Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Size: px
Start display at page:

Download "Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:"

Transcription

1 Second Revision No. 3-NFPA [ Section No ] * Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the burner Such device or devices shall be placed in a readily accessible location at a safe distance from the burner For electrically powered appliances, the requirement of shall be accomplished by an identified switch in the burner supply circuit, placed outside of and adjacent to the entrance to the room where the appliance is located For appliances that are not electrically powered, an identifiable valve in the oil supply line, operable from a location that can be reached without passing near the burner, shall be used. Submittal Date: Mon Apr 06 14:06:14 EDT 2015 Second Revision No. 3 implements the text of Input No. 36 as proposed in the First Draft Report, along with the following amendments: (1) In , the reference to oil stoves has been deleted because these units are obsolete and no longer manufactured. (2) In , the reference to "flow of oil" has been deleted because it is the burner, and not just the flow of oil, that needs to be shut. (3) In , the reference to safe distance has been deleted because and define the required separation distance.

2 Second Revision No. 4-NFPA [ Section No ] An electrical service disconnect switch, arranged to stop and start the oil burner, shall be installed at the appliance and shall be located so that it is within easy reach of the service technician for control of the oil burner while observing the flame A single duplex electrical receptacle shall be permitted to be installed at the same location, wired in parallel with the electrical service disconnect. Submittal Date: Mon Apr 06 14:20:51 EDT 2015 Second Revision No. 4 implements the text of Input No. 36 as proposed in the First Draft Report, along with addition of new which provides for a duplex receptacle for use by the service technician.

3 Second Revision No. 5-NFPA [ Section No ] A water heater shall be provided with a water pressure, and temperature, and vacuum- relief devices device. Submittal Date: Wed Apr 08 11:47:55 EDT 2015 Second Revision No. 5 implements the text of Input No. 36 as proposed in the First Draft Report. Amendments made to recognize currently-used combination relief devices. Vacuum relief devices are no longer considered necessary.

4 Second Revision No. 1-NFPA [ Section No. A ] A One method of testing is as follows: (1) Close fireplace dampers and fireplace door doors, and close all exterior doors and windows in the building, and close all interior doors in the building. (2) Turn on building air exhaust systems, including clothes dryers, range hoods, bathroom exhausts, and mechanical ventilation and forced-air heating or cooling system blowers and operate them at their highest speed setting. Do not operate a whole-house cooling exhaust fan. (3) Operate the burner in the smallest oil heating appliance first, and then other appliances in order of increasing capacity. Measure and record the flue draft and over-fire draft of each appliance, and check for flue gas spillage. (4) Check that the flue draft and over-fire draft are at a level that is required by the oil heating equipment manufacturer as specified in the installation and operating manuals for the appliance. Over-fire draft in oil appliances are usually negative 0.01 to negative 0.02 in. of water column. (5) Return doors, windows, exhaust fans, fireplace dampers, and all fossil fuel burning appliances to their previous conditions of use. The oil heating equipment installer shall take action as needed to correct excessive depressurization of the appliance combustion air zone and return the flue draft of over-fire draft to the requirements of the oil heat equipment manufacturer and/or oil burner manufacturer. Notify the homeowner, building owner, or occupant if combustion air zone depressurization impacts the operation of the oil heating equipment and all actions and modifications that were required allow the flue draft and over-fire draft to the level required by the oil heating equipment manufacturer. The oil heating equipment installer should take action as needed to correct excessive depressurization of the appliance combustion air zone and return the flue draft and over-fire draft to the requirements of the oil heat equipment manufacturer. Submittal Date: Mon Apr 06 13:54:04 EDT 2015 Second Revision No. 1 (which is a Comment to First Revision No. 25) effects the following changes: (1) Replacement of the word "shall" with the word "should", because Annex text is not mandatory. (2) Deletion of redundant text. (3) Correction of transcription errors to improve understanding of the text. In addition, the last paragraph has been deleted, because NFPA 31 is an installation standard. The text of the last paragraph might give the impression that adverse conditions do not need to be

5 addressed, when, logically, this would be a part of the installation process.

6 Second Revision No. 2-NFPA [ Section No. A ] A Remedial actions to correct excessive negative pressure in the combustion air zone might include the following: (1) Air boots for oil burners to supply outdoor air directly to the burner (2) Air-in-a-can to supply outdoor air into the boiler/furnace room (3) Dedicated make-up air for kitchen exhausts (4) Blocked vent safety shut-offs off devices (5) Make-up air into furnace return ducts with barometric damper (6) Warning labels on whole house fans Submittal Date: Mon Apr 06 14:04:50 EDT 2015 This Second Revision (which is a Comment to First Revision No. 25) is an editorial correction.

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES*

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* *Vented appliances refer to natural draft appliances equipped with a barometric draft regulator or Category I appliances equipped with a draft

More information

Indiana WX Oil Furnace Inspection Guide

Indiana WX Oil Furnace Inspection Guide Indiana WX Oil Furnace Inspection Guide Client: Job # : Address: Phone: Client Interview: Oil Dealer: Date of last service: Comments/Billing information: Standard Inspection / Clean and Tune Follow-up:

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

State of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety

State of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety 5.3.1A(2) Page 1 of 2 State of ALASKA, Weatherization Assistance Program Technical Support Document Combustion Safety This document is intended to support in detail the Combustion Safety Test Report. The

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

Electric Heat Inspection Form Revised September 2012

Electric Heat Inspection Form Revised September 2012 Client name: Address: Primary Heat Source: Auxiliary Heat Application: Heat Pump Information: Equipment Information Electric Electric Heat Inspection Form Revised September 2012 Audit Existing furnace

More information

Direct Vent System Required

Direct Vent System Required CB-200A Cottage Base Installation Instructions IMPORTANT: Read all instructions carefully before beginning the installation. This base must be installed by a qualified installing agency and in accordance

More information

Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs

Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs Rebecca Olson Neighborhood Energy Connection Duluth Energy Design Conference February 26 th, 2013 Duluth, MN Learning Objectives

More information

about your house Before You Start an Energy-Efficient Retrofit Mechanical Systems

about your house Before You Start an Energy-Efficient Retrofit Mechanical Systems about your house CE 28i Before You Start an Energy-Efficient Retrofit Mechanical Systems One of the best ways to make your home more comfortable, healthier and less expensive to operate is to upgrade the

More information

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION SECTIONS 23.20.100 Local Amendments To The International Mechanical Code, 2000 Edition 23.20.202 Definitions 23.20.301.14

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

(Information about THERMAL dampers for gas-fired appliances available on request.) WARNING

(Information about THERMAL dampers for gas-fired appliances available on request.) WARNING FLAIR INTERNATIONAL CORPORATION 600 OLD WILLETS PATH HAUPPAUGE, NEW YORK 11788 U.S.A. TEL.: (516) 234-3600 FAX: (516) 234-3610 SPECIFICATIONS, INSTALLATION INSTRUCTIONS AND TROUBLE-SHOOTING GUIDE FOR STACK

More information

RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO

RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO rgalenmoore1@msn.com This session will address the basics of combustion and the latest

More information

Leisure Line Power Vent Operations & Maintenance Manual And Safety Instructions

Leisure Line Power Vent Operations & Maintenance Manual And Safety Instructions Leisure Line Power Vent Operations & Maintenance Manual And Safety Instructions Black Rock Manufacturing DBA Leisure Line Stove Company Rear 620 Broad Street Berwick, PA 18603 http://www.leisurelinestoves.com/ind

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

Spray Polyurethane Foam and Open-Combustion Appliances

Spray Polyurethane Foam and Open-Combustion Appliances Spray Polyurethane Foam and Open-Combustion Appliances Before applying SPF (spray foam polyurethane) insulation in an attic or crawl space it is important to determine if there are any appliances present,

More information

Energy Saver 101: Home Energy Audits

Energy Saver 101: Home Energy Audits Energy Saver 101: Home Energy Audits Take the first step to improving your home s energy efficiency: get a home energy audit. What is a home energy audit? A home energy audit helps you pinpoint where your

More information

Natural Gas Appliance Testing Action Guidelines (Non ESA/Low Income 5 )

Natural Gas Appliance Testing Action Guidelines (Non ESA/Low Income 5 ) Natural Gas Appliance Testing Action Guidelines (n ESA/Low Income 5 ) The purpose of these Action Guidelines is to describe the actions participating contractors and/or inspectors should take in the event

More information

PVE SERIES POWER VENTER SYSTEM MANUAL

PVE SERIES POWER VENTER SYSTEM MANUAL PVE SERIES POWER VENTER SYSTEM MANUAL Contents Page I. Typical Venting System Components 2 II. System Operation 3 III. Power Venter Sizing 3,4 IV. Installation Safety Instructions 5,6 V. Installation of

More information

POWER VENTER. Model: PVE Series

POWER VENTER. Model: PVE Series POWER VENTER Model: PVE Series CONTENTS Typical Venting System Components... System Operation... Power Venter Sizing... Installation Safety Instructions... Installation of Power Venter... Connecting Power

More information

TECHNICAL INFORMATION COMMUNICATION

TECHNICAL INFORMATION COMMUNICATION Quality and Continuous Improvement Number: TIC2013-0014 Date: 10/30/2013 Title: New 35 Condensing Furnace Condensation Product Category: Heating Products Products Affected New 35 condensing gas furnaces

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

CHIMNEY INSTALLATION. Technical Bulletin #1

CHIMNEY INSTALLATION. Technical Bulletin #1 Technical Bulletin #1 CHIMNEY INSTALLATION A chimney performs two functions: it removes smoke and flue gases from the stove/furnace, and it provides draft for the fire. Draft is the term used to describe

More information

Combustion Safety Testing: What we learn from Standards and Research. Objectives. Objectives 2/24/2016

Combustion Safety Testing: What we learn from Standards and Research. Objectives. Objectives 2/24/2016 Combustion Safety Testing: What we learn from Standards and Research Better Buildings Better Business Conference March 2016 Experience. Innovation. Results. Confiden al 2015 Objectives Identify differences

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

SnuggPro DATA COLLECTION FORM

SnuggPro DATA COLLECTION FORM SnuggPro DATA COLLECTION FORM Section 1: General Information Trade Ally: Trade Ally Telephone: Trade Ally Email: Auditor Name: Auditor Telephone: Auditor Email: Home Owner Name: Home Owner Telephone: Home

More information

Leisure Line Power Vent Operations & Maintenance Manual And Safety Instructions

Leisure Line Power Vent Operations & Maintenance Manual And Safety Instructions Leisure Line Power Vent Operations & Maintenance Manual And Safety Instructions Black Rock Manufacturing DBA Leisure Line Stove Company Rear 620 Broad Street Berwick, PA 18603 http://www.leisurelinestoves.com/ind

More information

WARNING FLAIR INTERNATIONAL CORPORATION 600 OLD WILLETS PATH HAUPPAUGE, NEW YORK U.S.A. TEL.: (516) FAX: (516) AMERICAN

WARNING FLAIR INTERNATIONAL CORPORATION 600 OLD WILLETS PATH HAUPPAUGE, NEW YORK U.S.A. TEL.: (516) FAX: (516) AMERICAN 600 OLD WILLETS PATH HAUPPAUGE, NEW YORK 11788 U.S.A. TEL.: (516) 234-3600 FAX: (516) 234-3610 SPECIFICATIONS, INSTALLATION INSTRUCTIONS AND TROUBLE-SHOOTING GUIDE FOR STACK PACK MOTORIZED VENT DAMPER

More information

2015 MECHANICAL CODE REQUIREMENTS

2015 MECHANICAL CODE REQUIREMENTS 2015 MECHANICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Mechanical requirements for residential buildings per

More information

Objectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance?

Objectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance? Home Performance Diagnostics with the House of Pressure (Part 1) Objectives Learn the basic rules of air flow and differences Begin to be able to recognize building problems related to airflow and differences

More information

REQUIREMENTS & GUIDELINES

REQUIREMENTS & GUIDELINES SMALL CENTERS IN A RESIDENCE (6-12 Children) REQUIREMENTS & GUIDELINES Mecklenburg County Code Enforcement and the North Carolina Department of Health and Human Services Division of Child Development are

More information

RESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO

RESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO RESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO rgalenmoore1@msn.com Effective insulation and air sealing treatments can make a huge difference

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION DL Bohac * Center for Energy and Environment, Minneapolis, MN USA ABSTRACT Extensive

More information

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems about your house CE 28 k Assessing the Comfort and Safety of Your Home s Mechanical Systems The heating, ventilating and air conditioning (HVAC) systems are a vital part of every home. These mechanical

More information

Combustion Appliance Safety Testing Guidelines

Combustion Appliance Safety Testing Guidelines Combustion Appliance Safety Testing Guidelines This guide is intended to assist home performance contractors complete all combustion safety tests adequately and safely according to the Building Performance

More information

Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below)

Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below) CALIFORNIA MECANICAL CODE MATRIX ADOPTION TABLE CAPTER CIMNEY AND VENTS Adopting Agency BSC SFM CD DSA OSPD 1 1/AC AC SS SS/CC 1 4 Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended

More information

TASKS REGARDING COMBUSTION AIR

TASKS REGARDING COMBUSTION AIR TASKS REGARDING COMBUSTION AIR DETERMINE IF THERE IS ENOUGH COMBUSTION AIR FOR THE TYPES OF APPLIANCES IN THE CAZ Use one of two methods, depending on appliance type and whether or not you have a blower

More information

Code verification sign-off

Code verification sign-off Code verification sign-off Following is a list of the most common manufactured home code non-compliant items found in used or altered manufactured homes. These are only the most commonly found items and

More information

BEST DRAFT CONTROL: MANUAL DAMPERS IN MULTIPLE BOILER SYSTEMS

BEST DRAFT CONTROL: MANUAL DAMPERS IN MULTIPLE BOILER SYSTEMS BEST DRAFT CONTROL: MANUAL DAMPERS IN MULTIPLE BOILER SYSTEMS WHITEPAPER Decades of evolving codes have led to much confusion over how dampers can and cannot be used. Contrary to popular belief, manual

More information

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA 32-2015 [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement:

More information

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. 1.1.1.1 (B), (C), & (D)

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

The Committee updated the edition dates for the reference sources for extracted text within the standard per the NFPA Manual of Style.

The Committee updated the edition dates for the reference sources for extracted text within the standard per the NFPA Manual of Style. Second Revision No. 51-NFPA 86-2013 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 54, National Fuel Gas Code, 2009 2015 edition. NFPA 69, Standard on Explosion Prevention

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2006 Edition... 2 23.20.101.2 Scope... 2 23.20.303.4

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS NAHA001DH & NAHA002DH Chimney Adapter Kit Category I Furnace Vent Accessory KEEP THESE INSTRUCTIONS WITH THE FURNACE SAFETY REQUIREMENTS Improper installation, adjustment, alteration,

More information

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE:

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B-09-32-03 POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: SUMMER AND FALL 2017 CONSULTATION Ministry of Municipal Affairs PROPOSED

More information

INSTALLER'S GUIDE MASONRY CHIMNEY VENT KIT WARNING: BAYVENT800B 18- CH23D2-05

INSTALLER'S GUIDE MASONRY CHIMNEY VENT KIT WARNING: BAYVENT800B 18- CH23D2-05 INSTALLER'S GUIDE IMPORTANT This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work. Model: BAYVENT800B For use with Category

More information

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation City of Victoria Building Inspections Department 7951 Rose Street P. O. Box 36 Victoria, MN 55386 (952) 443-4210 Ventilation, Makeup and Combustion Air Calculations Instructions and Example These instructions

More information

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings Site Address Contractor Contractor Email Contractor Phone Date SECTION A Square feet * Number of bedrooms Ventilation Quantity

More information

Installation Instructions

Installation Instructions Single-Stage Tables For Category I Fan-Assisted Furnaces Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Installing and servicing

More information

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev This fact sheet provides an overview of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. These revisions are published

More information

Inspection Checklist Mechanical Rough in

Inspection Checklist Mechanical Rough in Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and

More information

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Combustion Safety RESNET Conference San Antonio, TX February 27, 2006 Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Goals of this session Recognize the need for combustion safety

More information

Do not use this vent pipe or fittings for venting incinerators of any kind.

Do not use this vent pipe or fittings for venting incinerators of any kind. ! CAUTION! Do not use this vent pipe or fittings for venting incinerators of any kind. C.S.A. Certified For Natural Gas Or Propane Tested For 100 LBS. ASME Working Pressure For correct installation of

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 Deleted Part II Definitions.............................. 3 CHAPTER 2 DEFINITIONS.................... 3 R201 General..................................

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 235533 - FUEL-FIRED UNIT HEATERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas fired unit heaters. B. Oil fired unit heaters. C. Tubular infrared heaters. 1.2 RELATED REQUIREMENTS A. Section 230513

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

Vent Supplement Ultra-80, -105, -155, -230 & -310

Vent Supplement Ultra-80, -105, -155, -230 & -310 Gas-fired water boiler Vent Supplement Ultra-80, -105, -155, -230 & -310 Installation of: Vent piping Air piping with This document must only be used by a qualified heating installer/service technician.

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

EnergyMeasure HOME DATA COLLECTION FORM

EnergyMeasure HOME DATA COLLECTION FORM EnergyMeasure HOME DATA COLLECTION FORM Section 1: General Information Customer Name: Site ID: Assessment Date: Street Address: City: State: Zip Code: Alternate Address: City: State: Zip Code: Telephone

More information

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce. Ventilation ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce /NDCommerce /NDCommerce /NDCommerce /NDCommerce WHATS NEW IN ASHRAE 62.2 2016 Controls (Override) Shutoff for maintenance

More information

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

POWER VENTER SYSTEM. Model: PVO-300, PVO-600 POWER VENTER SYSTEM Model: PVO-300, PVO-600 Included is one ETL and cetl listed Power Venter to be used primarily with a single 120VAC controlled oil fired furnace, boiler, or water heater. The PVO may

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Masonry Chimney Draft Hood Kit GENERAL INFORMATION DESCRIPTION Tile Lined Chimney Kit Model Numbers CK060 and CK0604 permits the venting of an 80% induced draft

More information

Whole House Action Guidelines

Whole House Action Guidelines for Pacific Gas and Electric Company's (PG&E) Whole House Rebate Progam 12/23/2011 The purpose of these Action Guidelines is to describe the actions participating contractors and/or inspectors should take

More information

COMBUSTION SAFETY BASICS

COMBUSTION SAFETY BASICS COMBUSTION SAFETY BASICS Joe Konopacki Why Combustion Safety? Hydrocarbon fuels are hazardous Explosion or fire is possible Poor indoor air quality Exhaust byproducts are harmful or deadly Safe and efficient

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2012 Edition.... 2 23.20.101.2 Scope.... 2 23.20.103-110

More information

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Comment No. 7-NFPA 30A-2013 [ Section No ] Page 1 of 13 Public Comment No. 7-NFPA 30A-2013 [ Section No. 6.4.2 ] 6.4.2 Additional Proposed Changes Each pump shall have installed on the discharge side a listed leak detection device that will provide

More information

New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011

New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011 New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011 Customer: Street: City: Zip: Phone: (Home): ( ) - Phone: (Work): ( ) - Owner: Yes No/ Name: Phone: ( )

More information

SECTION BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS

SECTION BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS SECTION 11 53 53 BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section

More information

PART 5: HVAC & DHW SYSTEMS

PART 5: HVAC & DHW SYSTEMS PART 5: HVAC & DHW SYSTEMS Building Science Review Building Science Review: HVAC & DHW Systems This document will help you: Correctly answer all parts of the HVAC Systems section in the Home Energy Score

More information

2006 Upgrade Kit FPX Wood Fireplaces

2006 Upgrade Kit FPX Wood Fireplaces 2006 Upgrade Kit Summary The Fireplace Xtrordinair wood fireplaces have been updated in 2006 to improve performance in cold environments when the fireplace is not in use. Gasket for the face and a revised

More information

MBPA Home Performance FIELD DATA COLLECTION FORM

MBPA Home Performance FIELD DATA COLLECTION FORM MBPA Home Performance FIELD DATA COLLECTION FORM Customer Information Test Date: Name Address City State Zip Phone: ( ) Email: Electric Provider Heating Fuel Provider Account Number Account Number Customer

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

Completed Projects / Projets terminés

Completed Projects / Projets terminés Completed Projects / Projets terminés New Standards New Editions Special Publications Gas Technician Training 2 Module 10, 3rd edition Piping and Tubing Systems for Industrial and Commercial Applications...

More information

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS AUTOMATIC MAKE-UP AIR DAMPER WITH READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. Installation

More information

DaVinci Heat Exchanger

DaVinci Heat Exchanger Compatibility Notes This kit must be installed in conjunction with a DaVinci pre-configured for heat-exchanger use. NOTE: Does not work for island or bay configurations or any unit with 58 tall glass.

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

X Article/Section 902.0(D) X X X X X X X X X X X

X Article/Section 902.0(D) X X X X X X X X X X X CALIFORNIA MECHANICAL CODE MATRIX ADOPTION TABLE CHAPTER 9 INSTALLATION OF SPECIFIC APPLIANCES Adopting Agency BSC SFM HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt Entire Chapter X X X X X Adopt Entire

More information

HOME INSPECTOR EDUCATION EXPO 2016

HOME INSPECTOR EDUCATION EXPO 2016 An Education in Hot Water HOME INSPECTOR EDUCATION EXPO 2016 Residential Water Heater Inspection Course Objective Course Objective Completing this course should enable an inspector to identify components

More information

REFERENCE GUIDE TO SUCCESSFUL BPI EXAMS

REFERENCE GUIDE TO SUCCESSFUL BPI EXAMS REFERENCE GUIDE TO SUCCESSFUL BPI EXAMS compiled to assist you by A. Tamasin Sterner President and Chief Coach December 2014 Major Standards of Reference BPI Exams Note - All BPI exams are based on a mixture

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST

BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST 1. Pre-Inspection Homeowner Interview (3 minutes) A. Turn on & zero CO Meters. Determine ambient CO : B. Record Outside Temperature: C. Homeowner interview:

More information

The Heating System and Ventilation and Combustion Air

The Heating System and Ventilation and Combustion Air The Heating System and Ventilation and Combustion Air Introduction Both you and your furnace need some fresh air coming into the house, but most Canadian homes have too much. In fact, 25 percent or more

More information

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717) City of York Qdot Engineering 101 S. George St 116 E Gas Ave York, PA 17405 York, PA 17405 (717) 849-2329 (717) 744-8315 INSPECTION CHECKLIST Residential Mechanical 2009 Codes This checklist is intended

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 (IFGC) GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and

More information