passes by a flow switch and the Process Supply thermocouple. The thermocouple senses the temperature of the coolant delivered to process and communicates this temperature to the PLC controller. This thermocouple also functions as a freezestat. If the multiple modules are installed and are controlling as a system, a remote process supply sensor is installed downstream of the main coolant supply header to sense the common to process temperature. This sensor is the control sensor for the PLC control system. Refrigerant Circuit The heat transferred in the evaporator from the coolant to the refrigerant changes the state of the refrigerant from a liquid to a gas. This refrigerant gas then moves from the evaporator to the compressor. The compressor is the heart of the refrigeration circuit. Cool, low-pressure gas enters the compressor and hot, highpressure gas exits the compressor. Since the compressor is not 100% efficient, some extra heat gain occurs as the refrigerant is compressed. The hot, high-pressure gas exiting the compressor goes to the condenser. In water-cooled condenser units (MXW models), the heat is transferred from the refrigerant flow around the tubes to the water that is flowing through the tubes. In aircooled condenser units (MXR models), the heat is transferred from the refrigerant in the finned tubes to the air that is flowing across the finned tubes. As the heat transfer occurs, the refrigerant changes from a gas to a liquid. The condenser removes the heat from the process load and the heat that added by the compressor. After leaving the condenser, the liquid refrigerant passes through the filter dryer and sight glass. The filter dryer filters out any particles and/or moisture from the refrigerant. Use the sight glass to monitor the stream of liquid refrigerant. The liquid refrigerant then passes through the electronic expansion valve, which meters the flow into the evaporator where the process begins again. Oil Circuit The compressor uses oil to control the discharge temperature, lubricate the compressor bearings, and seal the rotors. The compressor has a vessel directly attached to the end of the compressor, which acts as an oil reservoir and contains the oil separator. Due to the pressure difference between the suction and discharge sides of the compressor, the oil flows from the reservoir through a filter to the bearing chambers and to the profile spaces of the rotors. The oil travels in the direction of compression and flows with the compressed refrigerant into the reservoir vessel. In the reservoir vessel, oil separation from the refrigerant occurs and it collects in bottom of vessel where the process repeats. 16

21 Components Chilled Water In Temperature Sensor The thermocouple sensor is in the rear of the evaporator and senses the temperature of the chilled water entering the evaporator. The chilled water in temperature is on the HMI screen. This probe is directly in the evaporator water, there is not a sensor well included. Chilled Water Out Temperature Sensor This thermocouple sensor is in the chilled water piping leaving the evaporator and provides readings of the chilled water out temperature to the PLC. This temperature sensor input to the PLC is the control sensor if there is only one chiller installed and the Local Temp Sensor is selected in the system options screen. This temperature input is also used as the freezestat. If the chilled water out temperature falls below the freezestat set point, the compressor will shutdown in order to protect the chilled water from freezing in the evaporator. This probe is directly in the evaporator water, there is not a sensor well included. Compressor The MX series chillers use semi-hermetic, direct-drive helical rotary type screw compressors with an integral three-stage oil separator and filter. Each compressor has two rotors, male and female, which provide compression. The motor attaches to and drives the male rotor. The male rotor, in turn, drives the female rotor. Separately housed bearing sets are at each end of both rotors. The helical rotary compressor is a positive displacement device. The refrigerant from the evaporator goes into the suction opening, across the motor, and into the intake of the compressor rotor section where it is compressed. The gas then flows through the integral oil separator and finally out of the compressor at the discharge port. The compressor is also equipped with infinite or four step capacity control, start unloading, an economizer port, liquid injection cooling, external oil cooling, suction and discharge service valves, discharge check valve, internal pressure relief valve, oil sight glass, oil insertion type heater, oil service valve, oil level safety, suction gas filter, and an electronic protection device. Depending on your exact chiller configuration, the compressor may not contain all the available items as listed above. The position of the slider valve determines compressor load capacity. The slider valve moves along the length of the rotor profile and controls the amount of suction gas flow. The exact position of the slider valve determines how much refrigerant gas moves through the compressor. The compressor capacity varies to match the process load conditions. Compressor Electronic Motor Module The compressor is fitted with an electronic protection device located within the compressor motor terminal box. This device monitors the temperature of the motor with a series of PTC sensors mounted in the motor winding, the discharge gas and oil temperature via the oil temperature sensor, motor rotation, and phase failure. The trip point for motor temperature is 212 F and 251 F for discharge gas and or oil temperature. At the trip-point temperature, the compressor shuts down immediately. If an incorrect phase rotation or phase failure occurs within the first five seconds after startup, the compressor will also shutdown immediately. If repeated phase failures occur or any other fault listed above occurs, the module locks out and requires a manual reset. The main power must be off for at least five seconds to reset the module. If a temperature fault occurred, the compressor must also first cool down before the module will reset. Compressor Internal Relief Valve The compressor is fitted with an internal relief valve for burst protection. Compressor Service Valve The compressor is equipped with rotalock shut off valves on the suction and discharge connections. Condenser Remote Air-Cooled (MXR Models Only) The remote air-cooled condenser has a copper tube and aluminum fin coil with multiple fans. The refrigerant passes through the copper tubes, while the air passes over the fins. The condenser supplied is equipped to vary the header fan(s) speed and operate the remaining fans as needed to control the refrigerant discharge pressure under varying ambient and chiller loading conditions. The chiller PLC manages this control. Please see the air-cooled remote condenser installation instructions for proper mounting and connection of the condenser. 17

22 Condenser Water-Cooled (MXW Models Only) The shell and tube condenser is a steel shell, removable cast iron end bells, and a bundle of copper tubes. The condenser water passes through the copper tubes, while the refrigerant flows around the tubes on the shell side. A water maintenance program should be in place to preserve the quality of water used to cool the condenser. Excessive condenser fouling caused by poor water quality will cause poor chiller performance and or chiller failure. Condenser Water In Temperature Sensor (MXW Models Only) This thermocouple sensor is located in piping entering the condenser and senses the entering condenser water temperature. The condenser water in temperature is on the HMI screen. This probe is directly in the condenser water, there is not a sensor well included. Condenser Water Out Temperature Sensor (MXW Models Only) This thermocouple sensor is in piping leaving the condenser and senses the leaving condenser water temperature. The condenser water out temperature is on the HMI screen. This probe is directly in the condenser water, there is not a sensor well included. Condenser Water Regulating Valve (MXW Models Only) An electronic condenser water-regulating valve is standard on all MXW models. The valve is a modulating type butterfly valve located in the condenser water piping at the outlet of the condenser. The chiller PLC controls the valve actuator using a high-side refrigerant pressure signal from a pressure transducer. The valve regulates the flow of water through the condenser in order to maintain the pressure set point. The valve may be set to operate in Auto or Manual mode. In Auto mode, the PLC selects the minimum operating discharge pressure and fixes the set point. When in the manual mode, use the HMI to enter the set point. In manual mode, the pressure is set at the factory to maintain 135 PSIG (931 kpa) based on the design inlet temperature of 85 F (29 C). The valve only passes as much water as is required to maintain the refrigerant pressure, so less water will be required if the water temperature is lower than the design 85 F (29 C). Adjust the setting if inlet temperatures are different from the design 85 F (29 C). It is possible to manually opened or closed by sliding and holding the gear release on the side of the actuator. Do not manual open or close the valve while the circuit is enabled. If the valve is manually opened, it must be manually closed prior to enabling the circuit if automatic control is desired. The valve will automatically close when the circuit is disabled or the compressor shuts down due to an alarm condition. When the circuit is enabled, the valve automatically opens to a predetermined position before starting the compressor. Coolant Flow Switch This switch is located in the piping directly after the evaporator outlet. It is to shut the unit down if there is insufficient coolant flow through the evaporator. The switch is not adjustable. If the chiller shuts down due to low coolant flow, restart is using the HMI on the control panel. Crankcase Heater The compressor crankcase heater prevents too high of refrigerant concentration in the oil during shutdown. It is in a heater sleeve and is replaceable if necessary without accessing the refrigeration circuit. Discharge Check Valve A check valve is in the discharge chamber of the compressor to protect against reverse running when the compressor is off. Discharge Pressure Sensor The discharge pressure sensor or transducer monitors the discharge pressure. On the MXW models, the chiller PLC uses this input to control the electronic condenser water-regulating valve. On the MXR models, the chiller PLC uses this input to control the remote condenser fan operation. The discharge pressure or compressor head pressure is on the PLC screen. Discharge Temperature Sensor This thermocouple sensor is in the refrigerant discharge line and provides readings of the refrigerant vapor temperature to the PLC. The chiller PLC uses this temperature input to control the operation of the liquid injection valve. The discharge temperature is on the HMI screen under the system statistics tab. This sensor is in a sensor well and can be removed without opening the refrigeration circuit. 18

23 Electronic Expansion Valve (EEV) The electronic expansion valve separates the refrigerant high pressure/temperature on the condenser side from the refrigerant low pressure/temperature on the evaporator side. The EEV can serve three different control functions depending on the system operating conditions. The three control functions are superheat control, suction pressure control, and manual control. Superheat Control - The EEV meters the amount of refrigerant into the evaporator in the precise quantity in order to maintain superheat. The difference between the saturated evaporative temperature and the suction line temperature is the superheat. The superheat is factory set for 10 F to 12 F (5 C to 6 C) and should never exceed 15 F (8 C) or go below 4 F (2 C). Only a trained refrigeration service technician should adjust this valve. Suction Pressure Control - The EEV behaves as a high limit suction pressure regulator when the suction pressure rises above a preset suction pressure. The valve regulates to maintain suction pressure instead of superheat. The suction pressure set point is factory set to allow the compressor to run at the highest allowable suction pressure. This value is typically equivalent to a saturated suction temperature of 55 F (12.8 C). The EEV control reverts back to superheat control if the suction pressure falls below the maximum limit or if the superheat becomes dangerously low. While in suction pressure control, the superheat may float as long as it is within the allowable range. Manual Control The EEV also operates in a manual control mode. While in manual mode, the PLC holds a predefined EEV position during the sequence of steps prior to compressor startup. Once the compressor starts, this predefined EEV position holds until reaching the minimum compressor differential pressure. The minimum pressure differential set point is adjustable within the HMI options screen. Once reaching the minimum differential pressure, or if the superheat becomes dangerously low, the EEV mode switches to superheat control. This control function aids in quickly establishing a stable compressor operation at startup prior to the release of active EEV control. Evaporator The evaporator has stainless steel plates and copper brazing. The refrigerant passes between every other set of plates, while the coolant flows on the other side of the plates in the opposite direction. We recommend implementing a proper water maintenance program to preserve the quality of chilled water desired. Excessive evaporator fouling caused by poor chilled water quality will cause poor chiller performance and or chiller failure. High Refrigerant Pressure Switch The high refrigerant pressure switch limits the compressor discharge pressure so that it stays within the design parameters of the compressor. The switch is located on the discharge service valve and is set to open at 260 PSIG (1793 kpa). This switch has a manual reset. Should the switch open when a fault condition occurs, pressing the reset button on the back of the switch and pressing the Alarm Reset on the control panel will reset the alarm. The setting on the switch is not adjustable. Human Machine Interface (HMI) The human machine interface (HMI) provides a user interface with the PLC, which controls the operation of the chiller. The HMI allows data entry for chiller setup, accepts commands to operate chiller, and displays chiller status. Liquid Line Check Valve MXR chillers have a non-return liquid line check valve installed in the liquid condensate line upstream of the receiver. This check valve is essential to prevent migration of the refrigerant to the condenser during low ambient temperatures when the condenser ambient is cooler than the receiver ambient temperature. Liquid Injection Solenoid Valve The liquid injection solenoid valve supplies liquid refrigerant, as required, to the liquid injection nozzle integral to the compressor. The nozzle meters refrigerant directly into the compressor to provide cooling. Liquid injection cooling is required during reduced capacity operation while running at high condensing and or low evaporating temperatures. The PLC monitors the compressor discharge temperature with a sensor mounted in the discharge line and energizes the liquid injection solenoid valve when the discharge temperature reaches 230 F (110 C) and de-energizes the solenoid when the discharge temperature cools to 212 F (100 C). 19

24 Liquid Line Solenoid Valve The liquid line solenoid valve is located upstream of the electronic expansion valve. The valve is normally closed and opens when the circuit is enabled and cooling is required. The valve will open ten seconds prior to starting the compressor if the compressor superheat is greater than 20 F (11 C) prior to starting. This action helps to avoid a low suction pressure fault on startup, especially important for remote air-cooled chillers during low ambient conditions. The solenoid valve closes when the compressor stops to prevent migration of liquid refrigerant back to the compressor during shutdown. Pump down prior to shutdown is not used. The use of pump down control leads to potential situations where the compressor is operating in a vacuum. Operating in a vacuum causes high discharge temperatures that cause thermal expansion of the rotor, which can interfere with the housing and cause compressor damage. Loader / Unloader Solenoid Valve The compressor is equipped with four solenoid valves flange mounted to the compressor. These solenoid valves control the location of the slide valve, which determines the cooling capacity of the compressor. The (1) loader valve increases cooling capacity, and (3) unloader valves decrease cooling capacity. With the combination of these valves, it is possible to either control cooling capacity in (4) finite stages or in infinite capacity control. The current setup of the chiller employs infinite capacity control with the use of (2) solenoids. The cooling capacity of the compressor can vary from % of full capacity. Oil Filter The compressor is fitted with a lifetime 10-micron oil filter that is internal to the compressor. This filter requires no maintenance. Oil Level Switch The oil level switch directly monitors the level of oil in the compressor. Oil Separator The oil separator is integral to the compressor and is contained within the vessel on the discharge side of compressor. The oil separator helps to eliminate oil circulation with the refrigerant, thus retaining the oil within the compressor and reducing heat exchanger fouling. Oil Service Valve The oil service valve assists in adding oil to the compressor and retrieving oil samples. Oil Sight Glass The compressor oil level should be visible within the sight glass at all times when the compressor is running. The oil level may vary as the compressor loads and unloads. Oil Temperature Sensor A PTC temperature sensor is in the compressor oil sump and monitors the oil temperature. The sensor connects directly to the compressor electronic motor module. If the oil temperature reaches 251 F (122 C), the motor module will trip. Pressure Relief Valve A pressure relief valve is installed on all pressure vessels to safely relieve pressure due to fire or other abnormal operating conditions. MXW chillers will have a pressure relief valve installed on the water-cooled condenser and MXR chillers will have one installed on the receiver. Replace this valve if it opens. Note: Vent refrigerant relief valves in accordance to ANSI/ASHRAE Standard 15, Safety Code for Mechanical Refrigeration. Process Supply Temperature Sensor When installing and configuring multiple chillers to operate as a single system, a remote process-supply temperature sensor is required to be field installed in system piping. This sensor should be installed downstream of all individual chilled water supply streams. This sensor will be the control sensor for the chilled water set point and will determine the loading/unloading of all compressors. Select the Remote Temp Sensor in the system options screen within the HMI. 20

25 Receiver The receiver is primarily a liquid storage tank to hold liquid refrigerant when not in circulation. Since an air-cooled condenser located outdoors provides the refrigeration cycle cooling, the refrigerant charge will vary from winter to summer operation. During the summer months, the receiver holds the excess refrigerant charge required in the winter. The receiver also aids in holding the refrigerant charge while in pump down. Only MXR units contain a receiver. Refrigerant Filter/Drier The filter/drier is located in the liquid line between the condenser and the liquid line solenoid. It removes any moisture and/or foreign matter that may have gotten into the refrigerant stream. Moisture and foreign matter can cause serious damage to the components of a refrigeration system. For this reason, it is important that the chiller be equipped with a clean filter drier. Replace the filter drier core if any of the following conditions occur. Opening the refrigeration system to the atmosphere for repairs or maintenance Indication of moisture in the sight glass (the green ring has changed to yellow) An excessive pressure drop develops across the filter drier (a significant temperature difference between the filter inlet and outlet indicates this) Refrigerant Service Valve A manual two-way ball valve with an access fitting is provided in the refrigerant liquid line just downstream of the watercooled condenser for MXW chillers or just downstream of the receiver for MXR chillers. The MXR chillers provide another valve in the refrigerant liquid condensate line just before the liquid injection solenoid valve. Refrigerant Sight Glass The refrigerant sight glass is located on the electronic expansion valve. It allows the operator or service technician to observe the flow of liquid refrigerant in the circuit. Prolonged periods of foaming in the sight glass may indicate a low refrigerant condition or a restriction in the liquid line. Note: Occasional bubbling in a sight glass may occur at a time when load conditions are changing and the expansion valve is adjusting to the new conditions. This momentary occurrence is a result of normal chiller operation. Another use for the sight glass is check if there is moisture in the refrigeration circuit. If there is moisture in the circuit, the green ring around the perimeter of the sight glass will turn yellow. If this occurs, service the chiller immediately. Suction Pressure Sensor The suction pressure sensor or transducer monitors the suction pressure. The suction pressure is on the HMI screen. The chiller PLC uses this input to control the electronic expansion valve. Suction Temperature Sensor This thermocouple sensor is in the refrigeration suction line and provides readings of the refrigerant vapor temperature to the PLC. The chiller PLC uses this input to control the electronic expansion valve. The suction temperature is on the HMI screen. This sensor is in a sensor well and is removable without opening the refrigeration circuit. Water Service Valves (Optional) Manual two-way flanged butterfly valves provide isolation of the chilled and condenser water piping at the supply and return connections to the process piping. MXR chillers have chilled water service valves only. Y Strainer A Y-strainer with a 20-mesh screen is in the entering chilled water line to help protect the evaporator passages from clogging. 21

26 Operator Interface The chiller uses a color touch-screen interface that uses clear language text menus. Menu access and adjustment are by touching the screens. HMI Screens and Setup Graphical representations presented here may vary based upon the model or job-specific criteria, but the content of operation will remain consistent. When three-phase power is properly connected and chiller operation is ready to commence, the HMI (Human/Machine Interface) panel will display the following depending on the chiller type: Overview While in local mode, chiller operation is controlled by start/stop buttons. While in remote mode, chiller operation is controlled by remote contacts. MXR-TYPE OVERVIEW SCREEN Displays current chiller module #. Allows navigation between chiller modules if more than one exist. Buttons allow navigation to other screens. MXW-TYPE OVERVIEW SCREEN 22

27 Chiller Pushing the CHILLER button or touching the chiller in the graphic on the OVERVIEW screen will open the CHILLER screen as shown below. The CHILLER screen shows the most relevant information for the current selected chiller. Pushing the OVERVIEW button returns the operator to the previous screen. Displays the current status of remote condenser fans. Must be setup in Chiller Options Screen. MXR-TYPE CHILLER SCREEN Displays current operating mode of Electronic Expansion Valve. This key is only visible when logged in at level 3 security. MXW-TYPE CHILLER SCREEN 23

28 Chiller Statistics Pushing the SYSTEM STATISTICS button on the OVERVIEW or CHILLER screen will open the CHILLER STATISTICS screen as shown below: MXR-TYPE SYSTEM STATISTICS SCREEN MXW-TYPE SYSTEM STATISTICS SCREEN These screens are popup screens. To close them touch the X-button in the upper right corner. Security Selecting the CHILLER MODE or the CHILLER SETUP button on the CHILLER or OVERVIEW screen will activate the message window below. Both of these screens are password (password level 1) protected. 24

29 Press the LOGIN button on the HMI to display the SECURITY screen as shown below: Selecting User / Password Info on the SECURITY screen will open a USER/PASSWORD LIST as shown below: - Passwords for User Level 1 Level 3 are adjustable in the update password screen. - User Level 12 is a System Password and is not changeable. Please protect the distribution of this password value as seen fit by the policies of your company. Pushing the button Select User on the SECURITY screen will open the SELECT USER window as shown below: After selecting the required user (1, 2, 3 or 12) push OK to close this window. 25

30 To enter the Password for the Selected User, touch the display area indicated by the asterisks on the SECURITY screen: Use the displayed keypad to enter the following factory default password for User 1: 9999 Then press the enter key and the keypad display will close. If the password was incorrect, a red light will activate to indicate a Password Error. If the login was successful, the Current Access Classes for Logged-in User displays as below. 26

31 If ACCESS CLASS is C or higher (User 3 or User 12 is activated) a Change Password button is shown on the SECURITY screen. Pushing this button will open the UPDATE PASSWORDS screen as shown below: The Passwords for User 1, User 2 & User 3 can be modified. System Options If ACCESS CLASS is C or higher (User 3 or User 12 is activated), the OPTION button is visible in the lower left corner on the OVERVIEW screen. Pushing this button will open the SYSTEM OPTION S screen as shown below: Compressor Staging Order This determines the control sensor. If multiple chillers are present, a remote sensor installed downstream of all chillers is required. The local sensor is the leaving chilled water temperature sensor of the master chiller. Selections on this SYSTEM OPTIONS page include: - Number of chillers on the system - Type of each chiller (Water / Air-cooled) - Chiller size (MX?50 / MX?75 / MX?100 / MX?125) - System Startup. If auto is selected, the compressors are arranged in order from least to most running hours once a day and the compressors are staged accordingly to balance running hours between all compressors. If manual is selected, the order the compressors stage can be designated based on user preference. - Number of pumps on the system. There are a maximum of two pumps allowed in the system. The PLC will enable and disable the remote pumps in parallel with the chiller operation. - Type of Data Display (Imperial / Metric) 27

32 Chiller Options Up to four chillers are selectable on the SYSTEM OPTIONS page. Every selected chiller has an additional CHILLER OPTION page as shown below: Control parameters for MOP feature of electronic expansion valve. Control parameters for Manual mode of electronic expansion valve. Only present for MXR units. Sets the dead band around the chilled water set point for the lead chiller. These values are factory preset. Only a qualified refrigeration technician should change them. Mode To check the status of the individual compressor mode(s) of operation press the CHILLER MODE button in the lower right corner of the OVERVIEW or CHILLER screen. This screen is password protected (Level 1) and will bring up the following display: The mode selection is displayed with a highlighted field. Normal operation selection is ENABLED. Chiller Setup Pushing the button CHILLER SETUP in the lower right corner of the OVERVIEW or CHILLER screen will open the password protected (Level 1) CHILLER SETUP display as shown below: The setup screen will display the current chiller setup information. Press any of the numerical fields shown to enter changes to them. The keypad will pop up as before for entries. 28

33 Menu Navigating through the MENU button on the lower left corner of the HMI will allow access to the listed screens. Tuning MXR Models Chiller PID, Water Regulating Valve and Electronic Expansion Valve control parameters are bundled in the menu selection TUNING. They are accessible only by a factory password. The screens are for information only: MXR Chiller Type Please note: The Chiller Tuning screens require a higher level of protection (Level 2). Login with User 2 (or higher) and Password Please follow the instruction in the Security section above to login. Wide and narrow band compressor slide valve PID parameters CHILLER STAGING PID SCREEN 29

34 In manual mode, the discharge set point is changeable. In auto mode, the discharge set point is set to minimum in order to maximize chiller efficiency. Electronic Expansion Valve Superheat Setpoint DISCHARGE PRESSURE / EXPANSION VALVE SETPOINTS Condenser Fan PID parameters CONDENSER FAN PID SCREEN CONDENSER FAN SEPOINTS 30

35 Electronic Expansion Valve PID parameters EXPANSION VALVE PID EXPANSION VALVE STARTUP SETPOINTS This screen below is for testing the Electronic Expansion Valve when the chiller is not in RUNNING mode. This function is only for service or troubleshooting and should only be change by a qualified refrigeration technician. EXPANSION VALVE MANUAL TEST VALUES 31

36 Tuning MXW Models MXW Chiller Type TUNING SELECTION MENU Please note: The Chiller Tuning screens require a higher level of protection (Level 2). Login with User 2 (or higher) and Password Please follow the instruction in the Security section above to login. Wide and narrow band compressor slide valve PID parameters CHILLER STAGING PID SCREEN In manual mode, the discharge set point is changeable. In auto mode, the discharge set point is set to minimum in order to maximize chiller efficiency. Electronic Expansion Valve Superheat Setpoint DISCHARGE PRESSURE / EXPANSION VALVE SETPOINTS 32

37 Condenser Water Regulating Valve PID parameters CHILLER WATER REGULATING VALVE PID SCREEN CHILLER WATER REGULATING VALVE STARTUP SETPOINTS This screen below is for testing the Chiller Water Regulating Valve when the chiller is not in RUNNING mode. This function is only for service or troubleshooting. Only a qualified refrigeration technician should change this setting. CHILLER WATER REGULATING VALVE MANUAL TEST VALUES 33

38 Electronic Expansion Valve PID parameters EXPANSION VALVE PID EXPANSION VALVE STARTUP SETPOINTS The screen below is for testing the Electronic Expansion Valve when the chiller is not in RUNNING mode. This function is only for service or troubleshooting. Only a qualified refrigeration technician should change this setting. EXPANSION VALVE MANUAL TEST VALUES 34

39 Chiller Operation After confirming and/or adjusting the previous setup parameters to the desired values, the chiller is ready for operation. Press the MENU button in the lower left corner of the HMI. Then press the OVERVIEW button to return to that screen. Press START to initiate chiller operation. The chiller will begin a controlled startup process if the temperatures indicate a heat load demand. During the startup process, the SYSTEM STATUS message will change as follows: - ENABLE CHILLER CIRCUIT - CHILLERCIRCUIT ENABLED - SYSTEM RUNNING The full execution of the startup sequence lasts for approximately 3 minutes, after which the chiller is in full automatic operation, controlling the water temperature to meet setpoint. If the STOP button is pressed, the following messages will appear in the SYSTEM STATUS field: - DISABLE CHILLER CIRCUIT - CHILLER CIRCUIT OFF - SYSTEM STOPPED During system startup and shutdown, the messages in the CHILLER STATUS field will also change to indicate the current chiller status. Details to these messages are on the CHILLER screen. Messages during system operation: - OFF - RUNNING - RECYCLE - READY - UNLOADING - NO DEMAND - OPENING CWRV - CLOSING CWRV - SEQUENCE DELAY - RESET FAULT - FAULT 35

40 After the startup sequence is complete, various informational screens are available. Navigating through the MENU button on the lower left corner of the HMI will allow access to these screens. Examples follow: Runtime Hours Compressor operating hours are available from the HOURS selection button. Alarm List Below is a sample alarm pop-up banner with its resultant posting to the history screen. The active alarm is scrolling across the ALARM BANNER. ACKNOWLEDGE Turn off alarm horn RESET: Reset inactive alarms The ALARM LIST screen displays current active alarms. If an alarm has been RESET it will be removed from the ALARM LIST display. Touching the file cabinet symbol will open the ALARM HISTORY display. 36

41 The ALARM HISTORY display captures all alarm activity. The alarms on this screen stay on even after power is off. Touching the alarm horn symbol will open the ALARM LIST display. I/O View Convenient maps of states of PLC digital Inputs and digital Outputs are available. MXR- Inputs: MXR-Outputs: 37

42 MXW-Inputs: MXW-Outputs: Graphics Graphics help the operator to run the system efficiently. 38

43 Chiller Trend Real Time Values Push the TREND HISTORY button on the bottom of the screen to change to the TREND HISTORY screen Chiller Trend History Values Push the TREND REAL TIME button on the bottom of the screen to change to the TREND REAL TIME screen Service Info 39

44 Touching the Thermal Care logo on the overview screen will open the Thermal Care information screen as shown below: The information screen is displayable in multiple languages by selecting the appropriate language button on the bottom of the screen. Clock Calendar Setup Touching the Time / Date area on the overview or chiller screen will open a clock / calendar pop-up screen as shown below: To adjust the time and date, touch the appropriate field and entering the new value on the pop-up keypad as shown below: 40

45 HMI Screen Navigation 41

46 42

47 43

48 Control System Parameters Table 9 Parameter List Security Level HMI Screen Parameter Name Chiller # Range Default Setting Overview / Chiller Control Mode Common Local, Remote Local Clock-Calendar Setup Hours Common 0-23 N/A Clock-Calendar Setup Minutes Common 0-59 N/A Clock-Calendar Setup Seconds Common 0-59 N/A Clock-Calendar Setup Month Common 0-12 N/A Clock-Calendar Setup Date Common 0-31 N/A Clock-Calendar Setup Year Common N/A Security Select User Common Security Password Common N/A N/A Level 1 Chiller Setup Process Setpoint 1,2,3, Level 1 Chiller Setup Freeze Stat Setpoint 1,2,3, Level 1 Chiller Setup Hi Alarm Setpoint 1,2,3, Level 1 Chiller Setup Discharge Setpoint 1,2,3, Level 1 Chiller Setup Refrigerant High Pressure Setpoint 1,2,3, Level 1 Chiller Mode Control Mode 1,2,3,4 Enable, Disable Disable Level 2 Chiller Slide Valve PID Wide Band Gain P 1,2,3, Level 2 Chiller Slide Valve PID Wide Band Reset I 1,2,3, Level 2 Chiller Slide Valve PID Wide Band Rate D 1,2,3, Level 2 Chiller Slide Valve PID Narrow Band Gain P2 1,2,3, Level 2 Chiller Slide Valve PID Narrow Band Reset I2 1,2,3, Level 2 Chiller Slide Valve PID Narrow Band Rate D2 1,2,3, Level 2 Discharge / EEV Setpoint Control Mode 1,2,3,4 Auto, Manual Auto Level 2 Discharge / EEV Setpoint Discharge Setpoint 1,2,3, Level 2 Discharge / EEV Setpoint EEV Setpoint 1,2,3, Level 2 Condenser Fan PID (Air Cooled Only) Gain P 1,2,3, Level 2 Condenser Fan PID (Air Cooled Only) Reset I 1,2,3, Level 2 Condenser Fan PID (Air Cooled Only) Rate D 1,2,3, Level 2 Condenser Fan Staging (Air Cooled Only) Fan Bank On % 1,2,3, Level 2 Condenser Fan Staging (Air Cooled Only) Fan Bank Off % 1,2,3, Level 2 Condenser Fan Staging (Air Cooled Only) On Delay 1,2,3, Level 2 Condenser Fan Staging (Air Cooled Only) Off Delay 1,2,3, Level 2 Condenser Fan Staging (Air Cooled Only) On Pressure / Upper Deadband 1,2,3, Level 2 Condenser Fan Staging (Air Cooled Only) Off Pressure / Lower Deadband 1,2,3, Level 2 Condenser Fan Staging (Air Cooled Only) Fan Pressure Deadband Timer 1,2,3, Level 2 CWRV PID (MXW50 Only) Gain P 1,2,3, Level 2 CWRV PID (MXW50 Only) Reset I 1,2,3, Level 2 CWRV PID (MXW50 Only) Rate D 1,2,3, Level 2 CWRV PID (MXW75,100,125 Only) Gain P 1,2,3, Level 2 CWRV PID (MXW75,100,125 Only) Reset I 1,2,3, Level 2 CWRV PID (MXW75,100,125 Only) Rate D 1,2,3, Level 2 CWRV Startup Values (MXW50 Only) Supply Temp 1,2,3, Level 2 CWRV Startup Values (MXW50 Only) Below Supply Temp 1,2,3, Level 2 CWRV Startup Values (MXW50 Only) Above Supply Temp 1,2,3, Level 2 CWRV Startup Values (MXW75,100,125 Only) Supply Temp 1,2,3, Level 2 CWRV Startup Values (MXW75,100,125 Only) Below Supply Temp 1,2,3, Level 2 CWRV Startup Values (MXW75,100,125 Only) Above Supply Temp 1,2,3, Level 2 CWRV Manual Test Values (Water Cooled Only) Control Mode 1,2,3,4 Auto, Manual Auto Level 2 CWRV Manual Test Values (Water Cooled Only) %-Value 1,2,3,

49 Table 9 Parameter List (continued) Security Level HMI Screen Parameter Name Chiller # Range Default Setting Level 2 EEV PID Superheat Gain P 1,2,3, Level 2 EEV PID Superheat Reset I 1,2,3, Level 2 EEV PID Superheat Rate D 1,2,3, Level 2 EEV PID Suction Pressure Gain P 1,2,3, Level 2 EEV PID Suction Pressure Reset I 1,2,3, Level 2 EEV PID Suction Pressure Rate D 1,2,3, Level 2 EEV PID Differential Pressure Gain P 1,2,3, Level 2 EEV PID Differential Pressure Reset I 1,2,3, Level 2 EEV PID Differential Pressure Rate D 1,2,3, Level 2 EEV Manual Valve Control Mode 1,2,3,4 Auto, Manual Auto Level 2 EEV Manual Valve %-Value 1,2,3, Level 2 EEV Startup Values (MX50 Only) Start Position 1,2,3, Level 2 EEV Startup Values (MX50 Only) Startup Time 1,2,3, Level 2 EEV Startup Values (MX75,100,125 Only) Start Position 1,2,3, Level 2 EEV Startup Values (MX75,100,125 Only) Startup Time 1,2,3, Level 3 System Options # of Chillers Common Level 3 System Options Chiller Type Common Water Cooled, Air Cooled N/A Level 3 System Options Chiller Model Common MXW50, MXW75, MXW100, MXW125, MXR50, MXR75, MXR100, MXR125 N/A Level 3 System Options Temperature Sensor Common Local, Remote Local Level 3 System Options # of Pumps Common Level 3 System Options Units Display Common Imperial, Metric Imperial Level 3 Chiller Options Suction Pressure Start Pressure > 1,2,3, Level 3 Chiller Options Suction Pressure Start Delay 1,2,3, Level 3 Chiller Options Suction Pressure Stop Pressure < 1,2,3, Level 3 Chiller Options Suction Pressure Stop Superheat < 1,2,3, Level 3 Chiller Options Suction Pressure Stop Delay 1,2,3, Level 3 Chiller Options Manual Pressure Stop Pressure < 1,2,3, Level 3 Chiller Options Manual Pressure Stop Superheat < 1,2,3, Level 3 Chiller Options Manual Pressure Stop Delay 1,2,3, Level 3 Chiller Options Start Temp Offset 1,2,3, Level 3 Chiller Options Stop Temp Offset 1,2,3, Level 3 Chiller Options # of Fans (Air Cooled Only) 1,2,3,4 3-6 Model Specific Level 3 Update Password User 1 Common Level 3 Update Password User 2 Common **** Alarm Banner Summary The following list summarizes the alarm conditions displayed on the alarm banner when a fault occurs. When a fault occurs, the circuit number and alarm conditions are on the operator interface. Refer to the Troubleshooting section when determining the cause and remedy of the fault. Chiller Compressor Fault If there is a fault in the compressor protection motor module, it will cause the chiller to shut down immediately. Causes for this fault are such things as a reversal of 3-phase rotation, a phase failure, a high motor winding temperature, or a high oil temperature. An approximate motor winding temperature of 212 F (100 C) and/or an oil/discharge temperature of 251 F (122 C) will cause a fault. If three repeated phase failures occur within 18 minutes or any other fault listed above occurs, the module will lock out and will require manual reset by turning off the power for 5 seconds. 45

50 The module will not reset if the compressor has not cooled. Once the module is reset and the compressor anti cycle timer has expired, the chiller will restart. The compressor protection motor module is located within the compressor terminal box. Chiller Compressor High Pressure Fault The discharge pressure is higher than the refrigerant high-pressure switch trip point. The high-pressure switch opens at 260 psig (1792 kpa) and closes at 200 psig (1379 kpa). The switch requires a manual reset. If a compressor high pressure fault occurs while the chiller is running, the chiller will shut down and only restart once the discharge pressure switch is reset, the fault is reset via the HMI, and the compressor anti cycle timer has expired. The high-pressure switch is at the compressor discharge on the body of the compressor. Chiller Compressor Low Pressure Fault The compressor suction pressure is lower than the trip point. This setting is 0 psig (0 kpa). This setting is not adjustable and shuts down the chiller immediately. If a compressor low suction pressure fault occurs while the chiller is running, the chiller will shut down and only restart once the fault is reset via the HMI, and the compressor anti cycle timer has expired. A pressure transducer mounted at the compressor suction provides the PLC with the refrigerant suction pressure. Chiller Crankcase Oil Level Low Fault The oil level in the compressor is below the minimum level and the oil level switch has opened. The oil should be visible within the sight glass at all times while the compressor is running. If a low oil level fault occurs while the chiller is running, the chiller will shut down and only restart once the level switch is closed, the fault is reset via the HMI, and the compressor anti cycle timer has expired. Chiller Compressor Run Contactor Fault The compressor run contactor fails to pull in while the compressor run signal from the PLC is active. The chiller will shut down and will only restart once the fault is reset via the HMI, and the compressor anti cycle timer has expired. Chiller Compressor Run Contactor Overload The current draw in the compressor motor part winding has exceeded the overload setting. The overload setting is factory set according to the electrical schematic for the particular chiller model. The overload once tripped, requires a manual reset. The chiller will shutdown if this fault occurs and will only restart once the overload is reset, the fault is reset via the HMI, and the compressor anti cycle timer has expired. Chiller Compressor Start Contactor Fault The compressor start contactor fails to pull in while the compressor run signal from the PLC is active. The chiller will shut down and will only restart once the fault is reset via the HMI, and the compressor anti cycle timer has expired. Chiller Compressor Start Contactor Overload The current draw in the compressor motor part winding has exceeded the overload setting. The overload setting is factory set according to the electrical schematic for the particular chiller model. The overload once tripped, requires a manual reset. The chiller will shutdown if this fault occurs and will only restart once the overload is reset, the fault is reset via the HMI, and the compressor anti cycle timer has expired. Chiller E-Stop Pressed or MCR Off If the E-stop is pressed, the chiller will shut down immediately and disables all the outputs including any remote enabled pump contacts. The chiller restarts when the E-stop button is depressed, the fault is reset via the HMI, and the compressor anti cycle timer has expired. Chiller Flow Switch Fault There is not adequate chilled water flow through the evaporator in order to close the flow switch. The chilled water flow must be present in order for the chiller to run. If a no flow fault occurs while the chiller is running, the chiller will shut down and only restart once the chilled water flow is reestablished, the fault is reset via the HMI, and the compressor anti cycle timer has expired. The chilled water flow switch is in the chilled water piping leaving the evaporator. 46

51 Chiller Freezestat Fault The temperature at the outlet of the evaporator is lower than the freezestat setting. The freezestat setting is adjustable within the chiller setup screen. This setting should be set for 10 F (5.6 C) higher than the freezing point of the chilled water. If a freezestat fault occurs while the chiller is running, the chiller will shut down and only restart once the chilled water temperature rises above the freezestat set point, the fault is reset via the HMI, and the compressor anti cycle timer has expired. This fault will not shutdown external pumps if enabled and controlled by the chiller PLC. A thermocouple sensor mounted in the chilled water piping leaving the evaporator serves to provide the leaving evaporator water temperature to the PLC. Chiller Glycol Warning The process supply set point is set to 40 F (4.4 C) or below, requiring glycol for freeze protection. See Table 11 - Recommended Glycol Solutions for recommended glycol solutions for the set point temperature desired. This alarm will not cause chiller to shutdown. Chiller High Superheat Alarm The compressor gas suction superheat is higher than 20 F (11.1 C) for more than 30 minutes while the EEV is operating in superheat mode. This setting is not adjustable. The chiller will not shutdown due to this alarm, but may lead to additional problems if the source of the problem is not addressed. The superheat is a calculated value based on the inputs of the compressor suction temperature sensor and the compressor suction pressure transducer. Chiller Leaving Water High Temperature Alarm The supply water is greater than the alarm set point. This setting is adjustable within the chiller setup screen and is factory set at 100 F (37.8 C). If the leaving chilled water temperature rises above the set point, an alarm message will display along with an additional pop up window. The additional window will show the current leaving temperature, the shutdown temperature, which is 5 F (2.8 C) above set point, and the time remaining until shutdown. If the option to override the alarm for 30 minutes is not taken, the chiller will shut down once the leaving water temperature rises 5 F (2.8 C) above the set point. Selecting to override the alarm will ignore the high temperature alarm for 30 minutes. If the temperature cools below the set point, the warning will disappear. If the temperature remains above the shutdown temperature after 30 minutes, the chiller will shutdown. The chiller can restart only if the follow occur; the alarm is reset using the HMI, the temperature is below the shutdown temperature or if it is overridden for 30 minutes, and the compressor anti cycle timer has expired. Restart once the chilled water temperature rises above the freezestat set point, the fault is reset via the HMI, and the compressor anti cycle timer has expired. A thermocouple sensor mounted in the chilled water piping leaving the evaporator serves to provide the leaving water temperature to the PLC if a local temperature sensor is selected within the system options screen. A remote sensor if otherwise selected will provide the PLC with the leaving water temperature. Chiller Low Superheat Fault The compressor gas suction superheat is lower than 3 F (1.7 C) for more than 30 seconds. This setting is not adjustable and will shutdown the chiller if this fault occurs. The chiller will restart once the fault is reset via the HMI, and the compressor anti cycle timer has expired. The superheat is a calculated value based on the inputs of the compressor suction temperature sensor and the compressor suction pressure transducer. Chiller Open Pressure Transducer Fault The discharge or suction pressure transducer has failed or the wiring is open. The chiller will shutdown if a transducer failure occurs and will not restart until the transducer is reading within the normal operation range, the fault has been reset within the HMI, and the compressor anti cycle timer has expired. Chiller Refrigerant High Pressure Fault The discharge pressure is higher than the refrigerant high-pressure trip point. This setting is adjustable within the chiller setup screen. If a refrigerant high pressure fault occurs while the chiller is running, the chiller will shut down and only restart once the discharge pressure falls below the set point, the fault is reset via the HMI, and the compressor anti cycle timer has expired. A pressure transducer mounted at the compressor discharge provides the PLC with the refrigerant discharge pressure. Chiller Refrigerant Low Pressure Fault The suction refrigerant pressure is lower than the refrigerant low-pressure tip point. This setting is 4 psig (27.6 kpa) and is ignored the first 5 minutes after the compressor starts. There is a two-minute time delay from then on. This setting is not adjustable. If a refrigerant low pressure fault occurs while the chiller is running, the chiller will shut down and only restart 47

52 once the fault is reset via the HMI, and the compressor anti cycle timer has expired. A pressure transducer mounted at the compressor suction provides the PLC with the refrigerant suction pressure. Chiller TC Module Slot 1 Ch.(X) Alarm The thermocouple is bad or open. This alarm does not shutdown the chiller unless it occurs on the Process Supply control thermocouple. A bad thermocouple will display 0 F (-17.8 C) on the HMI. A list of thermocouple channels and their description is below. Channel #0 - Process Return Channel #1 - Compressor Discharge Channel #2 - Condenser Water In (MXW models) Channel #3 - Condenser Water Out (MXW models) Channel #4 Process Supply or Evaporator Out Channel #5 Compressor Suction Condenser Fan VFD Alarm The remote condenser fan VFD has experienced a fault. An alarm message is on the HMI, but the chiller will not shutdown when this alarm occurs. Address this alarm quickly as failure of the VFD may cause other faults. The lead fan(s) on the condenser are the only fans equipped with a VFD. Maximum Differential Pressure The differential between the discharge and suction pressures is more than 225 psig (1551 kpa) for more than 5 seconds. This setting is not adjustable. If a maximum differential pressure fault occurs while the chiller is running, the chiller will shut down and only restart once the differential pressure falls below the set point, the fault is reset via the HMI, and the compressor anti cycle timer has expired. Pressure transducers mounted at the compressor suction and discharge provide the PLC with the refrigerant suction and discharge pressures. Minimum Differential Pressure The differential between the discharge and suction pressures is less than 50 psig (345 kpa) for more than 150 seconds. This setting is not adjustable. If a minimum differential pressure fault occurs while the chiller is running, the chiller will shut down and only restart once the fault is reset via the HMI and the compressor anti cycle timer has expired. Pressure transducers mounted at the compressor suction and discharge provide the PLC with the refrigerant suction and discharge pressures. PLC Battery Low The PLC battery is low and needs replacing. See maintenance instructions. Power Phase Fault The incoming power is incorrectly phased. Check the phasing with a phase sequence meter prior to applying power. See Startup procedures earlier in this manual. The power phase monitor is within the main control panel. WARNING: It is imperative that L1-L2-L3 are connected in the A-B-C phase sequence to prevent equipment damage due to reverse rotation. Remote Temperature Sensor Fault The remote temperature sensor has failed or the wiring is open. The chiller will shutdown if a sensor failure occurs and will not restart until the sensor is reading within the normal operation range, the fault has been reset within the HMI, and the compressor anti cycle timer has expired. This sensor is a remote sensor used as the control input for the PLC if the remote sensor is selected within the system options screen. 48

53 Control Sequence The MX chillers use variable capacity control. The compressors are equipped with a slide valve that provides variable capacity control from %. The slide valve provides infinite capacity control by directly controlling the amount of refrigerant gas that is taken in by the compressor rotors. The amount of gas taken in depends on the valve position. The male loader and unloader solenoid valves control the slide valve position. Energizing the male loader and de-energizing the male unloaderloads the compressor. De-energizing the male loader and energizing the male unloader unloads the compressor. These valves are pulsed in short time increments to balance compressor capacity with the chiller load. The chiller PLC accomplishes this by using a PID control algorithm with the supply temperature as the process variable. The compressors have a minimum start to start recycle time of ten minutes. For example, if the compressor has run for ten minutes and cycles down on normal temperature control, then it may restart immediately. If the compressor has run for six minutes, then it will be off for a minimum of four minutes before a restart may occur. Startup and Running Sequence If the chiller circuit(s) is enabled and all the safeties are met, pressing the start button on the HMI overview screen will ready the chiller for cooling as required. When there is a demand for cooling, chilled water is greater than the chilled water set point, and the recycle timer has expired, the system will begin its Startup process. Any process water pumps, if controlled by the PLC, will start first. The condenser water-regulating valve and then the electronic expansion valve for the lead chiller circuit will open to a predefined position over a predefined time. The liquid line solenoid valve will open and the compressor will start. The compressor will run unloaded for approximately two minutes. After two minutes, the compressor will load/unload as required to maintain the chilled water set point. If additional compressors are needed to provide the required cooling capacity, they will start in same sequence as listed above and then load/unload as needed according to Table 10 System Compressor Staging. If the process load falls below the minimum cooling capacity of one compressor, the compressor will cycle on and off according to differential temperatures setup within the Systems Options screen. The system will remain on until an initiated shutdown sequence occurs or a system fault. If a system fault occurs, the compressor affected by the fault will shut down immediately. Shutdown Sequence The unit will run through a controlled shutdown sequence if demand decreases and the compressor shuts off or the stop button is pressed on the HMI overview screen. The stop button will shut off all running compressors. During this sequence, the compressors will run unloaded for approximately 30 seconds and then one compressor at a time will shut off with a two-second time delay between compressors. When the compressor(s) stop, the liquid line solenoid valve(s), condenser water regulating valve(s), and electronic expansion valve(s) will close. The unloader solenoid valve(s) will stay enabled for approximately two minutes once the compressor shuts off. The MX chiller does not require a pump down sequence due the nature of its design. The system is now ready to begin the next Startup sequence. If a safety fault occurs on a particular circuit, that circuit will stop immediately. WARNING: The E-Stop button will stop the chiller immediately. A controlled shutdown sequence will not occur. 49

54 Table 10 System Compressor Staging System Compressor Staging 4 Compressors % Compressor Compressor 2 Off Off Compressor 3 Off Off Off Compressor 4 Off Off Off Off Compressors % Compressor Compressor 2 Off Off Compressor 3 Off Off Off Compressors % Compressor Compressor 2 Off Off Compressors 0 25% Compressor System % Demand Compressor % Staging Initial Startup Full testing of MXW chillers occurs prior to shipping. Readings of voltage, amperage, compressor suction and discharge pressures, water inlet and outlet temperatures, water flow rates, etc., are recorded to make sure that all system components are performing up to their specifications. Since the remote condenser ships separately and a full system design is not possible, electrical testing only occurs for MXR chillers prior to shipping. Every unit is factory set to deliver chilled water in accordance with the standard operating specifications for that particular chiller. Due to variables involved with different applications and different installations, minor adjustments may be required during the initial Startup to ensure proper operation. We recommend a qualified experience refrigeration technician perform the start-up in proper sequence. If trouble occurs while putting a chiller in operation, the fault is usually one of the control or safety devices. Use this outline as a checklist for the initial Startup and for subsequent Startups after the chiller is out of service for a prolonged period. 1. Connect the main power source properly, make sure it matches the voltage shown on the nameplate of the unit, and that it is within the voltage utilization range given in Table 5 Chiller Electrical Data (60 Hz). a. Check the electrical phase sequence at installation and prior to Startup. Operation of the compressor with incorrect electrical phase sequencing will result in mechanical damage to the compressors. Check the phasing with a phase sequence meter prior to applying power. The proper sequence should read ABC on the meter. If the meter reads CBA, open the main power disconnect and switch two line leads on the line power terminal blocks (or the unit mounted disconnect). All components requiring electric power are in-phase at the factory. Do not interchange any load leads that are from the unit contactors or the motor terminals. After confirming proper power connection and grounding exist, turn the main power on. WARNING: It is imperative that L1-L2-L3 are connected in the A-B-C phase sequence to prevent equipment damage due to reverse rotation. b. It is also highly recommended to perform a mechanical rotation test in addition to testing power with a phase sequence meter. This may also be performed if a meter is not available. Verify that the compressor discharge valve is fully open. Connect a compound gauge to the compressor suction service valve and close the valve. Then rotate two turns open from fully closed. Bump start the compressor for approximately 0.5 to 1 second. A correct compressor rotation will indicate an immediately drop in suction pressure. A rise in pressure or a cutout of the compressor control module will indicate a wrong direction of rotation. If this happens, open the main power disconnect switch and switch two line leads on the line power terminal blocks (or the unit 50

55 mounted disconnect). All components requiring electric power are in-phase at the factory. Do not interchange any load leads that are from the unit contactors or the motor terminals. Note: The main power must be on for 24 hours prior to starting the compressor to allow the crankcase heater to sufficiently vaporize any liquid refrigerant that may be present in the compressor. 2. Check the compressor oil level. The level should be visible in the sight glass. 3. Check to make sure that all of the process chilled water piping connections are secure. Fill the chilled water reservoir with the proper water or water/glycol solution. Use a glycol with a corrosion inhibitor only. See Table 11 - Recommended Glycol Solutions. Table 11 - Recommended Glycol Solutions Chilled Water Temperature Percent Glycol By Volume 50 F (10 C) Not required 45 F (7.2 C) 5 % 40 F (4.4 C) 10 % 35 F (1.7 C) 15 % 30 F (-1.1 C) 20 % 25 F (-3.9 C) 25 % 20 F (-6.7 C) 30 % 15 F (-9.4 C) 35 % 10 F (-12.2 C) 35 % 5 F (-15 C) 40 % 0 F (-17.8 C) 40 % 4. (MXW Models Only) Check the condenser water lines to make sure all connections are secure. Make sure sufficient condenser water flow and pressure are available, the condenser water supply pump is on, and all shut-off valves are open. The electronic water regulating valves are in the closed position from the factory and will open automatically when the circuit is enabled. 5. (MXR Models Only) Check the refrigerant lines to make sure all connections are secure and that a proper evacuation of the chiller field piping and the remote condenser has occured. 6. Charge the chiller with refrigerant. For MXR chillers, please refer to the MXR Series Chiller Remote Air-Cooled Condenser Installation Guidelines Manual to determine the required refrigerant charge. MXW chillers come factory charged and should require no additional refrigerant. 7. (MXR Models Only) Check the remote condenser main power and control wiring to ensure all connections are secure. 8. Verify that all refrigerant valves are open. CAUTION: Do not operate the unit with the compressor or liquid line service valves CLOSED. Failure to have these OPEN may cause serious compressor damage. 9. Turn on the control power by pulling the E-Stop button to On. This should illuminate the panel displays. 10. Due to extreme temperatures during shipment the High Refrigerant Pressure switch may have tripped. If this is the case, reset the High Refrigerant Pressure by depressing the manual reset button located on the switch. 11. Make sure the Process Set Point, Freezestat Set Point, Hi Alarm Set point, Discharge Set point, and Refrigerant High Pressure Set Point are set appropriately for the operating conditions of the chiller. The parameters are in the Chiller Setup screen. The freezestat should be set at 10 F (5 C) below the minimum chilled water temperature setting that the chiller operate. Be sure the coolant solution has sufficient freeze protection (glycol) to handle at least 5 F (2.8 C) below the Freezestat setting. All chillers arrive from the factory with the Freezestat set at 40 F (4 C). This is to protect against a possible freeze-up if no glycol is present in the coolant. Once the proper glycol solution is added, the Freezestat can be adjusted to the appropriate setting. Access to this screen is limited by password protection. User password level 1 is required. 51

56 Note: Our warranty does not cover the evaporator from freezing. It is vital that the Freezestat is set properly. 12. Verify that the chiller mode setup selected is Auto. This screen access is password protected. User password level 1 is required. 13. All remaining chiller setup parameters within the Chiller Tuning screen and System Options should be setup or verified. This screen access is password protected. User password level 3 is required. 14. Establish flow through the evaporator(s). Note: The compressors will not start as long as the flow switch is open. Establish a positive flow through the evaporator(s) before the compressor(s) can operate. Set process water flow through the evaporator(s) as indicated in Table 8 - Chilled Water Flow Rate Requirements. If a flow meter is not available, run the chiller fully loaded and balance the flow until a 10 F (6 C) rise is established. A significant increase in flow beyond the recommended rate may damage the evaporators and create excessive pressure drops that influence the overall efficiency of the system. 15. Start System. A compressor will not start until its cycle time has expired, its electronic condenser water regulating valve (CWRV) is open (MXW Models only), its electronic expansion valve is open, its liquid line solenoid valve is open, and its safeties are met. The time to complete this is on the HMI screen. Once the compressor starts, it will operate fully unloaded for two minutes. If the demand requires additional loading after the two minutes has expired, the compressor will load accordingly. This sequence is to improve the compressor s liquid refrigerant handling capability during Startup. WARNING: During normal operation, enable all circuits. Failure to heed this warning may lead to evaporator freeze-up. If a circuit needs to be shutdown, shut off the water to that circuit s evaporator. WARNING: Under no circumstance, deactivate the High Refrigerant Pressure switch. Failure to heed this warning can cause serious compressor damage, severe personal injury, or death. 16. The chiller controls to the supply chilled water temperature. Unless otherwise specified, it is factory set to deliver coolant at 50 F (10 C) or as changed as directed in step 9. Adjust to the desired operating temperature. Resetting the temperature will change the operating conditions of the chiller. Only lower readjustment of the controller after providing adequate antifreeze protection to the coolant as shown in Table 11 - Recommended Glycol Solutions. 17. Operate the system for approximately 30 minutes. Check the liquid line sight glasses. The refrigerant flow past the sight glasses should be clear. Bubbles in the refrigerant indicate either low refrigerant charge or excessive pressure drop in the liquid line. A shortage of refrigerant is indicated if operating pressures are low and subcooling is low. The normal subcooling range is from 3 F (1.7 C) to 20 F (11 C). If the subcooling is not within this range, check the superheat and adjust if required. The superheat should be approximately 10 F (5.5 C). For MXW chillers, the unit is factory charged so adding or removing refrigerant charge should not be necessary. If the refrigerant pressure, sight glass, superheat, and subcooling readings indicate a refrigerant shortage, gas-charge refrigerant into each circuit, as required. With the unit running, add refrigerant vapor by connecting the charging line to the suction service valve and slowly charging through the backseat port until operating conditions become normal. CAUTION: A clear sight glass alone does not mean that the system is properly charged. Also, check system superheat, subcooling, and unit operating pressures. If both suction and discharge pressures are low but subcooling is normal, a problem other than refrigerant shortage exists. Do not add refrigerant, as this may result in overcharging the circuit. 52

57 Preventive Maintenance Once your chiller is in service, follow the maintenance procedures as closely as possible. Specific site conditions may require repeating certain tasks more frequently. The importance of a properly established preventive maintenance program cannot be overemphasized. Taking the time to follow these simple procedures will result in substantially reduced downtime, reduced repair costs, and an extended useful lifetime for the chiller. Any monetary costs of implementing these procedures will usually more than pay for itself. To make this as simple as possible, prepare a checklist with the recommended service operations and record the record the date and time when performed. At the end of this manual, you will find a checklist for this purpose. Please notice that there are locations for voltage readings, amperages, etc. for monitoring over time. With this information, maintenance personnel may be able to correct a potential problem before it causes any downtime. For best results, take these readings with a full heat load from process, preferably with similar operating conditions each time. The following is a list of suggested periodic maintenance. Once a Week 1. Check to make sure that the To Process temperature is reasonably close to the Set Point temperature. If the temperature stays more than 5 F (3 C) away from the set point, there may be a problem with the chiller. If this is the case, refer to the Troubleshooting Chart or contact our Customer Service Department. 2. Check the suction and discharge refrigerant pressure at the compressor. 3. Check each refrigerant sight glass for air bubbles or moisture indication. Bubbles in the refrigerant indicate either low refrigerant charge or excessive pressure drop in the liquid line. If the sight glass indicates that there is a refrigeration problem, have the unit serviced as soon as possible. 4. Check the compressor oil level in sight glass. View the oil level through the sight glass while the compressor is running. The level will vary as the compressor loads and unloads. Once a Month Repeat items 1 through 4 listed above and continue with the following. 5. Shut off the power disconnect. Check the condition of electrical connections at all contactors, starters, and controls. Check for loose or frayed wires. 6. Check the incoming voltage to make sure it is within 10% of the design voltage for the chiller. 7. Check the amp draws to each leg of the compressor(s) to confirm that it is drawing the proper current. 8. Check the system superheat and subcooling. The normal superheat is 10 F (5.5 C) and should not be more than 20 F (11.1 C). The normal subcooling range is from 3 F (1.6 C) to 20 F (11 C). 9. Check the condition of the compressor discharge check valve. When the compressor shuts off, the compressor should not run backward for more than five seconds. If this occurs and the discharge and suction pressures equalize, replace the check valve. 10. Check the operation of the compressor crankcase heater. Energize the heater while the compressor is off. Taking an amp reading of the heater leads is the best way to determine the correct operation. Another way is to feel if there is localized heat around the crankcase heater when the heater is on. 11. Units are equipped with a Y-strainer between the return connection and the evaporator inlet. Open the blow-down valve attached to the Y-strainer to flush the screen free of debris. If the chilled water contains a heavy concentration of particulates, clean the Y-strainer more regularly. 53

58 Once a Year Repeat items 1 through 11 listed above and continue with the following. 12. Check the condition of the chilled water for algae and particulate fouling. Back flush the evaporator with water or another suitable cleaning agent. The frequency at which this task is required depends on specific site conditions. 13. (MXW Models) Check the condition of the condenser water for algae, scale, and particulate fouling. Rod out the tubes and back flush the condensers. If scaling exists on the condenser tubes, chemical cleaning of the tubes may also be necessary. If a chemical cleaning agent is used, it should be suitable with the internal components composed of copper, steel, and cast iron. The frequency at which this task is required depends on specific site conditions. 14. (MXR Models) Check the condition of the air coils of the remote condensers for dirt and debris. If the coils are dirty or clogged, use a compressed air source to blow the contaminants out of the air coil. The frequency at which this task is required depends on specific site conditions. 15. Have a qualified laboratory perform a compressor oil analysis to determine system moisture content and acid level. Maintenance Installing and Replacing Processor Battery The variable settings in the chiller PLC are stored in memory by a replaceable lithium battery. The lithium battery provides backup for approximately 2 years. A PLC BATTERY LOW Alarm on the operator interface and a red BATTERY LOW LED will alert you when the battery voltage has fallen below a threshold level. Once the BATTERY LOW LED goes on, do not remove processor power or your variable settings will revert to the factory settings. An EEPROM Module backs up the processor program. Replace the battery as soon as possible. You can replace the battery while powering the processor and the chiller is running. For battery, installation or replacements do as follows. 1. Open the door of the processor. 2. If installing a battery in a new processor (battery never installed before), remove the jumper from the battery connector socket. Store the jumper in a safe place for possible future use without the battery. 3. If replacing an old battery, unplug the existing battery connector and remove from the retainer clips. 4. Insert a new or replacement battery in the holder. Make sure the retainer clips hold it in. 5. Plug the battery connector into the socket. 6. Close the processor door. Replacing a Fuse on the Power Supply To replace a fuse on the power supply: 1. Remove power from the power supply. 2. Open the door of the power supply and use a fuse puller to remove the fuse. 3. Install a replacement fuse. WARNING: Use only replacement fuses of the type and rating specified for the unit. Improper fuse selection can result in equipment damage. The exposed pin on the 3-pin jumper is electrically live. Contact with the pin may cause injury to personnel. 54

59 Cleaning the Operator Interface Use of abrasive cleaners or solvents may damage the window. Do not scrub or use brushes. To clean the display window: 1. Disconnect power from the terminal at the power source. 2. Using a clean sponge or a soft cloth, clean the display with a mild soap or detergent. If paint or grease splash is present, remove before drying by rubbing lightly with isopropyl alcohol. Afterward, provide a final wash using a mild soap or detergent solution. Rinse with clean water. 3. Dry the display with a chamois or moist cellulose sponge to avoid water spots. Checking Compressor Oil Level The oil level should be visible in sight glass while the compressor is running. If adding oil, use only approved Polyol Ester oil, or Solest

60 Warranty Information Thermal Care warrants its equipment to be free from defects in material and workmanship when used under recommended operating conditions. Thermal Care s obligation is limited to repair (i.e. rewind a motor) or replacement (not adjustment or maintenance), F.O.B. the factory of any parts supplied by Thermal Care within a period as shown below from the date of shipment to the original purchaser. Model Parts Labor 1 SQ, LQ 18 months 12 months EQ 12 months 12 months EQR, LQR, SQR(remote condensers) 12 months 12 months 2 TCW, TSW, TXW 12 months 12 months TCR, TSR, TXR (remote condensers) 12 months 12 months 2 Optional Compressor Warranty 5 years Chilled Water Systems See note 3 12 months 4 FT or FC Tower Systems See note 3 12 months 4 FT Cooling Tower 12 months (10 years - shell) FC Cooling Tower 5 years (10 years - shell) RA, RB (See Warranty Sheet Form 1-415) All other products 12 months 1 Continental U.S.A., Canada, and Puerto Rico only. 2 Refrigerant and any labor associated with its evacuation or replacement are not covered for remote condenser systems. 3 See individual product listing for parts warranty coverage. 4 The labor warranty covers all equipment purchased at the same time consisting of a minimum of at least one pumping system and one cooling tower and/or chiller. This warranty does not cover the cost of labor during overtime hours (after normal working hours or during weekends and holidays). Any cost differential for overtime labor will be the responsibility of the customer. Thermal Care is not responsible for any sales, use, excise or other applicable taxes associated with the replacement of parts under this warranty. This warranty will be voided when, in Thermal Care s opinion, the equipment and/or system has been subject to misuse, negligence or operation in excess of recommended limits, including freezing, or has been altered, and/or repaired without express factory authorization. If equipment is installed in hostile environments, unless such conditions were specified at the time of purchase; or the serial number has been removed or defaced, this warranty shall not apply. This warranty is not transferable. Under no circumstances shall Thermal Care be liable for loss of prospective or speculative profits, or special, indirect, incidental or consequential damages. Thermal Care must authorize all warranty service prior to work being performed and have a Thermal Care purchase order issued. All defective parts become the property of Thermal Care and must be returned as advised by Thermal Care. Thermal Care neither assumes, nor authorizes any person to assume for it, any liability not expressed in this warranty. There is an implied warranty of merchantability and of fitness for that particular purpose; all other implied warranties, and any liability not based upon contract are hereby disclaimed and excluded by this warranty. This warranty is part of the standard conditions and terms of sale of Thermal Care N. Lehigh Avenue Niles, Illinois Phone: (847) (888) Fax: (847) info@thermalcare.com Customer Service Phone: (847) Fax: (847) Form Effective 4/9/07 56

Installation, Operation and Maintenance Manual. TC Series. Centrifugal Chillers 60 to 180 Tons. Copyright 2009 Thermal Care

Installation, Operation and Maintenance Manual. TC Series. Centrifugal Chillers 60 to 180 Tons. Copyright 2009 Thermal Care Installation, Operation and Maintenance Manual TC Series Centrifugal Chillers 60 to 180 Tons Copyright 2009 Thermal Care Table of Contents FOREWORD...1 SAFETY GUIDELINES...1 GENERAL DATA...2 Table 1 Water

More information

PORTABLE AND REMOTE CONDENSER CHILLERS

PORTABLE AND REMOTE CONDENSER CHILLERS PORTABLE AND REMOTE CONDENSER CHILLERS Model NQ INSTRUCTION MANUAL November 2016 IMS Company 10373 Stafford Road Chagrin Falls, OH 44023-5296 Copyright 2013 IMS Company. All rights reserved. Telephone:

More information

EQ Series Portable Chillers

EQ Series Portable Chillers EQ Series Portable Chillers Installation, Operation and Maintenance Manual Copyright Thermal Care Inc. 2010 Table of Contents Foreword... 1 Installation... 1 Receiving Inspection... 1 Rigging, Handling,

More information

Hydra Negative Pressure, Closed-Loop Mold Temperature Controllers INSTRUCTION MANUAL

Hydra Negative Pressure, Closed-Loop Mold Temperature Controllers INSTRUCTION MANUAL Hydra Negative Pressure, Closed-Loop Mold Temperature Controllers INSTRUCTION MANUAL July 2012 IMS Company 10373 Stafford Road Chagrin Falls, OH 44023-5296 Telephone: (440) 543-1615 Fax: (440) 543-1069

More information

Installation, Operation and Maintenance Manual. TS Series. Scroll Central Chillers 20 to 100 Tons. Copyright Thermal Care Inc.

Installation, Operation and Maintenance Manual. TS Series. Scroll Central Chillers 20 to 100 Tons. Copyright Thermal Care Inc. Installation, Operation and Maintenance Manual TS Series Scroll Central Chillers 20 to 100 Tons Copyright Thermal Care Inc. Table of Contents Foreword... 1 Installation... 1 Receiving Inspection... 1 Rigging,

More information

EP2 Series Portable Chillers

EP2 Series Portable Chillers USER GUIDE UGH041-0317 www.conairgroup.com EP2 Series Portable Chillers Portable and Remote Condenser Chillers 4 to 43 tons 2 Thank you for purchasing Conair equipment. This manual is addressed to operators

More information

EP1 Series Portable Chillers

EP1 Series Portable Chillers USER GUIDE UGH036-0613 www.conairgroup.com EP1 Series Portable Chillers Air-Cooled Models EP1A-01, EP1A-02, EP1A-03 Water-Cooled Models EP1W-02, EP1W-03 Remote Condenser Model EP1R-03 Thank you for purchasing

More information

EP1 Series Portable Chillers Air-Cooled Models EP1A-01, EP1A-02, EP1A-03 Water-Cooled Models EP1W-02, EP1W-03 Remote Condenser Model EP1R-03

EP1 Series Portable Chillers Air-Cooled Models EP1A-01, EP1A-02, EP1A-03 Water-Cooled Models EP1W-02, EP1W-03 Remote Condenser Model EP1R-03 USER GUIDE UGH036-1015 www.conairgroup.com EP1 Series Portable Chillers Air-Cooled Models EP1A-01, EP1A-02, EP1A-03 Water-Cooled Models EP1W-02, EP1W-03 Remote Condenser Model EP1R-03 Thank you for purchasing

More information

Installation, Operation and Maintenance Manual. LQ Series. Portable Chillers 7 to 40 Tons

Installation, Operation and Maintenance Manual. LQ Series. Portable Chillers 7 to 40 Tons Installation, Operation and Maintenance Manual LQ Series Portable Chillers 7 to 40 Tons Copyright Thermal Care Inc. 2011 Page intentionally blank Table of Contents Foreword... 1 Installation... 1 Receiving

More information

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers Installation, Operation and Maintenance Manual LQ Series Portable Chillers Table of Contents Foreword... 1 Installation... 1 Receiving Inspection... 1 Rigging, Handling, and Locating Equipment... 1 Electrical

More information

Installation, Operation and Maintenance Manual. RQ Series. Mold Temperature Control Units 0.75 to 7.5 hp and 0 to 24 kw

Installation, Operation and Maintenance Manual. RQ Series. Mold Temperature Control Units 0.75 to 7.5 hp and 0 to 24 kw Installation, Operation and Maintenance Manual RQ Series Mold Temperature Control Units 0.75 to 7.5 hp and 0 to 24 kw Copyright 2010 Thermal Care Inc. Table of Contents Foreward... 3 Safety Guidelines...

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

RECORD SUBMITTAL COVER SHEET

RECORD SUBMITTAL COVER SHEET RECORD SUBMITTAL COVER SHEET PROJECT TITLE: AXCELLERATE PHARMA EQUIPMENT DESCRIPTION: CARRIER AQUASNAP AIR-COOLED CHILLER CH-1 OWNER: AXCELLERATE PHARMA MECHANICAL ENGINEER: ARDEN DATE: JUNE 27, 2014 SUBMITTED

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

Installation Instructions

Installation Instructions 30GTN015-035 Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION.................................1-11

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F Temperature Control Units Water & Oil - F Portable Chillers Air & Water-Cooled - 7 F Central Chillers Air & Water-Cooled Packages & Modules - 7 F Pump Tank Stations Chilled or Tower Water - gallons Cooling

More information

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES 60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

Installation Instructions

Installation Instructions AQUAFORCE 30XW150-400 Water-Cooled Liquid Chillers Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................1,2 System Design...................................

More information

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE I.O.M. #123 updated 03/28/2016 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE Covering models From 5 to 40 tons With M1 Instruments & Scroll Compressors Model: Serial Number : 525 East Stop 18 Road

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE Master Rack Compressor Sequencer 7/21/2017 1 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PARALLEL RACK NOMENCLATURE...

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

CHILLER. Operator s & Installation Manual

CHILLER. Operator s & Installation Manual CHILLER MODELS: CH1001-A Operator s & Installation Manual Release Date: August 9, 2002 Publication Number: 620914301 Revision Date: May 6, 2010 Revision: E Visit the IMI Cornelius web site at www.cornelius.com

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet The following information must be completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Date of Installation:

More information

Aquatherm Series Temperature Controllers. Installation, Operation and Maintenance Manual

Aquatherm Series Temperature Controllers. Installation, Operation and Maintenance Manual Aquatherm Series Temperature Controllers Installation, Operation and Maintenance Manual Table of Contents FOREWORD... 1 INSTALLATION... 1 Receiving Inspection... 1 Rigging, Handling, and Locating Equipment...

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, Operation and Maintenance Manual IOMM WGZ-1 Group: Chiller Part Number: 330389301 Effective: October 2004 Supercedes: IOMM WGZ Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 100AW,

More information

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE I.O.M. #023 10/96 updated 10/19/2017 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE Covering Models From 20-180 Tons Air & Water Cooled Model: Serial Number : 525 East Stop 18 Road Greenwood, IN

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

SYSTEM DESIGN REQUIREMENTS

SYSTEM DESIGN REQUIREMENTS P a g e 1 SYSTEM DESIGN REQUIREMENTS WFC-S SERIES WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLERS / CHILLER-HEATERS Yazaki WFC-S Series water-fired chillers and chiller-heaters are available with nominal

More information

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons Product Data 07DA, DB 07EA, EB, ED Condensing Units 3 to 40 Nominal Tons 06D, 06E Compressors An excellent choice for your built-up system Carrier 07 Series condensing units built for the engineer who

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

Packaged Air-Cooled Water Chiller

Packaged Air-Cooled Water Chiller Installation, Operation and Maintenance Manual IOMM ALR-3 Group: Chiller Part Number: 330145710 Effective: September 2001 Supersedes: IM ALR-2 Packaged Air-Cooled Water Chiller ALR 110F - ALR 150F Refrigerant

More information

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Product Data Catalog Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Variable Speed Total Access Modules MS010W, MS020W, MS030W, MS050W MS010V, MS020V,

More information

Precise Temperature Control; Compact Footprint

Precise Temperature Control; Compact Footprint Precise Temperature Control; Compact Footprint The Conair EP1 Series Portable Chillers are designed for 1 to 3 ton applications. Available as air-cooled or water-cooled, with pump sizes from 1/4 to 3 Hp

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Liebert CRV Warranty Inspection Check Sheet

Liebert CRV Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Date of Installation

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Surna 25-Ton Chiller Operating & Maintenance Manual

Surna 25-Ton Chiller Operating & Maintenance Manual www.surna.com 303.993.5271 Surna 25-Ton Chiller Operating & Maintenance Manual Models: 300F3-3. 300F4-3, 300FW-3 Revised: July 2015 Table of Contents Warranty Information 4 Limited Warranty 4 Limitation

More information

Central Chillers TS Series

Central Chillers TS Series www.thermalcare.com Central Chillers TS Series With over 40 years of process cooling experience, Thermal Care is the dependable choice for industrial process chillers. Our TS Series is just one of several

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

Installation Instructions

Installation Instructions . AquaSnap 30MPA,MPW015-071 Liquid Chillers with Scroll Compressors and ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page GENERAL........................................ 1 SAFETY CONSIDERATIONS.....................1,2

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

NQ Series Portable Chillers

NQ Series Portable Chillers NQ Series Portable Chillers Electrical Components Mounted and Wired All electrical components and sensors are mounted, wired, and fully tested at the factory to reduce installation time and ensure the

More information

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE I.O.M. #075 updated 11/01/2016 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE Covering models From 5 to 40 tons With CF Instruments & Scroll Compressors Model: Serial Number : 525 East Stop 18 Road

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 1 Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION...

More information

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Product Data. Features/Benefits. 19XB Positive Pressure Storage System Product Data 19XB Positive Pressure Storage System 19XB028 Copyright 1992 Carrier Corporation 19XB052 Carrier s Positive Pressure Storage (PPS) System ensures the critical conservation of refrigerants

More information

Submittal. Date: September 04, Customer P.O. Number: Customer Project Number:

Submittal. Date: September 04, Customer P.O. Number: Customer Project Number: Submittal Prepared For: All Bidders Sold To: Date: September 04, 2012 Customer P.O. Number: Customer Project Number: Job Number: Job Name: DCS 12473 80 Ton Chiller Dept of Wildlife 1801 N Lincoln OKLAHOMA

More information

Rev B, 9/2/2009. Kodiak Chiller Overview

Rev B, 9/2/2009. Kodiak Chiller Overview 930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part

More information

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated.

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated. NOMENCLATURE INTRODUCTION The HTT HWDX water-cooled chillers range is the latest addition to HTT s growing family of commercial products, featuring the most current technologies advances. The HWDX main

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R Products That Perform...By People Who Care FORM NO: MS0455A WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R134a HXWC SERIES 205 to 560 Tons 60Hz INTRODUCTION Dunham-Bush's HXWC water cooled

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Packaged Chiller Models CC 6601, 6501, 6401, 6301, 6201, 6101 For Service, please contact Pfannenberg Service Company: U.S.A. Pfannenberg Inc. 68 Ward Road.

More information

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons Models A and later Design Sequence CTA 090A***A 60 HZ 120A***A 60 HZ 120B***A 60 HZ 180B***A 60 HZ SS-SVN11A-EN

More information

Installation Instructions

Installation Instructions 8GXM / 0GXM Multi---Split High---Wall Duct Free Split System 8GXM --- Size 18k, k, and 0k 0GXM --- Size 9k, 1k, and 18k Installation Instructions NOTE: Read the entire instruction manual before starting

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS ORTEC Compressed Air, Gas & Fluid Technologies HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS Energy Lean Planet Green Cycling and Non-Cycling Design Energy Efficient s Fluctuating and Intermittent Loads Capacity,0

More information

SA Series Startup Form

SA Series Startup Form SA Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance / 015-060 Air-cooled scroll chillers and heat pumps 43-164 kw CG-SVX027B-GB Original instructions Table of Contents General Information...4 Model Number Description...6

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Indoor liquid chiller with integrated hydraulic module Water-cooled: CGWN 205-206 - 207-208 - 209-210 - 211-212 -213-214 - 215 Condenserless: CCUN 205-206 - 207-208 -

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, and Maintenance Manual IMM WGZ-2 Group: Chiller Part Number: 331374401 Effective: October 2005 Supercedes: IOMM WGZ-1 Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 120AW, Packaged

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

Installation & Operation Manual Models: TSU

Installation & Operation Manual Models: TSU TSU-I-O Rev A Installation & Operation Manual Models: TSU 150-940 CAUTION: This appliance is not intended for potable water. This manual must only be used by a qualified heating installer / service technician.

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

IM Installation and Maintenance Manual. Templifier Heat Recovery Water Heaters

IM Installation and Maintenance Manual. Templifier Heat Recovery Water Heaters Installation and Maintenance Manual Templifier Heat Recovery Water Heaters IM 1137-4 Group: Chiller Part Number: IM1137-4 Date: June 2018 Supersedes: July 2017 Model TGZ, B Vintage 600 to 3100 MBH HFC-134a

More information

NOTE: Special care should be given to those areas where these symbols appear.

NOTE: Special care should be given to those areas where these symbols appear. CONGRATULATIONS ON THE SELECTION OF A DATA AIRE PRECISION ENVIRONMENTAL CONTROL SYSTEM. PROPER INSTALLATION, OPERATION AND MAINTENANCE OF THIS EQUIPMENT WILL ENSURE YEARS OF OPTIMAL PERFORMANCE. There

More information

R E D I C O N T R O L S

R E D I C O N T R O L S R E D I C O N T R O L S File Literature Number 1144-01-1 Installation Operation & Maintenance Manual CONTINUOUS REFRIGERANT DEHYDRATOR Model: CD-120 For use with Refrigerants R-11, R-123, R-12, R-22, R-134a

More information

WCOX B Water-Cooled Packaged Chillers with Helical Rotary Compressors

WCOX B Water-Cooled Packaged Chillers with Helical Rotary Compressors WCOX056-07B Water-Cooled Packaged Chillers with Helical Rotary Compressors Installation, Operation, and Maintenance Instructions TABLE OF CONTENTS PAGE. GENERAL INFORMATION...2. Receiving and Inspection...

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

Installation Instructions

Installation Instructions Installation Instructions Part No. 30RA-900---057 and 30RA-900---060 30RAP010-150 Remote Cooler Mounting Accessory SAFETY CONSIDERATIONS Installation of this accessory can be hazardous due to system pressures,

More information

Large Ceiling Systems

Large Ceiling Systems Large Ceiling Systems Installation, Operation & Maintenance Manual Air, Water and Glycol Cooled DX and Chilled Water 6, 8, 10 and 13 ton Data Aire, Inc. 230 W. BlueRidge Avenue Orange, CA 92865 www.dataaire.com

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information