SKY-COM HI-CAP SERIES. Precise Environmental Control SKY-COM 15 & 20 TON Series. Suited for Telecommunications, Laboratories and Computer Rooms

Size: px
Start display at page:

Download "SKY-COM HI-CAP SERIES. Precise Environmental Control SKY-COM 15 & 20 TON Series. Suited for Telecommunications, Laboratories and Computer Rooms"

Transcription

1 SKY-COM HI-CAP SERIES Precise Environmental Control SKY-COM 15 & 20 TON Series Suited for Telecommunications, Laboratories and Computer Rooms

2 GENERAL MECHANICAL SPECIFICATIONS AIRFLOW CONFIGURATION Units are available in a variety of airflow configurations to suit a wide variety of applications. Basic airflow arrangement may be either upflow or downflow. Downflow models are designed for free air return through the top of the unit, with either ducted or free discharge through the bottom of the unit. Upflow models may be free return via the standard front return air grille, or through the bottom return air access. Alternatively, the return air may be ducted into the rear of the unit. The upflow unit discharge can be ducted from the top of the unit, or optional plenums may be ordered for free discharge into the conditioned space. FRAME AND CABINET The structural frame of the unit is constructed of heavy gauge welded steel tube and formed steel sections. The frame is powder coated after assembly for maximum corrosion protection. All external panels are removable for total service access. The electrical compartment and compressor/piping access panels may be removed for service and monitoring without interrupting unit operation. Panels are retained with quick-opening captive fasteners. The steel panels include 1 inch thick, 1-1/2 pound insulation to ensure quiet operation. All exterior panels are powder coated to provide maximum durability and appearance. FAN AND MOTOR The high capacity fan assembly features two forward curved, double width, double inlet centrifugal blowers with selfaligning and lifetime lubricated ball bearings. The fans are selected to provide system airflow at low RPM, enhancing quiet operation. The fan assembly is employed in a drawthrough design to ensure an even airflow pattern across the coil and filter sections. Motors are NEMA T-frame designs, provided with manual reset overloads mounted in the high voltage control compartment. The motor is mounted on a heavy duty adjustable slide base. Variable pitch drive pulleys allow field adjustment of the system airflow capacity. EVAPORATOR COIL FILTERS All units are provided with deep pleated, 4 inch thick, 30 % efficiency filters (efficiency rating as per ASHRAE Std ). Filters can be quickly and easily changed on all models. Filter access is from the top or both sides on downflow models, and from the right hand side on upflow models. Higher filter efficiencies may be substituted as an option. ELECTRICAL PANEL The user interface for the microprocessor control system is flush mounted on the front of the unit. Access to all control components is through this hinged vertical front panel. The high voltage section is protected by a self-latching inner panel, allowing access to the low voltage circuits without risk to operating personnel. The high voltage section contains all contactors, transformers, overload devices, and terminal connections. Independent overcurrent protection is provided for all internal branch circuits. REFRIGERATION CIRCUITS Dual independent refrigeration circuits include high efficiency 'Scroll' compressors. Scroll compressors provide unmatched efficiency, durability, and reliability. The compressors are mounted on vibration isolators to further enhance their low operating sound levels. Each compressor is protected by a auto-reset internal overload, and external high and low pressure switches. The compressor compartment may be accessed without interrupting system operation. Liquid line sight glasses/moisture indicators are provided for visual inspection of adequate system refrigerant charge, or if moisture has contaminated the system. A high capacity refrigerant filter-drier is installed in each circuit to ensure long term system reliability. Externally equalized thermal expansion valves are installed on both evaporator coil circuits. The valves feature a balanced port design to ensure optimum refrigerant flow modulation through a wide cooling load range. The A-frame direct expansion refrigerant coil features two completely interwoven circuits to ensure that maximum coil surface is active under all load conditions. The coil design features enhanced fin and tube surfaces for maximum heat transfer and efficiency. The large face area result in low air velocity with minimum turbulence. The state-of-the-art coil design results in a consistently high sensible heat ratio, under all operating conditions, which is most desired for applications involving cooling of electronic equipment. The entire coil assembly sits in a corrosion free stainless steel drain pan. The drain outlet connection is conveniently accessible, through the front access panel, for inspection and cleaning. 2

3 SYSTEMS ELECTRIC REHEAT The two-stage electric reheat elements are of an open wire design with low thermal mass for immediate response to system demand. The reheat has sufficient capacity to maintain dry bulb temperatures during the dehumidification cycle. The low watt density grid spans a significant percentage of the air path area, resulting in minimal temperature stratification through the unit. The electric coil wires are supported by ceramic insulating bushings in a rigid steel frame. Overheat protection is provided by a fast acting thermal switch. STEAM HUMIDIFIER An electric steam generating humidifier, with proportional output, injects hygienic vapor directly into the air stream. The humidifier features a disposable cylinder, electronic controls, an auto-flush cycle, and self-diagnostics. Water borne impurities are removed at the electrodes and deposited in the removable cylinder where they are periodically flushed out through the automatic drain sequence. Solid mineral scale sinks to the bottom of the cylinder, which is easily removed and replaced. The control unit provides an indication to advise when cylinder replacement is required. AIR-COOLED SYSTEMS Condenser Outdoor remote condensers feature multiple direct-drive propeller fans with one variable speed fan for low ambient head pressure control. Condensers are selected to provide the required heat rejection for the indoor system. The condenser casing is constructed from heavy gauge galvanized steel. Cabinet is sectioned with individual fan chambers. Coils are constructed of aluminum fins mechanically bonded to copper tubes. Fan motors are individually wired to a weather resistant control panel with weather resistant harnesses. Separate fusing is provided for each motor. The standard head pressure control system features a dual input electronic speed controller which senses the head pressure of both compressor circuits and varies the speed of one fan to maintain consistent condensing pressure. The other fan motors are cycled by pressure actuated switches. This system allows for operation to ambient temperatures as low as 0 F. WATER-COOLED SYSTEMS Condenser High efficiency shell and tube counterflow condensers are solidly mounted within the unit to provide the required heat rejection. Condensers are constructed of enhanced copper inner tubes within a steel outer shell. Pressure controlled water regulating valves are provided to maintain consistent condensing pressures at various water temperatures and flow rates. Three-way regulating valves may be ordered to allow constant water flow through the unit and tower pump circuit. GLYCOL-COOLED SYSTEMS Condenser High efficiency shell and tube counterflow condensers are solidly mounted within the unit to provide the required heat rejection. Condensers are constructed of enhanced copper inner tubes within a steel outer shell. Pressure controlled glycol regulating valves are provided to maintain consistent condensing pressures at various fluid temperatures and flow rates. These three-way regulating valves allow constant glycol flow through the unit and dry-cooler, to prevent dead-heading of the pump circuit. Glycol Dry-cooler Outdoor glycol dry-coolers feature multiple direct-drive propeller fans. The dry-cooler casing is constructed from heavy gauge galvanized steel. The cabinet is sectioned with individual fan chambers. Coils are constructed of aluminum fins mechanically bonded to copper tubes. Fan motors are individually wired to a weather resistant control panel with weather resistant harnesses. Separate fusing is provided for each motor. Dry-cooler capacity is controlled by fan cycling. CHILLED WATER SYSTEMS A - Frame Chilled Water Coil The multi-circuited chilled water coil is designed for maximum fluid heat transfer, at low water pressure drop. The entire coil surface is active under all cooling conditions, resulting in maximum dehumidification capacity. The entire coil assembly sits in a corrosion free stainless steel drain pan. Chilled Water Control Valve The fully modulating valve is throttled in response to the cooling ramp output signal from the microprocessor control system. Cooling output is proportional to setpoint deviation. The valve features a direct coupled actuator with no external linkages to adjust. The valve configuration may be either 3- way (standard) or 2-way, as required by the circulating water loop arrangement. 3

4 SYSTEM OPTIONS & ACCESSORIES SYSTEM OPTIONS AIR-COOLED SYSTEMS Refrigerant Head Pressure Control The outdoor air-cooled condenser may be outfitted with a liquid flooding system to maintain consistent condensing pressures under extreme low ambient conditions. The system includes heated and insulated receivers, check valves, and three-way head pressure control valves. This package allows system startup and operation at ambient temperatures to -30F. WATER/GLYCOL-COOLED SYSTEMS Hot Gas Reheat The heat reclaim coil is suspended below the A-frame evaporator. Hot discharge gas is routed through the reclaim coil to provide the first stage of reheat. Water-cooled units include an additional supplemental electric coil, employed to ensure sufficient reheat capacity to offset the compressor capacity during dehumidification. The hot gas reheat circuit includes a one row reclaim coil and a three-way solenoid operated valve. (This option not available on upflow units) Free-cooling Option An auxiliary chilled water coil is located upstream of the DX evaporator coil and piped in series with the refrigerant condensers. Depending on the entering fluid temperature this coil can provide partial or full cooling capacity, equal to the mechanical refrigeration system output. The microprocessor control system monitors the entering fluid temperature versus the room temperature to determine sufficient differential for free-cooling. A motorized three-way valve diverts fluid flow to the auxiliary coil. In order to allow full fluid flow through the unit at all times, three-way regulating valves are provided on the refrigerant condensers. The Deluxe Microprocessor Control must be ordered with this option. High Pressure Water Circuit The standard 150 psig condenser water circuit rating may be increased with the option of two-way, 230 psig or 350 psig rated water regulating valves. The coaxial condenser is rated for maximum working pressure of 400 psig on the fluid side. ACCESSORIES Unit Mounted Disconnect Switch A panel mounted non-fused disconnect is installed in the line voltage section of the electrical panel. This rotary action selector handle is mounted through the external front electrical access panel. The switch mechanism prevents opening of the panel unless the selector is in the 'OFF' position. (A hidden interlock bypass is provided to allow access by qualified personnel.) Hot Gas Bypass Bypass regulators are provided on both compressor circuits. Hot gas from the compressor discharge is diverted to the evaporator coil inlet, to maintain evaporator pressure at a preset minimum. The resulting reduction in cooling capacity allows extended compressor operation at minimal loads. Hydronic Reheat Hot water or steam reheat coils are factory installed and piped in all downflow models (upflow models - coils are mounted in discharge plenum; shipped loose). Control is by a modulating output signal from the microprocessor, to a motorized two-way valve. The reheat coil capacity is selected with sufficient output to maintain space temperatures during the dehumidification process. Upflow Discharge Plenum Discharge plenums are available in standard heights of 20", 24", and 36". Plenums are fully insulated with front mounted, double deflection discharge grilles. High Efficiency Filters The standard 30% efficient filters may be upgraded to 4 inch thick 60-65% or 80-85% efficient filters. Condensate Pump A high temperature condensate pump is factory mounted in the unit (Upflow models only - Downflow models; pump ships loose for field mounting under the floor). Condensate pump is complete with high capacity sump, factory wired motor, and automatic control. Water Detectors Single point water detectors provide indication of fluid leakage from the unit or associated piping. The detectors alert the microprocessor of the presence of water, which signals a visual and audible alarm. Multiple detectors may be connected in parallel to the alarm inputs. Floorstand Floorstands are adjustable + 2 inches. The floorstand allows installation and connection of the unit independent of the raised floor structure. 4

5 CONTROLS STANDARD MICROPROCESSOR CONTROLS The standard electronic control provides for the complete management of precision air-conditioners. The control is flush mounted in the unit, with a front LCD display and five programming keys for operator interface. The control system allows selection and programming of temperature and humidity setpoints, alarm parameters, and operating configuration. Multi-level passwords are required to make changes to the system setup and configuration parameters. CONTROL FEATURES Control Type: The user shall be able to select the type of control regulation that the microprocessor will use. Selection will be either proportional or proportional plus integral (P+I). If P+I is selected, the user shall be able to set the integration time constant. Compressor Short-Cycle Control: The control system includes time constants for compressor minimum on-time and minimum off-time. Compressor Rotation: Compressor run times are automatically equalized to maximize operating life. Sequential Load Activation: During start-up the microprocessor sequences operational loads to minimize inrush current. Auto Restart: The system will automatically restart after a power interruption. Time delay on restart is adjustable. Data Collection: The microprocessor shall maintain accumulative operating hours of all rotating components (fan motor and compressor motors). In the event of an alarm condition the alarm code, hour, minute and date are recorded, up to a maximum of 300 signals. Data logs are protected by a battery back-up in the event of power failure. ALARM FUNCTIONS The control system monitors unit operation and activates an audible and visual alarm upon occurrence of the following conditions: High Temperature Low Temperature High Humidity Low Humidity Humidifier Fault High Head Pressure (C1 or C2) Low Suction Pressure (C1 or C2) Heater Overload (Electric Reheat only) Loss of Airflow Change Filters Loss of Cooling Operating Hours exceeded Water under floor (opt) Operational alarms, that are not safety related, can be programmed for a time delay of 0 to 250 seconds to prevent nuisance alarm trips. COMMUNICATIONS Two sets of output contacts for monitoring of alarm conditions are provided. Master alarm contact shall be activated by any condition defined as "serious alarm" by the user. The secondary contact is activated by non-safety related alarms. Serial connection to generic supervisory systems is available through optional external gateway devices. Up to sixteen peripheral devices may be connected through each gateway, depending on the communication protocol (i.e. Modbus TM, BACnet TM ). Sensor Calibration: Temperature and humidity sensors are capable of being calibrated, using the front monitor panel controls, to achieve readings consistent with other temperature and humidity sensors in the room. DISPLAY PARAMETERS The front monitor panel allows visual monitoring of room temperatures and humidity levels, adjustment and display of each control setpoint, displays active functions (cooling, heating, dehumidification), and indicates any active alarms. ACTIVE DISPLAY FUNCTIONS Temperature Setpoint - 60 F to 85 F Temperature Differential - +/-1 to +/-10 F Humidity Setpoint - 40% to 60% RH Humidity Differential - +/-1% to +/-10% RH High Temperature Alarm - 60 F to 95 F Low Temperature Alarm - 50 F to 85 F High Humidity Alarm - 40% to 80% RH Low Humidity Alarm - 20% to 60% RH 5

6 CONTROLS DELUXE MICROPROCESSOR CONTROL SYSTEM The optional electronic control system offers enhanced features for management of precision air-conditioners. The control is flush mounted in the unit, with a backlit LCD display and fifteen programming and menu short-cut keys for operator interface. An optional large LCD display allows graphical presentation of acquired variables. An optional interface board is available for direct connection to a serial printer. The control system allows selection and programming of temperature and humidity setpoints, alarm parameters, and operating configuration. Multi-level passwords are required to make changes to the system setup and configuration parameters. CONTROL FEATURES Control Type: The user shall be able to select the type of control regulation that the microprocessor will use. Selection will be either proportional or proportional plus integral (P+I). If P+I is selected, the user shall be able to set the integration time constant. Compressor Short-Cycle Control: The control system includes time constants for compressor minimum on-time and minimum off-time. Compressor Rotation: Compressor run times are automatically equalized to maximize operating life. Sequential Load Activation: During start-up the microprocessor sequences operational loads to minimize inrush current. Auto Restart: The system will automatically restart after a power interruption. Time delay on restart is adjustable. Manual Control: The user may manually operate the output devices connected to the control system. All safety interlocks and protective functions remain enabled. Free-Cooling Mode: User may select from two energy saving sequences; free-cool only, or free-cooling with compressor supplement. When conditions are not favorable for free-cooling, the compressor stages operate normally. Data Collection: The microprocessor shall maintain accumulative operating hours of all rotating components (fan motor and compressor motors). In the event of an alarm condition the alarm code, hour, minute and date are recorded, up to a maximum of 300 signals. Data logs are protected by a battery back-up in the event of power failure. Sensor Calibration: Temperature and humidity sensors are capable of being calibrated, using the front monitor panel controls, to achieve readings consistent with other temperature and humidity sensors in the room. DISPLAY PARAMETERS The front monitor panel allows visual monitoring of room temperatures and humidity levels, adjustment and display of each control setpoint, displays active functions (cooling, heating, dehumidification), and indicates any active alarms. ACTIVE REGULATION VARIABLES Temperature Setpoint - 60 F to 85 F Temperature Differential - +/-1 to +/-10 F Humidity Setpoint - 40% to 60% RH Humidity Differential - +/-1% to +/-10% RH High Temperature Alarm - 60 F to 95 F Low Temperature Alarm - 50 F to 85 F High Humidity Alarm - 40% to 80% RH Low Humidity Alarm - 20% to 60% RH ALARM FUNCTIONS The control system monitors unit operation and activates an audible and visual alarm upon occurrence of the following conditions: High Temperature Low Temperature High Humidity Low Humidity Humidifier Fault High Head Pressure (C1 or C2) Low Suction Pressure (C1 or C2) Heater Overload (Electric Reheat only) Loss of Airflow Fan Motor Overload Change Filters Loss of Cooling Manual Control Operating Hours exceeded Condensate Drain Pan Overflow Water under floor (opt) Smoke/Fire detected (opt) Loss of water flow (opt) Generic Alarm (user-defined) Operational alarms, that are not safety related, can be programmed for a time delay of 0 to 250 seconds to prevent nuisance alarm trips. 6

7 COMMUNICATIONS COMMUNICATIONS Two sets of output contacts for monitoring of alarm conditions are provided. Master alarm contact shall be activated by any condition defined as "serious alarm" by the user. The secondary contact is activated by non-safety related alarms. Multiple systems may be connected into a local network, allowing monitoring and control of up to thirty-one units from one user interface panel. A dedicated supervisory interface may be located up to a distance of 600 feet from the nearest control board. A site supervision software package is available for networked monitoring and control of multiple unit installations. This Windows TM based software allows centralized control of up to 800 compatible devices. Serial connection to generic supervisory systems, without external gateway devices, using embedded multiprotocol software. The unit control can be directly connected to remote management systems currently operating on the Modbus TM, BACnet TM, or Echelon standard. Skymark Model # Nomenclature Code Product Type Accessory Options Unit Type Airflow Configuration Reheat Option Cooling Capacity Cooling Source Humidifier Option Voltage System Control Option 7

8 AIR COOLED FLOOR MOUNTED UNITS Model PVA_180 PVA_235 Net Cooling Performance (Btu/hr), Standard 0.5 in wg ESP 80 F DB/67 F WB 75 F DB/62.5 F WB 75 F DB/61 F WB 72 F DB/60 F WB 72 F DB/58.6 F WB Total 204, ,900 Sensible 166, ,700 Total 189, ,600 Sensible 162, ,600 Total 187, ,600 Sensible 175, ,100 Total 180, ,900 Sensible 158, ,700 Total 182, ,900 Sensible 173, ,400 Reheat/Heat Data (Btu/hr) - Includes Blower Motor Heat Electric - BTUH (Kw) 100,800 (25) 125,700 (30) Quantity of Stages 3 3 Hot Water F EWT, 75 F EAT 1) Capacity (Btu/hr) 118, ,700 Flow Rate (gpm) Pressure Drop (ft wc) Steam - 15 PSIG Steam, 75 F EAT 1) Capacity (Btu/hr) 136, ,600 Humidification - Steam Canister with Adjustable Output Capacity (lb/hr) Control Evaporator Blower Data - Centrifugal, Belt Drive Proportional Quantity of Blowers 2 2 Standard Motor (Hp) CFM with Standard Motor 8,150 10,000 Design ESP (in wg) with Standard Motor Oversize Motor (Hp) n/a n/a MAX ESP (in wg) with Oversize Motor n/a n/a Evaporator Coil-Copper Tubes, Aluminum Fins Face Area (sq ft) Rows 3 4 Filters - Qty/Size (in) Downflow 4/24x24x4 4/24x24x4 Upflow 6/25x16x4 6/25x16x4 Compressor-Type/Qty. Scroll / 2 Outdoor Condenser Data (95 F) - Propeler Fan, Direct Drive Model ACC180 ACC240 CFM Motor (Hp) / Qty. 0.5 / / 4 Condenser Coil-Copper Tubes, Aluminum Fins Face Area (sq ft) Rows/FPI 2/10 3/10 Connection Sizes Hot Gas 7/8OD 1-1/8OD Liquid Line 5/8OD 5/8OD Condensate Drain 7/8OD Humidifier Inlet 1/4OD Hot Water Inlet/Outlet 5/8OD Steam Inlet/Outlet 3/4MPT Max. Weight (lb) ) Hot water and steam reheat will reduce blower performance. Consult factory for details. 8

9 WATER COOLED FLOOR MOUNTED UNITS Model PVW_190 PVW_245 Net Cooling Performance (Btu/hr), Standard 0.5 in wg ESP 80 F DB/67 F WB 75 F DB/62.5 F WB 75 F DB/61 F WB 72 F DB/60 F WB 72 F DB/58.6 F WB Total 217, ,000 Sensible 172, ,600 Total 200, ,900 Sensible 168, ,000 Total 196, ,100 Sensible 180, ,000 Total 190, ,500 Sensible 163, ,000 Total 187, ,000 Sensible 175, ,500 Reheat/Heat Data (Btu/hr) - Includes Blower Motor Heat Electric - BTUH (kw) 100,800 (25) 125,700 (30) Quantity of Stages 3 3 Hot Gas 1) Total Capacity (Btu/hr) / (Electric Capacity - kw) 104,400 / (10) 130,500 / (10) Hot Water F EWT, 75 F EAT 1) Capacity (Btu/hr) 118, ,700 Flow Rate (gpm) Pressure Drop (ft wc) Steam - 15 PSIG Steam, 75 F EAT 1) Capacity (Btu/hr) 136, ,600 Humidification - Steam Canister with Adjustable Output Capacity (lb/hr) Control Proportional Evaporator Blower Data - Centrifugal, Belt Drive Quantity of Blowers 2 2 Standard Motor (Hp) CFM with Standard Motor 8,150 10,000 Design ESP (in wg) with Standard Motor Oversize Motor (Hp) n/a n/a MAX ESP (in wg) with Oversize Motor n/a n/a Evaporator Coil-Copper Tubes, Aluminum Fins Face Area (sq ft) Rows 3 4 Filters - Qty/Size (in) Downflow 4/24x24x4 4/24x24x4 Upflow 6/25x16x4 6/25x16x4 Compressor-Type/Qty. Scroll / 2 Shell & Tube Condenser Data - 75 F DB/62.5 F WB EAT Water Flow (GPM) 85 o F EWT - 10 o F dt Pressure Drop (psi) (Includes regulating valve) Standard Head Pressure Control 2-way, 150PSIG Water Regulating Valve Connection Sizes Water In 1-5/8 OD 2-1/8 OD Water Out 1-5/8 OD 2-1/8 OD Condensate Drain 7/8OD Humidifier Inlet 1/4OD Hot Water Inlet/Outlet 5/8OD Steam Inlet/Outlet 3/4MPT Max. Weight (lb) ) Hot gas, hot water and steam reheat will reduce blower performance. Consult factory for details. 9

10 GLYCOL COOLED FLOOR MOUNTED UNITS Model PVG_185 PVG_240 Net Cooling Performance (Btu/hr), Standard 0.5 in wg ESP 80 F DB/67 F WB 75 F DB/62.5 F WB 75 F DB/61 F WB 72 F DB/60 F WB 72 F DB/58.6 F WB Total 210, ,900 Sensible 178, ,300 Total 194, ,300 Sensible 173, ,600 Total 192, ,100 Sensible 185, ,800 Total 185, ,800 Sensible 169, ,000 Total 187, ,200 Sensible 181, ,200 Reheat/Heat Data (Btu/hr) - Includes Blower Motor Heat Electric - BTUH (Kw) 100,800 (25) 125,700 (30) Quantity of Stages 3 3 Hot Gas 1) Capacity (Btu/hr) 105,800 / (10) 132,300 / (10) Hot Water F EWT, 75 F EAT 1) Capacity (Btu/hr) 118, ,700 Flow Rate (gpm) Pressure Drop (ft wc) Steam - 15 PSIG Steam, 75 F EAT 1) Capacity (Btu/hr) 136, ,600 Humidification - Steam Canister with Adjustable Output Capacity (lb/hr) Control Proportional Evaporator Blower Data - Centrifugal, Belt Drive Quantity of Blowers 2 2 Standard Motor (Hp) CFM with Standard Motor 8,150 10,000 Design ESP (in wg) with Standard Motor Oversize Motor (Hp) n/a n/a MAX ESP (in wg) with Oversize Motor n/a n/a Evaporator Coil-Copper Tubes, Aluminum Fins Face Area(sq ft) Rows 3 4 Filters - Qty/Size (in) Downflow 4/24x24x4 4/24x24x4 Upflow 6/25x16x4 6/25x16x4 Compressor-Type/Qty. Scroll / 2 Shell & Tube Condenser Data - 75 F DB/62.5 F WB EAT Glycol Flow (GPM) 105 F EGT 10 o F dt Pressure Drop (ft wc) Standard Head Pressure Control 3-way, 150PSIG Water Reg. Valve Drycooler Data - 95 F Outdoor Air, 40% Solution Model ACG185 ACG240 CFM 24,000 38,400 Motor (Hp)/Number Used 0.5/4 0.5/6 Pressure Drop (ft wc) Connection Sizes Glycol In 1-5/8 OD 2-1/8 OD Glycol Out 1-5/8 OD 2-1/8 OD Condensate Drain 7/8OD Humidifier Inlet 1/4OD Hot Water Inlet/Outlet 5/8OD Steam Inlet/Outlet 3/4MPT Max. Weight (lb) ) Hot gas, hot water and steam reheat will reduce blower performance. Consult factory for details. 10

11 CHILLED WATER FLOOR MOUNTED UNITS Model PVF_195 PVF_250 Net Cooling Performance (Btu/hr), 45F EWT, 10F water temp rise Total 335, , F DB/67 F WB 75 F DB/62.5 F WB 75 F DB/61 F WB 72 F DB/60 F WB 72 F DB/58.6 F WB Sensible 234, ,700 Flow Rate (GPM) Press. Drop (PSI) Total 235, ,640 Sensible 198, ,900 Flow Rate (GPM) Press. Drop (PSI) Total 219, ,800 Sensible 206, ,100 Flow Rate (GPM) Press. Drop (PSI) Total 190, ,300 Sensible 177, ,100 Flow Rate (GPM) Press. Drop (PSI) Total 185, ,400 Sensible 183, ,200 Flow Rate (GPM) Press. Drop (PSI) Reheat/Heat Data (Btu/hr) - Includes Blower Motor Heat Electric - BTUH (kw) 100,800 (25) 125,700 (30) Quantity of Stages 3 3 Hot Water F EWT, 75 F EAT 1) Capacity (Btu/hr) 119, ,200 Flow Rate (gpm) Pressure Drop (ft wc) Steam - 15 PSIG Steam, 75 F EAT 1) Capacity (Btu/hr) 136, ,600 Humidification - Steam Canister with Adjustable Output Capacity (lb/hr) Control Proportional Evaporator Blower Data - Centrifugal, Belt Drive Quantity of Blowers 2 2 Standard Motor (Hp) CFM with Standard Motor 8,700 10,500 Design ESP (in wg) with Standard Motor Oversize Motor (Hp) n/a n/a MAX ESP (in wg) with Oversize Motor n/a n/a Chilled Water Coil-Copper Tubes, Aluminum Fins Face Area(sq ft) Rows 4 5 Valve Type 3-Way 3-Way Valve Actuation Modulating Modulating Filters - Qty/Size (in) Downflow 4/24x24x4 4/24x24x4 Upflow 6/25x16x4 6/25x16x4 Connection Sizes Water In 2-1/8 OD Water Out 2-1/8 OD Condensate Drain 7/8OD Humidifier Inlet 1/4OD Hot Water Inlet/Outlet 5/8 OD Steam Inlet/Outlet 1/2MPT Max. Weight (lb) ) Hot water and steam reheat will reduce blower performance. Consult factory for details. 11

12 12 PRECISION UPFLOW UNIT 15 & 20 TON

13 PRECISION DOWNFLOW UNIT 15 & 20 TON 13

14 ELECTRICAL DATA- STANDARD MOTORS Note: 1) Values shown are for the PV unit only. Outdoor condensers or drycoolers require a separate electrical service. 2) Ratings are based on dehumidification with single compressor stage only. Contact Skymark for ratings with two stage dehumidification. 14

15 ELECTRICAL DATA- HOT GAS REHEAT WITH STANDARD MOTORS Note: 1) Values shown are for the PV unit only. Outdoor condensers or drycoolers require a separate electrical service. 2) Ratings based on dehumidification with single compressor stage only. Contact Skymark for ratings with two stage dehumidification. 15

16 CHILLED WATER UNIT ELECTRICAL DATA- STANDARD MOTORS MODEL VOLTAGE EVAP. FAN HEATER HUMIDIFER MCA MAX FUSE / # HP FLA AMP AMP CCT. BKR. AMP PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/ PVF* /3/

17 OUTDOOR AIR-COOLED CONDENSER DATA - 15 & 20 TON CONDENSER ELECTRICAL DATA MODEL NUMBER ACC180 ACC240 UNIT VOLTAGE FLOODED CONDENSER CONTROL FAN SPEED CONTROL FLA MCA MFS FLA MCA MFS /1/ /3/ /3/ /3/ CONDENSER DIMENSIONAL DATA MODEL NUMBER HOT GAS LIQUID WEIGHT DIM'N DIM'N FAN SPEED CONTROL FLOODED CONDENSER HP QTY (lbs.) A L ACC180 2 X 1-1/8 OD 2 X 7/8 OD 2 X 5/8 OD 1/ ACC240 2 X 1-3/8 OD 2 X 1-1/8 OD 2 X 3/4 OD 1/ FANS 17

18 GLYCOL DRY-COOLER DATA 15 & 20 TON DRYCOOLER ELECTRICAL DATA MODEL NUMBER ACG180 ACG240 UNIT VOLTAGE FLA MCA MFS /1/ /3/ /3/ /3/ /1/ /3/ /3/ /3/ DRYCOOLER DIMENSIONAL DATA MODEL NUMBER IN / OUT CONNECTIONS FANS VOLUME WEIGHT DIM'N DIM'N HP QTY (gal.) (lbs.) A L ACG /2 MPT 1/ ACG /2 MPT 1/

19 19

20 SKYMARK PRODUCT WARRANTY Skymark International warrants to the original owner/user of the Skymark International unit identified above to be free of original defects in material or workmanship for a period of one year from the effective date of this warranty. This warranty extends to twelve (12) months from the date of start-up, but no longer than eighteen (18) months from the date of shipment. The warranty does not include the filter. This warranty on the unit obligates Skymark International to repair or replace, free of charge, any part or parts that show evidence of being defective in material and workmanship and are so deemed so defective by authorized personnel of Skymark International. The part must be returned for replacement with the proper information when requested. Skymark International assumes no obligation for labor required to replace the defective part or parts nor the freight or postage required to return or to secure the part which shall be at the cost and expense of the original Owner/User. Skymark International will replace the defective part or parts within 21 days after the return to Skymark International of such defective part or parts provided notice of such defect was given by the original Owner/User within the Warranty period. An optional, additional four year protection plan on the compressor is available at modest cost at the time of original unit sale only. This obligates Skymark International to replace f.o.b. factory, a defective compressor of equal capacity free of charge. No responsibility is assumed by Skymark International for refrigerant, labor, or freight to and from the factory. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESSED WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE ARE LIMITED IN DURATION TO ONE (1) YEAR FROM EFFECTIVE DATE OF THIS WARRANTY. SKYMARK INTERNATIONAL IS NOT LIABLE FOR CONSEQUENTIAL DAMAGES RESULTING FROM ANY DEFECT IN PART. THERE ARE NO OTHER OBLIGATIONS ON THE PART OF SKYMARK INTERNATIONAL. WARRANTY OF FITNESS Skymark International does not provide a warranty of fitness since, in good faith, Skymark International cannot anticipate or control the many different conditions under which Skymark International information and products may be used. City of New York Department of Buildings MEA Skymark maintains a continuous product improvement policy, therefore specifications are subject to change without notice. PHONE: FAX: TOLL FREE: SKYMARK ( ) WEB: 10/04

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) DX Product Description Performance and Electrical Data 3 the pioneer and builder of the most

More information

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) with refrigerant Product Description Performance and Electrical Data Dimensional Data Guide

More information

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified Shelf Units 2, 3, and 4 ton R-407C ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-410A. ISO 9001 Certified

Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-410A. ISO 9001 Certified Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Back in the late

More information

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first

More information

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first

More information

Data Aire Series Chilled Water 7 through 50 ton

Data Aire Series Chilled Water 7 through 50 ton Data Aire Series Chilled Water 7 through 50 ton ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system

More information

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

Modular Data Temp Systems Air Cooled Water/Glycol Cooled R-407C. 8, 10 and 13 ton capacities. ISO 9001 Certified

Modular Data Temp Systems Air Cooled Water/Glycol Cooled R-407C. 8, 10 and 13 ton capacities. ISO 9001 Certified Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-407C ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Back in

More information

Series 8. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 8. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 8 Guide Specification 60 Hz S8-GS-602017.doc 2014 ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 Series 8 Guide Specification-60

More information

ENGINEERING MANUAL 3, 5, & 7 TONS PRECISION ENVIRONMENTAL CONTROL

ENGINEERING MANUAL 3, 5, & 7 TONS PRECISION ENVIRONMENTAL CONTROL ENGINEERING MANUAL 3, 5, & 7 TONS PRECISION ENVIRONMENTAL CONTROL MODEL DESCRIPTION Table of Contents The LAYTON Advantage... Total Protection----------------------------------------------------------

More information

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision

More information

CeilMate TM Series 3 and 4 tons of cooling capacity. Ceiling Mounted Systems. Air Handler with Remote Condensing Unit Air Handler designed for R-410A

CeilMate TM Series 3 and 4 tons of cooling capacity. Ceiling Mounted Systems. Air Handler with Remote Condensing Unit Air Handler designed for R-410A A e r o S y s I n c o r p o r a t e d Ceiling Mounted Systems CeilMate TM Series 3 and 4 tons of cooling capacity Air Handler with Remote Condensing Unit Air Handler designed for R-410A AeroSys, Inc. 929

More information

VariCool VAV Engineering Guide

VariCool VAV Engineering Guide Engineering Guide Effective September 2017 Water-Cooled and Chilled Water, Variable Air Volume Contents Product Features... 3 UNIT FEATURES... 3 Product Features... 4 Marvel Plus Microprocessor Control

More information

VertiCool Aurora Engineering Guide

VertiCool Aurora Engineering Guide Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8

More information

Water-Cooled Self-Contained Units

Water-Cooled Self-Contained Units CATALOG FORM SK145.15-EG1 (1017) Water-Cooled Self-Contained Units C-Series, Vertical Nomenclature WATER-COOLED SELF-CONTAINED UNIT 1, 2 3 4, 5, 6 7 8 9 10 11 12 13 14 15 16 17 CS V 180 B 2 M 1 V A A A

More information

gforce - R-407C Air Cooled, Water/Glycol Cooled kw Dual Circuits

gforce - R-407C Air Cooled, Water/Glycol Cooled kw Dual Circuits gforce - R-407C Air Cooled, Water/Glycol Cooled 21-106 kw Dual Circuits 1 2 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling

More information

R-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits

R-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits R-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system

More information

STULZ FLAiR Systems Floor Mounted Console Air Conditioners 5-17 kw / Single Circuit / DX Air / Water / Glycol. Engineering Manual

STULZ FLAiR Systems Floor Mounted Console Air Conditioners 5-17 kw / Single Circuit / DX Air / Water / Glycol. Engineering Manual Indoor Cooling Perimeter STULZ FLAiR Systems Floor Mounted Console Air Conditioners 5-17 kw / Single Circuit / DX Air / Water / Glycol Self-contained Precision Air Conditioner Utilizing EC Fan Technology

More information

Mini-Space EC DX and CW 4 12 kw Systems Vertical Floor Mounted, 60 Hz Data

Mini-Space EC DX and CW 4 12 kw Systems Vertical Floor Mounted, 60 Hz Data Mini-Space EC DX and CW 4 12 kw Systems Vertical Floor Mounted, 60 Hz Data Engineering Manual ABOUT STULZ STULZ is a privately owned, global manufacturer of highly efficient temperature and humidity management

More information

technical guide Water-Cooled Self-Contained Units

technical guide Water-Cooled Self-Contained Units technical guide Water-Cooled Self-Contained Units C-Series, Vertical Technical Guide: YK145.00-EG3 (710) TABLE OF CONTENTS Water-Cooled Self-Contained Units Introduction...............................................................................

More information

Chilled Water 7 to 211 kw

Chilled Water 7 to 211 kw Chilled Water 7 to 211 kw Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing facility

More information

Series 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 6 Guide Specification 60 Hz S6-GS-602017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 Series 6 Guide Specification-60

More information

Advance Release September 2009

Advance Release September 2009 Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*

More information

STULZ CyberAiR Floor Mounted Systems. Engineering Manual. Floor Mounted Air Conditioners

STULZ CyberAiR Floor Mounted Systems. Engineering Manual. Floor Mounted Air Conditioners Floor Mounted Air Conditioners Indoor Cooling Perimeter STULZ CyberAiR Floor Mounted Systems 60-730 kw Chilled Water Systems Precision Air Handlers Utilizing EC Fan Technology (60Hz Data) EM Engineering

More information

CoolSpot Engineering Guide

CoolSpot Engineering Guide Engineering Guide Effective December 2017 Air-Cooled, Water-Cooled, Chilled Water or Magna Cool Precision Cooling Package Contents Contents....................................................... 2 Product

More information

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 37,800* Design CFM: 1,200 Seasonal

More information

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 25,240* Design CFM: 800 Seasonal

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information

CeilMate. Ceiling Mounted Units. Series 1 to 3 tons of cooling capacity

CeilMate. Ceiling Mounted Units. Series 1 to 3 tons of cooling capacity A e r o S y s I n c o r p o r a t e d Ceiling Mounted Units CeilMate Series 1 to 3 tons of cooling capacity Air Cooled, Self-Contained Water Cooled Glycol Cooled Remote Air Cooled Condenser Air Handler

More information

Chilled Water 7 to 211 kw

Chilled Water 7 to 211 kw Chilled Water 7 to 211 kw Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing facility

More information

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons 491 East Princess Street York, PA 17403 877-905-1111 717-843-4311 Fax: 717-854-4462 uca@unitedcoolair.com www.unitedcoolair.com VERTICOOL TECHNICAL DATA MANUAL Vertical Air/Water Cooled 3-25 Tons UNITED

More information

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump VertiCool CLASSIC Engineering Guide Effective March 2018 Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump Contents Product Features... 3 UNIT FEATURES... 3 OPTIONS:... 3 Physical Data...

More information

Guide Specifications for InRow Direct Expansion

Guide Specifications for InRow Direct Expansion Guide Specifications Guide Specifications for InRow Direct Expansion THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information

"SWVP - SWHP" COMMERCIAL WATER SOURCE HEAT PUMPS & AIR CONDITIONERS

SWVP - SWHP COMMERCIAL WATER SOURCE HEAT PUMPS & AIR CONDITIONERS "SWVP - SWHP" COMMERCIAL WATER SOURCE HEAT PUMPS & AIR CONDITIONERS Belt Driven Self-Contained Packages Vertical and Horizontal Configuration Size 6-8-10 Ton Capacities Spinnaker Industries Inc. SWHP /

More information

gforce GT R-407C Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw

gforce GT R-407C Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw gforce GT Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw 1 2 the pioneer and builder of the most complete line of precision cooling equipment Back in the late 1960 s and early 70 s with the advancement

More information

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/ 1 of 3 Cooling Capacity [Btuh] 24,800 * Condensing Unit SEER: 13.0 ** Condensing Unit CFM: 1,600 Condenser Fan No./Type: 1/CENTRIFUGAL Diameter x Width [in]: 10x10 Drive: Adjustable Belt Motor HP: 0.5

More information

SC SpotCool. 1 to 3 Tons. R407c & R410a. 2 x 4 Packaged & Split. Spot-Cooler & Ducted. eair above-the-ceiling air conditioners (ASC-L22)

SC SpotCool. 1 to 3 Tons. R407c & R410a. 2 x 4 Packaged & Split. Spot-Cooler & Ducted. eair above-the-ceiling air conditioners (ASC-L22) Engineering Manual R407c & R410a SC SpotCool 2 x 4 Packaged & Split Ceiling Mounted A/C s (DX & CW Systems) Features & Benefits 1 to 3 Ton Capacities Comfort Applications - General Office Spaces - Conference

More information

RTU. Roof Top Units 8 30 Ton. Maxi-Kool.

RTU. Roof Top Units 8 30 Ton. Maxi-Kool. Maxi-Kool RTU Roof Top Units 8 30 Ton www.compu-aire.com MK A-3 034 -RTU Maxi-Kool Type Air Cooled - A Chilled Water Cooled - C Glycol Cooled - G Water Cooled - W Nominal Tonnage 8 30 Ton Voltage 2-208

More information

Series PS6, Vertical Floor-Mount Units

Series PS6, Vertical Floor-Mount Units Series PS6, Vertical Floor-Mount Units Technical Data 60 Hz sps6em6ea.doc Dec-12 ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 Table of Contents Table of Contents...

More information

Liebert Mini-Mate2. 8-Ton (28kW) Capacity, Air, Water, Glycol, GLYCOOL, Chilled Water; 50 & 60 Hz. Technical Data Manual

Liebert Mini-Mate2. 8-Ton (28kW) Capacity, Air, Water, Glycol, GLYCOOL, Chilled Water; 50 & 60 Hz. Technical Data Manual Liebert Mini-Mate2 8-Ton (28kW) Capacity, Air, Water, Glycol, GLYCOOL, Chilled Water; 50 & 60 Hz Technical Data Manual Technical Support Site If you encounter any installation or operational issues with

More information

Computer Room Air-Conditioning 60 Hz. Technical Data

Computer Room Air-Conditioning 60 Hz. Technical Data TM Computer Room Air-Conditioning 60 Hz 10 kw (3 tons) Technical Data Contents Overview.............................................................. 1 Standard Features.......................................................

More information

Liebert Deluxe System/3

Liebert Deluxe System/3 Precision Cooling For Business-Critical Continuity Liebert Deluxe System/3 Technical Data Manual - Floor Mounted, 60 Hz, 6-30 Tons, Air, Water, Glycol and GLYCOOL Cooled TABLE OF CONTENTS DEDICATED, PRECISE

More information

Liebert. Deluxe System/3 Chilled Water Systems ENVIRONMENTAL CONTROL TECHNICAL DATA MANUAL. 50 Hz and 60 Hz ISO 9000 CERTIFIED COMPANY

Liebert. Deluxe System/3 Chilled Water Systems ENVIRONMENTAL CONTROL TECHNICAL DATA MANUAL. 50 Hz and 60 Hz ISO 9000 CERTIFIED COMPANY Liebert Keeping Business in Business ENVIRONMENTAL CONTROL Deluxe System/3 Chilled Water Systems TECHNICAL DATA MANUAL 50 Hz and 60 Hz ISO 9000 CERTIFIED COMPANY Table of Contents Liebert Technology and

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

-2x2. eair floor mounted precision air conditioners (MC22-L10) R407C & R410a Data. From 1 to 3 Tons. Engineering Manual

-2x2. eair floor mounted precision air conditioners (MC22-L10) R407C & R410a Data. From 1 to 3 Tons. Engineering Manual Engineering Manual From 1 to 3 Tons MC-2x2-2x2 MissionCritical Vertical Floor Mounted A/C s (Single Circuit DX & CW) R407C & R410a Data ta 1 to 3 Tons Compact 24 W x 24 D Footprint Features & Benefits

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems Mission Critical Air Conditioning Systems vertical floor mount Series 6, 8 & 9 2-30 Ton Units Single Circuit for Superior Economy and Dual Circuit for Ultimate Protection Series 6 2-5 tons Compact Footprint

More information

Contents. APC NetworkAIR CW. CW 020 C= Chilled Water BA= /3/60 D= Downflow. Capacity (kw) Configuration Voltage Air Pattern

Contents. APC NetworkAIR CW. CW 020 C= Chilled Water BA= /3/60 D= Downflow. Capacity (kw) Configuration Voltage Air Pattern Contents Overview.............................................................. 1 Standard Features....................................................... 2 Optional Features.......................................................

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw) FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz

More information

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental TECAM S.A. Tecnología Ambiental R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz harmony 5PZA Direct Expansion Registration No.: SC 4696-1 Registration No.: CO-SC 4696-1 Air Conditioning Equipment Manufacturer

More information

Precision Air-Conditioning Units 60 Hz. Technical Data

Precision Air-Conditioning Units 60 Hz. Technical Data NetworkAIR Precision Air-Conditioning Units 60 Hz TM AFX Series Technical Data Contents Available Models................................. 1 Downflow 1 Upflow front-return 1 Upflow rear-return 1 Indoor

More information

System Floor Mount Systems DX / Glycol / Chilled Water 6-12 Tons. High Density Presicion Cooling. Kompact.

System Floor Mount Systems DX / Glycol / Chilled Water 6-12 Tons. High Density Presicion Cooling. Kompact. High Density Presicion Cooling Floor Mount Systems DX / Glycol / Chilled Water 6-12 Tons System 2100 Kompact www.compu-aire.com CA A - 8 34 -K System 2100 K Type Air Cooled - A Chilled Water Cooled - C

More information

GUIDE SPECIFICATIONS AQUARIUS ii

GUIDE SPECIFICATIONS AQUARIUS ii Catalog (AP Technical Data Sheet) GUIDE SPECIFICATIONS AQUARIUS ii AP Series Two Stage R-410A GENERAL Units shall be performance certified to ISO standard 13256-1 for Water Loop Heat Pump, Ground Water

More information

Computer Room Air-Conditioning 60 Hz. Technical Data

Computer Room Air-Conditioning 60 Hz. Technical Data TM Computer Room Air-Conditioning 60 Hz 35 150 kw (10 45 tons) Technical Data Contents Overview.............................................................. 1 Scalable Solution for Critical Environments.................................

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES 60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,

More information

SpaceKeeper Console (SKC)

SpaceKeeper Console (SKC) SpaceKeeper Console (SKC) With finished cabinet or custom enclosure SKC 008-015 ¾ - 1¼ tons 12 W x 25¼ H x 48 L CGC-09 SpaceKeeper Console R410A MODEL NO. SKC _ 008 010 012 015 Net Cooling Capacity - Rated

More information

Environmental Control

Environmental Control engineering manual Environmental Control mini-might Environmental Ceiling A/C s 1, 1-1/2, 2 and 3 Ton Capacities Perfect for Telecom, ATM & Server Room Applications T-Bar Ceiling Mounted - Ductless Spot

More information

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons Product Data OMNIZONE 50BRN,BZN006-024 Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems 5 to 20 Nominal Tons The 50BRN,BZN water-cooled and remote air-cooled indoor, self-contained units

More information

Contents. APC NetworkAIR AFX AFX

Contents. APC NetworkAIR AFX AFX Contents Overview.............................................................. 1 Standard Features....................................................... 2 Optional Features.......................................................

More information

Liebert PDX and PCW Thermal Management Systems

Liebert PDX and PCW Thermal Management Systems Liebert PDX and PCW Thermal Management Systems 3 to 8 Ton (11 to 29 kw) Nominal Capacity, Upflow and Downflow, 60 Hz, Air-, Water-, Glycoland Chilled-water-cooled Models System Design Catalog Technical

More information

System 2100 & System 2100k

System 2100 & System 2100k System 2100 & System 2100k Floor Mount System 6-60 tons Optimal solution for modern applications LIS T E D Compu-Aire Inc.. Was established 1980 in fullerton, california usa. Presently, the company is

More information

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled FORM 145.05-EG1 (1004) VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU 10 105 Ton Water-Cooled Table of Contents FORM 145.05-EG1 (0804) Features and Benefits.....................................................

More information

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps Product Data OMNIZONE 50BV020-064 Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps 18 to 60 Nominal Tons omnizonebwlogo 50BVC,E,J,K,Q020-034 SINGLE PIECE OMNIZONE

More information

Precise Temperature Control; Compact Footprint

Precise Temperature Control; Compact Footprint Precise Temperature Control; Compact Footprint The Conair EP1 Series Portable Chillers are designed for 1 to 3 ton applications. Available as air-cooled or water-cooled, with pump sizes from 1/4 to 3 Hp

More information

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS Cooling Capacity from 115,000 to 670,000 Btu/hr Btu/hr Smartwise Innovations... Towards Green, Quality & Reliability Solutions SERIES INTRODUCTION

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

Control Systems. Design & Manufacturing. Eco-Friendly. High Performance

Control Systems. Design & Manufacturing. Eco-Friendly. High Performance Temperature & Humidity Control Systems Design & Manufacturing DX Air / Water / Glycol Cooled Air and Water Side Economizer Chilled Water Systems Eco-Friendly High Performance OPTIMAL COOLING SOLUTIONS

More information

Precision Air-Conditioning Units 60 Hz. Technical Data

Precision Air-Conditioning Units 60 Hz. Technical Data â NetworkAIR TM CM Series Precision Air-Conditioning Units 60 Hz Technical Data Contents Available Models................................. 1 Spot-cooled 1 Ducted 1 System Configurations.............................

More information

INSTALLATION AND OPERATIONAL MAINTENANCE MANUAL

INSTALLATION AND OPERATIONAL MAINTENANCE MANUAL INSTALLATION AND OPERATIONAL MAINTENANCE MANUAL IN ROW SYSTEMS AYAN IV SERIES IN ROW COOLING 8176 Byron Road, Whittier, CA 90606 Phone: (562) 945-8971 Fax: (562) 696-0724 Website: www.compu-aire.com Email:

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling

More information

Contents. APC NetworkAIR AFX AFX

Contents. APC NetworkAIR AFX AFX Contents Overview.............................................................. 1 Standard Features....................................................... 2 Optional Features.......................................................

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON

More information

SKYPAK II Heating & Cooling Self Contained Packages

SKYPAK II Heating & Cooling Self Contained Packages SKYPAK II Heating & Cooling Self Contained Packages SKYPAK II gives you a complete airconditioning and heating system as an all-in-one package unit. Designed for conventional through-the-wall installation

More information

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons 560.20-TG1Y (388) EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons Each circuit includes a fully hermetic compressor with a crankcase

More information

CATALOG. SKYPAK Self-Contained Heating/Cooling Units

CATALOG. SKYPAK Self-Contained Heating/Cooling Units CATALOG SKYPAK Self-Contained Heating/Cooling Units FORM SK145.00-EG6 (1211) TABLE OF CONTENTS SKYPAK Self-Contained Heating/Cooling Units Introduction...3 Product Overview...3 Nomenclature...4 SKYPAK

More information

Flexible & Innovative. Cooling Solutions

Flexible & Innovative. Cooling Solutions Flexible & Innovative Cooling Solutions Flexible & Innovative Compu-Aire Inc. offers a variety of high performance precision cooling systems that can adapt to your application needs. With today s rapidly

More information

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH MHCCW-06-00 Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH Rev. 1.21 HVAC Guide Specifications Chilled or Hot Water Fan Coil 2-Pipe Nominal Size: 18,000 BTUH

More information

STULZ Compact CWE. Engineering Manual. Computer Room Air Handlers kw Precision Air Handlers Utilizing EC Fan Technology (60 Hz Data)

STULZ Compact CWE. Engineering Manual. Computer Room Air Handlers kw Precision Air Handlers Utilizing EC Fan Technology (60 Hz Data) Indoor Cooling Perimeter STULZ Compact CWE Computer Room ir Handlers 30-360 kw Precision ir Handlers Utilizing EC Fan Technology (60 Hz Data) EM Engineering Manual 1 STULZ Our Mission Our mission is to

More information

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ) Technical Guide SUNLINE 2000 SPLIT-SYSTEM EVAPORATOR BLOWER K4EU180 15 NOMINAL TONS (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

JCseries EVAPORATIVE CONDENSER. engineering data

JCseries EVAPORATIVE CONDENSER. engineering data JCseries EVAPORATIVE CONDENSER engineering data Recold JC Series Evaporative Condenser Contents 2 Construction... 3 Schematic... 4 Engineering Data... 5 Selection Procedure... 6-9 Multi-Circuited Selection

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

NQ Series Portable Chillers

NQ Series Portable Chillers NQ Series Portable Chillers Electrical Components Mounted and Wired All electrical components and sensors are mounted, wired, and fully tested at the factory to reduce installation time and ensure the

More information

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features: Heat Pumps SA SERIES SA Series Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features: Vertical self-contained units with capacities from 23 70 tons Direct drive backward curved plenum

More information

VK 3-30 Tons. R407C Data. Vertical Comfort Cooling A/C s & Heat Pumps. 3 to 30 Tons. VK Veritical Cooling Comfort air conditioners (AVK-R7-L25)

VK 3-30 Tons. R407C Data. Vertical Comfort Cooling A/C s & Heat Pumps. 3 to 30 Tons. VK Veritical Cooling Comfort air conditioners (AVK-R7-L25) Engineering Manual R47C Data VK 3-3 Tons Vertical Comfort Cooling A/C s & Heat Pumps Features & Benefits 3 to 3 Ton Capacities Comfort Applications - General Office Spaces - Retail Stores - Restuarants

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

> Refrigerant R-410A. Uniflair LE TDER-TUER kW. Energy-saving units with backward-curved fans. Perimeter cooling for medium/large data center

> Refrigerant R-410A. Uniflair LE TDER-TUER kW. Energy-saving units with backward-curved fans. Perimeter cooling for medium/large data center Uniflair LE TDER-TUER Energy-saving units with backward-curved fans 20-100kW > Perimeter cooling for medium/large data center > Refrigerant R-410A Available Versions: > Downflow (TDER) > Upflow (TUER)

More information

Guide Specifications PART 1 GENERAL 1.01 SUMMARY

Guide Specifications PART 1 GENERAL 1.01 SUMMARY Guide Specifications PART 1 GENERAL 1.01 SUMMARY A The environmental control system shall be designed specifically for precision temperature control applications. It will automatically monitor and control

More information

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH MHCCW-10-05 Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH Rev. 1.21 HVAC Guide Specifications Chilled Water Fan Coil with Electric Heat 2-Pipe Nominal Size:

More information

Liebert Mini-Mate2 1 To 8 Tons

Liebert Mini-Mate2 1 To 8 Tons Liebert Mini-Mate2 1 To Overhead Precision Cooling And Humidity Control Precision Cooling For Business-Critical Continuity Precision Cooling In A Space-Saving, Ceiling-Installed System When IT equipment

More information

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts GTIP60 ISO GT Series, Inch Pounds 60 Hz GT010070 (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts Rev: 903 Rev 1 Revisions: 31103 Changed HZ dwg to field convertible 5902 changed Unit

More information